CATEGORY I NATURAL GAS AND LP GAS
HIGH EFFICIENCY
TWO STAGE VARIABLE SPEED
WARM AIR FURNACE
MODEL 77
For future reference write down the model, serial
number, and date of purchase. Use these numbers in
any correspondence or service calls concerning your
furnace.
Model
Serial Number
Date of Purchase
Keep these instructions for future reference.
Please read the operating instructions and safety
precautions carefully and thoroughly before installing
and operating your furnace. Keep this manual in a
safe place for future reference.
FV95A054 FV95A072 <
FV95A090<
FV95A108
USER’S INSTRUCTION GUIDE
LOCATED AFTER PAGE 43 OF THIS
INSTALLATION, OPERATION AND
MAINTENANCE MANUAL
This 95% efficient gas fired furnace series is CGA / AGA
esign certified as a Category I (condensing with positive
d
vent pressure) non-direct or direct vent central forced air furnace. It is an upflow, downflow, horizontal left and right furnace suitable for residential and light commercial heating
applications from 54,000 to 108,000 BTU/Hr. When installed
as a direct vent furnace, all combustion air is supplied directly to the furnace burners through a special air intake system.
(See Section “Ventilation and Combustion Air.”)
ll models may be fired by natural gas or field convertible to
A
LP gas (propane). The furnace is shipped completely assembled except for the drain trap assembly and the venting.
Please inspect for damage when the furnace is unpacked.
SAFETY
Throughout the manual, symbols and words are used to draw
attention to potentially hazardous conditions.
DANGER
THIS INDICATES AN IMMINENTLY HAZARDOUS
SITUATION WHICH, IF NOT AVOIDED, WILL RESULT IN
DEATH OR SERIOUS INJURY.
WARNING
THIS INDICATES A POTENTIALLY HAZARDOUS
SITUATION WHICH, IF NOT AVOIDED, COULD RESULT IN
DEATH OR SERIOUS INJURY.
CAUTION
THIS INDICATES A POTENTIALLY HAZARDOUS
SITUATION, WHICH, IF NOT AVOIDED, MAY RESULT IN
MINOR OR MODERATE INJURY.
. Always install furnace to operate within the furnace’s
6
intended temperature rise range with a duct system
which has an external static pressure within the
allowable range, as specified in the Furnace Sizing
section on page 4, the Ductwork section on page 7, and
he Airflow section on page 35 of these instructions.
t
7. When a furnace is installed so that the supply ducts carry
air circulated by the furnace to areas outside the space
ontaining the furnace, the return air shall also be
c
handled by duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
(Furnace for heating the home located in the attached
arage, for example).
g
8. A gas fired furnace for installation in a residential
garage must be installed so that the burners and ignitor
are no less than 18 inches above the floor. The furnace
must be located, or protected to avoid physical damage
by vehicles.
9.
THIS FURNACE IS NOT TO BE USED FOR TEMPORARY
HEATING FOR BUILDINGS UNDER CONSTRUCTION.
DANGER
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!
THIS FURNACE IS NOT APPROVED FOR INSTALLATION IN
A MOBILE HOME. DOING SO COULD CAUSE FIRE,
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF
LIFE.
WARNING
THE FURNACE CONTAINS FOIL COVERED FIBERGLASS
INSULATION. INHALATION OF FIBERGLASS PARTICLES IS
ASSOCIATED WITH RESPIRATORY DISEASE INCLUDING
CANCER.
Safety Rules:
1. Use this furnace only with type of gas approved for this
furnace. Refer to the furnace rating plate.
2. Install this furnace only in dry indoor locations
(protected from weather).
3. Provide adequate combustion and ventilation air to the
furnace space as specified in the Determining
Combustion Air section on page 13 of these instructions.
4. Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only, as
specified in the Furnace Venting section on page 14 of
these instructions.
5. Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically
for the detection of leaks to check all connections as
specified in the Gas Supply section on page 28 of these
instructions.
WARNING
THE FUEL SUPPLIER NORMALLY ODORIZES NATURAL
GAS AND PROPANE. IN SOME CASES, THE ODORANT
MAY NOT BE PERCEIVABLE. INSTALLATION OF UL AND
CUL RECOGNIZED FUEL GAS DETECTORS INSTALLED IN
ACCORDANCE WITH THEIR MANUFACTURER’S
INSTRUCTIONS IS RECOMMENDED AS AN ADDITIONAL
MARGIN OF SAFETY.
DANGER
FIRE OR EXPLOSION HAZARD
IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT
, A FIRE OR EXPLOSION MA
FOLLOWED EXACTL
RESULT, CAUSING PROPERTY DAMAGE, PERSONAL
INJURY OR LOSS OF LIFE.
Y
CAUTION
MAKE SURE TO REMOVE FOAM BLOWER HOUSING
SHIPPING SUPPORTS BEFORE OPERATING FURNACE.
