Ferroli ENERGY TOP B 80, ENERGY TOP B 125, ENERGY TOP B 250, ENERGY TOP B 160 Instructions For Use, Installation And Maintenance

Page 1
6
cod. 3540S738 — Rev. 00 - 01/2014
ENERGY TOP B
IT -
ISTRUZIONE PER L’USO L'INSTALLAZIONE E LA MANUTENZIONE
ES -
INSTRUCCIONES DE USO, INSTALACIÓN Y MANTENIMIENTO
KULLANMA, KURULUM VE BAKøM TALIMATLAR
ø
EN -
INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE
FR -
INSTRUCTIONS D'UTILISATION, D'INSTALLATION ET D'ENTRETIEN
RO -
INSTRUCğIUNI DE UTILIZARE, INSTALARE ùI ÎNTRETINERE
RU -
ɊɍɄɈȼɈȾɋɌȼɈ ɉɈ ɗɄɋɉɅɍȺɌȺɐɂɂ, ɆɈɇɌȺɀɍ ɂ ɌȿɏɈȻɋɅɍɀɂȼȺɇɂɘ
UA -
ȱɇɋɌɊɍɄɐȱə Ɂ ȿɄɋɉɅɍȺɌȺɐȱȲ, ɆɈɇɌȺɀɍ ɌȺ ɈȻɋɅɍȽɈȼɍȼȺɇɇə
Page 2
ENERGY TOP B
61
EN
cod. 3540S738 - Rev. 00 - 01/2014
EN
1. GENERAL WARNINGS
Carefully read and follow the instructions contained in this instruction booklet.
After boiler installation, inform the user regarding its operation and give him this manual, which is an integral and essential part of the product and must be kept with care for future reference.
Installation and maintenance must be carried out by professionally qualified person­nel, in compliance with the current regulations and according to the manufacturer's instructions. Do not carry out any operation on the sealed control parts.
Incorrect installation or inadequate maintenance can result in damage or injury. The Manufacturer declines any liability for damage due to errors in installation and use, or failure to follow the instructions.
Before carrying out any cleaning or maintenance operation, disconnect the unit from the electrical power supply using the switch and/or the special cut-off devices.
In case of a fault and/or poor operation, deactivate the unit and do not try to repair it or directly intervene. Contact professionally qualified personnel. Any repair/re­placement of the products must only be carried out by qualified personnel using orig­inal replacement parts. Failure to comply with the above could affect the safety of the unit.
This unit must only be used for its intended purpose. Any other use is deemed im­proper and therefore hazardous.
The packing materials are potentially hazardous and must not be left within the reach of children.
The unit must not be used by people (including children) with limited physical, sen­sory or mental abilities or without experience and knowledge of it, unless instructed or supervised in its use by someone responsible for their safety.
The unit and its accessories must be appropriately disposed of, in compliance with the current regulations.
The images given in this manual are a simplified representation of the product. In this representation there may be slight and insignificant differences with respect to the product supplied.
2. OPERATING INSTRUCTIONS
2.1 Introduction
Dear Customer, Thank you for choosing ENERGY TOP B, a latest-generation heat generator featuring
FERROLIadvanced design and cutting-edge technology. Please read this manual care­fully since it provides important information on safe installation, use and maintenance.
ENERGY TOP B is a high-efficiency modular premix condensing heat generator for heating with very low emissions , running on natural gas or LPG and arranged for in-
stallation in cascade. Each module ENERGY TOP B is equipped with one (version ENERGY TOP B 80 - 125)
or two (version ENERGY TOP B 160 - 250) aluminium finned tube exchangers with steel premix burners, housed in a vertical cabinet in epoxy powder coated steel resistant to atmospheric agents.
The plumbing circuits of the exchangers, each equipped with its own local circulating pump, run into system delivery and return manifolds inside the module. The control sys­tem has a microprocessor, user interface with a large display and advanced cascade control functions.
2.2 Control panel
fig. 1 - Control panel
The control panel is located inside the cabinet. To access it, open the front door with the special key supplied.
Key
1 =
DHW temperature setting decrease button (with optional hot water tank installed)
2 =
DHW temperature setting increase button (with optional hot water tank installed)
3 = Heating system temperature setting decrease button 4 = Heating system temperature setting increase button 5 = Display 6 = Summer/Winter mode selection button 7 = Economy/Comfort mode selection (with optional hot water tank installed) and
unit On/Off button
8 = Reset button 9 = DHW operation (with optional hot water tank installed) 10 = Summer mode 11 = Multifunction 12 = Eco (Economy) mode (with optional hot water tank installed) 13 = Heating mode 14 = Unit On / Off button 15 = Burner On 16 = Appears on connecting the Remote Timer Control (optional) 17 = Information symbol 18 = Top boiler shell 19 = Top boiler shell system fault reset request 20 = Fault 21 = Circulating pump On 22 = Appears on connecting the external probe (optional) 23 = Boiler Off 24 = Bottom boiler shell 25 = Bottom boiler shell system fault reset request (model ENERGY TOP B 160 -
250only)
Indication during operation
Heating
A heating demand (generated by the Room Thermostat or Remote Timer Control or 0­10 Vdc signal) is indicated by activation of the circulating pump and the radiator (details 13 and 21 - fig. 1).
The display (detail 11 - fig. 1) shows the actual heating delivery temperature and, during heating standby time, the message "d". Activation of the arrows (details 18 and 24 ­fig. 1) indicates which boiler shell is on.
fig. 2
DHW (with optional hot water tank installed)
A hot water tank heating demand is indicated by activation of the circulating pump and the tap (details 9 and 21 - fig. 1). The display (detail 11 - fig. 1) shows the actual hot water tank sensor temperature and, during heating standby time, the message "d". Activation of the arrows (details 18 and 24 - fig. 1) indicates which boiler shell is on.
fig. 3 -
Exclude hot water storage tank (economy)
Hot water tank temperature maintaining/heating can be excluded by the user. If exclud­ed, domestic hot water will not be delivered. The hot water tank can be deactivated by the user (ECO mode) by pressing the eco/comfort button (detail 7 - fig. 1). In ECO mode the display activates the symbol (detail 12 - fig. 1). To activate the COMFORT mode, press the eco/comfort button (detail 7 - fig. 1) again.
17 18 2320
4
16
22
2
1 9 12
21
3
13
10
6 8 14
11
5
7
15 25
!"!#
!$%
$%&'% #
19
24
!"!#
!$%
$%&'% #
!"!#
!$%
$%&'% #
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
!"!#
!$%
$%&'% #
!"!#
!$%
$%&'% #
Page 3
ENERGY TOP B
62
EN
cod. 3540S738 - Rev. 00 - 01/2014
2.3 Lighting and turning off
Boiler lighting
Press the On/Off button (detail 14 - fig. 1).
fig. 4 - Boiler lighting
For the following 120 seconds the display will show FH which identifies the heating system air venting cycle.
During the first 10 seconds the display will also show the software version of the cards:
A = Display card software version B = Top boiler shell control unit software version C = Bottom boiler shell control unit software version (model ENERGY TOP B 160 ­250only)
Open the gas cock ahead of the boiler.
When the message FH disappears, the boiler is ready to operate automatically in case of a room thermostat demand.
Turning the boiler off Press the button eco/comfort (detail 7 - fig. 1) for 5 seconds.
fig. 5 - Turning the boiler off
When the boiler is turned off, the PCB is still powered. Domestic hot water (with optional hot water tank installed) and heating operation are dis-
abled. The antifreeze system remains activated. To relight the boiler, press the button eco/comfort (detail 7 - fig. 1) again for 5 seconds.
fig. 6
The boiler will be immediately ready to operate whenever domestic hot water is drawn (with optional hot water tank installed) or in case of a room thermostat demand.
To completely disconnect the power to the unit, press the button detail 14 - fig. 1.
B
The antifreeze system does not work when the power and/or gas to the unit are turned off. To avoid damage caused by freezing during long idle periods in win­ter, it is advisable to drain all water from the boiler, DHW circuit and system; or drain just the DHW circuit and add a suitable antifreeze to the heating system, complying with that prescribed in sec. 3.3.
2.4 Adjustments
Summer/Winter Switchover
Press the button (detail 6 - fig. 1) for 1 second.
fig. 7
The display activates the Summer symbol (detail 10 - fig. 1). The heating function is de­activated, whereas the possible production of domestic hot water (with optional external hot water tank) remains activated. The antifreeze system remains activated.
