Fantech SER 1504N, SER 1504, SER 3204D, SER 3204N, SER 2004N Installation, Operation And Maintenance Manual

...
Page 1
1
SER Models
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
SER 1504, SER 1504N, SER 2004, SER 2004N, SER 3204D & SER 3204N
Your ventilation system should be installed in conformance with the appropriate state requirements or in the absence of such requirements ASHRAE’s “ Good Engineering Practices”.
IMPORTANT - PLEASE READ THIS MANUAL
BEFORE INSTALLING UNIT
will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflow’s of the Energy Recovery Ventilators by using the balancing procedure found in this manual.It is always important to assess how the operation of any ERV may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).
NEVER - install a ventilator in a situation where its normal operation, lack of operation or
partial failure may result in the backdrafting or improper functioning of vented combustion equipment!!!
SER Series
Energy Recovery Ventilator
Page 2
2
TABLE OF CONTENTS
TECHNICAL DATA
SER 1504 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
SER 1504N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
SER 2004 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
SER 2004N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
SER 3204D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
SER 3204N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Modes Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..15
Optional Remote Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Intellitek Multi-Function Controls EDF5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..16
Intellitek Multi-Function Controls EDF2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Mounting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...18
Location & Ducting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...19
Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Air Flow Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
The Best Limited Warranty in the Business
• The energy recovery enthalpic core has a limited 5 year war
ranty.
• The motors found in all Fantech ERV’s require no lubrication, and are factory balanced to prevent vibration and promote silent operation.
• The limited warranty covers normal use. It does not apply to any defects, malfunctions or failures as a result of improper installation, abuse, mishandling, misapplication, unfortuitous occurrence or any other circumstances outside Fantech’s control.
• Inappropriate installation or maintenance may result in the cancellation of the warranty.
• Any unauthorized work will result in the cancellation of the warranty.
• Fantech is not responsible for any incidental or consequential damages incurred in the use of the ventilation system.
• Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area.
• Fantech reserves the right to supply refurbished parts as replacements.
• Transportation, removal and installation fees are the responsibility of the purchaser.
• The purchaser is responsible to adhering to all codes in effect in his area.
• The warranty is limited to 5 years on par
ts and 7 years on the motor from the date of purchase, including parts replaced during this time period. If there is no proof of purchase available, the date associated with the serial number will be used for the beginning of the warranty period.
* This warranty is the exclusive and only
warranty in effect relative to the ventilation system and all other warranties either expressed or implied are invalid.
Sizing (Example) for maximum airflow normally required.
ERVs are typically sized to ventilate the whole house at a minimum of 0.35 air changes per hour. To calculate, simply take the square footage of the house (including basement) and mul­tiply by the height of the ceiling to get cubic volume. Then, divide by 60 and multiply by 0.35. Example: Sq Ft of House 1100
Basement 1100 (if applicable)
Total Sq Ft 2200
Height of ceiling x 8
Cubic volume 17600
/ 60
Maximum airflow required (CFM) 293
x 0.35
103
* Always consult your local code for sizing requirements in your area.
***Illustrations & images in this
manual may not be exactly like unit
purchased, these illustrations &
images are for examples only.***
Page 3
3
SER Series
SER 1504
FEATURES
• Compact design
• Backward curved impellers
• Electrostatic filters (washable)
• Enthalpy energy recovery core
• External screw type dry contacts for optional controls
• Improved core guide channels for easy removal of core
OPTIONAL CONTROLS
• EDF 5 – Digital multi-function wall control with cycle timer
• EDF 2 – Digital multi-function wall control
• MDEH 2 – Mechanical low voltage dehumidistat with On/Off switch
• MDEH 1 – Mechanical low voltage dehumidistat
• RTS 2 – 15 Minute pushbutton timer
• FD 30M – 30 Minute crank timer
• AQS 1 – Air quality sensor
WARRANTY
• 7 year on motors
• 5 year on parts
• 5 year on core (limited)
SPECIFICATIONS
CASE 24 gauge galvanized steel. Baked powder coated paint,
antique white. Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
MOTORS Two (2) German-engineered, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed ball bearings guarantee long life and maintenance-free operation. Seven (7) year warranty.
CORE A enthalpy energy recovery core configured for an efficient cross-flow ventilation. Core is 9" x 9" (229 x 229 mm) with a 15" (380 mm) depth. Cores are manufactured to withstand extreme temperature variations.
FILTERS Two (2) Washable Electrostatic Panel Type Air Filters, SER 1504 is 8.5" (216mm) x 15" (380mm) x 0.125" (3mm),
CONTROLS External three (3) position (Low/Stand By/Medium) rocker switch that will offer continuous ventilation. Fantech offers a variety of external controls. (see optional controls)
DEFROST During the defrost sequence, the supply blower shuts down and the exhaust blower switches into high speed to maximize the effectiveness of the defrost strategy.
INSTALLATION Unit is typically hung by using installation kit supplied with unit. Mounting bolts provided on top four (4) corners of unit.
SERVICEABILITY Core, filters, motors and drain pan can be easily serviced through latched access door. Core conveniently slides out with ease on an improved railing system. Electrical box, placed on the outside of the unit, can also be easily accessed.
Energy Recovery Ventilator
Distributed by:
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea­tures, designs, components and specifications to maintain their technological leadership position.
Exhaust at
High Speed
Page 4
4
Dimensions & Airflow
- All units feature three foot plug-in power cord with 3-prong plug on top of electrical box.
Pa in wg L/s cfm L/s cfm L/s cfm
25 0.1 77 162 77 162 77 162 50 0.2 72 152 72 152 72 152
75 0.3 67 143 67 143 67 143 100 0.4 63 134 63 134 63 134 125 0.5 60 127 60 127 60 127 150 0.6 57 121 57 121 57 121 175 0.7 54 115 54 115 54 115 200 0.8 51 108 51 108 51 108
EXT. STATIC
PRESSURE
NET SUPPLY
AIR FLOW
GROSS AIR FLOW
SUPPLY EXHAUST
˚C ˚F L/s cfm
Heating 0 32 30 64 67 70% 82% 0.58
0 32 39 83 121 66% 79% 0.56 0 32 57 121 168 61% 74% 0.55
Total Recovery Efficiency
Cooling 35 95 30 64 66 44%
35 95 55 117 143 36%
SUPPLY
TEMPERATURE
NET
AIRFLOW
Ventilation Performance
POWER
CONSUMED
WATTS
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVENESS
NET MOISTURE TRANSFER
Submitted by: Date:
Qty: Model #:
Comments:
Project #:
Location:
Architect:
Engineer:
Contractor:
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
0 255075100125150175200
cfm (l/s = n x 0.47)
in w.g. (Pa = n x 248)
Net Supply
Net Exhaust
Specifications and Ratings
• Model: SER 1504
• Total assembled weight: 45 lbs
• Cabinet: 24 ga. steel w/ powder coat finish
• Motors: ebm motor w/backward curved blades
• Filters: 2 washable electrostatic filters
8.5" (216mm) x 15" (380mm) x 0.125" (3mm)
• Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
• Core: Enthalpy
9" (229mm) x 9" (229 mm) x 15" (380 mm)
• Supply & exhaust ducts: 6" (152.4mm)
• Mounting: Suspended by chains & hooks
• Electrical requirements: Volts Frequency Amps Watts
120V 60Hz 1.5A 150W 3' plug-in power cord w/ 3-prong plug
Contacts
High
Speed
United States
1712 Northgate Blvd.
Sarasota, FL. 34234
Phone: 800.747.1762; 941.309.6000
Fax: 800.487.9915; 941.309.6099
www.fantech.net
info@fantech.net
Canada
50 Kanalflakt Way
Bouctouche, NB E4S 3M5
Phone: 800.565.3548; 506.743.9500
Fax: 877.747.8116; 506.743.9600
www.fantech.ca
info@fantech.ca
Article #: 301XXX
Rev Date: 110104
Energy Performance
Enthalpy Core
Access
Door
6" dia.
(152 mm)
(All Ports)
Electrostatic Filters
Fresh Air
From Outside
16 ¹⁄₈"
(413 mm)
Exhaust Air
To Outside
2 ¹⁄₄"
(56 mm)
23 ¹⁄₂"
(596 mm)
2 ⁵⁄₈"
(67 mm)
17 ³⁄₈"
(441 mm)
EBM Motor Polypropolene Core Electrical Box
1/2 " NPT
Exhaust Air
From Building
Fresh Air
To Building
Page 5
5
SER Series
SER 1504N
FEATURES
• Compact design
• Backward curved impellers
• Electrostatic filters (washable)
• Enthalpy energy recovery core
• External screw type dry contacts for optional controls
• Improved core guide channels for easy removal of core
OPTIONAL CONTROLS
• EDF 5 – Digital multi-function wall control with cycle timer
• EDF 2 – Digital multi-function wall control
• RTS 2 – 15 Minute pushbutton timer
• FD 30M – 30 Minute crank timer
• AQS 1 – Air quality sensor
WARRANTY
• 7 year on motors
• 5 year on parts
• 5 year on core (limited)
SPECIFICATIONS
CASE 24 gauge galvanized steel. Baked powder coated paint,
antique white. Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
MOTORS Two (2) German-engineered, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed ball bearings guarantee long life and maintenance-free operation. Seven (7) year warranty.
