Festo CMMP Series Description

PROFIBUS for motor controller CMMP…
Description
PROFIBUS CMMP…
Description
557 338 de 0708NH [723 751]
Edition __________________________________________________ de 0708NH
Description ________________________________ P.BE-CMMS-FHPP-PB-SW-EN
Order no ____________________________________________________ 557 338
(Festo AG & Co KG., D-73726 Esslingen, 2008)
Internet: http://www.festo.com
E-mail: service_international@festo.com
The copying, distribution and utilization of this document as well as the communication of its contents to others without expressed authorization is prohibited. Offenders will be held liable for compensation of damages. All rights reserved, in particular the right to carry out patent, utility model or ornamental design registrations.
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 3
Index of revisions
Author:
Name of manual:
File name:
File saved at:
Consec. no.
Description
Index of revisions
Date of amendment
001
Produced
0708NH
21.04.2008
Trade names
PROFIBUS, PROFIBUS-DP® are registered trade marks of PROFIBUS International (P.I.)
SIMATIC® is registered trade mark of Siemens AG
4 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
1. General information
Table of contents
1. General information ................................................................................................ 6
1.1 Documentation ...................................................................................................... 6
1.2 Festo Profile for Handling and Positioning (FHPP) ................................................. 6
1.3 Data exchange in the PROFIBUS ............................................................................ 7
2. Safety instructions for electric drives and controllers ............................................ 8
2.1 Icons and signs ...................................................................................................... 8
2.2 General instructions .............................................................................................. 8
2.3 Dangers due to incorrect use ............................................................................... 10
2.4 Safety instructions .............................................................................................. 11
2.4.1 General safety information .................................................................. 11
2.4.2 Safety instructions for assembly and maintenance .............................. 12
2.4.3 Protection aganst touching electric components ................................. 14
2.4.4 Protection by low voltage (PELV) against electric shock ...................... 16
2.4.5 Protection from dangerous movements ............................................... 16
2.4.6 Protection aganst touching hot components ....................................... 17
2.4.7 Protection when handling and assembling .......................................... 18
3. Assembly and installation .................................................................................... 19
3.1 Connecting and display elements ........................................................................ 19
3.2 Assembly ............................................................................................................. 20
3.3 Installation .......................................................................................................... 21
3.3.1 Pin assignment of PROFIBUS interface................................................. 22
3.3.2 Termination and bus terminating resistors .......................................... 23
4. Configuration of the PROFIBUS module ............................................................... 24
4.1 Setting the slave address .................................................................................... 25
4.2 PROFIBUS communication ................................................................................... 25
4.3 PROFIBUS configuration ...................................................................................... 26
4.4 PROFIBUS slave configuration ............................................................................. 26
4.5 PROFIBUS master configuration .......................................................................... 26
4.5.1 Configuration with SIMATIC manager .................................................. 27
5. Diagnosis .............................................................................................................. 30
5.1 Network status LED ............................................................................................. 30
5.2 PROFIBUS error codes ......................................................................................... 30
A. Technical specifications ........................................................................................ 32
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 5
1. General information
1. General information
1.1 Documentation
This documentation describes how to connect the field bus to the CMMP motor controller in a PROFIBUS-DP network. It describes how to configure the PROFIBUS and explains the user protocol FHPP. A detailed description of the FHPP can be found in the FHPP manual.
Further information can be found in the following CMMP manuals:
- Product manual CMMP-AS--3A:
Description of the technical specifications and device functions as well as instructions on installing and operating the servo positioning controller CMMP-AS-C10-3A-P3 for 1­phase servo positioning controllers.
- Product manual "Servo positioning controller P-BE-CMMP-AS--11A":
Description of the technical specifications and device functions as well as instructions on installing and operating the servo positioning controller CMMP-AS-C10-11A-P3 for 3-phase servo positioning controllers.
- FHPP manual "P.BE-CMM-FHPP-SW-…":
Description of the implemented Festo profiles for handling and positioning.
