Fedders CH24ACD1, CH30ACD1, CH36ACD1, CH42ACD1, CH48ACD1 Installation, Operation And Maintenance Manual

Page 1
Installation, Operation and Maintenance
1.5 Through 5 Ton Heat Pump
TABLE OF CONTENTS
INTRODUCTION ..............................................................................1
NOTES TO INSTALLER ....................................................................1
CODES ............................................................................................1
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS ................1
INSPECTION AND UNPACKING......................................................1
Clearances ..........................................................................2
Support ..............................................................................2
Exposure ............................................................................2
Proximity to Evaporator....................................................2
ELECTRICAL CONNECTIONS ..........................................................2
SERVICE VALVE CONNECTIONS
Braze Joints ..............................................................................3
Evacuation ................................................................................3
Opening the Service Valve (Step Valve) ................................3
Opening the Service Valve (Straight Valve) ............................3
CONNECT REFRIGERANT PIPING ..................................................4
Precautions................................................................................4
Liquid Line Sizes........................................................................4
Suction Line Sizes......................................................................4
SUBCOOLING CHARGING ............................................................5
......................................................5
FINAL CHECKS FOR INST
COOLING OPERATION ..................................................................5
HEATING OPERATION ..................................................................5
DEFROST OPERATION ....................................................................6
MAINTENANCE INSTRUCTIONS ....................................................6
CONDENSING UNIT NOMENCLATURE ..........................................6
LIMITED W
ARRANTY
ALLER
....................................................................
7
NOTE: THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS EQUIPMENT. READ THE ENTIRE INSTRUCTION MANUAL THOROUGHLY BEFORE ATTEMPTING INST
TION OR OPERA
ALLA
TION.
Page 2
INTRODUCTION
You have made a major investment in a fine piece of equipment. Keep your investment sound by reading these
nstructions before installing this unit. This will ensure that
i
he full potential of this equipment is achieved. It will also
t be helpful in avoiding any needless service costs or operational problems. Included in these instructions are safety rules, installation, operation, and maintenance
nstructions.
i Only the highest quality components were used in the
construction of your unit. With proper maintenance, your system should provide years of economical, trouble-free service.
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
What You Need To Know About Safety Instructions
Warning and Important Safety Instructions appearing in this manual are not meant to cover all possible conditions and situations that may occur. Common sense, caution and care must be exercised when operating or cleaning tools and equipment.
Always contact your dealer, distributor, service agent or manufacturer about problems or conditions you do not understand.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
Installation and service personnel are required by some locales
o be licensed. Persons not qualified SHALL NOT install this
t equipment nor interpret these instructions.
This installation and maintenance manual is provided to ensure the proper installation and the most satisfactory performance of your equipment. The instructions contained herein SHALL NOT be deemed to extend, modify, alter or expand any of the representations contained in the limited warranty.
WARNING
A QUALIFIED INSTALLER MUST PERFORM INSTALLATION AND SERVICE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE, MAINTENANCE OR USE CAN CAUSE EXPLOSION, FIRE, ELECTRICAL SHOCK OR OTHER CONDITIONS WHICH MAY CAUSE DEATH, PERSONAL INJURY OR PROPERTY DAMAGE AND WILL VOID THE WARRANTY. REFER TO THIS MANUAL FOR PROPER INSTRUCTIONS.
DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS OR OTHER COMBUSTIBLE MATERIALS IN THE VICINITY OF THIS OR ANY OTHER EQUIPMENT.
BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT, POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK, INJURY, DAMAGE TO EQUIPMENT OR DEATH.
CONSULT A QUALIFIED INSTALLER FOR INFORMATION OR ASSISTANCE.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTES TO INSTALLER
The words “SHALL” and “MUST” indicate a requirement which is essential to satisfactory and safe product performance. The words “SHOULD” and “MAY” indicate a recommendation or advice which is not essential and not required but which may be useful or helpful.
CODES
The installer SHALL comply with all local, state, and federal codes and/or regulations pertaining to this type of equipment and its installation. Such codes and/or regulations should take precedence over any recommendations contained herein in lieu of local codes. Installations SHALL be made in accordance with
.
the National Electrical Code, local codes and recommendations made by the National Board of Fire Underwriters. Consult local building codes and National Electrical Code (NEC) for special requirements.