SHIPPING SUPPORTS ARE LOCATED ON THE BOTTOM
RIGHT AND BOTTOM LEFT SIDES OF BLOWER HOUSING.
Y
1
DANGER
WHAT TO DO IF YOU SMELL GAS:
• DO NOT TRY TO LIGHT ANY APPLIANCE
• DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT
USE ANY PHONE IN YOUR BUILDING
IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A
•
EIGHBOR’S PHONE, OR A CELLULAR PHONE FROM A
N
LOCATION WELL AWAY FROM THE BUILDING.
FOLLOW THE GAS SUPPLIER’S INSTRUCTIONS.
IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL
•
THE FIRE DEPARTMENT
• DO NOT ENTER THE BUILDING UNTIL AUTHORIZED TO
DO SO BY THE GAS SUPPLIER OR THE FIRE
DEPARTMENT
IMPROPER INSTALLATION, OPERATION, ADJUSTMENT,
ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE
INJURY, PROPERTY DAMAGE OR LOSS OF LIFE. REFER TO
THIS MANUAL FOR PROPER INSTALLATION, OPERATION,
VICE, AND MAINTENANCE INSTRUCTIONS.
SER
A QUALIFIED INSTALLER, SERVICE AGENCY OR
THE GAS SUPPLIER MUST PERFORM
INSTALLATION AND SERVICE.
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE
FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
DANGER
HEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL
W
GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND
IGNITION SOURCE ARE LOCATED NO LESS THAN 18
INCHES ABOVE THE FLOOR TO PREVENT THE RISK OF
IGNITING FLAMMABLE VAPORS WHICH MAY BE
RESENT IN THE GARAGE.
P
THE FURNACE MUST BE LOCATED OR PROTECTED TO
AVOID PHYSICAL DAMAGE BY VEHICLES.
FAILURE TO HEED THESE WARNINGS CAN CAUSE A FIRE
OR EXPLOSION, RESULTING IN PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.
WARNING
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
QUALIFIED SERVICE PERSONNEL FOR PROPER
INSTALLATION, ADJUSTMENT AND OPERATION OF THIS
FURNACE. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT
IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR
MAINTENANCE, POSSIBLY RESULTING IN FIRE,
ELECTRICAL SHOCK, CARBON MONOXIDE POISONING,
EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH.
DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS, OR OTHER
COMBUSTIBLE MATERIALS IN THE VICINITY OF THIS OR
ANY OTHER APPLIANCE.
WARNING
THE EXHAUST GASES FROM THIS FURNACE CONTAIN
CHEMICALS, WHICH ON SOME OCCASIONS MAY
INCLUDE CARBON MONOXIDE (CO). CARBON
MONOXIDE IS AN ODORLESS, TASTELESS, CLEAR
COLORLESS GAS, WHICH IS HIGHL
CONCENTRA
DEFECTS AND OTHER REPRODUCTIVE HARM.
UL AND CUL RECOGNIZED CO DETECTORS ARE
RECOMMENDED FOR ALL BUILDINGS EQUIPPED WITH
FOSSIL FUEL BURNING APPLIANCES. ALL CO DETECTORS
SHOULD BE INST
MANUFACTURER’S INSTRUCTIONS AND APPLICABLE
LOCAL BUILDING CODES.
TIONS ARE SUSPECTED OF CAUSING BIR
ALLED IN ACCORDANCE WITH THEIR
Y TOXIC. EVEN LOW
TH
2
CODES:
This furnace must be installed:
In accordance with all local codes, bylaws and
•
regulations by those authorities having jurisdiction
• In the United States, this furnace must be installed in
ccordance with the current ANSI Z223.1 (NFPA 54)
a
National Fuel Gas Code
• In Canada, this furnace must be installed in
ccordance with the current CAN/CGA -B149
a
Installation Code for Fuel Burning Appliances
Electrical connections must be made
in accordance with:
• Any applicable local codes, bylaws and regulations
• Canada: current edition of CAN/CSA C22.1, Canadian
Electrical Code (Part 1)
• United States: current edition of ANSI/NFPA 70,
National Electrical Code
Codes and additional information may
be obtained from:
• American Gas Association
1515 Wilson Boulevard
Arlington, VA, 22209
703-841-8400
•
National Fire Protection Association
1 Batterymarch Park
Quincy, MA, 02269-9101
617-770-3000
•
Canadian Gas Association
Suite 1, 243 Consumers Road
North York, ON, M2J 5E3
416-498-1994
INSTALLATION REQUIREMENTS SPECIFIC
TO THE STATE OF MASSACHUSETTS FOR
DIRECT VENT APPLIANCES.
FOR ALL SIDE WALL HORIZONTALLY VENTED GAS FUELED
EQUIPMENT INSTALLED IN EVERY DWELLING, BUILDING OR
STRUCTURE USED IN WHOLE OR IN PAR
PURPOSES, INCLUDING THOSE OWNED OR OPERATED BY
THE COMMONWEALTH AND WHERE THE SIDE WALL
EXHAUST VENT TERMINATION IS LESS THAN SEVEN (7)
FEET ABOVE FINISHED GRADE IN THE AREA OF THE VENTING, INCLUDING BUT NOT LIMITED TO DECKS AND PORCHES, THE FOLLOWING REQUIREMENTS SHALL BE SA
INSTALLA
1.
