Ferroli Bluehelix HiTech RRT 24/28/34 C INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE (Cod. 3541V691 — Rev. 00 - 04/2022)

Page 1

BlueHelix HiTech RRT C

CE INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE

"BLUEHELIX HITECH RRT 24C" GC N° 47-267-74 "BLUEHELIX HITECH RRT 28C" GC N° 47-267-75 "BLUEHELIX HITECH RRT 34C" GC N° 47-267-76

Page 2

BlueHelix HiTech RRT C

Ferroli

  • Read the warnings in this instruction booklet carefully since they provide important information on safe installation, use and maintenance.
  • This instruction booklet is an integral and essential part of the product and must be kept with care by the user for future reference.
  • If the unit is sold or transferred to another owner or if it is to be moved, always make sure the booklet stays with the boiler so that it can be consulted by the new owner and/or installer.
  • Installation and maintenance must be carried out by professionally qualified personnel, according to current regulations and the manufacturer's instructions.
  • Incorrect installation or inadequate maintenance can result in damage or injury. The manufacturer declines any liability for damage caused by errors in installation and use or by failure to follow the instructions provided.
  • Before carrying out any cleaning or maintenance operation, disconnect the unit from the power supply using the system switch and/or the special cut-off devices.
  • In case of a fault and/or poor operation, deactivate the unit and do not try to repair it or directly intervene. Contact professionally qualified personnel. Any repair/replacement of the products must only be carried out by qualified personnel using genuine parts. Failure to comply with the above can compromise the safety of the unit.

  • Periodic maintenance performed by qualified personnel is essential in order to ensure proper operation of the unit.
  • This unit must only be used for its intended purpose. Any other use is deemed improper and the refore hazardous.
  • After unpacking, check the good condition of the contents. The packing materials are potentially hazardous and must not be left within the reach of children.
  • The unit can be used by children aged at least 8 years and by persons with reduced physical, sensory or mental capabilities, or lacking experience or the necessary knowledge, only if under supervision or they have received instructions on its safe use and the related risks. Children must not play with the unit. Cleaning and maintenance intended to be done by the user can be carried out by children aged at least 8 years only if under supervision.
  • In case of doubt, do not use the unit. Contact the supplier.
  • The unit and its accessories must be appropriately disposed of in compliance with current regulations.
  • The images given in this manual are a simplified representation of the product. In this representation there may be slight and insignificant differences with respect to the product supplied.

This symbol indicates "CAUTION" and is placed next to all safety warnings. Strictly follow these instructions in order to avoid danger and damage to persons, animals and things

This symbols calls attention to a note or important notice.

This symbol, which is used on the product, packaging or documents, means that at the end of its useful life, this product must not be collected, recycled or disposed of together with domestic waste.

Improper management of electric or electronic waste can lead to the leakage of hazardous substances contained in the product. For the purpose of preventing damage to health or the environment, users are kindly asked to separate this equipment from other types of waste and to ask for it to be dealt with by the municipal waste service or dealer under the conditions and according to the methods set down in national and international laws transposing the Directive 2012/19/EU.

Separate waste collection and recycling of unused equipment helps to save natural resources and to guarantee that this waste is processed in a manner that is safe for health and the environment.

For more information about how to collect electric and electronic equipment and appliances, please contact your local Counci or Public Authority competent to issue the relevant permits.

The CE marking certifies that the products meet the essential requirements of the relevant directives in force.

The declaration of conformity may be requested from the manufacturer.

COUNTRIES OF DESTINATION: GB

∎æ

Page 3
1 Operating instructions 4
1.1 Introduction 4
1.2 Control panel 4
1.3 Connection to the power supply, switching on and off 7
1.4 Adjustments 10
2 Installation 18
2.1 General Instructions 18
2.2 Place of installation 19
2.3 Plumbing connections 19
2.4 Gas connection 22
2.5 Electrical connections 23
2.6 Fume ducts 25
2.7 Condensate drain connection 30
3 Service and maintenance 32
3.1 Adjustments 32
3.2 Commissioning
3.3 Maintenance
3.4 Troubleshooting 46
4 Technical data and characteristics51 1
4.1 Dimensions and connections 1
4.2 General view 2
4.3 Hydraulic circuit 2
4.4 Technical data table 3
4.5 Diagrams 7
4.6 Wiring diagram 3
Ferroli
Page 4

1. Operating instructions

1.1 Introduction
Dear Customer,

BlueHelix HiTech RRT C is a high-efficiency, low emissions premix condensing heat generator with heat exchanger in s/steel and incorporated DHW production, equipped with a microprocessor control system.

It can use Natural Gas (G20), Liquefied Gas (G30-G31), Propane Air (G230) and, thanks to the "Hydrogen plug-in" system, it self adjusts to also work with mixtures of natural gas and hydrogen (Natural Gas/Hydrogen mixtures 80%/ 20%), that will soon arrive in Europe to fight global warming.

The sealed chamber unit is suitable for indoor installation or outdoors in a partially protected place (according to EN 15502 ) with temperatures to -5°C.

1.2 Control panel

fig. 1- Control panel

Panel legend fig. 1

  • 1 DHW temperature setting decrease button
  • 2 DHW temperature setting increase button
  • 3 Heating system temperature setting decrease button
  • 4 Heating system temperature setting increase button
  • 5 Display
  • 6 Return button
  • 7 "Winter", "Summer", "Unit OFF", "ECO", "COMFORT" mode selection button
  • Eco mode (Ø) DHW mode
  • 10 Summer/Winter mode
  • 11 Menu / confirm button
  • 12 System pressure
  • 13 Heating mode
  • 14 Burner lit

ğ

15 "Key lock" on

Page 5
Indication during operation
Heating

A heating request (generated by the Room Thermostat or Remote Timer Control) is indicated by the flashing radiator symbol.

When the burner is lit, the flame symbol appears and the 3 levels indicate the actual intensity.

Ferroli

DHW (domestic hot water)

A DHW request (generated by hot water draw-off) is indicated by the flashing faucet icon.

When the burner is lit, the flame symbol appears and the 3 levels indicate the actual intensity.

Page 6
Comfort

In Comfort mode (restoration of boiler internal temperature) the flame symbol appears while the faucet flashes.

Frost protection

In frost protection mode (flow temperature below 5°C) the flame symbol appears.

Fault

In case of a fault, the display shows the fault code with different graphics depending on the type

A-type fault (fig. 5): To unlock the boiler in the presence of this type of fault, press the button U until the message "Confirm?" appears. Then confirm with the button

F-type fault (fig. 4): A fault which will be automatically reset after the problem has been eliminated.

Message-type fault (fig. 6): The fault is such as not to compromise boiler operation. The message disappears when the problem is eliminated.

Page 7

1.3 Connection to the power supply, switching on and off

Boiler not electrically powered

To avoid damage caused by freezing during long idle periods in winter, it is advisable to drain all the water from the boiler.

Boiler electrically powered

Electrically power to the boiler.

fig. 7- Switching on / Software version

fig. 8- Vent with fan on

  • During the first 5 seconds the display shows the software version of the board and display (fig. 7)
  • During the first 5 seconds the display shows the software version of the board and display (iig. 7). For the following 20 seconds the display will show FH which identifies the heating system air venting cycle with the fan running (fig. 8).
  • In the next 280 seconds, the venting cycle continues with the fan off (fig. 9).
  • Open the gas valve ahead of the boiler
  • When the message Fh disappears, the boiler is ready to operate automatically whenever hot water is drawn or in case of a room thermostat request

To interrupt the venting phase (FH or Fh), keep the button pressed until the message " Stop? " appears. Then confirm with the button

fig. 10

Page 8
Turning the boiler off and on

Changing from one mode to another is possible by repeatedly pressing the button U, following the sequence shown in fig. 11.

A ="Summer" mode - B = "Winter" mode - C = "Off" mode

To turn the boiler off, repeatedly press the button () until detail C of fig. 11 is displayed.

fig. 11- Turning the boiler off

When the boiler is turned off, the PCB is still powered. DHW and heating are disabled. The frost protection system remains on. To relight the boiler, press the button ().

The boiler will be immediately ready in Winter and DHW mode.

The frost protection system does not work when the power and/or gas to the unit are turned off. To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all water from the boiler, the DHW circuit and the heating system water; or drain just the DHW circuit and add a suitable antifreeze to the heating system, as prescribed in sec. 2.3.

Page 9

1.4 Adjustments

Winter/summer switchover

Repeatedly press the button U until the summer symbol (sun) appears, with the word "OFF" for heating (detail 10 - fig. 1): the boiler will only deliver hot water. The frost protection system remains on.

To reactivate the winter mode, repeatedly press the button () until the snowflake appears.

Ferroli

Heating temperature adjustment

Use the heating buttons (details 3 and 4 - fig. 1) to adjust the temperature from a minimum of 20°C to a maximum of 80°C. The maximum value can be changed inside the parameters menu [TSP] via parameter P40.

Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a minimum of 40°C to a maximum of 55°C. The maximum value can be changed inside the parameters menu [TSP] via parameter P46.

fig. 15

If little water is drawn and/or with a high water inlet temperature, the DHW outlet temperature may differ from the set temperature.

Page 10
Room temperature adjustment (with optional room thermostat)

Using the room thermostat, set the temperature required in the rooms. If the room thermostat is not installed, the boiler will keep the system at the set system delivery setpoint temperature.

Room temperature adjustment (with optional remote timer control)

Using the remote timer control, set the required temperature in the rooms. The boiler will adjust the system water according to the required room temperature. For operation with remote timer control, please refer to the relevant instruction manual.

ECO/COMFORT selection

The unit has a function that ensures fast hot water delivery and maximum comfort for the user. When this function is active ( COMFORT mode), the water in the boiler is kept at temperature, thus giving the immediate availability of hot water from the boiler when the faucet is turned on, avoiding waiting times.

The COMFORT function can be disabled by the user ( ECO mode) by pressing the button \bigcup for 2 seconds. In ECO mode the display activates the symbol (detail 12 - fig. 1). To activate COMFORT mode press the button \bigcup again for 2 seconds; the symbol disappears.

Main menu [MENU]

Pressing the button main displays the main menu of the boiler [MENU] shown in fig. 16.

The desired items can be selected with the buttons ----- and ----- heating.

To access the menus contained in the navigation menu [MENU] , press the button a after selecting the desired item.

  • [Service] Menu reserved for the installer See "Installer menu [SERVICE]" on page 12.
  • [Diagnostic] Provides information on boiler status, in real time. See "Boiler information menu [Diagnostic]" on page 13.
  • [Counters] Boiler counters. See "Boiler counters menu [Counters]" on page 14.
  • [Alarm] Storage of last faults that occurred in the boiler. See "Boiler faults menu [Alarm]" on page 14.
  • [Display] For doing the display settings. See "Display adjustment menu [Display]" on page 15.

fig. 16- Main menu

Page 11

Ferroli

Installer menu [SERVICE]

After selecting the installer menu [Service] , press the button E . To continue, enter the password " 1234 ". Use the buttons and — DHW to set the cell value, and the buttons and — heating to shift position (fig. 17).

fig. 17- Password entry

Confirm with the button ______to access the installer menu[SERVICE] screen where the following menus are available:

  • [TSP] Menu for modifying transparent parameters
  • [Test] Activation of boiler Test mode.
  • [OTC] Setting of climatic curves for adjustment with external probe.
  • [Zone] Settings of climatic curves of additional zones.
  • [Auto Setup] This menu is used to activate calibration. Visible only with parameter b27 set to 5.
SERVICE
TSP
Test ۲
ОТС ۲
Zone ۲
Auto Setup ٢
fig. 18
Page 12

Boiler information menu [Diagnostic]

This menu provides the information, in real time, of the various sensors present in the boiler.

