ferroli Optimax HE Plus 18 OV User guide

Page 1
OPTIMAX HE PLUS 18 OV
wall-mounted gas fired, pre-mix condensing gas boiler
0
cod. 3540M164 - 02/2009 (Rev. 00)
INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE
Seasonal Efficiency
band A
G C N° 47-267-34
Page 2
OPTIMAX HE PLUS 18 OV
IMPORTANT
Your "benchmark" Installation, Commissioning and Service Record Log Book is enclosed in the
last pages of this manual. “This record must be completed and left with the end user”.
Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme.
Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency. Please see installation and servicing guidelines.
"Ferroli declare that no substances harmful to health are contained in the appliance or used
during the appliance manufacture”.
This symbol indicates “Caution” and is placed next to all safety information. Strictly follow these instructions in order to avoid danger and damage to persons, or property.
This symbols calls attention to a note or important information, please read thor­oughly.
• Read the warnings given in this manual thoroughly. They provide important information for safe instal­lation, use and maintenance
• By law the instruction manual must be left with the end user.
• If the appliance is sold or transferred to another owner or if the owner moves, leaving the appliance behind, always ensure that the manual is kept with the appliance for consultation by the new owner and /or installer.
• Incorrect installation or poor maintenance absolves the manufacturer from all liability for damage to people or property.
• Installation and maintenance must be carried out in conformity with current legislation, according to the manufacturer’s instructions and by qualified personnel.
• Before service or maintenance work is, carried out isolate the appliance from the mains electricity supply.
• In the event of malfunction or faulty operation, iso­late the appliance. Do not attempt to repair or carry out any other operation on the appliance directly. Contact qualified personnel only.
• Repairs or the replacement of components must be carried out exclusively by qualified personnel using original spare parts only. Failure to respect the above may compromise the safety of the appliance.
• To guarantee efficient operation, the appliance must be serviced once a year by a corgi registered engi­neer.
• The appliance may not be used for purposes other than those for which it was explicitly designed. Any other use is considered improper and therefore dan­gerous.
• Incorrect installation and use or failure to follow the instructions provided by the manufacturer absolve the manufacturer from all liability for damage.
• After unpacking, check that the contents are complete and undamaged.
• Keep the packaging out of reach of children as it is potentially hazardous.
• To clean external parts, use a damp cloth moistened with soapy water if necessary. Avoid using abrasive cleaning products and solvents.
2
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 3
OPTIMAX HE PLUS 18 OV
1. OPERATING INSTRUCTIONS .................................................................4
1.1 Introduction ............................................................................................................4
1.2 Control panel ..........................................................................................................5
1.3 Turning ON and OFF ..............................................................................................6
1.4 Adjustments ............................................................................................................7
1.5 Maintenance ............................................................................................................8
1.6 Faults .......................................................................................................................8
2. INSTALLATION .......................................................................................9
2.1 General Instructions ................................................................................................9
2.2 Boiler location .......................................................................................................10
2.3 Boiler water connections ......................................................................................11
2.4 Connection to the gas system ..............................................................................14
2.5 Electrical Connections ..........................................................................................14
2.6 Flue system ...........................................................................................................17
2.7 Condensate outlet connection .............................................................................23
3. SERVICE AND MAINTENANCE ............................................................25
3.1 Adjustments ..........................................................................................................25
3.2 System start-up .....................................................................................................26
3.3 Maintenance ..........................................................................................................27
3.4 Troubleshooting ....................................................................................................29
4. TECHNICAL CHARACTERISTICS AND DATA ..........................................................31
4.1 Dimensions and connections ................................................................................31
4.2 General view and main components ....................................................................32
4.3 Hydraulic diagram .................................................................................................33
4.4 Technical data table ..............................................................................................34
4.5 Wiring diagram .....................................................................................................35
BENCHMARK ...........................................................................................36
0
Cod. 3540M164 - 02/2009 (Rev. 00)
3
Page 4
OPTIMAX HE PLUS 18 OV
1. OPERATING INSTRUCTIONS
1.1 Introduction
Dear Customer, Thank you for choosing OPTIMAX HE PLUS 18 OV, a FERROLI wall-mounted boiler of the latest gene-
ration, featuring advanced design and cutting-edge technology. OPTIMAX HE PLUS 18 OV is a high-efficiency condensing pre-mix appliance for heating with extremely
low emissions, running on natural gas or LPG. The boiler consists of an aluminium laminar heat exchanger providing effective condensation of the
water vapour contained in the flue gases, permitting extremely high efficiency. Above the heat exchanger, in the boiler, there is a ceramic surface pre-mix burner, equipped with
electronic ignition and ionization flame control, which achieves extremely low emissions while ensuring high reliability and long life operation.
The boiler is totally room sealed from the installation room: the air needed for combustion is drawn from outside. The boiler also includes a modulating speed fan, modulating gas valve, safety valve, temperature sensors, a safety thermostat and a flue gas sensor.
Thanks to the twin microprocessor control and adjustment system with advanced self-diagnosis, unit operation is for the most part automatic. The power for heating is automatically governed by the control system.
The user only has to set the temperature desired inside the home (by means of a room thermostat and or regulate the temperature of the system). The adjustment and control system will provide optimum operation throughout the year.
The display continuously provides information on the unit’s operating status and it is easily possible to obtain additional information on the sensor temperatures, set-points, etc. or configure them. Any operating problems associated with the boiler or system is immediately signalled by the display and, if possible, corrected automatically.
4
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 5
OPTIMAX HE PLUS 18 OV
1.2 Control panel
8
11
12
21
436
15
comfort
1314
fig. 1
75
eco
reset
1 = Domestic Hot Water temperature setpoint decreasing push button (not used) 2 = Domestic Hot Water temperature setpoint increasing push button (not used) 3 = Central Heating water temperature setpoint decreasing push button 4 = Central Heating water temperature setpoint increasing push button 5 = Display LCD 6 = Reset 7 = On-Off push button
8 = Domestic Hot Water symbol 11 = Multi-function indication 12 = Degrees indication 13 = Central Heating mode operation 14 = Central Heating symbol 15 = Burner on and actual load indication
Indication during boiler operation
Demand mode
The Boiler heat demand (generated by the Programmer, room thermostat and cylinder thermostat) is indicated by the flashing of the Hot Air symbol over the radiator (part. 13 and 14 – fig. 1). The display (part. 11 – fig. 1) indicates the actual System water temperature and, during the delay time, the text “d2”.
eco
comfort
reset
fig. 2
eco
comfort
reset
Cod. 3540M164 - 02/2009 (Rev. 00)
5
Page 6
1.3 Turning ON and OFF
Without main power supply
fig. 3 - Boiler without main power supply
To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all water from the system.