CORE A enthalpy energy recovery core configured for an efficient cross-flow ventilation. Core is 9" x 9" (229 x 229 mm) with a 15" (380 mm) depth. Cores are manufactured to withstand extreme temperature variations.
FILTERS Two (2) Washable Electrostatic Panel Type Air Filters, they are 8.5" (216mm) x 15" (380mm) x 0.125" (3mm).
PORT SELECTION (Reversing Unit) Units are shipped indicating airflow (see "Dimensions & Airflow" on next page). These ports can be selected on site by the installer and changed around as needed. IE "Exhaust Air From Building" could be changed to "Air From Outside" and "Exhaust To Outside" switched to "Air To Building". The same is true for the other ports. This gives the installer greater flexibility in placement of the unit and ductwork.
INSTALLATION Unit is typically hung by using installation kit supplied with unit. Mounting bolts provided on top four (4) corners of unit.
SERVICEABILITY Core, filters, and motors can be easily serviced through latched access door. Core conveniently slides out with ease on an improved railing system. Electrical box, placed on the outside of the unit, can also be easily accessed.
NOTE This model is not recommended for climates that experience temperatures below 23˚F (-5˚C) for more than 2 consecutive days.
Energy Recovery Ventilator
Distributed by:
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea­tures, designs, components and specifications to maintain their technological leadership position.
Page 6
6
Dimensions & Airflow
- All units feature three foot plug-in power cord with 3-prong plug on top of electrical box.
Pa in wg L/s cfm L/s cfm L/s cfm
25 0.1 77 162 77 162 77 162 50 0.2 72 152 72 152 72 152
75 0.3 67 143 67 143 67 143 100 0.4 63 134 63 134 63 134 125 0.5 60 127 60 127 60 127 150 0.6 57 121 57 121 57 121 175 0.7 54 115 54 115 54 115 200 0.8 51 108 51 108 51 108
EXT. STATIC
PRESSURE
NET SUPPLY
AIR FLOW
GROSS AIR FLOW
SUPPLY EXHAUST
˚C ˚F L/s cfm
Heating 0 32 30 64 67 70% 82% 0.58
0 32 39 83 121 66% 79% 0.56 0 32 57 121 168 61% 74% 0.55
Total Recovery Efficiency
Cooling 35 95 30 64 66 44%
35 95 55 117 143 36%
SUPPLY
TEMPERATURE
NET
AIRFLOW
Ventilation Performance
POWER
CONSUMED
WATTS
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVENESS
NET MOISTURE TRANSFER
Submitted by: Date:
Qty: Model #:
Comments:
Project #:
Location:
Architect:
Engineer:
Contractor:
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
0 255075100125150175200
cfm (l/s = n x 0.47)
in w.g. (Pa = n x 248)
Net Supply
Net Exhaust
Specifications and Ratings
• Model: SER 1504N
• Total assembled weight: 45 lbs
• Cabinet: 24 ga. steel w/ powder coat finish
• Motors: ebm motor w/backward curved blades
• Filters: 2 washable electrostatic filters
8.5" (216mm) x 15" (380mm) x 0.125" (3mm)
• Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
• Core: Enthalpy 9" (229mm) x 9" (229 mm) x 15" (380 mm)
• Supply & exhaust ducts: 6" (152.4mm)
• Mounting: Suspended by chains & hooks
• Electrical requirements: Volts Frequency Amps Watts
120V 60Hz 1.5A 150W 3' plug-in power cord w/ 3-prong plug
Contacts
High
Speed
United States
1712 Northgate Blvd.
Sarasota, FL. 34234
Phone: 800.747.1762; 941.309.6000
Fax: 800.487.9915; 941.309.6099
www.fantech.net
info@fantech.net
Canada
50 Kanalflakt Way
Bouctouche, NB E4S 3M5
Phone: 800.565.3548; 506.743.9500
Fax: 877.747.8116; 506.743.9600
www.fantech.ca
info@fantech.ca
Article #: 301XXX
Rev Date: 110104
Energy Performance
Enthalpy Core
Enthalpy Co
Access
Door
6" dia.
(152 mm)
(All Ports)
Electrostatic Filters
Fresh Air
From Outside
16 ¹⁄₈"
(413 mm)
Exhaust Air
To Outside
2 ¹⁄₄"
(56 mm)
23 ¹⁄₂"
(596 mm)
2 ⁵⁄₈"
(67 mm)
17 ³⁄₈"
(441 mm)
EBM Motor Polypropolene Core Electrical Box
Exhaust Air
From Building
Fresh Air
To Building
Page 7
7
SER Series
SER 2004
FEATURES
• Compact design
• Backward curved impellers
• Electrostatic filters (washable)
• Enthalpy energy recovery core
• External screw type dry contacts for optional controls
• Improved core guide channels for easy removal of core
OPTIONAL CONTROLS
• EDF 5 – Digital multi-function wall control with cycle timer
• EDF 2 – Digital multi-function wall control
• MDEH 2 – Mechanical low voltage dehumidistat with On/Off switch
• MDEH 1 – Mechanical low voltage dehumidistat
• RTS 2 – 15 Minute pushbutton timer
• FD 30M – 30 Minute crank timer
• AQS 1 – Air quality sensor
WARRANTY
• 7 year on motors
• 5 year on parts
• 5 year on core (limited)
SPECIFICATIONS
CASE 22 gauge galvanized steel. Baked powder coated paint,
antique white. Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
MOTORS Two (2) German-manufactured, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed ball bearings guarantee long life and maintenance-free operation. Seven (7) year warranty.
CORE A enthalpy energy recovery core configured for an efficient cross-flow ventilation. Core is 12" x 12" (305 x 305 mm) with a 15" (380 mm) depth. Cores are manufactured to withstand extreme temperature variations.
FILTERS Two (2) Washable Electrostatic Panel Type Air Filters, they are 11.75" (298mm) x 15" (380mm) x 0.125" (3mm).
CONTROLS External three (3) position (Low/Stand By/Medium) rocker switch that will offer continuous ventilation. Fantech offers a variety of external controls. (see optional controls)
DEFROST During the defrost sequence, the supply blower shuts down and the exhaust blower switches into high speed to maximize the effectiveness of the defrost strategy.
INSTALLATION Unit is typically hung by using installation kit supplied with unit. Mounting bolts provided on top four (4) corners of unit.
SERVICEABILITY Core, filters, motors and drain pan can be easily serviced through latched access door. Core conveniently slides out with ease on an improved railing system. Electrical box, placed on the outside of the unit, can also be easily accessed.
Energy Recovery Ventilator
Distributed by:
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea­tures, designs, components and specifications to maintain their technological leadership position.
ore
Exhaust at
High Speed
Page 8
8
Dimensions & Airflow
- All units feature three foot plug-in power cord with 3-prong plug on front right hand side top of unit.
Pa in wg L/s cfm L/s cfm L/s cfm
25 0.1 88 186 88 186 88 186 50 0.2 83 176 83 176 83 176
75 0.3 78 166 78 166 78 166 100 0.4 73 155 73 155 73 155 125 0.5 68 145 68 145 68 145 150 0.6 63 134 63 134 63 134 175 0.7 58 123 58 123 58 123 200 0.8 53 112 53 112 53 112 225 0.9 48 101 48 101 48 101 250 1.0 42 90 42 90 42 90
EXT. STATIC
PRESSURE
NET SUPPLY
AIR FLOW
GROSS AIR FLOW
SUPPLY EXHAUST
˚C ˚F L/s cfm
Heating 0 32 30 64 62 81% 92% 0.78
0 32 55 117 128 74% 86% 0.76 0 32 76 161 194 70% 84% 0.71
Total Recovery Efficiency
Cooling 35 95 30 64 57 52%
35 95 55 117 130 46%
SUPPLY
TEMPERATURE
NET
AIRFLOW
Ventilation Performance
POWER
CONSUMED
WATTS
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVENESS
NET MOISTURE TRANSFER
Submitted by: Date:
Qty: Model #:
Comments:
Project #:
Location:
Architect:
Engineer:
Contractor:
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
0 255075100125150175200
cfm (l/s = n x 0.47)
in w.g. (Pa = n x 248)
Net Supply
Net Exhaust
Specifications and Ratings
• Model: SER 2004
• Total assembled weight: 61 lbs
• Cabinet: 22 ga. steel w/ powder coat finish
• Motors: ebm motor w/backward curved blades
• Filters: 2 washable electrostatic filters
11.75" (298mm) x 15" (380mm) x 0.125" (3mm)
• Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
• Core: Enthalpy 12" (305mm) x 12" (305 mm) x 15" (380 mm)
• Supply & exhaust ducts: 6" (152.4mm)
• Mounting: Suspended by chains & hooks
• Electrical requirements: Volts Frequency Amps Watts 120V 60Hz 1.9A 150W 3' plug-in power cord w/ 3-prong plug
High
Speed
United States
1712 Northgate Blvd.
Sarasota, FL. 34234
Phone: 800.747.1762; 941.309.6000
Fax: 800.487.9915; 941.309.6099
www.fantech.net
info@fantech.net
Canada
50 Kanalflakt Way
Bouctouche, NB E4S 3M5
Phone: 800.565.3548; 506.743.9500
Fax: 877.747.8116; 506.743.9600
www.fantech.ca
info@fantech.ca
Article #: 301XXX Rev Date: 110104
Contacts
Energy Performance
Enthalpy Core
Access
Door
6" dia.
