"BLUEHELIX HITECH RRT 24C" GC N° 47-267-74 "BLUEHELIX HITECH RRT 28C" GC N° 47-267-75 "BLUEHELIX HITECH RRT 34C" GC N° 47-267-76
This symbol indicates "CAUTION" and is placed next to all safety warnings. Strictly follow these instructions in order to avoid danger and damage to persons, animals and things
This symbols calls attention to a note or important notice.
This symbol, which is used on the product, packaging or documents, means that at the end of its useful life, this product must not be collected, recycled or disposed of together with domestic waste.
Improper management of electric or electronic waste can lead to the leakage of hazardous substances contained in the product. For the purpose of preventing damage to health or the environment, users are kindly asked to separate this equipment from other types of waste and to ask for it to be dealt with by the municipal waste service or dealer under the conditions and according to the methods set down in national and international laws transposing the Directive 2012/19/EU.
Separate waste collection and recycling of unused equipment helps to save natural resources and to guarantee that this waste is processed in a manner that is safe for health and the environment.
For more information about how to collect electric and electronic equipment and appliances, please contact your local Counci or Public Authority competent to issue the relevant permits.
The CE marking certifies that the products meet the essential requirements of the relevant directives in force.
The declaration of conformity may be requested from the manufacturer.
∎æ
1 Operating instructions | 4 |
---|---|
1.1 Introduction | 4 |
1.2 Control panel | 4 |
1.3 Connection to the power supply, switching on and off | 7 |
1.4 Adjustments | 10 |
2 Installation | 18 |
---|---|
2.1 General Instructions | 18 |
2.2 Place of installation | 19 |
2.3 Plumbing connections | 19 |
2.4 Gas connection | 22 |
2.5 Electrical connections | 23 |
2.6 Fume ducts | 25 |
2.7 Condensate drain connection | 30 |
3 Service and maintenance | 32 |
---|---|
3.1 Adjustments | 32 |
3.2 Commissioning | |
3.3 Maintenance | |
3.4 Troubleshooting | 46 |
4 Technical data and characteristics51 | 1 |
---|---|
4.1 Dimensions and connections | 1 |
4.2 General view | 2 |
4.3 Hydraulic circuit | 2 |
4.4 Technical data table | 3 |
4.5 Diagrams | 7 |
4.6 Wiring diagram | 3 |
Ferroli
BlueHelix HiTech RRT C is a high-efficiency, low emissions premix condensing heat generator with heat exchanger in s/steel and incorporated DHW production, equipped with a microprocessor control system.
It can use Natural Gas (G20), Liquefied Gas (G30-G31), Propane Air (G230) and, thanks to the "Hydrogen plug-in" system, it self adjusts to also work with mixtures of natural gas and hydrogen (Natural Gas/Hydrogen mixtures 80%/ 20%), that will soon arrive in Europe to fight global warming.
The sealed chamber unit is suitable for indoor installation or outdoors in a partially protected place (according to EN 15502 ) with temperatures to -5°C.
fig. 1- Control panel
ğ
15 "Key lock" on
A heating request (generated by the Room Thermostat or Remote Timer Control) is indicated by the flashing radiator symbol.
When the burner is lit, the flame symbol appears and the 3 levels indicate the actual intensity.
Ferroli
A DHW request (generated by hot water draw-off) is indicated by the flashing faucet icon.
When the burner is lit, the flame symbol appears and the 3 levels indicate the actual intensity.
In Comfort mode (restoration of boiler internal temperature) the flame symbol appears while the faucet flashes.
In frost protection mode (flow temperature below 5°C) the flame symbol appears.
In case of a fault, the display shows the fault code with different graphics depending on the type
A-type fault (fig. 5): To unlock the boiler in the presence of this type of fault, press the button U until the message "Confirm?" appears. Then confirm with the button
F-type fault (fig. 4): A fault which will be automatically reset after the problem has been eliminated.
Message-type fault (fig. 6): The fault is such as not to compromise boiler operation. The message disappears when the problem is eliminated.
To avoid damage caused by freezing during long idle periods in winter, it is advisable to drain all the water from the boiler.
Electrically power to the boiler.
fig. 7- Switching on / Software version
fig. 8- Vent with fan on
To interrupt the venting phase (FH or Fh), keep the button pressed until the message " Stop? " appears. Then confirm with the button
fig. 10
Changing from one mode to another is possible by repeatedly pressing the button U, following the sequence shown in fig. 11.
A ="Summer" mode - B = "Winter" mode - C = "Off" mode
To turn the boiler off, repeatedly press the button () until detail C of fig. 11 is displayed.
fig. 11- Turning the boiler off
When the boiler is turned off, the PCB is still powered. DHW and heating are disabled. The frost protection system remains on. To relight the boiler, press the button ().
The boiler will be immediately ready in Winter and DHW mode.
The frost protection system does not work when the power and/or gas to the unit are turned off. To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all water from the boiler, the DHW circuit and the heating system water; or drain just the DHW circuit and add a suitable antifreeze to the heating system, as prescribed in sec. 2.3.
Repeatedly press the button U until the summer symbol (sun) appears, with the word "OFF" for heating (detail 10 - fig. 1): the boiler will only deliver hot water. The frost protection system remains on.
To reactivate the winter mode, repeatedly press the button () until the snowflake appears.
Ferroli
Use the heating buttons (details 3 and 4 - fig. 1) to adjust the temperature from a minimum of 20°C to a maximum of 80°C. The maximum value can be changed inside the parameters menu [TSP] via parameter P40.
Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a minimum of 40°C to a maximum of 55°C. The maximum value can be changed inside the parameters menu [TSP] via parameter P46.
fig. 15
If little water is drawn and/or with a high water inlet temperature, the DHW outlet temperature may differ from the set temperature.
Using the room thermostat, set the temperature required in the rooms. If the room thermostat is not installed, the boiler will keep the system at the set system delivery setpoint temperature.
Using the remote timer control, set the required temperature in the rooms. The boiler will adjust the system water according to the required room temperature. For operation with remote timer control, please refer to the relevant instruction manual.
The unit has a function that ensures fast hot water delivery and maximum comfort for the user. When this function is active ( COMFORT mode), the water in the boiler is kept at temperature, thus giving the immediate availability of hot water from the boiler when the faucet is turned on, avoiding waiting times.
The COMFORT function can be disabled by the user ( ECO mode) by pressing the button for 2 seconds. In ECO mode the display activates the symbol (detail 12 - fig. 1). To activate COMFORT mode press the button again for 2 seconds; the symbol disappears.
Pressing the button main displays the main menu of the boiler [MENU] shown in fig. 16.
The desired items can be selected with the buttons ----- and ----- heating.
To access the menus contained in the navigation menu [MENU] , press the button a after selecting the desired item.
fig. 16- Main menu
After selecting the installer menu [Service] , press the button E . To continue, enter the password " 1234 ". Use the buttons — and — DHW to set the cell value, and the buttons — and — heating to shift position (fig. 17).
fig. 17- Password entry
Confirm with the button ______to access the installer menu[SERVICE] screen where the following menus are available:
SERVICE | |
---|---|
TSP | • |
Test | ۲ |
ОТС | ۲ |
Zone | ۲ |
Auto Setup | ٢ |
fig. 18 |
This menu provides the information, in real time, of the various sensors present in the boiler.
To access it, press the button from the main screen, select the item [Diagnostic] and confirm with the button
fig. 19
Table 1 - Description - Boiler information menu [Diagnostic]
Parameter displayed | Description | Range |
---|---|---|
[CH 1 temp] | NTC Flow sensor (°C) | 0 ÷ 125 °C |
[CH 2 temp] | NTC Return sensor (°C) | 0 ÷ 125 °C |
[DHW temp] | NTC DHW sensor (storage tank probe) (°C) | 0 ÷ 125 °C |
[Ext temp] | NTC External sensor (°C) | +70 ÷ -30°C |
[Fume temp] | NTC Fume sensor (°C) | 0 ÷ 125 °C |
[Fan rpm] | Actual fan rpm | 0 ÷ 9999 RPM |
[Pump speed] | Actual modulating circulating pump speed (%) | 00% = Min., 100% = Max. |
[Power] | Actual burner power (%) | 0 ÷ 100 % |
[DHW flow] | Actual DHW draw (I/min) | 00 ÷ 99 l/min |
[Water Pressure] | Actual system water pressure (bar) | 0.0 ÷ 9.9 bar |
[Flame] | Flame status | ÷ 255 |
If the sensor is damaged or disconnected, the display will show dashes (--).
To return to the main screen, repeatedly press the button O or wait for automatic switching after 15 minutes.
The system counters are displayed in this menu:
Burner operation total hours.
[Ignition ok] Number of successful ignitions
[Ignition error] Number of failed ignitions.
[CH pump time] Pump operation hours in heating
pump operation hours in DHW.
Burner
Ignition ok Ignition error CH pump time |
||
---|---|---|
Ignition ok
Ignition error CH pump time |
0h | Burner |
Ignition error
CH pump time |
3 | Ignition ok |
CH pump time | 0 | Ignition error |
h | CH pump time | |
DHw pump time | h | DHW pump time |
fig. 20
The card can store the last 10 faults. Alarm 1 represents the most recent fault that occurred.
The codes of the faults saved are also displayed in the relevant menu of the Remote Timer Control.
Press the buttons + and - Heating to scroll the list of faults. Cancel is the last item in the list and which, once selected and confirmed with the button _____, allows all the faults history to be reset.
To exit the Boiler faults menu [ALARM] , press the button O repeatedly until reaching the main screen or wait for automatic exit after 15 minutes.
