hereby declares that for the partly completed machinery:
Description:Barrier
Model:B614
The essential requirements of the Machinery Directive 2006/42/EC (including all applicable amendments) that have been applied and
fulfilled are as follows:
and that the relevant technical documentation has been compiled in compliance with part B of Annex VII.
Furthermore, the following harmonised standards have been applied:
And also undertakes to transmit, in response to a reasoned request by the national authorities, relevant information on the partly
completed machinery by mail or e-mail.
Finally, the manufacturer declares that the above-mentioned partly completed machinery must not be put into service until the final
machine in which it is to be incorporated has been declared compliant with the requirements of the above-mentioned Machinery
Directive 2006/42/EC.
Bologna, Italy, 01-07-2018
CEO
A. Marcellan
ENGLISH
Translation of the original instructions
B614 1 732998 - Rev.A
CONTENTS
EU Declaration of conformity ........................... 1
Declaration of incorporation for partly completed machine-
ry ..................................................... 1
1. INTRODUCTION TO THIS INSTRUCTIONS MANUAL .... 4
1.1 Meaning of the symbols used ......................... 4
2. SAFET Y RECOMMENDATIONS ......................... 6
1 Foundation for barrier in maximum configuration .....60
2 Balancing system ...................................61
B614 3 732998 - Rev.A
Translation of the original instructions
1. INTRODUCTION TO THIS INSTRUCTIONS MANUAL
This manual provides the correct procedures and
requirements for installing B614 and maintaining it
in a safe condition.
When drafting the manual, the results of the risk
assessment conducted by FAAC S.p.A. on the entire
product life cycle have been taken into account in
order to implement effective risk reduction measures.
The following stages of the life cycle of the product
have been considered:
- Delivery/handling
- Assembly and installation
- Set-up and commissioning
- Operation
- Maintenance/troubleshooting
ENGLISH
- Disposal at the end of the product’s life cycle
Risks arising from installation and using the product
have been taken into consideration; these include:
- Risks for the installation/maintenance technician
(technical personnel)
- Risks for the user of the automation system
- Risks to product integrity (damage)
In Europe, the automation of a barrier falls under the
Machinery Directive 2006/42/EC and the corresponding harmonised standards. Anyone automating a
barrier (new or existing) is classified as the Manufacturer of the Machine. They are therefore required by
law, among other things, to carry out a risk analysis
of the machine (automatic barrier in its entirety) and
take protective measures to fulfil the essential safety
requirements specified in Annex I of the Machinery
Directive.
Translation of the original instructions
FAAC S.p.A. recommends that you always comply
with the EN 12453 standard and in particular that you
adopt the safety criteria and devices indicated, without
exception, including the dead-man function.
This manual also contains general information and
guidelines, which are purely illustrative and not exhaustive, in order to facilitate the activities carried out by
the Manufacturer of the Machine in all respects with
regard to carrying out the risk analysis and drafting the
instructions for use and maintenance of the machine. It
should be clearly understood that FAAC S.p.A. accepts
no liability for the reliability and/ or completeness of
the above instructions. As such, the manufacturer of
the machine must carry out all the activities required
by the Machinery Directive and the corresponding
harmonised standards on the basis of the actual
condition of the locations and structures where the
product B614 will be installed, prior to commissioning
the machine. These activities include the analysis of all
the risks associated with the machine and subsequent
implementation of all safety measures intended to
fulfil the essential safety requirements.
This manual contains references to European stan-
dards. The automation of a barrier must fully comply
with any laws, standards and regulations applicable in
the country where installation will take place.
Unless otherwise specified, the measurements pro-
Li
vided in the instructions are in mm.
1.1 MEANING OF THE SYMBOLS USED
1 Symbols: notes and warnings on the instructions
WARNING ELECTRIC SHOCK HAZARD - The operation
or stage described must be performed following the
instructions supplied and applicable safety regulations
F
WARNING, PERSONAL INJURY HAZARD OR RISK OF
DAMAGE TO COMPONENTS - The operation or stage
described must be performed following the supplied
!
instructions and applicable safety regulations
WARNING - Details and specifications that must be
complied with in order to ensure that the system
i
operates correctly.