To access it, press the button from the main screen, select the item [Diagnostic] and confirm with the button

fig. 19

Table 1 - Description - Boiler information menu [Diagnostic]

Parameter displayed Description Range
[CH 1 temp] NTC Flow sensor (°C) 0 ÷ 125 °C
[CH 2 temp] NTC Return sensor (°C) 0 ÷ 125 °C
[DHW temp] NTC DHW sensor (storage tank probe) (°C) 0 ÷ 125 °C
[Ext temp] NTC External sensor (°C) +70 ÷ -30°C
[Fume temp] NTC Fume sensor (°C) 0 ÷ 125 °C
[Fan rpm] Actual fan rpm 0 ÷ 9999 RPM
[Pump speed] Actual modulating circulating pump speed (%) 00% = Min., 100% = Max.
[Power] Actual burner power (%) 0 ÷ 100 %
[DHW flow] Actual DHW draw (I/min) 00 ÷ 99 l/min
[Water Pressure] Actual system water pressure (bar) 0.0 ÷ 9.9 bar
[Flame] Flame status ÷ 255

If the sensor is damaged or disconnected, the display will show dashes (--).

To return to the main screen, repeatedly press the button O or wait for automatic switching after 15 minutes.

Page 13
Boiler counters menu [Counters]

The system counters are displayed in this menu:

[Burner]

Burner operation total hours.

[Ignition ok] Number of successful ignitions

[Ignition error] Number of failed ignitions.

[CH pump time] Pump operation hours in heating

[DHW pump time]

pump operation hours in DHW.

Burner
Ignition ok
Ignition error
CH pump time
Ignition ok
Ignition error
CH pump time
0h Burner
Ignition error
CH pump time
3 Ignition ok
CH pump time 0 Ignition error
h CH pump time
DHw pump time h DHW pump time

fig. 20

Boiler faults menu [Alarm]

The card can store the last 10 faults. Alarm 1 represents the most recent fault that occurred.

The codes of the faults saved are also displayed in the relevant menu of the Remote Timer Control.

Press the buttons + and - Heating to scroll the list of faults. Cancel is the last item in the list and which, once selected and confirmed with the button _____, allows all the faults history to be reset.

To exit the Boiler faults menu [ALARM] , press the button O repeatedly until reaching the main screen or wait for automatic exit after 15 minutes.

ALARM ALARM
Alarm 1 27 Alarm 4
Alarm 2 37 Alarm 5
Alarm 3 12 Alarm 6
Alarm 4 13 Alarm 7
Alarm 5 - Alarm 8 -
Alarm 6 - Alarm 9
Alarm 7 - Alarm 10
Alarm 8 Cancel -

fig. 21

Page 14
Display adjustment menu [Display]

In this menu it is possible to set some display parame-

[Contrast] - Contrast adjustment

[Brightness] - Brightness adjustment

[Backlight time] - Display lighting duration

[Lock time]* - Key lock

After keypad inactivity for a time equal to the set value (minutes), the symbol r appears and the buttons are inhibited

To reactivate the keypad, press the bu-tions () and simultaneously until the symbol sindi sindi aneousiy un symbol disappears (about 2 sec.).

* This function is available from version DSP FW 1.03

[Reset] - Restore factory values

Sliding Temperature

When the external probe (optional) is installed, the boiler adjustment system works with "Sliding Temperature". In this mode, the heating system temperature is regulated according to weather conditions, to ensure high comfort and energy efficiency throughout the year. In particular, as the outside temperature increases the system flow temperature decreases according to a specific "compensation curve".

With "Sliding Temperature", the temperature set using the heating buttons (details 3 and 4 - fig. 1) becomes the maximum system flow temperature. It is advisable to set a maximum value to allow system adjustment throughout its useful operating range.

The boiler must be adjusted at the time of installation by qualified personnel. However, the user can make any further adjustments necessary to optimize comfort levels.

Compensation curve and curve offset

From the main screen, press the button to access the navigation menu [MENU] Using the buttons + and heating select the installer menu [SERVICE] and confirm with the button _____. Enter the password (see "Installer menu [SERVICE]" on page 12 ) and press the button _____. Using the buttons _____ and ____ heating select the menu Climatic curves setting [OTC] and confirm by pressing the button

Curve: select this item and use the buttons + and ---- DHW to adjust the desired curve f

By adjusting the curve to 0, the sliding temperature adjustment is disabled (see fig. 24).

  • Offset: Access this sub-menu to access parallel offset of the curves using the buttons + and — DHW Refer to fig 25 for the chara - unio
  • OFF: This item gives access to the "external temperature shutdown" value. Use the buttons + and - DHW to modify the value (from to 40°C), if set to 0 the function is disabled. Ignition occurs when the temperature of the external probe is more than 2°C lower than the set temperature.

Page 15

Ferroli

To exit the Climatic curves setting [OTC] menu, press the button () repeatedly until reaching the main screen.

If the room temperature is lower than the desired value, it is advisable to set a higher order curve and vice versa. Proceed by increasing or decreasing in steps of one and check the result in the room.

05 80 70 60 50 40 30 fig. 24- Compensation curves

Adjustments from Remote Timer Control

If the boiler is connected to the Remote Timer Control (optional), the previously described adjustments are managed as described in table 2

Table 2
Heating temperature adjustment Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
DHW temperature adjustment Adjustment can be made from the Remote Timer Control menu and the boiler control panel.
Summer/Winter Switchover Summer mode has priority over a possible Remote Timer Control heating demand.
On disabling DHW from the Remote Timer Control menu, the boiler selects Economy mode.
In this condition, the eco/comfort button on the boiler panel is disabled.
Eco/Comfort selection By enabling DHW from the Remote Timer Control menu, the boiler selects the Comfort mode (if previously enabled from the boiler panel). In this condition it is possible select one of the two modes on the boiler panel.
Sliding Temperature You can make all the adjustments by using the remote timer control.
System water pressure adjustment

The filling pressure, with system cold, read on the boiler water gauge (detail 2 - fig. 26) must be approx 1.0 bar. If the system pressure falls below minimum values, the boiler stops and fault F37 is displayed.

Once the system pressure is restored, the boiler will activate the 300-second air venting cycle, indicated on the display by Fh.

To avoid boiler shutdown, it is advisable to periodically check (with system cold) the pressure on the pressure gauge or on the display (detail 12 - fig. 1). In case of a pressure below 0.8 bar, it is advisable to restore it

Display Description Operation
F40 High pressure The boiler stops
• 2.3 bar Pressure slightly high The boiler works at reduced power
Page 16
Display Description Operation
✓ 1.2 bar Optimum pressure Normal operation
• 0.7 bar Pressure slightly low
(The indication with the symbol
is visible only if parameter b09 is set
to 1 ).
The boiler continues to work.
It is advisable to refill the system as soon as possible.
F37 Low pressure The boiler stops
System draining

The drain cock ring nut is located under the safety valve inside the boiler.

To drain the system, turn the ring nut (ref. 3 - fig. 26) counter-clockwise to open the cock. Do not use any tools; use hands only.

To drain only the water in the boiler, first close the shut-off valves between the system and boiler before turning the ring nut.

To connect the safety valve to a disposal system, install the kit supplied (details 1 and 2 - fig. 26).

fig. 26

Page 17

2. Installation

2.1 General Instructions

BOILER INSTALLATION MUST ONLY BE CARRIED OUT BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIPTIONS OF THE TECHNICAL STANDARDS (BS), ANY LOCAL REGULATIONS AND THE RULES OF PROPER WORKMANSHIP.

Incorrect installation can cause damage or injury for which the manufacturer declines any responsibility.

Installation of this unit must be carried out in strict compliance with the present instructions and the following regulations applicable in Great Britain.

Gas Safety Regulations (Installations & Use).

Local Building Regulations..

The Building Regulations (Part L).

The Buildings Standards (Scotland - Consolidated) Regulations. British Standards Codes of Practice (BSI):

B.S. 5440 Detail 1 Flues
B.S. 5440 Detail 2 Air supply and ventilation
B.S. 5449 Systems for hot water production with forced circulation
B.S. 6798 Installation of gas-fired boilers for hot water
B.S. 6891 Gas systems
B.S. 7671 IEE wiring system regulations
B.S. 4814 Specifications for expansion tanks
B.S. 5482 LPG systems
B.S. 7593 Water treatment in central heating systems for domestic hot water production
B.S. 5546 Installation of systems for domestic hot water production

  • Model Water By-Laws
  • B.S.

5955-8

Installation of plastic pipes

For Northern Ireland, observe the current applicable regulations.

Safe handling of materials

Pay attention when handling the boiler insulation panels because the material they are made of could irritate the skin. No part of the boiler contains asbestos, mercury or CFC's.

Advice for transport and handling

For lifting and transport always take suitable safety precautions: keep your back straight, bend knees, do not turn your body, move feet, avoid bending forward or sideways and keep the load as close as possible to your body.

If possible, use a trolley or other suitable means to carry the boiler.

Grip the boiler firmly and, before lifting it, try and find the point where the load is concentrated in order to establish the centre of gravity and suitably reposition yourself.

Page 18
2.2 Place of installation

The combustion circuit is sealed with respect to the place of installation and therefore the unit can be installed in any room except in a garage. The place of installation must be sufficiently ventilated to prevent the creation of dangerous conditions in case of even small gas leaks. Otherwise there may be risk of suffocation and intoxication or explosion and fire. This safety standard is set by the EEC Directive no. 2009/142 for all units that use gas (including sealed chamber units).

The unit is designed to operate in a partially protected place, with minimum temperature of -5°C. If provided with the special frost protection kit it can be used with minimum temperature to -15°C. The boiler must be installed in a sheltered place, e.g. under the slope of a roof, inside a balcony or in a protected recess.

The place of installation must be free of dusts, flammable materials or objects, or corrosive gases.

The boiler is arranged for wall mounting and comes as standard with a hooking bracket. Wall fixing must ensure stable and effective support for the generator.

If the unit is enclosed in a cabinet or mounted alongside, a space must be provided for removing the casing and for normal maintenance operations. fig. 27 gives the minimum distances to be respected

fia. 27

Α Min. 2.5 cm
В Min. 20 cm
С Min. 30cm
D Min. 60 cm (via an openable panel)
2.3 Plumbing connections
Important

The heating capacity of the boiler must be previously established by calculating the building's heat requirement according to the current regulations. To ensure proper operation and long boiler life, the plumbing system must be adequately sized and complete with all the necessary accessories, including a room thermostat, a thermostatic radiator valve (TRV), etc. The system flow and return pipes must have a diameter of at least 22 mm for the first 3 m of length from the ùnit.