- Manual P.BE-CMMP-AS-PB-S7
This manual is intended for people who are already familiar with this motor controller series and the DeviceNet protocol.
The documentation contains safety instructions which must be observed.
1.2 Festo Profile for Handling and Positioning (FHPP)
Festo has developed an optimised data profile, the "Festo Handling and Positioning Profile (FHPP)", tailored to the target applications for handling and positioning tasks.
The FHPP enables uniform control and programming for the various field bus systems and controllers from Festo.
In addition it defines the following for the user:
the operating modes the I/O data structure the parameter objects the sequence control.
6 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
1. General information
Field bus communication
Record select
Direct mode
Parameter channel
1
2
n
Modes
Position
Velocity
Free access to all parameters
for reading and writing
Tab. 1.1: The FHPP principle
Information on the FHPP profile (parameters, device data…) can be found in the
documentation P.BE-CMM-FHPP-SW-EN.
1.3 Data exchange in the PROFIBUS
PROFIBUS (PROcess Field BUS) is a standard developed by the PROFIBUS User Organisation. A complete description of the field bus system can be found in the following standard:
IEC 61158 "Digital data communication for measurement and control – Field bus for use in industrial control systems": This standard contains several parts and defines 10 "field bus protocol types." PROFIBUS is specified amongst these as type 3. PROFIBUS exists in two designs. PROFIBUS-DP can be found for fast data exchange in manufacturing technology and building automation (DP = decentral periphery). The incorporation into the ISO/OSI layer model is also described in this standard.
Further information, contact addresses etc. can be found under www.PROFIBUS.com
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 7
2. Safety instructions for electric drives and controllers
Note
Important information and instructions
Caution
Considerable damage to property may occur if these instructions are not observed.
Warning
DANGER!
Considerable damage to property and injury to human beings may occur if these instructions are not observed.
Warning
Dangerous voltage
The safety instructions contain reference to dangerous voltages which may occur.
Note
Before commissioning you must read the Safety instructions for electric drives and controllers as from page 8.
2. Safety instructions for electric drives and
controllers
2.1 Icons and signs
2.2 General instructions
Festo AG & Co. KG is not liable for damage caused by failure to observe the warning instructions in these operating instructions.
If the documentation is not clearly understood in this language version, please inform the supplier.
The faultless and reliable operation of the motor controller depends on its correct trans­port, storage, mounting and installation as well as on careful operation and maintenance.
8 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
2. Safety instructions for electric drives and controllers
Note
Only trained and qualified personnel should be allowed to handle the electric systems.
These safety instructions must be observed at all times.
Do not try to install or commission the motor controller before
you have carefully read through all safety instructions for
electric drives and controllers in this documentation. You must read through these safety instructions and all other user instructions before working with the motor controller.
If you do not have any user instructions for the motor controller, please contact your relevant sales representative.
Request that the operating instructions are sent immediately to
the responsible person, in order that the motor controller can
be operated correctly and safely.
These safety instructions must also be provided if the motor controller is sold, lent and/or passed on to third parties.
Trained and qualified personnel
For the purpose of this manual and the warning instructions on the product itself, techni­cians working with this product must be adequately familiar with the setting up, mounting, commissioning and operation of the product as well as with all warnings and precautionary measures in accordance with the operating instructions in this product manual, and must be sufficiently qualified for this task:
- Training and instructions on or authorization to switch on and switch off devices/
systems in accordance with technical safety standards, and to earth and mark them appropriately in accordance with the application requirements.
- Training or instructions in using and maintaining suitable safety equipment in
accordance with technical safety standards.
- Training in first aid.
The following instructions must be read before the first commissioning of the sytem in order that bodily injuries and/or damage to property can be avoided.
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 9
2. Safety instructions for electric drives and controllers
For safety and guarantee reasons it is not permitted for the motor controller to be opened by the user.
The prerequisite for faultless functioning of the motor controller is skilled project planning.
Warning
DANGER!