OPTIMAX HE PLUS 18 OV
eco
comfort
reset
Ignition
Ensure the power is on to the appliance.
eco
comfort
reset
fig. 4 - Ignition
For the first 120 seconds, the display shows FH that identifies the Air purge function.
• During the first 5 seconds, the display shows the software version of the pcb.
• Open the gas cock on the boiler and purge the air from the pipework upstream of the gas valve.
• When the FH disappears, the boiler is ready to function automatically whenever the external controls
eco
comfort
reset
fig. 5 - Air purge
are calling for heat.
Turning off
Press the (part. 7 - fig. 1) for 5 seconds.
eco
comfort
reset
fig. 6 - Turning off
6
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 7
OPTIMAX HE PLUS 18 OV
When the boiler is turned off with this key, the p.c.b is still powered, heating operation is disabled and the display is off however the frost protection will still be active.
To totally isolate close the gas cock ahead of the boiler and disconnect electrical power.
To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all water from the system.
To turn the boiler on again, press (part.7 - fig.1) for 5 seconds.
eco
comfort
reset
fig. 7
The boiler is ready to function automatically whenever the external controls are calling for heat.
1.4 Adjustments
Heating temperature setting
To set the system flow temperature, use the CH push buttons (Part. 3 and 4 – fig. 1). It can be varied from a minimum of 20°C to a maximum of 90°C.
eco
comfort
reset
fig. 8
Room temperature adjustment (using a room thermostat )
Using the room thermostat, set the temperature desired in the rooms. Controlled by the room ther­mostat, the boiler lights and heats the system water to the system delivery setpoint temperature. The burner shuts down when the desired temperature in the room is reached.
A room thermostat and programmer are a mandatory requirement (Building regulations Doc ‘L’
2002).
Cod. 3540M164 - 02/2009 (Rev. 00)
7
Page 8
OPTIMAX HE PLUS 18 OV
1.5 Maintenance
It is strongly recommended to carry out annual maintenance of the boiler and heating system. Please refer to the “maintenance” section in this manual.
The casing, the control panel and the aesthetic parts of the boiler can be cleaned using a soft and damp cloth, do not use abrasives or solvents.
1.6 Faults
In the unlikely event of an operating problem, or component failure, the display flashes and a fault identification code appears.
The boiler is equipped with an advanced self-diagnosis system that signals any faults on the display. Some faults (“A“ indication) cause a boiler shutdown. In this case, operation must be reset manually by
pressing the Other faults (“F“ indication) cause temporary shutdowns that are automatically reset as soon as the
value causing the fault comes back within the boiler’s normal working range. Listed below are some anomalies that can be caused by simple, user-solvable problems. If the problem remains after two attempts at resetting, contact the Ferroli Service Centre. For other faults, refer to section 3.4 “Troubleshooting”.
reset
(Part. 6 – fig. 1) for 1 second.
Fault Cure
Make sure that the gas cocks ahead of the boiler and on the meter are open.
No burner ignition
Before calling a Ferroli service engineer, check that the problem is not due to there being no gas or electricity.
Press the RESET button (for 1 second). In case of repeated shutdowns, contact the Ferroli
Service Department.
8
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 9
OPTIMAX HE PLUS 18 OV
2. INSTALLATION
2.1 General Instructions
This device must only be used for the purpose for which it is specially designed. This unit is designed to heat water to a temperature below boiling point and must be connected to a heat­ing system and/or a water supply system for domestic use, compatible with its performance, characteristics and its heating capacity. Any other use is considered improper.
BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE RECOMENDATION OF BS STANDARDS, ANY LOCAL REGULATIONS AND THE RULES OF COMPETENT WORKMANSHIP.
Incorrect installation can cause damage or physical injury for which the manufacturer declines any re­sponsibility.
This appliance must be installed strictly in accordance with these instructions and regulations:
The Gas Safety Regulations (Installations & Use). The Local Building Regulations. The Building Regulations (Part L). The Buildings Standards (Scotland - Consolidated) Regulations. British Standards Codes of Practice: B.S. 5440 Part 1 Flues B.S. 5440 Part 2 Air supply B.S. 5449 FORCED CIRCULATION HOT WATER SYSTEMS B.S. 6798 INSTALLATION OF GAS FIRED HOT WATER BOILERS B.S. 6891 GAS INSTALLATIONS B.S. 7671 IEE WIRING REGULATIONS B.S. 4814 SPECIFICATION FOR EXPANSION VESSELS B.S. 5482 INSTALLATION OF LPG B.S. 7593 TREATMENT OF WATER IN DOMESTIC HOT WATER CENTRAL HEATING SYSTEMS B.S. 5546 INSTALLATION OF HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
Model Water Bye Laws B.S. 5955-8 PLASTIC PIPEWORK INSTALLATION
For Northern Ireland the rules in force apply
Cod. 3540M164 - 02/2009 (Rev. 00)
9
Page 10
2.2 Boiler location
The unit’s combustion chamber is sealed off from the installation room and therefore requi­res no compartment ventilation.
The installation room must be sufficiently well ventilated to prevent any dangerous condi­tions from forming in the event of even slight gas leakage. This safety standard is required by the EEC Directive no. 90/396 for all gas units, including those with a so-called sealed chamber.
Therefore the place of installation must be free of dust, flammable materials or objects or corrosive gases. The room must be dry and not subject to freezing.
The boiler is designed to be installed on a solid wall. The wall fixing must ensure a stable and effective support for the appliance, using the bracket and fixings supplied.
If the unit is enclosed in a cupboard or moun­ted alongside, there must be space for normal maintenance work. Fig. 9 and tab. 1 give the minimum clearances to leave around the unit.