At the time of installation of the side wall horizontal
vented gas fueled equipment, the installing plumber
or gas fitter shall observe that a hard wired carbon
monoxide detector with an alarm and battery back-up
is installed on the floor level where the gas equipment is to be installed. In addition, the installing
plumber or gas fitter shall observe that a battery
operated or hard wired carbon monoxide detector
TION OF CARBON MONOXIDE DETECTORS:
T FOR RESIDENTIAL
TISFIED:
with an alarm is installed on each additional level of
the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall
be the responsibility of the property owner to secure
the services of qualified licensed professionals for the
installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented
gas fueled equipment is installed in a crawl space or
an attic, the hard wired carbon monoxide detector
ith alarm and battery backup may be installed on
w
he next adjacent floor level.
t
b. In the event that the requirements of this subdivi-
sion can not be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however that during said thirty (30) day
period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS:
Each carbon monoxide detector as required in accor-
dance with the above revisions shall comply with NFPA
720 and be ANS/UL 2034 listed and IAS certified.
3. SIGNAGE:
A metal or plastic identification plate shall be perma-
nently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly
in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than
one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION:
The state or local gas inspector of the side wall hori-
zontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the
inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248
CMR 5.0(2)(a)1 through 4.
5. PRODUCT-APPROVED VENT/AIR-INTAKE:
A product-approved vent terminal must be used and, if
applicable, a product-approved air intake must be
used. Installation shall be in strict compliance with the
manufacturer’s instructions.
6. INST
ALLATION INSTRUCTIONS:
A copy of all installation instructions for all product
approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at
the completion of the installation.
3
FURNACE SIZING
The maximum hourly heat loss for each heated space shall
be calculated in accordance with the procedures described
n Manual J titled, "Load Calculation" published by the Air
i
Conditioning Contractors of America, or by any other
method which is suitable for local conditions, provided the
results obtained are in substantial agreement with, and not
less than those obtained using the procedure described in
heir manual.
t
In Canada, the maximum hourly heat loss for each heated
space shall be calculated in accordance with the procedures
escribed in the manuals of the Heating, Refrigeration and
d
Air Conditioning Institute of Canada (HRAI), or by any other
method which is suitable for local conditions, provided the
results obtained are in substantial agreement with, and not
less than those obtained using the procedure described in
their manuals.
If the installation is a retrofit application, do not rely on the
capacity of the existing heating equipment as a method to
size the new fur
listed in earlier versions of load calculation manuals were
much higher than those listed in more recent editions. It is
possible that energy saving measures have been completed
since the installation of the existing furnace. This might
include additional insulation in the attic or walls, the
application of sprayed foam insulation, the addition of
storm windows and doors, weather stripping, caulking, etc.
Many of the older furnaces were equipped with large belt
drive blower systems, operating at low RPMs. If replacing an
existing furnace, be sure that the existing ductwork can
handle the amount of airflow necessary for a reasonable
temperature rise. Most older gas furnaces operated with a
system temperature rise of 70 - 100°F. This series furnace has
been designed for operation with a system temperature rise
(
∆T) of 35 - 65°F. If the furnace selected has an identical
output capacity as the original furnace, a substantial
increase in system airflow will be required.
nace. Many of the heat transfer multiples
Existing ductwork should be assessed for its air handling
capabilities. For residential applications, the recommended
air velocity of a supply air trunk duct is 700 feet per minute
(fpm), and should not exceed 900 fpm. The recommended
air velocity of a supply air branch run is 600 fpm, and should
not exceed 900 fpm. These values are slightly lower for
lexible ducting. The recommended air velocity of a return
f
ir trunk duct is 600 fpm, and should not exceed 700 fpm.
a
The recommended and maximum air velocity of a return air
branch is 600 fpm.
The equal friction chart, as published by ASHRAE and HRAI,
is the basis for the various air duct calculators available
through heating supply companies.
IMPORTANT
The return air system is equally as important as the
supply air system. An undersized return air system will
prevent sufficient quantities of air from reaching the
supply air system, properly sized or otherwise, and will
consequently reduce the service life of the furnace and
its components.
AIR CONDITIONING
This furnace may be used as part of an air conditioning
system. The furnace wiring and control system are “air
conditioning ready”. There are the following factors to
consider:
• The air conditioning evaporator coil must be
downstream of the heat exchanger. The cooled air
passing over the warm ambient air inside the heat
exchanger tubes can cause condensation inside the
tubes, resulting in corrosion and premature failure.
• A parallel duct system can be installed to direct the air
from the furnace through the evaporator coil only. Use
dampers or other means to bypass the heat exchanger.