If the system delivery and return pipes follow a path where air pockets could form in certain places, it is advisable to install vent valves at these points. Also, install type "A" drain cocks at the lowest points in the system to allow complete emptvina.

The temperature drop between the delivery manifold and the return to the boiler should not exceed 20 °C.

A flow rate of at least 6 litres/min through the heat exchanger is required

Do not use the water system pipes to earth electrical appliances.

Page 19

Before installation, carefully flush all the heating system pipes to remove any residuals or impurities that could affect proper operation of the unit (as required by BS 7593 Building regs Doc L).

Carry out the connections to the unit as indicated in .

The safety valve discharge must be connected to a 15 mm diameter copper pipe descending from the boiler to run off system water in case of overpressure in the heating circuit. Otherwise, the boiler manufacturer cannot be held liable if the discharge valve operates and floods the room. The discharge must be run to the outside of the building to prevent the risk of damage or injury caused by discharged hot water in case of overpressure in the system.

Connections to the boiler are to be made in such a way as to ensure that its internal pipes and fittings are free of stress. If a non-return valve is installed also on the DHW circuit (if provided for), it is necessary to install a safety valve between the boiler and circuit (with non-return valve at least 3 metres from the boiler) or an expansion tank for domestic use.

Typical System By-pass layout

The automatic by-pass must be installed a least 3 metres from the boiler & set to allow a minimum of 6 ltr/min through the valve when all TRV's are closed.

Page 20
Make up water

Provision must be made for replacing water lost from the sealed system. Reference should be made to BS6798, for methods of filling and making up sealed systems. There must be no direct connection between the boiler's central heating system and the mains water supply. The use of mains water to charge and pressurise the system directly, is conditional upon the Local Water Byelaws. Again any such connection must be disconnected after use. Ensure the filling point is on the return pipe to the boiler.

Attention - is drawn to the Model Water Byelaws.

Filling Loop in fig. 29 is supplied with boiler.

Key

  • 1. C.H. filling valve
  • 2. Temporary connection
  • 3. Cold water supply valve
  • 4. Double check valve

fig. 29 - Filling Loop (supplied with boiler)

The maximum domestic water pressure for the inlet supply is 9 bar (130 P.S.I.). If the cold mains supply exceeds 5 bar (72 P.S.I.), a water governor or pressure reducing valve must be fitted by the installer into the mains supply in an inconspicuous but accessible position preferably between 3 and 5 metres (10-16ft) before the appliance. Such a valve must be approved by WRAS. The fitting of a DHW expansion vessel is also recommended.

Isolation valve kit

The isolation valves supplied (see fig. 30) must be installed between the boiler and heating system to allow the boiler to be isolated from the system if necessary.

  • A Heating Flow 3/4" (22mm with isolation valve fitted)
  • B DHW outlet elbow 1/2" (15mm with outlet union fitted)
  • C Gas 3/4" (22mm with yellow isolation valve fitted)
  • D Cold water inlet 1/2" (15mm with isolation valve fitted)
  • F Heating Return 3/4" (22mm with isolation valve c/w filter fitted)
fig. 30 - Isolation valve kit
Frost protection system, antifreeze liquids, additives and inhibitors

If necessary, the use of antifreeze liquids, additives and inhibitors is allowed, only and exclusively if their manufacturer guarantees that the products are suitable for use and do not cause damage to the boiler's heat exchanger.or other components and/or materials of the boiler and system. It is prohibited to use generic antifreeze liquids, additives or inhibitors that are not expressly suitable for use in heating systems and compatible with the materials of the boiler and system

Page 21

j.

System water characteristics

B

BlueHelix HiTech RRT C boilers are suitable for installation in heating systems with non-significant entry of oxygen (ref. systems "case I" EN14868). A physical separator (e.g. plate heat exchanger) must be provided in systems with continuous entry of oxygen (e.g. underfloor systems without antidiffusion pipes or open vessel), or intermittent (less than 20% of system water content).

The water inside a heating system must comply with the applicable laws and regulations, the characteristics required by UNI 8065, and the indications of EN14868 (protection of metal materials against corrosion) must be observed.

The filling water (first filling and subsequent replenishment) must be clear, with hardness below 15°F and treated with suitable chemical conditioners against the initiation of corrosion, that are not aggressive on metals and plastics, do not develop gases and, in low-temperature systems, do not cause proliferation of bacterial or microbial masses.

The water contained in the system must be checked regularly (at least twice a year during the season of use, as required by UNI8065) and have: a possibly clear appearance, a hardness lower than 15°F for new systems or 20°F for existing systems, a PH higher than 7 and less than 8.5, an iron content (Fe) less than 0.5 mg/l, a copper content (Cu) less than 0.1 mg/l, a chloride content lower than 50mg/l, an electrical conductivity lower than 200 µS/cm, and must contain chemical conditioning agents in a concentration sufficient to protect the system at least for one year. Bacterial or microbial loads must not be present in low temperature systems.

Only use conditioners, additives, inhibitors and antifreeze liquids declared by the producer suitable for use in heating systems and that do not cause damage to the heat exchanger or other components and/or materials of the boiler and system.

Chemical conditioners must ensure complete deoxygenation of the water, contain specific protective agents for yellow metals (copper and its alloys), anti-scaling agents for limestone, neutral PH stabilizers and, in low-temperature systems, specific biocides for use in heating systems.

Recommended chemical conditioners:

SENTINEL X100 and SENTINEL X200

FERNOX F1 and FERNOX F3

The unit is equipped with a frost protection system that activates the boiler in heating mode when the system flow water temperature falls below 6°C. The device is not active if the power and/or gas supply to the unit is turned off. If necessary, to protect the system use a suitable antifreeze liquid that meets the above requirements and provided for by UNI 8065.

In the presence of adequate chemical/physical system and feed water treatments and related high cyclicity controls able to ensure the required parameters, for industrial process applications the product can be installed in open-vessel systems with vessel hydrostatic height able to ensure compliance with the minimum operating pressure indicated in the product technical specifications.

The presence of deposits on the boiler exchange surfaces due to non-compliance with the above requirements will involve non-recognition of the warranty.

2.4 Gas connection

Before making the connection, ensure that the unit is arranged for operation with the type of fuel available.

The gas connection must be made to the relevant connection (see fig. 64) in compliance with current legislation, using a rigid metal pipe or a continuous wall flexible hose in stainless steel, placing a gas valve between the system and boiler. Make sure all the gas connections are tight. Otherwise there may be a risk of fire, explosion or suffocation.

Page 22
2.5 Electrical connections
ATTENTION

BEFORE CARRYING OUT ANY OPERATION REQUIRING REMOVAL OF THE CASING, DISCONNECT THE BOILER FROM THE ELECTRIC MAINS WITH THE MAIN SWITCH.

NEVER TOUCH THE ELECTRICAL COMPONENTS OR CONTACTS WITH THE MAIN SWITCH TURNED ON! DANGER OF ELECTRIC SHOCK WITH RISK OF INJURY OR DEATH!

The unit must be connected to an efficient grounding system in accordance with applicable safety regulations. Have the efficiency and suitability of the grounding system checked by professionally qualified personnel; the Manufacturer declines any liability for damage caused by failure to ground the system.

The boiler is pre-wired and equipped with a three-core connection cable to the electric line without plug. The connections to the grid must be made with a permanent connection and equipped with a bipolar switch with contact opening of at least 3 mm, interposing fuses of max. 3A between the boiler and line. Make sure to respect the polarities (LINE: brown wire / NEUTRAL: blue wire / GROUND: yellow-green wire) in the connections to the electric line.

The unit's power cable MUST NOT BE REPLACED BY THE USER . If the cable gets damaged, turn the unit off and have the cable replaced only by professionally qualified personnel. In case of replacement, use exclusively "HAR H05 VV-F" 3x0.75 mm2 cable with maximum ext. diameter of 8 mm.

Room thermostat (optional)

ATTENTION: THE ROOM THERMOSTAT MUST HAVE VOLTAGE-FREE CON-TACTS. CONNECTING 230V TO THE ROOM THERMOSTAT TERMINALS WILL PERMANENTLY DAMAGE THE PCB.

When connecting a time control or timer, do not take the power supply for such devices from their cutoff contacts. Their power supply must be via a direct connection from the grid or with batteries, depending on the kind of device.

Page 23

Ferroli

Accessing the electrical terminal block and fuse

Remove the front panel ("Opening the front panel" on page 38) to access the terminal block (M) and fuse (F) by proceeding as follows (fig. 31 and fig. 32). The terminals indicated in fig. 31 must be with voltage-free contacts (not 230V). The arrangement of the terminals for the various connections is also given in the wiring diagram in fig. 70.

fig. 31

fig. 32

Page 24
Variable output relay card LC32 (optional - 043011X0)

The variable output relay LC32 consists of a small card with a switchover of free contacts (closed means contact between C and NO). Operation is managed by the software.

For installation, carefully follow the instructions provided in the kit package and on the wiring diagram of fig. 70. To use the desired function, refer to the table 3.

Table 3- Settings LC32
Parameter b07 Function LC32 Action LC32
0 Manages a secondary gas valve (default) The contacts are closed when the gas valve (in the boiler) is powered
1 Use as an alarm output (warning light comes on) The contacts are closed when there is an error condition (generic)
2 Manages a water loading valve The contacts are closed until the water pressure in the hea-
ting circuit is restored to the normal level (after manual or
automatic topping up)
3 Manages a solar 3-way valve The contacts are closed when the DHW mode is active
4 Manages a second heating pump The contacts are closed when the heating mode is active
5 Use as an alarm output (warning light goes off) The contacts are opened when there is an error condition (generic)
6 Indicates ignition of the burner The contacts are closed when the flame is present
7 Manages the trap heater The contacts are closed when the frost protection mode is active
ON/OFF (A fig. 31) configuration
Table 4- Switch A setting
DHW configuration Parameter b06 Parameter b06
b06=0 Contact open disables DHW and re-enables it if closed.
b06=1 Contact open disables heating and displays F50. Contact closed enables heating.
b01 = 3 b06=2 The contact acts as a room thermostat.
b06=3 Contact open displays F51 and the boiler continues to operate.
It is used as an alarm.
b06=4 The contact acts as a limit thermostat, if open it displays F53 and turns off the request.
2.6 Fume ducts

THE BOILERS MUST BE INSTALLED IN ROOMS THAT MEET THE FUNDA-MENTAL VENTILATION REQUIREMENTS. OTHERWISE THERE IS A DAN-GER OF ASPHYXIA OR POISONING.

READ THE INSTALLATION AND MAINTENANCE INSTRUCTIONS BEFORE INSTALLING THE UNIT.

ALSO RESPECT THE DESIGN INSTRUCTIONS.

IN CASE OF PRESSURES EXCEEDING 200 Pa INSIDE THE FUME EXHAUST PIPES, THE USE OF CLASS "H1" FLUES IS MANDATORY.

Important

The unit is a "C-type" with sealed chamber and forced draft; the air inlet and fume outlet must be connected to one of the extraction/suction systems indicated below. Before proceeding with installation, check and carefully observe the above instructions. Also, comply with the provisions on the positioning of wall and/or roof terminals and the minimum distances from windows, walls, ventilation openings, etc.