To deactivate Summer mode, press the button (detail 6 -
fig. 1
) again for 1 second.
Heating temperature adjustment
Use the heating buttons +/- (details 3 and 4 - fig. 1) to adjust the temperature from a min. of 20°C to a max. of 90°C.
fig. 8
DHW temperature adjustment (with optional hot water tank installed)
Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a min. of 10°C to a max. of 65°C.
fig. 9
Room temperature adjustment (with optional room thermostat)
Using the room thermostat, set the temperature required in the rooms.
Room temperature adjustment (with optional remote timer control)
Using the remote timer control, set the temperature desired in the rooms. The boiler unit will set the system water according to the required room temperature. For information on the remote timer control, please refer to its user's manual.
Sliding temperature
When the optional external probe is installed the corresponding symbol (detail 22 - fig. 1) is activated on the control panel display (detail 5 - fig. 1). The boiler control system works with "Sliding Temperature". In this mode, the heating system temperature is controlled according to the outside weather conditions in order to ensure high comfort and energy saving throughout the year. In particular, as the outside temperature increases, the sys­tem delivery temperature is decreased according to a specific "compensation curve".
With Sliding Temperature adjustment, the temperature set with the heating buttons (de- tails 3 and 4 - fig. 1) becomes the maximum system delivery temperature. It is advisable to set a maximum value to allow system adjustment throughout its useful operating range.
The boiler must be adjusted at the time of installation by qualified personnel. Adjust­ments can in any case be made by the user to improve comfort .
Compensation curve and curve offset Press the reset button (detail 8 - fig. 1) for 5 seconds, to display the actual compensation
curve (fig. 10) which can be modified with the DHW buttons (details 1 and 2 - fig. 1). Adjust the required curve from 1 to 10 according to the characteristic (fig. 12). By setting the curve to 0, sliding temperature adjustment is disabled.
fig. 10 - Compensation curve
Press the heating buttons (details 3 and 4 - fig. 1) to access parallel curve offset (fig. 13), modifiable with the DHW buttons (details 1 and 2 - fig. 1).
fig. 11 - Curve parallel offset
Press the reset button (detail 8 - fig. 1) again for 5 seconds to exit parallel curve adjust­ment mode.
!"!#
!$%
$%&'% #
!"!#
!$%
$%&'% #
!"!#
!$%
$%&'% #
!"!#
!$%
$%&'% #
A
B (
!"!#
!$%
$%&'% #
!"!#
!$%
$%&'% #
!"!#
!$%
$%&'% #
!"!#
!$%
$%&'% #
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
!"!#
!$%
$%&'% #
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
!"!#
!$%
$%&'% #
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
!"!#
!$%
$%&'% #
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Page 4
ENERGY TOP B
63
EN
cod. 3540S738 - Rev. 00 - 01/2014
If the room temperature is lower than the required value, it is advisable to set a higher order curve and vice versa. Proceed by increasing or decreasing in steps of one and check the result in the room.
fig. 12 - Compensation curves
fig. 13 - Example of compensation parallel curve offset
A
If the Remote Timer Control (optional) is connected to the boiler, the above ad­justments are managed according to that given in table 1.
Table. 1
System water pressure adjustment
The filling pressure with the system cold must be approx. 1.0 bar. If the system pressure falls to values below minimum, the boiler card will activate fault F37 (fig. 14). Flashing of the arrows (details 18 and 24 - fig. 1) together with the error code indicates which boiler shell is in fault status.
fig. 14 - Low system pressure fault
A
Once the system pressure is restored, the boiler will activate the 120-second air venting cycle indicated on the display by FH.
3. INSTALLATION
3.1 General Instructions
THE BOILER MUST ONLY BE INSTALLED BY QUALIFIED PERSONNEL, IN COMPLI­ANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE NATIONAL AND LOCAL REGULATIONS, AND THE RULES OF PROPER WORKMANSHIP.
ENERGY TOP B is a heat generator arranged to operate alone or in cascade (bank). When two or more generators are installed in cascade with the original kits ENERGY TOP B, respecting the prescriptionsFERROLIof this manual, they can be considered as a single heat generator of total power equal to the sum of the powers of all the units con­nected in cascade.
All the requirements of the current standards and regulations applicable to this "equiva­lent" total heating capacity generator must be met. In particular, the place of installation, safety devices and fume exhaust system must be adequate for the total heating capacity of the bank of units.
In fact, each ENERGY TOP B is a complete and independent heat generator, equipped with its own safety devices. In case of overtemperature, no water or no circulation in the unit , the protection devices cause the unit to shutdown , preventing its operation.
The installation instructions given in the following paragraphs concern single units and connection in cascade.
Given below are the possible configurations for connection in cascade.
Configurations in line
fig. 15 - Configuration - in line (example with 4 modules)
Table. 2 - Configurations in line
Heating temperature adjustment
Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
DHW temperature adjustment (with optional hot water tank installed)
Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
Summer/Winter Switchover
Summer mode has priority over a possible Remote Timer Control heating demand.
Eco/Comfort selection
(with
optional hot water tank installed)
On disabling DHW from the Remote Timer Control menu, the boiler selects the Economy mode. In this condition, the button detail 7 -fig. 1 on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the boiler selects the Comfort mode. In this condition it is possible select one of the two modes with the button detail 7 -fig. 1.
Sliding Temperature
Both the Remote Timer Control and the boiler card manage Sliding Tempera­ture adjustment: of the two, the Sliding Temperature of the boiler card has prior­ity.
20
30
40
50
60
70
80
90 85
20 10 0 -10 -20
1
2
3
4
5
68910 7
20
30
40
50
60
70
80
90 85
20
30
40
50
60
70
80
90 85
1
2
3
4
5
6
8910
7
1
2
3
4
568910 7
)**+,-.=.20 )**+,-.=.40
!"!#
!$%
$%&'% #
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Heating power Combinations
max.
kW
Model
Module 1
Model
Module 2
Model
Module 3
Model
Module 4
Model
Module 5
Ø; A
75
80 / / / / / 500
116
125 / / / / / 500
150
160 / / / 200 1000
232
250 / / / 200 1000
225
160 80 / / / 200 1500
266
160 125 / / / 200 1500
307
250 80 / / / 200 1500
348
250 125 / / / 200 1500
300
160 160 / / / 200 2000
382
250 160 / / / 200 2000
464
250 250 / / / 200 2000
375
160 160 80 / / 200 2500
416
160 160 125 / / 200 2500
457
250 160 80 / / 200 2500
498
250 160 125 / / 300 2500
539
250 250 80 / / 300 2500
580
250 250 125 / / 300 2500
450
160 160 160 / / 300 3000
532
250 160 160 / / 300 3000
614
250 250 160 / / 300 3000
696
250 250 250 / / 300 3000
525
160 160 160 80 / 300 3500
566
160 160 160 125 / 300 3500
607
250 160 160 80 / 300 3500
648
250 160 160 125 / 300 3500
689
250 250 160 80 / 300 3500
730
250 250 160 125 / 300 3500
771
250 250 250 80 / 300 3500
812
250 250 250 125 / 300 3500
600
160 160 160 160 / 300 4000
682
250 160 160 160 / 300 4000
764
250 250 160 160 / 300 4000
846
250 250 250 160 / 300 4000
928
250 250 250 250 / 300 4000
1003
250 250 250 250 80 300 4500
1044
250 250 250 250 125 300 4500
1078
250 250 250 250 160 300 5000
1160
250 250 250 250 250 300 5000
1700
A
325
Ø
Page 5
ENERGY TOP B
64
EN
cod. 3540S738 - Rev. 00 - 01/2014
Opposed configurations
fig. 16 - Opposed configurations
Table. 3 - Opposed configurations
fig. 17 - Examples of opposed configurations
1 Model ENERGY TOP B 160 - 250 2 Model ENERGY TOP B 80 - 125 4 Safety devices and separator module
3.2 Place of installation
The generator can be installed directly outside or in a suitable room with ventilation open­ings to the outside as prescribed by the current regulations. If there are several burners or extraction units that can work together in the same room, the ventilation openings must be sized for simultaneous operation of all the units. The place of installation must be free of flammable objects or materials, corrosive gases, volatile substances or dusts. For positioning, leave enough space around the modules for normal maintenance oper­ations. Make sure the front door opens without hindrance.
B
The air necessary for combustion enters through special openings in the bot­tom and top part of the unit. Make sure these air passages are not obstructed in any way.
fig. 18 - Air inlet
3.3 Gas and water connections
Plumbing connections
Make the relevant connections according to the instructions given below. Make the gen­erator connection in such a way that its internal pipes are free of stress. For proper op­eration and long life of the generator, the plumbing system must be of suitable size and complete with all the accessories that guarantee regular operation and running.