(152 mm)
(All Ports)
Electrostatic Filters
Fresh Air
From Outside
20 ¹⁄₂"
(520 mm)
Exhaust Air
To Outside
2 ¹⁄₄"
(56 mm)
27 ⁷⁄₈"
(707 mm)
2 ⁵⁄₈"
(67 mm)
17 ³⁄₈"
(441 mm)
EBM Motor
1/2 " NPT
Polypropolene Core Electrical Box
Exhaust Air
From Building
Fresh Air
To Building
Page 9
9
SER Series
SER 2004N
FEATURES
• Compact design
• Backward curved impellers
• Electrostatic filters (washable)
• Enthalpy energy recovery core
• External screw type dry contacts for optional controls
• Improved core guide channels for easy removal of core
OPTIONAL CONTROLS
• EDF 5 – Digital multi-function wall control with cycle timer
• EDF 2 – Digital multi-function wall control
• RTS 2 – 15 Minute pushbutton timer
• FD 30M – 30 Minute crank timer
• AQS 1 – Air quality sensor
WARRANTY
• 7 year on motors
• 5 year on parts
• 5 year on core (limited)
SPECIFICATIONS
CASE 22 gauge galvanized steel. Baked powder coated paint,
antique white. Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
MOTORS Two (2) German-manufactured, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed ball bearings guarantee long life and maintenance-free operation. Seven (7) year warranty.
CORE A enthalpy energy recovery core configured for an efficient cross-flow ventilation. Core is 12" x 12" (305 x 305 mm) with a 15" (380 mm) depth. Cores are manufactured to withstand extreme temperature variations.
FILTERS Two (2) Washable Electrostatic Panel Type Air Filters, they are 11.75" (298mm) x 15" (380mm) x 0.125" (3mm).
PORT SELECTION (Reversing Unit) Units are shipped indicating airflow (see "Dimensions & Airflow" on next page). These ports can be selected on site by the installer and changed around as needed. IE "Exhaust Air From Building" could be changed to "Air From Outside" and "Exhaust To Outside" switched to "Air To Building". The same is true for the other ports. This gives the installer greater flexibility in placement of the unit and ductwork.
INSTALLATION Unit is typically hung by using installation kit supplied with unit. Mounting bolts provided on top four (4) corners of unit.
SERVICEABILITY Core, filters, and motors can be easily serviced through latched access door. Core conveniently slides out with ease on an improved railing system. Electrical box, placed on the outside of the unit, can also be easily accessed.
NOTE This model is not recommended for climates that experience temperatures below 23˚F (-5˚C) for more than 2 consecutive days.
Energy Recovery Ventilator
Distributed by:
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea­tures, designs, components and specifications to maintain their technological leadership position.
Page 10
10
Dimensions & Airflow
- All units feature three foot plug-in power cord with 3-prong plug on front right hand side top of unit.
Pa in wg L/s cfm L/s cfm L/s cfm
25 0.1 88 186 88 186 88 186 50 0.2 83 176 83 176 83 176
75 0.3 78 166 78 166 78 166 100 0.4 73 155 73 155 73 155 125 0.5 68 145 68 145 68 145 150 0.6 63 134 63 134 63 134 175 0.7 58 123 58 123 58 123 200 0.8 53 112 53 112 53 112 225 0.9 48 101 48 101 48 101 250 1.0 42 90 42 90 42 90
EXT. STATIC
PRESSURE
NET SUPPLY
AIR FLOW
GROSS AIR FLOW
SUPPLY EXHAUST
˚C ˚F L/s cfm
Heating 0 32 30 64 62 81% 92% 0.78
0 32 55 117 128 74% 86% 0.76 0 32 76 161 194 70% 84% 0.71
Total Recovery Efficiency
Cooling 35 95 30 64 57 52%
35 95 55 117 130 46%
SUPPLY
TEMPERATURE
NET
AIRFLOW
Ventilation Performance
POWER
CONSUMED
WATTS
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVENESS
NET MOISTURE TRANSFER
Submitted by: Date:
Qty: Model #:
Comments:
Project #:
Location:
Architect:
Engineer:
Contractor:
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
0 255075100125150175200
cfm (l/s = n x 0.47)
in w.g. (Pa = n x 248)
Net Supply
Net Exhaust
Specifications and Ratings
• Model: SER 2004N
• Total assembled weight: 61 lbs
• Cabinet: 22 ga. steel w/ powder coat finish
• Motors: ebm motor w/backward curved blades
• Filters: 2 washable electrostatic filters
11.75" (298mm) x 15" (380mm) x 0.125" (3mm)
• Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
• Core: Enthalpy 12" (305mm) x 12" (305 mm) x 15" (380 mm)
• Supply & exhaust ducts: 6" (152.4mm)
• Mounting: Suspended by chains & hooks
• Electrical requirements: Volts Frequency Amps Watts 120V 60Hz 1.9A 150W 3' plug-in power cord w/ 3-prong plug
High
Speed
United States
1712 Northgate Blvd.
Sarasota, FL. 34234
Phone: 800.747.1762; 941.309.6000
Fax: 800.487.9915; 941.309.6099
www.fantech.net
info@fantech.net
Canada
50 Kanalflakt Way
Bouctouche, NB E4S 3M5
Phone: 800.565.3548; 506.743.9500
Fax: 877.747.8116; 506.743.9600
www.fantech.ca
info@fantech.ca
Article #: 301XXX Rev Date: 110104
Contacts
Energy Performance
Enthalpy Core
Access
Door
6" dia.
(152 mm)
(All Ports)
Electrostatic Filters
Fresh Air
From Outside
20 ¹⁄₂"
(520 mm)
Exhaust Air
To Outside
2 ¹⁄₄"
(56 mm)
27 ⁷⁄₈"
(707 mm)
2 ⁵⁄₈"
(67 mm)
17 ³⁄₈"
(441 mm)
EBM Motor
Polypropolene Core Electrical Box
Exhaust Air
From Building
Fresh Air
To Building
Page 11
11
SER Series
SER 3204D
FEATURES
• Compact design
• Backward curved impellers
• Electrostatic filters (washable)
• Enthalpy energy recovery core
• External screw type dry contacts for optional controls
• Improved core guide channels for easy removal of core
OPTIONAL CONTROLS
• EDF 5 – Digital multi-function wall control with cycle timer
• EDF 2 – Digital multi-function wall control
• MDEH 2 – Mechanical low voltage dehumidistat with On/Off switch
• MDEH 1 – Mechanical low voltage dehumidistat
• RTS 2 – 15 Minute pushbutton timer
• FD 30M – 30 Minute crank timer
• AQS 1 – Air quality sensor
WARRANTY
• 7 year on motors
• 5 year on parts
• 5 year on core (limited)
SPECIFICATIONS
CASE 22 gauge galvanized steel. Baked powder coated paint,
antique white. Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
MOTORS Four (4) German-engineered, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed ball bearings guarantee long life and maintenance-free operation. Seven (7) year warranty.
CORES Two (2) enthalpy energy recovery cores configured for an efficient cross-flow ventilation. Cores are 12" x 12" (305 x 305 mm) with a 11.34" (288 mm) depth. Cores are manufactured to withstand extreme temperature variations and material is Flame-proof paper and polyester-based synthetic paper.
FILTERS Four (4) Washable Electrostatic Panel Type Air Filters, they are 11.75" (298mm) x 11.4" (290mm) x 0.125" (3mm).
