Ferroli ARENA 30 C Installation And Operating Instructions Manual

Page 1
ARENA 30 C
WALL-HUNG, PRE-MIX
GAS-FIRED CONDENSING BOILER
INSTALLATION
AND
OPERATING INSTRUCTIONS
Appr. nr. B99.14 A - CE 0063 BL 3475
Page 2
ARENA 30 C
2
IMPORTANT
Your “benchmark” Installation, Commissioning and Service Record Log Book will be enclosed in your customer information pack. “This record must be completed and left with the end user”.
Ferroli is a member of the Benchmark initiative and fully supports the aims of the programme. Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency. Please see installation and servicing guidelines.
CE MARK
CE mark documents that the Ferroli gas appliances comply with the requirement contained in European directives applicable to them. In particular, the appliances comply with the following CEE directives and the technical specifications provided from them:
• Gas appliances directive 90/396
• Efficiencies directive 92/42
• Low tension directive 73/23 (modified from the 93/68)
• Electromagnetic compatibility directive 89/396 (modified from the 93/68)
Year 2000 Compliance Declaration
We will guarantee that this products is altogether suitable for the data change in the Year 2000 (boiler has no dependence from date change) and that no disruptions will occur which is caused by this product.
• Read the warnings given in this manual thorough­ly. They provide important information for safe installation, use and maintenance
• Keep the manual carefully for future consultation.
• The instruction manual is an integral and essential part of the product and must be kept by the user.
• If the appliance is sold or transferred to another owner or if the owner moves, leaving the appli­ance behind, always ensure that the manual is kept with the appliance for consultation by the new owner and /or installer.
• Incorrect installation or poor maintenance ab­solves the manufacturer from all liability for dam­age to people or things.
• Installation and maintenance must be carried out i conformity with current legislation, according to the manufacturer’s instructions and by qualified personnel.
• Before cleaning or maintenance, disconnect the appliance from the mains via the switch on the appliance or a suitable isolating device.
• In the event of malfunction or faulty operation, deactivate the appliance. Do not attempt to re­pair or carry out any other operation on the appliance directly. Contact qualified personnel only.
• Repairs or the replacement of components must be carried out exclusively by qualified personnel using original spare parts only. Failure to respect the above my compromise the safety of the appli­ance.
• To guarantee efficient operation, the appliance must be serviced once a year by an authorised service centre.
• The appliance may not be used for purposes other than those for which it was explicitly de­signed. Any other use is considered improper and therefore dangerous.
• Incorrect installation and use or failure to follow the instructions provided by the manufacturer absolve the manufacturer from all liability for damage.
• After unpacking, check that the contents are whole and undamaged.
• Keep packing out of reach of children as it is potentially hazardous.
• To clean external parts, use a damp cloth mois­tened with soapy water if necessary. Avoid using abrasive cleaning products and solvents.
Page 3
ARENA 30 C
3
INDEX
1. CHARACTERISTICS AND TECHNICAL DATA ................................................................ 4
1.1 Introduction ......................................................................................................................... 4
1.2 Structural charateristics ....................................................................................................... 5
1.3 Technical data table ............................................................................................................. 8
1.4 Diagrams.............................................................................................................................. 9
1.5 Functional flow chart ......................................................................................................... 10
2. INSTALLATION ............................................................................................................ 11
2.1 General Instructions .......................................................................................................... 11
2.2 Positioning and wall mounting .......................................................................................... 11
2.3 Connection to the hydraulic system.................................................................................. 12
2.4 Characteristics of the boiler water .................................................................................... 13
2.5 Connection to the gas system........................................................................................... 14
2.6 Condensation discharge connection ................................................................................. 14
2.7 Electrical connections ........................................................................................................ 15
2.8 Room thermostat, external unit and auxiliary controls..................................................... 15
2.9 Positioning the external probe.......................................................................................... 16
2.10 Flues................................................................................................................................. 17
2.11 Connection to concentric pipes ...................................................................................... 17
2.12 Connection to separate pipes ......................................................................................... 19
2.13 Table of losses for piping and accessories ...................................................................... 20
2.14 Terminal Position ............................................................................................................. 23
3. SERVICE AND MAINTENANCE .................................................................................. 24
3.1 Settings .............................................................................................................................. 24
3.2 Commissioning and testing ............................................................................................... 27
3.3 Maintenance ...................................................................................................................... 28
3.4 Replacement of parts ........................................................................................................32
3.5 Troubleshooting................................................................................................................. 36
4. OPERATING INSTRUCTIONS ...................................................................................... 39
4.1 Operation and controls ..................................................................................................... 39
4.2 Boiler control panel ........................................................................................................... 39
4.3 Ignition ............................................................................................................................... 40
4.4 Shut-down.......................................................................................................................... 40
4.5 Operating indications on the display ................................................................................ 40
4.6 Accessing the operating menu.......................................................................................... 40
4.7 Setting the heating system temperature .......................................................................... 41
4.8 Setting the domestic hot water temperature ................................................................... 41
4.9 Summer/Winter Selection ................................................................................................. 41
4.10 Aquafast device ............................................................................................................... 41
4.11 Outside temperature compensation ............................................................................... 42
4.12 Maintenance .................................................................................................................... 42
4.13 Anomalies ........................................................................................................................ 42
Page 4
ARENA 30 C
4
1.1 Introduction
Dear Customer, Thank you for having chosen the Arena 30 C, the latest generation FERROLI wall-hung boiler, featuring
advanced design and cutting-edge technology. The Arena 30 C is a pre-mix condensing thermal generator for heating and the production of domestic hot
water, with very high thermal efficiency and very low emissions, fired by natural gas or LPG. The boiler body is made up of a prismatic mono-block heat exchanger, with a hexagonal base made from
aluminium alloy, inserted in a cylindrical steel jacket, with water cavity, and insulated externally with high­density foam. The special design of the heat exchanger allows effective condensation of the water vapour contained in the flue gases, making the Arena highly efficient. The heat exchanger has been designed to maintain its characteristics of high thermal exchange over time.
Inside the aluminium mono-block heat exchanger, in a cooled combustion chamber, lies the pre-mix burner assembly, with a radial shape and metallic surfaces, featuring electronic ignition with ionisation flame control, which allows extremely low emission values, and at the same time guarantees high reliability and constant operation over time.
The combustion circuit and the air intake are sealed from the installation environment. The boiler is fitted with a variable speed fan and built-in modulating gas valve, connected directly to the
outside. The boiler control and regulation system is microprocessor-based, with advanced self-diagnostics. The user
interface, made up of a keypad and display, is user-friendly, and shows the operating status of the appliance at all times. The operating parameters and the data logs are saved internally and can be called up using the Personal Computer interface to simplify Service operations.
The heat output is regulated continuously across the entire operating range, with temperature-scrolling climate control, which automatically adapts the operating mode to the characteristics of the internal and external environments, of the building and its location.
A special internal device allows ultra-fast production of domestic hot water: hot water is available at the boiler outlet as soon as the hot water tap is opened.
Completing the fitted devices are a variable-speed heating pump and a fixed-speed domestic hot water pump, a high-capacity expansion vessel, flowmeter, safety valve, drain cock, water pressure switch, flue gas sensor, temperature sensors and safety thermostat.