ALARM | ALARM | ||
---|---|---|---|
Alarm 1 | 27 | Alarm 4 | |
Alarm 2 | 37 | Alarm 5 | |
Alarm 3 | 12 | Alarm 6 | |
Alarm 4 | 13 | Alarm 7 | |
Alarm 5 | - | Alarm 8 | - |
Alarm 6 | - | Alarm 9 | |
Alarm 7 | - | Alarm 10 | |
Alarm 8 | Cancel | - |
fig. 21
In this menu it is possible to set some display parame-
[Contrast] - Contrast adjustment
[Brightness] - Brightness adjustment
[Backlight time] - Display lighting duration
[Lock time]* - Key lock
After keypad inactivity for a time equal to the set value (minutes), the symbol r appears and the buttons are inhibited
To reactivate the keypad, press the bu-tions () and simultaneously until the symbol sindi sindi aneousiy un symbol disappears (about 2 sec.).
* This function is available from version DSP FW 1.03
[Reset] - Restore factory values
When the external probe (optional) is installed, the boiler adjustment system works with "Sliding Temperature". In this mode, the heating system temperature is regulated according to weather conditions, to ensure high comfort and energy efficiency throughout the year. In particular, as the outside temperature increases the system flow temperature decreases according to a specific "compensation curve".
With "Sliding Temperature", the temperature set using the heating buttons (details 3 and 4 - fig. 1) becomes the maximum system flow temperature. It is advisable to set a maximum value to allow system adjustment throughout its useful operating range.
The boiler must be adjusted at the time of installation by qualified personnel. However, the user can make any further adjustments necessary to optimize comfort levels.
From the main screen, press the button to access the navigation menu [MENU] Using the buttons + and heating select the installer menu [SERVICE] and confirm with the button _____. Enter the password (see "Installer menu [SERVICE]" on page 12 ) and press the button _____. Using the buttons _____ and ____ heating select the menu Climatic curves setting [OTC] and confirm by pressing the button
Curve: select this item and use the buttons + and ---- DHW to adjust the desired curve f
By adjusting the curve to 0, the sliding temperature adjustment is disabled (see fig. 24).
To exit the Climatic curves setting [OTC] menu, press the button () repeatedly until reaching the main screen.
If the room temperature is lower than the desired value, it is advisable to set a higher order curve and vice versa. Proceed by increasing or decreasing in steps of one and check the result in the room.
05 80 70 60 50 40 30 fig. 24- Compensation curves
If the boiler is connected to the Remote Timer Control (optional), the previously described adjustments are managed as described in table 2
Heating temperature adjustment | Adjustment can be made from the Remote Timer Control menu and the boiler control panel. | |
---|---|---|
DHW temperature adjustment | Adjustment can be made from the Remote Timer Control menu and the boiler control panel. | |
Summer/Winter Switchover | Summer mode has priority over a possible Remote Timer Control heating demand. | |
On disabling DHW from the Remote Timer Control menu, the boiler selects Economy mode.
In this condition, the eco/comfort button on the boiler panel is disabled. |
||
Eco/Comfort selection | By enabling DHW from the Remote Timer Control menu, the boiler selects the Comfort mode (if previously enabled from the boiler panel). In this condition it is possible select one of the two modes on the boiler panel. | |
Sliding Temperature | You can make all the adjustments by using the remote timer control. |
The filling pressure, with system cold, read on the boiler water gauge (detail 2 - fig. 26) must be approx 1.0 bar. If the system pressure falls below minimum values, the boiler stops and fault F37 is displayed.
Once the system pressure is restored, the boiler will activate the 300-second air venting cycle, indicated on the display by Fh.
To avoid boiler shutdown, it is advisable to periodically check (with system cold) the pressure on the pressure gauge or on the display (detail 12 - fig. 1). In case of a pressure below 0.8 bar, it is advisable to restore it
Display | Description | Operation | |
---|---|---|---|
F40 | High pressure | The boiler stops | |
• 2.3 bar | Pressure slightly high | The boiler works at reduced power |
Display | Description | Operation |
---|---|---|
✓ 1.2 bar | Optimum pressure | Normal operation |
• 0.7 bar |
Pressure slightly low
(The indication with the symbol is visible only if parameter b09 is set to 1 ). |
The boiler continues to work.
It is advisable to refill the system as soon as possible. |
F37 | Low pressure | The boiler stops |
The drain cock ring nut is located under the safety valve inside the boiler.
To drain the system, turn the ring nut (ref. 3 - fig. 26) counter-clockwise to open the cock. Do not use any tools; use hands only.
To drain only the water in the boiler, first close the shut-off valves between the system and boiler before turning the ring nut.
To connect the safety valve to a disposal system, install the kit supplied (details 1 and 2 - fig. 26).
fig. 26
BOILER INSTALLATION MUST ONLY BE CARRIED OUT BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIPTIONS OF THE TECHNICAL STANDARDS (BS), ANY LOCAL REGULATIONS AND THE RULES OF PROPER WORKMANSHIP.
Incorrect installation can cause damage or injury for which the manufacturer declines any responsibility.
Installation of this unit must be carried out in strict compliance with the present instructions and the following regulations applicable in Great Britain.
Gas Safety Regulations (Installations & Use).
Local Building Regulations..
The Building Regulations (Part L).
The Buildings Standards (Scotland - Consolidated) Regulations. British Standards Codes of Practice (BSI):
B.S. | 5440 | Detail 1 | Flues |
---|---|---|---|
B.S. | 5440 | Detail 2 | Air supply and ventilation |
B.S. | 5449 | Systems for hot water production with forced circulation | |
B.S. | 6798 | Installation of gas-fired boilers for hot water | |
B.S. | 6891 | Gas systems | |
B.S. | 7671 | IEE wiring system regulations | |
B.S. | 4814 | Specifications for expansion tanks | |
B.S. | 5482 | LPG systems | |
B.S. | 7593 | Water treatment in central heating systems for domestic hot water production | |
B.S. | 5546 | Installation of systems for domestic hot water production | |
5955-8
Installation of plastic pipes
For Northern Ireland, observe the current applicable regulations.
Pay attention when handling the boiler insulation panels because the material they are made of could irritate the skin. No part of the boiler contains asbestos, mercury or CFC's.
For lifting and transport always take suitable safety precautions: keep your back straight, bend knees, do not turn your body, move feet, avoid bending forward or sideways and keep the load as close as possible to your body.
If possible, use a trolley or other suitable means to carry the boiler.
Grip the boiler firmly and, before lifting it, try and find the point where the load is concentrated in order to establish the centre of gravity and suitably reposition yourself.
The combustion circuit is sealed with respect to the place of installation and therefore the unit can be installed in any room except in a garage. The place of installation must be sufficiently ventilated to prevent the creation of dangerous conditions in case of even small gas leaks. Otherwise there may be risk of suffocation and intoxication or explosion and fire. This safety standard is set by the EEC Directive no. 2009/142 for all units that use gas (including sealed chamber units).
The unit is designed to operate in a partially protected place, with minimum temperature of -5°C. If provided with the special frost protection kit it can be used with minimum temperature to -15°C. The boiler must be installed in a sheltered place, e.g. under the slope of a roof, inside a balcony or in a protected recess.
The place of installation must be free of dusts, flammable materials or objects, or corrosive gases.
The boiler is arranged for wall mounting and comes as standard with a hooking bracket. Wall fixing must ensure stable and effective support for the generator.
If the unit is enclosed in a cabinet or mounted alongside, a space must be provided for removing the casing and for normal maintenance operations. fig. 27 gives the minimum distances to be respected
fia. 27
Α | Min. 2.5 cm |
---|---|
В | Min. 20 cm |
С | Min. 30cm |
D | Min. 60 cm (via an openable panel) |
The heating capacity of the boiler must be previously established by calculating the building's heat requirement according to the current regulations. To ensure proper operation and long boiler life, the plumbing system must be adequately sized and complete with all the necessary accessories, including a room thermostat, a thermostatic radiator valve (TRV), etc. The system flow and return pipes must have a diameter of at least 22 mm for the first 3 m of length from the ùnit.
If the system delivery and return pipes follow a path where air pockets could form in certain places, it is advisable to install vent valves at these points. Also, install type "A" drain cocks at the lowest points in the system to allow complete emptvina.
The temperature drop between the delivery manifold and the return to the boiler should not exceed 20 °C.
A flow rate of at least 6 litres/min through the heat exchanger is required
Do not use the water system pipes to earth electrical appliances.
Before installation, carefully flush all the heating system pipes to remove any residuals or impurities that could affect proper operation of the unit (as required by BS 7593 Building regs Doc L).
Carry out the connections to the unit as indicated in .
The safety valve discharge must be connected to a 15 mm diameter copper pipe descending from the boiler to run off system water in case of overpressure in the heating circuit. Otherwise, the boiler manufacturer cannot be held liable if the discharge valve operates and floods the room. The discharge must be run to the outside of the building to prevent the risk of damage or injury caused by discharged hot water in case of overpressure in the system.
Connections to the boiler are to be made in such a way as to ensure that its internal pipes and fittings are free of stress. If a non-return valve is installed also on the DHW circuit (if provided for), it is necessary to install a safety valve between the boiler and circuit (with non-return valve at least 3 metres from the boiler) or an expansion tank for domestic use.
The automatic by-pass must be installed a least 3 metres from the boiler & set to allow a minimum of 6 ltr/min through the valve when all TRV's are closed.
Provision must be made for replacing water lost from the sealed system. Reference should be made to BS6798, for methods of filling and making up sealed systems. There must be no direct connection between the boiler's central heating system and the mains water supply. The use of mains water to charge and pressurise the system directly, is conditional upon the Local Water Byelaws. Again any such connection must be disconnected after use. Ensure the filling point is on the return pipe to the boiler.
Attention - is drawn to the Model Water Byelaws.
Filling Loop in fig. 29 is supplied with boiler.
fig. 29 - Filling Loop (supplied with boiler)
The maximum domestic water pressure for the inlet supply is 9 bar (130 P.S.I.). If the cold mains supply exceeds 5 bar (72 P.S.I.), a water governor or pressure reducing valve must be fitted by the installer into the mains supply in an inconspicuous but accessible position preferably between 3 and 5 metres (10-16ft) before the appliance. Such a valve must be approved by WRAS. The fitting of a DHW expansion vessel is also recommended.