CONTROLS External three (3) position (Low/Stand By/Medium) rocker switch that will offer continuous ventilation. Fantech offers a variety of external controls. (see optional controls)
DEFROST During the defrost sequence, the supply blower shuts down and the exhaust blower switches into high speed to maximize the effectiveness of the defrost strategy.
INSTALLATION Unit is typically hung by using installation kit supplied with unit. Mounting bolts provided on top four (4) corners of unit.
SERVICEABILITY Cores, filters, motors and drain pan can be easily serviced through latched access doors located on 2 sides of the unit. Cores conveniently slides out with ease on an improved railing system. Electrical box, placed on the outside of the unit, can also be easily accessed.
Energy Recovery Ventilator
Distributed by:
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea­tures, designs, components and specifications to maintain their technological leadership position.
Exhaust at
High Speed
Page 12
12
Dimensions & Airflow
- All units feature three foot plug-in power cord with 3-prong plug on top of electrical box.
Pa in wg L/s cfm L/s cfm L/s cfm
25 0.1 126 268 131 277 139 294 50 0.2 124 262 127 270 132 279
75 0.3 116 246 119 253 126 266 100 0.4 109 231 112 238 117 247 125 0.5 103 219 107 226 111 236 150 0.6 96 204 100 211 101 215 175 0.7 93 196 95 202 101 213 200 0.8 89 188 92 194 94 200 250 1.0 77 163 79 168 82 174 300 1.2 69 147 71 151 71 151 350 1.4 56 118 57 121 58 123
EXT. STATIC
PRESSURE
NET SUPPLY
AIR FLOW
GROSS AIR FLOW
SUPPLY EXHAUST
˚C ˚F L/s cfm
Heating 0 32 30 64 126 76 91 0.78
0 32 55 117 212 78 92 0.76 0 32 74 157 262 78 91 0.71
Total Recovery Efficiency
Cooling 35 95 54 115 206 48 %
35 95 74 159 260 48 %
SUPPLY
TEMPERATURE
NET
AIRFLOW
Ventilation Performance
POWER
CONSUMED
WATTS
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVENESS
LATENT
RECOVERY/MOISTURE
TRANSFER
Submitted by: Date:
Qty: Model #:
Comments:
Project #:
Location:
Architect:
Engineer:
Contractor:
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0 50 100 150 200 250 300 350
Net Supply
Net Exhaust
cfm (l/s = n x 0.47)
in w.g. (Pa = n x 248)
Specifications and Ratings
• Model: SER 3204D (2 access doors)
• Total assembled weight: 80 lbs
• Cabinet: 22 ga. steel w/ powder coat finish
• Motors: ebm motor w/backward curved blades
• Filters: 4 washable electrostatic filters
11.75" (298mm) x 11.4" (290mm) x 0.125" (3mm)
• Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
• Two (2) cores: Enthalpy
12" (305mm) x 12" (305 mm) x 11.4" (288 mm)
• Supply & exhaust ducts: 8" (200 mm)
• Mounting: Suspended by chains & hooks
• Electrical requirements: Volts Frequency Amps Watts 120V 60Hz 2.5A 300W 3' plug-in power cord w/ 3-prong plug
Contacts
High
Speed
Energy Performance
United States
1712 Northgate Blvd.
Sarasota, FL. 34234
Phone: 800.747.1762; 941.309.6000
Fax: 800.487.9915; 941.309.6099
www.fantech.net
info@fantech.net
Canada
50 Kanalflakt Way
Bouctouche, NB E4S 3M5
Phone: 800.565.3548; 506.743.9500
Fax: 877.747.8116; 506.743.9600
www.fantech.ca
info@fantech.ca
Article #: 301XXX
Rev Date: 110104
Page 13
13
SER Series
SER 3204N
FEATURES
• Compact design
• Backward curved impellers
• Electrostatic filters (washable)
• Enthalpy energy recovery core
• External screw type dry contacts for optional controls
• Improved core guide channels for easy removal of core
OPTIONAL CONTROLS
• EDF 5 – Digital multi-function wall control with cycle timer
• EDF 2 – Digital multi-function wall control
• RTS 2 – 15 Minute pushbutton timer
• FD 30M – 30 Minute crank timer
• AQS 1 – Air quality sensor
WARRANTY
• 7 year on motors
• 5 year on parts
• 5 year on core (limited)
SPECIFICATIONS
CASE 22 gauge galvanized steel. Baked powder coated paint,
antique white. Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
MOTORS Four (4) German-engineered, factory-balanced ebm™ motors with backward curved blades. Motors come with permanently lubricated sealed ball bearings guarantee long life and maintenance-free operation. Seven (7) year warranty.
CORES Two (2) enthalpy energy recovery cores configured for an efficient cross-flow ventilation. Cores are 12" x 12" (305 x 305 mm) with a 11.34" (288 mm) depth. Cores are manufactured to withstand extreme temperature variations and material is Flame-proof paper and polyester-based synthetic paper.
FILTERS Four (4) Washable Electrostatic Panel Type Air Filters, they are 11.75" (298mm) x 11.4" (290mm) x 0.125" (3mm).
PORT SELECTION (Reversing Unit) Units are shipped indicating airflow (see "Dimensions & Airflow" on next page). These ports can be selected on site by the installer and changed around as needed. IE "Exhaust Air From Building" could be changed to "Air From Outside" and "Exhaust To Outside" switched to "Air To Building". The same is true for the other ports. This gives the installer greater flexibility in placement of the unit and ductwork.
SERVICEABILITY Cores, filters and motors can be easily serviced through latched access door. Cores conveniently slides out with ease on an improved railing system. Electrical box, placed on the outside of the unit, can also be easily accessed.
NOTE This model is not recommended for climates that experience temperatures below 23˚F (-5˚C) for more than 2 consecutive days.
Energy Recovery Ventilator
Distributed by:
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea­tures, designs, components and specifications to maintain their technological leadership position.
Page 14
14
Dimensions & Airflow
- All units feature three foot plug-in power cord with 3-prong plug on top of electrical box.
Pa in wg L/s cfm L/s cfm L/s cfm
25 0.1 126 268 131 277 139 294 50 0.2 124 262 127 270 132 279
75 0.3 116 246 119 253 126 266 100 0.4 109 231 112 238 117 247 125 0.5 103 219 107 226 111 236 150 0.6 96 204 100 211 101 215 175 0.7 93 196 95 202 101 213 200 0.8 89 188 92 194 94 200 250 1.0 77 163 79 168 82 174 300 1.2 69 147 71 151 71 151 350 1.4 56 118 57 121 58 123
EXT. STATIC
PRESSURE
NET SUPPLY
AIR FLOW
GROSS AIR FLOW
SUPPLY EXHAUST
˚C ˚F L/s cfm
Heating 0 32 30 64 126 76 91 0.78
0 32 55 117 212 78 92 0.76 0 32 74 157 262 78 91 0.71
Total Recovery Efficiency
Cooling 35 95 54 115 206 48 %
35 95 74 159 260 48 %
SUPPLY
TEMPERATURE
NET
AIRFLOW
Ventilation Performance
POWER
CONSUMED
WATTS
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVENESS
LATENT
RECOVERY/MOISTURE
TRANSFER
Submitted by: Date:
Qty: Model #:
Comments:
Project #:
Location:
Architect:
Engineer:
Contractor:
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0 50 100 150 200 250 300 350
Net Supply
Net Exhaust
cfm (l/s = n x 0.47)
in w.g. (Pa = n x 248)
Specifications and Ratings
• Model: SER 3204N
• Total assembled weight: 80 lbs
• Cabinet: 22 ga. steel w/ powder coat finish
• Motors: ebm motor w/backward curved blades
• Filters: 4 washable electrostatic filters
11.75" (298mm) x 11.4" (290mm) x 0.125" (3mm)
• Insulated with 1" (25 mm) high density polystyrene foam to prevent condensation and meet the requirements of the Underwriters Laboratories 94HF.
• Two (2) cores: Enthalpy 12" (305mm) x 12" (305 mm) x 11.4" (288 mm)
• Supply & exhaust ducts: 8" (200 mm)
• Mounting: Suspended by chains & hooks
• Electrical requirements: Volts Frequency Amps Watts 120V 60Hz 2.5A 300W 3' plug-in power cord w/ 3-prong plug
Contacts
High
Speed
United States
1712 Northgate Blvd.
Sarasota, FL. 34234
Phone: 800.747.1762; 941.309.6000
Fax: 800.487.9915; 941.309.6099
www.fantech.net
info@fantech.net
Canada
50 Kanalflakt Way
Bouctouche, NB E4S 3M5
Phone: 800.565.3548; 506.743.9500
Fax: 877.747.8116; 506.743.9600
www.fantech.ca
info@fantech.ca
Article #: 301XXX Rev Date: 110104
Energy Performance
Page 15
15
OPERATION
An Energy Recovery Ventilator (ERV) is designed to bring in fresh air into the building while exhausting an equal amount of stale air. During colder months, utilizing the heat recovered from the stale air before it is exhausted outdoors warms the cold fresh air. At the same time, humidity contained indoors is transferred back to the incoming fresh and dried air. During warm and humid months, the ERV will cool the incoming outdoor air by using the cool air-conditioned air that is being exhausted from indoors while allowing the humidity contained in the fresh air to be transferred to the exhaust air.
