FAAC SPX-5501 User Manual

SPX-5000 Series
Operations Manual
Suprex® Reader Extender - RF Wireless Interface
SPX-5521 900 Mhz
SPX-5601
2.4GHz
SPX-6601
2.4GHz
2.4GHz Repeater
IOX-7621
2.4GHz
EXP-2000
SPX-5000_MAN_082112
This manual covers the operation and setup of the Cypress Suprex RF SPX-5000 series wireless units.
Cypress Suprex SPX-5000 Series Overview
Physical
Weatherproof Enclosure - ABS - IP65 SPX units 6.75” x 4.75” x 2.10 (Each unit) - IOX units 7.25x 5.75x 3
Temp
Storage(-55˚C to + 150˚C) - Operating(-40˚C to +80˚C)
Humidity
95% (non-condensing)
Power
Input
Unreg Input 8 to 16 VDC* @ 500mA Max Unreg Input 8 to 24 VDC @ 500mA Max ( IOX-7000 )
Power
Output
+5VDC @100mA ( except IOX-7000 )
Data I/O
Interface
Reader -Wiegand, Strobed (Clock & Data), F/2F LED - 0 - 30V
(220Vdc 30W (resistive) 1A)
Max Switching (250Vac 37.5VA 1A)
Relays
(30Vdc 1A (resistive), 1 x 10
5
operations at 20o C
Relays
Running Spec with load 125Vac .3A (resistive), 1 x 10
5
operations at 20o C
Overview:
The SPX-5000 series of RF Wireless solutions provides a wireless bridge from Card Readers with gates or door hardware to most access control manufacturers panels. The SPX or Suprex® products include both the remote ( Door/Gate ) unit and the central ( AC Panel ) unit. In the case of the SPX-5000 series of wireless products optional repeaters / extenders are also available.
Features:
-- Includes complete solution with remote ( reader/gate/door ) and central ( panel ) interface.
-- Service mode for setup and configuration.
--“Quiet” protocol to conserve bandwidth and power
-- Field configurable reader formats
-- Multifunction indicator for determining operational status of the unit
-- Auxiliary I/O connections available for Door/Gate/Panel status signaling.
-- Multiplexing of RF bridge providing for additional door/gate on a single RF link.
-- Economical expansion capabilities using Suprex Lynk technology
RF Specifications:
2.4GHz or 900Mhz frequency AES Encryption upon request
Electrical and Mechanical Specifications
Cypress Computer Systems, Inc. Lapeer, MI 48446 www.cypresscomputer.com
© 2012 Cypress Computer Systems Inc.
SPX-5521
915 Mhz - extender 10000 ft range
Wiegand or Clock & Data
816684003387
RPT-5551
915 Mhz - repeater 1000 ft range
N/A
816684003394
SPX-5601
2.4GHz - extender 2000 ft range
Wiegand or Clock & Data
816684003219
SPX-5621
2.4GHz - extender 10000 ft range
Wiegand or Clock & Data
816684003189
SPX-6601
2.4GHz - extender 2000 ft range
RS-232/RS-485
816684004599
RPT-5651
2.4GHz - repeater 1000 ft range
N/A
816684003172
IOX-7601
2.4GHz - extender 2000 ft range
N/A - Relays only
816684004551
810121416805535-40
Ambient Temperature
(Degrees Celsius)
Supply Voltage
Temperature/Voltage de-rating curve
Suprex® RF Part Numbers
Part Number! Description! ! ! ! Interface !! UPC
The Suprex units should be operated with a filtered 12 Volt nominal DC supply. Any voltage between 8 and 16 volts can be utilized by following the temperature /voltage derating curve. Voltage should not exceed 16 VDC under normal operating conditions.
Switch
6 7 8
0
1 x
2 x
3 x x
4 x
5 x x
6 x x
7 x x x
Wiegand
Wiegand / No Filter
Strobed Rising Edge (MR-5)
Strobed Rising Edge (Dorad0 644)
Strobed Rising (Mag-Tek)
Strobed Falling Edge
Reserved
F2F
x = ON
1234567
8
Dip switch #4 is ON
-Disable Pullup resistors
Dip switch #4 is OFF
-Enable Pullup resistors
Switch
6 7 8
0
1 x
2 x
3 x x
4 x
5 x x
6 x x
7 x x x
Wiegand
Wiegand / No Filter
Strobed Rising Edge (MR-5)
Strobed Rising Edge (Dorad0 644)
Strobed Rising (Mag-Tek)
Strobed Falling Edge
Reserved
F2F
x = ON
1234567
8
Dip switch #4 is ON
-Enable Pullup resistors
Dip switch #4 is OFF
-Disable Pullup resistors
1 - 8 to 16 VDC In 2 - Ground
Status LED
1 - exp (+) 2 - exp (-) 3 - +5 VDC out 4 - Prog Res 4 5 - Prog Res 3 6 - LED In 7 - D1/Data out 8 - D0/Clk out
1 - 8 to 16 VDC In 2 - Ground
Status LED
1 - exp (+) 2 - exp (-) 3 - +5 VDC out 4 - R4 5 - R3 6 - LED out 7 - D1/Data In 8 - D0/Clk In
External connections and DIP Switch Settings
SPX-5000
Central
SPX-5000
Remote
1- Relay 4 N.O. 2- Relay 4 Com 3 - Relay 4 N.C. 4 - Relay 3 N.O. 5 - Relay 3 Com 6 - Relay 3 N.C. 7 - Ground 8 - Aux out 9 - R2 in 10 - R1 in
1- Relay 2 N.O. 2- Relay 2 Com 3 - Relay 2 N.C. 4 - Relay 1 N.O. 5 - Relay 1 Com 6 - Relay 1 N.C. 7 - Ground 8 - Aux in 9 - Not used 10 - Not used
Central Unit Settings
DIP Switch #1 ON
-Service Mode DIP Switch #1 OFF
-Run Mode
Remote Unit Settings
DIP Switch #1 ON
-Service Mode DIP Switch #1 OFF
-Run Mode
DC
Ground
Ground
Power
Supply
Access Control
Panel
Quick Reference For Typical Connections
SPX-5000 Series Central
+8 to +16 VDC
Diagnostic LED
LED In D1/Data Out D0/Clock Out
R1 Input Controls Strike on Remote
R1 IN
DC
Power
Supply
Card
Reader
See page 10 for other strike control options
SPX-5000 Series Remote
+8 to +16 VDC
Diagnostic LED
R1 N.O. R1 Com R1 N.C.
LED Out D1/Data In D0/Clock In
Door
Strike
Output
Typical RF installation with repeater
ACS
ACS
SPX-5000R (1)
SPX-5000C (1) RPT-5X51
Typical RF installation - line of sight
SPX-5000C (1)
Typical RF installation ­expansion modules
ACS
SPX-5000C (1)
EXP-2000C (2)
SPX-5000R (1)
EXP-2000R (2)
EXP-2000R (3)
SPX-5000R (1)
Wiegand connection
Card reader
EXP-2000C (3)
RS-485 multi-drop
Control and I/O
Loading...
+ 14 hidden pages