The isolation valves supplied (see fig. 30) must be installed between the boiler and heating system to allow the boiler to be isolated from the system if necessary.
If necessary, the use of antifreeze liquids, additives and inhibitors is allowed, only and exclusively if their manufacturer guarantees that the products are suitable for use and do not cause damage to the boiler's heat exchanger.or other components and/or materials of the boiler and system. It is prohibited to use generic antifreeze liquids, additives or inhibitors that are not expressly suitable for use in heating systems and compatible with the materials of the boiler and system
j.
B
BlueHelix HiTech RRT C boilers are suitable for installation in heating systems with non-significant entry of oxygen (ref. systems "case I" EN14868). A physical separator (e.g. plate heat exchanger) must be provided in systems with continuous entry of oxygen (e.g. underfloor systems without antidiffusion pipes or open vessel), or intermittent (less than 20% of system water content).
The water inside a heating system must comply with the applicable laws and regulations, the characteristics required by UNI 8065, and the indications of EN14868 (protection of metal materials against corrosion) must be observed.
The filling water (first filling and subsequent replenishment) must be clear, with hardness below 15°F and treated with suitable chemical conditioners against the initiation of corrosion, that are not aggressive on metals and plastics, do not develop gases and, in low-temperature systems, do not cause proliferation of bacterial or microbial masses.
The water contained in the system must be checked regularly (at least twice a year during the season of use, as required by UNI8065) and have: a possibly clear appearance, a hardness lower than 15°F for new systems or 20°F for existing systems, a PH higher than 7 and less than 8.5, an iron content (Fe) less than 0.5 mg/l, a copper content (Cu) less than 0.1 mg/l, a chloride content lower than 50mg/l, an electrical conductivity lower than 200 µS/cm, and must contain chemical conditioning agents in a concentration sufficient to protect the system at least for one year. Bacterial or microbial loads must not be present in low temperature systems.
Only use conditioners, additives, inhibitors and antifreeze liquids declared by the producer suitable for use in heating systems and that do not cause damage to the heat exchanger or other components and/or materials of the boiler and system.
Chemical conditioners must ensure complete deoxygenation of the water, contain specific protective agents for yellow metals (copper and its alloys), anti-scaling agents for limestone, neutral PH stabilizers and, in low-temperature systems, specific biocides for use in heating systems.
Recommended chemical conditioners:
SENTINEL X100 and SENTINEL X200
FERNOX F1 and FERNOX F3
The unit is equipped with a frost protection system that activates the boiler in heating mode when the system flow water temperature falls below 6°C. The device is not active if the power and/or gas supply to the unit is turned off. If necessary, to protect the system use a suitable antifreeze liquid that meets the above requirements and provided for by UNI 8065.
In the presence of adequate chemical/physical system and feed water treatments and related high cyclicity controls able to ensure the required parameters, for industrial process applications the product can be installed in open-vessel systems with vessel hydrostatic height able to ensure compliance with the minimum operating pressure indicated in the product technical specifications.
The presence of deposits on the boiler exchange surfaces due to non-compliance with the above requirements will involve non-recognition of the warranty.
Before making the connection, ensure that the unit is arranged for operation with the type of fuel available.
The gas connection must be made to the relevant connection (see fig. 64) in compliance with current legislation, using a rigid metal pipe or a continuous wall flexible hose in stainless steel, placing a gas valve between the system and boiler. Make sure all the gas connections are tight. Otherwise there may be a risk of fire, explosion or suffocation.
BEFORE CARRYING OUT ANY OPERATION REQUIRING REMOVAL OF THE CASING, DISCONNECT THE BOILER FROM THE ELECTRIC MAINS WITH THE MAIN SWITCH.
NEVER TOUCH THE ELECTRICAL COMPONENTS OR CONTACTS WITH THE MAIN SWITCH TURNED ON! DANGER OF ELECTRIC SHOCK WITH RISK OF INJURY OR DEATH!
The unit must be connected to an efficient grounding system in accordance with applicable safety regulations. Have the efficiency and suitability of the grounding system checked by professionally qualified personnel; the Manufacturer declines any liability for damage caused by failure to ground the system.
The boiler is pre-wired and equipped with a three-core connection cable to the electric line without plug. The connections to the grid must be made with a permanent connection and equipped with a bipolar switch with contact opening of at least 3 mm, interposing fuses of max. 3A between the boiler and line. Make sure to respect the polarities (LINE: brown wire / NEUTRAL: blue wire / GROUND: yellow-green wire) in the connections to the electric line.
The unit's power cable MUST NOT BE REPLACED BY THE USER . If the cable gets damaged, turn the unit off and have the cable replaced only by professionally qualified personnel. In case of replacement, use exclusively "HAR H05 VV-F" 3x0.75 mm2 cable with maximum ext. diameter of 8 mm.
ATTENTION: THE ROOM THERMOSTAT MUST HAVE VOLTAGE-FREE CON-TACTS. CONNECTING 230V TO THE ROOM THERMOSTAT TERMINALS WILL PERMANENTLY DAMAGE THE PCB.
When connecting a time control or timer, do not take the power supply for such devices from their cutoff contacts. Their power supply must be via a direct connection from the grid or with batteries, depending on the kind of device.
Remove the front panel ("Opening the front panel" on page 38) to access the terminal block (M) and fuse (F) by proceeding as follows (fig. 31 and fig. 32). The terminals indicated in fig. 31 must be with voltage-free contacts (not 230V). The arrangement of the terminals for the various connections is also given in the wiring diagram in fig. 70.
fig. 31
fig. 32
The variable output relay LC32 consists of a small card with a switchover of free contacts (closed means contact between C and NO). Operation is managed by the software.
For installation, carefully follow the instructions provided in the kit package and on the wiring diagram of fig. 70. To use the desired function, refer to the table 3.
Parameter b07 | Function LC32 | Action LC32 |
---|---|---|
0 | Manages a secondary gas valve (default) | The contacts are closed when the gas valve (in the boiler) is powered |
1 | Use as an alarm output (warning light comes on) | The contacts are closed when there is an error condition (generic) |
2 | Manages a water loading valve |
The contacts are closed until the water pressure in the hea-
ting circuit is restored to the normal level (after manual or automatic topping up) |
3 | Manages a solar 3-way valve | The contacts are closed when the DHW mode is active |
4 | Manages a second heating pump | The contacts are closed when the heating mode is active |
5 | Use as an alarm output (warning light goes off) | The contacts are opened when there is an error condition (generic) |
6 | Indicates ignition of the burner | The contacts are closed when the flame is present |
7 | Manages the trap heater | The contacts are closed when the frost protection mode is active |
DHW configuration | Parameter b06 | Parameter b06 | ||
---|---|---|---|---|
b06=0 | Contact open disables DHW and re-enables it if closed. | |||
b06=1 | Contact open disables heating and displays F50. Contact closed enables heating. | |||
b01 = 3 | b06=2 | The contact acts as a room thermostat. | ||
b06=3 |
Contact open displays
F51
and the boiler continues to operate.
It is used as an alarm. |
|||
b06=4 | The contact acts as a limit thermostat, if open it displays F53 and turns off the request. |
THE BOILERS MUST BE INSTALLED IN ROOMS THAT MEET THE FUNDA-MENTAL VENTILATION REQUIREMENTS. OTHERWISE THERE IS A DAN-GER OF ASPHYXIA OR POISONING.
READ THE INSTALLATION AND MAINTENANCE INSTRUCTIONS BEFORE INSTALLING THE UNIT.
IN CASE OF PRESSURES EXCEEDING 200 Pa INSIDE THE FUME EXHAUST PIPES, THE USE OF CLASS "H1" FLUES IS MANDATORY.
The unit is a "C-type" with sealed chamber and forced draft; the air inlet and fume outlet must be connected to one of the extraction/suction systems indicated below. Before proceeding with installation, check and carefully observe the above instructions. Also, comply with the provisions on the positioning of wall and/or roof terminals and the minimum distances from windows, walls, ventilation openings, etc.
In case of installation with maximum resistance (coaxial or separate flue) it is advisable to carry out a calibration procedure [AUTO SETUP] to optimize boiler combustion.
fig. 33- Examples of connection with coaxial pipes ( = Air / = Fumes)
For coaxial connection, fit the unit with one of the following starting accessories. For the wall hole dimensions, refer to the figure on the cover. Any horizontal sections of the fume exhaust must be kept sloping slightly towards the boiler, to prevent possible condensate from flowing back towards the outside and causing dripping.