Fantech ERV’s are designed to run continuous or on intermittent, giving the homeowner complete control over their air quality. Continuous low speed ventilation is recommended, which will help eliminate carbon dioxide, voc’s and other gases as well as freshen up the home. Intermittent high speed ventilation can be obtained through a variety of optional remote controls found in this manual.
The entire line of SER series Energy Recovery Ventilators comes equipped with Fantech's new electronic uni-control board which offers a wide vari­ety of features making it the ultimate ventilation control system. Fantech engineers have used the latest technology to provide solid, trouble free oper­ation under any conditions.
The Fantech uni-control board offers stand alone operating capabilities as well as an exclusive 2 wire communication to most external controls. The trouble-free optional controls include: two different rotary dial dehumidistats, an air quality sensor (3 wire communication required), a 15 minute remote push-button timer, as well as the most sophisticated line of remote wall mounted controls, the Intellitek EDF5 (5MR).
An on-board diagnostic LED helps find problems quickly and efficiently. For example the LED can be used to signal a broken or shorted electronic wall control wire. Electronic air temperature probe gives this board accurate readings in order to minimize unnecessary defrost operation, and the on­board jumpers provide the user with the option of adjusting defrost time and sequence to optimize performance under abnormal conditions. The defrost operation is automatic and is usually never adjusted.
3. Defrost (on selected models)
The automatic defrost cycle consists of a fan shutdown. When the supply air stream temperature goes below ­5°C (23°F), the supply motor shuts down and the exhaust motor goes into high speed. Ambient air is passed through the unit for a period of 5 minutes. The supply motor will then re-start and run at the preset speed. The exhaust motor will also slow down to the preset speed, and the unit will operate in the run cycle for 25 min­utes. This fan shutdown defrost cycle continues until the supply air stream rises above 0°C (32°F).
MODES OF OPERATION
1. Continuous / Ventilation Mode
In this mode of operation both fans are operating and exchanging air with the outside. The energy recovery ven-
tilator (ERV) constantly exchanges the air at the rate you select, either at low or medium speed, and switches to high speed when activated by an optional remote control. The "Low" and "Med" fan speed selection will cause the unit to operate in continuous exchange mode at an exchange rate of 35% and 50% maximum airflow rating respectively. Continuous mode is recommended, since pollutants are slowly but constantly being generated in your house.
Air from
House
Air from
Outside
Air to
House
Air to
Outside
2. Intermittent / Standby Mode
The system is always on standby and operates at high speed when activated by an optional remote control. "Standby" should be selected if the user wishes to stop the unit from
continuous exchange. We recommend that the "Standby" mode only be used if your system is equipped with an optional external control, in which case, the unit would activate to "High" fan speed, until the control is satisfied and then return to standby (off).
* no exchange of air
Air from
House
Air to
outside
Page 16
16
15-min Timer - The 15-minute remote timer is typically installed in areas where contamination such as moisture and odors, are produced. Simply push the button and the ERV will activate to high speed for 15 minutes. Up to 5 electronic timers can be installed in parallel throughout the building at a distance of up to 500 feet (152 meters) from the ERV.
Air Quality Sensor - The wall mount Air Quality Sensor (AQS) monitors indoor air quality and activates the override mode when carbon monoxide, formaldehyde, benzene, volatile organic compounds and other pollutants are detected. The unit will then return to normal mode once the air pollutants are reduced to a pre-determined lower level.
* This control is not a warning device.
Dehumidistat II - The wall mount dehumidistat II offers the same features of the dehumidistat I plus additional off/on control for the ERV. Dial illuminates when in override mode.
Dehumidistat I - The wall mount dehumidistat monitors the humidity level in the area it is installed. When the humidity level rises above the desired set­point, the ERV will activate to high speed/override mode. Once the humidity level returns to desired condition, the unit will return to the normal mode.
To avoid window condensation:
• If a dehumidistat or EDF control is installed, the humidity setting should be raised to its highest setting (e.g. 99% on EDF) when using an ERV during warm and humid months. Otherwise, the ERV may stay on HIGH speed, bringing in more humid air indoors.
PRACTICAL TIPS
OPERATION (CONT'D)
* All controls are low voltage. 18 to 24
gauge wire is recommended.
OPTIONAL REMOTE CONTROLS
*
NOTE:
A dehumidistat is ideal for use in energy efficient houses where indoor humidity (during the heating
season) is higher than outdoor levels. High humidity is a major cause of structure damage and IAQ problems such as mold and mildew.
2 wire installation
4 wire installation
3 wire installation
2 wire installation
EDF5 INTELLITEK MULTI-FUNCTION WALL CONTROL
Control multiple func­tions of your Fantech ERV with one slimline wall control. Two wire connection simplifies installation. Use one EDF5 per ERV installed.
OVERRIDE SPEED CONTROL
Push to select override speed of unit. (High Speed Recommended)
CYCLE CONTROL
Set unit to cycle on 15, 20, or 30 min­utes every hour
MODE SPEED
Set Unit to Low, Medium or High Speed
OVERRIDE TIMER
When pressed, unit will provide high speed ventilation for one 15, 30 or 60 minute period.
DIGITAL HYGROMETER DISPLAY
Shows Indoor Humidity Level
*
DEHUMIDISTAT CONTROL (see description)
MAINTENANCE LIGHT
Light comes on when it’s time to clean unit.
POWER
On/Off and Reset
MODES
Select Intermittent or Continuous Ventilation Modes
OPTIONAL INTELLITEK CONTROL
NOTE:
When an Intellitek control is installed, the rocker switch located on the right hand side of the ERV will be automatically deactivated giving the user complete control from wherever he/she wishes to mount the control pad.
NOTE:
The override speed cannot be set at a fan speed lower or equal to the normal operating fan speed. For example, if the unit is normally operating at a medium fan speed, the override fan speed will be automatically set to high.
NOTE:
EDF5 model, changing the override speed will change default override speed for other external controls.
EXAMPLES:
If on the EDF5 control, you have set the override control at medium, and you start an external remote control (15 min. timer), the unit will run at medium speed for 15 min.
PRACTICAL TIPS
4 1/2"
(114 mm)
5 1/8"
(130 mm)
Width = 4 1/2" (114mm)
Height = 5 1/8" (130mm)
Thickness = 5/8" (16mm)
• All controls are low voltage. 18 to 24 gauge wire is recommended.
*
*
Page 17
17
OPERATION (CONT'D)
OPTIONAL INTELLITEK CONTROL
Note: All controls are low voltage. 18 to 24 gauge wire is recommended.
EDF2
INTELLITEK MULTI­FUNCTION WALL CONTROL
Control multiple functions of your Fantech SER with one slimline wall control. Two wire connection simplifies installa­tion. Use one 2M per SER installed.
FILTER LIGHT RESET & MODE FAN SPEED SELECTOR
Press to reset the filter mainte­nance reminder light. The com­bination filter light reset and up setpoint selector buttons let’s you choose at which speed the HRV, ERV unit will operate at. Pressing the filter light reset but­ton once displays the mode fan speed on the LCD. The LCD should display one of the follow­ing three letters, L for Low, M for Medium and H for High. To change the mode speed, press the up setpoint until desired speed is displayed, selector. After 1 second of inac­tivity, the LCD will return to rela­tive humidity reading.
OVERRIDE TIMER
When pressed, unit will provide high speed ventilation for 15 minute period. Once the time elapsed the unit will return to its normal function. To move from one time to the other, continue pressing the timer button until you reach the desired time.
DIGITAL HYGROMETER DISPLAY
Shows Indoor Humidity Level This control will not read below 29% RH
DEHUMIDISTAT CONTROL
A Dehumidistat is ideal for use in energy efficient houses where indoor humidity (during the heating season) is higher than outdoor levels. High humidity is a major cause of structure damage and IAQ problems such as mold and mildew. This feature can be turned off when installed in climates that do not require it.
MAINTENANCE LIGHT
When the light is on it indicates it may be time to clean unit. To reset the light, after cleaning the filters, just push the power but­ton and restart the unit. This will turn the light off and reset the clock for your filter check.
POWER
On/Off This function is to turn your unit on or off. To go from the on to off position just press once.
MODES
Select Intermittent, or Continuous Ventilation Modes.