INSPECTION AND UNPACKING
A thorough inspection of the shipping container should be made immediately upon receiving your unit. Look for any punctures or openings and if it appears damage has occurred note it on the freight bill before signing. Contact the delivering carrier immediately to inspect damage, and no installation work should begin until this inspection is completed.
Locate rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specification.
111
Rating plate located inside control box cover
1
Page 3
INSTALLATION Condensing Unit Location
The condensing unit should be located outdoors as close as possible to the evaporator. Consider the following factors:
Clearances
The air inlet should be located at least 12" from a wall or other
bstruction for unrestricted air flow.
o The air outlet should be located so as to direct discharged air
away from the building. Three feet of clearance around the unit and a minimum of six feet clearance above the unit is required to avoid recirculation of condenser discharge air on vertical discharge models. Avoid locating unit under low overhanging roofs.
Support
Mount the unit on a sturdy base approximately four to six inches above the ground. In areas known for snow accumulation, the unit should be elevated at least 18" above the ground. A concrete slab is recommended. Concrete slab should not contact the building foundation to prevent possible sound or vibration transmission.
Rooftop installation is acceptable in areas of low snow accumulations, provided the roof will support the unit and provisions are made for water drainage and the noise or vibration through the structure.
Exposure
If practical, unit should be located on the south side of the structure away from northerly winds to minimize the effects of blowing snowdrifts and freezing rain. A wind screen or wind block can also be used.
Placement of the unit should be in a well-drained area, or the unit must be supported high enough so run-off will not enter the unit.
Avoid installations under roof overhangs without guttering. Water draining from the roof onto the unit could produce excessive noise and may cause ice to build up on the coil or fan during cold weather.
Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
Do not locate where heat, lint or exhaust fumes will be discharged on the unit (as from dryer or furnace vent).
112
Proximity to Evaporator
Locating the condenser as close as possible to the evaporator will increase the system capacities by reducing the line set refrigerant pressure drop, and will make the system less
usceptible to liquid migrations due to less refrigerant charge.
s
Electrical Connections
WARNING
BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT, POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK, INJURY, DEATH OR DAMAGE TO EQUIPMENT.
WARNING
ELECTRICAL EQUIPMENT SHOULD BE INSTALLED BY A QUALIFIED, LICENSED ELECTRICIAN. IMPROPER ELECTRICAL HOOK-UP MAY DAMAGE EQUIPMENT, CAN CREATE A HAZARD, CAUSE PERSONAL INJURY OR DEATH, AND WILL VOID THE WARRANTY.
1. The installer shall check available power to make certain it matches the unit rating plate (located inside control box cover) and that constant voltage can be maintained to the unit. Unsatisfactory performance would otherwise result. The local power company should be contacted regarding any problems or questions concerning power supply.
113
114
Control box
cover
Opening for line voltage conduit or cable
Opening for low-voltage wiring
Wiring diagram and rating plate are located inside control box cover
Rain Gutters
Six feet
clearance
above the
unit
Three feet
clearance
Concrete slab
Three feet
clearance
2. Install a line service disconnect switch within sight of the condensing unit. The line voltage service wiring for the condensing unit should include a fused disconnect switch.
3. Use correct wire size and fuse size. To ensure that adequate voltage will be available at the condensing unit, the line voltage service wiring must be of adequate size. Minimum recommended wire ampacities and maximum fuse sizes are listed on the unit name plate.
4. Two holes are provided in the control box.
One is for the connection of the line voltage conduit or
a.
cable. The hole is sized for 3/4" conduit.
b. One is for low-voltage wiring. (Refer to the wiring
diagram attached to electrical box cover for connection.)
5. Be sure to ground the condensing unit by securing the
ground wire to the grounding lug inside the control box. Be sure to follow National Electrical Code and all local
6.
codes.
2
Page 4
Electrical Connections (cont.)
Connect control wiring
1. Route 24 volt control wires through control wiring grommet and connect leads to control wiring.
. Use No. 18 AWG color coded, insulated wire. If thermostat is
2
located more than 100 ft. from unit, as measured along the control voltage wires, use No. 16 AWG wire to avoid excessive voltage drop.
3. All wiring must be NEC Class 1 and must be separated from incoming power leads. Use furnace transformer, fan coil transformer, or accessory transformer for control power.
ote: Use of available 24 volt accessories may exceed the
N minimum power requirement. Determine total transformer load and increase the transformer capacity or split the load with an accessory transformer as required.