OPTIMAX HE PLUS 18 OV
C
A A
B
D
fig. 9
Table 1
Minimum
A
2,5 cm
B
20 cm
C 30 cm
60 cm
D
(via an openable panel)
Safe Handling of Substances
Care should be taken when handling the boiler insulation panels, which can cause irritation to the skin. No asbestos, mercury or CFCs are included in any part of the boiler.
Product Handling Advice
When handling or lifting always use safe techniques - keep your back straight, bend your knees, don’t twist - move your feet, avoid bending forwards and sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley. Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the
centre of gravity, repositioning yourself as necessary.
10
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 11
OPTIMAX HE PLUS 18 OV
2.3 Boiler water connections
The heating capacity of the unit should be previously established by calculating the building’s heat requirement according to current regu­lations. For good operation and long life of the boiler, the plumbing system must be well proportioned and always complete with all those accessories that guarantee regular operation and running, room ther­mostat, trv’s etc. The flow and return must be a minimum diameter of 22mm for the first 3 metres from the appliance.
If the flow and return pipes follow a path where air pockets could form in certain places, it is essential to install vent valves at these points. Also, install type “A” drain cock device at the lowest points in the system to allow complete draining.
The temperature differential between the flow manifold and the return to the boiler should not exceed 20° C.
A minimum flow of 6 litres/min is required through the heat exchan­ger, calibrated on site. An automatic by-pass must be fitted to the system.
Do not use the water system pipes to earth electrical applian­ces.
Before installation, carefully flush all the pipes of the heating system to remove residues or impurities that could affect the unit’s operation (BS 7593 Building regs Doc L).
205
145
1 5
77
104
320
45 25
35
45
50
Make the connections to the appliance as shown in fig. 10.
Key
1 System flow (22 mm compression union) 3 Gas inlet (22 mm with isolation valve fitted) 5 System return - 22 mm compression union)
fig. 10
Make the boiler connection in such a way that its internal pipes are free of stress.
192
3
137
128
Cod. 3540M164 - 02/2009 (Rev. 00)
11
Page 12
OPTIMAX HE PLUS 18 OV
The connecting kits shown in fig. 4 are supplied as standard.
A
22
mm
X2
Key
A = Nut B = Compression olive C = Nipple F = 1/2 gas seal - Blue
ACBB
Flow
Return
fig. 11
F
AB
22
mm
X1
Gas isolation valve
Make Up Water
This appliance is designed to work on an open vented fully pumped heating system only, (see fig 12 page
13). The make up of water must be made via a suitably sized cold feed and expansion tank installed to
the current regulations. This appliance is not suitable for gravity type installations or primatic type cylinders only indirect ones
should be used. The system must be fully pumped due to the complex design of the Aluminium Laminar heat exchang-
ers high efficiency design. Attention - is drawn to the Model Water Byelaws. Fittings manufactured from duplex (alpha-beta) brass are not acceptable for underground use and certain
water undertakings will not accept their use above ground.
12
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 13
OPTIMAX HE PLUS 18 OV
Schematic layout for fully pumped heating and hot water. (Close couple)
Static Head
min. 2 m
500 mm
22 mm
45°
15 mm
Open Vent
Motorised valve 22 mm DHW
Balancing
valve
Open Vent
Indirect cylinder
Indirect coil missing
Isolating
valve
To DHW taps
Isolating valve
Drain
Motorised valve 22 mm CH
Radiator Radiator
Flow
150 mm
Return
max.
CH Pump
Automatic By-pass
Fig. 12
Cod. 3540M164 - 02/2009 (Rev. 00)
13
Page 14
OPTIMAX HE PLUS 18 OV
Water treatment
If treatment is used ferroli limited recommended only the use of Fernox or Sentinel water treatment products, which must be used in accordance with the manufactures instructions. for further information
contact: Fernox Manufacturing Co. LTD. Sentinel Performance Solutions Ltd Cookson Electronics, Forsyth Road The Heath Business & Technical Park Sheerwater, Woking, surrey, GU21 5RZ Runcorn, Cheshire WA7 4QX Tel: 0870 8700362 Tel: 01928 588331
Note - If the boiler is installed on an existing system any unsuitable additives must be removed by tho-
rough cleansing. All systems should be cleansed according to B.S. 7593.
Note - In hard water areas treatment to prevent lime scale may be necessary.
Note - It is important that the correct concentration of the water treatment product is maintained in
accordance with the manufacturers instructions.
2.4 Connection to the gas system
If necessary the local Gas supplier should be consulted, at the installation planning stage, in order to
establish the availability of an adequate supply of gas.
An existing service pipe must not be used without prior consultation with the local Gas supplier.
A gas meter can only be connected by the Local Gas supplier, or by a Local Gas suppliers Contractor.
Installation pipes should be fitted in accordance with BS6891.
Appliance inlet working pressure must be 20mbar MINIMUM, for NG and 37 mbar minimum for LPG.
Do not use pipes of a smaller size than the boiler inlet gas connection (22 mm).
The complete installation must be tested for gas soundness and purged as described in BS689. All pipework must be adquately supported. An isolating gas valve is provided and should be fitted on the boiler gas inlet. Please wait 10 minutes when lighting from cold before checking gas rate. Gas pressures should be checked after the boiler has operated for 10 minutes to reach thermal equilibrium. This appliance has no facility to check the burner pressure and the gas valve is sealed and should not be adjusted. A combustion test can be carried out (see page 28 combustion analyser testing).
The isolation kit shown in Fig. 11 is supplied as standard.
2.5 Electrical Connections
The unit must be installed in conformity with current national and local regulations.
Connection to the electrical Supply
The boiler must be connected to a single-phase, 230 Volt-50 Hz electric supply.
The unit’s electrical safety is only guaranteed when correctly connected to an efficient earthing system executed according to current safety standards. Have the efficiency and suitability of the earthing system checked by professionally qualified personnel. The manufacturer is not responsible for any damage caused by failure to earth the system. Also make sure that the electrical system is adequate for the maximum power absorbed by the unit, as specified on the boiler dataplate, in particular ensuring that the cross sectional area of the system’s cables is suitable for the power
absorbed by the unit. The boiler is prewired and provided with a cable and fitted with a 3 amp plug for connection to the electricity supply.