In case of installation with maximum resistance (coaxial or separate flue) it is advisable to carry out a calibration procedure [AUTO SETUP] to optimize boiler combustion.

Page 25

fig. 33- Examples of connection with coaxial pipes ( = Air / = Fumes)

For coaxial connection, fit the unit with one of the following starting accessories. For the wall hole dimensions, refer to the figure on the cover. Any horizontal sections of the fume exhaust must be kept sloping slightly towards the boiler, to prevent possible condensate from flowing back towards the outside and causing dripping.

fig. 34- Starting accessories for coaxial ducts

Table 5- Max. length coaxial ducts
Coaxial 60/100 Coaxial 80/125
Max. permissible length (horizontal) All models 7 m BlueHelix HiTech RRT 24 C = 28 m
Max. permissible length (vertical) All models 8 m BlueHelix HiTech RRT 28 C = 20 m
BlueHelix HiTech RRT 34 C = 20 m
Reduction factor 90° bend 1 m 0.5 m
Reduction factor 45° bend 0.5 m 0.25 m

Ferroli

Page 26
( Connection with separate pi pes
C5x C
fig. 35- Examples
s of connection with separate pipes (i) = Air / i) = Fumes
1 Table 6- Typology
ŝ Туре Description
]_ C1X Wall horizontal exhaust and intake conditions (within 50cm) . The inlet/outlet terminals must be concentric or close enough to be subjected to similar wind
C3X Roof vertical exhaust and intake. In nlet/outlet terminals like for C12
C5X Separate wall or roof intake and ex
located on opposite walls
chaust and in any case in areas with different pressures. The exhaust and intake must not be
C6X Intake and exhaust with separately / certified pipes (EN 1856/1)
B2X Intake from installation room and w vall or roof exhaust ST BE PROVIDED WITH APPROPRIATE VENTILATION
£ F cts, fit the unit with the following starting accessory:
fig. 36- Starting accessory for separate ducts
E
ti
1
2
3
  • Before installation, make sure the ion:
  • Establish the layout of the system.
  • Consult table 8 and identify the tion.
  • Check that the sum total of los
maximum permissible length has not been exceeded by means of a simple calcula-
tem of split flues, including accessories and outlet terminals.
e losses in m eq (equivalent m) of every component, according to the installation posi-
sses is less than or equal to the maximum permissible length in table 7.
٦ able 7- Max. length separat e ducts
Max. p ermissible length BlueHelix HiTech RRT 24 C = 80 m eq

BlueHelix HiTech RRT 34 C = 70 m e

Page 27
Table 8- Accessories
Losses in m eq
Air Fume exhau exhaust
intake Vertical Horizontal
PIPE 1 m M/F 1KWMA83W 1.0 1.6 2.0
BEND 45° M/F 1KWMA65W 1.2 1.8
90° M/F 1KWMA01W 1.5 2.0
PIPE SECTION with test point 1KWMA70W 0.3 0.3
Ø 80 TERMINAL air, wall 1KWMA85A 2.0 -
fumes, wall with antiwind 1KWMA86A - 5.0
FLUE Split air/fumes 80/80 010027X0 - 12.0
Fume outlet only Ø80 010026X0 +
1KWMA86U
- 4.0

Connection to collective flues

Table 9- Typology
Туре Description 4 -
C8X Exhaust in single or common flue and wall intake
B3X Intake from installation room by means of concentric duct (that encloses the exhaust) and exhaust in common flue with natural draft
C93 Exhaust to a vertical terminal and intake from existing flue.
Page 28

If the BlueHelix HiTech RRT C boiler is to be connected to a flue or a single chimney with natural draft, the flue or chimney must be expressly designed by professionally qualified technical personnel in conformity with the current regulations and be suitable for sealed chamber units equipped with fan.

Backflow preventer valve

The BlueHelix HiTech RRT C boiler is fitted as standard with a clapet non-return valve (backflow preventer) therefore it can be connected, only if running on G20 gas , to collective flues in positive pressure.

Using this type of installation, parameter P67 must be set to 1.

In case of a type C(10)3 or C(11)3 boiler installation apply, IN A CLEARLY VISIBLE PLACE on the FRONT PA-NEL, the relevant white sticker included in the document envelope supplied with the unit.

After installation, check the tightness of the fumes and gas circuit.

• OTHERWISE THERE IS DANGER OF SUFFOCATION DUE TO THE EMISSION OF COMBUSTION FUMES.

osition of terminals

fiq. 38

Minimum dimensions of fume exhaust terminals
Α Directly under an opening, air inlet, openable window, etc. 300 mm
В Above an opening, air inlet, openable window, etc. 300 mm
С Horizontally to an opening, air inlet, openable window, etc. 300 mm
D Under gutters, drain pipes 75 mm
Е Under cornices or under eaves 200 mm
F Under balconies or garages 200 mm
G From a drain pipe or a vertical drain pipe 150 mm
н From an internal or external corner 100 mm
I Above ground level, a roof or balcony 300 mm
J From a surface facing the terminal 600 mm
К From a terminal facing the terminal 1200 mm
L From a garage opening (e.g. door, window) with access to the home 1200 mm
М Vertically from a terminal on the same wall 1500 mm
Page 29
Minimum dimensions of fume exhaust terminals
Ν Horizontally from a terminal on the same wall 300 mm
0 From the wall on which the terminal is fitted N/A
Р From a vertical structure on the roof 150 mm
Q Above the intersection with the roof 300 mm
NOTES
  • N/A = Not applicable
  • Also, the terminal must be at least 150 mm (fanned draught) from an opening made in the structure of the l house a fitted element such as a window frame.
  • Positions of flue terminals: if the flue is installed at a low level the potential effect of the plume must be con Special plume management kits are available by request.
  • The plume must not be directed towards:
    • A frequented approach
    • A window or door
    • An adjacent property
building to
nsidered.
2.7 Condensate drain connection
IMPORTANT

The boiler has an internal trap for draining condensate. Install the hose " B " by pressing it into place. Before commissioning, fill the trap with approx. 0.5 L of water and connect the hose to the disposal system.

The connections to the drainage system must be resistant to acid condensation and always allow the condensate produced by the boiler to drain.

If the condensate drain is not connected to the waste water drainage system, a neutralizer must be installed.

OTHERWISE THERE IS A DANGER OF SUFFOCATION DUE TO THE EMIS-SION OF COMBUSTION FUMES.

THE CONDENSATE DRAIN MUST BE CONNECTED TO THE DRAINAGE SYS-TEM IN SUCH A WAY THAT THE LIQUID CONTAINED CANNOT FREEZE.

Page 30
Condensate drain

If possible, the condensate should be conveyed inside an underground drainage system or pipe. For that purpose, use a pipe of at least 22 mm diameter and a trap with flexible connection preinstalled in the unit to facilitate connection of the condensate drain pipe.

The pipe must be in glue-joined plastic and not in copper, since the condensate has a pH of 4 (slightly acid).

If the condensate drain pipe cannot be ended on the inside, it is advisable to run it outside as shown in the following figure.

The pipe sections going to the outside are exposed to the risk of freezing in particularly rigid weather conditions. To prevent this from occurring, it is advisable to reduce the length of the condensate drain pipes and run them on the inside, as much as possible, before going to the outside.

The pipes outside the building must be in glue-joined plastic with increased diameter of up to 32 or 40 mm and at least 3 m long for connection to a condensate collection pit or external drain.

If using a condensate collection pit, it must be as indicated in the figure below, or use a specific system (such as Mc Alpine SOAK1GR) available from the majority of suppliers of products and accessories for plumbing or heating systems.

fig. 40 - Condensate drain

Page 31

j.

3. Service and maintenance

All adjustments described in this chapter can only be carried out by qualified personnel.

3.1 Adjustments
Gas conversion

The unit can work with 2nd or 3rd family gases, which is clearly indicated on the packaging and on the data plate of the unit. If the unit has to be used with a gas other than the factory-set one, proceed as follows:

  • 1. Disconnect the power supply and turn off the gas.
  • 2. Remove the front panel (see "Opening the front panel" on page 38 ).
  • Apply the plate for LPG (contained in the document bag) near the technical data plate.
  • Refit the front panel and turn on the power to the boiler.
  • 5. Modify the parameter for the type of gas:
    • Access the Main menu [MENU] using the button
    • Follow the path installer menu [Service] >enter the Password 1234 (see fig. 17) >parameters menu [TSP].
    • Using the buttons + and Heating, select parameter b03 and set the corresponding value with the buttons + and DHW:
      • 0 =G20

1 =G30/G31

  • 2 =G230
  • To confirm, press the button
  • Turn the power off for 10 seconds and then back on.
  • Wait until the Fh mode has finished.
  • Put the boiler in standby mode and activate the calibration mode[AUTO SETUP] (see "IMPORTANT" on page 32 ).
Checking the combustion values

MAKE SURE THE FRONT PANEL IS CLOSED AND THE INTAKE/FUME EXHAUST DUCTS ARE COMPLETELY AS-SEMBLED.

  • 1. Put the boiler in heating or DHW mode for at least 2 minutes.
  • 2. Activate the Test [Test] mode (see "Test mode [Test]" on page 34 ).
  • 3. Using a combustion analyzer connected to the arrangements located on the starting accessories above the boiler, with boiler operating at maximum and minimum power check that the CO2 content in the fumes matches that indicated in the following table.
Cas e studies G20 G30/G31 G230
Α New boiler (first ignition/conversion or electrode replacement) 7.5%-9.9% 9%-11.5% 9%-11.5%
в Boiler with at least 500 hours of operation 9%+/-0.8 10%+/-0.8 10%+/-0.8

4. If the combustion values do not match, adjust the Offset values in the Test mode as described in the following paragraph.

IMPORTANT

During the CALIBRATION PROCEDURE [AUTO SETUP], the TEST PROCE-DURE [Test] or during the CO2 VALUE CHECK, the FRONT PANEL must be CLOSED and the INTAKE/FUME EXHAUST DUCTS completely assembled. Also, the boiler must not be in OFF mode or in vent cycle mode "FH-Fh" (see detail C of fig. 11) and there must not be a DHW or heating circuit request.

Page 32

Calibration procedure [AUTO SETUP]

  • 1. Access the parameters menuITSPI
  • 2. Select parameter b27 with the + and heating buttons and set it to 5 with the + and ----DHW buttons
    • Confirm with the button
    • Return to the main menu[MENU]
  • 3 Return to the installer menu [Service] >enter the Password 1234 (see fig. 17). Now the menu for calibration[Auto Setup] is
  • also displayed.
  • 4. Select it and confirm with the button
  • 5. The procedure starts automatically finding the optimal ignition point (a few ignition attempts are required to determine the exact point).
  • 6. After ignition, the burner goes to heating at the vaous powers (max, med, min) indicated by point (fig 41)

If the system heat dissipation is not sufficient to end the procedure, a DHW request can be activated only after the burner has ignited

  • 7. At the end of the calibration sequence [Comple ted] will be displayed for a few seconds and then return to the Service menu.
  • 8. If the ignition sequence described in point "6" not successful, the message max_err at point @ and an error code at point C will appear (fig. 41). 9. Exit with the button C and unlock the boiler.
  • Repeat the sequence from point "1".