Continuous
This function will exchange outside air with your stale
air.
Intermittent
This function will put your
unit on stand by and can be over ride by timer, air quality sensor, etc
To move from function to the other, continue pressing the mode button until you reach the desired function. This function goes from Continuous to Intermittent.
The LCD (Liquid Crystal Display) indicates the percentage of Relative Humidity in the air surrounding the control and ultimately in the house. Pressing either of the setpoint selectors ( , ) once, will display the desired RH level. The setpoint selection mode is now acti­vated and can be adjusted with either selectors to a newly desired set­point. The LCD will return to the actual RH level display after a few seconds.
Page 18
18
• Install the unit close to the outside wall on which the supply and exhaust hoods will be mounted.
• Have a nearby power supply 120 Volts, 60Hz.
• Have the possibility of mounting the unit to supporting beams.
• Mount the unit as level as possible in order to allow proper condensate drainage.
• For units that have defrost access to a water drain for the condensate of the unit is required.
• Minimize any noise level that would be created by the unit in the living area.
• Have access for future maintenance.
* Note: Unit may also be
placed on a platform, however 3" clearance on bottom is still required for drain (where applicable) and to open access latches.
2 Install the drain hose,
making a “P” trap
INSTALLATION
PRACTICAL TIPS
3 Hang the unit by
slipping a link onto the hanging hooks, making sure the unit is level.
2 Attach a hanging chain
(provided) to each 10 3/4” (19 mm) bolt (provided) in the top 4 corners of the unit and tighten.
1 Place Fastening hooks
on the strapping board or the floor joists.
1 Install the drain nipple.
Installing Drain Line - Units with defrost Through normal operation and during its defrost mode, the ERV may produce some condensation. This water should flow into a nearby drain, or be taken away by a condensate pump. The ERV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point. A “P” trap should be made in the drain line. This will prevent odors from being drawn back up into the unit.
MOUNTING *
LOCATION
The ERV should be located in a conditioned space where it will be possible to conveniently service the unit. Typically the ERV would be located in the mechanical room or an area close to the out­side wall where the weatherhoods will be mounted. Connecting appliances to the ERV It is not recommended, including:
- clothes dryer
- range top
- stovetop fan
- central vacuum system
These appliance may cause lint, dust or grease to collect in the ERV , damaging the unit.
NOTE: Connecting any of these type of appliances to the ERV will "void" your warranty
Page 19
19
3 Push the hood into
the opening. Attach the hood to the outside wall with mounting screws. Repeat the installation procedure for both the Supply and Exhaust hood.
2 Pull the insulated
flexible duct through the opening until it is well extended and straight. Slide the duct’s inner vinyl sleeve over the hood collar and secure, pull the insulation over the duct and then the vapor barrier over the sleeve and secure with duct tape.
4 Using a caulking
gun, seal around both hoods to prevent any leaks.
1 Using the collar of
the outside hood, outline the intake & exhaust holes to be cut. The holes should be slightly larger than the collar to allow for the thickness of the insulated flexible duct. Cut a hole for both the intake and exhaust hoods.
• Decide where your intake and
exhaust hoods will be located.
PRACTICAL TIPS
INSTALLING DUCTS GOING TO / FROM OUTSIDE
A well designed and installed ducting system will allow the ERV to operate at its maximum efficiency. Always try to keep duct runs as short and straight as possible.
See Installation Diagrams for installation examples.
INSTALLING THE DUCTING TO THE WEATHERHOODS
The inner liner of the flexible insulated duct must be clamped to the sleeve of the weath­erhoods (as close to the outside as possible) and to the appropriate port on the ERV. The insulation should remain full and not be squished. The outer liner, which acts as a vapor barrier must be completely sealed to outer wall and the ERV using tape and or caulking. A good bead of high quality caulk­ing (preferably acoustical sealant) will seal the inner flexible duct to both the ERV port and the weatherhood prior to clamping.
To minimize air flow restriction, the flexible insulated duct that connects the two outside weatherhoods to the ERV should be stretched tightly and be as short as possible. Twisting of folding the duct will severely restrict air flow.
Locating the Intake Weatherhood
• Should be located upstream (if
there are prevailing winds) from the exhaust outlet
• At least 4' - 6’ (2m) from the
exhaust weatherhood
• At least 6’ (2m) away from
dryer vents and furnace exhaust ( medium or high effi­ciency furnaces)
• A minimum of at least 6’ (2m)
from driveways, oil fill pipes, gas meters, or garbage con­tainers
• At least 18” (457mm) above
the ground
• At least 3’ (1m) from the cor-
ner of the building
• Do not locate in a garage, attic
or crawl space
Locating the Exhaust Weatherhood
• At least 6’ (2m) from the
ventilation air intake
• At least 18” (457mm) above
ground
• At least 3’ (1m) away from the
corner of the building
• Not near a gas meter, electric
meter or a walkway where fog or ice could create a hazard
• Not into a garage, workshop
or other unheated space
When installing the weather­hood, it’s outside perimeter must be sealed with exterior caulking.
Model Description
FML 8* 8" White Fixed Metal Hoods COM 6P Supply & Exhaust Plastic Hood Kit COM 6M Supply & Exhaust Metal Hood Kit
* Application for Supply or Exhaust
Page 20
CAUTION: In humid climates, it may be "preferable" to have a dedicated ducting system to the house
for the ERV instead of connecting the ERV to the central air-conditioner. Since the central air-conditioner fan must be running continuously to allow the fresh air from the ERV to be properly distributed throughout the house, it may pick up humidity from the cooling coil when it is not operating and re-distribute it to the house, causing excess humidity. This situation may be particularly aggravated if the air-conditioner is over-sized.
20
PRACTICAL TIPS
INSTALLING DUCTS TO / FROM INSIDE
• Building Codes and Combustion Appliance Installation Codes do not allow location of return air Grills or any opening such as a “breathing tee” in an enclosed room with spillage susceptible combustion appliances.
• The fresh air inlet from the ERV needs to respect a minimum distance from the furnace return drop to ensure proper air mixing and temperature at the furnace core. See furnace manufacturer for appropriate specifications.
Direct Connection
• Should you wish to hard duct the supply air directly into the air duct return of the furnace or air handler, remember to check the airflow balance of the ERV with the furnace fan both “on” and “off” to determine that it does not imbalance the ERV more than 10%.
from ERV
For minimum distance See local building codes and practical tips.
To maximize airflow in the ductwork system, all ducts should be kept short and have as few bends or elbows as possible. Forty-five degree are preferred to 90º elbows. Use “Y” tees instead of 90º elbows whenever possible. All duct joints must be fastened with screws or duct sealant and wrapped with a quality duct tape to prevent leakage. Aluminum foil duct tape is recommended. Galvanized ducting from the ERV to the living areas in the house is recommended whenever possible, although flexible duct can be used in moderation when necessary.
SUPPLY AIR DUCTING
In homes without a forced air furnace, fresh air should be supplied to all habitable rooms including, bedrooms and living areas. It should be supplied from high wall or ceiling locations. Grills that diffuse the air comfortably such as Fantech grille {MGE (metal) or PGE (plastic)}s are recommended.To avoid possible noise transfer through the ductwork system, a short length (approximately 12”, 300 mm) of nonmetallic flexible insulated duct should be connected between the ERV and the supply/exhaust ductwork system. The main supply and return lines to/from the ERV should be sized to matched the diameter of the port collar found on the ERV model chosen. Branch lines to the individual rooms may be as small as 4 inches (100 mm), but 5 inch (125 mm) lines are preferred.If the floor is the only option available, then special care should be taken in locating Grills. Areas such as under baseboard heaters will help to temper the air.
Page 21
21
• Choose the location for your Supply and Exhaust Grills - Fantech MGE (metal) or PGE (plastic). The Supply Grills should be located in every habitable room and the Exhaust Grills should be located in the wet rooms.
• A piece of flexible ducting should be placed between the Supply Air In and Out collar of the ERV and the rigid ducting to absorb any noise or vibrations.
• For proper network of ducting, see TYPES OF
INSTALLATIONS.
• The Grills are to be installed on the ceiling or on the wall 6” (152 mm) to 12” (305 mm) from the ceiling.
4 Push the Fantech grill - MGE (metal) or PGE (plastic) - into the optional
mounting collar or directly into installed elbow.
INSTALLING DUCTS TO / FROM INSIDE (CONT'D)
PRACTICAL TIPS
2 Working from a closet, attic or inside your joist wall, run the length of
ducting required for the proper grille location and cut a hole in the drywall. Fasten the mounting collar (optional) to the ducting and fasten the collar to the wall or ceiling with screws.
3 The Fantech grill - MGE (metal) or PGE (plastic) - airflow can be
adjusted by rotating the inside unit. It is recommended that the Grills be completely opened at first and then adjusted later as needed.