14
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 15
OPTIMAX HE PLUS 18 OV
The user must never change the unit’s power cable. If the cable gets damaged, switch off the unit and have it changed only by professionally qualified personnel. If changing the electric power cable, use only “HAR H05 VV-F” 3x0.75 mm2 cable with a maximum outside diameter of 8 mm.
Access to the electrical terminal block
Follow the instructions given in fig. 13 to access the electrical connection terminal block. The layout of the terminals for the various connections is given in the wiring diagram in the Technical Data chapter.
Key
62 Time Clock (optional)
Room thermostat
Remove connections 5 - 6 if external control fitted. If using external controls the switched line can be connected into terminal 5 of the electrical block ( see fig 15 and 16 ).
fig. 13
Warning: the room thermo­stat works at 230V
fig. 14
Cod. 3540M164 - 02/2009 (Rev. 00)
15
Page 16
OPTIMAX HE PLUS 18 OV
Central heating Demand
The heat demand can be controlled by the room thermostat (terminal 5-6) or by a switch line 230 V (terminal 5).
Standard Systems
For a general pipe layout and wiring diagram on the “S” and “Y” plan systems please see fig.
15a, 15b, and 16a, 16b.
OPTIMAX “S” Plan
Pipe layout
OPTIMAX FERROLI
BOILER
A.A.V
A.A.V
Auto air vent
DHW zone valve
Balancing valve
Remove Link between terminals 5-6
PROGRAMMER
DHW ON
CH ON
NEUTRAL
LIVE
*Note: cold feed and expansion
not shown for clarity (see fig. 12)
Junction Box
5
4321
6
NEL
L
Terminal 5 - SWITCH LINE
Automatic
bypass
(mimimum flow of 6l/min.)
Wiring diagram
Pre-Fitted flex
Central heating
from boiler
L
N
E
pump
12345678910
C.H. Zone Valve
N E L
Fig. 15a
230 Vac
16
CH
zone
valve
DHW
zone
valve
BROWN BLUE
GREY ORANGE
Cod. 3540M164 - 02/2009 (Rev. 00)
Room Thermostat
Cylinder Thermostat
Fig. 15b
Page 17
OPTIMAX HE PLUS 18 OV
Optimax “Y” Plan
Pipe layout
OPTIMAX
FERROLI
BOILER
*Note: cold feed and expansion
not shown for clarity (see fig. 15)
A.A.V
A.A.V
Auto air vent
Automatic
bypass
(mimimum flow of 6LTR/min.)
Balancing valve
Junction Box
5
6
L
Remove Link
Terminal 5 - SWITCH LINE
between terminals 5-6
PROGRAMMER
NEUTRAL
LIVE
CH ON
DHW ON
DHW OFF
3 WAY ZONE VALVE
BLUE
WHITE
GREY
ORANGE
4321
NL
Wiring diagram
Pre-Fitted flex
from boiler
L
Central heating
pump
NE
12345678910
Honeywell V4073H mid position
Room Thermostat
Cylinder Thermostat
fig. 16a
N E
240 Vac
L
2
C
1
fig. 16b
2.6 Flue system
The unit is “type C” with a sealed chamber and forced draught, the air inlet and flue outlet must be connected to one of the following flue systems. With the aid of the tables and methods of calculation indi­cated, before commencing installation, it is first necessary to check that the flue system does not exceed the maximum permissible length. The current standards and local regulations must be observed.
It should be noted that only Ferroli flue system and accessories should be used on this appliance, as per BS 5440 2000 and C.E. test certification.
Cod. 3540M164 - 02/2009 (Rev. 00)
17
Page 18
OPTIMAX HE PLUS 18 OV
Connection with concentric flue system
The unit can be connected to a concentric air/flue duct with a Horizontal or Vertical outlet as shown on the following drawings. Numerous accessories are available on request to meet the various installation requirements. Please refer to our “flue manual” or the price list.
Standard concentric flue installation
Standard 041025G0 Flue kit
80
77
180
Rear Outlet
Side view
P
85
95
30
View from above
205
145
125
50*
S
Install level
Drill the wall 10÷20 mm more than the pipe diameter
* = between 10 e 60 mm
80
205
180 140
145
Side Outlet
30
95
Front view
L
DS
View from above
50*
* = between 10 e 60 mm
Install level
Drill the wall 10÷20 mm more than the pipe diameter
fig. 17a
30
Install level
85
S 50*
P
P = S + 155 mm
180 140
fig. 17b
95
D
S 50*
L
L = S + D + 130 mm
Install level
Horizontal flue installation
1. Define the position for installing the unit.
2. If using standard flue (041025G0) this must be installed level, for non-standard flue lengths over 1mtr
a fall of 3 mm per metre should be incorporated back to the boiler.
3.
Make a hole of diameter 10 - 20 mm greater than the nominal diameter of the concentric pipe used.
4. If necessary, cut the terminal length to size, ensuring that the external pipe protrudes from the wall
by between 10 and 60 mm (fig. 17a and 17b). Remove the cutting burrs.
5. Connect the flue to the boiler, positioning the seals correctly. Seal the flue into the wall with silicone
or sand + cement and cover with wall seals provided.
Flue seals should be lubricated with a silicone type grease to prevent damage (grease not sup­plied)
18
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 19
OPTIMAX HE PLUS 18 OV
Vertical Outlet
The total length in equivalent metres of the concentric flue must not exceed the maximum lengths stated in the following table, note that each bend gives rise to the stated reduction. For example, a duct = 60/100 composed of 1 bend of 90° +1 horizontal metre + 2 bends of 45° + 1 horizontal metre has a total equivalent length of 4 metres.
Vertical flueing
The installation of a concentric vertical flue can be carried out as follows, Install the appliance as previously mentioned in this manual.
1. Connect onto the flue assembly at the top of the appliance a concentric vertical adaptor part number 1KWMA71W,
2. Use the required amount of 1mtr flue extensions (part number 1KWMA56U) inserting them spigot down ensuring the seals are well lubricated with silicone grease (not supplied) and correctly located into the sockets.