fig. 34- Starting accessories for coaxial ducts
Coaxial 60/100 | Coaxial 80/125 | |
---|---|---|
Max. permissible length (horizontal) | All models 7 m | BlueHelix HiTech RRT 24 C = 28 m |
Max. permissible length (vertical) | All models 8 m |
BlueHelix HiTech RRT 28 C =
20
m
BlueHelix HiTech RRT 34 C = 20 m |
Reduction factor 90° bend | 1 m | 0.5 m |
Reduction factor 45° bend | 0.5 m | 0.25 m |
Ferroli
( | Connection with separate pi | pes | |
---|---|---|---|
C5x C
fig. 35- Examples |
s of connection with separate pipes (i) = Air / i) = Fumes | ||
1 | Table 6- Typology | ||
ŝ | Туре | Description | |
]_ | C1X | Wall horizontal exhaust and intake conditions (within 50cm) | . The inlet/outlet terminals must be concentric or close enough to be subjected to similar wind |
C3X | Roof vertical exhaust and intake. In | nlet/outlet terminals like for C12 | |
C5X |
Separate wall or roof intake and ex
located on opposite walls |
chaust and in any case in areas with different pressures. The exhaust and intake must not be | |
C6X | Intake and exhaust with separately | / certified pipes (EN 1856/1) | |
B2X | Intake from installation room and w | vall or roof exhaust ST BE PROVIDED WITH APPROPRIATE VENTILATION | |
£ | F | cts, fit the unit with the following starting accessory: | |
fig. 36- Starting accessory for separate ducts | |||
E
ti 1 2 3 |
|
maximum permissible length has not been exceeded by means of a simple calcula-
tem of split flues, including accessories and outlet terminals. e losses in m eq (equivalent m) of every component, according to the installation posi- sses is less than or equal to the maximum permissible length in table 7. |
|
٦ | able 7- Max. length separat | e ducts | |
Max. p | ermissible length | BlueHelix HiTech RRT 24 C = 80 m eq |
BlueHelix HiTech RRT 34 C = 70 m e
Losses in m eq | ||||||
---|---|---|---|---|---|---|
Air Fume exhau | exhaust | |||||
intake | Vertical | Horizontal | ||||
PIPE | 1 m M/F | 1KWMA83W | 1.0 | 1.6 | 2.0 | |
BEND | 45° M/F | 1KWMA65W | 1.2 | 1.8 | ||
90° M/F | 1KWMA01W | 1.5 | 2.0 | |||
PIPE SECTION | with test point | 1KWMA70W | 0.3 | 0.3 | ||
Ø 80 | TERMINAL | air, wall | 1KWMA85A | 2.0 | - | |
fumes, wall with antiwind | 1KWMA86A | - | 5.0 | |||
FLUE | Split air/fumes 80/80 | 010027X0 | - | 12.0 | ||
Fume outlet only Ø80 |
010026X0 +
1KWMA86U |
- | 4.0 |
Connection to collective flues
Туре | Description | 4 | - |
---|---|---|---|
C8X | Exhaust in single or common flue and wall intake | ||
B3X | Intake from installation room by means of concentric duct (that encloses the exhaust) and exhaust in common flue with natural draft | ||
C93 | Exhaust to a vertical terminal and intake from existing flue. |
If the BlueHelix HiTech RRT C boiler is to be connected to a flue or a single chimney with natural draft, the flue or chimney must be expressly designed by professionally qualified technical personnel in conformity with the current regulations and be suitable for sealed chamber units equipped with fan.
The BlueHelix HiTech RRT C boiler is fitted as standard with a clapet non-return valve (backflow preventer) therefore it can be connected, only if running on G20 gas , to collective flues in positive pressure.
Using this type of installation, parameter P67 must be set to 1.
In case of a type C(10)3 or C(11)3 boiler installation apply, IN A CLEARLY VISIBLE PLACE on the FRONT PA-NEL, the relevant white sticker included in the document envelope supplied with the unit.
After installation, check the tightness of the fumes and gas circuit.
• OTHERWISE THERE IS DANGER OF SUFFOCATION DUE TO THE EMISSION OF COMBUSTION FUMES.
osition of terminals
fiq. 38
Minimum dimensions of fume exhaust terminals | |||||
---|---|---|---|---|---|
Α | Directly under an opening, air inlet, openable window, etc. | 300 mm | |||
В | Above an opening, air inlet, openable window, etc. | 300 mm | |||
С | Horizontally to an opening, air inlet, openable window, etc. | 300 mm | |||
D | Under gutters, drain pipes | 75 mm | |||
Е | Under cornices or under eaves | 200 mm | |||
F | Under balconies or garages | 200 mm | |||
G | From a drain pipe or a vertical drain pipe | 150 mm | |||
н | From an internal or external corner | 100 mm | |||
I | Above ground level, a roof or balcony | 300 mm | |||
J | From a surface facing the terminal | 600 mm | |||
К | From a terminal facing the terminal | 1200 mm | |||
L | From a garage opening (e.g. door, window) with access to the home | 1200 mm | |||
М | Vertically from a terminal on the same wall | 1500 mm |
Minimum dimensions of fume exhaust terminals | ||||
---|---|---|---|---|
Ν | Horizontally from a terminal on the same wall 300 mm | |||
0 | From the wall on which the terminal is fitted N/A | |||
Р | From a vertical structure on the roof 150 mm | |||
Q | Above the intersection with the roof 300 mm | |||
NOTES |
|
building to
nsidered. |
The boiler has an internal trap for draining condensate. Install the hose " B " by pressing it into place. Before commissioning, fill the trap with approx. 0.5 L of water and connect the hose to the disposal system.
The connections to the drainage system must be resistant to acid condensation and always allow the condensate produced by the boiler to drain.
If the condensate drain is not connected to the waste water drainage system, a neutralizer must be installed.
OTHERWISE THERE IS A DANGER OF SUFFOCATION DUE TO THE EMIS-SION OF COMBUSTION FUMES.
THE CONDENSATE DRAIN MUST BE CONNECTED TO THE DRAINAGE SYS-TEM IN SUCH A WAY THAT THE LIQUID CONTAINED CANNOT FREEZE.
If possible, the condensate should be conveyed inside an underground drainage system or pipe. For that purpose, use a pipe of at least 22 mm diameter and a trap with flexible connection preinstalled in the unit to facilitate connection of the condensate drain pipe.
The pipe must be in glue-joined plastic and not in copper, since the condensate has a pH of 4 (slightly acid).
If the condensate drain pipe cannot be ended on the inside, it is advisable to run it outside as shown in the following figure.
The pipe sections going to the outside are exposed to the risk of freezing in particularly rigid weather conditions. To prevent this from occurring, it is advisable to reduce the length of the condensate drain pipes and run them on the inside, as much as possible, before going to the outside.
The pipes outside the building must be in glue-joined plastic with increased diameter of up to 32 or 40 mm and at least 3 m long for connection to a condensate collection pit or external drain.
If using a condensate collection pit, it must be as indicated in the figure below, or use a specific system (such as Mc Alpine SOAK1GR) available from the majority of suppliers of products and accessories for plumbing or heating systems.
fig. 40 - Condensate drain
j.
All adjustments described in this chapter can only be carried out by qualified personnel.
The unit can work with 2nd or 3rd family gases, which is clearly indicated on the packaging and on the data plate of the unit. If the unit has to be used with a gas other than the factory-set one, proceed as follows:
1 =G30/G31
MAKE SURE THE FRONT PANEL IS CLOSED AND THE INTAKE/FUME EXHAUST DUCTS ARE COMPLETELY AS-SEMBLED.
Cas | e studies | G20 | G30/G31 | G230 |
---|---|---|---|---|
Α | New boiler (first ignition/conversion or electrode replacement) | 7.5%-9.9% | 9%-11.5% | 9%-11.5% |
в | Boiler with at least 500 hours of operation | 9%+/-0.8 | 10%+/-0.8 | 10%+/-0.8 |
4. If the combustion values do not match, adjust the Offset values in the Test mode as described in the following paragraph.
During the CALIBRATION PROCEDURE [AUTO SETUP], the TEST PROCE-DURE [Test] or during the CO2 VALUE CHECK, the FRONT PANEL must be CLOSED and the INTAKE/FUME EXHAUST DUCTS completely assembled. Also, the boiler must not be in OFF mode or in vent cycle mode "FH-Fh" (see detail C of fig. 11) and there must not be a DHW or heating circuit request.
If the system heat dissipation is not sufficient to end the procedure, a DHW request can be activated only after the burner has ignited
The calibration procedure [Auto Setup] can only be performed if parameter b27 is set to 5.
Parameter b27 can be set manually to the value 5 , or by:
In each of the above cases, b27 automatically changes to 5.
It is necessary to perform the calibration procedure [Auto Setup] in the following cases:
The calibration procedure [Auto Setup] resets the combustion parameters previously recorded and must be done only in the cases described above.
Do a heating or DHW request.
1. Access the Main menu [MENU] using the button
Follow the path installer menu [Service] >enter the Password 1234 (see fig. 17) >test mode menu [Test].
Confirm with the button
When the Power value is followed by "ok" the combustion value will be saved.
5. The "Offset" adjustment range is from -8 to +8. Increasing the value decreases the CO2, decreasing it increases the CO2.
The CO2 adjustment must not be done with less than 500 burner operation hours, because the system adjusts itself.
Ferroli
To exit the test mode [Test] hold down the button 💍.
If the Test mode [Test] is active and enough hot water is drawn to activate the DHW mode , the boiler remains in Test mode [Test] but the 3-way valve switches to DHW.
The Test mode [Test] is automatically disabled in any case after 15 minutes or by stopping hot water draw-off (if enough hot water was drawn to activate the DHW mode).
ONLY QUALIFIED PERSONNEL CAN ACCESS THE SERVICE MENU AND MODIFY PARAMETERS.
Access the Main menu[MENU] with the button
Follow the path installer menu[Service] > enter the Password 1234 (see fig. 17). Confirm with the button
Press the Heating buttons to scroll the list, and display with value with the button E . To modify press the DHW buttons , confirm with the button E or cancel with the button ( ).