If [summer/winter] dampers are used, they should be
interlocked to prevent system operation unless the
dampers are in the full open or full closed position.
INSPECTION / ACCESS PANEL
If an air conditioning coil is not to be used in the supply air
plenum, it is recommended that the outlet duct be provided
with a removable access panel, which is accessible when
installed so the heat exchanger may be viewed for possible
openings using light assistance or a probe that can be
inserted for sampling the air stream. The access cover must
be fabricated in such a manner as to prevent leaks.
4
LOCATION of UNIT
General
1. The furnace is not weatherized. Select a dry indoor
location.
2. Select a location where the exhaust and combustion air
iping can be routed between the furnace and their
p
terminations with a minimum of lengths and fittings.
Be sure to check that the proposed termination location
will meet code requirements with respect to location
and minimum clearances. (See venting section for
inimum and maximum limits.)
m
. Select a location as near as possible to the existing or
3
proposed duct system.
4. The furnace location must permit access for servicing,
and be within the clearance to combustibles guidelines
as marked on the appliance rating plate.
5. The furnace should be installed on a firm base when
installed in the upflow position. This is typically a
concrete floor if installing the furnace in a basement.
6. If the furnace is being installed so that the return air
will enter through the bottom, the perimeter of the
furnace must be properly supported.
7. When installed in the horizontal position, the furnace
may be supported from the bottom, or suspended.
8. When installed in the down flow position on a
combustible floor, subbase kit #30476 is required
(contact manufacturer for availability).
9. The furnace location must have provisions for
condensate drainage. If a suitable drain is unavailable
near the furnace, a condensate pump must be used. The
condensate pump drain tubing must not terminate
outdoors; similar to some air conditioning condensate
installations. Be sure to select a condensate pump that
has been approved for furnace condensate
applications.
10. The furnace must be installed level, or tilted slightly
down in the front, to allow for the proper drainage of
condensate. The furnace may shut down during
operation if the condensate does not drain freely away
from the furnace.
11. If the furnace is installed in an area where freezing may
occur, a garage, an attic, a crawl space or any
unconditioned space, steps must be taken to protect
the condensate trap and drain line from freezing. One
possible measure could be to use a self-regulating 5 or
6 watt per foot heat tape covered with a jacket of
insulation. Heat tapes are available in plumbing supply
houses.
Other Considerations:
1. This furnace is not to be used for temporary heating of
buildings or structures under construction.
2. If this furnace is to be used with air conditioning and is
o be installed in an area over a finished ceiling or
t
living area, install a field fabricated auxiliary drain pan
under the furnace to protect that area from accidental
condensate spills. The auxiliary pan should be large
enough to collect accidentally spilled condensate from
he air conditioning evaporator coil assembly if
t
applicable. Follow local codes.
3. These furnaces are approved for installation in attics,
alcoves, utility rooms, closets and crawlspaces. If this
furnace is to be installed in a utility room, be sure that
it is located in such a way as to allow access for
servicing or the removal of any other appliance, (hot
water heater, for example).
4. If the furnace is to be installed in a residential garage,
the burners must be a minimum of 18 inches (460 mm)
above the floor
5. If the furnace is to be installed in a commercial (repair)
garage, the burners must be a minimum of 4.5 feet
(1375 mm) above the floor.
6. The furnace must be protected from physical damage
by metal barriers or other acceptable means.
7. If the furnace is to be located in an area where the
combustion air is laden with chemical compounds such
as bromine, chlorine or fluorine, as may be found in
swimming pool chemicals, laundry detergents, etc., use
outdoor air for combustion. These compounds when
exposed to flame, form acids, which attack the heat
exchanger and other components.
A partial list of these contaminants includes:
• Aerosols, particularly CFC based aerosols
• Air fresheners
• “Airplane” glue and similar cements
• Ammonia, as is commonly found in permanent wave
solutions used in women’
• Anti-static fabric softeners used in clothes dryers
• Carbon tetrachloride
• Chlorinated cleaners and waxes
• Chlorine and bromine based swimming pool
chemicals and treatments
• De-icing salts or chemicals, rock salt, etc.
• Dry cleaning solutions such as perchloroethylene
• Halogen based refrigerants including R-12 and R-22
• Hydrochloric acid, muriatic acid, or other acid based
masonry washing compounds
Table 2 provides the certified clearances to combustibles.
IMPORTANT
This furnace requires a minimum of 24-inches of front
clearance for service purposes. For this purpose, service
learance takes precedence over clearance to
c
combustibles.