1. CHARACTERISTICS AND TECHNICAL DATA
Page 5
ARENA 30 C
5
60
220
205
110120
460
760
368
739576,576,59544
108
50
68
12345
6
8
9
7
1.2 Structural charateristics
Dimensions and connections
Key
1 Heating outlet 2 Domestic hot water outlet 3 Gas inlet 4 Domestic hot water inlet 5 Heating return 6 Drain cock 7 Safety valve 8 Flue gas outlet 9 Air inlet
Fig. 1
Page 6
ARENA 30 C
6
114
213
14
220 16 136 151 194
32
216
56
44
69
70
215
214
179
161
217
191
186
49 34
35
Overall view and main components
Key
14 Safety valve 16 Fan 32 Heating pump 34 Heating temperature sensor 35 Auto air vent. 44 Gas valve 49 Safety thermostat 56 Expansion vessel 69 Flue gas outlet pipe
70 Air intake pipe 114 Water pressure switch 136 Flow-meter
151 System drain cock 161 Condensing heat exchanger 179 Non-return valve 186 Return sensor 191 Flue gas temperature sensor 194 Domestic hot water heat exchanger 213 Flexible inlet air pipe coupling 214 Flue gas outlet reducer 215 Air inlet reducer 216 Domestic hot water pump 217 Boiler body lagging 220 Ignition board
Fig. 2
Page 7
ARENA 30 C
7
Heating
outlet
Domestic hot water
outlet
Gas
inlet
Domestic hot water
inlet
Heating
inlet
Air
inlet
Flue gas
outlet
1644
56
49
191
136
32
34
186
22
82
188
216
114 14
Condensation
discharge
42
221
179
194
179
Key
14 Safety valve 16 Fan 22 Main burner assembly 32 Heating pump 34 Heating temperature sensor 42 Domestic hot water temperature sensor 44 Gas valve 49 Safety thermostat 56 Expansion vessel 82 Detection electrode
114 Water pressure switch 136 Flow-meter 179 Non-return valve 186 Return sensor 188 Ignition electrode 191 Flue gas temperature sensor 194 Domestic hot water heat exchanger 216 Domestic hot water pump 221 Bypass cock
Hydraulic diagram
Fig. 3
Page 8
ARENA 30 C
8
Heating
Maximum operating temperature, heating °C Maximum operating pressure, heating bar Minimum operating pressure, heating bar Expansion vessel capacity litri Expansion vessel pre-fill pressure bar Boiler total water content litri
Domestic hot water
Domestic hot water supply t 25°C l/min Domestic hot water supply t 30°C l/min
Domestic hot water supply t 35°C l/min Range of temperature regulation, domestic hot water °C Maximum operating pressure, domestic hot water bar Minimum operating pressure, domestic hot water bar
Dimensions, weights, conections
Height mm Width mm Depth mm Empty weight kg Gas system connections poll. Heating system connections poll. Domestic hot water circuit connections poll. Condensation discharge (flexible pipe) mm Maximum length separate flues D=80*
m
eq
(*Values expressed in equivalent air metres - refer to FERROLI calculation system)
Electrical power supply
Max Electrical Power Consumption W Pump electrical power consumption (Speed I-II-III) W
Power supply voltage/frequency V/Hz
85
3
0,8
12
1
11,8
17,5 14,6
12,5
40 - 65
6
0,25
760 460 368
55 1/2” 3/4” 1/2”
15x20
100
150
48-67-93
230/50
Power
Heat rate Hi
Heat rate Hs
Natural Gas rate (G20) Natural gas supply pressure (G20) LPG Gas rate (G31) LPG Gas supply pressure (G31)
Pmax Pmin
kW 31,5 8,2 kcal/h 27.090 7.052 nm
3
/h 3,27 0,80
mbar 20 20
kg/h 2,44 0,60
mbar 37 37
Useful heat output 80°C - 60°C
Useful heat output 50°C - 30°C
Combustion
CO2 (Natural Gas - G20) % CO2 (LPG - G31) % Flue gas temperature 80°C-60°C °C Flue gas temperature 50°C-30°C °C Flue gas flow rate kg/h Quantity of condensation kg/h pH of condensation water pH
Pmax
9,5
10,2
70 40 49
3,3
Pmin
9,0 9,5
65 32 13
1,4
4,1
kW 30,9 7,6 kcal/h 26.574 6.536
kW 34,3 8,4 kcal/h 29.498 7.224
kW 30,0 7,4 kcal/h 25.800 6.364
1.3 Technical data table
Page 9
ARENA 30 C
9
6,0
III
I
I
0,0
1,0
2,0
3,0
4,0
5,0
0 0,5 1 1,5 2 2,5 3
Q (m3/h)
3,5 4
H (m C.A.)
1.4 Diagrams
Heating pump head
Loss of boiler pressure
Fig. 4
Fig. 5
6,0
41,5 2 2,5 3 3,5
Q (m3/h)
1,0
2,0
3,0
4,0
5,0
1
0,0
0 0,5
H (m C.A.)
Page 10
ARENA 30 C
10
13
12
151412111087654
1245678101112
NL
321
24 V AC
24 V AC
X2
X1
131415
X5
X6
175
X10
X11
PC
3 2
X3
X4
123
6789101112
S4575B 1033
121110
87542
1
9
6
16
-
-
+
Output
-
-
DMF04
NL
L
N
NL
42
114
121110987654321
X7
----
191
72
32
98
216
186
188 82
34
136
139
138
49
4
5
NL
230 V
50 Hz
230 V
50 Hz
83
101
230V 50Hz Low voltage
Eco/Comfort
selection
12
1
DHW
disable switch
Key
16 Fan
32 Central heating pump
34 C.H. flow temperature sensor
42 D.H.W. temperature sensor
49 Overheat cut-off thermostat
72 Room thermostat (not fitted)
82 Ionisation electrode
83 Full sequence automatic control
98 Switch
101 Main P.C.B.
114 Water pressure switch
136 Flowmeter
138 Outside temperature sensor
139 Room unit (not fitted)
175 Transformer
186 Return temperature sensor
188 Hot surface igniter
191 Exhaust temperature sensor
216 Domestic hot water pump
1.5 Functional flow chart
Fig. 6
Page 11
ARENA 30 C
11
2. INSTALLATION
2.1 General Instructions
Gas Safety (Installation & Use) Regulations: 1996
In the interest of safety, it is the law that all gas appliances are installed by a competent person in accordance with the above Regulations, Building Regulations/Building Standards Scotland, Codes of Practice, current I.E.E. Regulations and the byelaws of the Local Water Undertaking. Failure to comply with the Regulations may lead to prosecution; it is your responsibility to ensure that the law is complied with.
N.B. For Northern Ireland the rules in force apply.
IMPORTANT If the boiler is to be fitted in
a timber framed building it should be fitted in accordance with the Institute of Gas Engineers document IGE/UP/7. If in doubt advice should be sought from the Local Supplier.
WARNING!! This appliance must be installed in a room with sufficient ventilation, to avoid dangerous conditions arising in the event of, even minor, gas leaks. These safety standards are imposed by the EEC Directive no. 09/396 for all gas appliances, including the so-called sealed appliances.
2.2 Positioning and wall mounting
The installation of the ARENA must be on a suitable non-combustible load bearing wall which will provide an adequate fixing for the boiler mounting bracket assembly. The loca­tion should be in an area where the water pipes will not be subjected to frost conditions. In siting the combination boiler the following limitations must be observed:
The combination boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current I.E.E. wiring regulations and in Scotland the electrical provisions of the building regulations applicable in Scotland, with respect to the installation of the combination boiler in a room or internal space containing a bath or shower.
Where a room sealed appliance is installed in a room containing a bath or shower any electrical switch or appliance control utilising mains electricity must be situated so that it cannot be touched by a person using the bath or shower.
The boiler is supplied ready for wall-hung installation. The rear frame of the appliance has a series of slots
> 50 cm
Minimum Recommended
A B
D
3 cm 15 cm
1,5 cm (from any openable panel)
15 cm 30 cm
C 10 cm 15 cm
A A
B
D
C
Fig. 7a
Page 12
ARENA 30 C
12
108
68
12345
6
Key
1 Heating outlet 2 Domestic hot water outlet 3 Gas inlet 4 Domestic hot water inlet 5 Heating return 6 Drain cock
Fig. 8
for fastening it to the wall, using screws with metal wall plugs. The fastening to the wall must provide stable and effective support of the appliance.
The boiler must be fastened to a closed part of wall, which is free of apertures or holes behind the frame of the boiler that may allow the internal components of the boiler to be reached.
If the appliance is enclosed in a cabinet or alongside another appliance, space must be allowed for normal maintenance operations. Fig. 7a shows the minimum and recommended space to be left free around the appliance.
The boiler is supplied with a paper drilling template used to trace the holes for fastening the appliance onto the wall. Furthermore, upon request a metal version of the wall drilling template is available, which can be reused for more than one appliance.
