28
If there are no active user alarms, the “EMPTY” string is displayed for 2 seconds.
Alarms shown on display Components involved Alarm effect Cause of alarm
high temperature water evaporator
evaporator water inlet probe
Stop compressor and fan
The pump stays on
Values outside limit
evaporator 1 antifreeze evaporator water outlet probe
circuit 1 high press auto/man circuit 1 high press transducer
Stop compressor and fan
The evaporator pump stays on
Stop condenser pump
-Values outside limit
circuit 2 high press auto/man circuit 2 high press transducer
Circuit 1 low pressure circuit 1 low press transducer
Circuit 2 low pressure circuit 2 low press transducer
compressor 1 thermal protection
Compressor electronic protector
Discharge pipe compressor switch (if installed)
-current value outside limit
-electronic thermal protector
damaged
compressor 2 thermal protection
compressor 1A thermal protection
compressor 1B thermal protection
compressor 1C thermal protection
compressor 2A thermal protection
compressor 2B thermal protection
compressor 2C thermal protection
Compressor 1 discharge temp Discharge pipe compressor 1 sensor
- Values outside limit
Compressor 2 discharge temp Discharge pipe compressor 2 sensor
evaporator pump A unavailable
evaporator pump A Stop evaporator pump A
-Pump not available from the controller
evaporator pump B unavailable
evaporator pump B Stop evaporator pump B
evaporator pump A thermal protection
evaporator pump A Stop evaporator pump A
-current value outside limit
evaporator pump B thermal protection
evaporator pump B Stop evaporator pump B
evaporator water flow
evaporator 1 water flow
evaporator water differential pressure
switch and/or flowswitch.
Stop unit with only 1 pump present.
Swap to the other pump if two
pump are present If the alarm
persist, stop the unit.
-no water circulation or insufficent
water flow rate
-defective sensors switch not correct
fans 1 thermal protections thermal protection Fans 1
Stop compressor and fan
The evaporator pump stays on
-current value outside limit
fans 2 thermal protections thermal protection Fans 2
Heat recovery pump A thermal protections
Heat recovery pump A Stop heat recovery pump A
-current value outside limit
Heat recovery pump B thermal protections
Heat recovery pump B Stop heat recovery pump B
heat recovery pump A unavailable
Heat recovery pump A Stop heat recovery pump A
-Pump not available from the controller
heat recovery pump B unavailable
Heat recovery pump B Stop heat recovery pump B
heat recovery water flow
differential pressure switch and/or flow
switch, recovery water heat exchanger
immediate exit
from recovery mode
-no water circulation or insufficent
water flow rate
-defective sensors switch not correct
Circuit 1 EEV alarm electronic expansion valv 1 error
Stop compressor and fan
The pump stays on
- value outside limit
Circuit 2 EEV alarm electronic expansion valv 2 error
Immediate stop chiller
Electrical panel temperature switch
(high temperature version)
Stop the unit
- too high temperature inside the
electrical panel
- electrical panel fans damaged
- fans filters dirty
(high temperature version)
User alarms table
USER ALARMS
They are only manual reset alarms and concern solely the machine’s components (compressors, fans, pumps, sensors, pressure switches, etc.) and do not involve the HW and SW operation of the micro-controller.
in order to restart the system it is necessary:
- removing the cause of alarm
- to reset manually the alarm from the alarm submenu
MONITORING SYSTEM - Alarms