Attic or Garage Installation
1 Begin with the duct collar marked “Exhaust Air In”. Slide a short piece
(12”) of flexible duct over the duct collar. Using duct tape, tape the flexible duct to the collar. Run the flexible ducting to the main rigid duct trunk line, which connects to the remainder of the ducts going to and from rooms in the house. Repeat the steps for the “Supply Air Out” on the side of the ERV.
Exhaust Air Ducting
The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur. It is rec­ommended that return air ducts be installed in the bathroom, kitchen, and laundry room. The furnace or air handler return duct may be also used to exhaust from. In this method, the exhaust air is not ducted back from bathrooms, kitchens, etc to the ERV with “dedicated lines”.
Page 22
22
Bedrooms
Fresh Air
Exhaust Air
Central Control - optional
Fresh air to living room
Exhaust
Bathroom
18 inches (460 mm)
6 feet
(1800 mm)
ERV
INSTALLATION EXAMPLES
Example diagram only-duct configuration may change depending on model
It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended. All air movement devices have a performance curve. The amount of air (CFM) that an ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system. Static pressure is a measure of resistance imposed on the blower by length of duct work/number of fittings used in duct work, duct heater etc.
Fully Dedicated System (new construction)
Stale air drawn from key areas of home (bathroom, kitchen, laundry)
Fresh air supplied to main liv­ing areas
ERV must be balanced
Page 23
23
Bedrooms
Fresh Air
Exhaust Air
Furnace thermostat
Exhaust
Bathroom
460 mm
ERV
Central Control - optional
Return Air
ERV Connection
1800 mm
INSTALLATION EXAMPLES (CONT'D)
Example diagram only-duct configuration may change depending on model
Partially Dedicated System
Stale air drawn from key areas of home (bathroom, kitchen, laundry)
Fresh air supplied to main living areas via the forced air system.
ERV must be balanced
DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN (Stale air drawn from key areas of home)
Exhaust Air from various parts of home. i.e. bathrooms (if required), kitchens (if required)
NOTES:
1.Furnace blower may be required to operate when ERV is on to provide good air distribution. (SEE CAUTION ABOVE)
2.Weatherhood arrangement is for drawing purposes only. 6’ (2m) minimum separation recommended.
18” (460mm) above grade minimum.
3.Due to the differences in pressure between the ERV and the equipment it is being connected to, the ERV’s airflow must be confirmed on
site, using the balancing procedure found in the installation manual.
* Unit is normally balanced on HIGH speed with furnace blower ON.
Outdoors
Return Air
1 m
(3’-3”) min.
recommended
Cool Air
Return
* Ducts connection may vary depending on model
CAUTION
In very humid climates, it may be "preferable" to have a dedicated ducting system to the house for the ERV instead of connecting the ERV to the central air-conditioner. Since the central air-conditioner fan must be running continu­ously to allow the fresh air from the ERV to be properly distributed throughout the house, it may pick up humidity from the cooling coil when it is not operating and re-dis­tribute it to the house, causing excess humidity. This sit­uation may be particularly aggravated if the air-condition­er is over-sized.
Page 24
24
INSTALLATION EXAMPLES (CONT'D)
DIRECT CONNECTION of both the ERV SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN
Simplified Installation
Option 1 (Return/Return Method)
• ERV must be balanced
• ERV must be interlocked with the furnace blower
• Check local codes/authority having jurisdiction for acceptance
Note: Option 1 is the pre­ferred/recommended method when doing a simplified installation
NOTES:
1. Furnace blower is required to operate when ventilation from ERV is required. ERV should beinterlocked with fur­nace blower (SEE CAUTION ABOVE)
2. A minimum separation of 39 inches (1m) is recommended between the two direct connections.
3. The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.
4. Weatherhood arrangement is for drawing purposes only. 6’ (2m) minimum separation recommended. 18” (460 mm) above grade minimum.
5. Due to the differences in pressure between the ERV and the equipment it is being connected to, the ERV’s airflow must be confirmed on site, using the balancing procedure found in the installation manual.
* Unit is normally balanced on HIGH speed with furnace blower ON.
Return Air
1 m
(3’-3”) min.
recommended
Cool Air
Return
Outdoors
40” Min.
* Ducts connection may vary depending on model
Example diagram only-duct configuration may change depending on model
CAUTION
In humid climates, it may be "preferable" to have a dedi­cated ducting system to the house for the ERV instead of connecting the ERV to the central air-conditioner. Since the central air-conditioner fan must be running continu­ously to allow the fresh air from the ERV to be properly distributed throughout the house, it may pick up humidity from the cooling coil when it is not operating and re-dis­tribute it to the house, causing excess humidity. This sit­uation may be particularly aggravated if the air-condition­er is over-sized.
Page 25
25
INSTALLATION EXAMPLES (CONT'D)
DIRECT CONNECTION of both the ERV SUPPLY AIR STREAM & EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE
Simplified Installation
Option 2 (Supply/Return Method)
• ERV must be balanced
• ERV must be interlocked with the furnace blower
• Check local codes /authority having jurisdiction for acceptance
Note: Option 1 is the pre­ferred/recommended method when doing a simplified installation
NOTES:
1. Furnace blower may be required to operate when ventilation from ERV is required. The furnace should be interlocked with ERV.
2. The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.
3. Weatherhood arrangement is for drawing purposes only. Six feet (2m) minimum separation recommended. Eighteen inches (460 mm) above grade minimum.
4. Due to the differences in pressure between the ERV and the equipment it is being connected to, the ERV’s airflow must be confirmed on site, using the balancing procedure found in the installation manual.
* Unit is normally balanced on HIGH speed with furnace blower ON.
Return Air
1m
(3’-3”) min.
recommended
Cool Air
Return
Outdoors
1 m
(3’-3”) min.
recom-
mended
* Ducts connection may vary depending on model
Example diagram only-duct configuration may change depending on model
CAUTION
In humid climates, it may be "preferable" to have a dedi­cated ducting system to the house for the ERV instead of connecting the ERV to the central air-conditioner. Since the central air-conditioner fan must be running continu­ously to allow the fresh air from the ERV to be properly distributed throughout the house, it may pick up humidity from the cooling coil when it is not operating and re-dis­tribute it to the house, causing excess humidity. This sit­uation may be particularly aggravated if the air-condition­er is over-sized.
Page 26
26
AIR FLOW BALANCING
CAUTION
• If the unit’s airflows are not properly balanced...
- The unit may not operate at it’s maximum efficiency.
- Energy recovery core damage may occur.
- The unit’s use could cause negative or positive pressure in your home causing cold air to enter or other combustible equipment to backdraft.
- The unit may not defrost properly.
PITOT TUBE BALANCING PROCEDURE
* Pitot tube should be kept at least 12” away from fans elbows and dampers to ensure accurate reading.
• The balancing procedure consists of measuring the exhaust air leaving the system and the supply air entering the system and ensuring that these
two are equal. A deviation of 10% or less is acceptable.
Place pitot tube a minimum of 18" from blower elbows.
Note: Duct connections may
vary, depending on model.
PITOT TUBE
BALANCING PROCEDURE
The following is a method of field balancing an ERV using a Pitot tube, advantageous in situations when flow stations are not installed in the ductwork. Procedure should be performed with the ERV on high speed.
The first step is to operate all mechanical systems on high speed, which have an influence on the ventilation system, i.e. the ERV itself and the forced air furnace or air handler if applicable. This will provide the maximum pressure that the ERV will need to overcome, and allow for a more accurate balance of the unit.
Drill a small hole in the duct (about 3/16), three feet downstream of any elbows or bends, and one foot upstream of any elbows or bends. These are recommended distances but the actual instal­lation may limit the amount of straight duct. The Pitot tube should be connected to a magnehelic gauge or other manometer capable of reading from 0 to 0.25 in. (0-62 Pa) of water, preferably to 3 digits of resolution. The tube coming out of the top of the pitot is connected to the high pressure side of the gauge. The tube coming out of the side of the pitot is connected to the low pressure or reference side of the gauge.
Insert the Pitot tube into the duct; pointing the tip into the airflow. For general balancing it is sufficient to move the pitot tube around in the duct and take an average or typical reading. Repeat this procedure in the other (supply or return) duct. Determine which duct has the highest airflow (highest reading on the gauge). Reduce this airflow using damper. The flows should now be bal­anced. Actual airflow can be determined from the gauge reading.
The value read on the gauge is called the velocity pressure. The Pitot tube comes with a chart that will give the air flow velocity based on the velocity pressure indicated by the gauge. This velocity will be in either feet per minute or meters per sec­ond. To determine the actual airflow, the velocity is multiplied by the cross sectional areas of the duct being measured.