Position the drilling template on the part of the wall chosen for the installation of the boiler; using a spirit level, check that the lower bracket is perfectly horizontal. Temporarily fasten the drilling template to the wall using some adesive tape. Trace the fastening points “A”. Drill two 10 mm holes 90 mm deep to accept the wall plugs, fit wall plugs. Fit two special wall plugs on the wall as described in the fig. 7c. Fasten the wall bracket to the wall using an antitheft nut on the right side and a standard nut (M8) on the left side. Mount the boiler on the wall bracket and fix using an antitheft nut on the left side and a standard nut (M8) on the right side.. The connection for the water and gas pipes to the boiler are then defined, from “B” lines (for vertical connections) or from ”C” holes for horizontal connections (using optional Ferroli kit).
Note If there is no drilling template for mounting
the appliance, simply fasten the boiler to the wall using suitable support screws with metal wall plugs, through the holes in the boiler frame.
2.3 Connection to the hydraulic system
Make the connections to the corresponding couplings, according to the positions indicated in Fig. 3.
Arena
30 A
748
460
44 109,5 62 62 109,5 73
16 16
11
16
205
220
60
110120
8
9
7511061,561,511045
139
368
760
460
1 2 3 4 5
6
115
Ø 3/4” Ø 1/2” Ø 3/4”
Kit Ferroli cod. 1KWMA78Y
A
A
B
C
Fig. 7b
Fig. 7c
Page 13
ARENA 30 C
13
In addition, shut-off valves should be installed between the boiler and the heating system to allow, if necessary, the boiler to be isolated from the system. If a non-return valve is also installed in the domestic hot water circuit, a safety valve must be fitted between the boiler and this circuit.
The discharge of the safety valve must be connected to a funnel or collection pipe, to avoid water leaking onto the ground in the event of excessive pressure in the heating circuit.
Make the connections to the boiler so as its internal pipes are not subject to stress. For proper operation and long-life of the boiler, the hydraulic system must be correctly proportioned and always complete with all the accessories required to guarantee regular operation and conduction.
Upon request a connection kit can be supplied, simplifying connection to the system.
2.4 Characteristics of the boiler water
In the presence of water with hardness above 18 Clarke degrees, the water should be suitably treated, to avoid any deposits in the boiler caused by hard water, or corrosion caused by aggressive water. It should also be remembered that even minor deposits measuring just a few millimetres thick can cause, due to their low thermal conductivity, significant overheating of the walls of the boiler, with consequent and serious problems.
The water must always be treated in the case of very large systems (with high water capacity) or systems with the frequent inlet of recovered water. If, in these cases, the system needs to be partially or completely emptied, it must be refilled with treated water.
Water System
Note The boiler is designed for sealed systems only and must NOT be used on open vented systems.
Central Heating
Detailed recommendations are given in BS6798, BS5449, BS6700 and CP342 Part 2. Pipework not forming part of the useful heating surface should be insulated to prevent any heat losses or possible freezing (i.e. in roof spaces or ventilated underfloor spaces). Drain taps should be positioned at the lowest point of the system in accessible locations to permit the whole system to be drained down. The drain taps should be in accordance with BS2879. Copper tubing to BS2871, Part 1 is recommended for water carrying pipework. Pipework in horizontal runs should have a gradient where possible to facilitate the removal of air. Ensure that the boiler heat exchanger is not a natural point for air collection.
Make Up Water
Provision must be made for replacing water lost from the sealed system. Reference should be made to BS6798, for methods of filling and making up sealed systems. There must be no direct connection between the boiler's central heating system and the mains water supply. The use of mains water to charge and pressurise the system directly, is conditional upon the Local Water Byelaws. Again any such connection must be disconnected after use.
Domestic Hot Water
Always fit a scale reducer in "hard water areas" (18 clarke degrees or over)". A 15mm copper connection point on the boiler for attaching to the main supply is provided. The maximum domestic water pressure for the inlet supply is 10 bar (145 P.S.I.). If the cold mains supply exceeds 5 bar (72 P.S.I.), a water governor or pressure reducing valve must be fitted by the installer into the mains supply in an inconspicuous but accessible position preferable between 3 and 5 metres (10-16ft) before the appliance. Such a valve must be approved by the Water Research Council.
Attention - is drawn to the Model Water Byelaws. Fittings manufactured from duplex (alpha-beta) brass are not acceptable for underground use and certain
water undertakings will not accept their use above ground.
Ensure all pipework is adequately supported.
Page 14
ARENA 30 C
14
2.5 Connection to the gas system
If necessary the local Gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas.
An existing service pipe must not be used without prior consultation with the Local Gas supplier. A gas meter can only be connected by the Local Gas supplier, or by a Local Gas suppliers Contractor. Installation pipes should be fitted in accordance with BS6891-1988. Appliance inlet working pressure must be 20mbar MINIMUM, for NG and 37 mbar minimum for LPG. Pipework from the meter to the combination boiler must be of an adequate size. The boiler requires 2.73m3/h of natural gas, and 2,00 kg/h of LPG. Do not use pipes of a smaller size than the combination boiler inlet gas connection. The complete installation must be tested for gas soundness and purged as described in BS6981-1988. All
pipework must be adequately supported. An isolating gas valve is provided and should be fitted on the boiler gas inlet. Please wait 10 minutes when lighting from cold before checking gas rate. Gas pressures should be checked after the boiler has operated for 10 minutes to reach thermal equilibrium.
2.6 Condensation discharge connection
The boiler must be connected to the condensation discharge siphon, supplied as standard with the appliance.
1) Take out the flexible grey condensation discharge pipe A, already mounted in the boiler, from the proper slot on the bottom;
2) Place the siphon on the wall, fix it to the wall with a screw + plug through the fixing point B;
3) Connect the grey pipe A to the hose connector E on the top of siphon, cutting it to the right length if necessary;
4) Connect the corrugated pipe C to the bottom connector D;
5) Before definitively connecting the corrugated pipe C to the drainage system, fill the siphon with about 0,5 litres of water
Attenzione:
Riempire il sifone con acqua prima di collegarlo
A
Fig. 9
B
E
C
D
Attention:
Fill the siphon with water before con­necting
Page 15
ARENA 30 C
15
EDCBA
123456789101112
2.8 Room thermostat, external unit and auxiliary controls
Below the electrical control box is a multipolar terminal block, for connecting:
• Room thermostat (1-2) WARNING: THE ROOM THERMOSTAT MUST NOT HAVE LIVE CONTACTS. CONNECTING 230V TO THE ROOM THERMOSTAT TERMI­NALS WILL CAUSE IRREVERSIBLE DAMAGE TO THE ELECTRONIC BOARD. When connecting a room thermostat with daily or weekly program, or a timer, avoid taking the power supply to these devices from their switch contacts. Their power supply must derive from a direct connection to the mains or using bat­teries, depending on the type of device. This appliance can also operate without a room thermostat, yet the latter is recommended for increased comfort and greater energy savings.
• Switch for economy/comfort remote selection (3-
4). With the switch turned off the boiler is main­tained in “Comfort”, independently from the setting on the menu or on the remote control.
• DHW exclusion switch (5-6) for remotely dis­able the DHW function. Open contact will ex­clude DHW.
• External temperature probe (7-8) With the probe (optional) connected, the boiler works in outside compensation temperature mode, depending on the compensation curve settled (ref. 4.11). If none probe is connected, the boiler works in standard mode and setting of a compensation curve (parameter 9 of menu) is ignored by the control system.
• Remote control (9-10), for remote control and regu­lation of the boiler, with weekly chronothermostat and climatic regulation functions.
To make these connections, unscrew the four screws which fasten the lower protective plate and connect the wires to the terminal block, respecting the position of the terminals (refer to the wiring diagrams, chap. 1.5)
Fig. 10 a
Fig. 10 b
Fig. 10 c
A Room thermostat B Eco/Comfort selection switch C Domestic hot water exclusion switch D External temperature sensor E Remote control
2.7 Electrical connections
Power supply
The boiler must be connected to a single-phase, 230 Volt-50 Hz power line, with max 3A fuses fitted between boiler and the line, as well as a bipolar switch ON/OFF with contacts whose opening is at least 3 mm. The boiler must always be properly earthed.