Table 10- | Transparen | t Parameters | Table |
---|
Index | Description | Range | Default |
---|---|---|---|
b01 | Boiler type selection | 3 = HEATING ONLY COMBI (DO NOT MODIFY) | 3 |
b02 | Boiler type |
1 = 24 kW
2 = 28 kW 3 = 34 kW 4 = Do not use 5 = Hybrid 24 C 6 = Hybrid 28 C 7 = Hybrid 34 C |
1 = 24 kW
2 = 28 kW 3 = 34 kW 4 = / 5 = Hybrid 24 C 6 = Hybrid 28 C 7 = Hybrid 34 C |
Index | Description | Range | Default | |
---|---|---|---|---|
b03 | Gas type |
0 = Natural gas
1 = Liquefied gas 2 = Propane-air |
0 | |
b04 |
System water pressure protec-
tion selection |
0 = Pressure switch
1 = Pressure transducer |
1 | |
b05 | Summer/Winter mode |
0 = WINTER - SUMMER - OFF
1 = WINTER - OFF |
0 = Enabled | |
b06 | Variable input contact operation selection |
|
2 | |
ь07 | Relay card LC32 operation selection |
|
0 | |
ζ γ | b08 | Hours without DHW draw-off |
0 ÷ 24 hours
(time for temporary deactivation of comfort mode without draw-off with b012 = 0 ) |
24 |
b09 | Fault 20 status selection |
|
0 | |
b10 | Not implemented | |||
b11 | Flowmeter timing |
0 = Deactivated
1-10 = seconds |
0 | |
b12 | Comfort mode |
|
0 | |
b13 | Not implemented | |||
b14 | DHW factor | 0 - 1 | 0 | |
b15 | Flowmeter type selection |
1 = Flow. (450 imp/l)
2 = Flow. (700 imp/l) 3 = Flow. (190 imp/l) |
3 | |
ب | b16 | Not implemented | ||
b17 | Not implemented | |||
b18 | DHW mode activation flow rate | 0 ÷ 100l/min/10 (do not set this value below 16) | 25 | |
b19 | DHW mode deactivation flow rate | 0-100 l/min/10 | 20 | |
b20 | Flue material selection |
0
= Standard
1 = PVC 2 = CPVC |
0 | |
b21 | Not implemented | |||
b22 | Not implemented | |||
b23 |
Standard flue shutdown maxi-
mum temperature |
60-110°C | 105 | |
b24 | PVC flue shutdown maximum temperature | 60-110°C | 93 | |
7 | b25 | CPVC flue shutdown maximum temperature | 60-110°C | 98 |
b26 | Not implemented | |||
b27 |
Calibration procedure [AUTO
SETUP] |
5
= Calibration procedure [AUTO SETUP] enabled
All other values = Calibration procedure [AUTO SETUP] disabled (See "Calibration procedure [AUTO SETUP]" on page 32) |
0 | |
b28 | Not implemented |
Index | Description | Range | Default |
---|---|---|---|
b29 | Restore Factory Values | See "* Restore Factory Values" on page 37. | 0 |
P30 | Heating ramp |
10÷80
(ex. 10=20°C/min, 20=12°C/min, 40=6°C/min, 80=3°C/min) |
40 |
P31 | Heating standby time | 0 ÷ 10 minutes | 4 |
P32 | Heating Post-Circulation |
0 ÷ 255
(Multiply the value by 10. Example 15 x 10 = 150 seconds ) |
15 |
P33 | Pump operation |
|
1 |
P34 | Pump modulation DeltaT | 0 ÷ 40°C | 20 |
P35 | Modulating pump min. speed | 30 ÷ 100% | 30 |
P36 | Modulating pump start speed | 90 ÷ 100% | 90 |
P37 | Modulating pump max. speed | 90 ÷ 100% | 100 |
P38 |
Pump deactivation temperature
during Post-Circulation |
0 ÷ 100°C | 55 |
P39 |
Pump activation hysteresis tem-
perature during Post-Circulation |
0 ÷ 100°C | 25 |
P40 | Heating user max. setpoint | 20 ÷ 90°C | 80 |
P41 | Max. output in heating | 0 ÷ 100% |
24 kW =
80
28 kW = 85 34 kW = 90 |
P42 | Burner shutdown in DHW |
0 = Fixed
1 = Linked to setpoint 2 = Solar |
0 |
P43 |
Comfort mode activation tempe-
rature |
0 ÷ 80°C | 40 |
P44 |
Comfort mode deactivation hys-
teresis |
0 ÷ 20°C | 20 |
P45 | DHW standby time | 30 ÷ 255 seconds | 120 |
P46 | DHW user max. setpoint | 40 ÷ 65°C | 55 |
P47 | DHW pump Post-Circulation | 0 ÷ 255 seconds | 30 |
P48 | Max. output in DHW | 0 ÷ 100% | 100 |
P49 | Not implemented (b01=2) | ||
P50 | Not implemented (b01=2) | ||
P51 |
Burner shutdown in DHW
(P42=2) |
0 ÷ 100
OFF = DHW user setpoint + P51 |
10 |
P52 | Burner ignition in DHW (P42=2) |
0 ÷ 100
ON = DHW user setpoint - P52 |
10 |
P53 | Solar standby time | 0 ÷ 255 seconds | 10 |
P54 |
System pre-circulation time in
heating |
0 ÷ 60 seconds | 30 |
P55 | System filling mode |
0 = Disabled
1 = Automatic |
0 |
P56 | Minimum system pressure limit value | 0-8 bar/10 (Only for boilers with water pressure sensor) | 4 |
P57 | System nominal pressure value | 5-20 bar/10 (Only for boilers with water pressure sensor) | 7 |
P58 | Maximum system pressure limit value | 25-35 bar/10 (Only for boilers with water pressure sensor) | 28 |
P59 | Circulating pump deactivation with OpenTherm |
|
0 |
P60 | Frost protection power | 0 ÷ 50% (0 = minimum) | 0 |
P61 | Minimum power | 0 ÷ 50% (0 = minimum) | 0 |
Index | Description | Range | Default | |
---|---|---|---|---|
Ť | P62 Fan minimum speed |
DO NOT MODIFY
(The parameters are automatically updated) |
G20/G230:
24 kW = 47 28 kW = 47 34 kW = 49 G30/G31: 24 kW = 49 28 kW = 49 34 kW = 48 |
|
P63 | Fan on speed |
DO NOT MODIFY
(The parameters are automatically updated) |
G20/G230:
24 kW = 160 28 kW = 160 34 kW = 140 G30/G31: 24 kW = 152 28 kW = 152 34 kW = 132 |
|
$ | P64 | Fan maximum speed |
DO NOT MODIFY
(The parameters are automatically updated) |
G20/G230:
24 kW = 140 28 kW = 172 34 kW = 194 G30/G31: 24 kW = 134 28 kW = 156 34 kW = 186 |
P65 | Not implemented | 1 | ||
P66 | Valve frequency | 0 ÷ 2 | 1 | |
P67 | Installation C(10)3/C(11)3 | 0 - 1 (1 = installation C(10)3 / C(11)3) | 0 | |
P68 | Flue parameter | 0 ÷ 10 (modify according to flue table) | 0 | |
P69 |
Heating hysteresis after ignition.
(available from MAIN and DSP FW 1.03) |
6 ÷ 30 °C | 10 |
To restore all the parameters to the factory values, set parameter b29 to 10 and confirm. Turn the power off for 10 seconds and then back on.
At this point it is necessary to restore parameter b02 and the modified parameters to the correct value according to the type of boiler. Parameter b27 will be automatically set to 5 .
Here it is possible to set some display parameters.
[Contrast] | |
---|---|
Contrast adjustment. | Contrast |
[Brightness] | Brightness |
Brightness adjustment | Backlight time |
[Backlight time]
Display backlight duration. |
Reset |
[Reset] | |
Restore factory values. |
DISPLAY
Мах
1m
IF THE ABOVE INSTRUCTIONS ARE NOT OBSERVED THERE MAY BE RISK OF SUFFOCATION OR POISONING DUE TO GAS OR FUMES ESCAPING; DANGER OF FIRE OR EXPLOSION. ALSO, THERE MAY BE A RISK OF ELEC-TRIC SHOCK OR FLOODING THE ROOM.
ALL MAINTENANCE WORK AND REPLACEMENTS MUST BE CARRIED OUT BY SKILLED QUALIFIED PERSONNEL.
Before carrying out any operation inside the boiler, disconnect the power and close the gas cock upstream. Otherwise there may be a danger of explosion, electric shock, suffocation or poisoning.
Some internal components of the boiler can reach temperatures high enough to cause severe burns. Before carrying out any operation, wait for these components to cool or else wear suitable gloves.
To open the boiler casing:
fig. 44- Front panel opening
On this unit, the casing also acts as a sealed chamber. After any operation involving opening the boiler, carefully check the correct refitting of the front panel and its seal.
Proceed in reverse order to refit the front panel. Make sure it is correctly hooked to the upper fastenings and is correctly positioned at the sides. Once the screw "1" is tightened, the head must not be below the lower reference fold (see fig. 45).
fig. 45- Correct position of front panel
To ensure proper operation of the unit over time, have qualified personnel carry out a yearly inspection, providing for the following checks:
After replacing the gas valve, burner, electrode and PCB, it is necessary to do the calibration procedure [AUTO SE-TUP] (see "Calibration procedure [AUTO SETUP]" on page 32). Then follow the instructions in par. "Checking the combustion values" on page 32.
fig. 46
fig. 47
fig. 48
Before carrying out the following instructions it is advisable to protect the room and the boiler's electrical box against accidental water spillage.
Disconnect the power supply and close the gas cock ahead of the valve
nnect the fume sensor connector 1.
• For assembly, proceed in reverse order
Ferroli
fig. 49
fig. 55
fiq. 56
fia. 58
fig. 59
fig. 60
If, even after touching the buttons, the display does not come on, check that the card is electrically powered. Using a digital multimeter, check for presence of power.
In case of no voltage, check the wiring
If the voltage is sufficient (Range 195 – 253 Vac), check the fuse (3.15AL@230VAC). The fuse is on the card. To access it, see fig. 31.
In case of operation problems or faults, the display shows the fault identification code.
There are faults that cause permanent shutdowns (indicated with the letter " A "): to restore operation, just hold down the button Until the message " Confirm ?" appears and confirm with the button (optional) , or use the RESET of the remote timer control (optional) if installed. If the boiler does not restart, the fault must be eliminated.
Other faults cause temporary shutdowns (indicated with the letter "F") which are automatically reset as soon as the value returns within the boiler's normal working range.
