Faber 1200 CFM User Manual

Version 05/06 - Page 1
Observe all governing codes and ordinances. Proper installation is your responsibility. Make sure you have everything necessary for correct installation. It is the responsibility of the installer to comply with the clearances specified.
To avoid damage to motor bearings and impellers, keep drywall spray, construction dust, etc. away from the remote blower.
Before installing remote blower, read the installation instructions for the vent system that will be used in conjunction with this remote blower.
Important
READ AND SAVE THESE INSTRUCTIONS
The installer must leave these instructions with the homeowner. The homeowner must keep these instructions for future reference and for local electrical inspectors' use.
Care of your remote blower
Disconnect power supply and lock out service panel before cleaning or servicing. To clean, remove cover and vacuum blower and housing, being careful not to damage blower wheel. The motor is permanently lubricated. Do not oil or disassemble.
Electrical requirements
Important: Observe all governing codes and ordinances. It is the customer’s responsibility:
• To contact a qualified electrical installer.
• To assure that the electrical installation is adequate and in conformance with:
National Electrical Code, ANSI/NFPA 70 — latest edition*, or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No.0-M91 - latest edition** and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the ground path is adequate. Do not ground to a gas pipe. Check with a qualified electrician if you are not sure remote blower is properly grounded. Do not have a fuse in the neutral or ground circuit.
A 120-volt, 60-Hz, AC-only supply wired for 15 amp service is required.
The blower motor must be connected with copper wire only.
The remote blower must be connected to the downdraft vent system or rangehood wiring as described in the downdraft vent system or rangehood instructions for connecting the remote blower motor wiring. Flexible armored or nonmetallic cable must be used. A U.L./CSA-listed strain relief must be provided at each end of the power supply cable. Wire sizes must conform to the requirements of the National Electrical Code ANSI/NFPA 70 — latest edition* or Canadian Electrical Code, C22.1 and C22.2 No. 113-M1984 (or latest edition),** and all local codes and ordinances. 14 gauge wire (minimum) is recommended.
Remote Blower (1200 CFM) Installation Instructions Use & Care Manual
You can be killed or seriously injured if you don’t follow instructions.
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable Codes and Standards, including Fire Rated Construction. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. Ducted fans must always be vented to the outdoors.
Use this unit only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on ac­cidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
WARNING - TO REDUCE THE RISK OF SHOCK: This fan must be installed with an isolating wall control/
switch.
CAUTION: For General Ventilating Use Only. Do Not Use To Exhaust Hazardous or Explosive Materials and Vapors.
To reduce the risk of fire, use only metal ductwork.
This unit must be grounded.
This unit is suitable for use with solid-state speed controls.
For Residential use ONLY
Copies of standards listed may be obtained from:
* National Fire Protection Association One Batterymarch Park Quincy, Massachusetts 02269
** CSA International 8501 East Pleasant Valley Road Cleveland, Ohio 44131-5575
WARNING
!
CAUTION – To reduce risk of fire and to properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces within walls or ceilings or into attics, crawl spaces, or garages”
Version 05/06 - Page 2
Venting requirements
Maximum length of ductwork
Duct length is given as a general reference only. For a longer duct run, or smaller duct system, contact a qualified and trained duct installer. Check with local codes for makeup air requirements, if any. It is recommended that you use round duct instead of rectangular duct, especially if elbows are required. If rectangular duct is required, if should be transitioned to 10" (25.4 cm) round duct as soon as possible.
For best performance, use no more than three 90° elbows. If more than one elbow is used, make sure that there is a minimum of 24 inches of straight duct between any two elbows. Do not install two elbows together.
55 feet for 10" round ductwork - count 90° elbows as 5 feet and 45° elbows as 3 feet.
Begin the installation
1. Discard any cardboard packaging from the blower wheel.
2. Remove wiring box cover and screws.
3. Attach an appropriate U.L./CSA-listed strain relief in the
knockout.
Note: For most installations, it is recommended that the strain relief be installed so that it can be tightened from inside the remote blower housing.
4. Reattach the wiring box cover loosely. It will be removed again later.
Follow the instructions on the next page for your type of installation
Determine which ducting method is best for your application. Duct system can extend either through the wall or the roof. Locate the remote blower so that the length of the duct system and the number of elbows is kept to a minimum to provide efficient performance. Where possible, remote blower should be centered between wall studs or roof rafters. The size of the duct system should be uniform. Do not install two elbows
together.