When electrically connecting the boiler to an electrical system with live and neutral, THE POLARITY MUST BE RESPECTED (LIVE: brown wire / NEUTRAL: blue wire / EARTH: yellow-green). Note: If replacing the electrical power cable, use only the “HAR H05 VV-F” cable, 3x0.75 mm2, with a maximum external diameter of 8 mm.
Page 16
ARENA 30 C
16
Fig. 12
Fig. 11
2.9 Positioning the external probe
The external probe is best installed on a wall facing north, north-west or which borders the majority of the main living area. The probe must never be exposed to the early morning sun, and, in general and where possible, must not receive direct sunlight; if necessary, it should be shielded.
The probe must not in any case be fitted near windows, doors, ventilation openings, flues, or sources of heat which may alter the reading.
Note: The maximum length allowed for the electrical cable connecting the boiler to the external probe is
50 m. A common two-lead cable can also be used.
H
1/2H
1/2H
H
N
N W
Page 17
ARENA 30 C
17
2.10 Flues
Arena is a type-C boiler with forced draught, the air inlet and the flue gas outlet must be connected to one of the exhaust–intake systems indicated as follows. Using the tables and the methods of calculation described, first verify, before installation, that the flues do not exceed the maximum allowed length.
2.11 Connection to concentric pipes
An aluminium “60/100 concentric adapter” is available for connecting the boiler to 60/100 mm concentric pipes. The extreme ease of mounting and the use of double-lip gaskets in the couplings makes this solution extremely advantageous and safe. Furthermore, an aluminium and plastic concentric kit is available for discharge using 80/125 concentric pipes.
The total length in linear metres of the concentric pipes must not exceed the maximum length indicated in the first table below. The second table shows the reductions to be used for any bends in the pipes, excluding the initial one.
For installation, connect the concentric kit directly to two diameter 80 bell-shaped reducers in the boilers, as indicated in Fig. 13. The concentric kit can then be connected directly to a concentric bend using a horizontal pipe or a concentric pipe in the vertical position.
Maximum allowable pipe length
Ø100/60 mm concentric
Arena 30 C 12 m
Vertical
11 m
Horizontal*
Reducers for concentric bends
90° concentric bend 45° concentric bend
1 m
0,5 m
Ø125/80 mm concentric
21 m
Vertical
20 m
Horizontal*
Fig. 13
1KWMA55Y
1KWMA57W
1KWMA35W
Ø 100
Ø 60
Øi 100
Øi 60
Page 18
ARENA 30 C
18
To locate the centre of the hole for the passage of the pipes in the wall, refer to Fig. 14:
Please consider that the horizontal concentric piping must have a slope towards the boiler of at least 3 mm/ m, to allow the condensation which forms in the flues to flow back to the boiler, and avoid external dripping. The concentric pipes should be sealed with the relative pipe coupling seal at the points of coupling to the wall. The external piping must protrude from the wall between 10 and 60 mm (Fig.15).
Fig. 14
Fig. 15
3°
60
110
142
Page 19
ARENA 30 C
19
Upon request, a wide range of pipes, bends and accessories can be supplied. For the various components, refer to tables 1 – 2 – 3 or to the flue accessory catalogue.
A simple calculation can be performed to ensure that the maximum allowable pipe length is not exceeded:
1 For each component, table 1 – 2 – 3 lists the loss of pressure in “equivalent air-metres”, depending
on the position of installation of the component itself (air intake or flue gas exhaust, vertical or horizontal).
The loss is called “equivalent air-metres” as it relates to the loss of a metre of air intake pipe (defined as being equal to 1). For example, a 90° Ø80 bend in flue gas exhaust has a loss equivalent to 2.5 air-metres, that is equal to 2.5 linear metres of air intake pipe.
2 Once having completely defined the layout of the double flue system, add the losses in equivalent-
metres, according to the position of installation of all the components and accessories in the system
3 Check that the total loss calculated is less than or equal to 100 equivalent metres, that is the maximum
allowable for this model of boiler. If the flue system chosen exceeds maximum allowable limit, some sections of the pipes should be
larger in diameter.
2.12 Connection to separate pipes
The separate Ø60 pipes for air intake and flue gas exhaust can be connected directly to the boiler, as shown in Fig. 16a. Separate Ø80 pipes can be connected directly, once the two 80/60 (optional) reducers have been fitted inside the boiler (Fig. 16b).
Ø60 Ø60
Flue Air
Ø80 Ø80
Ø80 Ø80
Flue Air
Fig. 16 a Fig. 16 b Fig. 16 c
Page 20
ARENA 30 C
20
2.13 Table of losses for piping and accessories
KWMA83U
KWMA86A
KWMA85A
KWMA86U
KWMA84U
Air Flue
Vertical
Horizontal
Vertical
Horizontal
KWMA01K
KWMA02K
KWMA05K
KWMA82A
KWMA38A • 0,50 m KWMA83A • 1,00 m KWMA06K • 2,00 m KWMA07K • 4,00 m
Description
Tubo Ø 80
male-female
Female-female
bend 45° Ø 80 mm
Female-female
bend 90° Ø 80 mm
Male-female
bend 90° Ø 80 mm
Pipe fitting M/M/F Ø80
with inspecting
plug+trap for
condensate drainage
system
Description
Airwall terminal
products of
combustion Ø80 mm
Air terminal of inlet protection Ø80 mm
Outlet flue air inlet
for concentric system
Ø80
Pipe fitting for
outlet flue Ø80 mm
Outlet flue air inlet for connection with
split end Ø80 mm
0,5
1 2 4
0,5
1 2 4
0,8 1,6 3,2 6,4
1 2 4 8
1,2 1,8
2,0 2,5
1,5 2,0
7
Reduction
KWMA55U
5
2
4
3
Air Flue
Vertical
Horizontal
Vertical
Horizontal
Reduction
12
Condensate flue
outlet
KWMA03U
Spigot and socket
reduction Ø 80/100 mm
0
Accessories Ø 80 Accessories Ø 80
Tab. 2
The loss values listed refer to original FERROLI pipes and accessories
Tab. 1
Page 21
ARENA 30 C
21
Air Flue
Vertical
Horizontal
Vertical
Horizontal
Description
3 3 4,0 4,5
3 4,5
4 5,2
Reduction
9
0
Accessories Ø 60
Air/flue wall terminal
Ø60 mm
KWMA90A
Male-female
bend 90° Ø 60 mm
KWMA88W
Male-female
bend 45° Ø 60 mm
KWMA39W
Male-female
flue Ø 60
KWMA89W • 1,00 m
5
KWMA02W
Spigot and socket
reduction
Ø 60/80 mm
Tab. 3
Page 22
ARENA 30 C
22
Fig. 17
For other accessories please refer to the manual: “Flue accessories and installation of forced air appliances”
Example of how to calculate the connection of two separate pipes, max flue length: 100 metres The flue and air pipes must be sloped towards the boiler by at least 3%.
Ref.
