Festo CPI-CL, CPI-EL Series, CP-E16-KL-CL, CP-A04-M12-CL, CP-E08-M12-CL Series Manual

...
Compact performance
Description Manual
CPI−CL modules:
− CP−E08−M12−CL
− CP−E08−M8−CL
− CP−E16−KL−CL
− CP−A04−M12−CL
CPI−EL modules
− CP−E16−M12−EL
− CP−A08−M12−EL−Z
Description
539 300 en 0711a [726 334]
Contents and general safety instructions
Original German text. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edition en 0711a. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
Designation P.BE−CPEA−CL−EN . . . . . . . . . . . . . . . . . . . . . . . .
Order no. 539 300. . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
E (Festo AG&Co. KG, D73726 Esslingen, Federal Republic of Germany, 2007) Internet: http://www.festo.com E−mail: service_international@festo.com
The copying, distribution and utilization of this document as well as the communication
of its contents to others without expressed authorization is prohibited. Violations give rise to compensation. All rights are reserved, in particular the right to carry out patent, utility model or ornamental design reg istration.
Festo P.BE−CPEA−CL−EN en 0711a
I
Contents and general safety instructions
II
Festo P.BE−CPEA−CL−EN en 0711a
Contents and general safety instructions

Contents

Intended use VI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting the power unit VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Target group VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service VII . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Important user instructions VIII . . . . . . . . . . . .
Notes on the use of this manual X . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
1. System overview CPI/CP system 1−1 . . . . . . . . . . . . .
1.1 Setting up CPI systems 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.1 Method of operation of the CPI/CP system 1−5 . . . . . . . . . . . . . . . . . . .
1.1.2 Rules for extending the CPI system 1−8 . .
1.1.3 Use of the I/O modules 1−11 . . . . . . . . . . . . . . . . . . . . . . .
1.1.4 Basic rules for addressing 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Input modules
2.1 Function of the input modules CP−E08−M...−CL and CP−E16−KL−CL 2−3 . . . . . . . . .
2.1.1 Display and connecting elements 2−4 . . . . . . . . . . .
2.2 Mounting 2−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Installation 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Connecting sensors 2−9 . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.2 Connect the input module to the CP string 2−12 . . . . . . . . . . . . . . . . . . .
2.4 Diagnosis 2−14 . . . . . . . . . .
2.4.1 Diagnosis via LEDs 2−14 . . . .
2.4.2 Diagnosis via the field bus 2−17 . . . . . . . . . . .
3. Output module type CP−A04−M12−CL 3−1 . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Function of output module type CP−A04−M12−CL 3−3 . . . . . . . . . . . . . . . . . . . . . .
3.1.1 Display and connecting elements 3−4 . . . . . . . . . . . . .
3.2 Mounting 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Installation 3−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 Connecting the actuators 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2 Connect the output module to the CP string 3−8 . . . . . . . . . . . . . . . . . .
types CP−E08−M...−CL and CP−E16−KL−CL 2−1 . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . .
Festo P.BE−CPEA−CL−EN en 0711a
III
Contents and general safety instructions
3.4 Diagnostics 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1 Diagnostics via LEDs 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.2 Diagnostics via the fieldbus 3−13 . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL 4−1 . . . . . . . . . . . . . . .
4.1 Function of the
input modules CP−E16−M...−EL and CP−E32−M8−EL 4−3 . . . . . . . .
4.1.1 Display and connecting elements 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Mounting 4−7 . . . . .
4.3 Labelling of
4.4 Installation 4−10 . . . . . . . . . . . . . .
4.4.1 Connecting sensors 4−11 . . . . . . . . . . .
4.4.2 Connect the input module to the CP string 4−14 . . . . . . . . . . . . . . .
4.5 Diagnostics 4−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
inscription label holder 4−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . .
. . . . . .
4.5.1 Diagnostics via LEDs 4−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.2 Diagnostics using fieldbus 4−20 .
5. Output module type CP−A08−M12−EL−Z 5−1 . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
5.1 Function of the output module type CP−A08−M12−E L−Z 5−3 . . . . . . . . . . . . . . . . .
5.1.1 Display and connecting elements 5−4 . . . . . . . . .
5.2 Mounting 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Labelling of inscription label holder 5−7 . . . . . . . . . . . . . . . . . . . . . . .
5.4 Installation 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . .
5.4.1 Connect external load supply 5−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.2 Connecting the actuators 5−10 . .
5.4.3 Connect the output module to the CP string 5−11 . . . . . . . . . . . .
5.5 Diagnostics 5−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . . . . .
5.5.1 Diagnostics via LEDs 5−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5.2 Diagnostics using
fieldbus 5−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. Technical appendix A−1 . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Technical specifications A−3 . . . . . . . . . . . . . . . . . . .
A.1.1 General technical data A−3 . . . . . . . . . . . . . . . . . . . . . . . .
A.1.2 Technical specifications of the CL input modules A−4 . . . . . . . . . . . . . .
A.1.3 Technical specifications of the CL output modules A−6 . . . . . . . . . . . .
IV
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
.
Festo P.BE−CPEA−CL−EN en 0711a
Contents and general safety instructions
A.1.4 Technical specifications of the EL input modules A−7 . . . . . . . . . . . . . .
A.1.5 Technical specifications of the EL output modules A−9 . . . . . . . . . . . . .
A.2 Internal structure of the inputs A−10 . . . . .
A.2.1 Internal structure type CP−E32−M8−EL A−10 . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .
A.2.2 Internal structure type CP−E08−M12−CL and CP−E16−M12−EL A−11 . . . . .
A.2.3 Internal structure type CP−E08−M8−CL and CP−E16−M8−EL A−12 . . . . . . . .
A.2.4 Internal structure type CP−E16−KL−CL A−13 . . . . . . . . . . . . . .
. . . . . . . . . .
A.3 Internal structure of the outputs A−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.3.1 Internal structure type CP−A04−M12−CL and CP−A08−M12−EL−Z A−14 . . .
A.4 Examples of circuitry A−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .
A.4.1 Circuitry examples for inputs A−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.4.2 Circuitry examples for outputs A−20 . . . . . . .
A.5 General information on parameterisation A−22 . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . .
A.5.1 Input debounce time (only with CP−EL modules) A−22 . . . . . . . . . . . . . . .
A.5.2 Signal extension (only with CP−EL modules) A−24 . . . . . . . . . . . . . . . . . .
A.6 Accessories A−27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.6.1 General accessories A−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.6.2 Accessories for modules with M12 connection A−27 . . . .
. . . . . . . . . . . .
A.6.3 Accessories for modules with M8 connection A−28 . . . . . . . . . . . . . . . . .
A.6.4 Connector sets for input module type CP−E16−KL−CL A−29 . . . . . . . . .
. . .
B. Index B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Festo P.BE−CPEA−CL−EN en 0711a
. . . . . . . . . . .
V
Contents and general safety instructions

Intended use

The CPI modules described in this manual are intended exclusively for use on a CP string on a CPI/CP master (e.g.: CPX−CP interface, CP fieldbus node, CPV Direct).
The CPI/CP modules may only be used as follows:
as specified in industrial applications
 without any modifications by the user. Only the conver
sions or supplied with the product are permitted.
In perfect technical condition.
If used together with additional commercially available com ponents, such as sensors and actuators, the specified limits for pressures, temperatures, electrical data, torques etc. must be observed.
modifications described in the documentation
Please comply with national and local safety laws and regula tions.
VI
Festo P.BE−CPEA−CL−EN en 0711a
Contents and general safety instructions

Selecting the power unit

Warning
· In order to provide the electric power supply, use only
PELV circuits as per IEC/DIN EN 60204−1 (Protective Extra−Low Voltage, PELV). Take into account also the general requirements for PELV circuits as per IEC/DIN EN60204−1.
· Use only power packs which guarantee reliable
electrical isolation of the operating voltage as per IEC/DIN EN 60204−1.
By the use of PELV power units, protection against electric shock (protection against direct and indirect contact) is guaran teed in accordance with IEC/DIN EN 60204−1 (electrical equip ment of machines, general requirements).