In particular, provide for all the protection and safety devices prescribed by current reg­ulations for the complete modular generator. They must be installed on the hot water cir­cuit delivery piping, immediately downstream of the last module, within a distance of 0.5 m, with no shut-off devices in between. A "Safety Device and Circuit Breaker module” equipped with internal hydraulic circuit breaker and safety units with ISPESL certification is available by request. Refer to the price-list or contact our sales network. The unit is not supplied with an expansion tank; its connection must therefore be made by the Installer.
B
A filter must also be installed on the system return piping to prevent impurities or sludge from the system clogging and damaging the heat generators.
The filter must necessarily be installed when replacing generators in existing systems. The manufacturer declines any liability for damage caused to the gen­erator by failure to install or inadequate installation of this filter.
Water system characteristics
In the presence of water harder than 25° Fr, it is advisable to use suitably treated water, in order to avoid possible scaling in the boiler caused by hard water, or corrosion pro­duced by aggressive water. Due to its low thermal conductivity, scaling even just a few mm thick causes significant overheating of the generator walls, with consequent serious problems.
Water treatment is indispensable in case of very large systems (containing large amounts of water) or with frequent introduction of replenishing water in the system. If par­tial or total emptying of the system becomes necessary in these cases, it is advisable to refill with treated water.
Gas connection
The gas must be connected to the corresponding union with a rigid metal pipe. The gas meter must be adequate for the simultaneous use of all units connected to it.
Carry out the generator gas connection in accordance with current regulations. The di­ameter of the gas pipe leaving the generator does not determine the diameter of the pipe between the unit and the meter; it must be chosen according to its length and pressure loss.
B
Make sure to install a fuel shutoff valve externally with respect to the modules, enabling the gas to be turned off even without opening the single modules equipped with key closing.
Connection instructions ENERGY TOP B is equipped on the inside with 3 manifolds (gas, system delivery and
return) and a condensate drain pipe that facilitate cascade connection and also connec­tion of a single module to the system. The manifolds are sized for a connection in series of up to 1000 kW.
The cabinet contains a set of 3 seals (2 for water manifolds, 1 for gas manifold) with re­spective bolts and nuts, to be used for connection to a subsequent module (connection in cascade). The optional kit code 042027X0, containing 3 blind flanges and 3 drilled flanges with respective seals and screws, is available on request for the connection to the system.
Heating capacity Combinations
max.
kW
Model
Module 1
Model
Module 2
Model
Module 3
Model
Module 4
Model
Module 5
Ø; A
150
80 80 / / / 200 500
191
125 80 / / / 200 500
232
125 125 / / / 200 500
300
160 160 / / / 200 1000
382
250 160 / / / 200 1000
464
250 250 / / / 200 1000
375
160 160 80 / / 200 1500
416
160 160 125 / / 200 1500
457
250 160 80 / / 200 1500
498
250 160 125 / / 300 1500
539
250 250 80 / / 300 1500
580
250 250 125 / / 300 1500
600
160 160 160 160 / 300 2000
682
250 160 160 160 / 300 2000
764
250 250 160 160 / 300 2000
846
250 250 250 160 / 300 2000
928
250 250 250 250 / 300 2000
1003
250 250 250 250 80 300 2500
1044
250 250 250 250 125 300 2500
1078
250 250 250 250 160 300 3000
1160
250 250 250 250 250 300 3000
1700
A=325
A
Ø
450
180120
475
330
185
900
A
B
4
41
2
Page 6
ENERGY TOP B
65
EN
cod. 3540S738 - Rev. 00 - 01/2014
To connect a single module
After establishing on which side of the module to make the water and gas connec­tions, connect the flanges with the joining section contained in the kit on that side after suitably welding them to the system pipes. Make sure to correctly fit the special seals contained in the kit.
Connect a Ø40 pipe to the condensate drain pipe for removing the condensate pro­duced during operation (see fig. 48).
Fit the blind flanges contained in the kit on the opposite side of the module, placing the special seals in between.
fig. 19
1 Gas inlet 2 System delivery 3 System return 4 Condensate drain 5 Blind flanges - kit 042027X0 (optional) 7 Blind flanges - kit 042027X0 (optional)
To connect several modules in line
Connect the first module to the system and gas pipes, as described above, but without fitting the blind flanges on the opposite side of the module to that of the connection.
Connect the second module on this side, making sure to align the connection flang­es and the condensate drain pipe. Place the seals contained in the kit between the flanges of the two modules.
Fit the bolts contained in the kit on the flanges from the inside of the first module, making them come out of the flanges in the second module. Partially tighten the nuts on the bolts from inside the second module.
Before tightening the nuts, make sure all the seals are correctly positioned and fit the condensate drain pipes of the two modules (see fig. 49).
Tighten the nuts and repeat the connection operations for the following modules.
fig. 20
1 Gas inlet 2 System delivery 3 System return 4 Condensate drain 5 Blind flanges - kit 042027X0 (optional) 7 Blind flanges - kit 042027X0 (optional) 8 Seals and screws (standard)
To connect several opposed modules Optional kit code 042026X0 is available for connecting the water and gas manifolds in
series. The kit contains 3 flanged "U" pipes.
fig. 21 - Kit for connection of opposed modules
A 1st Module B 2nd Module C 3rd Module D 4th Module 1 Gas inlet 2 System delivery 3 System return 5 Blind flanges 7 Drilled flanges 8 Seals and screws (standard)
Arrange the modules according to the layout of fig. 21.
Connect the first module to the system and gas pipes using the flanges with pipe section and respective seals contained in the kit 042027X0.
Position the second module, making sure to align the connection flanges and the con­densate drain pipe. Fit the seals (supplied) between the flanges of the two modules.
Fit the bolts (supplied) on the flanges from inside the first module, making them come out the flanges in the second module. Partially tighten the nuts on the bolts from inside the second module.
Before tightening the nuts, make sure all the seals are correctly positioned and fit the condensate drain pipes of the two modules (see fig. 49).
Tighten the nuts and repeat the connection operations for the "U" pipes and next modules. Fit the blind flanges contained in the kit 042027X0 on the last module.
Safety device and separator module (optional)
The Safety Device and Separator Module for series ENERGY TOP Bmodular gener­ators is an ISPESL certified module containing a hydraulic separator and safety, protec­tion and control devices required by file "R" section R3A and R3B, intended for use with series ENERGY TOP Bmodular generators .
Every ISPESL Safety Device Module comprises a cabinet of the same size and appear­ance as the modular generators ENERGY TOP B, containing a hydraulic separator with air valve and thermal insulation, the respective system delivery and return manifolds, a gas manifold, and a discharge manifold for the safety valve. The safety devices required by file "R" section R3A and R3B are fitted on the hydraulic manifolds and hydraulic sep­arator body. Provision is also made for the probe pocket of a possible fuel shutoff valve, to be installed in the system , on the outside of the bank of modules.
The hydraulic separator contained in the module allows the hydraulic circuit of the mod- ules ENERGY TOP B (primary circuit) to be made independent of the hydraulic circuit of the respective heating system (secondary circuit). The separator is sized for correct op­eration up to 1000 kW, and the main advantages offered are:
An external circulating pump for the primary circuit is not necessary. In fact, circula­tion in the primary circuit is ensured by the circulating pumps contained inside the generators ENERGY TOP B.
When the secondary pump is deactivated, also the circulation in the system circuit stops; the entire flow delivered by the circulating pumps contained inside the gener­ators ENERGY TOP B is bypassed through the hydraulic separator.
The flow in the primary circuit can remain constant, whereas the secondary circuit can function with a variable or intermittent flow rate.
There are no anomalous operating conditions in which the system pumps interact with the circulating pumps in side the generators ENERGY TOP B, creating unwant- ed head and flow-rate variations in the circuits.
Sizing of the system circulating pump can be carried out according to the needs of just the secondary circuit.