Final Wiring Check
Check factory wiring and field wire connections to ensure terminations are secured properly ensure wires are not in contact with tubing, sheet metal, etc.
. Check wire routing to
SERVICE VALVE CONNECTIONS
Braze Joints
1. Remove the valve core from the schrader port. Wrap a
quenching cloth around the service valve. Clean and flux the joint and braze with brazing rod containing at least 10% silver (such as silphos type brazing rod). DO NOT USE SOFT SOLDER. Replace the schrader valve core after brazing has cooled.
2. Leak-check all braze joints at approximately 80 psi pressure,
purge and evacuate the lines.
Evacuation
The outdoor unit is factory charged. Evacuation is necessary
n the uncharged portions of the total system. Purge the
o system with dry nitrogen. Then connect a vacuum pump and a vacuum gage capable of accurately measuring below 1,000 microns vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and
iquid water.
l
WARNING
IF THE INSTALLER IS MAKING UP HIS OWN LINE SETS, HE MUST MAKE SURE THE TUBING IS CLEAN OF ANY IMPURITIES OR MOISTURE.
Opening the Service Valve (Step Valve)
NOTE: This is not a back-seating valve.
1. Remove the valve cap using an adjustable wrench.
2. Open the valve by inserting a hex wrench (3/16" for the liquid line, 5/16" for the vapor line) into the stem and back out counter-clockwise until the valve stem just touches the retaining ring. Do not over tighten.
3. Replace the valve cap finger-tight, then tighten an additional now complete.
1/12 turn or 1/2 hex flat. A metal-to-metal seal is
116
WARNING
DO NOT USE AIR TO LEAK-CHECK BRAZE JOINTS. DRY NITROGEN SHOULD BE USED TO LEAK-CHECK.
WARNING
ALWAYS HAVE A FIRE EXTINGUISHER AVAILABLE WHEN WORKING WITH AN OPEN FLAME.
ALWAYS USE SAFETY GLASSES, PROTECTIVE CLOTHING, AND WORK GLOVES.
115
T
orch
Brazing rod
Quenching cloth
Service valve
Schrader valve port
Remove cap
Open valve
Replace cap
Opening the Service Valve (Straight Valve)
NOTE: This is not a back-seating valve.
Open the valve by using an adjustable wrench to turn the adjusting flange 1/4 turn counter come to a stop and the seal is now complete.
-clockwise. The flange will
117
Adjusting flange
Open valve
3
Page 5
CONNECT REFRIGERANT PIPING
10
MA
X
20’
OUTDOOR SECTION
INDOOR COIL
LIQUID LINE
SUCTION LINE
The following should be followed when installing refrigerant piping. Comply with all local, state, and federal codes and/or
egulations pertaining to this type of equipment and its
r installation.
1. Run the tubing by the most direct route and support every few feet. Do not run the lines underground unless
hey are in a chase. Leave enough material between
t structure and unit to absorb vibration.
2. Insulate the vapor line to prevent sweating and line loss. In underground chases, the vapor line should be insulated to provide vibration isolation between the vapor and liquid line. A minimum of 3/8” insulation is recommended in conditioned space and 1/2” to 3/4” in unconditioned space. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
3. In general, the piping should be sloped toward the outdoor unit to prevent oil trapping. Where vertical risers occur, a suction line trap should be located at the base of the riser to assure proper oil return.
WARNING
REFRIGERANT LINE LENGTH MUST NOT EXCEED 75’ ON HORIZONTAL RUNS AND 40’ ON VERTICAL RISERS.
118
Precautions
efer to the chart below for the minimum recommended tube
R outside diameter sizes on liquid and suction lines. Ensure that vapor and liquid tube diameters are appropriate for unit capacity. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
• Undersized line sets will increase the refrigerant pressure drop between the indoor evaporator and outdoor unit, resulting in a decrease in system capacity. Oversizing the line
ets may result in excessive refrigerant charge, thereby
s making the system more susceptible to liquid migration.
• When passing refrigerant tubes through the wall, seal
pening with RTV or other pliable silicon based caulk
o
• Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls
• Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing
• When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation
• Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation
• Condensing units are available with pre-charged, sweat-type copper connecting fittings
Units are factory charged for 15’ of line set tubing.
Adjust charge 0.66 oz per foot of variation from chart for 3/8” and 3/4” line set.
Adjust charge 0.67 oz per foot of variation from chart for 3/8" and 7/8" line set.