The calibration procedure [Auto Setup] can only be performed if parameter b27 is set to 5.

Parameter b27 can be set manually to the value 5 , or by:

  • changing the parameter "gas type" b03
  • setting parameter P67 to 1 .
  • changing the value of parameter P68
  • doing "Restore Factory Values" with the parameter b29=10 (after carrying out this operation, disconnect and reconnect the power supply for about ten seconds).

In each of the above cases, b27 automatically changes to 5.

It is necessary to perform the calibration procedure [Auto Setup] in the following cases:

  • after replacing the PCB
  • after changing the gas (b03)
  • setting parameter P67 to 1
  • after changing the value of parameter P68
  • after setting parameter b27 to 5 for replacement of components such as the electrode, burner, gas valve, fan or for installations with maximum flue resistance
  • in case of fault conditions A01. A06 or other faults when required (see table 11. Respect the sequence of fault cures)

The calibration procedure [Auto Setup] resets the combustion parameters previously recorded and must be done only in the cases described above.

Page 33
Test mode [Test]

Do a heating or DHW request.

1. Access the Main menu [MENU] using the button

Follow the path installer menu [Service] >enter the Password 1234 (see fig. 17) >test mode menu [Test].

Confirm with the button

  • 2. After ignition, the power adjusts to Medium "med". When the combustion value is stable, "med ok" is displayed (point a).
  • The heating buttons are used for the 4 power levels: min (minimum power), med (medium power), max CH (maximum power CH) and max (maximum power DHW) (point a).
  • 4. Only when the step value at the set power is followed by "ok" (med ok, min ok...) can the CO2 be adjusted with the DHW buttons. Pressing the button DHW increases the "Offset" value by one unit (point D ). By pressing buttons A and A DHW for more than 2 sec., the Offset value will change by 3 units.

When the Power value is followed by "ok" the combustion value will be saved.

5. The "Offset" adjustment range is from -8 to +8. Increasing the value decreases the CO2, decreasing it increases the CO2.

The CO2 adjustment must not be done with less than 500 burner operation hours, because the system adjusts itself.

Ferroli

To exit the test mode [Test] hold down the button 💍.

If the Test mode [Test] is active and enough hot water is drawn to activate the DHW mode , the boiler remains in Test mode [Test] but the 3-way valve switches to DHW.

The Test mode [Test] is automatically disabled in any case after 15 minutes or by stopping hot water draw-off (if enough hot water was drawn to activate the DHW mode).

Installer menu [SERVICE]

ONLY QUALIFIED PERSONNEL CAN ACCESS THE SERVICE MENU AND MODIFY PARAMETERS.

Access the Main menu[MENU] with the button

Follow the path installer menu[Service] > enter the Password 1234 (see fig. 17). Confirm with the button

Menu for modifying parameters [TSP]

Press the Heating buttons to scroll the list, and display with value with the button E . To modify press the DHW buttons , confirm with the button E or cancel with the button ( ).

Table 10- Transparen t Parameters Table
Index Description Range Default
b01 Boiler type selection 3 = HEATING ONLY COMBI (DO NOT MODIFY) 3
b02 Boiler type 1 = 24 kW
2 = 28 kW
3 = 34 kW
4 = Do not use
5 = Hybrid 24 C
6 = Hybrid 28 C
7 = Hybrid 34 C
1 = 24 kW
2 = 28 kW
3 = 34 kW
4 = /
5 = Hybrid 24 C
6 = Hybrid 28 C
7 = Hybrid 34 C
Page 34
Index Description Range Default
b03 Gas type 0 = Natural gas
1 = Liquefied gas
2 = Propane-air
0
b04 System water pressure protec-
tion selection
0 = Pressure switch
1 = Pressure transducer
1
b05 Summer/Winter mode 0 = WINTER - SUMMER - OFF
1 = WINTER - OFF
0 = Enabled
b06 Variable input contact operation selection
  • 0 = Flowmeter exclusion
  • 1 = System thermostat
  • 2 = Second room therm.
  • 3 = Warning/Alert
  • 4 = Safety thermostat
2
ь07 Relay card LC32 operation selection
  • 0 = External gas valve
  • 1 = Alarm
  • 2 = System filling solenoid valve
  • 3 = Solar 3-way valve
  • 4 = Second heating pump
  • 5 = Alarm2
  • 6 = Burner lit
  • 7 = Frost protection On
0
ζ γ b08 Hours without DHW draw-off 0 ÷ 24 hours
(time for temporary deactivation of comfort mode without draw-off with
b012 = 0 )
24
b09 Fault 20 status selection
  • 0 = Deactivated
  • 1 = Enabled (only for versions with pressure transducer)
0
b10 Not implemented
b11 Flowmeter timing 0 = Deactivated
1-10 = seconds
0
b12 Comfort mode
  • 0 = Activation with draw-off
  • 1 = Always active
0
b13 Not implemented
b14 DHW factor 0 - 1 0
b15 Flowmeter type selection 1 = Flow. (450 imp/l)
2 = Flow. (700 imp/l)
3 = Flow. (190 imp/l)
3
ب b16 Not implemented
b17 Not implemented
b18 DHW mode activation flow rate 0 ÷ 100l/min/10 (do not set this value below 16) 25
b19 DHW mode deactivation flow rate 0-100 l/min/10 20
b20 Flue material selection 0 = Standard
1 = PVC
2 = CPVC
0
b21 Not implemented
b22 Not implemented
b23 Standard flue shutdown maxi-
mum temperature
60-110°C 105
b24 PVC flue shutdown maximum temperature 60-110°C 93
7 b25 CPVC flue shutdown maximum temperature 60-110°C 98
b26 Not implemented
b27 Calibration procedure [AUTO
SETUP]
5 = Calibration procedure [AUTO SETUP] enabled
All other values = Calibration procedure [AUTO SETUP] disabled
(See "Calibration procedure [AUTO SETUP]" on page 32)
0
b28 Not implemented
Page 35
Index Description Range Default
b29 Restore Factory Values See "* Restore Factory Values" on page 37. 0
P30 Heating ramp 10÷80
(ex. 10=20°C/min, 20=12°C/min, 40=6°C/min, 80=3°C/min)
40
P31 Heating standby time 0 ÷ 10 minutes 4
P32 Heating Post-Circulation 0 ÷ 255
(Multiply the value by 10. Example 15 x 10 = 150 seconds )
15
P33 Pump operation
  • 0 = Continuous pump (active only in winter mode)
  • 1 = Modulating pump
1
P34 Pump modulation DeltaT 0 ÷ 40°C 20
P35 Modulating pump min. speed 30 ÷ 100% 30
P36 Modulating pump start speed 90 ÷ 100% 90
P37 Modulating pump max. speed 90 ÷ 100% 100
P38 Pump deactivation temperature
during Post-Circulation
0 ÷ 100°C 55
P39 Pump activation hysteresis tem-
perature during Post-Circulation
0 ÷ 100°C 25
P40 Heating user max. setpoint 20 ÷ 90°C 80
P41 Max. output in heating 0 ÷ 100% 24 kW = 80
28 kW = 85
34 kW = 90
P42 Burner shutdown in DHW 0 = Fixed
1 = Linked to setpoint
2 = Solar
0
P43 Comfort mode activation tempe-
rature
0 ÷ 80°C 40
P44 Comfort mode deactivation hys-
teresis
0 ÷ 20°C 20
P45 DHW standby time 30 ÷ 255 seconds 120
P46 DHW user max. setpoint 40 ÷ 65°C 55
P47 DHW pump Post-Circulation 0 ÷ 255 seconds 30
P48 Max. output in DHW 0 ÷ 100% 100
P49 Not implemented (b01=2)
P50 Not implemented (b01=2)
P51 Burner shutdown in DHW
(P42=2)
0 ÷ 100
OFF = DHW user setpoint + P51
10
P52 Burner ignition in DHW (P42=2) 0 ÷ 100
ON = DHW user setpoint - P52
10
P53 Solar standby time 0 ÷ 255 seconds 10
P54 System pre-circulation time in
heating
0 ÷ 60 seconds 30
P55 System filling mode 0 = Disabled
1 = Automatic
0
P56 Minimum system pressure limit value 0-8 bar/10 (Only for boilers with water pressure sensor) 4
P57 System nominal pressure value 5-20 bar/10 (Only for boilers with water pressure sensor) 7
P58 Maximum system pressure limit value 25-35 bar/10 (Only for boilers with water pressure sensor) 28
P59 Circulating pump deactivation with OpenTherm
  • 0 = Circulating pump activated in heating
  • 1 = Circulating pump deactivated in heating with request from Open-Therm only
0
P60 Frost protection power 0 ÷ 50% (0 = minimum) 0
P61 Minimum power 0 ÷ 50% (0 = minimum) 0

Page 36

Ferroli

Index Description Range Default
Ť P62 Fan minimum speed DO NOT MODIFY
(The parameters are automatically updated)
G20/G230:
24 kW = 47
28 kW = 47
34 kW = 49
G30/G31:
24 kW = 49
28 kW = 49
34 kW = 48
P63 Fan on speed DO NOT MODIFY
(The parameters are automatically updated)
G20/G230:
24 kW = 160
28 kW = 160
34 kW = 140
G30/G31:
24 kW = 152
28 kW = 152
34 kW = 132
$ P64 Fan maximum speed DO NOT MODIFY
(The parameters are automatically updated)
G20/G230:
24 kW = 140
28 kW = 172
34 kW = 194
G30/G31:
24 kW = 134
28 kW = 156
34 kW = 186
P65 Not implemented 1
P66 Valve frequency 0 ÷ 2 1
P67 Installation C(10)3/C(11)3 0 - 1 (1 = installation C(10)3 / C(11)3) 0
P68 Flue parameter 0 ÷ 10 (modify according to flue table) 0
P69 Heating hysteresis after ignition.
(available from MAIN and DSP
FW 1.03)
6 ÷ 30 °C 10
* Restore Factory Values

To restore all the parameters to the factory values, set parameter b29 to 10 and confirm. Turn the power off for 10 seconds and then back on.

At this point it is necessary to restore parameter b02 and the modified parameters to the correct value according to the type of boiler. Parameter b27 will be automatically set to 5 .

Display Adjustment Menu [DISPLAY]

Here it is possible to set some display parameters.

[Contrast]
Contrast adjustment. Contrast
[Brightness] Brightness
Brightness adjustment Backlight time
[Backlight time]
Display backlight duration.
Reset
[Reset]
Restore factory values.

DISPLAY

Мах

1m

Page 37

3.2 Commissioning

Before lighting the boiler

  • Check the tightness of the gas system
  • Check correct expansion vessel precharge.
  • Fill the hydraulic system and make sure that all air contained in the boiler and the system has been vented.
  • Make sure there are no water leaks in the system, DHW circuits, connections or boiler.
  • Make sure there are no flammable liquids or materials near the boiler.
  • Check correct connection of the electrical system and efficiency of the grounding system.
  • Fill the trap (see cap. 2.7 "Condensate drain connection")

IF THE ABOVE INSTRUCTIONS ARE NOT OBSERVED THERE MAY BE RISK OF SUFFOCATION OR POISONING DUE TO GAS OR FUMES ESCAPING; DANGER OF FIRE OR EXPLOSION. ALSO, THERE MAY BE A RISK OF ELEC-TRIC SHOCK OR FLOODING THE ROOM.