Incorrect handling of the motor controller and failure to observe the specified warning instructions, as well as unskilled interference with the safety devices can lead to damage to property, bodily injury, electric shock or in extreme cases to death.
Warning
DANGER!
High electric voltage and high working current.
Danger of death or serious bodily injury due to electric shock!
Warning
DANGER!
High electric voltage due to incorrect connection.
Danger of death or bodily injury due to electric shock!
Warning
DANGER!
Surfaces of the device housing may be hot.
Danger of injury. Danger of burning.
Warning
DANGER!
Dangerous movements.
Danger of death, serious bodily injury or damage to property due to unintentional movement of the motors.
2.3 Dangers due to incorrect use
10 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
2. Safety instructions for electric drives and controllers
Warning
The motor controller complies with protection class IP20.
Warning
Use only accessories and spare parts which are approved of by the manufacturer.
Warning
The motor controllers must be connected to the mains network in accordance with EN standards and appropriate national regula­tions, so that they can be disconnected with suitable uncoupling devices (e.g. main switch, fuse, circuit breaker).
The motor controller can be fused with a 300 mA all-current sensi­tive FI protective switch (RCD = Residual Current protective Device).
Warning
For switching the control contacts you should use gold-plated contacts or high-pressure contacts.
Precautionary measures must be taken for preventing interference to switching systems, e.g. switching protective switches and relays with RC elements or diodes.
You must observe the safety regulations and directives of the country in which the device is to be used.
Warning
The environmental conditions specified in the product
documentation must be observed. Safety-critical applications are not permitted if they are not
explicitly approved of by the manufacturer.
2.4 Safety instructions
2.4.1 General safety information
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 11
2. Safety instructions for electric drives and controllers
Instructions for EMC-approved installations can be found in the
product manuals for the CMMP family. The manufacturer of the system or machine is responsible for ensuring that the limit values requested by the national regulations are observed.
Warning
The technical specifications as well as the connection and installa­tion conditions for the motor controller can be found in this product manual. These specifications must be observed at all times.
Warning
DANGER!
The general installation and safety regulations for working on
high-current systems (e.g. DIN, VDE, EN, IEC or other national
and international regulations) must be observed here. Failure to observe these regulations can lead to bodily injury, death
or considerable damage to property.
The following precautionary measures also apply without claim to completeness:
- VDE 0100 Regulation for setting up high-voltage systems
up to 1000 volts
- EN 60204 Electrical equipment for machines
- EN 50178 Equipping high-voltage systems with electronic
operating media
Warning
The operation, maintenance and/or commissioning of the motor controller may only be carried out by trained qualified personnel and with electrical appliances suited for this work.
2.4.2 Safety instructions for assembly and maintenance
For assembling and maintaining the system, the relevant DIN, VDE, EN and IEC regulations, as well as all national and local safety and accident prevention regulations must always be observed. The system manufacturer or the user is responsible for ensuring that these regulations are observed.
12 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
2. Safety instructions for electric drives and controllers
Warning
The series-supplied motor holding brake or an external motor­holding brake controlled by the drive controller alone is not suitable for protecting human beings.
Vertical axes must be additionally secured against falling or
sliding down when the motor is switched off with e.g.
- mechanical locking of the vertical axis,
- external braking, safety catch or clamping devices or
- sufficient weight compensation of the axis.
Warning
The external or internal braking resistance is activated and can carry a dangerous intermediate circuit voltage for up to approx. 5 minute after the motor controller has been switched off. Ths can cause serious bodily injury or even death if it is touched.
Before carrying out maintenance work, make sure that the
power supply is switched off and locked and that the
intermediate circuit is discharged.
Switch the electrical equipment free of voltage via the main
switch and make sure that it cannot be switched on again.
Wait until the intermediate circuit is discharged after
- maintenance work and repairs
- cleaning
- long periods out of use.
Warning
Proceed carefully with mounting. Make sure that during mounting as well as later during the operation of the drive that no drilling shavings, metal dust or mounting parts (screws, nuts, pieces of wire) can fall into the motor controller.