3. If required 45° bends (Part number1KWMA64A) may be used with a resistance value of 0.5mtrs each, the flue should be routed in such away to avoid any unnecessary deviation and thus minimise the amount of bends required.
4. The termination should be made through our concentric flue outlet (part number 1KWMA83U) in conjunction with a roof slate pitched (part number 1KWMA82U) or flat roof (part number 1KWMA81U) The storm collar must be fixed on using the three screws provided and sealed with an external grade silicone (not supplied).
5. For longer flue lengths a 125mm concentric flue system is available.
6. All flue installations must comply with BS5440 part 1 and must only be of Fèrroli manufacture. The vertical flue must continually rise and be supported throughout its length. The flue must be inspected whilst commissioning the appliance to ensure it is sound throughout its length.
Vertical Terminal
1KWMA83U
Pitch roof slate
1KWMA82U
1KWMA56U
1000 125
50
950
50
10
max. 6 mt 60/100
max. 16 mt 80/125
This information is for guidance purposes and Fèr­roli will in no way be held responsible for incorrect installation following this guide.
Table 2a
Maximum permissible duct length (Horizontal)
Maximum permissible duct length (Vertical)
Table 2b
Reduction factors for bends
Ø mm
60/100
5 m 15 m
6 m 16 m
Ø mm 80/125
1 m
0,5 m
0,5 m
0,25 m
Cod. 3540M164 - 02/2009 (Rev. 00)
950
50
041002X0
50 950
120
fig. 17c
19
Page 20
OPTIMAX HE PLUS 18 OV
Connection with 80 mm pipe system
The unit can be connected to a system of separate air/flue pipes for a Horizontal or Vertical outlet as shown fig 18 - 19 . Numerous accessories are available on request to meet the various installation requirements. The components used most frequently are stated in tables 4 - 5. Please refer to the flue manual or the price list for additional components.
To check you do not exceed the maximum permissible flue length, it is necessary to make a simple calculation before installation:
Remove the closing cap
Ø80
Ø80
FLUE
AIR
041039X0
104
76
140
145
1. For each component, tables 4 - 5 provide an “equiva-
lent loss in linear metres”, depending on the position of installation of the component (with air intake or flue extraction, vertical or horizontal).
The loss is called “equivalent length” since it is compared
to the loss of one metre of flue (defined as equal to 1). For example, a bend at 90° of Ø80 in flue extraction has an equivalent loss of 2 linear metres, i.e. it has a loss equal to that of 2 linear metres of flue length.
2. After completely defining the layout of the system of split
flues, add up the losses in equivalent metres, depending on the installation position, of all the components and accessories in the system.
3. Check that the total calculated loss is less than or equal
to 95 equivalent metres, i.e. the maximum permissible for this model of boiler.
For complete flue options please contact ferroli or check our comprehensive flue manual.
fig. 18
280
1KWMA84U
5
1KWMA82U
1KWMA83W
2
4
20
Table 3
Ref.
2
4
5
36
29
Description
Vertical air pipe Ø80
Vertical flue pipe Ø80
1
80 Ø vertical flue Kit
Total
Equivalent
loss
36 m
46,4 m
12,0 m
94,4 m
041039X0
fig. 19
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 21
OPTIMAX HE PLUS 18 OV
Table of Ø80 flue and accessory
Table 4 Table 5
Equivalent losses in
metres (linear)
Accessories Ø 80 Accessories Ø 80
Air Flue
Equivalent losses in
metres (linear)
Air Flue
Description
Pipe Ø 80
male-female
1KWMA83W  1,00 m
Bend 45° Ø 80 mm
male - female
Bend 90° Ø 80 mm
male - female
Terminal Position
1KWMA65W
1KWMA01W
Vertical
Horizontal
Vertical
1 1 1.6 2
1.2 1.8
1.5 2.0
terminal
Description
1KWMA86A
1KWMA85A
1KWMA84U
Vertical
Horizontal
Vertical
Horizontal
5
2
12
Horizontal
Horozontial
flue terminal
Horozontial air terminal
Vertical flue
The stated loss values refer to genuine Ferroli flue accessories.
P
Q
l
Q
D, E
Q
F
J
L
B
G
C
A
H
N
MM
N
H
K
fig. 20
Cod. 3540M164 - 02/2009 (Rev. 00)
21
Page 22
OPTIMAX HE PLUS 18 OV
Minimum Dimensions of Flue Terminal Positions
A
B
C
D
E
F
G
H
I
J
K
L
Directly below an opening, air brick, opening windows, etc.
Above an opening, air brick,
opening windows, etc.
Horizontally to an opening, air brick,
opening windows, etc.
Below gutters, soil pipes or drain pipes
Below eaves
Below balconies or car port roof
From a vertical drain pipe or soil pipe
From an internal or external corner
Above ground roof or balcony level
From a surface facing the terminal
From a terminal facing the terminal
From an opening in the car port (e.g. door, window) into the dwelling
300mm
300mm
300mm
75mm
200mm
200mm
150mm
100mm
300mm
600mm
1200mm
1200mm
M
N
O
P
Q
NOTE
N/A = Not applicable
In addition, the terminal should not be nearer than 150mm (fanned draught) to an opening in the building fabric formed for the purpose of accommodating a built-in element such as a window frame. A terminal guard must be used if the terminal is less than 2 metre's from the ground.
Condensing Terminal Positions: If the flue is to be terminated at low level, then the potential effect of the plume must be considered.
The plume should not be directed:
Vertically from a terminal on the same wall
Horizontally from a terminal on the same wall
From the wall on which the terminal is mounted
From a vertical structure on the roof
Above intersection with roof
across a frequently used access route
towards a window or door
across a neighbouring property
1500mm
300mm
N/A
150mm
300mm
22
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 23
OPTIMAX HE PLUS 18 OV
Connection to collective flues or single flues with natural draught
If you are then going to connect the OPTIMAX HE PLUS 18 OV boiler to a collective flue or a single flue with natural draught, the flue must be expressly designed by professionally qualified technical personnel in conformity with the standards and rules in force.
