Galvanized steel exterior cabinet with
1,000-hour salt spray, powder-coated finish
Powder-coated fan guard
Full louvered panel to protect coil
Formed base with 2
Limited 5-y
ear warranty on par
1
⁄2" ground c
learance
ts
Low pressure port
Integrated solid state control with adjustable
emp demand defrost
ime-t
t
Easy To Install:
F
a
c
Rated in Accordance with ARI Standard
210/240. Certification Applies Only When Used
with Proper Components as Listed with ARI.
Additional rating information can be found
at www.aridirectory.org
Model
Number
CH18ABD1VF11⁄2R-2218,00013.52032 1⁄2 X 21 1⁄2 X 21 1⁄224 x 24 132 / 127
CH24ACD1VF2R-2224,00016.02532 1⁄2 X 29 1⁄2 X 29 1⁄232 x 32 195 / 186
CH30ACD1VF 21⁄2R-2230,00018.83032 1⁄2 X 29 1⁄2 X 29 1⁄232 x 32 195 / 186
CH36ACD1VF 3R-2236,00020.53532 1⁄2 X 29 1⁄2 X 29 1⁄232 x 32 197 / 188
CH42ACD1VF31⁄2R-2242,00024.84032 1⁄2 X 29 1⁄2 X 29 1⁄232 x 32208 / 201
CH48ACD1VF4R-2248,00027.34532 1⁄2 X 29 1⁄2 X 29 1⁄232 x 32212 / 203
CH60ACZ1VF5R-410A60,00038.46039 X 29 1⁄2 X 29 1⁄232 x 32258 / 249
FAN MOTOR FLA (Full Load Amps)1.41.81.81.81.81.81.9
REFRIGERANT CONNECTIONS
LIQUID LINE CONNECTION SIZE (In. OD)3/83/83/83/83/83/83/8
SUCTION LINE CONNECTION SIZE
RECOMMENDED LINE SET LIQUID TUBE DIAMETER (In. OD)3/83/83/83/83/83/83/8
RECOMMENDED LINE SET SUCTION DIAMETER (In. OD)3/43/47/87/87/81 1/81 1/8
FACTORY CHARGE - OZ.103164154164207233233*
(In. OD)
2
18243036424860
13.516.018.820.524.827.338.5
3
20253035404550
3/43/47/87/87/87/87/8
NOTE: Control circuit is 24V on all units and requires external power source. Copper wire must be used from
service disconnect to unit. ALL motors/compressors contain internal overload protection.
1. Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will
require larger wire sizes.
2. Time delay fuses may be used in place of HACR circuit breaker.
COP – Coefficient of Performance
TDR – Time – Delay Relay
HSPF – Heating Seasonal Performance Factor
EER – Energy Efficiency Ratio
NOTES:
1. Tested combination per ARI 210/240 standard. Fedders air handlers contain the TDR as standard equipment.
2. Supplemental electric heat is not included.
3. Ratings are based on:
Cooling Standard: 80ºF db 67ºF wb indoor entering air temperature and 95ºF db air entering outdoor unit.
High – Temp Heating Standard: 70ºF db indoor entering air temperature and 47ºF db 43ºF wb air entering outdoor unit.
Low – Temp Heating Standard: 70ºF db indoor entering air temperature and 17ºF db 15ºF wb air entering outdoor unit.
3
Specifications subject to change without notice.
Split System Heat Pump
LINE SET LENGTH AND SIZE
BTUH
15 ft.25 ft.50 ft.75 ft.15 ft.25 ft.50 ft.75 ft.
183/43/43/43/43/83/83/83/8
243/43/43/43/43/83/83/83/8
303/47/87/87/83/83/83/83/8
363/47/87/87/83/83/83/83/8
427/87/87/87/83/83/83/81/2
481 1/81 1/81 1/81 1/83/83/83/81/2
601 1/81 1/81 1/81 1/83/83/83/81/2
ecommended liquid & suction tube line size is for standard installations. The unit charge is correct for the outdoor unit, matched indoor coil and
R
5 feet of refrigerant tubing. For tubing length other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied
1
by the per foot value. These recommendations do not apply to Long Line Length Installations that exceed 75 feet or where there is more than 40 feet
ertical separation between indoor and outdoor units. (Lengths in excess of 75 feet or more than 40 feet vertical separation are not recommended.)
v
ote: See unit installation instructions for proper installation.
N
SUCTION LINE SIZES LIQUID LINE SIZES
OUTDOOR
UNIT
MODEL
CH18ABD1VFAFPB24A118,00013650
CH24ACD1VFAFPB24B124,00013840
CH30ACD1VFAFPB36A128,000131,000
CH36ACD1VFAFPB36A134,000131,200
CH42ACD1VFAFPC48A140,000131,350
CH48ACD1VFAFPC48B146,000131,550
CH60ACZ1VFAZFPC60B156,000131,750
*TDR required to obtain SEER rating.
AIR
HANDLER
RATINGS AT STANDARD CONDITIONSCOOLING DATA AT EXTENDED OUTDOOR AMBIENTS F.M.B.T.U.H.