TABLE 2: CLEARANCES TO COMBUSTIBLES
TOP
PLENUM
TOP/BOTTOM
PLENUM SIDES
UNIT FRONT
UNIT BACK
UNIT SIDES
UNIT BASE
UNIT FLUE PIPE
ENCLOSURE
* 24" REQUIRED FOR SERVICE
** SUPPLY AIR END / RETURN AIR END
*** CERTIFIED FOR CLOSET INSTALLATION ON COMBUSTIBLE FLOORING
**** CERTIFIED FOR INSTALLATION ON COMBUSTIBLE FLOORING ONLY WHEN INSTALLED
ON SPECIAL BASE PART #30476
UPFLOW
CLOSET
COUNTERFLOW
1"
1"1"
0.5"
0" *
0" 0"
0" ***
0"
0"
0.5"0.5"
0" *
0" ****
0"
CLOSET
See the appliance rating plate affixed to the
furnace for specific model number, serial
number and clearance to combustibles
information.
HORIZONTAL
2"
2.5"
0" *
1" **
0"
0"
CLOSET
ALL DIMENSIONS IN INCHES
IGURE 2: DIMENSIONS
F
TABLE 3: DIMENSIONS
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR
AGAINST THE FURNACE JACKET.
PLACEMENT OF COMBUSTIBLE MATERIALS ON, AGAINST
OR AROUND THE FURNACE JACKET CAN CAUSE AN
EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.
THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR
AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING
GASOLINE AND OTHER FLAMMABLE VAPORS AND
LIQUIDS.
THE HOMEOWNER SHOULD BE CAUTIONED THA
FURNACE AREA MUST NOT BE USED AS A BROOM
CLOSET OR FOR ANY OTHER STORAGE PURPOSE.
UPFLOW FURNACES ARE DESIGN CER
INSTALLATION ON COMBUSTIBLE FLOORS. THIS SHALL
BE INTERPRETED AS A WOOD FLOOR ONLY.
THE FURNACE MUST NOT BE INSTALLED DIRECTLY ON
CARPETING, VINYL TILE, OR OTHER COMBUSTIBLE
MATERIAL EXCEPT WOOD. INSTALLATION ON
COMBUSTIBLE MATERIAL CAN RESULT IN FIRE, CAUSING
PROPER
DANGER
DANGER
TY DAMAGE, PERSONAL INJUR
T THE
TIFIED FOR
Y OR DEA
TH.
6
DUCTWORK
Proper airflow is required for the correct operation of this
furnace. Insufficient airflow may cause erratic operation,
ould cause the furnace to cycle on the high temperature
c
limit, and may damage the heat exchanger. Excessive
airflow may result in an excessively noisy duct system and
may result in undesirable consequences such as creating
uncomfortable drafts and causing drapes or curtains to
low around.
b
If air conditioning is to be used with the furnace, the duct
system must be capable of delivering the correct amount of
irflow for each system.
a
The ductwork should be sized and constructed in
accordance with accepted industry standards. Duct sizing
and construction information may be obtained from:
• A.C.C.A. (Air Conditioning Contractors of America)
• A.S.H.R.A.E. (American Society of Heating,
Refrigeration and Air Conditioning Engineers)
• H.R.A.I. (Heating, Refrigerating and Air Conditioning
Institute (Canada)
• S.M.A.C.N.A. (Sheet Metal and Air Conditioning
Contractors’ National Association (United States)
All of the above professional organizations have duct sizing
manuals available.
The total static pressure drop of the air distribution system
should not exceed 0.5 inches water column.
Guide:
Filter free area (in2) = 144 x (CFM / desired velocity (fpm))
IMPORTANT
Some high efficiency filters have a greater than normal resistance to airflow. This can adversely affect furnace operation. Pressure check the static differential
from before the filter to the supply.
NOTE
When calculating an air filter size use the free air not
the advertised size.
NOTE
UNITS FOR 4 AND 5 TON CF AIR CONDITIONING MUST
HAVE DUAL RETURN AIR INLETS FOR OPTIMAL
AIRFLOW AND AIR FIL
STATED BY THE FILTER MANUFACTURER, FOR
EFFECTIVE AIR FILTRATION, ASSUME A MAXIMUM
VELOCITY OF 300 FPM FOR DISPOSABLE TYPE FIL
OR 600 FPM FOR PERMANENT TYPE FILTERS.
TION. IF NOT SPECIFICALLY
TRA
TERS,
WARNING
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT
RETURN OR SUPPLY AIR DUCTWORK TO OR FROM ANY
THER HEAT-PRODUCING DEVICE SUCH AS A FIREPLACE
O
INSERT, STOVE, ETC. DOING SO MAY RESULT IN FIRE,
CARBON MONOXIDE POISONING, EXPLOSION,
PERSONAL INJURY, LOSS OF LIFE, OR PROPERTY
AMAGE.
D
Ductwork Steps:
1. Position the furnace to minimize ductwork length and
fittings.
2. Cut open a return air inlet. The choices are:
a) either side
b) furnace bottom
c) any combination, i.e. two sides or a side and the
bottom.
In all cases, cut the inlet air opening the full width of
NOTE
When two return air inlets are used, both must be
equipped with filters.
CAUTION
DO NOT USE THE REAR PANEL AS A RETURN AIR INLET.