2
1
3
4
75
2
1
3
2
1
3
4
7
2
1
3
8
5
2./.3
1
2
1
3
7
5
8
AB
6(
2 3
1
Page 7
ENERGY TOP B
66
EN
cod. 3540S738 - Rev. 00 - 01/2014
fig. 22 - Opposed configurations
A 1st Module B 2nd Module 1 Gas inlet 2 System delivery 3 System return 4 Hydraulic separator
The safety devices and separator module must be installed directly next to the last mod­ule ENERGY TOP B making up the modular generator. The particular symmetrical shape of the module allows it to be installed on the right side and left side of the generator bank. Some possible connection examples are given below.
fig. 23 - Configuration in line
C 3rd Module 1 Gas inlet 2 System delivery 3 System return 4 Hydraulic separator
Plumbing circuit examples
Key of examples
I ISPESL safety devices D Hydraulic separator 42 DHW temperature sensor (not supplied) 72 Room thermostat (not supplied) 72b Room thermostat (not supplied) 95 3-way valve - with spring return: at rest on DHW side (not supplied) 130 Hot water tank circulating pump (not supplied) 138 External probe (not supplied) 139 Remote control (not supplied) 298 Cascade temperature sensor (not supplied) 306 Heating system circulating pump (not supplied) 307 Heating system second circulating pump (not supplied) SM Delivery probe (supplied with kit FZ4) TS Safety thermostat (not supplied) PZ Zone pump (not supplied) FZ4 Zone regulator
Parameters
Each system requires a different parametrisation. Follow the procedure for accessing the two menus, given below; for the parameters to be modified, refer to the tables given alongside the plumbing diagrams.
"Service Menu"
Press the Reset button for 10 seconds to access the card Service Menu. Press the Heating buttons to select "tS", "In", "Hi" or "rE". tS" means Transparent Param-
eters Menu, "In" Information Menu, "Hi" History Menu, and "rE" History Menu Reset. Se­lect "tS" and press the RESET button.
The card has 29 transparent parameters also modifiable from Remote Control (Service Menu).
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or­der. Press the DHW buttons to modify the value of a parameter: the change will be au­tomatically saved.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec­onds to exit to the card Service Menu.
"System Type Menu"
Press the Summer/Winter button for 10 seconds to access the card System Type Menu. The card has 21 transparent parameters. Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au­tomatically saved.
Press the Summer/Winter button for 10 seconds to exit the card System Type Menu.
One direct heating circuit
Check/Change parameter P02 of the "Transparent Parameters Menu" to 4. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1.
fig. 24
One direct heating circuit and one DHW circuit with pump
Check/Change parameter P02 of the "Transparent Parameters Menu" to 5. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1.
fig. 25
One direct heating circuit and one DHW circuit with diverter valve Check/Change parameter P02 of the "Transparent Parameters Menu" to 6. Change parameter P.02 of the "System Type Menu" to 1. Chan
ge parameter P.09 of the "System Type Menu" to 1.
Change parameter P.11 of the "System Type Menu" to 1.
fig. 26
B
A
4
4
1
1
2 3
2 3
(
4
2 3
1
A
I
6
138
298
72:139
30;
B
I
6
138
298
30;
42
130
72:139
(
I
6
138
298
30;
95
42
72:139
Page 8
ENERGY TOP B
67
EN
cod. 3540S738 - Rev. 00 - 01/2014
Two direct heating circuits
Check/Change parameter P02 of the "Transparent Parameters Menu" to 4. Change parameter P.01 of the "System Type Menu" to 4. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1.
fig. 27
Two mixed heating circuits and one direct heating circuit
Check/Change parameter P02 of the "Transparent Parameters Menu" to 4. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1. For the electrical connection and the zone system settings, refer to the "FZ4 zone regu-
lator" handbook
fig. 28
Two mixed heating circuits, one direct heating circuit and one DHW circuit with pump Check/Change parameter P02 of the "Transparent Parameters Menu" to 5. Change parameter P.02 of the "System Type Menu" to 1. Change parameter P.09 of the "System Type Menu" to 1. For the electrical connection and the zone system settings, refer to the "FZ4 zone regu-
lator" handbook
fig. 29
3.4 Electrical connections
Connection to the electrical grid
B
The unit's electrical safety is only guaranteed when correctly connected to an efficient earthing system executed according to current safety standards. Have the efficiency and suitability of the earthing system checked by professionally qualified personnel. The manufacturer is not responsible for any damage caused by failure to earth the system. Also make sure that the electrical system is adequate for the maximum power absorbed by the unit, as specified on the boiler dataplate.
The boiler is prewired and provided with a Y-cable and plug for connection to the elec­tricity line. The connections to the grid must be made with a permanent connection and equipped with a bipolar switch whose contacts have a minimum opening of at least 3 mm, interposing fuses of max. 3A between the boiler and the line. It is important to re­spect the polarities (LINE: brown wire / NEUTRAL: blue wire / EARTH: yellow-green wire) in making connections to the electrical line. During installation or when changing the power cable, the earth wire must be left 2 cm longer than the others.
B
The user must never change the unit's power cable. If the cable gets damaged, switch off the unit and have it changed solely by professionally qualified person­nel. If changing the electric power cable, use solely “HAR H05 VV-F” 3x0.75 mm2 cable with a maximum outside diameter of 8 mm.
Room thermostat (optional)
B
CAUTION: The room thermostat must have clean contacts. CONNECTING 230 V. TO THE TERMINALS OF THE ROOM THERMOSTAT WILL IRREPA­RABLY DAMAGE THE ELECTRONIC CARD.
When connecting a remote timer control or a timer switch, do not take the pow­er supply for these devices from their cut-out contacts. Their power supply must be taken with a direct connection from the mains or with batteries, depending on the kind of device.
External probe (optional)
Connect the probe to the respective terminals. The maximum permissible length of the electric cable connecting the boiler - external probe is 50 m. A common 2-wire cable can be used. The external probe should preferably be installed on the North, North-West wall or on the wall facing most of the main living-room. The probe must never be exposed to the early morning sun, and in general (as far as possible) it should not be exposed to direct sunlight; protect it if necessary. In any case, the probe must not be installed near windows, doors, vents, flues or heat sources that could affect the reading.
fig. 30 - Inadvisable positioning of external probe
6
I
6
138
307 30;
298
72<
72:139
,
>%?@.1 >%?@.2 >%?@.3
C C
I
6
+C
298
138
D>
-+
+C
D>
-+
DE
*>4
72:139 72:139 72:139
*
>%?@.1 >%?@.2 >%?@.3
C C
I
6
+C
298
+C
DE
D>
130
42
138
D>
-+ -+
72:139
*>4
72:139 72:139
Page 9
ENERGY TOP B
68
EN
cod. 3540S738 - Rev. 00 - 01/2014
Accessing the electrical terminal block
The electrical terminal block is located inside a sealed box at the bottom left of the cab­inet. Make the electrical connections as shown in the wiring diagram on sec. 65 and run the cables through the special cable glands.
fig. 31 - Electrical terminal block
42 DHW temperature sensor (not supplied) 72 Room thermostat (not supplied) 72b Room thermostat (not supplied) 95 Diverter valve (not supplied)
A = Heating phase B = DHW phase C = Neutral
Note: For valves with 2 wires and spring return, use the connections B and C 130 DHW circulating pump (not supplied) 138 External probe (not supplied) 139 Remote timer control (not supplied) 298 Cascade temperature sensor (not supplied) 299 Input 0-10 Vdc 300 Burner lit contact (voltage-free contact) 301 Fault contact (voltage-free contact) 302 Remote reset input (230 Volt) 306 Heating system circulating pump (not supplied) 307 Heating system second circulating pump (not supplied)
For connection in cascade (MAX. 5 MODULES)
1. Connect the modules as shown in fig. 32 (example with 4 modules)
fig. 32 - Connection in cascade
A 1st Module B 2nd Module C 3rd Module D 4th Module
2. Carry out all the electrical connections (terminals 4 to 24) on module no. 1
3. On the remaining modules only connect the power supply and possible contacts for:
burner lit (300), fault contact (301) and remote reset input (302).
4. Switch on the power to the entire cascade
5. After the "FH" procedure, check correct operation of the cascade:
Module 1: arrow symbol at top left of the display
Module 2: arrow symbol at bottom right of the display
Module 3: arrow symbol at bottom right of the display
Module 4: arrow symbol at top right of the display
If this does not occur, disconnect the power and check the wiring in fig. 32.
Settings
All adjustments must be made on all the modules.
Possible faults
If the electrical connection of a module is disconnected for any reason, module 1 will ac­tivate fault F70.
If the electrical connection of a module is disconnected for any reason, the next module will activate fault F71.
3.5 Flue connection
Important
The unit is a B23 type with combustion air drawn from the installation room and fume ex­haust by means of a fan (operation with flue under pressure) and must be connected to one of the discharge systems indicated below. Before proceeding with installation, check and carefully comply with the local regulations and provisions. Also comply with the pro­visions concerning the positioning of wall and/or roof terminals and the minimum distanc­es from windows, walls, ventilation openings, etc.