In particular, flues must have the following characteristics:
• Be sized according to the method of calculation stated in the standard
• Be airtight to the products of combustion, resistant to the fumes and heat and waterproof for the condensate
• Have a circular or square cross-section (some hydraulically equivalent sections are permissible), with a vertical progression and with no constrictions
• Have the flue conveying the hot fumes adequately distanced or isolated from combustible mate­rials
• Be connected to just one unit per floor, for at most 6 units in all (8 if there is a compensation duct or opening)
• Have no mechanical suction devices in the main ducts
• Be at a lower pressure, all along their length, under conditions of stationary operation
• Have at their base a collection chamber for solid materials or condensation of at least 0.5 m, equipped with a metal door with an airtight closure.
2.7 Condensate outlet connection
0,5 lt.
fig. 21
The boiler is equipped with an internal air-trap to drain off the condensate. Fit the inspection coupling A and the hose B, pushing it on for approximately 3 cm and securing it with a clamp.
Fill the air-trap with approximately 0.5 ltrs of water and connect the hose to the waste system, or soakaway.
Cod. 3540M164 - 02/2009 (Rev. 00)
23
Page 24
OPTIMAX HE PLUS 18 OV
Condensate discharge
Where possible the condensate should discharge into an internal soil pipe or waste system. The minimum pipe diameter required is 22 mm, a trap has already been fitted to the appliance with a flexible tail to facilitate the connection to the condensate discharge pipe.
The pipe should be a solvent weld plastic, not copper, as the condensate has a ph value of 4 (slightly acidic).
Where it is not possible to terminate internally, the condensate discharge pipe may be run outside (see below drawing).
Any external run is subject to freezing, in severe weather conditions. To avoid this the pipework should be installed to dispose of the condensate quickly, with as much as possible run internally, before passing through the wall.
Pipework external to the building should be increased in diameter to 32 or 40 mm solvent weld. It should be run to a external drain or soakaway, with a maximum length of 3 metres.
When a soakaway (condensate absorption point) is used, it should be constructed as shown below, or use a specifically designed unit, for example Mc Alpine SOAK1GR available from most plumbing and heating stockists.
Internal
External
32/40mm Solvent weld pipework
Cement seal
25mm
100mm Dia tube
Lime stone chippings
Hole depth 400mm
Ground level (either/Or)
-300mm
2 Rows of 3x12 mm Holes
Bottom sealed
24
fig. 22
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 25
OPTIMAX HE PLUS 18 OV
3. SERVICE AND MAINTENANCE
3.1 Adjustments
All adjustment and conversion operations must be carried out by Qualified Personnel such as ferroli Technical Service.
FERROLI declines any responsibility for damage or physical injury caused by unqualified and unauthorized persons tampering with the device.
Gas supply conversion
The unit can function with either Natural Gas or LPG (commercial propane)and is factory-set for use with one of the two gases, as clearly shown on the packing and on the unit’s dataplate. Whenever a different gas to that for which the unit is preset has to be used, a conversion kit will be required, proceeding as follows:
1 Remove the casing. 2 Open the sealed chamber. 3 Release the fixing clip C and remove the gas pipeA from the fan - venturi assembly. 4 Replace the nozzle B inserted in the gas pipe with that contained in the conversion kit. 5 Reassemble the gas pipe A with the clip and check the seal of the connection. 6 Apply the plate contained in the conversion kit, near the dataplate. 7 Refit the sealed chamber and casing. 8 Adjust the parameter for the specific type of gas to be used:
- Turn the boiler onto standby
- Press the DHW buttons (part. 1, 2 - fig. 1) for 10 seconds: the display will show “P01”
blinking
- Press the DHW buttons (part. 1, 2 - fig. 1) to set parameter 00 (for natural gas operation)
or 01 (for LPG operation)
- Press the DHW buttons (part. 1, 2 - fig. 1) for 10 seconds
- The boiler will go back onto standby
9 Check working pressure. 10 Check CO2mixture as detailed (page 28 combustion analyser testing).
fig. 23
Cod. 3540M164 - 02/2009 (Rev. 00)
25
Page 26
OPTIMAX HE PLUS 18 OV
3.2 System start-up
Commissioning must be performed by Qualified Personnel. Checks to be made at first ignition, and after all maintenance operations that involved discon­necting from the systems or an intervention of a safety device.
Before lighting the boiler:
• Open any isolation valves between the boiler and the system.
• Check the tightness of the gas system, proceeding with caution and use gas leak detection fluid to detect any leaks in connections.
• Check the pre-filling of the expansion tank (ref. sec.4.4)
• Fill the water system and make sure that all air contained in the boiler and the system has been vented by opening the air vent valve on the boiler and any vent valves on the system.
• Make sure there are no water leaks in the system, hot water circuits, connections or boiler.
• Make sure the electrical system is properly connected.
• Make sure that the unit is connected to a good earthing system.
• Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler.
• Vent and spin the pump.
• Ensure the flue system is correctly fitted, including terminal locations.
Ignition
• Open the gas valve upstream of the boiler.
• Purge the air from the installation pipework to the appliance.
• Switch on the boiler electrical supply.
• Press the key on the boiler for 5 seconds (part. 7 - fig. 1).
• The boiler is now ready to function automatically whenever the external controls call for a demand.
In case of an electrical power failure while the boiler is working, the burner will go out. When power returns, the boiler will run the self-test cycle again, after which the burner will automatically re-ignite (if there is still demand for heat).
Checks during operation
• Check the tightness of the gas circuit and water systems.
• Check the efficiency of the flue and air-flue ducts while the boiler is working.
• Check that the water is circulating properly between the boiler and the system.
• Make sure that the gas valve modulates correctly.
• Check the proper ignition of the boiler by performing various tests, turning it on and off with the room thermostat or remote control.
• Make sure that the fuel consumption indicated on the meter corresponds to that given in the technical data table in section 4.4 page 33
Turning off
26
Press the key for 5 seconds (
part. 7 - fig. 1
Cod. 3540M164 - 02/2009 (Rev. 00)
).
Page 27
OPTIMAX HE PLUS 18 OV
3.3 Maintenance
The following operations are strictly reserved for Qualified Personnel, such as corgi registered engineers or Ferroli engineers.