Adjust charge 0.72 oz per foot of variation from chart for 1/2" and 1 1/8" line set.
Can only be 20’ vertical separation without additional accessories.
ARNING
W
IF THE INSTALLER IS MAKING UP HIS OWN LINE SETS, HE MUST MAKE SURE THE TUBING IS CLEAN OF ANY IMPURITIES OR MOISTURE. USE ONLY CLEAN AIR CONDITIONING AND REFRIGERATION GRADE SEAMLESS COPPER TUBING. PLUMBING GRADE COPPER IS INADEQUATE. TO ENSURE A CLEAN SYSTEM FREE OF ANY CONTAMINANTS, PURGING WITH DRY NITROGEN AND A DEEP VACUUM IS NECESSARY ON ALL SWEAT-TYPE MODELS AND ON THE UNCHARGED PORTIONS OF ALL MODELS NOT INCORPORATING PRECHARGED LINES. IT IS DESIRABLE TO PULL A VACUUM TO 1,000 MICRONS (29.96” HG) TO ENSURE TROUBLE FREE OPERATION.
Liquid Line Sizes
HEAT PUMP
MODEL
NUMBER
CH18ABD1 3/8” CH24ACD1 3/8” 3/8” 3/8” 3/8” CH30ACD1 3/8” 3/8” 3/8” 3/8” CH36ACD1 3/8” 3/8” 3/8” 3/8” CH42ACD1 3/8” 3/8” 3/8” 3/8” CH48ACD1 3/8” 3/8” 1/2” 1/2”
uction Line Sizes
S
HEAT PUMP
MODEL
NUMBER
CH18ABD1 3/4” 3/4” 3/4” 3/4” CH24ACD1 3/4” 3/4” 3/4” 3/4” CH30ACD1 7/8” CH36ACD1 7/8” 7/8” 7/8” 7/8” CH42ACD1 7/8” 7/8” 7/8” 1 1/8” CH48ACD1 7/8”
* DO NOT EXCEED 75 FT MAXIMUM LINE SET LENGTH
LINE SET LENGTH AND SIZE
15 FT
LINE SET
15 FT
LINE SET
25 FT
LINE SET
3/8”
LINE SET LENGTH AND SIZE
25 FT
LINE SET
7/8”
1 1/8”
50 FT
LINE SET
3/8”
50 FT
LINE SET
7/8” 7/8”
1 1/8”
LINE SET*
LINE SET*
1 1/8”
3/8”
75 FT
75 FT
4
Page 6
Model
37
35
33
31
29
27
25
23
21
OUTDOOR TEMPERATURE °F (T1)
OUTDOOR TEMPERATURE
°F (T1)
HEATING MODE
COOLING MODE
SUBCOOLING (T2-T3)
SUBCOOLING (T2-T3)
°F °F °F °F °F °F
4
6
8
10
12
SUB-COOLING CHARGING
For proper sub-cooling readings, a standard high side gauge is required for pressure readings.
se the charts below to determine the required sub-cooling value.
U
INSTRUCTIONS
1. Measure the outdoor air temperature. (T1)
2. Measure the liquid line pressure and determine the liquid refrigerant temperature by the scale on the high side pressure gauge. (T2) In cooling mode take reading at the indoor coil before TXV. In heating mode take reading at the
iquid line service valve on outdoor unit.
l
3. Measure the liquid line temperature on the liquid line. (T3) In cooling mode take reading at the indoor coil before TXV. In heating mode take reading at the liquid line service valve on outdoor unit.
4. Subtract T3 from T2. (T2 – T3) This is the subcooling value. Compare this value and the outdoor temperature (T1), to the charts below. If the value is below the line, add refrigerant. If the value is above the line, remove refrigerant charge. When removing refrigerant, always use standard reclaim procedures.
Adjusting TXV
For the majority of installations no adjustment to the TXV setting is required. However, if the measured superheat at the indoor coil is less than 4° or greater than 8° an adjustment is required. The adjustment stem is at the base of the valve under the flare nut. To increase superheat, tighten the stem clockwise and to decrease superheat, back-out the stem counter­clockwise. Use a 1/4” refrigeration service wrench for this function.
119
SUB-COOLING CHARTS FOR UNITS WITH TXV
All values are for reference only and may vary up or down. All heating values ar outdoor temperatur unit before reading.
e with fr
e is below 40°F manually defrost the
ee outdoor coil. When the
ost-fr
FINAL CHECKS FOR INSTALLER
1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub-through or wire pinching.
