Ferroli Installation And Maintenance Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
INSTALLATION AND
MAINTENANCE INSTRUCTIONS
Appr. nr. A 9503 A - 0085 AQ 0765
PEGASUS F2
GAS-FIRED CAST-IRON BOILERS
WITH ELECTRONIC IGNITION
AND FLAME RECTIFICATION MONITORING
Models 51 - 68 - 85 - 102
cod. 3540724/2 - 04/98
Pegasus F2
2
Contents
1. General technical data
2. Dimensions and technical data
3. Installation
4. Wiring diagrams
5. Startup and shutdown
6. Gas regulation
7. Conversion
8. Maintenance and cleaning
9. Fault finding
Pegasus F2
3
1. GENERAL TECHNICAL DATA
1.01 Introduction
The Pegasus F2, with CE approval, is designed for use with natural gas (G20) or LPG (G31) for indirect
central heating and hot water.
1.02 Installation requirements
Only CORGI registered installers should fit the Pegasus boilers.
The boiler installation should comply with relevant British Standards Specifications, codes of practice,
and Current Building Regulations, together with any special Regional Requirements of the Local
Authorities, gas supplier and Insurance Companies.
The standard cast-iron PEGASUS F2 boiler is set to operate on natural gas (G20).
The boiler is designed to operate with a flow temperature of 82°C and a maximum ∆t of 20°C.
Pegasus F2 51
Pegasus F2 68
Table 1
Pegasus F2 85
Pegasus F2 102
Pegasus F2 51
Pegasus F2 68
Table 2
Pegasus F2 85
Pegasus F2 102
Pegasus F2 51
Pegasus F2 68
Table 3
Pegasus F2 85
Pegasus F2 102
MODEL
MODEL
MODEL
A
mm
550
640
720
800
No.
OF MAIN
BURNERS
3
4
5
6
NUMBER OF
SECTIONS
4
5
6
7
HEAT
OUTPUT
kW
51
68
85
102
DIMENSIONSCONNECTIONS
B
C
D
E
mm
96,5
96,5
106,5
106,5
PRINCIPALES
INJECTORS
Ø mm
Nat. G20
3,5
3,5
3,5
3,5
Ø mm
180
180
200
200
G.P.L. G31
2,15
2,15
2,15
2,15
mm
43
46
44
42
Nat. G20
mm
35
38
36
34
PILOT
INJECTORS
Ø mm
G.P.L. G31
0,4
0,4
0,4
0,4
RETURN
0,24
0,24
0,24
0,24
a1 Ø
1 1/2"
1 1/2"
1 1/2"
1 1/2"
FLOW
a2 Ø
1 1/2"
1 1/2"
1 1/2"
1 1/2"
GAS SUPPLY
PRESSURE
(mbars)
Nat. G20
15 to 23
15 to 23
15 to 23
15 to 23
HEAT INPUT
(NETT)
kW
56
74,8
93,5
112
GAS
a3 Ø
3/4"
3/4"
3/4"
3/4"
LPG G31
37
37
37
37
WEIGHT
INCLUDING
PACKAGE
CONTENT
Kg.
260
300
350
400
GAS PRESS. AT
BURNER MANIFOLD
(mbars)
LPG G31
Nat. G20
36
13,3
36
13,3
36
13,3
36
13,3
HEAT INPUT
(GROSS)
kW
62,2
83
103,8
124,3
WATER
(liter)
22
26
30
34
GAS FLOW RATE
Nat. G20
m
5,9
7,9
9,9
11,8
MAX
OPERATING
PRESSURE
(bars)
3
/h
4
4
4
4
LPG G31
kg/h
4,34
5,79
7,24
8,68
Pegasus F2
5
2.03 Main components
Front view of the boiler without front casing
14
10
15
11
13
12
4
6 3
Fig. 2a
5
816
75
9
12
Key
1. Temperature-pressure gauge
2. Boiler control thermostat
3. Ignition lockout re-set botton
4. Boiler on/off switch
5. Flue gas safety thermostat
6. Limit thermostat reset botton
7. Ignition PCB
8. Electronic panel (not available UK)
6
6
4
2
1
Control panel
Fig. 2b
9. Control panel
10. Gas valve
11. Pilot burner assembly
12. Gas burner manifold
13. Gas pressure test point
14. Automatic air vent
15. Drain cock
16. Flue gas sampling point
Pegasus F2
9
8
7
3
2.04 Characteristic pressure drop curve
Water pressure drop in all models is shown in fig.
3. The following diagram shows the pressure drop
in the boiler as a function of the water flow rate.
∆P mbar
200
100
90
80
70
60
50
40
30
20
4 EL.
5 EL.
6 EL.
7 EL.
Fig. 3
10
12345678910
Flow rate
2.05 Safe discharge of combustion products
The boiler comes with a FLUE GAS SAFETY THERMOSTAT, which provides a high level of safety and
control over the discharge of combustion products. This thermostat cuts off the supply of gas to the
burner in the event of a faulty flue draft.
If the FLUE GAS SAFETY THERMOSTAT has been activated, you should unscrew the protection cover
(part no. 5 in fig. 2a and 2b) and manually
“reset” the thermostat. After that, the boiler
will return to normal operation.
Boiler rear view
If the FLUE GAS SAFETY THERMOSTAT
needs to be replaced, use original
manufacturer’s parts only and make sure
the electric connections and positioning of
the bulb (see fig. 4) are correct; NEVER
UNDER ANY CIRCUMSTANCES LEAVE
THE FLUE GAS SAFETY THERMOSTAT
DISCONNECTED FROM THE ELECTRIC
CIRCUIT.
In case of frequent tripping of the thermostatic switch, contact qualified personnel
only.
During cleaning of the draft diverter, be
careful not to damage the thermostat phial.
Flue gas safety
thermostat phial
Fig. 4
Pegasus F2
7
3. BOILER INSTALLATION
(To be performed by qualified personnel only)
3.01 General warnings
The boiler should be installed according to current regulations (see para 1.02).
We suggest fitting isolating valves between the boiler and the heating system to isolate the boiler from
the system if necessary.
The rise in temperature of the heating water (the difference between the water flow and return
temperatures) should not exceed 20°C. This is so as to prevent possible damage caused by
condensation forming in the boiler.
Combustion products should be discharged through a flue with a cross section in accordance with
current standards and not less than the boiler flue outlet connection.
Connect the gas to the boiler in accordance with current regulations. The diameter of the boiler gas
inlet gas pipe does not dictate the choice of diameter for the pipe between the boiler and the gas meter
should be calculated based upon its length and pressure drop.
3.02 Boiler water characteristics
When the water supply has a hardness of more than 25 - 30 Fr., it should be treated before entering
the heating system to prevent both scaling (caused by hard water) and corrosion (caused by aggressive
water) in the boiler. Please remember that because of their low thermal conductivity, even small scales
just a few millimetres thick cause the boiler walls to overheat considerably with serious consequences.
You must treat the water used for the heating system in the following cases:
A) Very large systems (with large volumes of water).
B) Systems where partial or complete draining - and water refilling - are frequent.
Pegasus F2
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.