Make sure also that the external voltage supply of the controller (24 V) is switched off.
The intermediate circuit or the mains voltage must always be switched off before the 24 V controller supply is switched off.
Avoiding accidents, bodily injury and/or material damage:
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 13
2. Safety instructions for electric drives and controllers
Warning
Other work in the vicinity of the machine must only be carried
out when the AC or DC supply is switched off and locked. Switched-off final stage or switched-off controller enable are not
suitable locking conditions. In the event of a fault, this could lead to unintentional movement of the drive.
Warning
Carry out commissioning with a free-running motor, in order to avoid mechanical damage, e.g. due to incorrect direction of rotation.
Warning
Electronic devices are never fail-proof.
The user is responsible for ensuring that his system is brought
into a safe state if the electric device fails.
Warning
DANGER!
The servo drive controller and in particular the braking resistance, external or internal, can become very hot. This can cause serious burning if the devices are touched.
Warning
Dangerous voltage
High electric voltage!
Danger of death or serious bodily injury due to electric shock!
2.4.3 Protection aganst touching electric components
This section concerns only devices and drive components with voltages over 50 V. It is dangerous to touch components with voltages of more than 50 V, as this can cause an electric shock. When electric devices are operated, certain components in these devices are always under dangerous tension.
For operation the relevant DIN, VDE, EN und IEC regulations, as well as all national and local safety and accident prevention regulations must always be observed. The system manufacturer or the user is responsible for ensuring that these regulations are observed.
14 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
2. Safety instructions for electric drives and controllers
Warning
Before switching the device on, fit the covers and protective
screens so that the device cannot be touched. For devices which are to be fitted in a control cabinet, make sure that a housing is fitted so that the electric components cannot be touched.
Regulation VGB4 must be observed.
Warning
Always connect the protective earth conductor of the electrical
equipment and the devices firmly to the supply network. Due to the integrated network filter the leakage current is greater
than 3.5 mA.
Warning
Note the minimum copper cross section for the protective conductor during the complete sequence in accordance with standard EN 60617.
Warning
Before commissioning, also for brief measuring and test pur-
poses, always connect the protective conductor to all electric
devices or connect to an earth cable in accordance with the
connection diagram. Otherwise, high voltages may occur on the housing. These could
cause an electric shock.
Warning
Do not touch the electrical connection points of the components when the device is switched on.
Warning
Before touching electric components with voltages over 50 V,
disconnect the device from the mains or voltage source.
Protect the device against being switched on again.
Warning
During installation note the amount of intermediate circuit
voltage, especially with regard to insulation and protective
measures. Make sure that the earthing, the cross section size of the conductor and the corresponding short-circuit protection are correct.
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 15
2. Safety instructions for electric drives and controllers
Warning
The device has an intermediate fast discharge circuit in accordance with EN 60204, section 6.2.4. In certain device constellations, par­ticularly where several motor controllers are switched parallel in the intermediate circuit or with a non-connected braking resistance, the fast discharge may not have any effect. The motor controllers can stand under dangerous tension for up to 1 minute after being switched off (capacitor residual charge).
Warning
DANGER!
High electric voltage due to incorrect connection.
Danger of bodily injury or death due to electric shock!
2.4.4 Protection by low voltage (PELV) against electric shock
Voltages from 5 to 50 V on the connections and terminals of the motor controller are protective small voltages which can be touched without danger in accordance with the following standards:
- International: IEC 60364-4-41
- European countries in the EU: EN 50178/1998, section 5.2.8.1
Devices, electrical components and cables may only be connected to connections and terminals from 0 to 50 V, providing they have a protective low voltage (PELV = Protective Extra Low Voltage).
Connect only voltages and current circuits which have reliable separation of dangerous voltages.
Such separation is achieved e.g. with isolating transformers, reliable optocouplers or battery operation separate from the mains network.