. Ensure that all wiring and tubing is secure in unit before
2
adding panels and covers.
3. Tighten service valve stem caps to 1/12 turn past finger tight.
4. Leave this manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.
COOLING OPERATION
urn the thermostat heat/cool switch to the cool position.
T Set the desired temperature on the thermostat dial. Do not operate the cooling unit for extended periods at indoor temperatures over 85°F. The unit indoor design temperature range is between 70°F and 80°F in the cooling mode.
It is not recommended to vary the temperature settings more than 5°F. Varying the temperature more than 5 degrees or turning the thermostat off for periods less than 12 hours can actually cost you more in energy consumption than keeping the temperature constant. Consider indoor plants and pets when varying the temperature from the normal comfort level.
HEATING OPERATION
Turn the thermostat heat/cool switch to the heat position. Set the desired temperature on the thermostat dial. Do not operate the heating unit at indoor temperatures over 80°F. The unit indoor design temperature range is between 65°F and 80°F in the heating mode.
Never operate the unit in the cooling mode at outdoor temperatures below 60°F without a low ambient control. Never operate the unit in the heating mode at outdoor temperatures above 70°F.
Auxiliary heat
Most heat pump installations include electric resistance heat for auxiliary heat (when the outdoor temperature is too low for the heat pump to provide enough heat) and for emergency heat (the outdoor unit is not working). On a properly-sized installation the heat pump will supply all the heat needed during cool weather. As the temperature drops, the heat output from the heat pump will be reduced. The auxiliary heat installed in the system will come on as needed to make up for this reduction of heat output.
The need for auxiliary heat is detected by the thermostat. If the thermostat senses a temperature fall of more than 2°F below the set point, the auxiliary heat will turn on. For this reason, setting the thermostat to the desired temperature and not changing the temperature during the day can be more economical than varying the thermostat setting.
If it is intended to set the temperature back at night, consider that, when the temperature is turned back up to the normal setting, the system will be operating during the coldest time of the day (early morning hours) and may require auxiliary heat if the increase in temperature is above 2
Emergency heat
This switch will turn the outdoor unit off and use the electric auxiliary heat only to provide heat. If outdoor unit should malfunction, turn the emergency heat switch to the ON position and contact your service person.
5
F.
°
Page 7
24
AB
1 VF
D
CH
18 = 18000 BTU/H [5.28 kW] 24 = 24000 BTU/H [7.03 kW] 30 = 30000 BTU/H [8.79 kW] 36 = 36000 BTU/H [10.55 kW] 42 = 42000 BTU/H [12.31 kW] 48 = 48000 BTU/H [14.07 kW] 60 = 60000 BTU/H [17.5 kW]
1 = 208/230 Volts, 1 Phase, 60 Hz 2 = 230 Volts, 1 Phase, 50 Hz 3 = 208/230 Volts, 3 Phase, 60 Hz 4 = 460 Volts, 3 Phase, 60 Hz 5 = 230 Volts, 3 Phase, 50 Hz 6 = 380 Volts, 3 Phase, 50 Hz
C = Air Conditoner CH = Heat Pump
A
F= Fedders
Poduct Type
Brand
V = Sweat
Fitting Type
D = R-22 Refrigerant E = R-407C Refrigerant F = R-410A Refrigerant
Variations
Electrical Designation
B = 21 1/2” W x 21 1/2” D x H C = 29 1/2” W x 29 1/2” D x H
Chassis Size
Nominal Capacity
Series
DEFROST OPERATION
The heat pump has a control system designed to defrost the outdoor coil by warming it up to keep it clear of ice and operating efficiently. When the temperature drops below 40°F, the control system will sense that conditions are right for the formation of ice. After a time period of 60 to 90 minutes, the
eat pump will go into the defrost mode. At this time, the
h
utdoor coil may be heavily iced or no ice may be visible,
o
epending on the outdoor humidity. When the unit starts the
d defrost mode, the outdoor fan will turn off and a hissing noise may be heard that disappears as defrost continues. As the outdoor coil warms, you may notice steam coming off the coil. When the coil reaches a predetermined temperature (usually within 7 minutes), the defrost cycle will end. You may hear a hiss as the unit switches back to the normal heating mode.