Table 11- List of faults
Fault code Fault | Possible cause | Cure | ||||||
---|---|---|---|---|---|---|---|---|
No gas |
Check the regular gas flow to the boiler
and that the air has been eliminated from the pipes |
|||||||
Ignition/detection electrode
fault |
Check the wiring of the electrode and that
it is correctly positioned and free of any deposits; replace the electrode if neces- sary. |
|||||||
A01 | No burner ignition |
Insufficient gas supply pres-
sure |
Check the gas supply pressure | |||||
Ū | Trap blocked | Check the trap and clean it if necessary | ||||||
Air/fume ducts obstructed | Remove the obstruction from the flue, fume extraction ducts, air inlet and terminals. | |||||||
63~G | Wrong calibration | Do the Calibration procedure [AUTO SETUP]. | ||||||
Faulty gas valve | Check the gas valve and replace it if necessary | |||||||
Check the ionization electrode wiring | ||||||||
Check the condition of the electrode | ||||||||
A02 | Flame present signal with | Electrode fault | Electrode to ground | |||||
burner off | Cable to ground | |||||||
Check the trap and clean it if necessary | ||||||||
Card fault | Check the card | |||||||
No 230V power supply | ||||||||
F05 | Fan fault |
Tachometric signal interrup-
ted |
Check the 5-pin connector wining | |||||
Fan damaged | Check the fan and replace it if necessary | |||||||
-
J |
Ionization electrode fault |
Check the position of the ionization elec-
trode, free it from any encrustations and do the Calibration procedure [AUTO SETUP]. Replace the electrode if neces- sary. |
||||||
Flame unstable | Check the burner | |||||||
A06 | No flame after the ignition phase | air/fume ducts obstructed | Remove the obstruction from the flue, fume extraction ducts, air inlet and terminals | |||||
Trap blocked | Check the trap and clean it if necessary | |||||||
Wrong calibration | Do the Calibration procedure [AUTO SETUP]. | |||||||
Insufficient gas supply pres-
sure |
Check the gas supply pressure | |||||||
λυσ | Overtemperature protec- |
Flow or return sensors inco-
rrectly positioned or dama- ged |
Check the correct positioning and opera-
tion of the sensors and replace them if necessary. |
|||||
tion intervention | No water circulation in the system | Check the circulating pump | ||||||
Air in the system | Vent the system |
Fault code | Fault | Possible cause | Cure | |||
---|---|---|---|---|---|---|
No water circulation in the system | Check the circulating pump and heating system | |||||
A09 | Exchanger protection intervention |
Poor circulation and ano-
malous flow probe tempera- ture increase |
Vent the system | |||
blocked exchanger | check the exchanger and system | |||||
Overtemperature protec- | Flow sensor damaged |
Check correct positioning and operation
of the flow sensor and replace it if neces- sary |
||||
F09 | tion intervention | No water circulation in the system | Check the circulating pump and heating system | |||
Air in the system | Vent the system | |||||
Sensor damaged | ||||||
F10 | Flow sensor fault | Wiring shorted | Check the wiring or replace the sensor | |||
Wiring disconnected | 1 | |||||
Gas valve connector not inserted. | Insert the connector | |||||
A11 | Gas valve connection |
Electrical connection bet-
ween control unit and gas valve interrupted. |
Check the wiring | |||
Gas valve damaged. | Replace the gas valve | |||||
Sensor damaged | ||||||
F11 | Return sensor fault | Wiring shorted | Check the wiring or replace the sensor | |||
Wiring disconnected | ||||||
Sensor damaged | ||||||
F12 | DHW sensor fault | Wiring shorted | Check the wiring or replace the sensor | |||
Wiring disconnected | ||||||
Probe damaged | ||||||
F13 | Fume probe fault | Wiring shorted | probe | |||
Wiring disconnected | F | |||||
A14 |
Fume extraction duct
safety device intervention |
Fault A07 generated 3 times in the last 24 hours | See fault A07 | |||
Check the exchanger | ||||||
F15 - A07 | High fume temperature | excessive temperature | Check the fume probe | |||
Check the flue material parameter | ||||||
F19 | Card parameter fault |
Wrong card parameter set-
ting |
Check and if necessary modify parameter b15 to 3 | |||
F21 |
System pressure slightly
high (visible only in the Alarm menu) |
System water pressure too high |
Partially drain the system to a pressure
(shown on the display) of 1÷1.5 bar. Check the expansion tank |
|||
Wrongly configured para-
meter |
Check if the parameter b04 is correctly configured | |||||
A23-A24-F51 | -51 Pressure sensor fault System pressure problems (transducer) | System pressure value outside set limits | ||||
b06 set to 3 | ||||||
A 26 | Intervention of fault F40 System water pressure to high | Partially drain the system to a pressure (shown on the display) of 1÷1.5 bar | ||||
A20 | hours |
Expansion vessel dischar-
ged or damaged |
Charge or replace the expansion vessel |
Fault code | Fault | Possible cause | Cure | |||
---|---|---|---|---|---|---|
F34 | Supply voltage under 180V | Electric mains trouble | Check the electrical system | |||
F35 | Wrong supply frequency | Electric mains trouble | Check the electrical system | |||
Incorrect system water | Pressure too low | Fill the system | ||||
F37 | pressure |
Pressure transducer not
connected or damaged |
Check the pressure transducer | |||
Probe damaged or wiring shorted | Check the wiring or replace the sensor | |||||
F39 | External probe fault |
Probe disconnected after
activating the sliding tempe- rature |
Reconnect the external probe or disable the sliding temperature | |||
F40 | Pressure sensor fault |
System water pressure too
high and parameter P58 not set to default |
Partially drain the system to a pressure (shown on the display) of 1÷1.5 bar | |||
Expansion vessel dischar-
ged or damaged |
Charge or replace the expansion vessel | |||||
A44 | Multiple requests error | Repeated short-term requests |
Check if there are pressure peaks in the DHW circuit. If necessary, modify para-
meter b11. |
|||
F47 | Pressure transducer no |
Pressure transducer not
electrically connected |
Check the electrical connection, transdu-
cer connector and wiring. |
|||
Γ4/ | communication | Pressure transducer not working | Replace the pressure transducer | |||
Limit thermostat fault with | No/poor water circulation in the system | Check the circulating pump and heating system | ||||
F50 - F53 | parameter b06 = 1 or 4 | Air in the system | Vent the system | |||
Incorrect parameter | Check the correct parameter setting | |||||
F62 | Calibration required | New card or boiler not yet calibrated | Do the Calibration procedure [AUTO SETUP]. | |||
F64 |
Maximum number of con-
secutive Resets exceeded |
Maximum number of conse-
cutive Resets exceeded |
Disconnect the power supply to the boiler
for 60 seconds and then reinstate the boiler |
|||
A65 ÷ A97 |
Specific combustion con-
trol errors |
Fume ducts obstructed.
Low gas pressure (A78 - A84). Condensate trap blocked. Fumes recirculation or com- |
Check that the fume ducts and the con-
densate trap are not blocked. Check the correct gas supply pressure. Do the CO 2 adjustment in TEST mode. If necessary, do the Calibration procedure |
|||
bustion problem | [AUTO SETUP]. | |||||
F65 ÷ F98 |
Specific combustion con-
trol errors |
Fume ducts obstructed.
Low gas pressure. Condensate trap blocked. Fumes recirculation or com- bustion problem |
Check that the tume ducts and the con-
densate trap are not blocked. Check the correct gas supply pressure. Do the CO 2 adjustment in TEST mode. If necessary, do the Calibration procedure [AUTO SETUP]. |
|||
A80 | Parasite flame signal after valve closing |
Electrode problem.
Gas valve problem. PCB problem. |
Check the correct position and condition
of the electrode. Check the PCB. Check the gas valve and replace it if necessary. |
|||
A88 |
Specific combustion con-
trol errors or gas valve |
Calibration activation with
burner lit. Combustion problem, faulty gas valve or PCB |
Reset the fault and do the Calibration pro-
cedure [AUTO SETUP]. If necessary, replace the gas valve or PCB. |
Fault code | Fault | Possible cause | Cure | |||
---|---|---|---|---|---|---|
F96 | Specific flame combustion error | Unstable flame or unstable flame signal after ignition. |
Check the gas supply, fume ducts and
condensate drain. Check the correct posi- tion and state of the electrode After about 3 minutes the error is reset. |
|||
Board replacement |
Reset the fault and do the Calibration pro-
cedure [AUTO SETUP]. |
|||||
A98 |
Too many SW errors or
error occurred during board replacement |
Fume ducts obstructed.
