Festo AG & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
Instructions| Operating
8108871
2019-04a
[8108873]
8108871
Translation of the original instructions
EtherNet/IP®, OPCUA®, PI PROFIBUS PROFINET®, SPEEDCON® are registered
trademarks of the respective trademark owners in certain countries.
1Intended use
The module described in this document is intended for use in the industrial sector
as a gateway between industrial Ethernet networks and cloud applications, such
as, forexample, Festo Dashboard applications.
The module is intended for installation in machines or automation-technology
systems and may only be used only as follows:
–In perfect technical condition
–In its original condition, without unauthorised modifications, except for the
adaptations described in this document
–Within the limits of the product defined by the technical data.
Outside of industrial environments, e.g.in commercial and mixed-residential
areas, it may be necessary to take measures to suppress interference.
Information on commissioning and operating the gateway, e.g. to activate the
network connections "Cloud" and "Device" and to integrate them into the cloud
("Onboarding"):
Information on the terminal CPX:
èSystem description of the terminal CPX (CPX-SYS), www.festo.com/pk
3Connection and display components
LED displays
1
Network connection "Cloud"
2
Network connection "Device"
3
Rotary switch operating mode
4
DIL switch
5
Interface to the terminal CPX
6
without a network connection
è 8 Connection technology
Fig. 1 Connection and display components
3.1Network connections
For connection to the Internet and the local industrial Ethernet network or direct
connection to the field devices, there are two industrial Ethernet interfaces on the
module, the network connections "Cloud" and "Device". Both connections have
Auto-Negotiation und Crossover detection (factory setting).
5) equipotential bonding èSystem description of the terminal CPX (CPX-SYS)
FE,
Shield
4)
Functional earth5)FE,
Shield
Functional earth
5)
Tab. 1 Network connections
3.1.1Fieldbus protocol and field devices
Via the network connection "Device", field devices can be directly connected with
an industrial Ethernet connection to the Gateway, e.g. bus node or controllers
(controller, PLC) with protocols such as, forexample, PROFINET, EtherNet/IP or
OPCUA.
All available documents for the product èwww.festo.com/pk.
Note on licencing
This product uses open-source software, which is subject to "GNU General Public
License", Version2 and "GNU Lesser General Public License",
Version2.1,among others.
The licence conditions of the GPL, LGPL and the other open-source licences can be
viewed via the integrated web server of the product:
•Connect the gateway via the network connection "Device" with a PC or Note-
Switch off the power supply and secure it against being switched on again.
–For the electrical power supply, use PELV circuits in accordance with
IEC 60204-1/EN 60204-1.
–Observe the handling specifications for electrostatically sensitive devices.
–Seal unused connections with cover caps to achieve the required degree of
protection.
–Use connection hardware with the required degree of protection.
–Observe specifications in the system description of the terminal CPX
(CPX-SYS).
–Commission only a completely mounted and wired module.
Information on the supported field devices and controllers èFesto AppWorld,
www.festo.com/appworld.
3.1.2Network security
NOTICE!
Unauthorised access to the device can cause damage or malfunctions.
When connecting the device to a network, protect the network from unauthorised
access.
Measures to protect the network include:
• Firewall
• Intrusion Prevention System (IPS)
• Network segmentation
• Virtual LAN (VLAN)
• Virtual Private Network (VPN)
• Security at physical access level (Port Security)
An access password only protects against unintentional modification.
For additional information èGuidelines and standards for security in information
technology, e.g. IEC62443, ISO/IEC27001.
When connecting the gateway, configure the firewall setting for the network connection "Cloud" as follows:
–Outgoing connections: release for port 443 (HTTPS)
–Incoming connections: no port release
For further information on the required measures in terms of network security,
enter èwww.festo.com/sp: "CPX-IOT", filter according to Application Note .
3.2LED displays
3.2.3Module status "Onboarding"
Network-specific LED displaysGateway-specific LED displays
Cloud
(blue)
NS
(red/green)
TP1
(green)
TP2
(green)
1) General information on the LEDs PS and SF èSystem description of the terminal CPX (CPX-SYS)
2) Module positioning: LEDs PS, PL and NS flash at the same rate.