1
2
3
N° Pieces
20
20
1
Vertical flue pipe
Vertical air pipe
Flue
Description
Length
o loss
32 m
20 m
12 m
64 mTotal
20 m
12
3
Page 23
ARENA 30 C
23
2.14 Terminal Position
Fig. 18
P
D, E
Q
Q
l
B
C
A
G
F
L
J
H
H
K
N
N
MM
Q
Directly below an opening, air brick, (0-7 kW) opening windows, etc. (>7-14 kW)
(>14-32 kW) (>32-70 kW)
Above an opening, air brick, (0-7 kW) opening windows, etc. (>7-14 kW)
(>14-32 kW) (>32-70 kW)
Horizontally to an opening, air brick, (0-7 kW) opening windows, etc. (>7-14 kW)
(>14-32 kW)
(>32-70 kW) Below gutters, soil pipes or drain pipes Below eaves Below balconies or car port roof From a vertical drain pipe or soil pipe From an internal or external corner Above ground roof or balcony level From a surface facing the terminal
(also see 6.1.2) From a terminal facing the terminal From an opening in the car port ( e.g. door,
window) into the dwelling Vertically from a terminal on the same wall Horizontally from a terminal on the same wall From the wall on which the terminal is mounted From a vertical structure on the roof
Above intersection with roof
Dimensions Terminal position
(kW input expressed in net)
Balanced flues room
sealed
Open flues
Natural
draught
Natural
draught
Fanned
draught
Fanned draught
A
a
300 mm
600 mm 1500 mm 2000 mm
300 mm Not allowed 300 mm
B
a
300 mm 300 mm 300 mm 600 mm
300 mm Not allowed 300 mm
C
a
300 mm 400 mm 600 mm 600 mm
300 mm Not allowed 300 mm
D 300 mm 75 mm Not allowed 75 mm E 300 mm 200 mm Not allowed 200 mm F 600 mm 200 mm Not allowed 200 mm G 300 mm 150 mmbNot allowed 150 mm H 600 mm 300 mm Not allowed 200 mm I 300 mm 300 mm Not allowed 300 mm J 600 mm 600 mm N/A 600 mm
K 600 mm 1200 mm N/A 1200 mm L 1200 mm 1200 mm N/A 1200 mm
M 1500 mm 1500 mm N/A 1500 mm N 300 mm 300 mm N/A 300 mm O N/A N/A N/A 50 mm P N/A N/A See Table 2
and Fig. 6b
N/A
Q N/A N/A See Table 2
and Fig. 4
150 mm
NOTE N/A = Not applicable
a
I
n addition, the terminal should not be nearer than 150 mm (fanned draucht) or 300 mm (natural draught) to an opening in the building fabric formed for the purpose of accommodating
a built-in element such as a window frame, (see Figure C2). Separation distances are linked to the rated heat inputs as shown.
b
This dimension may be reduced to 75 mm for appliances of up to 5 kW heat input.
Minimum dimensions of flue terminal positions
Page 24
ARENA 30 C
24
Supply gas Restrictor Methane (G20)
Propane (G31)
-
Ø 5,2 mm
Category
2H 3P
Nominal CO2 at maximum power
9,5 %
10,2 %
3.
SERVICE AND MAINTENANCE
3.1 Settings
Gas conversion
The adjustment and transformation operations must only be performed by Qualified Personnel. FERROLI S.p.A. declines all liability for damage to persons and/or things deriving from tampering with the
appliance by non-authorised persons. The appliance can operate with natural or LPG supply gas, and is factory configured for use with one of the
two gases, as is clearly marked on the packaging and on the rating plate on the appliance itself. If the appliance has to be used with a gas other than the one it has been set for, it is necessary to insert (or
remove) the restrictor between the gas valve and the air inlet Venturi, and operate on the regulation screw F (fig. 19) placed on the Venturi unit to regulate the CO2 content in the flue gas to the nominal value (within +/- 0.1%) described in the following table::
To convert, proceed as follows:
1 Remove the lower protection plate and open the boiler casing 2 If necessary, insert or remove the restrictor following the instructions to points 3-11, otherwise go
to point 12
3 Disconnect the gas and the electrical power supply if the boiler is already installed 4 Remove the ignition device “A” from the valve body, removing the fastening screw ”B”
Fig. 19
C
D
B
A
F
Page 25
ARENA 30 C
25
5 Unscrew the union nut between the gas valve and the gas inlet pipe 6 Remove the flexible inlet air pipe from the Venturi mouthpiece on the fan 7 Unscrew the fastening screws “C” and remove the Venturi unit + gas valve
8 Unscrew the three fastening screws “D” and separate the gas valve and the Venturi 9 Replace the diaphragm “E”, making sure the new restrictor and the gasket are repositioned correctly
inside the housing in the valve body
10 Reassemble the gas valve, ignition device, connections, following the previous instructions in the
reverse order
11 Check the seal of the gas connections 12 Insert the probe of a combustion analyzer in the outlet flue gas of the boiler 13 Turn on the boiler and bring the burner to the maximum power: it is advised to open one or more
DHW taps and verify on the display that the parameter 8 (boiler power) arrives to 99.
14 By means of the analyzer, note the CO2 content in the flue gas with boiler to maximum power 15 If necessary, slowly operate on the regulation screw F (fig.19) placed on the Venturi to bring the CO
2
content to the nominal value (within +/- 0.1%) expected in the table for the correspondent gas type. It is recommended to operate only on the screw F and not on the gas valve: this operation could compromise the correct functioning of the appliance
16 Once the regulation has been made, apply the orange plate contained in the transformation kit next
to the data plate and reassemble the boiler casing and the lower protection plate.
Fig. 20
E
Page 26
ARENA 30 C
26
t setting
The thermal head t, that is the difference in heating water temperature between the central heating outlet and return, can be set by varying the speed of the pump system (Fig. 21- A). Note that an increase in speed corresponds to a reduction of the t, and vice­versa. The curve of flow rate/ head of the standard pump is shown in Chapter 1.
To fully exploit the advantages of condensation, the central heating return inlet should work at low temperatures, possibly below 45-50 °C. The boiler will also work correctly at higher return temperatures, but in this case the temperature of the flue gas outlet is near to or above the dew point, with consequent reductions in condensation.
One specific feature of the ARENA boiler is the possibility to work with high t, up to 50°C. This feature can be exploited to maintain a low central heating return inlet temperature even when the required outlet temperature is high, and thus allow the appliance to operate in full condensation mode.
Bypass setting
The boiler is fitted with a bypass between the outlet and return, which guarantees minimum circulation inside the appliance even with systems fitted with full-closing thermostatic zone valves. To adjust the bypass, use a screwdriver on the adjustment cock, operating from the bottom of the boiler
Adjusting the hydraulic system pressure
The fill pressure with the system cold, read on the boiler hydrometer “B”, must be around 1.5 bar. If the system pressure falls during operation (caused by the evaporation of the gases dissolved in the water) to values below the minimum described above, reset the initial value. For correct boiler operation, the pressure inside, when hot, must be around 2 – 2.5 bar.
Fig. 21
Fig. 22
A
B
Page 27
ARENA 30 C
27
3.2 Commissioning and testing
The appliance must only be set-up for use by Qualified Personnel, such as personnel from Technical organization.
Checks to be performed during the first ignition, and after all maintenance operations which may have required the disconnection of the systems or intervention on the safety devices or parts of the boiler:
Before igniting the boiler:
• Open any shut-off valves between the boiler and the systems
• Check the seal of the gas system, proceeding with care and using a soapy water solution to find any leaks from the connections.
• Fill the system as indicated earlier and ensure that the air contained in the boiler and the system has been completely vented, by opening the air bleeding valve on the top of the appliance (Fig. 2) and any bleeding valves in the system.
• Check that there are no water leaks in the heating system, in the domestic hot water circuits, in the connections or in the boiler
• Check the correct connection of the electrical system
• Check that the appliance is properly earthed;.
• Check the correct connection of the appliance to the system for draining the condensation and the functioning of the condensation drain system itself.
• Check that the pressure value and gas rate for the heating system are correct.
• Check that there are no flammable liquids or materials in the immediate vicinity of the boiler
• Check that the non-return valve is operating (fig. A)
Igniting the boiler:
• Open the gas cock upstream from the boiler.
• Bleed the air in the pipe upstream from the gas valve.
• Close any switches or insert any plugs upstream of the boiler
• Place the main switch in the ON position.
• The boiler will switch on and perform a complete self-test cycle lasting around one minute, to check the operation of the main parts. The display shows, in sequence:
Software version Parameter version Operation in test - ( )
• If the cycle is performed correctly:
- If domestic hot water or heating is not required, the display shows a small “o“ (standby mode) followed by the temperature value of the outlet sensor. Then use the room thermostat or remote control to activate the request for heating
- If there is a request, the display will pass from the standby phase “ o “ to the heating phase “ c “ and the boiler will automatically begin operation, controlled by its regulation and safety devices.
- If anomalies arise during the self-test cycle or the successive ignition phase, the display will show the corresponding error code and the boiler will shut-down. Wait around 15 seconds and then press the reset button. The boiler will repeat the ignition cycle. If, after a second attempt, the boiler does not start, refer to the paragraph on “Troubleshooting” 3.5.
Note In the case of power failures while the boiler is in operation, the burner assembly will switch off. On
the return of mains power, the boiler will again perform the self-test cycle, following which the burner assembly will automatically restart (if there is still a request for heat).
operating
locked
fig. A
Page 28
ARENA 30 C
28
Checks during operation
• Ensure there are no gas or water leaks.