RECYCLING and DISPOSAL - Components and structural
materials, batteries and electronic components must not
be disposed of together with household waste. They must
be taken to authorised disposal and recycling centres
For manual lifting, there should be 1 person for every
20 kg to be lifted
PAGE E.g.: 6 see Page 6
FIGURE E.g.: 1-3 see Figure 1 - item 3
TABLE E.g.: 1 see Table 1
§CHAPTER/SECTION E.g.: §1.1 see section 1.1
APPENDIX E.g.: 1 see Appendix 1
Automatic operation - automation locked
Manual operation - automation unlocked
B614 4 732998 - Rev.A
2 Symbols: safety signs (EN ISO 7010)
GENERAL HAZARD - Risk of personal burns or damage
to the parts
3 Symbols: personal protective equipment
Personal protective equipment must be worn to protect against hazards (e.g. crushing, cutting, shearing
etc.):
RISK OF ELECTRIC SHOCK - Risk of electric shock from
live parts
RISK OF CRUSHING, MUSCULAR - SKELETAL PROBLEMS
- Risk of crushing or muscular and skeletal injury when
lifting heavy loads
RISK OF BURNS OR BURNING - Risk of burns or burning
because of very hot parts.
RISK OF CRUSHING - Risk of crushing hands/feet due
to heavy parts
RISK OF CRUSHING HANDS - Risk of crushing hands
due to moving parts
RISK OF CUTS/AMPUTATION/SPEARING - Risk of cuts
due to sharp parts or the use of sharp implements (drill)
RISK OF SHEARING - Risk of shearing due to moving
parts
RISK OF IMPACT/CRUSHING/SHEARING - Risk of impact,
crushing or shearing due to moving parts
Obligation to wear head protection helmet
Obligation to wear safety footwear
Obligation to wear mask/goggles to protect the eyes
from the risk of fragments due to the use of drill or
welding machine
Obligation to wear work gloves
ENGLISH
Obligation to wear ear protectors
Obligatory use of work clothes without parts that could
become caught in moving parts
Translation of the original instructions
RISK OF OBJECTS FALLING FROM ABOVE - Risk of impact
due to objects falling
RISK OF TRIPPING - Risk of tripping due to raised
sections above 5 mm.
RISKS FROM BATTERIES AT THE END OF THEIR LIVES Risk to the environment and health posed by batteries
at the end of their lives due to fluid escaping
RISK OF FORKLIFT TRUCK IMPACT - Risk of being hit by
or colliding with forklift trucks
B614 5 732998 - Rev.A
2. SAFETY RECOMMENDATIONS
This product is placed onto the market as “partly
completed machinery”, therefore it cannot be commissioned until the machine in which it will be incorporated has been identified and declared to conform
to the Machinery Directive 2006/42/EC by the actual
Manufacturer.
Incorrect installation and/or incorrect use of the
!
product might cause serious harm to people. Read
and comply with all the instructions before starting
any activity on the product. Keep these instructions
for future reference.
Perform installation and other activities adhering to
ENGLISH
Translation of the original instructions
the sequences provided in the instructions manual.
Always comply with all the requirements contained in
the instructions and warning tables at the beginning
of the paragraphs. Always comply with the safety
recommendations.
Only the installer and/or maintenance technician
is authorised to work on the automation components. Do not modify the original components
in any way.
Close off the work site (even temporarily) and prevent
access/transit. EC countries must comply with the
legislation that transposes the European Construction
Site Directive 92/57/EC.
The installer is responsible for the installation/testing
of the automation and for completing the Register of
the system.
The installer must prove or declare to possess technical
and professional proficiency to perform installation,
testing and maintenance activities according to the
requirements in these instructions.