Seasonal inspection of the boiler and flue
It is advisable to carry out the following checks at least once a year:
• The control and safety devices (gas valve, flow meter, thermostats, etc.) must function correctly.
• The flue terminal end piece and ducts must be free of obstructions and leaks.
• The gas and water systems must be sound.
• The burner and exchanger must be clean.
• The electrodes must be free of scale and correctly positioned.
• The system pressure when cold must be approx 1 bar; otherwise, bring it to that value.
• The expansion vessel must be filled to 1 bar cold with zero system pressure.
• The gas flow and pressure must correspond to that given in table 10 section 4.4 page 33.
• The circulating pump must be vented and free of debris.
• The returned filter cleaned.
• The condensate trap inspection bowl should be cleaned and free of debris.
Cod. 3540M164 - 02/2009 (Rev. 00)
27
Page 28
OPTIMAX HE PLUS 18 OV
Opening the casing
To open the boiler casing, you need to follow the sequence given below and the instructions of fig. 24.
1 Using a screwdriver, fully unscrew and remove the 2 screws “A ” 2 Open by lowering the panel “B ” 3 Lift and take off the casing “C ”
C
fig. 24
A
A
B
Cleaning the boiler and burner
The body and burner must not be cleaned with chemical products or wire brushes. Special care must be taken over all the sealing systems pertaining to the sealed chamber (gaskets, cable clamps, etc.). In addition, it is necessary to pay attention after performing all these operations to check and carry out all the phases of ignition and thermostat operation, the gas valve and circulation pump.
After these checks, make sure there are no gas leaks.
Combustion analysis
It is possible to analyse the combustion through the air and flue sampling points shown in fig. 25.
To make the measurement, it is neces­sary to:
1) Open the flue sampling point
2) Insert the probe;
3) Press CH button (part. 3, 4 - fig. 1)
for 5 seconds to turn on TEST mode;
4) Wait 10 minutes for the boiler to sta­bilize
5) Take the measurement.
Flue gas
Air
Air Flue gas
fig. 25
28
NAT GAS; CO2 reading should be 8.7 to 9.0% L.P.G; CO2 reading should be 9.5 to 10%
Readings taken with an unstabilized boiler will cause measurement errors.
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 29
OPTIMAX HE PLUS 18 OV
3.4 Troubleshooting
Fault Diagnosis
In the event of operating problems or trouble, the display will flash and a fault identification code appears.
There are faults that in order to restore operation the RESET button must be pressed (ref.6 - fig. 1); or if the boiler fails to start, it will be necessary to repair the fault (code nos. F1 to F24). Other faults cause temporary shutdowns that are automatically reset as soon as the value comes back within the boiler’s normal working range (codes from 25 to 47).
When the boiler starts functioning normally again, the display stops flashing and the fault code disap­pears.
Fault Possible cause Cure
No burner ignition
A01
Flame detected with the burner off
A02
High limit protection
A03
Flue gas fault
A04
Fan problem
A05
No fl ame after the ignition phase (6
A06
times in 4 min.)
No gas
Detection or ignition electrode fault
Defective gas valve Check and change the gas valve
Incorrect inlet gas pressure Check inlet gas pressure
Siphon obstructed Check and if necessary change the siphon
Ionisation electrode defective Check the ionizing electrode wiring
Main board defective Check the PCB
Flow sensor not active or correctly located
No system circulation
Fault F07 happened 3 times in the last 24 hours
Tachometer signal interruped for 1 hour
Detection electrode fault
Flame instable Check the burner
Incorrect valve gas Offset Check Offset at the minimum power
Check the regular gas fl ow to the boiler and the air has been purged from the pipes.
Check that the electrodes are correctly positioned and free of any deposits
Check the correct positioning and operation of the fl ow sensor
Check the pump and radiator valves present in the system and automatic by-pass
Check the fl ue
Check the wiring and the fan
Check that the electrode is correct positioned and if necessary change it
Flue gas circuit obstructed Check if fl ue gas circuit is free
Siphon obstructed Check and if necessary change the siphon
Flow sensor disconnected Sensor disconnected
A41
The exhaust gases temperature becomes higher than 95°C for 2 minutes longer.
Sensor damaged or short circuited Check the wiring or change the sensor
Sensor damaged or wiring broken Check the wiring or change the sensor
Sensor damaged or wiring shorted Check the wiring or change the sensor
Sensor damaged or wiring broken Check the wiring or change the sensor
F07
F10
F11
Flue gas fault
Flow sensor fault
Return sensor fault
Check the correct position and operation of the fl ow sensor
Check the fl ue
Cod. 3540M164 - 02/2009 (Rev. 00)
29
Page 30
OPTIMAX HE PLUS 18 OV
Fault Possible cause Cure
Sensor damaged or wiring shorted Check the wiring or change the sensor
Flue sensor fault
F13
Sensor damaged or wiring broken
Check the wiring or change the sensor
Flow sensor fault
F14
Fan problem
F15
Supply voltage under 180V. Electric mains fault Check the electrical system
F34
Irregular mains frequency Electric mains fault Check the electrical system
F35
Flow sensor fault Sensor damaged Change the sensor
F42
Sensor damaged or short circuited Check the wiring or change the sensor
Sensor damaged or wiring broken Check the wiring or change the sensor
Tachometer signal interrupted, fan connection
Fan damaged, debris in fan Check the fan, clean debris
Check the wiring and fan
30
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 31
OPTIMAX HE PLUS 18 OV
4. TECHNICAL CHARACTERISTICS AND DATA
4.1 Dimensions and connections
1 5
45 25
35
205
145
77
104
280
700
320
45
3
50
Key
1 System flow (22 mm compression union) 3 Gas inlet (22 mm with isolation valve fitted) 5 System return - 22 mm compression union