• Check the efficiency of the flues and air-flue gas pipes during the operation of the boiler.
• Check that the water circulation between the boiler and the systems is correct.
• Ensure that the gas valve modulates correctly both in the heating phase and the production of domestic hot water.
• Check the correct ignition of the boiler, effecting a series of ignition and shut-down tests using the room thermostat or the remote control.
• Ensure that the consumption of the fuel indicated by the counter corresponds to the values indicated in table at pag. 8.
• Check that there is the correct flow rate of domestic hot water with the t declared in the table: do not rely on measurements effected using empirical systems. The measurements should be made using special instruments at a point as close as possible to the boiler, considering the dispersion of heat from the piping.
• Ensure that without the request for heating the burner assembly turns on correctly on opening a domestic hot water tap. Check that during operation in heating mode, on opening a domestic hot water tap, the heating pump switches off, the domestic hot water pump starts and there is regular production of domestic hot water.
• Check the correct setting of the parameters and effect any custom settings required (compensation curve, heat rates, temperatures, etc.)
Shut-down
Close the gas cock upstream from the boiler and disconnect the electrical power supply to the appliance. Warning - For long periods of inactivity during the winter months, in order to avoid damage due to freezing,
all the water should be drained from the boiler, both the domestic hot water and the heating system; alternatively, drain only the domestic hot water and introduce the relative antifreeze into the heating system.
3.3 Maintenance
The following operations must only be performed by Qualified Personnel, such as personnel from our Technical organization.
Seasonal checks on the boiler and the flue
The following checks should be made on the appliance at least once a year:
• The control and safety devices (gas valve, flow-meter, thermostats, etc.) must be working properly.
• The pipes and the air-flue gas terminals must be free of obstacles and not contain any leaks.
• The condensation draining system must be efficient and must not contain any leaks or blockages
• The gas and water systems must be perfectly sealed.
• The burner assembly and the heat exchanger must be clean. Follow the instructions in the next paragraph.
• The electrodes must be free of deposits and positioned correctly.
• The pressure of the water system when cold must be around 1 – 1.5 bar; if not, reset this value.
• The expansion vessel must be full.
• The circulation and domestic hot water pumps must not be blocked.
Page 29
ARENA 30 C
29
Cleaning the boiler body and the burner assembly
The burner assembly and the parts of the boiler body in contact with condensation should be cleaned once a year. To clean these parts, use soft brushes or compressed air; do not use chemical products or steel brushes.
To dismount the burner assembly and access the boiler body, proceed as follows:
1. Close the gas supply cock and disconnect
the electrical power supply
2. Remove the lower protection plate and
the boiler casing
3. Disconnect cables “G” and “H” of the
electrodes from the ignition devices, Fig. 23a
4. Remove the ignition devices from the val­ve body, unscrewing screw “A”
5. Loosen the two fastening screws “B” and slide the control panel support bracket “C” and all the wiring forward. Fasten the bracket in the position of maximum extension
6. Disconnect the gas valve from the gas inlet pipe, unscrewing the union nut behind the valve, disconnect the flexible inlet air pipe coupling “E” from the fan and the compensation pipe “F” from the gas val­ve.
7. If there is less than 30 centimetres free space below the fan, remove the fan-gas valve unit by unscrewing the 4 fan fastening nuts. If the space is greater, this is not necessary, and the entire unit can be removed together with the burner assembly hexagonal support base (see following points).
8. Progressively unscrew the 3 fastening nuts “L”. Once removed, the unit “M” - burner
assembly, electrodes, hexagonal support base - can be removed from the boiler body as indicated in the series of images 23d - 23g. Intervene with care, avoiding excessive force on the fins of the hexagonal support base if the gasket “K” opposes resistance due to deposits. Some drops of water or residues may by released; avoid where possible having these come into contact with the electrical parts.
Fig. 23b
B
Fig. 23a
L
E
F
A
G
H
Page 30
ARENA 30 C
30
Fig. 23c
Fig. 23d
Fig. 23e
C
M
WARNING The hot wire spark electrode
is fragile! Both during and after removal handle the unit “M” with care to avoid damaging the electrode.
9. The burner assembly can be cleaned in
place or removed by unscrewing the three fastening screws on the hexagonal support base.
10. The lower part of the boiler body – where
condensation takes place - can now be accessed for cleaning. Carefully clean the fins “N” and the condensation collection and discharge area “O”. The upper part where the burner assembly is located does not require special maintenance. If necessary, blow with compressed air to eliminate small residues of combustion.
11. Follow the previous instructions in the
reverse order and reassemble the boiler. Always work with caution and pay special care to all the sealing systems, especially the gas seals and the gasket “K” between the burner assembly hexagonal support base and the condensation collector.
12. Once the boiler has been reassembled,
perform a complete operating test (as specified in the previous chapter), checking all the phases of ignition and operation, and the correct functioning of the safety and control devices, the sensors, thermostats, gas valve, fan and pumps.
13. Check that there are no gas leaks, including
the parts inside the boiler (gas pipe, gas valve connections, fan connections).
K
Page 31
ARENA 30 C
31
fig. 23g
fig. 23f
fig. 23h
N
O
Page 32
ARENA 30 C
32
Fig. 24
C
D
B
A
3.4 Replacement of parts
Initial procedure a) The boiler is cold, electricity supply is isolated, and the gas supply is turned off at the inlet of the boiler
b) For replacement of parts where water connections are broken, it will be necessary to isolate and drain
either or both the central heating or domestic hot water circuits of the boiler only. The cold water mains inlet is isolated at the inlet cock. The D.H.W. is drained by opening a hot tap. The C.H. flow and return cocks are turned off at the isolation cocks. The C.H. is drained via the pressure relief valve (twist about 1/2 of a turn) and the discharge tap on right . To ensure complete C.H. water drainage, turn the screw of the non-return valve on “locked” position (fig. A - pag. 26)
c) Remove components following special notice below and replace in reverse order. d) Ensure water and gas washers are in good condition.
Removing Boiler Jacket and sliding control panel
To remove the boiler jacket, unscrew the four screws on bottom of the boiler and the two screws on front supporting the control panel. Gently pull up the jacket.
If necessary, to have more space for working, the control panel could be slid forward , loosing the two screws “B” (fig. 23b) and pulling the support bracket “C” (fig. 23c)
Final procedure
• Re-open cocks and re-charge the system to about 1.5 bar, and vent boiler and radiators. Re-charge to 1.5 bar if necessary.
• Upon completion of the work the following. Should be checked:
1) Gas soundness of all joints
2) Water soundness of all joints
3) The electricity supply.
4) The pressure of the sealed system and top up where necessary.
Gas valve
• Isolate gas and electricity supplies
• Remove the lower protection plate jacket
• Remove the ignition device “A” from the valve body, removing the fastening screw “B”
• Unscrew the union nut between the gas valve and the gas inlet pipe
• Remove the flexible inlet air pipe from the Venturi mouthpiece on the fan
• Unscrew the fastening screws “C” and remove the Venturi unit + gas valve
• Unscrew the three fastening screws “D” and separate the gas valve and Venturi
Page 33
ARENA 30 C
33
Fan
• Isolate gas and electricity supplies
• Remove the lower protection plate and jacket
• Remove the ignition device “A” (fig. 26) from the valve body, removing the fastening screw “B” (fig. 25)
• Unscrew the union nut between the gas valve and the gas inlet pipe
• Remove the flexible inlet air pipe from the Venturi mouthpiece on the fan
• Unscrew the four nut “A” fixing the fan (fig. 25)
Unscrew the fastening screws “C” (fig. 24) and remove the Venturi unit + gas valve
Burner and electrodes
• Follow the “cleaning procedure” at page 29 from 1 to 8 to remove the burner assembly
• Carefully remove the hexagonal ceramic fibre
• To change the burner, remove the three fastening screw “A” (fig. 26)
• To change electrodes, unscrew the two screws to the supporting plate and remove it. Undo the brass nuts, to electrodes “B” (fig. 27). Reassemble reverce order.
DHW Heat exchanger
• Isolate gas, electricity and water supplies
• Remove the lower protection plate and jacket. Slide forward the control panel.