First boiler ignition

  • Make sure there is no draw-off of hot water and room thermostat requests
  • Turn on the gas and check that the gas supply pressure ahead of the unit complies with the technical data table or in any case the tolerance provided for by the regulations.
  • Power the boiler electrically, the display shows the software version number of the control unit and display and then FH and Fh air venting cycle (see cap. 1.3 "Connection to the power supply, switching on and off" on page 7).
  • After the Fh cycle, the display will show the winter mode screen (fig. 11); do the temperature adjustments: heating flow and DHW outlet (fig. 14 and fig. 15). Check if the value of the flue parameter, P68 *** '- Transparent Parameters Table' on page 34 ***, is suitable for the length of flue installed.
  • In case of gas change (G20 G30 G31 G230), check if the relevant parameter is suitable for the type of gas present in the supply system (and cap. 3.1 "Adjustments" on page 32).
  • Put the boiler in DHW or heating mode (see cap. 1.3 "Connection to the power supply, switching on and off" on page 7).
  • In Heating mode, do a request: the radiator symbol flashes on the display and the flame appears when the burner ignites.
  • DHW mode with hot water draw-off present: the faucet symbol flashes on the display and the flame appears when the burner ignites.
  • Do the combustion check as described in par. "Checking the combustion values" on page 32.
3.3 Maintenance
IMPORTANT

ALL MAINTENANCE WORK AND REPLACEMENTS MUST BE CARRIED OUT BY SKILLED QUALIFIED PERSONNEL.

Before carrying out any operation inside the boiler, disconnect the power and close the gas cock upstream. Otherwise there may be a danger of explosion, electric shock, suffocation or poisoning.

Opening the front panel

Some internal components of the boiler can reach temperatures high enough to cause severe burns. Before carrying out any operation, wait for these components to cool or else wear suitable gloves.

Page 38

Ferroli

To open the boiler casing:

  • Undo the screws "1" (see fig. 44). Pull the panel outwards and lift it.

fig. 44- Front panel opening

On this unit, the casing also acts as a sealed chamber. After any operation involving opening the boiler, carefully check the correct refitting of the front panel and its seal.

Proceed in reverse order to refit the front panel. Make sure it is correctly hooked to the upper fastenings and is correctly positioned at the sides. Once the screw "1" is tightened, the head must not be below the lower reference fold (see fig. 45).

fig. 45- Correct position of front panel

Page 39

Periodical check

To ensure proper operation of the unit over time, have qualified personnel carry out a yearly inspection, providing for the following checks:

  • The control and safety devices (gas valve, flow meter, thermostats, etc.) must function correctly.
  • The fume exhaust circuit must be perfectly efficient.
  • The sealed chamber must be tight.
  • The air-fume end piece and ducts must be free of obstructions and leaks
  • The burner and exchanger must be clean and free of deposits. Use suitable brushes for cleaning. Never use chemical products.
  • The electrode must be properly positioned and free of scale.
  • The electrode can be cleaned of incrustations only with a non-metallic brush, and must NOT be sanded.
  • The gas and water systems must be tight.
  • The water pressure in the system when cold must be approx. 1 bar; otherwise bring it to that value.
  • The circulating pump must not be blocked.
  • The expansion tank must be filled.
  • The gas flow and pressure must match that given in the respective tables.
  • The condensate evacuation system must be efficient with no leakage or obstructions.
  • The trap must be full of water.
  • Check the quality of the water in the system.
  • Check the condition of the insulation of the exchanger.
  • Check the gas connection between the valve and Venturi.
  • Replace the burner gasket if damaged
  • At the end of the check, always check the combustion parameters (see "checking the combustion values").
Page 40
Extraordinary maintenance and replacement of components

After replacing the gas valve, burner, electrode and PCB, it is necessary to do the calibration procedure [AUTO SE-TUP] (see "Calibration procedure [AUTO SETUP]" on page 32). Then follow the instructions in par. "Checking the combustion values" on page 32.

Gas valve replacement

  • Disconnect the power supply and close the gas cock ahead of the valve.
  • Disconnect the electrical connectors "1" (fig. 46).
  • Disconnect the gas supply pipe "2" (fig. 46)
  • Undo the screws "3" (fig. 47)
  • Remove the gas valve "4" and the gas diaphragm "5" (fig. 48).
  • Fit the new valve, carrying out the above steps in reverse order
  • Refer to the instruction sheet included in the kit when replacing the gas diaphragm.

fig. 46

fig. 47

fig. 48

Page 41
Main exchanger replacement

Before carrying out the following instructions it is advisable to protect the room and the boiler's electrical box against accidental water spillage.

Disconnect the power supply and close the gas cock ahead of the valve

nnect the fume sensor connector 1.

  • Disconnect the fan connector
  • Disconnect the connector of the ignition electrode connected to the board.
  • Drain the water from the boiler heating circuit.
  • Remove the flue connection (concentric or accessorv for separate ducts)
  • Remove the fan
  • Remove the clips of the two pipes on the exchanger, pump and hydraulic unit
  • Loosen the 2 bottom screws "5" securing the exchanger to the frame (fig. 52)
  • Remove the 2 top screws "6" securing the exchanger to the frame (fig. 53)
  • Remove the exchanger
  • Insert the new exchanger, resting it on the bottom screws "5"

• For assembly, proceed in reverse order

Ferroli

fig. 49

Page 42

Page 43
PCB replacement

  • Disconnect the power supply and close the gas cock ahead of the valve.
  • Undo the two screws "1" and rotate the control panel.
  • Raise the electrical box cover by operating on the tabs "2"
  • Undo the screws "3". Raise the board by operating on the side tabs "4".
  • Remove all the electrical connectors.
  • Insert the new board and reconnect the electric

fig. 55

Page 44

Fan replacement

  • Disconnect the power supply and close the gas cock ahead of the valve.
  • Remove the fan electrical connections.
  • Undo the screws "1" and gas pipe connection "2".
  • Remove the venturi "3".

fiq. 56

Water pressure switch replacement

  • Disconnect the power supply and close the gas cock ahead of the valve.
  • Drain the water from the heating circuit.
  • Remove the pressure transducer connector and retaining clip "1".
  • Remove the pressure transducer "2".

fia. 58

Page 45
Water inlet filter cleaning

  • Disconnect the power supply and close the gas cock ahead of the valve.
  • Isolate the boiler by operating the DHW inlet and system shut-off valves.
  • Clean the water inlet filter.

fig. 59

fig. 60

3.4 Troubleshooting
Diagnostics
LCD display Off

If, even after touching the buttons, the display does not come on, check that the card is electrically powered. Using a digital multimeter, check for presence of power.

In case of no voltage, check the wiring

If the voltage is sufficient (Range 195 – 253 Vac), check the fuse (3.15AL@230VAC). The fuse is on the card. To access it, see fig. 31.

LCD display On

In case of operation problems or faults, the display shows the fault identification code.

There are faults that cause permanent shutdowns (indicated with the letter " A "): to restore operation, just hold down the button Until the message " Confirm ?" appears and confirm with the button (optional) , or use the RESET of the remote timer control (optional) if installed. If the boiler does not restart, the fault must be eliminated.

Other faults cause temporary shutdowns (indicated with the letter "F") which are automatically reset as soon as the value returns within the boiler's normal working range.

Page 46
Table of faults

Table 11- List of faults

Fault code Fault Possible cause Cure
No gas Check the regular gas flow to the boiler
and that the air has been eliminated from
the pipes
Ignition/detection electrode
fault
Check the wiring of the electrode and that
it is correctly positioned and free of any
deposits; replace the electrode if neces-
sary.
A01 No burner ignition Insufficient gas supply pres-
sure
Check the gas supply pressure
Ū Trap blocked Check the trap and clean it if necessary
Air/fume ducts obstructed Remove the obstruction from the flue, fume extraction ducts, air inlet and terminals.
63~G Wrong calibration Do the Calibration procedure [AUTO SETUP].
Faulty gas valve Check the gas valve and replace it if necessary
Check the ionization electrode wiring
Check the condition of the electrode
A02 Flame present signal with Electrode fault Electrode to ground
burner off Cable to ground
Check the trap and clean it if necessary
Card fault Check the card
No 230V power supply
F05 Fan fault Tachometric signal interrup-
ted
Check the 5-pin connector wining
Fan damaged Check the fan and replace it if necessary
-
J
Ionization electrode fault Check the position of the ionization elec-
trode, free it from any encrustations and
do the Calibration procedure [AUTO
SETUP]. Replace the electrode if neces-
sary.
Flame unstable Check the burner
A06 No flame after the ignition phase air/fume ducts obstructed Remove the obstruction from the flue, fume extraction ducts, air inlet and terminals
Trap blocked Check the trap and clean it if necessary
Wrong calibration Do the Calibration procedure [AUTO SETUP].
Insufficient gas supply pres-
sure
Check the gas supply pressure
λυσ Overtemperature protec- Flow or return sensors inco-
rrectly positioned or dama-
ged
Check the correct positioning and opera-
tion of the sensors and replace them if
necessary.
tion intervention No water circulation in the system Check the circulating pump
Air in the system Vent the system
Page 47