Network status "Cloud"PS
Network status "Device"
Connection status "Cloud"
("Link/Traffic")
Connection status "Device"
("Link/Traffic")
2)
2)
(green)
PLReserved
SF
1)
(red)
M
(yellow)
supply
(Power System)
System error
(System Failure)
Module status "Onboarding"
Status of operating voltage -
1)
Tab. 2 LED displays
Normal operating status
Behaviour of the LED displays in a normal operating status:
–PS and NS illuminated green
–Cloud illuminated blue
–TP1 and/or TP2 illuminated or flashing green
–PL, SF and M are not illuminated
3.2.1Network status "Cloud"
LED statusMeaningError handling
Illuminated blue
Flashes
blue 1x
Flashes
blue 2x
Off
Normal operating status:
Network connection to the cloud
("Link") created
Creation or new creation of a connection to the cloud
Network error–Check the configuration, e.g.
No connection to the cloud–Check network connection
–
–
DHCP address assignment,
static IP address
Tab. 3 Network status "Cloud" (LED with cloud symbol)
3.2.2Network status "Device" (Network Status)
LED statusMeaningError handling
Illuminated
green
Flashes
green
Illuminated red
Flashes
red
Normal operating status:
The gateway is connected with field
devices ("Devices").
No connection to field devices
("Devices"):
The gateway is online and has an IP
address, but is not yet connected
with field devices.
Communication with the field
devices("Devices") has failed:
Non-permitted network configuration, e.g. already used IP address.
Communication with field devices
has failed:
Network connection disturbed, z.B.
connecting cable interrupted.
The gateway is offline.–Check network connection
–
–Check configuration
–Check module status
–Restart module ("Reboot")
–Repeat "Onboarding"
–Check configuration, e.g.
DHCP address assignment,
static IP address
–Check device connection
LED statusMeaningError handling
Off
Flashes
yellow 1x
Flashes 2x
yellow
Flashes 3x
yellow
Illuminated yellow
Normal operating status:
Onboarding completed.
The gateway has been successfully
integrated into the cloud application.
The gateway is in the operating
mode "Off", "Read only" or
"Read/Write"
è 6.3 Rotary switch operating
mode.
Gateway Onboarding active:
The gateway is in operating mode
"Onboarding".
The gateway is integrated into the
cloud application.
The gateway is in operating mode
"Onboarding".
The gateway has been successfully
integrated into the cloud application.
Devices Onboarding active.
The gateway performs a network
scan: supported devices
("Devices") are integrated into the
cloud application.
The gateway is in operating mode
"Read/Write".
The gateway is not yet integrated
into the cloud application.
The gateway is in the operating
mode "Off", "Read only" or
"Read/Write"
è 6.3 Rotary switch operating
mode.
–
–
–Select operating mode
"Read only" or "Read/Write"
è 6.3 Rotary switch operating
mode
–
–Perform Onboarding
Tab. 5 Module status "Onboarding" (LED M)
3.2.4Connection status "Cloud"
LED statusMeaningError handling
Normal operating status:
Network connection to the cloud
established
Illuminated
green
Data traffic ("Traffic")
Flashes
green
No network connection–Check network connection
Off
1) Flashing frequency is dependent on the traffic.
1)
–
–
Tab. 6 Connection status "Cloud" (Link/Traffic, LED TP1)
3.2.5Connection status "Device"
LED statusMeaningError handling
Illuminated
green
Flashes
green
Normal operating status:
Network connection ("Link") to the
field devices ("Devices") established
Data traffic ("Traffic")
No network connection–Check network connection
1)
–
–
Off
Tab. 4 Network status "Device" (Network Status, LED NS)
Off
1) Flashing frequency is dependent on the traffic.
Tab. 7 Connection status "Device" ("Link/Traffic", LED TP2)
3.2.6Status of operating voltage supply (Power System)
LED statusMeaningError handling
Normal operating status:
Operating voltage applied.
Illuminated
green
Undervoltage:
Operating voltage outside the tolerance range.
Flashes
green
Operating voltage is not present–Check operating voltage sup-
Off
1)
General information on LEDPS èSystem description of terminalCPX (CPX-SYS)
–
–Rectify undervoltage.
ply
Tab. 8 Status of operating voltage supply (Power System, LED PS)
3.2.7System error (System Failure)
LED
Process1)MeaningError handling
(red)
Normal operating status:
No error.
–
4.1Assembly
1)
NOTICE!
Material damage due to incorrect mounting.