• Drain water from DHW and CH circuits
• Unscrew the four A nuts connecting the heat exchanger and remove it
A
A
A
B
Fig. 25
Fig. 26
Page 34
ARENA 30 C
34
Replacement of pump head (fig. 27)
• Isolate electricity and flow and return pipes
• Remove casing
• Release pressure from boiler via pressure relief valve
• Unplug the pump lead “B” from the pump head
• Place a piece of cloth or other absorbent material over the rear of the control panel to catch any drops of water that may fall when the pump head is removed.
• Using a 4 mm allen wrench undo the two allen screws “C” in the pump head, lift away pump head from the pump body
• Fit new head into pump body and secure with the allen screws tightening evenly.
• Replace electrical connection.
Replacement of pump body (fig. 27)
• Proceed as for removal of pump head
• Disconnect the two nuts “D“ fixing the pump body
• Remove pump
• Reassemble in reverse order taking care to ensure the O-rings are in place and undamaged.
Expansion Vessel (fig. 27) Isolate electricity and water supplies Remove outer case Loosen the “E” connections to expansion vessel Remove the expansion vessel Re-assemble in reverse order Re-pressure expansion vessel (charge pressure 0,8-1 bar) through the air charging valve Ensure pressure relief value is open (twist about 1/2 of a turn) when repressurizing
D.H.W. temperature sensor (fig. 27)
• Isolate electricity
• Remove outer case
• Pull out sensor “F” from tube, with its spring
• Remove electrical connections from sensor
• Remove spring from sensor
• Replace in reverse order
C.H. temperature sensor, overheat cut off thermostat and Aquafast Sensor
• Isolate electricity
• Remove outer case
• Identify the location of thermostat from fig.
28.
• Pull out thermostat or sensor from tube, with its spring
• Remove electrical connections from sensor or thermostat
• Remove spring from sensor or thermostat
Replace in reverse order
Fig. 27
A
F
C
D
D
E
A
B
C.H.
sensor
Fig. 28
Overheat
thermostat
Aquafast
sensor
Page 35
ARENA 30 C
35
D.H.W. flowmeter
• Isolate electricity and water supplies
• Open a hot water tap to release water pressure from the domestic side of the heat exchanger, close tap.
• Remove outer case
• Take off protective cover from main PCB and unplug flow meter lead from terminal
• Place a piece of cloth or some other absorbent material over rear of control panel to catch any drops of water that may be released when removing the flow meter
• Using a 24mm open ended spanner, undo flow meter unions “A” and “B” (fig. 30) taking care not to twist the copper tubing (access through base panel).
• Remove flow meter, check + clean filter + restrictor + fit to new flow meter.
• Reassemble in reverse order (fig. 30).
37 3938 38
Take care on correct position of components as reported in fig. 30
Key
37 Cold water inlet filter 38 Gasket 39 Cold water flow limiter
A
B
Fig. 29
Fig. 30
Page 36
ARENA 30 C
36
3.5 Troubleshooting
Diagnostics
The boiler features an advanced self-diagnostic system. In the case of an fault in operation, the display flashes and the code identifying the fault appears. The faults marked with the letter “A” cause the permanent shut­down of the boiler. To reset operation the boiler must be restarted manually, pressing the “R” (reset) button.
The faults marked by the letter “F” cause temporary shut-down and are reset automatically as soon as the value returns within the boiler’s normal operating range.
The following table lists a number of indications for resolving the faults signalled by the boiler. Interventions on the appliance must be effected only by Qualified Personnel, such as the personnel from the FERROLI Customer Technical Service Centre. For any operations on the appliance or which require the opening of the boiler, always request the assistance of the service centre.
Failed burner assembly ignition
• No gas or low gas pressure
• Ignition or detection electrode fault
• Defective gas valve
• Check that the gas pressure or the gas flow to the boiler is correct and that air has been eliminated from the piping
• Check the wiring to the electrodes and that these are positioned correctly and free of deposits
• Check and replace the gas valve
Safety thermostat activation
• Outlet sensor not active
• No system circulation
• Check the correct positioning and operation of the outlet sensor
• Check the pump
Flue safety device intervention
• Flue partially blocked or insufficient
• Check the efficiency of the flue, the flue gas exhaust pipes and the outlet terminal
No flame following the ignition phase
• Air/flue pipes blocked
• Air in gas supply
• Low gas pressure
• PCB
• Free the obstructions from the flue, flue gas exhaust and air inlet pipes and terminals
• Check and purge the gas line
• Check the pipe size and meter governor
• Check the main board
Insufficient water system pressure
• System empty • Fill the system
Fan fault • Fan not powered
• Defective fan
• Check the wiring to the fan
• Replace the fan
Fault Possible cause Solution
Page 37
ARENA 30 C
37
Domestic hot water sensor faulty
• Sensor damaged or wiring cut
• Check wiring or replace the sensor
Flue gas sensor faulty • Sensor damaged or
wiring cut
• Check wiring or replace the sensor
External probe faulty • Sensor damaged or
wiring short-circuited
• Check wiring or replace the sensor
No communication between main board and ignition devices
• Wiring cut or incorrect between main board and ignition devices
• Check the wiring and the connections between the boards
Fault Possible cause Solution
Microprocessor faulty • Microprocessor operation
faulty
• Disconnect and restore the electrical power supply. If the problem persists check and/or replace the main board
High flue gas temperature • Flue partially blocked
or insufficient
• Check the efficiency of the flue, the flue gas exhaust pipes and the outlet terminal
Excessive central heating outlet temperature
• Pump blocked
• Pump faulty
• Free the pump by removing the cap and rotating the shaft with a screwdriver
• Check or replace the condenser or the pump
Excessive central heating return temperature
• No system circulation
• Domestic hot water heat exchanger dirty or blocked
• Check system and pump
• Clean domestic hot water heat exchanger
Outlet sensor faulty • Sensor damaged or
wiring cut
• Check wiring or replace the sensor
Return sensor faulty • Sensor damaged or
wiring cut
• Check wiring or replace the sensor
Page 38
ARENA 30 C
38
Display and boiler off • Power failure • Check or await the return of the
electrical power supply
Radiators cold in winter • Room thermostat
adjusted too low or defective
• Adjust the knob to a higher temperature, replace if necessary
Radiators hot in summer • Room thermostat
adjusted too high or defective
• Adjust the knob to a lower temperature, replace if necessary
Large variations in domestic hot water temperature
• Water flow rate too low • Increase the water flow rate (minimum three litres per minute)
Fault Possible cause Solution
Low domestic hot water flow
• Insufficient mains water
pressure
• Heat exchanger with
passages partially blocked
• Install a pressure increase device
• Request the cleaning of the heat exchanger
No domestic hot water flow
• Heat exchanger blocked
• Defective flow-meter
• Request engineer for the cleaning operations
• Request engineer for the replacement of the flow-meter
No temperature increase with boiler on
• Boiler dirty
• Boiler insufficient
• Check and clean the boiler body
• Check that the boiler is the right capacity for the requirements of the heating system
Loss of condensation from the boiler
• Condensation discharge blocked
• Check and clean the drain trap
Page 39
ARENA 30 C
39
4. OPERATING INSTRUCTIONS
4.1 Operation and controls
The Arena 30C is a pre-mix condensing thermal generator for heating and the production of domestic hot water, using natural gas or LPG (configured at the moment of installation) and managed by an advanced microprocessor control system.
The operation of the appliance is mostly automatic. The heat rate for the heating function is regulated automatically by the control system according to the characteristics of the internal and external environment (with optional external probe installed), the characteristics of the building and its location. The heat rate for the domestic hot water function is regulated automatically and continuously, to ensure rapid delivery and comfort in all supply conditions.
The user simply has to set the required temperature from inside the living area (using the room thermostat or the optional, yet recommended, remote control) or set the heating system temperature and the required outlet temperature for the domestic hot water service. The regulation and control system will then provide for optimal operation all year round.
The display provides continuous indication on the operating status of the appliance, and can display additional information on the temperature of the sensors, the set-point, etc. or be used for the configuration of such via the operating menu, using the keypad.
Any anomalies in operation involving the boiler or the heating system are signalled on the display and, where possible, corrected automatically.