BlueHelix HiTech RRT C

Fault code Fault Possible cause Cure
No water circulation in the system Check the circulating pump and heating system
A09 Exchanger protection intervention Poor circulation and ano-
malous flow probe tempera-
ture increase
Vent the system
blocked exchanger check the exchanger and system
Overtemperature protec- Flow sensor damaged Check correct positioning and operation
of the flow sensor and replace it if neces-
sary
F09 tion intervention No water circulation in the system Check the circulating pump and heating system
Air in the system Vent the system
Sensor damaged
F10 Flow sensor fault Wiring shorted Check the wiring or replace the sensor
Wiring disconnected 1
Gas valve connector not inserted. Insert the connector
A11 Gas valve connection Electrical connection bet-
ween control unit and gas
valve interrupted.
Check the wiring
Gas valve damaged. Replace the gas valve
Sensor damaged
F11 Return sensor fault Wiring shorted Check the wiring or replace the sensor
Wiring disconnected
Sensor damaged
F12 DHW sensor fault Wiring shorted Check the wiring or replace the sensor
Wiring disconnected
Probe damaged
F13 Fume probe fault Wiring shorted probe
Wiring disconnected F
A14 Fume extraction duct
safety device intervention
Fault A07 generated 3 times in the last 24 hours See fault A07
Check the exchanger
F15 - A07 High fume temperature excessive temperature Check the fume probe
Check the flue material parameter
F19 Card parameter fault Wrong card parameter set-
ting
Check and if necessary modify parameter b15 to 3
F21 System pressure slightly
high (visible only in the
Alarm menu)
System water pressure too high Partially drain the system to a pressure
(shown on the display) of 1÷1.5 bar.
Check the expansion tank
Wrongly configured para-
meter
Check if the parameter b04 is correctly configured
A23-A24-F51 -51 Pressure sensor fault System pressure problems (transducer) System pressure value outside set limits
b06 set to 3
A 26 Intervention of fault F40 System water pressure to high Partially drain the system to a pressure (shown on the display) of 1÷1.5 bar
A20 hours Expansion vessel dischar-
ged or damaged
Charge or replace the expansion vessel
Page 48
Fault code Fault Possible cause Cure
F34 Supply voltage under 180V Electric mains trouble Check the electrical system
F35 Wrong supply frequency Electric mains trouble Check the electrical system
Incorrect system water Pressure too low Fill the system
F37 pressure Pressure transducer not
connected or damaged
Check the pressure transducer
Probe damaged or wiring shorted Check the wiring or replace the sensor
F39 External probe fault Probe disconnected after
activating the sliding tempe-
rature
Reconnect the external probe or disable the sliding temperature
F40 Pressure sensor fault System water pressure too
high and parameter P58 not
set to default
Partially drain the system to a pressure (shown on the display) of 1÷1.5 bar
Expansion vessel dischar-
ged or damaged
Charge or replace the expansion vessel
A44 Multiple requests error Repeated short-term requests Check if there are pressure peaks in the DHW circuit. If necessary, modify para-
meter b11.
F47 Pressure transducer no Pressure transducer not
electrically connected
Check the electrical connection, transdu-
cer connector and wiring.
Γ4/ communication Pressure transducer not working Replace the pressure transducer
Limit thermostat fault with No/poor water circulation in the system Check the circulating pump and heating system
F50 - F53 parameter b06 = 1 or 4 Air in the system Vent the system
Incorrect parameter Check the correct parameter setting
F62 Calibration required New card or boiler not yet calibrated Do the Calibration procedure [AUTO SETUP].
F64 Maximum number of con-
secutive Resets exceeded
Maximum number of conse-
cutive Resets exceeded
Disconnect the power supply to the boiler
for 60 seconds and then reinstate the
boiler
A65 ÷ A97 Specific combustion con-
trol errors
Fume ducts obstructed.
Low gas pressure (A78 -
A84).
Condensate trap blocked.
Fumes recirculation or com-
Check that the fume ducts and the con-
densate trap are not blocked. Check the
correct gas supply pressure.
Do the CO 2 adjustment in TEST mode. If
necessary, do the Calibration procedure
bustion problem [AUTO SETUP].
F65 ÷ F98 Specific combustion con-
trol errors
Fume ducts obstructed.
Low gas pressure.
Condensate trap blocked.
Fumes recirculation or com-
bustion problem
Check that the tume ducts and the con-
densate trap are not blocked. Check the
correct gas supply pressure.
Do the CO 2 adjustment in TEST mode. If
necessary, do the Calibration procedure
[AUTO SETUP].
A80 Parasite flame signal after valve closing Electrode problem.
Gas valve problem.
PCB problem.
Check the correct position and condition
of the electrode.
Check the PCB.
Check the gas valve and replace it if
necessary.
A88 Specific combustion con-
trol errors or gas valve
Calibration activation with
burner lit.
Combustion problem, faulty
gas valve or PCB
Reset the fault and do the Calibration pro-
cedure [AUTO SETUP].
If necessary, replace the gas valve or
PCB.
Page 49

BlueHelix HiTech RRT C

Fault code Fault Possible cause Cure
F96 Specific flame combustion error Unstable flame or unstable flame signal after ignition. Check the gas supply, fume ducts and
condensate drain. Check the correct posi-
tion and state of the electrode After about
3 minutes the error is reset.
Board replacement Reset the fault and do the Calibration pro-
cedure [AUTO SETUP].
A98 Too many SW errors or
error occurred during
board replacement
Fume ducts obstructed.
Low gas pressure.
Condensate trap blocked.
Fumes recirculation or com-
bustion problem.
Initially solve the problem, reset the fault
and check correct ignition.
Do the Calibration procedure [AUTO
SETUP]. Replace the board if necessary.
A99 Generic error PCB hardware or software error Reset the fault and check for correct igni-
tion. Do the Calibration procedure [AUTO
SETUP]. If the problem persists, replace
the board.
Connection cable interrup-
ted or not inserted
Check the connection
F99 Communication fault bet-
ween display and control
unit
Misalignment of parameters between control unit and display Turn the power off and on
Factory values reset Turn the power off and on

EN

Page 50

Page 51

4.2 General view

350

246

14

Safety valve Fan Heating circulating pump Heating temperature ser Automatic air vent DHW temperature probe Gas valve Expansion vessel Ionization/ignition electro Diverter valve Flowmeter

Ferroli

Water gauge Return sensor Fume temperature se

Trac DHW exchanger Condensate tray Pressure transduce Fan/Burner assembly

4.3 Hydraulic circuit

Domestic not water outlet
Cold water inlet
System flow
System return
Safety valve
Heating circulating pump
Heating temperature sensor
Automatic air vent
DHW temperature probe
Expansion vessel
System filling faucet
Diverter valve
Flowmeter
Return sensor
Тгар
DHW exchanger
Automatic bypass (inside pump unit)
Pressure transducer
Page 52

4.4 Technical data table

Table 12- Technical data table

0T4B2AGA BLUEHELIX HITECH RRT 24 C
0T4B4AGA BLUEHELIX HITECH RRT 28 C
0T4B7AGA BLUEHELIX HITECH RRT 34 C 1
-
GAS CATEGORY II2H3+ (GB)
PRODUCT IDENTIFICATION CODES 0T4B2AGA 0T4B4AGA 0T4B7AGA
Max heating canacity kW 20.4 24.5 30.6
Min, heating capacity k/W 20,4 3.5 3.5
Max best output in besting (80/60°C) 20 24 30
Min. heat output in heating (00/00 C) 2.0 24 2.4
Max heat output in heating (50/30°C) 21.6 26 32.5
Min. heat output in heating (50/30°C) 21,0 20 2.0
Max besting consolity in DHW 2,0 29.5 24.7
20 20,3 25
24.5 3,5 3,5
24,0 20 24
KVV 3,4 3,4
Efficiency Prilax (00-00 C) 90,1 90,1 97,9
90 90 90
Efficiency Pmax (50-30°C) % 106,1 106,1 106,1
Efficiency Pmin (50-30°C) % 107,5 107,5 107,5
% 109,7 109,7 109,5
Flue losses with burner ON - Pmax (80/60) % 2 1,9 2
Flue losses with burner ON - Pmin (80/60) % 1,5 1,/ 1,5
Shell losses with burner ON - Pmax (80/60) % 0,5 0,4 0,3
Shell losses with burner ON - Pmin (80/60) % 2,4 2,4 1,4
Flue losses with burner ON - Pmax (50/30) % 1,1 1,1 0,9
Flue losses with burner ON - Pmin (50/30) % 0,7 0,7 0,6
Shell losses with burner ON - Pmax (50/30) % 0,6 0,3 0,6
Shell losses with burner ON - Pmin (50/30) % 1,1 1,1 1,1
Flue losses with burner OFF (50K) % 0 0 0
Shell losses with burner OFF (50K) % 0,2 0,2 0,1
Flue losses with burner OFF (20K) % 0 0 0
Shell losses with burner OFF (20K) % 0,1 0,1 0,1
Gas supply pressure G20 mbar 20 20 20
Max. gas flow G20 m3/h 2,6 3 3,7
Min. gas flow G20 m3/h 0,4 0,4 0,4
CO2 - G20 % 90,8 90,8 90,8
Gas supply pressure G31 mbar 37 37 37
Max. gas flow G31 kg/h 1,9 2,2 2,7
Min. gas flow G31 kg/h 0,3 0,3 0,3
CO2 - G31 % 100,8 100,8 100,8
NOx emissions class - 6 (< 56 mg/kWh)
Max. working pressure in heating bar 2,5 2,5 2,5
Min. working pressure in heating bar 0,8 0,8 0,8
Heating adjustment max. temperature °C 95 95 95
Heating water content liters 2,9 2,9 4,3
Heating expansion vessel capacity liters 8 8 10
Heating expansion vessel precharge pressure bar 0,8 0,8 0,8
Max. working pressure in DHW bar 9 9 9
Min. working pressure in DHW bar 0,3 0,3 0,3
DHW flow rate ∆t 25°C l/min 14 16,1 19.5
DHW flow rate ∆t 30°C l/min 11.7 13,4 16.2
DHW water content liters 0.3 0.3 0.4
Protection rating IP 4 4 4
Power supply voltage V/Hz 230V~50HZ
Electrical power input W 73 82 105
Empty weight ka 28.4 28.4 30.7
Type of unit
C10-C1
1-C13-C23-C33 -C43-C53-C63-C 83-C93-B23-B33
C10-C11 flues installation pressure Pa 86 89 94

Ĵ

Page 53

ErP product fiche

MODEL: BLUEHELIX HITECH RRT 24 C - (0T4B2AGA)
Trademark: FERROLI
Condensing boiler: YES
Low-temperature boiler (**): YES
B1 Boiler: NO
Combination heater: YES
Cogeneration space heater: NO
Item Symbol Unit Value
Seasonal space heating energy efficiency class (from A+++ to D) А
Rated heat output Pn kW 20
Seasonal space heating energy efficiency η s % 94
Useful heat output
Useful heat output at rated heat output and high-temperature regime (*) P4 kW 20,0
Useful heat output at 30% of rated heat output and low-temperature regime (**) P1 kW 6,7
Useful efficiency
Useful efficiency at rated heat output and high-temperature regime (*) η4 % 88,3
Useful efficiency at 30% of rated heat output and low-temperature regime (**) η 1 % 98,8
Auxiliary electricity consumption
At full load elmax kW 0,024
At part load elmin kW 0,010
In standby mode PSB kW 0,004
Other items
Standby heat loss Pstby kW 0,042
Ignition burner power consumption Pign kW 0,000
Annual energy consumption QHE GJ 38
Sound power level LWA dB 47
Emissions of nitrogen oxides NOx mg/kWh 34
For combination heaters
Declared load profile XL
Water heating energy efficiency class (from A+ to F) А
Daily electricity consumption Qelec kWh 0,148
Annual electricity consumption AEC kWh 34
Water heating energy efficiency η wh % 87
Daily fuel consumption Qfuel kWh 20,220
Annual fuel consumption AFC GJ 17

(*) High-temperature regime means 60°C return temperature at neater inlet and 80°C feed temperature at neater outlet.

1 Juow temperature means for condensing policy so C, for low-temperature policy 37.°C and for other heaters 50°C return temperature (at heater inlet)

Page 54

ErP product fiche

MODEL: BLUEHELIX HITECH RRT 28 C - (0T4B4AGA)

Trademark: FERROLI
Condensing boiler: YES
Low-temperature boiler (**): YES
B1 Boiler: NO
Combination heater: YES
Cogeneration space heater: NO
Item Symbol Unit Value
Seasonal space heating energy efficiency class (from A+++ to D) А
Rated heat output Pn kW 24
Seasonal space heating energy efficiency η s % 94
Useful heat output
Useful heat output at rated heat output and high-temperature regime (*) P4 kW 24,0
Useful heat output at 30% of rated heat output and low-temperature regime (**) P1 kW 8,1
Useful efficiency
Useful efficiency at rated heat output and high-temperature regime (*) η4 % 88,3
Useful efficiency at 30% of rated heat output and low-temperature regime (**) η % 98,8
Auxiliary electricity consumption
At full load elmax kW 0,028
At part load elmin kW 0,011
In standby mode PSB kW 0,004
Other items
Standby heat loss Pstby kW 0,042
Ignition burner power consumption Pign kW 0,000
Annual energy consumption QHE GJ 44
Sound power level LWA dB 48
Emissions of nitrogen oxides NOx mg/kWh 31
For combination heaters
Declared load profile XL
Water heating energy efficiency class (from A+ to F) А
Daily electricity consumption Qelec kWh 0,148
Annual electricity consumption AEC kWh 32
Water heating energy efficiency η wh % 87
Daily fuel consumption Qfuel kWh 20,220
Annual fuel consumption AFC GJ 17

(*) High-temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.