Target group

Service

Festo P.BE−CPEA−CL−EN en 0711a
This manual is directed exclusively at technicians trained in control and automation technology.
Please consult your local Festo repair service if you have any technical problems.
VII
Contents and general safety instructions

Important user instructions

Danger categories
This manual contains instructions on the possible dangers which can occur if the product is not used correctly. These instructions are marked (Warning, Caution, etc), printed on a shaded background and marked additionally with a picto gram. A distinction is made between the following danger warnings:
Warning
... means that failure to observe this instruction may result in serious personal injury or damage to property.
Caution
... means that failure to observe this instruction may result in personal injury or damage to property.
VIII
Note
... means that failure to observe this instruction may result in damage to property.
The following pictogram marks passages in the text which describe activities using electrostatically sensitive devices.
Electrostatically sensitive devices: Incorrect handling can result in damage to components.
Festo P.BE−CPEA−CL−EN en 0711a
Contents and general safety instructions
Identifying special information
The following pictograms mark passages in the text which contain special information.
Pictograms
Information: Recommendations, tips and references to other sources of information.
Accessories: Information on necessary or useful accessories for the Festo product.
Environment: Information on the environment−friendly use of Festo products.
Festo P.BE−CPEA−CL−EN en 0711a
Text designations
· The bullet indicates activities which may be carried out in
any order.
1. Numbers denote activities which must be carried out in the sequence specified.
 Hyphens indicate general activities.
IX
Contents and general safety instructions

Notes on the use of this manual

This manual contains information on fitting, installing and commissioning the following CPI modules as well as a description of their method of operation:
This manual
refers to:
Input modules PNP:
CP−E08−M12−CL:
8 digital inputs, 4 M12 sockets, 5pin
CP−E08−M8−CL:
8 digital inputs, 8 M8 sockets, 3pin
CP−E16−KL−CL:
16 digital inputs, 2 series plugs, 10pin
Output modules PNP:
CP−A04−M12−CL
4 digital outputs, 4 M12 sockets, 5−pin
Tab.0/1: CP I/O modules type CP−...CL
Input modul e type CP−E16KL−CL offers 2 series plugs for screw terminal sockets or tension spring sockets (see
section A.6.4).
X
Festo P.BE−CPEA−CL−EN en 0711a
Contents and general safety instructions
This manual refers to:
Input modules PNP:
CP−E32−M8−EL:
32 digital inputs, 16 M8 sockets, 4−pin
CP−E16−M8−EL:
16 digital inputs, 16 M8 sockets, 3pin
CP−E16−M12−EL:
16 digital inputs, 8 M12 sockets, 5pin
Output modules PNP:
CP−A08−M12−EL−Z
8 digital outputs, 8 M12 sockets, 5pin
Festo P.BECPEACLEN en 0711a
Tab.0/2: CP I/O modules type CP−...EL
Basic information, which must be observed in conjunction with the CPI/CP master, can be found in the manuals for
the relevant CPI/CP master and in the CPI system description for
type CPX−CP−... .
XI
Contents and general safety instructions
Type Title Description
CPI system, Description electronics
Modules with CP connection, description of electronics
CP modules, description of electronics
Valve terminals, Pneumatics manual
CP system" Type P.BE−CPX−CP−...
CPV Direct" Type P.BE−CP−DI...
CP fieldbus node" Type P.BE−CPX−FB.../ CP−4−FB−...
CDVI ..." Type P.BE−CDVI−DN−...
CPA−SC / CPV−SC ..." Type P.BE−CPASC− CPVSC−...
CP modules" Type P.BE−CPEA−...
Valve terminals with CPV pneumatics" Type P.BE−CPV−...
Valve terminals with MPA pneumatics" Type P.BE−MPA−...
General basic information on fitting, installing and commissioning CPI systems and on their method of operation.
Instructio n s on fitting, installing, commissioning and diagnosing the relevant CPV valve terminal with direct connection.
Instructio n s on fitting, installing, commissioning and diagnosing the relevant fieldbus node.
Instructio n s on fitting, installing, commissioning and diagnosing the relevant CDVI with fieldbus direct connection DeviceNet."
Instructio n s on fitting, installing, commissioning and diagnosing the CPV−SC or CPA−SC valve ter minal with fieldbus direct connection for PROFI BUS DP or DeviceNet.
Information on fitting, installing and commission ing CP I/O modules.
Information on fitting, installing and commission ing CPV valve terminals (type 10).
Information on fitting, installing and commissioning MPA valve terminals (type 32), (type 33).
Valve terminals with CPA pneumatics" Type P.BE−CPA−...
Tab.0/3: Manuals on the CPI/CP system
XII
Information on fitting, installing and commission ing CPA valve terminals (type 12).
Festo P.BE−CPEA−CL−EN en 0711a
Contents and general safety instructions
The following product−specific terms and abbreviations are used in this manual:
Term/abbreviation
A Digital output
CP cable Special cable for connecting the various CPI/CP modules in a CP string.
CP functions Supports the CP protocol without extended functions
CP module/valve terminal
CP string CPI or CP modules which are connected by CPI/CP cable and which are
CP system Complete electrical installation system consisting of a CP master with one
CPI cable Special cable for connecting the various CPI/CP modules in a CP string.
CPI connection Socket or plug on the CPI modules which allows the modules to be con
CPI fieldbus interface Term for a CPI capable interface with fieldbus connection (e.g. combination
CPI fieldbus module Defined combination of a CPX fieldbus node and a CPX−CP interface.
Meaning
Colour: black, type KVI−CP1−... and type KVI−CP2−...
Common term for modules without extended functions which can be incor porated in a CPI/CP system.
connected to the CPX−CP interface. For reasons of simplicity, only the term CP string" is used, even if it has CPI functionality.
or more CP strings. The system consists of CP modules (without extended functions).
Colour: white, type KVI−CP3−...
nected using the CPI or CP cable.
of CPX fieldbus node and CPX−CP interface (CPI fieldbus module) or CPV with CPI string extension (CPV Direct))
Connects a CPI system with a fieldbus.
CPI functions Supports the CPI protocol with extended functions
CPI module/valve terminal
CPI system Also: CPI installation system"
E Digital input
Input module Input module
Festo P.BE−CPEA−CL−EN en 0711a
Common term for modules with extended functions which can be incorpo rated in a CPI/CP system.
Complete electrical installation system consisting of a CP master with one or more CP strings. The system consists of CPI/CP modules with and with out extended functions. The system need not consist exclusively of CPI modules.
XIII
Contents and general safety instructions
Term/abbreviation Meaning
I/Os Digital inputs and outputs
I/O modules Collective term for the modules which provide digital inputs and outputs
Output module Output module
String allocation Type and order of the CPI/CP modules connected to one or more CP strings.
(e.g., CPX I/O modules, CPI input modules and CPI output modules).
Tab.0/4: Specific terms and abbreviations
XIV
Festo P.BE−CPEA−CL−EN en 0711a

System overview CPI/CP system

Chapter 1
1−1Festo P.BE−CPEA−CL−EN en 0711a
1. System overview CPI/CP system

Contents

1. System overview CPI/CP system 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Setting up CPI systems 1−3 . . . . . . . . .
1.1.1 Method of operation of the CPI/CP system 1−5 . . . . . . . . . .
1.1.2 Rules for extending the CPI system 1−8 . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.3 Use of the I/O modules 1−11 . . . . . .
1.1.4 Basic rules for addressing 1−13 . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
1−2
Festo P.BE−CPEA−CL−EN en 0711a
1. System overview CPI/CP system

1.1 Setting up CPI systems

Festo can assist you in solving your automation task at the machine level with the aid of valve terminals. Due to their modular structure, the CP valve terminals from Festo will enable you to include valve terminals and I/O modules optimally in your machines and systems.
3
2
1
1
CPI fieldbus node
2 MPA−CPI valve terminal
3 CPV−CPI valve terminal
4 CP−CL module
5 CP−EL module
Fig.1/1: Example: Setting up a CPI system
Festo P.BE−CPEA−CL−EN en 0711a
45
1−3
1. System overview CPI/CP system
The CPI/CP system consists of individual modules which are connected to each other by means of CP cables. In this way it is possible to decentralize the arrangement of the CP system. The compact CP valve terminals can be mounted very close to the cylinders to be controlled. This enables short compressed air
tubing to be used.
System losses can be minimized if short compressed air tubing is used and the times required for pressurising and exhausting the tubing can be reduced.
This enables smaller valves with sufficient flow to be used, thereby helping to reduce costs.
1−4
Festo P.BE−CPEA−CL−EN en 0711a
1. System overview CPI/CP system

1.1.1 Method of operation of the CPI/CP system

CPI/CP systems are composed of the following modules:
Modules
CPI/CP master Special CP fieldbus nodes and CP modules
CPV/CPV−SC valve terminals with CPI connection
Function
are available for the various fieldbuses.  These provide the connection to certain
fieldbuses.
 These offer connections for up to four
strings to which I/O modules and CP valve terminals are connected.
 They transmit control signals to the con
nected modules and monitor their func tioning.
 These provide different valve functions
via valve plates for controlling pneu matic actuators.
 Relay plates, pressure zone separation
plates and blanking plates can also be fitted.
Festo P.BE−CPEA−CL−EN en 0711a
1−5
1. System overview CPI/CP system
Modules Function
MPA valve terminal with CPI connection
Input modules (type CL, EL, RL)
Output modules (type CL, EL, RL)
 These provide different valve functions
via valves for controlling pneumatic actuators.
 These provide inputs for connecting
sensors and enable e.g.cylinder posi tions to be scanned.
 These provide universal electric outputs
for controlling low−current consuming devices (further valves, bulbsetc.).
1−6
Tab.1/1: Overview of the CPI modules
Festo P.BE−CPEA−CL−EN en 0711a
1. System overview CPI/CP system
Depending on their design, CPI/CP masters control the transfer of data to the different control systems via the various fieldbuses.
1 Fieldbus
(incoming)
2 Fieldbus
(continuing)
3 CPI master (here
CPX−CP interface)
4 CP valve terminal
5 CPI input
module EL
6 Sensor
7 Cylinders
8 CPI input
module CL
9 CPI output
module EL
aJ CPI output
module CL
1
3
2
45
6
7
8
6
7
9
Fig.1/2: Method of operation of the CP system
Festo P.BE−CPEA−CL−EN en 0711a
aJ
1−7
1. System overview CPI/CP system