Display D1 Display D2
Ignition switch
0 1
L1 L2
fig. 31
4.2 Boiler control panel
MODE button - Use this button to scroll the parameters.
RESET button - Use this button to reset the operation of the boiler in the event of shut-
down.
MODIFY button - Use these buttons to modify the regulation values.
CONFIRM button - Use this button to enable the set regulation value.
MODE display - Indicates the operating mode of the boiler or the selected parameter.
DATA display - Indicates value of the parameters
Led L1 - Indicates:Economy Operation
Led L2 - Indicates:Comfort Operation
Function of the buttons
Display indications
Page 40
ARENA 30 C
40
4.3 Ignition
Check than any shut-off valves in the heating system and domestic hot water circuit outside of the boiler are open. Open the gas cock upstream from boiler and press the main switch. The boiler will perform an self­test cycle lasting approximately one minute, at the end of which it is ready for operation. The ignition and shut-down of the burner assembly are completely automatic operations, which depend on the requirements of the heating system or domestic hot water circuit.
4.4 Shut-down
In the event of extended periods of inactivity close the gas cock upstream from the boiler and disconnect the electrical power supply to the appliance. In this case, the boiler antifreeze protection function is also disabled; this function switches on the burner assembly when the heating system temperature falls below 5°C. For extended periods of inactivity during the winter months, in order to avoid damage due to freezing, all the water should be drained from the boiler, both the domestic hot water and the heating system; alternatively, drain only the domestic hot water and introduce the special antifreeze into the heating system.
4.5 Operating indications on the display
During operation, without pressing any of the buttons the display shows the operating status of the appliance:
Operating mode
Standby
Heating
Domestic hot water
Standby following domestic hot water op.
Standby following heating op.
Waiting for DHW production
Display “D1” Display “D2/D3”
Central heating outlet temperature
Central heating outlet temperature
Domestic hot water temperature
Domestic hot water temperature
Central heating outlet temperature
Domestic hot water temperature
Summer/Winter Selection (00=Summer • 11=Winter) Economy/Comfort Selection CH outlet temperature view and setting Aquafast temperature view/DHW output setting Domestic hot water temperature External temperature Flue gas temperature
­Domestic hot water flow rate Boiler power Compensation curve setting
-
DISPLAY D1 DISPLAY D2/D3
4.6 Accessing the operating menu
Pressing the “ - mode” button once accesses the operating menu. Pressing the “ - mode” button again displays the following parameters and information in sequence:
Page 41
ARENA 30 C
41
4.7 Setting the heating system temperature
Set, using the room thermostat or remote control, the desired temperature inside the rooms. When acting on the room thermostat, the boiler is turned on and the heating system water is brought to the central heating outlet set temperature or calculated temperature (with temperature scrolling active). On reaching the required temperature inside the rooms, the generator will switch off.
If no room thermostat or remote control is installed, the boiler will maintain the heating system temperature at the central heating outlet setpoint.
To set the central heating outlet temperature, access the operating menu, and using the button display parameter 1 – central heating outlet temperature. On pressing one of the buttons the display will start to flash, showing the outlet temperature setpoint. Use the buttons to set the required value. To activate the new value, press the button . To cancel the setting, do not press the button , and press
the button .
4.8 Setting the domestic hot water temperature
Set, using the control boiler panel, the required domestic hot water outlet temperature. On opening a hot water tap, the system regulates itself to supply water at the set temperature, according to the flow rate of delivery and the temperature of the cold water supplied to the boiler. If in terms of delivery or temperature difference between the inlet and outlet, the thermal capacity of the generator is exceeded (refer to the technical data), the outlet temperature will be proportionally lower than the setpoint.
To set the domestic hot water outlet temperature, access the operating menu, and using the button display parameter 2 – domestic hot water temperature. On pressing one of the buttons the display
will start to flash and the domestic hot water outlet temperature setpoint will be displayed. Use the buttons
to set the required value. To activate the new value, press the button . To cancel the setting, do
not press the button , and press the button .
4.9 Summer/Winter Selection
For Summer/Winter selection, enter functioning menu and visualize parameter “0.” through key . In correspondence of parameter “0.”, pressing one of keys Summer/Winter selection is visualized
(parameter “0.” flashes); through the same keys it is possible to select Summer functioning (set 00) or Winter functioning (set 11). To activate new setting, press key , to exit without saving the selection press key .
In “Summer” mode (00) heating is excluded. Antifreeze function remains enabled.
4.10 Aquafast device
The Arena 30C is fitted with a special Aquafast device for the rapid supply of domestic hot water to the boiler outlet. With Aquafast active, a small amount of water is maintained at temperature inside the boiler body, in order to immediately heat the domestic hot water upon request, eliminating the waiting time for the ignition and start-up of the boiler. The energy consumption of this device is quite limited, as its layout exploits the residual heat generated in the heating phase; Aquafast can however be deactivated by the user in order to operate in maximum economy.
When the Aquafast device for the ultra-fast production of domestic hot water is active (default setting), the “Comfort” LED on the control panel is on, while when inactive, the “Economy” LED on the control panel is on.
To deactivate Aquafast access the operating menu – parameter 0. Pressing one of the buttons , the display starts to flash, showing 1 if the device is active, 0 if inactive. Use the buttons to set the required value. To activate the new value press the button. To cancel the setting, do not press the button , and press the button .
Page 42
ARENA 30 C
42
4.11 Outside temperature compensation
When the (optional) external probe is installed, the boiler regulation system functions in “Outside temperature compensation” mode. In this mode, the temperature of the heating system is regulated according to the external climatic conditions, so as to guarantee a high degree of comfort and energy saving all year round. Specifically, when the external temperature falls, the central heating outlet temperature is increased, according to a pre-determined “compensation curve”.
In this mode, the temperature set in parameter 1 of the operating menu becomes the maximum central heatin g outlet temperature. This should be set to Maximum to allow the system to regulate over the entire working range.
The boiler must be set during installation by qualified personnel. Other minor modifications can be made by the user to improve the level of comfort: the compensation curve can in fact be modified by accessing the
operating menu with the button and scrolling the menu, again using the button, to parameter 9. The set compensation curve is displayed (refer to graph below). Pressing one of the buttons the display
starts to flash; use the buttons to set the required value. To activate the new curve, press the button
. To cancel the setting, do not press the button, and press the button .
If the ambient temperature is lower than the required value, it is suggested to set a higher curve, and vice­versa. Proceed with single unit increments or decreases, and check the results in the room.
Compensation curve
20
30
40
50
60
70
80
90
20 10 0 -10 -20
Temperatura esterna °C
Temperatura
di mandata impianto C°
1
2
3
4
5
6
7
8
9
10
4.12 Maintenance
It is strongly recommended to effect the annual maintenance of the heating system and at least biennial checks of the combustion device. Please refer to the “maintenance” section in this manual.
The casing, the control panel and the aesthetic parts of the boiler can be cleaned using a soft and damp cloth. Do not use abrasives or solvents.
4.13 Anomalies
In the event of operating anomalies or problems, the display flashes and shows the code identifying the anomaly.
The anomalies marked by the letter “F” cause temporary shut-down, and are reset automatically as soon as the value returns within the boiler’s normal operating range.
The anomalies marked by the letter “A” cause a shut-down of the boiler which can be reset by the user. To reset operation, press the (reset) button.
If the problem persists, or for any other anomalies, please refer to the “troubleshooting” chapter in this manual for more details.
Page 43
Page 44
Lichfield Road, Branston Industrial Estate, Burton Upon Trent, Staffordshire DE14 3HD
Tel. 08707 282 885 - Fax 08707 282 886
ALL SPECIFICATIONS SUBJECT TO CHANGE
Phone numbers:
Installer
Service Engineer
BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS.
Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check
this in not caused by lack of electricity supply, gas supply or low water pressure before calling
our Customer Service Helpline.
Should you require help with any difficulties
call our Technical Service Helpline on
08707 282 885
IMPORTANT
"All CORGI Registered Installers carry a CORGI ID card and have a registration number. Both should be recorded in your central heating log book. You can check to the CORGI registered by calling CORGI on 01256 372300".
Loading...