Select screws that are suitable for the material of the interlinking block:
• Polymer: thread-grooving screws
• Metal: screws with metric thread
When ordering an individual module, all the screws required are enclosed.
1. Switch off the power supply and secure it against being switched on again.
2. Check seal and seal surfaces. Replace damaged parts.
3. Push the module carefully and without tilting into the interlinking block up to
the stop.
4. Turn the screws into the existing thread.
5. Tighten the screws in diagonally opposite sequence.
Tightening torque:1Nm ±10%.
4.2Disassembly
1. Switch off the power supply and secure it against being switched on again.
2. Unscrew the screws.
3. Pull the module without tilting out of the interlinking block.
2)
5Power supply
The operating and load voltage supply is fed in via interlinking blocks or end
plates with system supply.
Off
Simple error / information
(error class 1)
Flashes
red 1x
Error
(error class 2)
Flashes
red 2x
Serious error, internal error, e.g.
hardware error
(error class 3)
Flashes
red 3x
1) The LED SF flashes if an error occurs and is dependent on the error class.
2)
General information on LEDSF èSystem description of the terminalCPX (CPX-SYS)
2: Readonly–Gateway sends process data of the configured field devices to
3: Read/Write–Gateway sends process data of the configured field devices to
face)
–No communication with the cloud
–Gateway for integration into the cloud ("Onboarding") ready
the cloud
–Manual adding of field devices enabled
–Automatic adding of field devices via the Auto-Scan function
blocked
–Removal of field devices and removal of the gateway from the
cloud ("Offboarding") blocked
–Receipt of data, e.g. parameters, from the cloud disabled
–Parameters of connected devices cannot be changed
the cloud
–Manual adding of field devices enabled
–Automatic adding of field devices via the Auto-Scan function
enabled
–Removal of field devices and removal of the gateway from the
cloud ("Offboarding") enabled
–Receipt of data, e.g. parameters, from the cloud enabled
–Parameters of connected devices can be changed
Tab. 14 Rotary switch operating mode
7Ensuring the degree of protection
NOTICE!
Short circuit as a result of ingress of liquids or foreign matter.
Malfunction or damage to the electronics.
• Use connection devices (connecting cables, plugs, adapters) with the
required degree of protection.
• Use cover caps to seal unused connections.
• Mount the DIL switch cover:
–Check the seal.
–Place cover and press it on.
–Tighten screws.
Tightening torque: maximum0.4Nm.
8Connection technology
Using the M12 socket 6 (è Fig.1), a terminal CPX can be directly connected with
the gateway without a network connection, i.e. without an industrial Ethernet
connection.
ConnectionConnecting hardwareCover cap
Network connection "Cloud"
Network connection "Device"
Interface to terminal CPX
without a network connection
The gateway can be parameterised via the FestoField Device Tool (FFT).
Alternatively, the integrated web server of the gateway can be used via the network connection "Device" for the parameterisation, e.g. for setting the IP
addresses of the network connections:
Connect the gateway via the network connection "Device" with a PC or Notebook.
Calling up the web server:
èhttp://<IP-Adresse_des_Netzwerkanschlusses_"Device"> (see IP configuration
(factory settings) è 13 Technical data)
Logging in:
èUser name: admin
èPassword (factory setting): CPX-IoT Product Key on the type plate, e.g.
3S7PMM2M93V
10Reset to factory setting ("FactoryReset")
1. Set rotary switch to "Off".
2. Switch off the power supply.
3. Set DIL switch 2.1 and 2.2 to "On".
4. Switch on the power supply.
LEDM flashes quickly for a few seconds.
Ä
–Do not switch off the power supply
–Do not actuate the DIL switch
5. If the LEDM has stopped flashing:
Set DIL switch 2.1 and 2.2 to "Off".
The gateway has returned to the factory setting.
Ä
11Firmware update
A firmware update is possible via the Festo Field Device Tool (FFT)
èwww.festo.com/sp.
12Module replacement
After replacing a gateway, integration into the cloud („Onboarding“) must be carried out again èFesto App World, www.festo.com/appworld.
13Technical data
PropertySpecification/value
General technical dataèSystem description of the
Power supply
Operating power supply U
Intrinsic current consumption at nominal operating voltage 24V from operating voltage supply
U
EL/SEN
Mains buffering time[ms]10
Separation of network interface from operating
voltage supply U
Protection against electric shock
Degree of protection by housing
With power supply connection