THERE IS INSUFFICIENT AREA TO PERMIT ADEQUATE
AIRFLOW.
3. Install the filter rack(s) (field supplied).
4. Connect the return air duct or fitting to the furnace. The
connection should be as air tight as possible to prevent
entraining combustion gases from an adjacent fuel
burning appliance, or entraining combustion air for this
furnace .
5. Ensure that there is adequate space and accessibility for
the air filter
6. If an air conditioning evaporator coil is required,
position it on the top of the furnace. Ensure that no air
can bypass the evaporator coil.
7. Connect the supply air plenum to the supply air outlet.
Flexible duct connectors are an effective device to
prevent the telegraphing of mechanical noise from the
furnace to other parts of the home via the ductwork. If
using flexible connectors, ensure that the adjoining
duct is independently supported.
Adequate provisions for combustion and ventilation air
must be in accordance with ANSI Z223.1 (NFP
5.3 "Air for Combustion and Ventilation" in the United
States, and CAN/CGA B149 in Canada. Check with local
authorities for any additional building codes, bylaws or
regulations.
.
A 54), section
7
INSTALLATION POSITIONS
he furnace can be installed in any of four positions:
T
• Upflow
• Downflow
• Horizontal left
• Horizontal right
aintain clearances to combustibles as outlined in Table 2.
M
Support the furnace cabinet to prevent twisting or
sagging.
General Considerations
When choosing an installation position the installer must
consider the following connections:
• Combustion air intake
• Exhaust vent
• Gas pipe
• Electrical wiring
• Condensate drain trap
Also consider the air conditioning connections, a/c drain,
access to filter(s) and access to furnace and a/c for repair.
The blower compartment should be completely isolated
from the burner compartment. In tight rooms with other
combustion devices, the blower compartment must be
completely isolated from the room. The combustion
compartment must also be completely isolated from the
room (unless non-direct vent). Sometimes the knockout
tool will punch too deep and open holes. Use caulking on
the inside of the cabinet to seal any holes. Insure that the
combustion door gasket is in good condition.
IMPORTANT
Always secure or support the exhaust vent and
combustion air inlet piping to the floor joists or rafters
to avoid sagging and possible fatigue of venting
materials. This ensures proper drainage and
preventing spilling of the products of combustion into
the building.
IMPORTANT
If the pipe and fittings are to be other than PVC, use
the proper cleaner, primer and cement for the
dissimilar materials.
IMPORTANT
Drains and traps of furnaces installed in spaces
subjected to freezing temperature must also be
protected against freezing.
IMPORTANT
lean and de-burr all pipe cuts. The shavings must not
C
be allowed to block the exhaust, combustion air inlet
r condensate drain lines.
o
Combustion Air Inlet Connection
The combustion air inlet fitting is a 2” PVC Socket to Pipe
Thread adapter. Chose the intake location and open the
appropriate knock out. Install the adapter to the exterior
anel using the gasket on the outside of the panel and the
p
locknut on the inside of the panel.
IMPORTANT
If the pipe is increased in size with a reducer it must
be on a vertical section of the pipe to facilitate draining the vent. Reducing the size of pipe to exit the
house (as shown on page 19, Figures 4 and 6), the
reducer can be on the horizontal.
WARNING
THERE MUST NOT BE ANY OPENINGS BETWEEN THE
BLOWER DIVISION PANEL AND THE COMBUSTION
COMPARTMENT. THE BLOWER COMPARTMENT IS UNDER
GREATER SUCTION THEN THE COMBUSTION
COMPARTMENT AND CAN PULL COMBUSTION AIR FROM
THE BURNERS AND CAUSE INCOMPLETE COMBUSTION
AND ERRATIC FURNACE OPERATION.
The exhaust vent must be clamped to the exterior panel(s)
with the clamp provided. Place the gasket between the
clamp and the side panel. Tighten clamp and fasten in
place using the three screws provided.
The clamp should secure the vent pipe to prevent internal
damage if the vent pipe is tampered with.
THE VENT MUST BE CLAMPED TO THE FURNACE PANEL
USING THE GASKET AND CLAMP PROVIDED.
THE INTAKE MUST USE THE THREADED PVC
CONNECTOR WITH THE GASKET AND LOCK NUT.
ent Connection
W
ARNING
8
Instructions for Re-orienting Air Inducer
FIGURE A : RIGHT INDUCER POSITION
FIGURE B : LEFT INDUCER POSITION
SUGGESTED METHOD FOR
SUSPENDING HORIZONTAL FURNACE
ALLOW ENOUGH ANGLE
IRON OVERHANG TO
PERMIT OPENING THE
BLOWER DOOR
3/8 INCH THREADED ROD
2 INCH ANGLE IRON
JAM NUTS
LOCK WASHER
FLAT WASHER
SUPPLY AIR PLENUM
RETURN AIR PLENUM
SUSPENDED INSTALLATION
This furnace comes assembled ready for left side or vertical
venting. Rotate the inducer 180 degrees to exit the right
hand side.