1.1.2 Rules for extending the CPI system

The CPI system supports a different number of modules per CP string, depending on the type of CP master and on the CPI/CP modules connected.
The CPV Direct is a CPI master.
Modules can be placed in two different groups:
 CPI modules (with extended functions)
CP modules (without extended functions)
Rules and properties
CPI system  Max. 4 modules on the CP string
CPI master A mixture of CPI/CP modules is possible on CPI masters:
CPI modules Modules always have an incoming and continuing interface on all CPI modules
1)
with extended functions
2)
without extended functions
 Max. 32 inputs and 32 outputs (per CP string)  The sequence of the modules within the CP string is optional
 Only one CP input module is possible at the end of a string  Only one CP valve terminal2) or one CP output module2) is possible per CP
string
 Unused" locations on the CP string can be filled" with CPI modules
(input modules, output modules) and valve terminals with CPI connection
1)
Tab.1/2: Rules for extending the CPI system
Note
Irrespective of the type of CPI/CP modules, not more than 32 inputs and 32 outputs may be connected (sum of all modules on a CP string).
This means that a CP string can be extended by maximum 2 CP valve terminals with CPI ability, as CP valve terminals always occupy 16 output addresses.
1−8
Festo P.BE−CPEA−CL−EN en 0711a
1. System overview CPI/CP system
CPI master
CP (O) CPI (I/O)
CPI (I/O) CPI (I/O)
CPI (I/O)
CPI (I/O)
CPI master
CPI (I/O)
CPI (I/O) CPI (I/O)
CPI (I/O)
grey: CPI (with extended functions) CP (I): CP input module CP (O): CP output module or CP valve terminal CPI (I/O): CPI input or output module (with extended functions) or CP valve terminal with CPI ability
(for valve terminal: max. 2 possible)
Rules: CP: The rules for the CP master remain valid. CPI: Max. 32 inputs and 32 outputs per string, max. 4 modules per string
Max. 1 CP output module or 1 CP valve terminal Max. 1 CP input module always at the end of the string Max. 2 valve terminals with CPI functions per string
CP (O)
CPI (I/O)
CPI (I/O)
CPI (I/O)
CP (O)
CPI (I/O)
CPI (I/O)
CP (O)
CPI (I/O)CPI (I/O)
CPI (I/O)
CPI (I/O)
CP (O)
CPI (I/O)
CPI (I/O)
CP (O)
CP (I)
CP (I)CP (O) CPI (I/O)
CP (I)
CP (I)
Fig.1/3: Expansion of a CPI/CP system
Festo P.BE−CPEA−CL−EN en 0711a
1−9
1. System overview CPI/CP system
The following list of CPI/CP modules shows in each case their functions as well as the maximum possible number of inputs or outputs on each CPI/CP module.
CPI/CP modules
Type Type Module
CPI/CP input modules
CPI/CP output modules
CP−E08−M8−CL CP−E08−M12−CL CP−E16−KL−CL CP−E16−M12−EL CP−E16−M8−EL CP−E32−M8−EL CP−E16−M8 CP−E16N−M8 CP−E16−M8−Z CP−E16−M12x2−5POL CP−E16N−M12x2 CP−E16−KL−IP20−Z
CP−A04−M12−CL CP−A08−M12−EL−Z CP−A08−M12−5POL CP−A08N−M12
supports extended functions
Yes Yes Yes Yes Yes Yes No No No No No No
Yes Yes No No
Assigned I/Os
on CP masters
with extended functions
E A E A
8 E 8 E 16 E 16 E 16 E 32 E 16 E 16 E 16 E 16 E 16 E 16 E
   
           
8 A 8 A 16 A 16 A
on CP masters
without ex tended functions
16 E 16 E 16 E 16 E 16 E
1)
 16 E 16 E 16 E 16 E 16 E 16 E
   
    
1)
      
16 A 16 A 16 A 16 A
1) No function on CP master
Tab.1/3: Assigned I/Os of the CPI/CP modules
1−10
Festo P.BE−CPEA−CL−EN en 0711a
1. System overview CPI/CP system

1.1.3 Use of the I/O modules

CPI/CP I/O modules can be used in conjunction with various CPI/CP masters. These are e.g.:
 CPX terminal with CPX−CP interface
CP fieldbus node
 CPV Direct
 CPV−SC−DN / CPA−SC−DN
 CPV−SC−DP / CPA−SC−DP
 CDVI−DN
The CPI/CP masters are distinguished by the different number of CP strings made available, by the functions, the maximum number of inputs and outputs the number of CPI/CP modules per string.
to be processed and
Festo P.BE−CPEA−CL−EN en 0711a
1−11
1. System overview CPI/CP system
CPI/CP master type Number of
strings
CPX with CP interface 4 CP 16 I + 16 O 2
4 CPI (advanced) 1)32 I + 32 O 4
CP fieldbus node 4 CP 16 I + 16 O 2
CPV Direct 1 CP 16 I + 16 O 2
1 CPI (advanced) 1)32 I + 32 O
CPV−SC−DP / CPA−SC−DP 1 CP 16 I + 16 O 2
1 CPI (advanced) 1)32 I + 32 O
CPV−SC−DN / CPA−SC−DN 1 CP 16 I + 16 O 2
1 CPI (advanced) 1)32 I + 32 O
CDVI−DN 1 CP 16 I + 16 O 2
1) Supporting the extended functions with CPV−DI02, CPV−CS02, CPV−DI02, CS02, DN3, CO3.
Functionality Max. number
of inputs/out puts per string
1)
1)
1)
Max. number of modules per string
1)
4
1)
4
1)
4
Tab.1/4: Overview, CPI/CP master
The compact CPI/CP I/O modules (type CP−...−CL and −EL) described in this manual support the extended functions of the CPI system. Combinations with other CPI/CP modules are possible, but limit the number of CPI/CP modules per string. The limitations described in section 1.1.2 apply.
1−12
Note
CPI I/O modules with extended functions, e.g. type CP−...−CL, −EL can also be operated on CP masters without extended functions (see Tab.1/3).
Festo P.BE−CPEA−CL−EN en 0711a
1. System overview CPI/CP system

1.1.4 Basic rules for addressing

Addressing depends on:
 CPI/CP master used
 The fieldbus protocol used
The following rules apply:
 Addressing is carried out in ascending order of connec
tion beginning on the CP master.
In the case of CP masters without extended functions,
each CPI/CP module occupies 16 inputs or 16 outputs, irrespective of the design.
In the case of
CPI masters with extended functions, the
following difference applies:
 Modules without extended functions usually occupy
16 inputs or 16 outputs.
 Depending on the type, modules with extended func
tions occupy 8 ... 32 inputs or 8 ... 32 outputs.
Note
Further information on addressing can be found in the relevant manuals for the CP masters.
Festo P.BE−CPEA−CL−EN en 0711a
1−13
1. System overview CPI/CP system
1−14
Festo P.BE−CPEA−CL−EN en 0711a
Input modules types CP−E08−M...−CL and CP−E16−KL−CL
Chapter 2
2−1Festo P.BE−CPEA−CL−EN en 0711a
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL

Contents

2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL 2−1 . . . . . . . . . . . . . .
2.1 Function of the input modules CP−E08−M...−CL and CP−E16−KL−CL 2−3 . . . . . . . . .
2.1.1 Display and connecting elements 2−4 . . . . . . . . .
2.2 Mounting 2−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Installation 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Connecting sensors 2−9 . . . . . . . . . . . . . . . . . . . . . . .
2.3.2 Connect the input module to the CP string 2−12 . . . . . . . . . . . . . . . . . . .
2.4 Diagnosis 2−14 . . . . . . . .
2.4.1 Diagnosis via LEDs 2−14 . .
2.4.2 Diagnosis via the field bus 2−17 . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
2−2
Festo P.BE−CPEA−CL−EN en 0711a
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL
2.1 Function of the input modules CP−E08−M...−CL and CP−E16−KL−CL
CP input modules provide digital inputs for connecting sen sors, thereby enabling e.g.cylinder positions to be scanned. A distinction is made between the following types:
Product
Type Explanation
illustration
Sensor connections via 4 sockets with M12 thread, 5−pin
CP−E08−M12−CL Provides 8 PNP inputs (IP65/IP67).
Sensor connections via 8 sockets with M8 thread, 3−pin
CP−E08−M8−CL Provides 8 PNP inputs (IP65/IP67).
Sensor connections via 2 series plugs, 10−pin and connector sockets in either screw or tension spring design.
CP−E16−KL−CL Provides 16 PNP inputs.
Especially suitable for fitting into a control cabinet (IP20).
Tab.2/1: Overview of input modules
Festo P.BE−CPEA−CL−EN en 0711a
2−3
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL

2.1.1 Display and connecting elements

The following diagram shows the display and connecting elements of input module CP−E08−M12−CL.
1 CP connection
incoming
2 Continuing
CP connection
3 Status LED short
circuit/overload/ undervoltage in sensor supply (red)
4 Status LEDs for
inputs (status display, green)
5 Status LED CP
communication (PS, green)
6 Mounting hole
7 Name plate
8 Groove for identifica
tion signs (6x) (type IBS 8x20)
9 Sensor connections
(2 inputs per socket)
aJ Fastening hole with
earth connection
aJ
5
8
7
1
3
2
4
9
6
Fig.2/1: Display and connecting elements type CP−E08−M12−CL
2−4
Festo P.BE−CPEA−CL−EN en 0711a
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL
The following diagram shows the display and connecting elements of input module CP−E08−M8−CL.
1 CP connection
incoming
2 Continuing
CP connection
3 Status LED short
circuit/overload/ undervoltage in sensor supply (red)
4 Status LEDs for
inputs (status display, green)
5 Status LED CP
communication (PS, green)
6 Mounting hole
7 Name plate
8 Groove for identifica
tion signs (6x) (type IBS 8x20)
9 Sensor connections
(1 input per socket)
aJ Fastening hole with
earth connection
aJ
5
8
7
1
PS
In
3
2
Out
4
1
0
9
6
3
2
5
4
7
6
Fig.2/2: Display and connecting elements type CP−E08−M8−CL
Festo P.BE−CPEA−CL−EN en 0711a
2−5
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL
The following diagram shows the display and connecting elements of input module CP−E16−KL−CL.
1 CP connection
incoming
2 Continuing CP
connection
3 Status LED short
circuit/overload/ undervoltage in sensor supply (red)
4 Status LED CP
communication (PS, green)
5 Name plate
6 Mounting hole
7 Groove for identifica
tion signs (4x) (type IBS 8x20)
8 Sensor connections
(8 inputs per plug)
9 Fastening hole with
earth connection
9
4
7
1
3
2
8
5
6
Fig.2/3: Display and connecting elements type CP−E16−KL−CL
2−6
Festo P.BE−CPEA−CL−EN en 0711a
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL

2.2 Mounting

The input modules are intended for fitting onto a wall or onto profiles. Take into account the following dimensions and weights:
Type
Dimensions Weight
CP−E08−M12−CL approx. 151 x 30 x 34.5 mm approx. 165 g
CP−E08−M8−CL approx. 151 x 30 x 34.5 mm approx. 190 g
CP−E16−KL−CL approx. 151 x 30 x 34.5 mm approx. 145 g
Tab.2/2: Dimensions of the input module
Fitting onto a wall The following diagram shows the dimensions for the holes of
screw size M4. Always fasten each module with 2 screws and a locking disc. Tightening torque of the fastening screws: 2 ± 0.5 Nm.
approx.151mm
In
1 Input module
type CP−E08−M12−CL
2 Input module
type CP−E08−M8−CL
3 Input module
type CP−E16−KL−CL
approx.30mm
approx.30mm
Out
75+0.5mm
In
Out
PS
In
Out
PS
10
1 0
141+0.5mm
3
2
3 2
X2
7
5
4
6
5
7
4
6
1
2
3
X1
Fig.2/4: Fitting dimensions CP−E...−CL
Tip: The position of the fastening screws on clipped−in drawing plates is marked with the symbol
Festo P.BE−CPEA−CL−EN en 0711a
.
2−7
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL

2.3 Installation

Warning
Sudden unexpected movements of the connected actua tors and undefined switching states of the electronics can cause injury to human beings and damage to property.
Before carrying out installation and maintenance work, switch off the following:
 the operating and load voltage supply on the CP master
(e.g.CPI/CP field bus node)
 separate power supplies
Warning
Incorrect or missing earthing measures can cause interfer ence due to electromagnetic influences.
Connect the earthing cable on the housing (screw under type plate, see Fig.2/1, Fig.2/2 or Fig.2/3) at low impe dance (short cable with large diameter) to the earth poten tial. A suitable cable clip is supplied with the module.
2−8
Festo P.BE−CPEA−CL−EN en 0711a
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL

2.3.1 Connecting sensors

Caution
Long signal cables reduce the immunity to interference. Do not exceed the maximum permitted signal cable length of 30 m.
Use plugs and cables from the Festo range (see Appendix A.6) for connecting sensors.
In the case of CP input modules type CP−E08−M12−CL and CP−E08−M8−CL:
· Tighten the plugs with the aid of the union nut in order to
prevent unintentional loosening, e.g. due to shock.
· Seal unused connections with protective caps. Only in this
way can you comply with protection class IP 65/IP67. Use protective caps from the Festo range (see Appendix A.6).
Festo P.BE−CPEA−CL−EN en 0711a
With CP input module type CP−E16−KL−CL:
Further information on connector sets as well as instructions on handling them can be found in Appendix A.6.4.
2−9
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL
Pin assignment (PNP inputs)
The following diagrams show as an example the pin assign ment of the sensor connections of the different CP input modules.
Pin assignment
1 1: 24V
2: Ix+1 3: 0V 4: Ix+0 5: Ground terminal
Ix = Input x
Fig.2/5: Pin assignment type CP−E08−M12−CL
Pin assignment
In
Out
01
23
PC
45
1 1: 24V
4: Ix+1 3: 0V
2 1: 24V
4: Ix+0 3: 0V
Ix = Input x
In
Out
PC
3
1 0
5
2
4
67
7 6
2
1
3
01
4
5
1
3
4
1 0
4
1
3
1
1
2
Fig.2/6: Pin assignment type CP−E08−M8−CL
2−10
Festo P.BE−CPEA−CL−EN en 0711a
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL
With input module type CP−E16−KL−CL, eight sensors can be connected to connections X1 and X2. The voltage supplied via the CP string is provided at the terminals + and  of X1 and X2 for supplying the sensors.
Caution
Do not connect an external supply to the terminals + and  of X1 and X2. Otherwise the input module will be dam aged.
Pin assignment
1 Plug X1
: 0 V DC
In
PC
7: Ix+7 6: Ix+6 ...
Out
2: Ix+2 1: Ix+1 0: ix+0 +: 24 V DC
2 Plug X2
: 0 V DC 7: Ix+15 6: Ix+14 ... 2: Ix+10 1: Ix+9
2
1
X2
X1
7 6 5 4 3 2 1 0
+
0: Ix+8 +: 24 V DC
Ix = Input x
Fig.2/7: Pin assignment of plugs X1 and X2 on type CP−E16−KL−CL
Use spring tension plugs or screw connector plugs from the Festo range (see Appendix A.6.4) for connecting sensors.
Festo P.BE−CPEA−CL−EN en 0711a
2−11
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL

2.3.2 Connect the input module to the CP string

Caution
Fault in data transfer on the CP string. Note the maximum permitted string lengths in the manual
for the CP master used. You will then avoid faults in data transfer between the
input module and the CP master (e.g. CP field bus node).
Caution
Functional damage Note the maximum permitted string lengths in the manual
for the CP master used.
Use only the intended original cable type KVI−CP−... from Festo for connecting the CPI/CP modules, see manual for the CP master used.
2−12
Note
Specifications on the current consumption of the different CPI/CP modules can be found in the relevant manuals.
The following functions are provided for the module via the CP cable:
 Operating voltage for internal electronics
 Connection for data exchange
 Operating voltage for the connected sensors
Festo P.BE−CPEA−CL−EN en 0711a
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL
The CPI modules are connected sequentially. The M9 plug is the incoming interface; the M9 socket is the continued inter face (see Fig.2/1 to Fig.2/3).
If the continuing CP connection is not used:
· Seal the CP connection with a protective cap type
FLANSCHDOSE SER.712, part no. 356684 (accessories). Only in this way can you comply with protection class IP 65/IP67.
Note
The continuing CP connection can only be used in conjunc tion with a CP master with extended functions.
Festo P.BE−CPEA−CL−EN en 0711a
2−13
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL

2.4 Diagnosis

2.4.1 Diagnosis via LEDs

Status LED CP communication (PS)
LED PS
Operating status Error handling
The operating status of the input module is shown by means of the status LED CP communication (see Tab.2/3).
(green)
Operating voltage applied, CP
LED lights up
LED is out
LED flashes
1)
Only on CP masters without extended functions
communication OK
 Operating voltage not ap
plied or no connection to CPI/CP master
 CPI/CP input module not
contained in string assign ment of the CPI/CP master
 Test phase when power sup
ply has been switched on or
 Undervoltage in sensor sup
ply (< 17 V)
1)
Tab.2/3: Status LED CP communication (PS)
None
· Check the CPI/CP cable and the operating
voltage connection on the CP master
· Save the CPI/CP string assignment on the
CPI/CP master (see manual for the CPI/CP master)
· None
or
· Eliminate undervoltage
2−14
Festo P.BE−CPEA−CL−EN en 0711a
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL
Status LED Short circuit/overload
Short circuit or overload of the sensor supply is shown by means of the status LED short circuit/overload (see Tab.2/4).
LED (red)
LED is out
LED lights up
Operating status Error handling
No short circuit/overload in
sensor supply
 Short circuit/overload in
sensor supply
Tab.2/4: Status LED short circuit/overload
Reaction to shor t circuit in the sensor supply
If there is a short circuit, the input module will switch off the power supply to the sensors and communicate the fault to the CP master. The status LEDs will be switched off and the inputs of the module supply a 0−signal.
· None
· Remove short circuit and, if applicable,
delete error
Festo P.BE−CPEA−CL−EN en 0711a
2−15
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL
Status LEDs Status display for input
Only with types CP−E08−M12−CL and CP−E08−M8−CL:
Next to the sensor connections there is a green LED for every input. This shows the status of the signal at the relevant input.
LED status of
Status
input
Logical 1 (signal present)
LED lights up
Logical 0 (no signal)
LED is out
Tab.2/5: Status LEDs for status display of input
2−16
Festo P.BE−CPEA−CL−EN en 0711a
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL

2.4.2 Diagnosis via the field bus

Depending on the CPI/CP master used, the CP modules type CP−...−EL provide different diagnostic information on fault searching.
Master
CP master (without extended functions)
CPI master (with extended functions)
Diagnosis of short circuit/overload in sensor supply
Yes No
Yes Yes
Diagnostics, undervoltage, sen sor supply
Tab.2/6: Diagnostic information
Note
Instructions on evaluating the diagnostic message can be found in the manual for the relevant CPI/CP master.
Festo P.BE−CPEA−CL−EN en 0711a
2−17
2. Input modules types CP−E08−M...−CL and CP−E16−KL−CL
2−18
Festo P.BE−CPEA−CL−EN en 0711a
Output module type CP−A04−M12−CL
Chapter 3
3−1Festo P.BE−CPEA−CL−EN en 0711a
3. Output module type CP−A04−M12−CL

Contents

3. Output module type CP−A04−M12−CL 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Function of output module type CP−A04−M12−CL 3−3 . . . . . . . . . .
3.1.1 Display and connecting elements 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Mounting 3−5 . . . . . .
3.3 Installation 3−6 . .
3.3.1 Connecting the actuators 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2 Connect the output module to the CP string 3−8 . . . . . . .
3.4 Diagnostics 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1 Diagnostics via LEDs 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.2 Diagnostics via the fieldbus 3−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . .
. . .
3−2
Festo P.BE−CPEA−CL−EN en 0711a
3. Output module type CP−A04−M12−CL
3.1 Function of output module type CP−A04−M12−CL
Output module type CP−A04−M12−CL provides 4 universally− usable digital outputs for controlling low−current consuming devices (e.g. bulbs, further valves, etc.).
Product
Type Explanation
illustration
Actuator connections via 4 sockets with M12 thread
CP−A04−M12−CL Provides 4 PNP outputs (IP65/IP67).
Tab.3/1: Overview of output modules
Festo P.BE−CPEA−CL−EN en 0711a
3−3
3. Output module type CP−A04−M12−CL

3.1.1 Display and connecting elements

The diagram below shows the display and connecting elements on the output modules.
1 CP connection
incoming
2 Continuing CP
connection
3 Status LED load
supply (PL, green)
4 Status LEDs for out
puts (status display, yellow)
5 Status LED short
circuit/overload at outputs (red)
6 Status LED CP
communication (PS, green)
7 Actuator connections
8 Name plate
9 Groove for identifica
tion signs, 6x (type IBS 8x20)
aJ Mounting hole
aA Fastening hole with
earth connection
aA
6
9
8
1
PS
PL
3
2
4
5
aJ
7
Fig.3/1: Display and connecting elements type CP−A04−M12−CL
3−4
Festo P.BE−CPEA−CL−EN en 0711a
3. Output module type CP−A04−M12−CL

3.2 Mounting

The output module is intended for fitting onto a wall or onto profiles. Take into account the following dimensions and weights:
Type
CP−A04−M12−CL approx. 151 x 30 x 34.5 mm approx. 165 g
Dimensions Weight
Tab.3/2: Dimensions of output module
Fitting onto a wall The following diagram shows the dimensions for the holes of
screw size M4. Always fasten each module with 2 screws and a locking disc. Tightening torque of the fastening screws: 2 ± 0.5 Nm.
approx. 151 mm
1 Output module
type CP−A04−M12−CL
approx. 30 mm
1
Fig.3/2: Fitting dimensions CP−A04−M12−CL
Tip: The position of the fastening screws on clipped−in drawing plates is marked with the symbol
.
Festo P.BE−CPEA−CL−EN en 0711a
3−5
3. Output module type CP−A04−M12−CL

3.3 Installation

Warning
Sudden unexpected movements of the connected actua tors and undefined switching states of the electronics can cause injury to human beings and damage to property.
Before carrying out installation and maintenance work, switch off the following:
 The operating and load voltage supply on the CP master
(e.g.CPI/CP fieldbus node)
 Separate power supplies
Warning
Incorrect or missing earthing measures can cause interfer ence due to electromagnetic influences.
Connect the earthing cable on the housing (screw under type plate, see Fig.3/1) at low impedance (short cable with large diameter) to the earth potential. (A suitable cable clip is supplied with the module.)
3−6
Festo P.BE−CPEA−CL−EN en 0711a
3. Output module type CP−A04−M12−CL

3.3.1 Connecting the actuators

For connecting the actuators, use plugs and cables with union nut and M12 thread from the Festo range (see Appendix A.6).
· Tighten the plugs with the aid of the union nut in order to
prevent unintentional loosening, e.g. due to shock.
· Seal unused connections with the protective caps sup
plied. Only in this way can you comply with protection class IP65/IP67.
Pin allocation
The following diagram shows as an example the pin allocation of the actuator connections on the CPI/CP output module.
1 25 3 45
Port 1 Port 2 Port 3 Port 4
1 Pin allocation
Connection 1 1: n.c. 2: Ax+1 3: 0V 4: Ax+0 5: FE
2 Pin allocation
Connection 2 1: n.c. 2: n.c. 3: 0V 4: Ax+1 5: FE
3 Pin allocation
Connection 3 1: n.c. 2: Ax+3 3: 0V 4: Ax+2 5: FE
5 Internal connection in module n.c.= (not connected)
AX = output x
Fig.3/3: Pin allocation type CP−A04−M12−CL
Festo P.BE−CPEA−CL−EN en 0711a
4 Pin allocation
Connection 4 1: n.c. 2: n.c. 3: 0V 4: Ax+3 5: FE
3−7
3. Output module type CP−A04−M12−CL
Note
When switching inductive loads, be sure to use a suitable safety circuit (e.g. free−whiling diode).

3.3.2 Connect the output module to the CP string

Caution
Fault in data transfer on the CPI/CP string. Note the maximum permitted string lengths in the manual
for the CPI master used. You will then avoid faults in data transfer between the
input module and the CP master (e.g.CP fieldbus node).
Caution
Functional damage Note the maximum permitted string lengths in the manual
for the CPI master used.
3−8
Use only the intended original cable type KVI−CP−... from Festo for connecting the CPI/CP modules, see manual for the CPI master used.
Note
Specifications on the current consumption of the different CPI/CP modules can be found in the relevant manuals.
Festo P.BE−CPEA−CL−EN en 0711a
3. Output module type CP−A04−M12−CL
The following functions are provided for the module via the CPI/CP cable:
 Operating voltage for internal electronics
 Connection for data exchange
 Operating voltage for the connected actuators
The CPI modules are connected sequentially. The M9 plug is the incoming interface; the M9 socket is the continued inter face (see Fig.3/1).
If the continuing CP connection
· Seal the CP connection with a protective cap type
is not used:
FLANSCHDOSE SER.712, part no. 356684 (accessories). Only in this way can you comply with protection class IP65/IP67.
Note
Check within the framework of your EMERGENCY STOP circuit, to ascertain the measures necessary for putting your machine/system into a safe state in the event of an EMERGENCY STOP (e.g. switching off the operating voltage for the valves and output modules, switching off the com pressed air).
Festo P.BE−CPEA−CL−EN en 0711a
3−9
3. Output module type CP−A04−M12−CL

3.4 Diagnostics

3.4.1 Diagnostics via LEDs

Status LED CP communication (PS)
LED PS
Operating status Error handling
The operating status of the output module is shown by means of the status LED CP communication (see Tab.3/3).
(green)
Operating voltage applied,
LED lights up
LED is out
LED flashes
1)
Only on CPI masters without extended functions
CPI/CP communication OK
 Operating voltage not ap
plied or no connection to CPI/CP master
 CPI/CP output module not
contained in string allocation of the CPI/CP master
 Test phase when the power
supply has been switched
1)
on
Tab.3/3: Status LED CP communication (PS)
None
· Check the CPI/CP cable and the operating
voltage connection on the CPI/CP master
· Save the CPI/CP string allocation on the CPI/
CP master (see manual for the CPI/CP master)
· None
3−10
Festo P.BE−CPEA−CL−EN en 0711a
3. Output module type CP−A04−M12−CL
Status LED Load supply (PL)
Short circuit or overload of the actuator supply is shown by means of the status LED short circuit/overload (see Tab.3/4).
LED PL
Operating status Error handling
(green)
Load supply OK None
LED lights up
 Undervoltage in actuator
supply (< 17 V)
LED flashes
 Load supply missing · Check the CPI/CP cable and the operating
LED is out
Tab.3/4: Status LED load supply (PL)
Status LEDs Status display of output
Next to the actuator connections there is a yellow LED for every output. This shows the status of the signal at the rel evant output.
LED status of output
· Check the CPI/CP cable and the operating
voltage connection on the CP master
voltage connection on the CP master
Status
Festo P.BE−CPEA−CL−EN en 0711a
Output supplies 1−signal
LED lights up
Output supplies 0−signal
LED is out
Tab.3/5: Status LEDs for status display of output
3−11
3. Output module type CP−A04−M12−CL
Status LEDs Short circuit/overload
Next to the actuator connections there is a red LED for each output. This shows a short circuit or overload at the output.
output
LED (red)
LED is out
LED lights up
1)
Fault will not be deleted automatically.
Operating status Error handling
No short circuit/overload · None
 Short circuit/overload at
output
· Eliminate short circuit and delete the fault
Tab.3/6: Status LED short circuit/overload at output
Reaction to shor t circuit in the load supply
Short circuit/overload If there is a short circuit/overload, the output module will
switch off the output self−holding and communicate the fault to the CPI master. When the short circuit has been eliminated, delete this fault as follows:
· Reset the output (e.g. by user program).
1)
3−12
Festo P.BE−CPEA−CL−EN en 0711a
3. Output module type CP−A04−M12−CL