Low gas pressure. Condensate trap blocked. Fumes recirculation or com- bustion problem. |
Initially solve the problem, reset the fault
and check correct ignition. Do the Calibration procedure [AUTO SETUP]. Replace the board if necessary. |
|||
A99 | Generic error | PCB hardware or software error |
Reset the fault and check for correct igni-
tion. Do the Calibration procedure [AUTO SETUP]. If the problem persists, replace the board. |
|||
Connection cable interrup-
ted or not inserted |
Check the connection | |||||
F99 |
Communication fault bet-
ween display and control unit |
Misalignment of parameters between control unit and display | Turn the power off and on | |||
Factory values reset | Turn the power off and on |
EN
350
246
14
Ferroli
Water gauge Return sensor Fume temperature se
Trac DHW exchanger Condensate tray Pressure transduce Fan/Burner assembly
4.3 Hydraulic circuit
Domestic not water outlet |
---|
Cold water inlet |
System flow |
System return |
Safety valve |
Heating circulating pump |
Heating temperature sensor |
Automatic air vent |
DHW temperature probe |
Expansion vessel |
System filling faucet |
Diverter valve |
Flowmeter |
Return sensor |
Тгар |
DHW exchanger |
Automatic bypass (inside pump unit) |
Pressure transducer |
Table 12- Technical data table
0T4B2AGA BLUEHELIX HITECH RRT 24 C | |||||
---|---|---|---|---|---|
0T4B4AGA BLUEHELIX HITECH RRT 28 C | |||||
0T4B7AGA BLUEHELIX HITECH RRT 34 C | 1 | ||||
- | |||||
GAS CATEGORY II2H3+ (GB) | |||||
PRODUCT IDENTIFICATION CODES | 0T4B2AGA | 0T4B4AGA | 0T4B7AGA | ||
Max heating canacity | kW | 20.4 | 24.5 | 30.6 | |
Min, heating capacity | k/W | 20,4 | 3.5 | 3.5 | |
Max best output in besting (80/60°C) | 20 | 24 | 30 | ||
Min. heat output in heating (00/00 C) | 2.0 | 24 | 2.4 | ||
Max heat output in heating (50/30°C) | 21.6 | 26 | 32.5 | ||
Min. heat output in heating (50/30°C) | 21,0 | 20 | 2.0 | ||
Max besting consolity in DHW | 2,0 | 29.5 | 24.7 | ||
20 | 20,3 | 25 | |||
24.5 | 3,5 | 3,5 | |||
24,0 | 20 | 24 | |||
KVV | 3,4 | 3,4 | |||
Efficiency Prilax (00-00 C) | 90,1 | 90,1 | 97,9 | ||
90 | 90 | 90 | |||
Efficiency Pmax (50-30°C) | % | 106,1 | 106,1 | 106,1 | |
Efficiency Pmin (50-30°C) | % | 107,5 | 107,5 | 107,5 | |
% | 109,7 | 109,7 | 109,5 | ||
Flue losses with burner ON - Pmax (80/60) | % | 2 | 1,9 | 2 | |
Flue losses with burner ON - Pmin (80/60) | % | 1,5 | 1,/ | 1,5 | |
Shell losses with burner ON - Pmax (80/60) | % | 0,5 | 0,4 | 0,3 | |
Shell losses with burner ON - Pmin (80/60) | % | 2,4 | 2,4 | 1,4 | |
Flue losses with burner ON - Pmax (50/30) | % | 1,1 | 1,1 | 0,9 | |
Flue losses with burner ON - Pmin (50/30) | % | 0,7 | 0,7 | 0,6 | |
Shell losses with burner ON - Pmax (50/30) | % | 0,6 | 0,3 | 0,6 | |
Shell losses with burner ON - Pmin (50/30) | % | 1,1 | 1,1 | 1,1 | |
Flue losses with burner OFF (50K) | % | 0 | 0 | 0 | |
Shell losses with burner OFF (50K) | % | 0,2 | 0,2 | 0,1 | |
Flue losses with burner OFF (20K) | % | 0 | 0 | 0 | |
Shell losses with burner OFF (20K) | % | 0,1 | 0,1 | 0,1 | |
Gas supply pressure G20 | mbar | 20 | 20 | 20 | |
Max. gas flow G20 | m3/h | 2,6 | 3 | 3,7 | |
Min. gas flow G20 | m3/h | 0,4 | 0,4 | 0,4 | |
CO2 - G20 | % | 90,8 | 90,8 | 90,8 | |
Gas supply pressure G31 | mbar | 37 | 37 | 37 | |
Max. gas flow G31 | kg/h | 1,9 | 2,2 | 2,7 | |
Min. gas flow G31 | kg/h | 0,3 | 0,3 | 0,3 | |
CO2 - G31 | % | 100,8 | 100,8 | 100,8 | |
NOx emissions class | - | 6 (< 56 mg/kWh) | |||
Max. working pressure in heating | bar | 2,5 | 2,5 | 2,5 | |
Min. working pressure in heating | bar | 0,8 | 0,8 | 0,8 | |
Heating adjustment max. temperature | °C | 95 | 95 | 95 | |
Heating water content | liters | 2,9 | 2,9 | 4,3 | |
Heating expansion vessel capacity | liters | 8 | 8 | 10 | |
Heating expansion vessel precharge pressure | bar | 0,8 | 0,8 | 0,8 | |
Max. working pressure in DHW | bar | 9 | 9 | 9 | |
Min. working pressure in DHW | bar | 0,3 | 0,3 | 0,3 | |
DHW flow rate ∆t 25°C | l/min | 14 | 16,1 | 19.5 | |
DHW flow rate ∆t 30°C | l/min | 11.7 | 13,4 | 16.2 | |
DHW water content | liters | 0.3 | 0.3 | 0.4 | |
Protection rating | IP | 4 | 4 | 4 | |
Power supply voltage | V/Hz | 230V~50HZ | |||
Electrical power input | W | 73 | 82 | 105 | |
Empty weight | ka | 28.4 | 28.4 | 30.7 | |
Type of unit |
C10-C1 |
1-C13-C23-C33 | -C43-C53-C63-C | 83-C93-B23-B33 | |
C10-C11 flues installation pressure | Pa | 86 | 89 | 94 |
Ĵ
ErP product fiche
Trademark: FERROLI | |||
Condensing boiler: YES | |||
Low-temperature boiler (**): YES | |||
B1 Boiler: NO | |||
Combination heater: YES | |||
Cogeneration space heater: NO | |||
Item | Symbol | Unit | Value |
Seasonal space heating energy efficiency class (from A+++ to D) | А | ||
Rated heat output | Pn | kW | 20 |
Seasonal space heating energy efficiency | η s | % | 94 |
Useful heat output | |||
Useful heat output at rated heat output and high-temperature regime (*) | P4 | kW | 20,0 |
Useful heat output at 30% of rated heat output and low-temperature regime (**) | P1 | kW | 6,7 |
Useful efficiency | |||
Useful efficiency at rated heat output and high-temperature regime (*) | η4 | % | 88,3 |
Useful efficiency at 30% of rated heat output and low-temperature regime (**) | η 1 | % | 98,8 |
Auxiliary electricity consumption | |||
At full load | elmax | kW | 0,024 |
At part load | elmin | kW | 0,010 |
In standby mode | PSB | kW | 0,004 |
Other items | |||
Standby heat loss | Pstby | kW | 0,042 |
Ignition burner power consumption | Pign | kW | 0,000 |
Annual energy consumption | QHE | GJ | 38 |
Sound power level | LWA | dB | 47 |
Emissions of nitrogen oxides | NOx | mg/kWh | 34 |
For combination heaters | |||
Declared load profile | XL | ||
Water heating energy efficiency class (from A+ to F) | А | ||
Daily electricity consumption | Qelec | kWh | 0,148 |
Annual electricity consumption | AEC | kWh | 34 |
Water heating energy efficiency | η wh | % | 87 |
Daily fuel consumption | Qfuel | kWh | 20,220 |
Annual fuel consumption | AFC | GJ | 17 |
(*) High-temperature regime means 60°C return temperature at neater inlet and 80°C feed temperature at neater outlet.
1 Juow temperature means for condensing policy so C, for low-temperature policy 37.°C and for other heaters 50°C return temperature (at heater inlet)
ErP product fiche
MODEL: BLUEHELIX HITECH RRT 28 C - (0T4B4AGA)
Trademark: FERROLI | |||
---|---|---|---|
Condensing boiler: YES | |||
Low-temperature boiler (**): YES | |||
B1 Boiler: NO | |||
Combination heater: YES | |||
Cogeneration space heater: NO | |||
Item | Symbol | Unit | Value |
Seasonal space heating energy efficiency class (from A+++ to D) | А | ||
Rated heat output | Pn | kW | 24 |
Seasonal space heating energy efficiency | η s | % | 94 |
Useful heat output | |||
Useful heat output at rated heat output and high-temperature regime (*) | P4 | kW | 24,0 |
Useful heat output at 30% of rated heat output and low-temperature regime (**) | P1 | kW | 8,1 |
Useful efficiency | |||
Useful efficiency at rated heat output and high-temperature regime (*) | η4 | % | 88,3 |
Useful efficiency at 30% of rated heat output and low-temperature regime (**) | η | % | 98,8 |
Auxiliary electricity consumption | |||
At full load | elmax | kW | 0,028 |
At part load | elmin | kW | 0,011 |
In standby mode | PSB | kW | 0,004 |
Other items | |||
Standby heat loss | Pstby | kW | 0,042 |
Ignition burner power consumption | Pign | kW | 0,000 |
Annual energy consumption | QHE | GJ | 44 |
Sound power level | LWA | dB | 48 |
Emissions of nitrogen oxides | NOx | mg/kWh | 31 |
For combination heaters | |||
Declared load profile | XL | ||
Water heating energy efficiency class (from A+ to F) | А | ||
Daily electricity consumption | Qelec | kWh | 0,148 |
Annual electricity consumption | AEC | kWh | 32 |
Water heating energy efficiency | η wh | % | 87 |
Daily fuel consumption | Qfuel | kWh | 20,220 |
Annual fuel consumption | AFC | GJ | 17 |
(*) High-temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return temperature (at heater inlet
ErP product fiche
Trademark: FERROLI | |||
Condensing boiler: YES | |||
Low-temperature boiler (**): YES | |||
B1 Boiler: NO | |||
Combination heater: YES | |||
Cogeneration space heater: NO | |||
Item | Symbol | Unit | Value |
Seasonal space heating energy efficiency class (from A+++ to D) | А | ||
Rated heat output | Pn | kW | 30 |
Seasonal space heating energy efficiency | η s | % | 94 |
Useful heat output | |||
Useful heat output at rated heat output and high-temperature regime (*) | P4 | kW | 30,0 |
Useful heat output at 30% of rated heat output and low-temperature regime (**) | P1 | kW | 10,1 |
Useful efficiency | |||
Useful efficiency at rated heat output and high-temperature regime (*) | η4 | % | 88,2 |
Useful efficiency at 30% of rated heat output and low-temperature regime (**) | η | % | 98,6 |
Auxiliary electricity consumption | |||
At full load | elmax | kW | 0,045 |
At part load | elmin | kW | 0,009 |
In standby mode | PSB | kW | 0,004 |
Other items | |||
Standby heat loss | Pstby | kW | 0,046 |
Ignition burner power consumption | Pign | kW | 0,000 |
Annual energy consumption | QHE | GJ | 55 |
Sound power level | LWA | dB | 49 |
Emissions of nitrogen oxides | NOx | mg/kWh | 26 |
For combination heaters | |||
Declared load profile | XXL | ||
Water heating energy efficiency class (from A+ to F) | А | ||
Daily electricity consumption | Qelec | kWh | 0,186 |
Annual electricity consumption | AEC | kWh | 41 |
Water heating energy efficiency | η wh | % | 85 |
Daily fuel consumption | Qfuel | kWh | 25,530 |
Annual fuel consumption | AFC | GJ | 22 |
(*) High-temperature regime means 60°C return temperature at neater inlet and 80°C teed temperature at neater outlet.