1. Disconnect inducer wire connections.
2. Remove pressure switch hoses.
3. Remove pressure switches.
4. Remove 4 inducer screws
5. Remove inducer.
6. Reverse the bands on the rubber drain coupling so the
screws are accessible if necessary. (Do not reverse the
drain coupling.) Confirm that directional arrows on
drain coupling point away from inducer.
7. Remove the appropriate knock out.
8. Reinstall the inducer in the correct orientation with 4
screws removed in step 1.
9. Reinstall the pressure switches so that the switches and
hose is above the heat exchanger drain.
10. Complete the external venting as installation requires.
11. Rotate the drain coupling so the drain holes are angled
downward and tighten coupling bands.
12. Tighten the vent clamp and secure in place using the
screws provided.
INSTALLATION POSITIONS
Non-Suspended Installation
Maintain clearances to combustibles as outlined in Table 2
on page 6. The furnace must be supported in such a way
as to not allow twisting or sagging of the cabinet.
Horizontal Suspended Installation
The furnace may be suspended in either the horizontal right
or left position by field fabricated a cradle of angle iron and
threaded rod. Secure the furnace with 2 inch minimum
slotted angle or equivalent, as shown in figure below. The
furnace must be supported in such a way as not to allow
twisting or sagging of the cabinet. Position the supports so
as not to interfere with accessing the burner and blower
compartments.
9
C
C
A
B
A
B
A
B
Upflow Installation
The combustion air and exhaust vent may exit through
the top, left or right side of the cabinet when viewed in
the upflow position. The inducer is installed so that the
exhaust vent may exit the top and left sides without
requiring rotation.
f exhaust vent exits the top panel, use the two street
I
elbows to route the vent. One elbow secured to the
inducer drain connector, will angle toward the front of
cabinet with the second nested inside directed towards
the top panel. (The 108,000 BTUH will require an
extension between the inducer and the first elbow that
is not provided.)
If exhaust vent exits the left-side panel the pipe can be
routed straight outside the cabinet.
exists the right-side panel the inducer requires
rotation.
The exhaust vent pipe exiting the cabinet in any
installation should be long enough to install the vent
clamp on the outside of the cabinet.
If exhaust vent
A
COMBUSTION AIR
B
EXHAUST VENT
C
CONDENSATE DRAIN
10
Downflow Installation
When the furnace is installed in the downflow position
the combustion air and exhaust vent may exit through
the left or right side of the cabinet (when viewed in the
upflow position.). The inducer is installed so that the left
side exits require no rotation.
If exhaust vent exits the left-side panel the pipe can be
routed straight outside the cabinet.
If exhaust vent exists the right-side panel the
inducer requires rotation.
The pipe exiting the cabinet in any installation should be
long enough to install the vent clamp on the outside of
the cabinet.
WARNING
WHEN INSTALLED IN THE DOWNFLOW POSITION ON A
COMBUSTIBLE FLOOR, SUBBASE KIT #30476 IS
REQUIRED. FAILURE TO INSTALL SUBBASE KIT COULD
RESULT IN FIRE, DEATH OR SERIOUS INJURY.
The opening in the floor must provide adequate clearances
to the combustible material.
A half-inch of clearance will be required between the
plenum and the combustible material. If installed on a
non-combustible material, zero clearance is required.
In the downflow installation, this furnace can only vent
through the left or right side of the furnace.
The condensate drain trap can be mounted on the right or
left side.
B
B
A
D
C
C
A
COMBUSTION AIR
B
EXHAUST VENT
C
CONDENSATE DRAIN
D
SUBBASE KIT - REQUIRED WHEN
A
D
INSTALLED IN THE DOWNFLOW POSITION
ON A COMBUSTIBLE FLOOR
11
C
A
B
A
A
B
B
B
A
C
C
Horizontal Left Installation
In the horizontal left installation the combustion air and
exhaust vent may exit through the top or left side of the
cabinet (when viewed in the upflow position). It is not
permissible to vent downwards. The inducer is installed
so that the top and left side exits require no rotation.
f exhaust vent exits the top panel, use the two street
I
elbows to route the vent. One elbow secured to the
inducer drain connector, will angle toward the front of
cabinet with the second nested inside directed towards
the top panel. (The 108,000 BTUH will require an
extension between the inducer and the first elbow that
is not provided.)
If exhaust vent exits the left-side panel the pipe can be
routed straight outside the cabinet.
The pipe exiting the cabinet in any installation should be
long enough to install the vent clamp on the outside of
the cabinet.
Horizontal Right Installation
In the horizontal right installation the combustion air
and exhaust vent may exit through the top or right side
of the cabinet (when viewed in the upflow position). In
the horizontal right installation, it is not permissible to
vent downwards.
he right side exit is used.
t
If exiting the top panel, use the two street elbows to
route the vent. One elbow secured to the inducer drain
connector, will angle toward the front of cabinet with
the second nested inside directed towards the top panel.