3.4.2 Diagnostics via the fieldbus

Depending on the CPI/CP master used, the CP modules type CP−...−EL provide different diagnostic information on fault searching.
Master
Diagnostics of short circuit/over load in sensor
Diagnostics, undervoltage, sensor supply
supply
CP master (without extended functions)
CPI master (with extended functions)
Yes No
Yes Yes
Tab.3/7: Diagnostic information
Note
Instructions on evaluating the diagnostic message can be found in the manual for the relevant CPI/CP master.
Festo P.BE−CPEA−CL−EN en 0711a
3−13
3. Output module type CP−A04−M12−CL
3−14
Festo P.BE−CPEA−CL−EN en 0711a
Input modules type CP−E16−M...−EL and CP−E32−M8−EL
Chapter 4
4−1Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL

Contents

4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL 4−1 . . . . . . . . . . . . . . .
4.1 Function of the input modules CP−E16−M...−EL and CP−E32−M8−EL 4−3 . . . . . . . .
4.1.1 Display and connecting elements 4−4 . . . . . . . . . .
4.2 Mounting 4−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Labelling of inscription label holder 4−9 . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Installation 4−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4.1 Connecting sensors 4−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4.2 Connect the input module to the CP string 4−14 . . . . . . . . . . . . . . . . . . .
4.5 Diagnostics 4−16 . . . . . . . . . . . . . . . . . . . . . .
4.5.1 Diagnostics via LEDs 4−16 . . . . . . . . . . . . . . . . . .
4.5.2 Diagnostics using fieldbus 4−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . .
4−2
Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
4.1 Function of the input modules CP−E16−M...−EL and CP−E32−M8−EL
CPI input modules provide digital inputs for connecting sen sors, thereby enabling e.g.cylinder positions to be scanned. A distinction is made between the following types:
Product illustration
Sensor connections via 16 M8 sockets, 4−pin
Sensor connections via 16 M8 sockets, 3−pin
Sensor connections via 8 M12 sockets, 5−pin
Type Explanation
CP−E32−M8−EL Provides 32 PNP inputs (IP65).
CP−E16−M8−EL Provides 16 PNP inputs (IP65). CP module
CP−E16−M12−EL Provides 16 PNP inputs (IP65).
It can only be connected to the CPI system with extended functions (CPI master). The CP module CP−E32−M8−EL enables module diagnosis and module monitoring of the sensor voltage.
CP−E16−M8−EL enables group diagnosis and group monitoring of the sensor voltage. A group consists of 4 inputs.
CP module CP−E16−M8−EL enables group diagnosis and group monitoring of the sensor voltage. A group consists of 4 inputs.
Tab.4/1: Overview of input modules
Festo P.BE−CPEA−CL−EN en 0711a
4−3
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL

4.1.1 Display and connecting elements

The following diagram shows the display and connecting elements of input module CP−E32−M8−EL.
45 67 8
1
2
3
1
CPI connection incoming
2 CPI connection continuing
3 Fastening hole with earth connection
4 Fastening holes
5 Status LED CP communication
(PS, green)
4
9
aJ
4
7 Status LEDs for inputs
(status display, green)
8 Mounting for inscription label holder
(type: ASCF−H−E2)
9 Module designation
aJ 32 sensor connections (two inputs per
socket)
6 Status LED short circuit/overload in
sensor supply (red)
Fig.4/1: Display components and connecting elements type CP−E32−M8−EL
4−4
Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
The following diagram shows the display and connecting elements of input module CP−E16−M8−EL.
45 678 9
1
2
3
Group
1 CPI connection incoming
2 CPI connection continuing
3 Fastening hole with earth connection
4 Fastening holes
5 Status LED CP communication
(PS, green)
6 Status LED (module) short
circuit/overload in sensor supply (red)
4
aJ
aA
4
7 Status LEDs for inputs
(status display, green)
8 Status LED (group)
short circuit/overload in sensor supply (red)
9 Mounting for inscription label holder
(type: ASCF−H−E2)
aJ Module designation
aA 16 sensor connections (one input per
socket)
Fig.4/2: Display components and connecting elements type CP−E16−M8−EL
Festo P.BE−CPEA−CL−EN en 0711a
4−5
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
The following diagram shows the display and connecting elements of input module CP−E16−M12−EL.
45 678 9
1
2
3
Group
1 CPI connection incoming
2 CPI connection continuing
3 Fastening hole with earth connection
4 Fastening holes
5 Status LED CP communication
(PS, green)
4
aJ
aA
4
7 Status LEDs for inputs
(status display, green)
8 Status LED (group) short
circuit/overload in sensor supply (red)
9 Mounting for inscription label holder
(type: ASCF−H−E2)
aJ Module designation
6 Status LED (module) short
circuit/overload in sensor supply (red)
Fig.4/3: Display components and connecting elements type CP−E16−M12−EL
4−6
aA 16 sensor connections (two inputs per
socket)
Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL

4.2 Mounting

The input modules are intended for fitting onto a wall or onto H−rails. Take into account the following dimensions and weights:
Type
CP−E32−M8−EL approx. 143 x 104 x 30 mm approx. 260 g
CP−E16−M8−EL approx. 143 x 104 x 30 mm approx. 260 g
CP−E16−M12−EL approx. 143 x 104 x 30 mm approx. 260 g
Dimensions Weight
Tab.4/2: Dimensions of the input module
Fitting onto a wall The following diagram shows the dimensions for the holes.
Always fasten each module with 4 screws and a locking disc. Tightening torque of the fastening screws: 1.2 ± 0.2 Nm.
approx. 104 mm
approx. 102 mm
approx. 142 mm
Festo P.BE−CPEA−CL−EN en 0711a
Fig.4/4: Fitting dimensions input module CP−E...−EL
4−7
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
H−rail mounting The module is suspended from above in the H−rail (see arrow
A in Fig.4/5). The module is ear thed via the clamping component (see arrow B in Fig.4/5). The clamping component and the mount ing screw are included with the module.
4−8
Fig.4/5: H−rail mounting input module CP−E...−EL
Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL

4.3 Labelling of inscription label holder

Inscription label holders with part number 547473 (type ASCF−H−E2) are provided for labelling the EL modules. You can find the dimensions of the inscription field in Fig.4/6.
approx. 60
Fig.4/6: Inscription label holders for EL modules,
type ASCF−H−E2 (dimensions in mm)
approx. 24
Festo P.BE−CPEA−CL−EN en 0711a
4−9
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL

4.4 Installation

Warning
Sudden unexpected movements of the connected actua tors and undefined switching states of the electronics can cause injury to human beings and damage to property.
Before carrying out installation and maintenance work, switch off the following:
 The operating and load voltage supply on the CP master
(e.g.CPI/CP fieldbus node)
 Separate power supplies
Warning
Incorrect or missing earthing measures can cause interfer ence due to electromagnetic influences.
Connect the earth connection on the housing with low impedance (short cable with large cross−sectional area) to the earth potential. A suitable cable lug is supplied with the module.
4−10
Note
 With wall mounting, earthing is done via a earthing
cable.
 With H−rail mounting, earthing is done via a clamping
component.
Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL

4.4.1 Connecting sensors

Caution
Long signal cables reduce the immunity to interference. Do not exceed the maximum permitted signal cable length of 30 m.
Use plugs and cables from the Festo range (see Appendix A.6) for connecting sensors.
For CPI input modules:
· Tighten the plugs with the aid of the union nut in order to
prevent unintentional loosening, e.g. due to shock.
· Seal unused connections with protective caps. Only in this
way can you comply with protection class IP65. Use protective caps from the Festo range (see Appendix A.6).
Festo P.BE−CPEA−CL−EN en 0711a
Further information on connector sets as well as instructions on handling them can be found in Appendix A.6.4.
4−11
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
Pin allocation (PNP inputs)
The following diagrams show as an example the pin allocation of the sensor connections of the different CP...EL input modules.
Pin allocation
1 1: 24V
2: Ix+1 3: 0V 4: Ix
Ix = Input x
Fig.4/7: Pin allocation type CP−E32−M8−EL
1
Pin allocation
1 1: 24V
3: 0V 4: Ix
Ix = Input x
Fig.4/8: Pin allocation type CP−E16−M8−EL
4−12
1
Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
Pin allocation
1 1: 24V
2: Ix+1 3: 0V 4: Ix 5: FE
Ix = Input x
Fig.4/9: Pin allocation type CP−E16−M12−EL
Use screw connector plugs from the Festo range (see Appendix A.6.4) for connecting sensors.
1
Festo P.BE−CPEA−CL−EN en 0711a
4−13
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL

4.4.2 Connect the input module to the CP string

Caution
Fault in data transfer on the CP string. Note the maximum permitted string lengths in the manual
for the CPI/CP master used. You will then avoid faults in data transfer between the
input module and the CPI/CP master.
Caution
Functional damage Note the maximum permitted string lengths in the manual
for the CP master used.
Use only the intended original cable type KVI−CP−3−... from Festo for connecting the CP modules, see manual for the CP master used.
4−14
Note
Specifications on the current consumption of the different CP modules can be found in the relevant manuals.
The following functions are provided for the module via the CP cable:
 Operating voltage for internal electronics
 Connection for data exchange
 Operating voltage for the connected sensors
Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
The CPI modules are connected sequentially. The M9 plug is the incoming interface; the M9 socket is the continued inter face (see Fig.4/1 to Fig.4/3).
If the continuing CP connection is not used:
· Seal the CP connection with a protective cap type
FLANSCHDOSE SER.712, part no. 356684 (accessories). Only in this way can you comply with protection class IP65.
Note
The continuing CP connection can only be used in conjunc tion with a CPI master (with extended functions).
Festo P.BE−CPEA−CL−EN en 0711a
4−15
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL

4.5 Diagnostics

4.5.1 Diagnostics via LEDs

Status LED CP communication (PS)
LED PS
Operating status Error handling
The operating status of the input module is shown by means of the status LED CP communication (see Tab.4/3).
(green)
Operating voltage applied, CP
LED lights up
LED is out
LED flashes
communication OK
 Operating voltage not ap
plied or no connection to CPI/CP master
 CPI input module not con
tained in string assignment of the CPI/CP master
 Undervoltage in sensor sup
ply (< 17 V)
Tab.4/3: Status LED CP communication (PS)
None
· Check the CPI/CP cable and the operating
voltage connection on the CPI/CP master
· Save the CP string assignment on the CPI/CP
master (see manual for the CPI/CP master)
· Eliminate undervoltage
4−16
Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
Status LED Short circuit/overload
Short circuit or overload of the sensor supply is shown by means of the status LED short circuit/overload (see Tab.4/4 and Tab.4/5).
LED (red)
Operating status Error handling
module
LED is out
LED lights up
LED lights up
No short circuit/overload in
sensor supply
Only for CP−E16−M8−EL and CP−E16−M12−EL:
 Short circuit/overload in
sensor supply (display module) 1 per module, lights up when a group LED P lights up
Only for CP−E32−M8−EL:
 Short circuit/overload in
sensor supply (display module) 1 per module, lights up when an input is faulty.
· None
· Remove short circuit and, if applicable,
delete error
· Remove short circuit and, if applicable,
delete error
Tab.4/4: Status LED (display module) short circuit/overload
Festo P.BE−CPEA−CL−EN en 0711a
4−17
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
LED (red)
Operating status Error handling
group
LED is out
LED lights up
No short circuit/overload in
sensor supply
Only for CP−E16−M8−EL and CP−E16−M12−EL:
 Short circuit/overload in
sensor supply (Display group, see Fig.4/2 and Fig.4/3) 1 per four inputs, lights up when one input per group is faulty.
· None
· Remove short circuit and, if applicable,
delete error
Tab.4/5: Status LED (display group) short circuit/overload
Reaction to shor t circuit in the sensor supply
If there is a short circuit, the input module will switch off the power supply to the sensors and communicate the fault to the CPI/CP master. The status LEDs will be switched off and the inputs of the module supply a 0−signal. After the short circuit or overload has been eliminated, the module must be separated from the supply voltage in order to reset the short circuit/overload.
4−18
Festo P.BE−CPEA−CL−EN en 0711a
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL
Status LEDs Status display for input
Above the sensor connections there is a green LED for every input. This shows the signal status at the relevant input.
LED status of
Signal status
input
Logical 1 (signal present)
LED lights up
Logical 0 (no signal)
LED is out
Tab.4/6: Status LEDs for status display of input
Festo P.BE−CPEA−CL−EN en 0711a
4−19
4. Input modules type CP−E16−M...−EL and CP−E32−M8−EL

4.5.2 Diagnostics using fieldbus

Depending on the CPI/CP master used, the CP modules type CP−...−EL provide different diagnostic information on fault searching.
Master
Diagnostics of short circuit/over load in sensor
Diagnostics, undervoltage, sensor supply
supply
CP master (without extended functions)
CPI master (with extended functions)
Yes No
Yes Yes
Tab.4/7: Diagnostic information
Note
Instructions on evaluating the diagnostic message can be found in the manual for the relevant CPI/CP master.
4−20
Festo P.BE−CPEA−CL−EN en 0711a
Output module type CP−A08−M12−EL−Z
Chapter 5
5−1Festo P.BE−CPEA−CL−EN en 0711a
5. Output module type CP−A08−M12−EL−Z

Contents

5. Output module type CP−A08−M12−EL−Z 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Function of the output module type CP−A08−M12−E L−Z 5−3 . . . . . . . . . . .
5.1.1 Display and connecting elements 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Mounting 5−5 . . . . . . . . . . . .
5.3 Labelling of inscription label holder 5−7 . . . .
5.4 Installation 5−8 . . . . . . . . . . . . . . . . . . . . .
5.4.1 Connect external load supply 5−9 . . . . . . . . . . . . . . . .
5.4.2 Connecting the actuators 5−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.3 Connect the output module to the CP string 5−11 . . . . . . . . . . . . . . . . . .
5.5 Diagnostics 5−13 . . . . . . . . . . . . . . . . . . . . . . . .
5.5.1 Diagnostics via LEDs 5−13 . . . . . . . . . . . . . . . . . . .
5.5.2 Diagnostics using fieldbus 5−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . .
. .
5−2
Festo P.BE−CPEA−CL−EN en 0711a
5. Output module type CP−A08−M12−EL−Z
5.1 Function of the output module type CP−A08−M12−EL−Z
Output module type CP−A08...−M12−EL−Z provides eight uni versally usable digital outputs for controlling low−current con suming devices (bulbs, further valves etc.).
Product illustration
Actuator connections via 8 sockets with M12 thread
Type Explanation
CP−A08−M12−EL−Z Provides 8 PNP outputs (IP65). CP module
Tab.5/1: Overview of output modules
CP−A08−M12−EL−Z has channel−by−channel monitoring of short circuit/overload of the outputs.
Festo P.BE−CPEA−CL−EN en 0711a
5−3
5. Output module type CP−A08−M12−EL−Z

5.1.1 Display and connecting elements

The following diagram shows the display and connecting elements of output module CP−A08−M12−EL−Z.
5
6
78 aJ
9 5
1
2
3
4
CPI connection incoming
1
2 CPI connection continuing
3 Load supply for outputs
4 Fastening hole with earth connection
5 Fastening holes
6 Status LED CP communication
(PS, green)
7 Status LED output (module) short
circuit/overload (red)
aA
aB
aC
5
8 Status LED
Load supply (PL, green)
9 Status LEDs for outputs
(status display, yellow)
aJ Status LED output (channel) short
circuit/overload (red)
aA Mounting for inscription label holder
(type: ASCF−H−E2)
aB Module designation
aC 8 outputs (1 output per socket)
Fig.5/1: Display components and connecting elements type CP−A08−M12−EL−Z
5−4
Festo P.BE−CPEA−CL−EN en 0711a
5. Output module type CP−A08−M12−EL−Z

5.2 Mounting

The output module is intended for fitting onto a wall or onto profiles. Take into account the following dimensions and weights:
Type
CP−A08−M12−EL−Z approx. 143 x 104 x 30 mm approx. 260 g
Dimensions Weight
Tab.5/2: Dimensions of output module
Fitting onto a wall The following diagram shows the dimensions for the holes.
Always fasten each module with 4 screws and a locking disc. Tightening torque of the fastening screws: 1.2 ± 0.2 Nm.
approx. 104 mm
approx. 102 mm
approx. 142 mm
Fig.5/2: Installation dimensions of output module
CP−A08−M12−EL−Z
Festo P.BE−CPEA−CL−EN en 0711a
5−5
5. Output module type CP−A08−M12−EL−Z
H−rail mounting The module is suspended from above in the H−rail (see arrow
A in Fig.5/3). The module is ear thed via the clamping component (see arrow B in Fig.5/3). The clamping component and the mount ing screw are included with the module.
5−6
Fig.5/3: H−rail mounting of output modules
CP−A08−M12−EL−Z
Festo P.BE−CPEA−CL−EN en 0711a
5. Output module type CP−A08−M12−EL−Z

5.3 Labelling of inscription label holder

Inscription label holders with part number 547473 (type ASCF−H−E2) are provided for labelling the EL modules. You can find the dimensions of the inscription field in Fig.5/4.
approx. 60
Fig.5/4: Inscription label holders for EL modules,
type ASCF−H−E2 (dimensions in mm)
approx. 24
Festo P.BE−CPEA−CL−EN en 0711a
5−7
5. Output module type CP−A08−M12−EL−Z

5.4 Installation

Warning
Sudden unexpected movements of the connected actua tors and undefined switching states of the electronics can cause injury to human beings and damage to property.
Before carrying out installation and maintenance work, switch off the following:
 Operating and load voltage supply for the CP master
(e.g. CP fieldbus node)
 Separate power supplies
Warning
Incorrect or missing earthing measures can cause interfer ence due to electromagnetic influences.
Connect the earth connection on the housing with low impedance (short cable with large cross−sectional area) to the earth potential. A suitable cable lug is supplied with the module.
5−8
Note
 With wall mounting, earthing is done via a earthing
cable.
 With H−rail mounting, earthing is done via a clamping
component.
Festo P.BE−CPEA−CL−EN en 0711a
5. Output module type CP−A08−M12−EL−Z