2.4.5 Protection from dangerous movements
Dangerous movements can be caused by incorrect control of connected motors. There are various causes:
- Unsafe or faulty circuitry or cabling
- Faults in operating the components
- Faults in the measured value and signal generators
- Defective or non-EMC valid components
- Faults in the software in the higher-order control system
These faults can occur immediately after the device is switched on or after a certain period of operation.
16 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
2. Safety instructions for electric drives and controllers
Warning
DANGER!
Dangerous movements.
Danger of injury or death, serious bodily injury or material damage.
Warning
DANGER!
Surfaces of the device housing may be hot.
Danger of injury. Danger of burning.
Warning
Danger of burning.
Do not touch the surface of the housing in the vicinity of hot
sources.
After switching devices off, leave them for 10 minutes to cool
down before touching them. If you touch hot parts of the device such as the housing which
contains the heat sink and resistors, you may burn yourself.
The monitoring functions in the drive components exclude to a large extent the possibility of incorrect operation of the connected drives. WIth regard to the protection of human beings, especially the danger of bodily injury and/or material damage, one must not rely on these circumstances alone. Until the fitted monitoring functions become effective, you must reckon with at least one incorrect drive movement, the extent of which depends on the type of control and on the operating state.
For the above-mentioned reasons, the protection of human beings must be ensured with the aid of monitoring systems or by measures which are of higher order than the system. These measures are foreseen depending on the specific features of a danger and fault analysis by the system manufacturer. The safety regulations applicable to the system must be observed here as well. Undesired movements of the machine or other incorrect func­tions can occur as a result of switching off, avoiding or failing to activate safety devices.
2.4.6 Protection aganst touching hot components
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 17
2. Safety instructions for electric drives and controllers
Warning
DANGER!
Danger of injury as a result of incorrect handling.
Bodily injury caused by squeezing, cutting, pushing.
Warning
Observe the general regulations on setting up and safety when
handling and assembling.
Use suitable assembly and transport devices. Prevent clamping and squashing (of fingers). Use only suitable tools. If specified, use special tools. Use lifting devices and tools in a correct manner. If necessary, use suitable protective equipment
(e.g. protective glasses, safety shoes, safety gloves).
Do not stand under hanging loads. Wipe up spilt liquids on the floor to avoid slipping.
2.4.7 Protection when handling and assembling
Handling and assembling certain components in an unsuitable manner can under circumstances cause injury.
The following safety measures apply here:
18 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
3. Assembly and installation
1 Two DIP switches
2 9-pin sub-D socket
3 LED for the bus readiness message
2
1
3
3. Assembly and installation
The PROFIBUS interface is implemented in the device family CMMP by an optional interface module CAMC-PB.
The PROFIBUS bus connection is designed as a 9-pin sub-D socket on the CAMC-PB as per EN 50170.
3.1 Connecting and display elements
The following elements can be found on the front plate of the CAMC-PB.
- a green LED for the bus readiness message
- a 9-pin sub-D socket
- two DIP switches for actuating the terminating resistors.
Fig. 3.1: Connecting and display elements on the PROFIBUS-DP interface
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 19
3. Assembly and installation
Caution
The motor controller must be disconnected from all current carrying cables before an additional module is fitted. After switching off the operating voltage, you must wait 1 minute before the capacitors in the motor controller are fully discharged.
Caution
Make sure that measures for ESD protection are taken when handling the additional module.
1 Front cover
1
3.2 Assembly
Use a suitable screwdriver to remove the front cover over the module shaft of the motor controller (Fig. 3/2). The additional module is now placed in the open module shaft so that the printed circuit board slides into the guides on the sides of the module shaft (Fig. 3.3). Push the board in as far as possible. The front plate of the additional modue is then screwed to the motor controller housing with a Philips screw. Make sure that the front plate fits flush with the front in order that it has conductive contact with the housing.