2.1 INSTALLER SAFETY
Installation activities require special work conditions
to reduce to the minimum the risks of accidents and
serious damage. Furthermore, the suitable precautions must be taken to prevent risks of injury to persons
or damage.
The installer must be in good physical and mental
!
condition, aware of and responsible for the hazards
that may be generated when using the product.
The work area must be kept tidy and must not be
left unattended.
Do not wear clothes or accessories (scarves, bracelets,
etc.) that may get caught in moving parts.
Always wear the personal protective equipment recommended for the type of activity to be carried out.
The required level of workplace lighting must be equal
to at least 200 lux.
Operate CE marked machinery and equipment in compliance with the manufacturer's instructions. Use
work instruments in good conditions.
Use the transport and lifting equipment recommended in the instructions manual.
Use safety-compliant portable ladders of adequate
size, fitted with anti-slip devices at the top and bottom, equipped with retainer hooks.
B614 6 732998 - Rev.A
2.2 TRANSPORT AND STORAGE
3
Kg ____
Follow the instructions on the packaging during
!
handling. Two people must move the package. Use
the HANDLES.
4 Symbols: markings on packaging
Read the instructions
This way up indication: do not turn upside down
Store away from water and humidity
Maximum number of stackable pallets
PALLETISED SUPPLY
RISKS
PERSONAL PROTECTIVE EQUIPMENT
Use a forklift or pallet truck, fol-
!
lowing safety regulations to avoid
the risk of impacts or collisions.
ENGLISH
Maximum number of stackable packages
Percent storage humidity
Storage temperature
CE marking
Wear work gloves
Wear safety footwear
20 kg is the MAX weight one person can lift
Weight of package
SINGLE PACKAGE
RISKS
PERSONAL PROTECTIVE EQUIPMENT
For manual lifting, there should
be 1 person for every 20 kg to
be lifted.
STORAGE
Store the product in its original packaging, in closed
and dry premises, protected from the sun and free
from dust and aggressive substances. Protect from
mechanical stress. If stored for more than 3 months,
regularly check the condition of the components and
the packaging.
- Storage temperature: 5°C to 30°C.
- Percentage of humidity: 30% to 70%.
Translation of the original instructions
B614 7 732998 - Rev.A
2.3 UNPACKING AND HANDLING
RISKS
PERSONAL PROTECTIVE EQUIPMENT
For manual lifting, there should be 1 person for every
20 kg to be lifted.
Two people must move the package. Use the handles.
ENGLISH
Never manage the barrier by holding the board holder.
!
1. Carefully set the package down on the ground.
2. Cut the packaging to open it right up and remove all
the packaging material.
3. Stand the barrier on the base.
Check that all components are present and intact
Li
1.
4. Dispose of the packaging materials.
The packaging materials (plastic, polystyrene etc.)
!
must not be left within reach of children as they are
potential sources of danger.
When you have finished with them, dispose of the
packaging in the appropriate containers, as per
applicable waste disposal regulations.
2.4 DISPOSAL OF THE PRODUCT
After having dismantled the product, dispose of it
in compliance with the current waste disposal regulations.
Components and structural materials, batteries and
electronic components must not be disposed of
together with household waste. They must be taken
to authorised disposal and recycling centres.
Translation of the original instructions
1 B614 barrier body
2 Top cover
3 Installation accessories
4 Instruction manual
5 Risk signalling
1
B614 8 732998 - Rev.A
2
3
4
5
1
3. B614
3.1 INTENDED USE
The B614 barriers are designed for vehicular access
control in residential buildings/apartment complexes.
To move the beam manually, follow the instructions
for manual functioning.
Any other use that is not expressly specified in these
!
instructions is prohibited and could affect the integrity of the product and/or represent a source of danger.
3.2 LIMITATIONS OF USE
Comply with the limitations on frequency of use listed
in the technical data section.
The B614 requires the use of a specific FAAC beam
that conforms to the dimensions indicated in this
manual. Only the FAAC accessories indicated in this
manual should be installed on the beam.