CAUTION
Wait at least 3 minutes after turning the heat pump off before trying to restart. If an attempt is made to start the compressor before the refrigerant pressures are equalized, the unit may fail to restart. An additional waiting period will then be required before restarting.
CONDENSING UNIT NOMENCLATURE
1110
MAINTENANCE INSTRUCTIONS
For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on
his equipment. Frequency of maintenance may vary depending
t
pon geographic areas, such as coastal applications.
u
WARNING
BE SURE THE UNIT DISCONNECT IS IN THE “OFF” POSITION AND THAT ALL ELECTRICAL POWER TO THE UNIT IS TURNED “OFF” BEFORE CLEANING THE SYSTEM.
1. Keep the outdoor unit clean. Wash it down with a garden hose if necessary.
WARNING
SERIOUS PERSONAL INJURY OR DEATH MAY RESULT IF WATER SPRAY IS DIRECTED TOWARD LIVE ELECTRICAL CONNECTIONS OR POWER SOURCES.
2. Remove any loose grass, leaves, papers, etc., from the area around the condenser coil. These could reduce the air supply through the coil and reduce the amount of cooling.
3. Always install and keep system filters clean. Consult your licensed Contractor for filter replacement schedules and instructions.
6
Page 8
Model C10 &
LIMITED WARRANTY
imited Five Year Warranty:
L
Fedders will provide a replacement part or component that proves to be defective in material or workmanship.
Warranty Limitations:
• Limited Warranty does not include allowances for labor or travel expense connected with the installation of parts, so furnished in this Limited Warranty or for field repair, or servicing of the equipment, nor for
efrigerant used
r
• For warranty purposes the purchase date is established by a proof of purchase. If a proof of purchase can not be verified, then warranty period will be measured from the date of manufacture plus 6 months.
• Cost of repair or replacement of consumable parts is not covered under the terms of this warranty
• Replacement parts are warranted only for the balance
of the original warranty period
• Applies only to original installation and normal use and service within the 48 contiguous United States, District of Columbia and Canada
• Applies to service performed by an authorized servicer
Warranty is Void if:
• Serial plate is defaced
• Product has defect or damage due to product alteration, connection to an improper electrical supply, shipping and handling, fire, flood, lightning or other conditions beyond the control of Fedders
• Product is not installed according to Fedders’ instructions and specifications
• Product is operated in a corrosive environment containing concentrations of corrosive agents causing deterioration of components
• Product is operated with indoor unit or refrigerant control device that does not meet Fedders’ specifications
• Product is moved from original installation site
Owner’s Responsibilities:
• Provide proof of purchase (sales receipt)
• Provide normal care and maintenance as outlined in this manual
• Make product reasonably accessible for service
• Pay for freight, labor and travel expenses Pay for premium service costs for service outside
• servicer’s normal business hours
• Pay for service calls related to product installation and maintenance
This Warranty Does Not Cover Damage Caused By:
Improper installation
• Misuse of equipment
• Negligent servicing
• Improper applications
• Preventative maintenance
• Unauthorized modifications Improper electrical supply
• Failure to follow manufacturer’s instructions and rating plate
nformation
i
• Accidents or other events beyond Fedders’ control
ENTIRE WARRANTY:
THE ABOVE CONTAINS THE SOLE AND EXCLUSIVE STATEMENT OF THE EXPRESS WARRANTIES AND ASSOCIATED REMEDIES AVAILABLE WITH THE PRODUCTS DESCRIBED. NO OTHER EXPRESS WARRANTIES ARE MADE. ALL IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, OR IMPLIED WARRANTIES OTHERWISE ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE. IN NO EVENT SHALL FEDDERS BE LIABLE FOR ANY INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. NO WARRANTIES, EXPRESS OR IMPLIED, ARE MADE TO ANY BUYER UPON RESALE.
SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS OR DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS, WHICH MA WARRANTIES ARE MADE FOR UNITS SOLD OUTSIDE THE ABOVE STATED AREAS. YOUR DISTRIBUTOR OR FINAL SELLER MAY PROVIDE A WARRANTY ON UNITS SOLD OUTSIDE OF THESE AREAS.
ARY FROM STATE TO STATE. NO
Y V
The information in this manual supersedes and replaces the previous instruction/operation manual. Illustrations cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any time without notice.
For replacement parts, please consult the installing dealer or contractor.
Fedders Corporation 505 Martinsville Rd. Liberty Corner, NJ 07938
REV. 7/06 23-23-0419N-011