This is an example for determining the airflow in a 6" duct. The Pitot tube reading was 0.025 inches of water. From the chart, this is 640 feet per minute. The 6" diameter (D) duct has cross sectional area (A) of
A = 3.14 x (D/24) 2 A = 3.14 x (6/24) 2 A = 0.196 or about 0.2 ft
2
The airflow is then: 640 ft/min x 0.2 ft2 = 128 cfm
For your convenience, the cross sectional area of some com­mon round duct is listed below:
DUCT DIAM. (inches) CROSS SECTION AREA (sq ft.)
5 0.14 6 0.20 7 0.27 8 0.35
The accuracy of the airflow reading will be affected by how close to any elbows or bends the readings are taken. Accuracy can be increased by taking an average of multiple readings as outlined in the literature supplied with the Pitot tube.
M
a g n
e h
e
l i c
c
i
l
e
h
e
n
g
a
M
Page 27
27
AIR FLOW BALANCING (CONT'D)
1 For this flow measuring station, cut
the duct and place the flow measuring station between each station. Make sure that the flow measuring station’s air direction arrow points in the direction of the airflow. Secure the flow measuring station with duct tape.
2 Before taking the reading, make
sure that the magnehelic gauge is level and at 0. Refer to the flow measuring station’s chart to determine your unit’s airflow velocity.
3 Adjust the damper until you reach
the desired velocity.
(damper should be 18” from grid)
Measure
here
Measure here
18” (457 mm)
18”
(457 mm)
• To avoid airflow turbulence and incorrect readings, the airflow velocity should be measured on steel ducting a minimum of 18” (457 mm) from the unit or elbow and before any transition.
AIRFLOW STATION (GRID) METHOD
MAINTENANCE
The filters (4) need to be checked and cleaned every three months or when they appear dirty. Wash in warm sudsy water (mild detergent) or use a soft brush vacuum. The filters should be replaced when they can no longer be cleaned properly.
PRACTICAL TIPS
• To prevent electrical shock, check that the unit is unplugged before doing any repairs or maintenance.
• A yearly inspection is recommended to ensure the efficiency and trouble-free use of your system. Run through the system and verify the different operating modes.
ENERGY RECOVERY CORE
FILTERS
The motor - The motors are factory balanced and lubri­cated for life. They require no maintenance.
The unit - The inside of the unit should be vacuumed yearly. Be careful not to damage any of the mechan­ical components and electri­cal connections.
CAUTION MAKE SURE UNIT IS UNPLUGGED BEFORE ATTEMPTING ANY MAINTENANCE WORK
The following components should also be inspected regularly and well maintained.
Clean the Enthalpic core annually or as needed with a vacuum cleaner. Use a soft brush attachment. Make sure the filters on the unit are cleaned. Failure to clean or use filters may damage the Enthalpic core resulting in a void WARRANTY.
Note:
The use of the Enthalpic core in adverse environment conditions such as dust, oil mist, exces­sive kitchen grease, corrosive fumes, organic solvents, paint or any other harmful chemicals can damage the Enthalpic core and in such void the warranty.
All filters (4) need to be checked regularly
The drain pan and drain line - Units with drain lines should have their line and connec­tion checked regularly.
Outside hoods - The outside hoods need to be checked every season to make sure there are no leaves or insects blocking the airflow. Check regularly that there are no pollutants near the intake hood. Make sure they are clear of any snow accumulation during the win­ter months.
Page 28
28
TROUBLESHOOTING
Solutions
CausesProblem
Dehumidistat control is set too low
Dehumidistat control is set too high
Sudden change in temperature
Storing too much wood for heating
Dryer vent exhaust is inside home
Poor air circulating near windows
Well sealed basement door is closed
Improper adjustment of dehumidistat control
Air is too dry
Air is too humid
Persistent condensation on window
Increase the desired level of humidity. Change ventilation mode from continuous mode to standby.
Balance ERV
Reduce the desired level of humidity. Combine this step with use of con­tinuous exchange mode.
Wait until outside temperature stabilizes (winter). Heating will also improve situation.
Store a majority of your wood outside. Even dried, a cord of wood con­tains more than 20 gallons of water.
Arrange outside vent for dryer.
Open curtains or blinds. Bay or bow windows may require mechanical method.
Balance ERV
Open the door or install a grill on the door.
Reduce the desired level of humidity. Combine this with the use of con­tinuous exchange mode.
Balance ERV
-Clean exterior hoods or vents
-Remove and clean filter
-Remove and clean core
-Check and open Grills
-Have electrician check supply voltage at house
-Check duct installation
-Increase the speed of the ERV
-Have contractor balance ERV
-Locate the Grills high on the walls or under the baseboards, install ceil­ing mounted diffuser or Grills so as not to directly spill the supply air on the occupant (eg. Over a sofa)
-Turn down the ERV supply speed. A small duct heater (1kw) could be used to temper the supply air
-Placement of furniture or closed doors is restricting the movement of air in the home
-If supply air is ducted into furnace return, the furnace fan may need to run continuously to distribute ventilation air comfortably
-Note: minimal frost build-up is expected on cores before unit initiates defrost cycle functions
-Have HVAC contractor balance the ERV
-Tape and seal all joints
-Tape any holes or tears made in the outer duct covering
-Ensure that the vapor barrier is completely sealed.
-1/4” (6mm) mesh on the outside hoods is plugged
-Filters plugged
-Core obstructed
-House Grills closed or blocked
-Dampers are closed if installed
-Poor power supply at site
-Ductwork is restricting ERV
-Improper speed control setting
-ERV airflow improperly balanced
Poor Air Flows
-Poor location of supply Grills, the airflow may irritate the occupant
-Outdoor temperature extremely cold
Supply air feels cold
-ERV air flows are improperly balanced
-Malfunction of the ERV defrost system
ERV and / or Ducts Frosting up
-Incomplete vapor barrier around insulated duct
-A hole or tear in outer duct covering
Condensation or Ice Build Up in Insulated Duct to the Outside
ERV out of balance
ERV out of balance
ERV out of balance
Page 29
29
ELECTRICAL CONNECTIONS
2 wires
2 wires
3 wires
Caution:
• Never connect a 120 volt AC circuit to the terminals of the Accessory Control Contacts. Only use the low voltage class 2 circuit of the furnace
blower control.
For a Fur
nace Connected to a
Cooling System:
• On some older thermostats,
energizing the R and G
terminals at the furnace has
the effect of energizing Y at
the thermostat and thereby turning on the cooling system. If you identify this type of thermostat, you must use the “Alternate Furnace Interlock Wiring”.
PRACTICAL TIPS
ELECTRICAL CONNEC­TION TO A FURNACE
Standard Accessory Control Contact
Alternate Accessory Control Contact
* Wiring diagram of complete unit
inside of access panel
Found on electrical box
3 position mode selection switch
Custom defrost mode jumper selection
Accessory Control Contact
(Open & Closes contact when HRV/ERV is ON/OFF)
Diagnostic LED
U
- +
Air Quality
Sensor
Dehumidistat
2 wires
15-minute timer
(up to 5 timers)
Mechanical
Crank Timer
2 wires
and /
or
EDF5 or EDF2 (not shown)
and /
or
(1 only)
Dehumidistat
On/Off 4 wires
TWO WIRE heating only
FURNACE
24-VOLT
TERMINAL BLOCK
FOUR
WIRE
TWO WIRE heating only
FURNACE
24-VOLT
TERMINAL BLOCK
Standard Furnace Interlock Wiring
THERMOSTAT
TERMINALS
RG
FOUR WIRE
W
W
R
G
C
Y
Y
TWO WIRE
Alternate Furnace Interlock Wiring
THERMOSTAT
TERMINALS
RG
W
W
R
WIRE JOINT
G
C
Y
Y
TWO
WIRE
COOLING SYSTEM
COOLING SYSTEM
HRV
ELECTRONIC BOARD
HRV
ELECTRONIC BOARD
Page 30
30
ELECTRICAL WIRING DIAGRAMS
SER 1504, SER 1504N, SER 2004 & SER 2004N
Page 31
31
ELECTRICAL WIRING DIAGRAMS
SER 3204D
SER 3204N
Page 32
Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, components and specifications to maintain their technological leadership position.
Article #: 301096
Item #: 401455
Rev Date: 020905
United States
1712 Northgate Blvd.,
Sarasota, FL. 34234
Phone: 800.747.1762; 941.309.6000
Fax: 800.487.9915; 941.309.6099
www.fantech.net; info@fantech.net
Canada
50 Kanalflakt Way,
Bouctouche, NB E4S 3M5
Phone: 800.565.3548; 506.743.9500
Fax: 877.747.8116; 506.743.9600
www.fantech.ca; info@fantech.ca
Loading...