(**) Low temperature means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return temperature (at heater inlet

Page 55

ErP product fiche

MODEL: BLUEHELIX HITECH RRT 34 C - (0T4B7AGA)
Trademark: FERROLI
Condensing boiler: YES
Low-temperature boiler (**): YES
B1 Boiler: NO
Combination heater: YES
Cogeneration space heater: NO
Item Symbol Unit Value
Seasonal space heating energy efficiency class (from A+++ to D) А
Rated heat output Pn kW 30
Seasonal space heating energy efficiency η s % 94
Useful heat output
Useful heat output at rated heat output and high-temperature regime (*) P4 kW 30,0
Useful heat output at 30% of rated heat output and low-temperature regime (**) P1 kW 10,1
Useful efficiency
Useful efficiency at rated heat output and high-temperature regime (*) η4 % 88,2
Useful efficiency at 30% of rated heat output and low-temperature regime (**) η % 98,6
Auxiliary electricity consumption
At full load elmax kW 0,045
At part load elmin kW 0,009
In standby mode PSB kW 0,004
Other items
Standby heat loss Pstby kW 0,046
Ignition burner power consumption Pign kW 0,000
Annual energy consumption QHE GJ 55
Sound power level LWA dB 49
Emissions of nitrogen oxides NOx mg/kWh 26
For combination heaters
Declared load profile XXL
Water heating energy efficiency class (from A+ to F) А
Daily electricity consumption Qelec kWh 0,186
Annual electricity consumption AEC kWh 41
Water heating energy efficiency η wh % 85
Daily fuel consumption Qfuel kWh 25,530
Annual fuel consumption AFC GJ 22

(*) High-temperature regime means 60°C return temperature at neater inlet and 80°C teed temperature at neater outlet.

(**) Low temperature means for condensing bollers 30°C, for low-temperature bollers 37°C and for other neaters 50°C return temperature (at neater inlet)

Page 56

Page 57

Ferroli

  • 16 Fan
  • 32 Heating circulating pump
  • 34 Heating temperature sensor
  • 42 DHW temperature probe
  • 44 Gas valve
  • 72 Room thermostat (not supplied)
  • 81 Ionization/ignition electrode
  • 95 Diverter valve

  • 136 Flowmeter
  • 138 External probe (optional)
  • 139 Remote timer control (optional)
  • 186 Return sensor
  • 191 Fume temperature sensor
  • 288 Frost protection kit
  • 246 Pressure transducer
  • A ON/OFF switch (configurable)

fig 70- Wiring diagram

Attention: Before connecting the room thermostat or remote timer control, remove the jumper on the terminal block.

To connect more zones of the hydraulic system controlled by thermostats with voltage-free contact, and the timer control has to be used as a remote control for the boiler, the voltage-free contacts of the zones must be connected to terminals 1-2 and the timer control to terminals 5-6

ALL CONNECTIONS TO THE TERMINAL BLOCK MUST BE WITH VOLTAGE-FREE CONTACTS (NOT 230V).

Page 58

Benchmark Commissioning and Servicing Section

It is a requirement that the boiler is installed and commissioned in accordance with manufacturer's instructions and the data fields on the commissioning checklist are completed in full.

To validate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation.

To maintain the boiler guarantee it is essential that the boiler is serviced annually by a Gas Safe registered engineer who has been trained on the boiler installed. The service details should be recorded on the Benchmark Service Interval Record and left with the householder.

www.centralheating.co.uk

Page 59
GAS BOILER SYSTEM COMMISSIONING CHECKLIST

This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.

Failure to install and commission according to the manufacturer's instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This does not affect the customer's statutory rights.

Customer name: Tele nhon hor
1010 prion. e num DEI.
Poilor make and model:
Gas s Sale regist ber.
Tele sphone e num ber:
Company address:
T- b Con nmiss date:
To be completed by the customer on receipt of a Bi egulatio ns C omplia ance Co ertific cate^
Building Regulations Notification Number er (if applicable) _
CONTROLS (tick the appropriate boxes $)
Time and temperature control to heating n Roo om therm losta it and p orogram ımer/ti imer Pr rograr mmab ole roor n theri nostat
, Load J/weath ier com pensa ation Op otimum start control
Time and temperature control to hot wa ter Cylind ler therm nosta t and p orogram ımer/ti imer Combi nation Boiler
Heating zone valves F itted Not re quired
Hot water zone valves F itted Not re quired
Thermostatic radiator valves F itted Not re quired
Automatic bypass to system F itted Not re quired
Boiler interlock Pr ovided
ALL SYSTEMS
The system has been flushed and clear ned in accordan ce with B nd bo oiler ma anufact urer's instru ctions Yes
What system cleaner was used?
What inhibitor was used? Q uanti tv litres
Has a primary water system filter been installed? Yes -, No
and record: 2/1 02/
Gas rate m³/nr | π s /nr
Burner operating pressure (if applicable ) mbar 0 R Gas I niet pre essure r mbar
Central heating flow temperature °C
Central heating return temperature °C
COMBINATION BOILERS ONLY
Is the installation in a hard water area (a above 200ppm) ? Yes No
If yes, has a water scale reducer been fitted? Yes No
What type of scale reducer has been fit ted?
DOMESTIC HOT WATER MODE Meas sure and Record 4: ,
Gas rate m³/hr OR ft³/hr
Burner operating pressure (at maximum ı rate) mbar OR Gas in let pres sure at t maxir num rate 1 mbar
Cold water inlet temperature °C
Hot water has been checked at all outle ts Yes Tem peratur е °C
Water flow rate ſ l/min
CONDENSING BOILERS ONLY
The condensate drain has been installe d in accordance with the manufac cturer r's instr ructions s and/ or BS 5546/BS 6798 Yes Τ
At max_rate: nnm 0 100 Potio
Record the following: At min_roto: ( - 00 00 /CO2 Batio
Mandatory Dequirement ssible) AND 002 Ralio
The besting and betweeter system com x Kate Duilding % CO 2 @Min Rate % -
The heiler and accession d products how Building , Rey - ufacture n'a ina tructio Vee
The operation of the heiler and evoters accord eman 1 5 11 5 siruciio 115 Vee
The operation of the bolier and system to al erstood i by th 4 Yes
I ne manufacturer s literature, including cora, n as beer n expi ained and left with tr ne cus tome er res
Commissioning Engineer's Signature
Customer's Signature
(To confirm satisfactory demonstration a and receipt of m anufactur rer's litera ature )
All installations in England and Wales m
*Competent Persons Scheme. A Building
ust be notified t
Regulations C
o Local Au
ompliance
uthority I Build
ate w
ing Co
vill ther
ntrol (L/
1 be iss
ABC)
ued to
either
o the c
directly
ustome
or thro ough a 1 ſ Бе 200 hn 101 k

© Heating and Hotwater Industry Council (HHIC)

www.centralheating.co.uk

THE MARK OF QUALITY FOR THE INSTALLATI Ind Servicing of Domestic Heating and I

Page 60
SERVICE INTERVAL RECORD

It is necessary that your heating system is serviced annually to validate your warranty and that the appropriate Service Interval Record is completed.

Service Provider

Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer's

instructions. Always use the manufacturer's specified spares when replacing parts.

SERVICE 01 Date: SERVICE 02 Date:
Engineer name: Engineer name:
Company name: Company name:
Telephone No: Telephone No:
Gas safe register No: Gas safe register No:
At max. rate: CO ppm AND CO 2 % At max. rate: CO ppm AND CO 2 % 6
Record: At min. rate: CO ppm AND CO 2 % Record: At min. rate: CO ppm AND CO 2 % 6
CO/CO 2 Ratio min. rate r nax rate CO/CO 2 Ratio min. rate max rate
Comments: Comments:
Signature Signature
SERVICE 03 Date: SERVICE 04 Date:
Engineer name: Engineer name:
Company name: Company name:
Gas safe register No: Gas safe register No:
%
Record: At min_rate: CO 2 /0 Record: At min_rate: CO
CO/CO Patio min rate max rate 2 70 0
nax rate Comments
Signature Signature
SERVICE US Date: SERVICE UD Date:
Engineer name: Engineer name:
Company name: Company name:
Telephone No: Telephone No:
Gas safe register No: Gas safe register No:
At max. rate: CO ppm A AND CO % At max. rate: CO ppm AND CO 2 % ,
)
Record: At min. rate: CO ppm A AND CO % At min. rate: CO ppm AND CO 2 % þ
CO/CO 2 Ratio min. rate r nax rate CO/CO 2 Ratio min. rate max rate
Comments: Comments:
1
Signature Signature
SERVICE 07 Date: SERVICE 08 Date:
Engineer name: 1 I Engineer name:
Company name: Company name:
Telephone No: Telephone No:
Gas safe register No: Gas safe register No
At max_rate: CO % 26
Record: At min_rate: CO % Record: At min_rate: CO ,
CO/CO 2 Ratio min rate may rate . 70 CO/CO. Botio min rate /0
Commonts: max rate Commonte:
Commenta.
0 ing at up
SERVICE 09 Date: SERVICE 10 Date:
Engineer name: Engineer name:
Company name: Company name:
Telephone No: Telephone No:
Gas safe register No: Gas safe register No:
At max. rate: CO ppm A AND CO2 % Peccerd: At max. rate: CO ppm AND CO2 C %
At min. rate: CO ppm A AND CO2 % At min. rate: CO ppm AND CO2 9 %
CO/CO 2 Ratio min. rate r nax rate CO/CO 2 Ratio min. rate max rate
Comments: Comments:
l
Signature Signature
oignature

*All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer.

Page 61

Page 62

Page 63

Page 64

Before contacting Ferroli please have available the completed BENCHMARK document (located in the back of this manual), boiler serial number and model detail.

For Technical assistance during the installation, call our Technical Helpline on 0330 205 0005.

You will be required to provide your Gas Safe Register Number.

Should you require a Service Engineer to visit, call our Service Centre on 0330 205 0005.

Calls to our 0330 numbers cost the same as a call to an 01 or 02 national number whether from a landline or mobile.

Calls are also inclusive in any bundle you may have with have your phone provider.

Phone numbers:

Installer

Service Engineer

BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS.

ALL SPECIFICATIONS SUBJECT TO CHANGE

Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check

this is not caused by lack of electricity supply, gas supply or low water pressure before calling our

Customer Service Helpline

FERROLI S.p.A.

Via Ritonda 78/a 37047 San Bonifacio - Verona - Italy www.ferroli.com Made in Italy

Loading...