Fig. 3.2: Unscrew front cover
20 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
3. Assembly and installation
1 PROFIBUS
interface
2 Module shaft
Warning
PROFIBUS® cabling
Due to the possibly very high baud rates, we recommend also the use of the standardized cable and plug connector. These are in some cases provided with additional diagnostic possibilities and in the event of a fault they facilitate the fast analysis of the field bus hardware.
When setting up the PROFIBUS network, you must follow the advice in the relevant literature or the folllowing information and instructions in order to maintain a stable, faultless system. If the cabling is not correct, faults may occur on the PROFIBUS which cause the motor controller to switch off with a fault for safety reasons.
2
Fig. 3.3: Insert PROFIBUS interface
3.3 Installation
On the CMMP motor contrllers the PROFIBUS interface has been designed in the form of an optional additional module.
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 21
3. Assembly and installation
Pin no.
Name
Value
Type
1
Screen
-
Cable screening/shield
6
+5V
+5 V
+5 V – output (potential isolated) 1)
2
-
-
not assigned
7
-
-
not assigned
3
RxD / TxD-P
Received / transmitted data B cable
8
RxD / TxD-N
Received / transmitted data A cable
4
RTS / LWL
Request to Send
2)
9
-
-
not assigned
5
GND5V
0 V
Reference potential GND 5V 1)
1)
Use for external bus termination or for suppling transmitter/receiver of an external LWL module.
2)
Signal is optional, serves for direction control when used with an external LWL module.
GND 5V
RTS/LWL
B-cable (RxD/TxD-P)
n.c.
Screen
n.c. A-cable (RxD/TxD-N) n.c. +5 V
3.3.1 Pin assignment of PROFIBUS interface
Fig. 3.4: PROFIBUS module - pin assignment
Tab. 3.1: Connector pin assignment: PROFIBUS-DP interface
22 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
3. Assembly and installation
An incorrect bus termination is often the cause of a fault.
390 ohms 390 ohms
220 ohms
B-cable A-cable
GND 5
+5 V
3.3.2 Termination and bus terminating resistors
Each bus segment of a PROFIBUS network must be fitted with terminating resistors in order to minimize cable reflexions and to set a defined rest potential on the cable. The bus termination is made at the beginning and end of a bus segment.
The terminating resistors are already provided on most commercially-available PROFIBUS plug connectors. The PROFIBUS-DP interface has its own terminating resistors for coupling to buses without terminating resistors. These can be switched via the two DIP switches on the module (both switches to ON). I
n order that the terminating resistors can be switched off,
In order that th enetwork can be operated reliably, only one bus termination must be used, internal (via DIP switch) or external.
both
switches must be set to OFF.
The external circuitry can also be set up discretely (see Fig. 3.5). The 5 V supply voltage required for the externally switched terminating resistors is provided at the PROFIBUS plug of the PROFIBUS-DP interface (see pin assignment in the Tab. 3.1).
Fig. 3.5: Bus termination
If the set baud rate is greater than 1.5 MBaud, plugs with integrated series inductance (110 nH) must be used due to the capacitive load of the slave and the cable reflexion thereby created.
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 23
4. Configuration of the PROFIBUS module
4. Configuration of the PROFIBUS module
Several steps are required in order to produce a functioning PROFIBUS module. Some of these settings should or must be carried out before the PROFIBUS communication is activated. This chapter provides an overview of the relevant steps. The exact procedure is described in the following chapters in more detail.
When planning the PROFIBUS module, the user must make firm decisions. Only then should the parametrizing of the field bus connection on both sides be made. We recom­mend that the parametrizing of the slave be undertaken first. Then the master should be configured. With correct parametrizing the application is ready immediately without com­munication faults.
As some parameters are not effective until save and reset, we recommend the following procedure.
1. Setting the bus address in the FCT program in the window Operation Parameters.
2. Parametrizing and commissioning with the FCT. Especially also the setting physical
units.
3. Configuration of the PROFIBUS master.
For correct functioning it is necesary to define the physical units of the processing data transmitted via the field bus. These can be set via the FCT.