Manifold, ducts and flue must be suitably sized, designed and made in compliance with the current standards. They must be made of suitable materials, i.e. resistant to heat and corrosion, smooth on the inside and hermetic. In particular, joints must be condensate­proof. Also provide for suitable condensate drainage points, connected through a trap to prevent the condensate produced in the flues from running into the generators.
B
The unit is equipped with one (models ENERGY TOP B 80 - 125) or two (mod­els ENERGY TOP B 160 - 250) separate Ø80 flue connections for the two burn- er - exchanger units.
The combustion circuits of the two units are completely independent. When joining the two fume outlets to a single flue or manifold (in case of a single mod­ule or connection in cascade) it is necessary to install a fume anti-backflow val­veon each outlet to prevent operation anomalies or the creation of hazardous conditions. Make sure to use the optional FERROLIkits , provided with special anti-backflow valves.
A
Before carrying out the flue connection, make sure to fill the condensate trap with approx. 0.5 litres of water through the flue connections.
Connection with separate pipes
Separate Ø80 ducts can be connected directly to the unit Insert the seal 1KWMA84A on the Ø80 pipes leaving the unit and make it adhere to the upper wall of the cabinet
Before installation, make sure the maximum permissible length has not been exceeded, by means of a simple calculation:
1. Establish the layout of the system of split flues, including accessories and outlet ter­minals for each of the two burner/exchanger bodies
2. Consult the table 5 and identify the losses in meq (equivalent metres) of every com­ponent, according to the installation position
3. Check that the sum total of losses is less than or equal to the maximum permissible length in table 4.
Table. 4 - Maximum length of separate ducts
Table. 5 - Accessories
4 5 ; 7 8 9 10 11 12
13 14 15 1; 17 18 19 20 21 22 23 24
FFF
F
300
301
95
302
299
139
72
138 298 42
25 2; 27 28 29 30
72B
130/307
306
A
B (
25 2; 27 28 29 30 25 2; 27 28 29 30 25 2; 27 28 29 30 25 2; 27 28 29 30
A B ( 6
Separate ducts
For each single Exchanger/Burner Body
ENERGY TOP B 80 - 160 ENERGY TOP B 125 - 250
Max. permissible length
20 m
eq
10 m
eq
Losses in m
eq
Fume exhaust
Vertical Horizontal
Ø 80 PIPE
1 m M/F 1KWMA83W 1.6 2.0
BEND
45° M/F 1KWMA65W 1.8 90° M/F 1KWMA01W 2.0
PIPE SECTION
with test point 1KWMA70W 0.3
TERMINAL
fumes, wall with antiwind 1KWMA86A 5.0
FLUE
Split air/fumes 80/80 1KWMA84U 5.0
Page 10
ENERGY TOP B
69
EN
cod. 3540S738 - Rev. 00 - 01/2014
Direct connection of Ø80 terminals code 041013X0
Each single module can be connected directly to the terminal kits 041013X0 as given in , even with fig. 33 connection in bank.
Each kit comprises a Ø80 terminal with grille (ref. 3), a seal (ref. 1) and a centring ring (not used in this model). For models ENERGY TOP B 160 - 250 use 2 kits perENERGY
TOP B 80 - 125module, and 1 kit for models .
fig. 33
B
Before installing the flues, fill the trap with approx. 0.5 l. of water through the flue connections.
B
For outside installations make the seal 1 adhere perfectly to the top part of the cabinet, to prevent possible infiltration of rain and atmospheric agents.
Connection with manifolds
To connect one or more modules in bank to a single flue, it is advisable to use the special manifolds (optionals) given in the table. The choice of diameter must be made according to the total power of the bank of units, respecting that given in the table. Use a starting kit for each bank (containing manifold plug and trap) and a suitable number of manifolds (one for each ENERGY TOP B 80 - 125 and two for each ENERGY TOP B 160 - 250).
90° bends and manifold extensions are also available for the flue connection.
Installation examples with modules in line
fig. 34
fig. 35
A - 041026X0 - Starting kit Ø200 B - 041027X0 - Starting kit Ø300 C - 041028X0 - Manifold kit Ø200 in line D - 041029X0 - Manifold kit Ø300 in line
Installation examples with opposed modules
fig. 36
Bank
heating capacity
Manifold diameter
Starting
kit
Manifold
kit
L=500
Manifold
extension
M/F
L=1000
90° bend manifold
Up to 500 kW
200 mm
in line
041026X0
C
041028X0
041019X0 041016X0
opposed
E
041030X0
Up to 1000 kW
300 mm
in line
041027X0
D
041029X0
041036X0 041035X0
opposed
F
041031X0
1
3
(
(
(
Ø.200
(
A
Ø.300
6
B
6
6
6
6
,
Ø.200
A
Page 11
ENERGY TOP B
70
EN
cod. 3540S738 - Rev. 00 - 01/2014
fig. 37
A - 041026X0 - Starting kit Ø200 B - 041027X0 - Starting kit Ø300 E - 041030X0 - Manifold kit Ø200 opposed F - 041031X0 - Manifold kit Ø300 opposed
Fume manifold installation
Fix the fume manifold brackets in the special holes arranged in the modules; see (fig. 38) for side by side modules and (fig. 39) for opposed modules.
fig. 38
fig. 39
Arrange the height and slope of the manifold by means of the special holes in the brack­ets (fig. 40 and fig. 41).
fig. 40
fig. 41
Couple together the fume manifolds and the trap cap using slippery agent or grease; see (fig. 42).
fig. 42
Ø.300
*
B
*
*
*
2G
3G
1G
4G
2G
1G
3G
4G
Page 12
ENERGY TOP B
71
EN
cod. 3540S738 - Rev. 00 - 01/2014
Position the manifolds on the previously fixed brackets (fig. 43) and fix them using the special clamps (fig. 44).
fig. 43
fig. 44
Fix the trap (fig. 45).
fig. 45
Insert the fume dampers (fig. 46), loosening screw “D”, and correctly fit them on the fume manifold. Then tighten screw “D” (fig. 47).
fig. 46
fig. 47
3.6 Condensate drain
B
The boiler has an internal condensate drain trap connected to an internal con­densate outlet manifold.
Condensate outlet connection using one generator
fig. 48 - Condensate drain connection with one generator
A Place the Ø40 pipe 1 (not supplied) on the side of the generator. B Slide the pipe 2 towards the arrow side at least 2-3 cm in order to insert it in the
pipe 1.
1
A
1
B
Page 13
ENERGY TOP B
72
EN
cod. 3540S738 - Rev. 00 - 01/2014
Condensate outlet connection using two or more generators
fig. 49 - Condensate drain connection with several generators
A Place the Ø40 pipe 1 (not supplied) on the side of the generator B Slide the pipe 2 (of each generator) towards the arrow side at least 2-3 cm in
order to insert it in the pipe 1.
4. SERVICE AND MAINTENANCE
All adjustment, conversion, startup and maintenance operations described below must only be carried out by Qualified Personnel (meeting the professional technical require­ments prescribed by current regulations) such as those of the Local After-Sales Techni­cal Service.
FERROLI declines any liability for damage and/or injury caused by unqualified and un­authorised persons tampering with the unit.
4.1 Adjustments
Gas conversion
The unit can operate on natural gas or LPG and is factory-set for use with one of these two gases, as clearly shown on the packing and on the dataplate. Whenever a gas dif­ferent from that for which the unit is arranged has to be used, a conversion kit will be re­quired, proceeding as follows:
1. Disconnect the power supply to the boiler.
2. Using the special key supplied, open the cabinet of the upper exchanger body.
3. Detach the electrical connections from the gas valve controller.
4. Loosen the gas valve (fig. 50 e fig. 51) fixing ring “A”.
5. Undo the two fixing screws "B" and remove the fan assembly as indicated in fig. 50 for the model ENERGY TOP B 80 - 160 and in for fig. 51 the model ENERGY TOP
B 125 - 250.
fig. 50 - model ENERGY TOP B 80 - 160
fig. 51 - model ENERGY TOP B 125 - 250
6. Undo the screws
"C"
and remove fan
"D" (fig. 52
- only model
ENERGY TOP B 125 - 250
)
fig. 52 - model ENERGY TOP B 125 - 250
7. Undo the fixing screws "E" (fig. 53 model ENERGY TOP B 80 - 160 and fig. 54 model ENERGY TOP B 125 - 250) and remove the gas valve.
fig. 53 - model ENERGY TOP B 80 - 160
fig. 54 - model ENERGY TOP B 125 - 250
8. Replace the gas nozzle "F" (see fig. 53 for the model ENERGY TOP B 80 - 160 and fig. 54 the model ENERGY TOP B 125 - 250) with the one contained in the con- version kit, positioning it inside the seal "G" . Refit the parts and check their tight­ness.