5.4.1 Connect external load supply

The output module CP−A08−M12−EL−Z is supplied via an exter nal load supply 24 V to supply the actuators.
 Power must be supplied via a power supply unit that
meets EN 60204−1 / IEC204 (PELV power supply unit).
 Max. 0.5 A is available per channel.
 The outputs are designed to be short−circuit proof and
overload
proof channel−by−channel.
Festo P.BE−CPEA−CL−EN en 0711a
5−9
5. Output module type CP−A08−M12−EL−Z

5.4.2 Connecting the actuators

For connecting the actuators, use plugs and cables with M12 union nut from the Festo range (see Appendix A.6).
· Tighten the plugs with the aid of the union nut in order to
prevent unintentional loosening, e.g. due to shock.
· Seal unused connections with the protective caps sup
plied. Only in this way can you comply with protection class IP65.
Pin allocation
The following diagram shows as an example the pin allocation of the actuator connections on the CPI output module.
1 25 3 45
1 Pin allocation
Port x1 1: n.c. 2: Ax+1 3: 0V 4: Ax 5: FE
Port x1 Port x2
2 Pin allocation
Port x2 1: n.c. 2: n.c. 3: 0V 4: Ax+1 5: FE
3 Pin allocation
Port x3 1: n.c. 2: Ax+3 3: 0V 4: Ax+2 5: FE
Port x3
5 Internal connection in module n.c.= (not connected)
AX = output x
Fig.5/5: Pin allocation type CP−A08−M12−E L−Z
5−10
Port x4
4 Pin allocation
Port x4 1: n.c. 2: n.c. 3: 0V 4: Ax+3 5: FE
Festo P.BE−CPEA−CL−EN en 0711a
5. Output module type CP−A08−M12−EL−Z
Note
When switching inductive loads, be sure to use a suitable safety circuit (e.g. free−whiling diode).

5.4.3 Connect the output module to the CP string

Caution
Fault in data transfer on the CP string. Note the maximum permitted string lengths in the manual
for the CP master used. You will then avoid faults in data transfer between the
input module and the CP master (e.g. CP fieldbus node).
Caution
Functional damage Note the maximum permitted string lengths in the manual
for the CP master used.
Festo P.BE−CPEA−CL−EN en 0711a
Use only the intended original cable type KVI−CP−3−... from Festo for connecting the CP modules, see manual for the CP master used.
Note
Specifications on the current consumption of the different CP modules can be found in the relevant manuals.
5−11
5. Output module type CP−A08−M12−EL−Z
The following functions are provided for the module via the CPI cable:
 Operating voltage for internal electronics
 Connection for data exchange
The CPI modules are connected sequentially. The M9 plug is the incoming interface; the M9 socket is the continued inter face (see Fig.5/1).
If the continuing CP connection is not used:
· Seal the CP connection with a protective cap type
FLANSCHDOSE SER.712, part no. 356684 (accessories). Only in this way can you comply with protection class IP65.
Note
Check within the framework of your EMERGENCY STOP circuit, to ascertain the measures necessary for putting your machine/system into a safe state in the event of an EMERGENCY STOP (e.g. switching off the operating voltage for the valves and output modules, switching off the com pressed air).
5−12
Festo P.BE−CPEA−CL−EN en 0711a
5. Output module type CP−A08−M12−EL−Z

5.5 Diagnostics

5.5.1 Diagnostics via LEDs

Status LED CP communication (PS)
LED PS (green)
LED lights up
LED is out
Operating status Error handling
Operating voltage applied, CP communication OK
 Operating voltage not ap
plied or no connection to CPI/CP master
 CPI output module not con
tained in string allocation of the CPI/CP master
The operating status of the output module is shown by means of the status LED CP communication (see Tab.5/3).
Tab.5/3: Status LED CP communication (PS)
Status LED Load supply (PL)
LED PL (green)
LED lights up
Operating status Error handling
Load supply OK None
Short circuit or overload of the actuator supply is shown by means of the status LED short circuit/overload (see Tab. 5/4).
None
· Check the CPI/CP cable and the operating
voltage connection on the CPI/CP master
· Save the CP string allocation on the CPI/CP
master (see manual for the CPI/CP master)
 Undervoltage in actuator
supply (< 17.5 V)
LED flashes
 Load supply missing (< 11 V) · Check the CP cable and the operating voltage
LED is out
Tab.5/4: Status LED load supply (PL)
Festo P.BE−CPEA−CL−EN en 0711a
· Check the CP cable and the operating voltage
connection on the CPI/CP master
connection on the CPI/CP master
5−13
5. Output module type CP−A08−M12−EL−Z
Status LEDs Status display of output
Status LEDs Short circuit/overload output
LED (red)
Operating status Error handling
module
No short circuit/overload · None
Next to the actuator connections there is a yellow LED for every output. This shows the status of the signal at the relevant output.
LED status of
Status
output
Output supplies 1−signal
LED lights up
Output supplies 0−signal
LED is out
Tab.5/5: Status LEDs for status display of output
Next to the actuator connections there is a red LED for each output. This shows a short circuit or overload at the output.
LED is out
Display module:
(1 per module, lights up when
LED lights up
1)
Fault will not be deleted automatically.
an output LED lights up)  Short circuit/overload out
put (display module)
· Eliminate short circuit and delete the fault
Tab.5/6: Status LED short circuit/overload output (display module)
5−14
Festo P.BE−CPEA−CL−EN en 0711a
1)
5. Output module type CP−A08−M12−EL−Z
LED (red)
Operating status Error handling
channel
No short circuit/overload · None
LED is out
Display channel:
(1 per output)
LED lights up
1)
Fault will not be deleted automatically.
 Short circuit/overload out
put (display output)
· Eliminate short circuit and delete the fault
Tab.5/7: Status LED short circuit/overload output (display channel)
Reaction to shor t circuit in the load supply
Short circuit/overload If there is a short circuit/overload, the output module will
switch off the output self−holding and communicate the fault to the CP master. In case of short circuit, the output remains switched off. When the short circuit has been eliminated, delete this fault as follows:
· To reactive the output, the power supply or the complete
module must be separated from the power supply. Only resetting the output does not trigger either the error message or the blocking of functions.
1)
Festo P.BE−CPEA−CL−EN en 0711a
5−15
5. Output module type CP−A08−M12−EL−Z

5.5.2 Diagnostics using fieldbus

Irrespecti ve of the CPI/CP master used, the CP output module type CP−...−EL provides diagnostic information on fault searching.
Master
Diagnostics of short circuit/over load in actuator
Diagnostics, undervoltage, actuator supply
supply
CP master (without extended functions)
CPI master (with extended functions)
Common fault message
Yes Yes
Tab.5/8: Diagnostic information
Note
Instructions on evaluating the diagnostic message can be found in the manual for the relevant CPI/CP master.
5−16
Festo P.BE−CPEA−CL−EN en 0711a

Technical appendix

Appendix A
A−1Festo P.BE−CPEA−CL−EN en 0711a
A. Technical appendix

Contents

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Technical specifications A−3 . .
A.1.1 General technical data A−3 . . . . . . .
A.1.2 Technical specifications of the CL input modules A−4 . . . . . . . . . . . . . .
A.1.3 Technical specifications
A.1.4 Technical specifications of the EL input modules A−7 . . . . . . . . . . . . . .
A.1.5 Technical specifications of the EL output modules A−9 . . . .
A.2 Internal structure of the inputs A−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2.1 Internal
A.2.2 Internal structure type CP−E08−M12−CL and CP−E16−M12−EL A−11 . . . . .
A.2.3 Internal structure type CP−E08−M8−CL and CP−E16−M8−EL A−12 . . . . . . .
A.2.4 Internal structure type CP−E16−KL−CL A−13 . . . . . . . . . . . . . . . . . . . . . . . .
A.3 Internal structure of the outputs A−14 . . . . . . . . . . . . . . . . .
A.3.1 Internal structure type CP−A04−M12−CL and CP−A08−M12−EL−Z A−14 . . .
A.4 Examples of circuitry A−15 . . . . . . . . . . . . . . . . . . . .
A.4.1 Circuitry examples for inputs A−15 . . . . . . . . . . . . . . . . . . . . . . .
A.4.2 Circuitry examples for outputs A−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.5 General information on parameterisation A−22 . . . . . .
A.5.1 Input debounce time (only with CP−EL modules) A−22 . . . . . . . . . . . . . . .
A.5.2 Signal extension (only with CP−EL modules) A−24 .
A.6 Accessories A−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.6.1 General accessories A−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.6.2 Accessories for modules with M12 connection A−27 . . . . . . . . . . . . . . . .
A.6.3 Accessories for modules with M8 connection A−28 . . . . . . . . . . . . . .
A.6.4 Connector sets for input module type CP−E16−KL−CL A−29 . . . . . . . . . . . .
structure type CP−E32−M8−EL A−10 . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
of the CL output modules A−6 . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . .
. . .
.
A−2
Festo P.BE−CPEA−CL−EN en 0711a
Loading...