24 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
4. Configuration of the PROFIBUS module
Please note that the PROFIBUS communication can only be acti­vated when the parameter records have been saved and a Reset has been carried out.
4.1 Setting the slave address
The inserted PROFIBUS module will be recognized automatically when the motor controller is switched on.
Each device (PROFIBUS module) in the network must be assigned with a clear bus address. The bus address is set in the FCT program in the window Operation Parameters.
Permitted bus addresses are 3 … 125.
Addresses cannot be assigned by the master (the service Set_Slave_Address is not supported). Each address is only assigned once.
4.2 PROFIBUS communication
After configuration with subsequent download and saving, the PROFIBUS communication will be actuated with a reset. Please note that the above mentioned parameters can only be modified when the protocol is deactivated. All parameters are only valid when the PROFIBUS communication is deactivated and then re-activated.
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 25
4. Configuration of the PROFIBUS module
PROFIBUS configuration
Cyclic I/O update
Acyclic data
PROFIBUS
2 modules for selection:
Module 1: Name = "FHPP standard"
Identifier = 0xB7 (8 bytes I/O consistent)
-
Module 2: Name = "FHPP standard + FPC"
Identifier = 0xB7, 0xB7
(2 x 8 bytes I/O consistent)
Note on commissioning with the Festo Configuration Tool can be found in the help to the device-specific FCT PlugIn.
4.3 PROFIBUS configuration
Tab. 4.1: PROFIBUS configuration
4.4 PROFIBUS slave configuration
This section provides an overview of the steps required by the slave for parametrization and configuration. As some parameters are only effective after saving and reset, we recommend that commissioning with the FCT without connection to the PROFIBUS be carried out first.
Important processing data for position, velocity and acceleration are transferred in physical units. These should be parametrized before starting communication because they determine how the data are to be interpreted in the motor controller.
4.5 PROFIBUS master configuration
This section provides an overview of the steps required by the master for parametrization and configuration. We recommend the following procedure:
1. Installing the GSD file
2. Slave address
3. Configuration of the input and output data
On the part of the master, the motor controller must be incorporated in the PROFIBUS. First the GSD file is installed if this has not already been done. Finally, the address and the input and output data for the slave must be configured.
In order to make commisssioning fast and simple, the abilities of the PROFIBUS interface of the motor controller are described in an EDS file. By using a suitable configuration tool you can configure a device within a network. The EDS is contained on the CD supplied with the product. The latest version can be downloaded from our home page (www.festo.com ­Automation - Download Area - Download Software - Product group "Electric drives").
26 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
4. Configuration of the PROFIBUS module
GSD file
Description
P-AS0B06.gsd
Motor controller CMMP-AS
Normal operating status
Diagnostic case
Special operating status
cmmpas_n.bmp
cmmpas_d.bmp
cmmpas_s.bmp
Tab. 4.2: GSD file
Use the following icon files in order to represent the motor controller CMMP-AS in your configuration software (e.g. SIEMENS SIMATIK S7).
Tab. 4.3: Bitmaps CMMP-AS
This is shown below as an example of incorporating under SIEMENS SIMATIC S7.
4.5.1 Configuration with SIMATIC manager
The software package SIMATIC Manager serves for project planning and commissioning in conjunction with PROFIBUS masters from Siemens or compatible masters.
In order that the motor controller can be incorporated in the PROFIBUS network, it must be selected in the hardware catalogue (HW Config) –SIMATIC…). The motor controller CMMP can be found under "PROFIBUS-DP\Additional Field Devices \Drives\Festo").
1. Pull the station type "Festo CMMP" by drag and drop onto the PROFIBUS-DP master
system.
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 27
4. Configuration of the PROFIBUS module
Configuration
I/O range
Description
Universal module
If step 7 is shown, do not use
FHPP standard
8 bytes of I/O data, consistent transmission
Cyclic transmitted 8-byte control and status data.