Use duct tape to seal all joints in the duct system. Use caulking to seal remote wall or floor opening around the cap. Flexible duct is not recommended. It creates back pressure/air turbulence and greatly reduces performance. Make sure there is proper clearance within the wall or floor for exhaust duct before making cutouts. Avoid pipes, wires, or other duct systems that may be running through the wall. Do not cut a joist or stud unless absolutely necessary. If a joist or stud must be cut, then a supporting frame must be constructed.
The remote blower carton contains a duct collar plate.
• The duct collar plate attaches to the front of downdraft duct system plenums so that the 10" (25.4 cm) round duct can be attached to the downdraft duct system.
Make sure that there is enough space for any vent transitions that may be needed between the remote blower and the connecting vent system. For optimum performance, locate any necessary vent transitions nearest to the rangehood or downdraft that will be used with this power system. This remote blower requires a separate U.L./CSA approved wiring cable that should be installed at the same time the vent system is being installed.
Install this side of the fan facing an unoccupied space.
Dimensional diagram
You can be killed or seriously injured if you don’t follow instructions. Excessive Weight Hazard Use two or more people to move and install remote blower. Failure to do so can result in back or other injury.
WARNING
MAKE SURE THAT THE DISCHARGE END OF THE REMOTE BLOWER FACES AWAY FROM THE DIRECTION OF PREVAILING WINDS.
!
Version 05/06 - Page 3
1. Choose a location on an outside wall where no wall studs, wires, pipes, etc. run through the opening area. A minimum distance of 24" (61 cm) from remote blower to ground may be required depending on local code. Make sure to leave room for anticipated snowfall in your region.
2. Drill the guide hole in the center of the 11" (27.9 cm) diameter opening area.
3. Mark a 27-1/2" x 34" (69.9 x 86.4 cm) rectangle on wall as indicated in FIGURE 1.
4. Cut a rectangular hole in the siding only. Do not cut sheathing. Nail down all siding ends.
5. Mark an 11" (27.9 cm) diameter circle around guide hole as indicated in FIGURE 1. Mark center of the 1-1/4" (or 3.0 cm) diameter hole for electrical wiring as indicated in FIGURE 1.
6. Cut 11" (27.9 cm) diameter hole in sheathing. Drill the 1-1/4" (or 3.0 cm) diameter electrical wiring hole.
7. Run a large bead of caulk on the back side of the housing along the outer edge.
8. Center the remote blower ring in the 11" (27.9 cm) diameter hole, making sure that the 1-1/4" (or 3.0 cm) diameter electrical wiring hole lines up with the hole in the wiring box.
9. Attach the remote blower to wall using screws appropriate for your installation. All four holes in the back panel must be filled to prevent moisture that may get inside the remote blower housing from leaking into the home.
10. Seal all around the mounting screw heads with caulk.
11. Go to “Make the duct & electrical connections”, Page 4.
Wall installations
Roof installations
FOR FLAT ROOF INSTALLATIONS SEE NEXT PAGE
1. Choose location on rear slope of roof that minimizes vent run.
Avoid obstacles such as TV leads, electric lines, etc. If remote blower top is level with roof peak, it will not be seen from street. Remember this location as you work from inside the attic.
2. Mark a point half-way between the rafters and drill a guide hole at this point.
3. From the outside, using the guide hole as a starting point, mark the rectangular cut-out as indicated in FIGURE 2. Remove ONLY the shingles in THIS AREA.
4. Mark an 11" (27.9 cm) diameter circle around guide hole as indicated in FIGURE 2. Mark center of the 1-1/4" (or 3.0 cm) diameter hole for the electrical wiring as indicated in FIGURE 2.
5. Cut out the roof boards along the 11" (27.9 cm) diameter circle. Drill the 1-1/4" (or 3.0 cm) diameter electrical wiring hole.
6. Remove roofing nails from the upper two-thirds of the shingles to allow the back flashing sheet on the remote blower housing to fit under them.
7. Center the remote blower ring in the 11" (27.9 cm) diameter hole, making sure that the 1-1/4" (or 3.0 cm) diameter electrical wiring hole lines up with the hole in the wiring box.
8. Attach the remote blower to roof or frame using screws appropriate for your installation. All four holes in the back panel must be filled to prevent moisture that may get inside the remote blower housing from leaking into the home.
9. Seal all the shingles around the remote blower housing, flashing sheet, and mounting screw heads or frame with roofing cement. Top and side flanges of the back plate may be covered with trim. It is recommended that electrical connection be made and checked first. Do not block the vent grill opening at the bottom of the trim. Doing so will decrease blower performance.
Figure 1- Wall installations Figure 2 - Roof installations
Loading...
+ 5 hidden pages