9. Modify the parameter for the type of gas:
put the boiler in standby mode
press the DHW buttons (details 1 and 2 - fig. 1) at the same time for 10 sec-
onds: the display shows "P01" flashing.
Press the DHW buttons (details 1 and 2 - fig. 1) toset parameter 00 (for use
with natural gas ) or 01 (for use with LPG).
press the DHW buttons (details 1 and 2 - fig. 1) together for 10 seconds. The
boiler will return to standby mode
10. Apply the label, contained in the conversion kit, near the dataplate.
11. Using a combustion analyser connected to the boiler fume outlet, make sure the CO
2
content in the fumes, with the boiler operating at max. and min. output, com-
plies with that given in the technical data table for the corresponding type of gas.
22
A
B
1
B
B
A
B
B
A
D
C
C
C
2
1
2
1
3
3
E
G
F
G
F
E
Page 14
ENERGY TOP B
73
EN
cod. 3540S738 - Rev. 00 - 01/2014
TEST mode activation Press the heating buttons +/- (details 3 and 4 - fig. 1) together for 5 seconds to activate
TESTmode. The boiler lights at the maximum heating power (Range Rated) set as de-
scribed in the following section. The heating symbol (detail 13 - fig. 1) and DHW symbol (detail 9 - fig. 1) flash; the heat-
ing power will appear alongside.
fig. 55 - TEST mode (heating power = 100%)
To deactivate Test mode, repeat the activation sequence. The TEST mode is automatically disabled in any case after 15 minutes.
Only for model ENERGY TOP B 160 - 250
In TEST mode, press the button (detail 7 - fig. 1) to obtain the following operation:
Top boiler shell on; bottom boiler shell off.
Top boiler shell off; bottom boiler shell on.
Top boiler shell on; bottom boiler shell on.
Heating Capacity Adjustment (RANGE RATED)
A
This is a “RANGE RATED” boiler (according to EN 483) and can be adjusted to the system's thermal requirement by setting the maximum heating capacity for operation in heating mode, as follows:
Put the boiler in TEST mode (see sec. 4.1).
Press the
heating buttons
(details 3 and 4 -
fig. 1
) to increase or decrease the power (min.
= 00 - max. = 100). See the diagram “Heating Capacity Adjustment” (
fig. 56
).
Press the reset button (detail 8 - fig. 1) within 5 seconds and the maximum heating capacity will remain that just set. Exit TEST mode (see sec. 4.1).
A
THE HEATING CAPACITY ADJUSTMENT THUS SET ENSURES KEEPING OF THE EFFICIENCY VALUES DECLARED ON cap. 5.4
Heating power adjustment diagram A = kW - B = Electronic Board Parameter
fig. 56
4.2 Start-up
B
Checks to be made at first lighting, and after all maintenance operations that involved disconnection from the systems or an operation on safety devices or parts of the boiler:
Before lighting the boiler
Open any on-off valves between the boiler and the systems.
Check the tightness of the gas system, proceeding with caution and using a soap and water solution to detect any leaks in connections.
Check correct prefilling of the expansion tank (ref. sec. 5.4).
Fill the water system and make sure all air contained in the boiler and the system has been vented, by opening the air vent valve on the boiler and any vent valves on the system.
Fill the condensate trap and check correct connection of the condensate elimination system.
Make sure there are no water leaks in the system, DHW circuits, connections or boiler.
Check correct connection of the electrical system and efficiency of the earthing system
Make sure the gas pressure value for heating is that required.
Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler
Checks during operation
Turn the unit on as described in sec. 2.3.
Make sure the fuel circuit and water systems are tight.
Check the efficiency of the flue and air-fume ducts while the boiler is working.
Check the correct tightness and functionality of the condensate elimination system and trap.
Make sure the water is circulating properly between the boiler and the systems.
Make sure the gas valve modulates correctly in the heating and domestic hot water production phases.
Check proper boiler lighting by doing several tests, turning it on and off with the room thermostat or remote control.
Using a combustion analyser connected to the boiler fume outlet, check that the CO
2
content in the fumes, with the boiler operating at max. and min. output, corre-
sponds to that given in the technical data table for the corresponding type of gas.
Make sure the fuel consumption indicated on the meter matches that given in the technical data table on sec. 5.4.
Check the correct programming of the parameters and carry out any necessary cus­tomization (compensation curve, power, temperatures, etc.).
4.3 Maintenance
Periodical check
To keep the unit working properly over time, it is necessary to have qualified personnel make an annual check that includes the following tests:
The control and safety devices (gas valve, flow meter, thermostats, etc.) must func­tion correctly.
The fume extraction circuit must be fully efficient.
The airtight chamber must be sealed
The air-fume end piece and ducts must be free of obstructions and leaks
The condensate evacuation system must be efficient with no leakage or obstructions.
The burner and exchanger must be clean and free of scale. When cleaning, do not use chemical products or wire brushes.
The electrode must be free of scale and properly positioned.
The gas and water systems must be airtight.
The water pressure in the cold water system must be about 1 bar; otherwise, bring it to that value.
The circulation pump must not be blocked.
The expansion tank must be filled.
The gas flow and pressure must correspond to that given in the respective tables.
A
The boiler casing, panel and aesthetic parts can be cleaned with a soft damp cloth, possibly soaked in soapy water. Do not use any abrasive detergents and solvents.
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display will flash together with the fault symbol (detail 20 -
fig. 1
) indicating the fault code.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore operation just press the RESET button (detail 8 - fig. 1) for 1 second or RESET on the optional remote timer control if installed; if the boiler fails to start, it is necessary to firstly eliminate the fault.
Other faults (marked with the letter “F”) cause temporary shutdowns that are automati­cally reset as soon as the value returns within the boiler's normal working range, except for fault F37 which is reset by turning the unit off and then on again with button 14 of fig. 1.
!"!#
!$%
$%&'% #
EANH,.EA-,6
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
100
90
80
70
60
50
40
30
20
10
0
0 20 40 60 80 100 120 140 160 180 200 220 240 260
!
80 "# $
12 5" # $
16 0" # $
25 0" # $
Page 15
ENERGY TOP B
74
EN
cod. 3540S738 - Rev. 00 - 01/2014
Table of faults
Table. 6 - List of faults
Fault code Fault Possible cause Cure
A01
No burner ignition
EXCHANGER SAFETY THERMOSTAT ACTIVATED
CHECK THE BOILER SHELL AND CLEAN IT IF NECESSARY
Check the thermostat and replace it if necessary
Check the thermostat wiring No gas Check the regular gas flow to the boiler and that the air has been eliminated from the pipes Ignition/detection electrode fault Check the wiring of the electrode and that it is correctly positioned and free of any deposits Faulty gas valve Check the gas valve and replace it if necessary Insufficient gas supply pressure Check the gas supply pressure Trap blocked Check the trap and clean it if necessary
A02
Flame present signal with burner off
Electrode fault Check the ionisation electrode wiring Card fault Check the card
A03
Overtemperature protection activated
Heating sensor damaged Check the correct positioning and operation of the heating sensor No water circulation in the system Check the circulating pump Air in the system Vent the system
A04
Fume extraction duct safety device activated Fault F07 generated 3 times in the last 24 hours See fault F07
A05
Fan protection activated Fault F15 generated for 1 hour (consecutive) See fault F15
A06
No flame after ignition stage (6 times in 4 minutes)
Ionisation electrode fault Check the position of the ionisation electrode and replace it if necessary Flame unstable Check the burner Gas valve Offset fault Check the Offset adjustment at minimum power air/fume ducts obstructed Remove the obstruction from the flue, fume extraction ducts and air inlet and terminals Trap blocked Check the trap and clean it if necessary
F07
High fume temperature
Flue partially obstructed or insufficient
Check the efficiency of the flue, fume extraction ducts and outlet terminal
Fume sensor position Check the correct positioning and operation of the fume sensor
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F11
Return sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F12
DHW sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F13
Fume sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
F15
Fan fault
No 230V power supply Check the 3-pin connector wiring Tachometric signal interrupted Check the 5-pin connector wiring Fan damaged Check the fan
F34
Supply voltage under 170V Electric mains trouble Check the electrical system
F35
Faulty mains frequency Electric mains trouble Check the electrical system
F37
Flowswitch or pressure switch contact open
Insufficient system pressure or circulation Check the system water pressure or for air in the system Circulating pump not working Check the circulating pump Wrong card parameter setting Check the card parameter and modify it if necessary
F38
Flowswitch contact blocked closed Flowswitch dirty or blocked Clean the flowswitch or replace it if necessary
F39
External probe fault
Probe damaged or wiring shorted Check the wiring or replace the sensor Probe disconnected after activating the sliding temperature Reconnect the external probe or disable the sliding temperature
A41
Sensor positioning Delivery sensor disconnected from the pipe Check the correct positioning and operation of the heating sensor
A42
Heating sensor fault Sensor damaged Replace the sensor
F42
Heating sensor fault Sensor damaged Replace the sensor
F50
Cascade temperature sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted Wiring disconnected
A61
Controller DBM12 fault Controller DBM12 internal error Check the earth connection and replace the controller if necessary.