FHPP standard + FPC
2 x 8 bytes of I/O data, consistent transmission
As FHPP standard, additional 8 bytes I/O data for parametrizing
Fig. 4.1: Hardware configuration
2. Enter the PROFIBUS address in the dialogue window "Properties - PROFIBUS inter-
face…" and confirm with OK.
The bitmap of the motor controller will be shown on the master system and must be selected.
3. Then the length of the input and output data must be defined. Pull the desired
configuration (with the mouse button) into the appropriate line under Module/ DP identifier. The following modules are contained in the GSD:
Tab. 4.4: Configuration
The I/O addresses can be defined with a double click on the location.
28 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
4. Configuration of the PROFIBUS module
Fig. 4.2: PROFIBUS module - address assignment
4. When the configuration is concluded, transfer the data to the master.
Control and parametrizing methods and the functioning of the parametrizing can be found in manual CMMP-AS-PB-S7-EN.
System functions used
An example of a project and the documentation CMMP-AS-PB-S7 can be found on the CD.
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 29
5. Diagnosis
LED is
Status
Shows:
Off
No bus communication
No communication via PROFIBUS.
green
Bus communication active
Fault message
Meaning of fault message
Measure
Main index
Sub­index
22
0
PROFIBUS: faulty initialization
Technology module defective? Please contact technical support.
1
PROFIBUS: reserved
2 PROFIBUS communication fault
Check set slave address Check bus connection Check cables
3 PROFIBUS: invalid slave address
Communication has been started with slave address 126. Select a different slave address.
4 PROFIBUS: fault in value range
Mathematical fault in the calculation of the physical units. Value range of the data and the physical units are not suited together. Contact technical support
5. Diagnosis
5.1 Network status LED
The network status LED shows the communication status.
Tab. 5.1: Status LED
5.2 PROFIBUS error codes
The following faults can occur if the PROFIBUS module is used: A complete list can be found in the System Manual for the controller.
Tab. 5.2: PROFIBUS error codes
The following faults concern FHPP, but can also occur if the PROFIBUS module is used: Please refer to the FHPP manual for detailed information.
30 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
5. Diagnosis
Code
Name
Description
Activity
70-1
FHPP: Maths error
Overrun/underrun or division by zero during calculation of cyclic data.
Check the cyclic data and/or check the factor group.
70-2
FHPP: Factor Group invalid
Calculation of the factor group leads to invalid internal values.
Check the factor group.
70-3
FHPP: Operation mode change failure
Changing from the current to the desired operating mode is not permitted.
Check your application. It may be that not every change is permitted.
Tab. 5.3: FHPP error codes
Fault messages can be quitted with:
- the parametrizing interface
- via the field bus (control word),
- a falling edge at DIN5 (controller enable).
Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH 31
A. Technical specifications
Range
Values
Storage temperature range
-25 +75 °C
Operating temperature range / deratings
0 +50 °C
Air humidity
0 ... 90 % non-condensing
Installation height
up to 1000 m above sea level
Dimensions (LxWxH):
approx. 92 x 65 x 19 mm suitable for the technology shaft
Weight
approx. 50 g
Range
Values
Communication interface
PROFIBUS module
Controller
PROFIBUS controller VPC3+, max. 12 MBaud
Baud rates supported (auto baud rate)
9.6 kBaud
19.2 kBaud
45.45 kBaud
93.75 kBaud
187.5 kBaud
500.0 kBaud
1.5 MBaud
3.0 MBaud
6.0 MBaud
12.0 MBaud
Protocol
PROFIBUS-DP
Interface
Potential-isolated, D-SUB 9-pin, integrated switchable bus terminating resistors
Special functions
Supports diagnostic data, RTS signal, no fail-safe mode, no Sync/Freeze
A. Technical specifications
General technical specifications see System manual for the controller used.
Tab. A.1: Technical specifications of environment
Tab. A.2: PROFIBUS technical specifications module
32 Festo P.BE-CMMS-FHPP-PB-SW-EN en 0708NH
Loading...