(The 108,000 BTUH will require an extension between
the inducer and the first elbow that is not provided.)
If exiting the right-side the pipe can be routed straight
outside the cabinet after the inducer has been rotated.
The pipe exiting the cabinet in any installation should be
long enough to install the vent clamp on the outside of
the cabinet.
The inducer will require rotation if
NOTE
It is not permissible to use a rear of the
furnace as a return.
IMPORTANT
The furnace must be installed level or sloping towards
the front to facilitate proper drainage.
NOTE
It is not permissible to use a rear of the
furnace as a return.
IMPORTANT
The furnace must be installed level or sloping towards
the front to facilitate proper drainage.
A
COMBUSTION AIR
B
EXHAUST VENT
C
CONDENSA
12
TE DRAIN
CASE 1:
FURNACE LOCATED IN AN UNCONFINED SPACE
nconfined space does not necessarily mean that combus-
U
tion and ventilation will not have to be introduced from
the outdoors, particularly in airtight homes. Refer to the
appropriate installation code requirements regarding the
minimum combustion air required for all fuel burning
appliances located within the unconfined area.
f the amount of combustion and ventilation air is insuffi-
I
ient to properly operate the furnace and other fuel burn-
c
ing appliances within the unconfined area, it will be necessary to supply it from the outdoors based on the criteria
used when calculating the air supply for a confined space.
NOTE
If planning to use the inside air of an unconfined
space, remember to test for proper furnace operation
(as well as other fuel burning appliances located
within the unconfined space) with respect to adequate
combustion and ventilation air with fireplace dampers
open, clothes dryer running, bathroom exhaust fans
on, kitchen range hood on, etc.
CASE 2:
FURNACE LOCATED IN A CONFINED SPACE
A confined space, (any space smaller than the minimums
discussed in CASE 1), must have two air openings one within 12 inches of the ceiling and the other within 12 inches of
the floor. The air openings must be sized based on whether
the combustion and ventilation air is being taken from
indoors or outdoors, the method outdoor air (if used) is
introduced, and taking into account any other fuel burning
appliances in the confined space.
If sufficient indoor combustion and ventilation air is available for the furnace and all other fuel burning appliances,
even when clothes dryers, bathroom fans, range hoods, etc.
are running, size each opening according to the appropriate installation codes.
NOTE
If using grilles to cover the two openings, factor in the
free area of the grille. Typically, a grille will have a
free area approximately 50% of its nominal size.
Consequently, if the required opening is 10 inches x 10
inches , it will have to be doubled if using a sidewall
grille with 50% free area.
IMPORTANT
CASE 3:
FURNACE LOCATED IN A CONFINED SPACE, OUT-
DOOR
AIR FROM ATTIC OR CRAWL SPACE
In this circumstance, refer to the appropriate installation code for the free area of the combustion and
ventilation air openings. If other fuel burning appli-
nces are present, their combustion air and ventilation
a
ir requirements must be added to those of the fur-
a
ace. If the attic has an exhaust fan (power vent), it
n
may create a negative pressure sufficiently large
enough to prevent the attic from being an effective
source of combustion and ventilation air.
Powered attic fans do not customarily run during the
heating season; however, some are controlled by a
humidistat as well as a thermostat, which may allow
some operation during the heating season.
The choices are (a) use the direct vent option; (b) obtain
outdoor air from elsewhere; or (c) interlock the attic
exhaust fan with the furnace such that the two cannot
operate simultaneously.
CASE 4:
FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR
AIR DUCTED HORIZONTALLY
Similar to CASE 3, outdoor air for combustion and ventilation may be drawn through horizontal ducting.
Consult the appropriate installation code for the free area
for openings. If other fuel burning appliances are present,
their combustion air and ventilation air requirements must
be added to those of the furnace.
IMPORTANT
The outdoor grilles must be installed in a location
where they will not be obstructed in any manner.
If grilles are used on the outside wall, they must be
sized properly. Most sidewall grilles have only 50%
free area, so the grill size opening must be twice the
size of the free air opening requirement.
WARNING
DO NOT ALLOW GAS PIPING TO BE ROUTED THROUGH
JOIST SP
POSES. DO NOT USE JOIST SPACES FOR RETURN AIR
PURPOSES IF THE JOIST SPACE ALREADY CONTAINS
PLUMBING STACKS, CHIMNEY COMPONENTS, ETC.
UNLESS THE PORTION USED FOR RETURN AIR PURPOSES CAN BE COMPLETEL
WITH OTHER USAGES.
ACES THA
T ARE USED FOR RETURN AIR PUR
Y ISOLATED FROM PORTIONS
-
If an exhaust fan, fireplace, clothes dryer or any similar device is present in the indoor area from which the
combustion and ventilation air will be drawn, negative
pressure could be a problem if natural infiltration
from the outdoors does not match the rate at which
air is exhausted.
13
Loading...
+ 35 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.