A62
No communication between controller and gas valve
Controller not connected Connect the controller to the gas valve Valve damaged Replace the valve
A63 A64 A65 F66
Controller DBM12 fault Controller DBM12 internal error Check the earth connection and replace the controller if necessary.
Page 16
ENERGY TOP B
75
EN
cod. 3540S738 - Rev. 00 - 01/2014
5. TECHNICAL DATA AND CHARACTERISTICS
Key of figures cap. 5
7 Gas inlet 10 System delivery 11 System return 14 Safety valve 16 Fan 22 Burner 29 Fume outlet manifold 32 Heating circulating pump 36 Automatic air vent 38 Flow switch 42 DHW temperature sensor (not supplied) 44 Gas valve 72 Room thermostat (not supplied) 72b Second room thermostat (not supplied) 81 Ignition electrode 82 Detection electrode 95 Diverter valve (not supplied)
a = Heating phase b = DHW phase c = Neutral
NOTE: For valves with 2 wires and spring return, use the connections B and C 98 Switch 114 Water pressure switch
5.1 Dimensions and connections
Model ENERGY TOP B 80 - 125
fig. 57 - Dimensions and connections model ENERGY TOP B 80 - 125
130 DHW circulating pump (not supplied) 138 External probe (not supplied) 139 Remote timer control (not supplied) 154 Condensate drain pipe 179 Non-return valve 186 Return sensor 191 Fume temperature sensor 193 Trap 196 Condensate tray 215 Air inlet reducer 220 Ignition card 252 3-way drain and shutoff cock 253 Shutoff cock 278 Double sensor (Safety + Heating) 298 Cascade temperature sensor (not supplied) 299 Input 0-10 Vdc 300 Burner lit contact (voltage-free contact) 301 Fault contact (voltage-free contact) 302 Remote reset input (230 Volt) 306 Heating system circulating pump (not supplied) 307 Heating system second circulating pump (not supplied) 345 Exchanger safety thermostat
Model ENERGY TOP B 160 - 250
fig. 58 - Dimensions and connections model ENERGY TOP B 160 - 250
1 = Gas inlet 2 = Heating system delivery 3 = Heating system return
120 132
110.5
Ø80
500
450
110
1700
475
330
185
105
120
180
2
1
3
Ø80
1000
450
110
1700
475
330
185
105
120
180
2
1
3
Ø80
250
250
500
120 132
110.5
120
380
252
Page 17
ENERGY TOP B
76
EN
cod. 3540S738 - Rev. 00 - 01/2014
5.2 General view and main components
Model ENERGY TOP B 80 - 125
fig. 59 - General view model ENERGY TOP B 80 - 125
Model ENERGY TOP B 160 - 250
fig. 60 - General view model ENERGY TOP B 160 - 250
10
7
11
10
7
11
193
32
196
82
220
44
29
215
36
16
278
252
253
154
179
14
186
114
38
81
345
191
10
11
7
10
11
7
Page 18
ENERGY TOP B
77
EN
cod. 3540S738 - Rev. 00 - 01/2014
5.3 Water circuit
Model ENERGY TOP B 80 - 125
fig. 61 - Water circuit model ENERGY TOP B 80 - 125
Model ENERGY TOP B 160 - 250
fig. 62 - Plumbing circuit model ENERGY TOP B 160 - 250
16
36
44
81
82
29
196
278
22
186
154
193
252
253
32
14
179
38
345
11
10
7
114
10
7
11
Page 19
ENERGY TOP B
78
EN
cod. 3540S738 - Rev. 00 - 01/2014
5.4 Technical data table
Factory settings
A
The unit is factory-set to 80% power.
Technical data
The column on the right gives the abbreviation used on the dataplate.
5.5 Diagrams
Circulating pump head / pressure losses
Pressurelosses modelENERGY TOP B 80 - 160
fig. 63
A Boiler pressure losses 1 - 2 - 3 Circulating pump speed
Pressurelosses modelENERGY TOP B 125 - 250
fig. 64
A Boiler pressure losses 1 - 2 - 3 Circulating pump speed
Data Unit ENERGY TOP B 80 ENERGY TOP B 125 ENERGY TOP B 160 ENERGY TOP B 250
Max. heating capacity kW 75.0 116.0 150.0 232.0 (Q)
Min. heating capacity kW 17.0 25.0 17.0 25.0 (Q)
Max. Heat Output in heating (80/60°C) kW 73.5 113.7 147.0 227.4 (P)
Min. Heat Output in heating (80/60°C) kW 16.7 24.6 16.7 24.6 (P)
Max. Heat Output in heating (50/30°C) kW 79.5 123.0 159.0 246.0
Min. Heat Output in heating (50/30°C) kW 18.3 26.9 18.3 26.9
Efficiency Pmax (80-60°C) % 98.0 98.0 98.0 98.0
Efficiency Pmin (80-60°C) % 98.5 98.5 98.5 98.5
Efficiency Pmax (50-30°C) % 106 106 106 106
Efficiency Pmin (50-30°C) % 107.5 107.5 107.5 107.5
Efficiency 30% % 109 109 109 109
Gas supply pressure G20 mbar 20 20 20 20
Max. gas delivery G20
m
3
/h
7.94 12.38 15.88 24.76
Min. gas delivery G20
m
3
/h
1.8 2.65 1.8 2.65
Gas supply pressure G31 mbar 37 37 37 37
Max. gas delivery G31 kg/h 5.87 9.08 11.74 18.16
Min. gas delivery G31 kg/h 1.33 1.96 1.33 1.96
Efficiency class Directive 92/42 EEC -
NOx emission class - 5 5 5 5 (NOx)
Max. working pressure in heating bar 6 6 6 6 (PMS)
Min. working pressure in heating bar 0.8 0.8 0.8 0.8
Max. heating temperature °C 95 95 95 95 (tmax)
Heating water content litres 13 15 26 30
Protection rating IP X5D X5D X5D X5D
Power supply voltage V/Hz 230V/50Hz 230V/50Hz 230V/50Hz 230V/50Hz
Electrical power input W 285 390 570 780
Empty weight kg 110 115 190 210
Type of unit B23
PIN CE 0461BS0879
1
2
3
0
0 1 2 3 4 5 6
1
2
3
4
5
6
7
8
9
10
H (m)
m
3
/h
A
1
2
3
0 1 2 3 4 5 6
0
1
2
3
4
5
6
7
8
9
10
m3/h
H (m)
A
Page 20
ENERGY TOP B
79
EN
cod. 3540S738 - Rev. 00 - 01/2014
5.6 Wiring diagram
fig. 65 - Wiring diagram
A Only model ENERGY TOP B 160 - 250
A
Important: Before connecting the room thermostat or the remote timer con­trol, remove the jumper on the terminal block
-J-J
230V 50KL
16
278
191
186
16
32
V1
V2
44
X1
X3
X2
98
L
N
12345
;
789
10
11
12
123
45;
12345
;
789
10
*M+, 3O15A
-J-J
6BC12P(
16
278
191
186
114
16
32
V1
V2
44
X1
X3
X2
A
25 2; 27 28 29 30
1
2
3
4
123
45;
6+D12(
X01 X04 X03
X05
13 14 15 1; 17 18 19 20 21 22 23 24
299
139
72
138 298 42
4 5 ; 7 8 9 10
11 12
FFF
F
300
301
95
302
130/307
72B
@ < $
6BC12E(
6BC12P( 6BC12E(
306
38
11438
82
81
345
82
81
345
Page 21
Declaración de conformidad
El fabricante: FERROLI S.p.A.