(**) Low temperature means for condensing bollers 30°C, for low-temperature bollers 37°C and for other neaters 50°C return temperature (at neater inlet)
fig 70- Wiring diagram
Attention: Before connecting the room thermostat or remote timer control, remove the jumper on the terminal block.
To connect more zones of the hydraulic system controlled by thermostats with voltage-free contact, and the timer control has to be used as a remote control for the boiler, the voltage-free contacts of the zones must be connected to terminals 1-2 and the timer control to terminals 5-6
ALL CONNECTIONS TO THE TERMINAL BLOCK MUST BE WITH VOLTAGE-FREE CONTACTS (NOT 230V).
It is a requirement that the boiler is installed and commissioned in accordance with manufacturer's instructions and the data fields on the commissioning checklist are completed in full.
To validate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation.
To maintain the boiler guarantee it is essential that the boiler is serviced annually by a Gas Safe registered engineer who has been trained on the boiler installed. The service details should be recorded on the Benchmark Service Interval Record and left with the householder.
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission according to the manufacturer's instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This does not affect the customer's statutory rights.
Customer name: | Tele | nhon | hor | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1010 | prion. | e num | DEI. | |||||||||||||||
Poilor make and model: | ||||||||||||||||||
Gas | s Sale | regist | ber. | |||||||||||||||
Tele | sphone | e num | ber: | |||||||||||||||
Company address: | ||||||||||||||||||
T- b | Con | nmiss | date: | |||||||||||||||
To be completed by the customer on | receipt of a Bi | egulatio | ns C | omplia | ance Co | ertific | cate^ | |||||||||||
Building Regulations Notification Number | er (if applicable) | _ | ||||||||||||||||
CONTROLS (tick the appropriate boxes | $) | |||||||||||||||||
Time and temperature control to heating | n | Roo | om therm | losta | it and p | orogram | ımer/ti | imer | Pr | rograr | mmab | ole roor | n theri | nostat | ||||
, | Load | J/weath | ier com | pensa | ation | Op | otimum | start | control | |||||||||
Time and temperature control to hot wa | ter | Cylind | ler therm | nosta | t and p | orogram | ımer/ti | imer | Combi | nation | Boiler | |||||||
Heating zone valves | F | itted | Not re | quired | ||||||||||||||
Hot water zone valves | F | itted | Not re | quired | ||||||||||||||
Thermostatic radiator valves | F | itted | Not re | quired | ||||||||||||||
Automatic bypass to system | F | itted | Not re | quired | ||||||||||||||
Boiler interlock | Pr | ovided | ||||||||||||||||
ALL SYSTEMS | ||||||||||||||||||
The system has been flushed and clear | ned in accordan | ce with B | nd bo | oiler ma | anufact | urer's | instru | ctions | Yes | |||||||||
What system cleaner was used? | ||||||||||||||||||
What inhibitor was used? | Q | uanti | tv | litres | ||||||||||||||
Has a primary water system filter been | installed? | Yes | -, | No | ||||||||||||||
and record: | 2/1 | 02/ | ||||||||||||||||
Gas rate | m³/nr | | | π s /nr | |||||||||||||||
Burner operating pressure (if applicable | ) | mbar | 0 | R Gas I | niet pre | essure | • | r | mbar | |||||||||
Central heating flow temperature | °C | |||||||||||||||||
Central heating return temperature | °C | |||||||||||||||||
COMBINATION BOILERS ONLY | ||||||||||||||||||
Is the installation in a hard water area (a | above 200ppm) | ? | Yes | No | ||||||||||||||
If yes, has a water scale reducer been | fitted? | Yes | No | |||||||||||||||
What type of scale reducer has been fit | ted? | |||||||||||||||||
DOMESTIC HOT WATER MODE Meas | sure and Record | 4: | , | |||||||||||||||
Gas rate | m³/hr | OR | ft³/hr | |||||||||||||||
Burner operating pressure (at maximum | ı rate) | mbar | OR | Gas in | let pres | sure at | t maxir | num | rate | 1 | mbar | |||||||
Cold water inlet temperature | °C | |||||||||||||||||
Hot water has been checked at all outle | ts | Yes | Tem | peratur | е | °C | ||||||||||||
Water flow rate | ſ | l/min | ||||||||||||||||
CONDENSING BOILERS ONLY | ||||||||||||||||||
The condensate drain has been installe | d in accordance | with the | manufac | cturer | r's instr | ructions | s and/ | or BS | 5546/BS | 6798 | Yes | Τ | ||||||
At max_rate: | nnm | 0 | 100 | Potio | ||||||||||||||
Record the following: | At min_roto: ( | - 00 | 00 | /CO2 | Batio | |||||||||||||
Mandatory Dequirement | ssible) | AND | 002 | Ralio | ||||||||||||||
The besting and betweeter system com | x Kate | Duilding | % | CO 2 | @Min | Rate | % | - | ||||||||||
The heiler and accession d products how | Building | , Rey | - | ufacture | n'a ina | tructio | Vee | |||||||||||
The operation of the heiler and evoters | accord | eman | 1 5 11 5 | siruciio | 115 | Vee | ||||||||||||
The operation of the bolier and system | to al | erstood | i by th | 4 | Yes | |||||||||||||
I ne manufacturer s literature, including | cora, n | as beer | n expi | ained | and left | with tr | ne cus | tome | er | res | ||||||||
Commissioning Engineer's Signature | ||||||||||||||||||
Customer's Signature | ||||||||||||||||||
(To confirm satisfactory demonstration a | and receipt of m | anufactur | rer's litera | ature | ) | |||||||||||||
All installations in England and Wales m
*Competent Persons Scheme. A Building |
ust be notified t
Regulations C |
o Local Au
ompliance |
uthority I |
Build
ate w |
ing Co
vill ther |
ntrol (L/
1 be iss |
ABC)
ued to |
either
o the c |
directly
ustome |
or thro | ough a | 1 | ſ | Бе | 200 | hn | 101 | k |
© Heating and Hotwater Industry Council (HHIC)
www.centralheating.co.uk
THE MARK OF QUALITY FOR THE INSTALLATI Ind Servicing of Domestic Heating and I
It is necessary that your heating system is serviced annually to validate your warranty and that the appropriate Service Interval Record is completed.
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer's
instructions. Always use the manufacturer's specified spares when replacing parts.
SERVICE 01 | Date: | SERVICE 02 | Date: | |
---|---|---|---|---|
Engineer name: | Engineer name: | |||
Company name: | Company name: | |||
Telephone No: | Telephone No: | |||
Gas safe register No: | Gas safe register No: | |||
At max. rate: CO ppm | AND CO | 2 % | At max. rate: CO ppm AND CO 2 % | 6 |
Record: At min. rate: CO ppm | AND CO | 2 % | Record: At min. rate: CO ppm AND CO 2 % | 6 |
CO/CO 2 Ratio min. rate r | nax rate | CO/CO 2 Ratio min. rate max rate | ||
Comments: | Comments: | |||
Signature | Signature | |||
SERVICE 03 | Date: | SERVICE 04 | Date: | |
Engineer name: | Engineer name: | |||
Company name: | Company name: | |||
Gas safe register No: | Gas safe register No: | |||
% | ||||
Record: At min_rate: CO | 2 /0 | Record: At min_rate: CO | ||
CO/CO Patio min rate | max rate | 2 70 | 0 | |
nax rate | Comments | |||
Signature | Signature | |||
SERVICE US | Date: | SERVICE UD | Date: | |
Engineer name: | Engineer name: | |||
Company name: | Company name: | |||
Telephone No: | Telephone No: | |||
Gas safe register No: | Gas safe register No: | |||
At max. rate: CO ppm A | AND CO | % | At max. rate: CO ppm AND CO 2 % |
,
) |
Record: At min. rate: CO ppm A | AND CO | % | At min. rate: CO ppm AND CO 2 % | þ |
CO/CO 2 Ratio min. rate r | nax rate | CO/CO 2 Ratio min. rate max rate | ||
Comments: | Comments: | |||
1 | ||||
Signature | Signature | |||
SERVICE 07 | Date: | SERVICE 08 | Date: | |
Engineer name: | 1 | I | Engineer name: | |
Company name: | Company name: | |||
Telephone No: | Telephone No: | |||
Gas safe register No: | Gas safe register No | |||
At max_rate: CO | % | 26 | ||
Record: At min_rate: CO | % | Record: At min_rate: CO | , | |
CO/CO 2 Ratio min rate | may rate | . 70 | CO/CO. Botio min rate | /0 |
Commonts: | max rate | Commonte: | ||
Commenta. | ||||
0 ing at up | ||||
SERVICE 09 | Date: | SERVICE 10 | Date: | |
Engineer name: | Engineer name: | |||
Company name: | Company name: | |||
Telephone No: | Telephone No: | |||
Gas safe register No: | Gas safe register No: | |||
At max. rate: CO ppm A | AND CO2 | % | Peccerd: At max. rate: CO ppm AND CO2 C | % |
At min. rate: CO ppm A | AND CO2 | % | At min. rate: CO ppm AND CO2 9 | % |
CO/CO 2 Ratio min. rate r | nax rate | CO/CO 2 Ratio min. rate max rate | ||
Comments: | Comments: | |||
l | ||||
Signature | Signature | |||
oignature |
*All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer.
Before contacting Ferroli please have available the completed BENCHMARK document (located in the back of this manual), boiler serial number and model detail.
For Technical assistance during the installation, call our Technical Helpline on 0330 205 0005.
You will be required to provide your Gas Safe Register Number.
Should you require a Service Engineer to visit, call our Service Centre on 0330 205 0005.
Calls to our 0330 numbers cost the same as a call to an 01 or 02 national number whether from a landline or mobile.
Calls are also inclusive in any bundle you may have with have your phone provider.
Phone numbers:
Installer
Service Engineer
BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS.
ALL SPECIFICATIONS SUBJECT TO CHANGE
Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check
this is not caused by lack of electricity supply, gas supply or low water pressure before calling our
Customer Service Helpline
Via Ritonda 78/a 37047 San Bonifacio - Verona - Italy www.ferroli.com Made in Italy