192
Cod. 3540M164 - 02/2009 (Rev. 00)
137
128
fig. 26
31
Page 32
OPTIMAX HE PLUS 18 OV
4.2 General view and main components
191 29
16
201
5
278
19
22
81 82
161
196
186
44
7154
fig. 27
32
5 Room sealed compartment 7 Gas inlet 10 CH flow 11 CH return 16 Premix fan assembly 19 Combustion compartment 22 Main burner 29 Flue Collar 44 Gas valve
Cod. 3540M164 - 02/2009 (Rev. 00)
81 Ignition electrode 82 Ionisation electrode 154 Condensate outlet pipe 161 Heat exchanger 186 Return sensor 191 Flue gas temperature sensor 196 Condensate collector 201 Fan Venturi 278 Double sensor (Safety + Heating)
Page 33
OPTIMAX HE PLUS 18 OV
4.3 Hydraulic diagram
16
278
10
11
161
193
154
186
Drain off valve
44
Key
7 Gas inlet 10 CH flow 11 CH return 16 Premix fan assembly 44 Gas valve
154 Condensate outlet pipe
7
fig. 28
161 Heat exchanger 186 Return sensor 193 Siphon 278 Double sensor (Safety + Heating)
Cod. 3540M164 - 02/2009 (Rev. 00)
33
Page 34
OPTIMAX HE PLUS 18 OV
4.4 Technical data table
Table 10
Max. CH Heat input Min. CH Heat input
Max. useful heat output 80° C - 60° C Min. useful heat output 80° C - 60° C Max. useful heat output 50° C - 30° C
Min. useful heat output 50° C - 30° C
Efficiency Pmax 80° C - 60° C Efficiency Pmin 80° C - 60° C Efficiency Pmax 50° C - 30° C
Efficiency Pmin 50° C - 30° C
Efficiency 30%
Gas Injector (G20 - Natural Gas)
Natural Gas supply pressure (G20) Max. CO2 (G20 - Natural Gas) %
Min. CO2 (G20 - Natural Gas) % Max. natural Gas flow rate (G20) Min. natural Gas flow rate (G20)
Gas Injector (G31 - Propane) LPG supply pressure (G31)
Max. CO2 (G31 - Propane) % Min. CO2 (G31 - Propane) Max. LPG flow rate (G31) Min. LPG flow rate (G31)
Unit Value
kW 18.0 kW
kW 17.7 kW kW 19.0
kW
% % %
% %
mbar
3
/h
m
3
/h
m
mbar
% kg/h kg/h
3.0
2.9
3.2
98.3
97.3
105.4
107.2
109.1
6.20
20
9
8.5
1.90
0.32
4.2
37 10
9.5
1.41
0.23
Energy marking (92/42 EEC directive) NOx emission class Max. flue gas temperature 80°C - 60°C °C Min. flue gas temperature 80°C - 60°C
Max. flue gas temperature 50°C - 30°C °C Min. flue gas temperature 50°C - 30°C
Max. flue gas flow rate kg/h Min. flue gas flow rate Max. working pressure in heating bar
Min. working pressure in heating
Maximum working temperature in heating °C Total boiler water content litres
Electrical protection rating IP Power voltage/frequency Max electrical power absorbed
Weight empty kg
Type of unit
PIN CE
°C
°C
kg/h
bar
V/Hz
5 64 60 45 30
30.3
5.3
3
0.3
85
1
X5D
230/50
W
C13-C23-C33-C43-C53
50
19
C63-C83-B33 0461 BT 0920
34
Cod. 3540M164 - 02/2009 (Rev. 00)
Page 35
OPTIMAX HE PLUS 18 OV
4.5 Wiring diagram
Key
16 Fan 44 Combination gas valve 62 Time clock (optional) 81 Spark Electrode 82 Ionisation electrode 101 Main p.c.b. 103 Relay 104 Fuse F3.15 amp
fig. 29
186 Return temperature sensor 191 Exhaust temperature sensor 202 Transformer 230V-24V 203 Supply lead 278 Double sensor (Safety + Heating)
Cod. 3540M164 - 02/2009 (Rev. 00)
35
Page 36
267
BENCHMARK
COLLECTIVE MARK
BENCHMARK No.
Please add the first 4 digits of the Boiler serial No to complete the BENCHMARK No.
GAS BOILER COMMISSIONING CHECKLIST
BOILER SERIAL No. NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING ROOM T/STAT & PROGRAMMER/TIMER PROGRAMMABLE ROOMSTAT
TIME & TEMPERATURE CONTROL TO HOT WATER CYLINDER T/STAT & PROGRAMMER/TIMER
HEATING ZONE VALVES FITTED NOT REQUIRED
HOT WATER ZONE VALVES FITTED NOT REQUIRED
THERMOSTATIC RADIATOR VALVES FITTED
AUTOMATIC BYPASS TO SYSTEM FITTED NOT REQUIRED
COMBI BOILER
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER’S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATE ft3/hr
BURNER OPERATING PRESSURE (IF APPLICABLE) mbar
CENTRAL HEATING FLOW TEMPERATURE °C
CENTRAL HEATING RETURN TEMPERATURE °C
m3/hr
N/A
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED? YES NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
GAS RATE ft3/hr
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE) mbar
COLD WATER INLET TEMPERA
HOT WATER OUTLET TEMPERATURE °C
WATER FLOW RATE
TURE °C
m
N/A
3
/hr
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS? YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
lts/min
THE HEATING AND HOT WATER SYSTEM COMPLIES WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING? N/A YES CO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER’S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
COMMISSIONING ENG’S NAME PRINT CORGI ID No.
SIGN DATE
Page 37
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls
SERVICE 1
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 3
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 5
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SERVICE 2
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 4
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 6
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
DATE
DATE
DATE
SIGNATURE
SERVICE 7
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 9
ENGINEER NAME
ANY NAME
COMP
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
TE
DA
SIGNATURE
SERVICE 8
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SERVICE 10
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
DATE
DATE
FERROLI TECHNICAL HELPLINE - 08707 282 885
Page 38
Page 39
Page 40
Should you require any assistance during the installation
Should you require a service engineer to visit
Phone numbers:
Installer
Service Engineer
call our Technical Service Helpline on
08707 282 885 option 1
call our service centre on
08707 282 885 option 2
BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS.
ALL SPECIFICATIONS SUBJECT TO CHANGE
Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check
this is not caused by lack of electricity supply, gas supply or low water pressure before calling our
Customer Service Helpline.
Lichfield Road, Branston Industrial Estate, Burton Upon Trent, Staffordshire DE14 3HD
Tel. 08707 282 885 - Fax 08707 282 886
Loading...