Dirección: Via Ritonda 78/a 37047 San Bonifacio (Verona)
declara que este equipo satisface las siguientes directivas CEE:
• Directiva de Aparatos de Gas 2009/142
• Directiva de Rendimientos 92/42
• Directiva de Baja Tensión 2006/95
• Directiva de Compatibilidad Electromagnética 2004/108
Presidente y representante legal
Caballero del Trabajo
Dante Ferroli
ES
Dichiarazione di conformità
Il costruttore: FERROLI S.p.A.
Indirizzo: Via Ritonda 78/a 37047 San Bonifacio VR
dichiara che questo apparecchio è conforme alle seguenti direttive CEE:
• Direttiva Apparecchi a Gas 2009/142
• Direttiva Rendimenti 92/42
• Direttiva Bassa Tensione 2006/95
• Direttiva Compatibilità Elettromagnetica 2004/108
Presidente e Legale rappresentante
Cav. del Lavoro
Dante Ferroli
IT
Uygunluk beyani
ømalatçi: FERROLI S.p.A.
Adres: Via Ritonda 78/a 37047 San Bonifacio VR
bu cihazin; asagida yer alan AET(EEC) yönergelerine uygunluk içinde oldugunu beyan etmektedir:
• 2009/142 Gazla çalistirilan üniteler için Yönetmelik
• 92/42 Randiman/Verimlilik Yönetmeligi
• Yönerge 2006/95, Düsük Voltaj
• 2004/108 Elektromanyetik Uygunluk Yönetmeligi
Baskan ve yasal temsilci
øú. Dep.
Dante Ferroli
TR
Declaration of conformity
Manufacturer: FERROLI S.p.A.
Address: Via Ritonda 78/a 37047 San Bonifacio VR Italy
declares that this unit complies with the following EU directives:
• Gas Appliance Directive 2009/142
• Efficiency Directive 92/42
• Low Voltage Directive 2006/95
• Electromagnetic Compatibility Directive 2004/108
President and Legal Representative
Cav. del Lavoro
Dante Ferroli
EN
Page 22
Ⱦɟɤɥɚɪɚɰɿɹɩɪɨɜɿɞɩɨɜɿɞɧɿɫɬɶ
ȼɢɪɨɛɧɢɤ: ɤɨɦɩɚɧiɹ FERROLI S.p.A.
ɡɚɚɞɪɟɫɨɸ: Via Ritonda 78/a 37047 San Bonifacio VR
ɡɚɹɜɥɹɽ, ɳɨɰɟɣɚɩɚɪɚɬɜɿɞɩɨɜɿɞɚɽɭɫɿɦɧɚɫɬɭɩɧɢɦȾɢɪɟɤɬɢɜɚɦȯɋ:
• Ⱦɢɪɟɤɬɢɜɚȯɋ 2009/142 (Ⱦɢɪɟɤɬɢɜɚɩɪɨɡɛɥɢɠɟɧɧɹɩɪɚɜɨɜɢɯɧɨɪɦɤɪɚʀɧ-ɱɥɟɧɿɜȯɋɞɥɹɝɚɡɨ-ɪɨɡɯɿɞɧɢɯ
ɭɫɬɚɧɨɜɨɤ)
Ⱦɢɪɟɤɬɢɜɚȯɋ 92/42 (ȾɢɪɟɤɬɢɜɚɩɪɨɜɢɦɨɝɢɄɉȾɞɥɹɧɨɜɢɯɜɨɞɨɝɪɿɣɧɢɯɤɨɬɥɿɜ, ɩɪɚɰɸɸɱɢɯɧɚɪɿɞɢɧɧɨɦɭ
ɿɝɚɡɨɩɨɞɿɛɧɨɦɭɩɚɥɢɜɿ)
• Ⱦɢɪɟɤɬɢɜɚȯɋ 2006/95 (Ⱦɢɪɟɤɬɢɜɚɩɪɨɡɛɥɢɠɟɧɧɹɩɪɚɜɨɜɢɯɧɨɪɦɤɪɚʀɧ-ɱɥɟɧɿɜȯɋ, ɳɨɫɬɨɫɭɸɬɶɫɹ
ɟɥɟɤɬɪɨɨɛɥɚɞɧɚɧɧɹ, ɹɤɟɜɢɤɨɪɢɫɬɨɜɭɽɬɶɫɹɜɩɟɜɧɢɯɦɟɠɚɯɧɚɩɪɭɝɢ)
Ⱦɢɪɟɤɬɢɜɚȯɋ 2004/108 (Ⱦɢɪɟɤɬɢɜɚɩɪɨɩɪɢɜɟɞɟɧɧɹɭɜɿɞɩɨɜɿɞɧɿɫɬɶɡɚɤɨɧɨɞɚɜɫɬɜɤɪɚʀɧ-ɱɥɟɧɿɜɜɨɛɥɚɫɬɿ
ɟɥɟɤɬɪɨɦɚɝɧɿɬɧɨʀɫɭɦɿɫɧɨɫɬɿ).
ɉɪɟɡɢɞɟɧɬɿɡɚɤɨɧɧɢɣɩɪɟɞɫɬɚɜɧɢɤ
Ʉɚɜɚɥɟɪɩɪɚɰɿ
Dante Ferroli
UA
Ⱦɟɤɥɚɪɚɰɢɹɫɨɨɬɜɟɬɫɬɜɢɹ
ɂɡɝɨɬɨɜɢɬɟɥɶ: FERROLI S.p.A.,
ɚɞɪɟɫ: Via Ritonda 78/a 37047 San Bonifacio VR,
ɡɚɹɜɥɹɟɬ, ɱɬɨɧɚɫɬɨɹɳɟɟɢɡɞɟɥɢɟɫɨɨɬɜɟɬɫɬɜɭɟɬɫɥɟɞɭɸɳɢɦɞɢɪɟɤɬɢɜɚɦ CEE:
Ⱦɢɪɟɤɬɢɜɚɩɨɝɚɡɨɜɵɦɩɪɢɛɨɪɚɦ 2009/142
ȾɢɪɟɤɬɢɜɚɩɨɄ.ɉ.Ⱦ. 92/42
Ⱦɢɪɟɤɬɢɜɚɩɨɧɢɡɤɨɦɭɧɚɩɪɹɠɟɧɢɸ 2006/95
Ⱦɢɪɟɤɬɢɜɚɩɨɷɥɟɤɬɪɨɦɚɝɧɢɬɧɨɣɫɨɜɦɟɫɬɢɦɨɫɬɢ 2004/108
ɉɪɟɡɢɞɟɧɬɢɭɩɨɥɧɨɦɨɱɟɧɧɵɣɩɪɟɞɫɬɚɜɢɬɟɥɶ
Ʉɚɜɚɥɶɟɪɟɞɟɥɶɥɚɜɨɪɨ (ɩɨɱɟɬɧɵɣɬɢɬɭɥ, ɩɪɢɫɭɠɞɚɟɦɵɣ
ɝɨɫɭɞɚɪɫɬɜɨɦɡɚɡɚɫɥɭɝɢɜɪɭɤɨɜɨɞɫɬɜɟɩɪɨɦɵɲɥɟɧɧɨɫɬɶɸ)
Dante Ferroli
RU
DeclaraĠie de conformitate
Producător: FERROLI S.p.A.
Adresă: Via Ritonda 78/a 37047 San Bonifacio VR
declară că acest aparat este în conformitate cu următoarele directive CEE:
• Directiva Aparate cu Gaz 2009/142
• Directiva Randament 92/42
• Directiva Joasă Tensiune 2006/95
• Directiva Compatibilitate Electromagnetică 2004/108
Preúedinte úi reprezentant legal
Cavaler al Muncii
Dante Ferroli
RO
Déclaration de conformité
Le constructeur : FERROLI S.p.A.
Adresse: Via Ritonda 78/a 37047 San Bonifacio VR
déclare que cet appareil est conforme aux directives CEE ci-dessous:
• Directives appareils à gaz 2009/142
• Directive rendements 92/42
• Directive basse tension 2006/95
• Directive Compatibilité Electromagnétique 2004/108
Président et fondé de pouvoirs
Cav. du travail
Dante Ferroli
FR
Page 23
Page 24
Page 25
FERROLI S.p.A.
Via Ritonda 78/a
37047 San Bonifacio - Verona - ITALY
www.ferroli.it
Loading...