The B614 requires the use of a FAAC spring that is
adequate for counterbalancing the weight of the beam
and the relative accessories.
The barriers with exclusively vehicle access control
must be fitted with suitable visible signs prohibiting
foot traffic. A separate route for foot traffic outside
the range of the beam must be provided and properly
indicated.
If foot traffic cannot be ruled out, the barrier falls within
the scope of the EN 12453 standard.
The presence of weather conditions such as snow, ice
and strong wind, even occasional, could affect the
correct operation of the automation, the integrity of
the components and be a potential source of danger
(see § Emergency use). The limitations of use of the
B614 in wind is equivalent to grade 10 on the Beaufort
Scale (max. speed: 102 km/h).
The installation must be visible during the day and
at night. If it is not, appropriate solutions must be
provided to make the fixed and moving parts visible
(light kit on the beam).
The B614 must be connected to a FAAC electronic
board as indicated in this manual ( Technical characteristics).
Implementing the automation requires the installation of the necessary safety devices, identified by the
installer through an appropriate risk assessment of
the installation site.
ENGLISH
Translation of the original instructions
B614 9 732998 - Rev.A
3.3 UNAUTHORISED USE
- Uses other than the intended use are prohibited.
- It is prohibited to install the automation system
outside of the limits specified in the Technical Data
and Installation Requirements sections.
- It is forbidden to use B614 in a constructional
configuration other than the one provided by the
manufacturer.
- No component part of the product may be mo-
dified.
- It is prohibited to install the automation system
on escape routes.
- It is prohibited to install the automation system in
environments in which there is a risk of explosion
and/or fire: the presence of flammable gases or
ENGLISH
fumes is a serious safety hazard.
- It is prohibited to power the system with energy
sources other than those specified.
- It is prohibited to integrate commercial systems
and/or equipment other than those specified, or
use them for purposes not intended and authorised
by their respective manufacturers.
- Do not allow water jets of any type or size to come
into direct contact with the actuator.
- Do not expose the actuator to corrosive chemicals
or atmospheric agents.
- Do not expose the barrier to direct jets of water of
any type and size.
- Do not expose the barrier to aggressive chemical
or environmental agents.
- The barrier may not be used to move moving parts
other than the beams produced by FAAC specified
Translation of the original instructions
in this manual.
- Use to control pedestrian access, bicycle traffic and
the passage of animals is prohibited.
- Use of the barrier at level crossings is prohibited.
- Use of the barrier on public thoroughfares is
prohibited.
- It is prohibited to use and/or install accessories
which have not been specifically approved by
FAAC S.p.A.
- It is prohibited to use the automation system before
performing commissioning.
- It is prohibited to use the automation system in the
presence of faults which could compromise safety.
- It is prohibited to use the automation system with
the fixed and/or mobile guards removed or altered.
- Do not use the automation system unless the area
of operation is free of persons, animals or objects.
- Do not enter/remain in the area of operation of the
automation system while it is moving.
- Do not try to prevent the movement of the auto-
mation system.
- Do not climb onto the actuator.
- Do not climb or catch on to the beam or lift yourself
B614 10 732998 - Rev.A
up on it. Do not climb on the barrier cabinet.
- Do not allow children to approach or play in the
area of operation of the automation system.
- Do not allow the control devices to be used by
anyone who is not specifically authorised and
trained to do so.
- Do not allow the control devices to be used by
children or persons with mental and physical deficiencies unless they are supervised by an adult
who is responsible for their safety.
During manual handling, accompany the beam slowly
!
for the entire stroke. Do not let the beam travel freely.
3.4 EMERGENCY USE
In emergencies or if there is a fault, turn off the power
supply to the automation and disconnect the buffer
batteries if there are any. If the beam can be moved
safely by hand, use the MANUAL OPERATION mode;
otherwise place the automation out of service until it
has been reset/repaired.
In the case of a breakdown, the automation must be
reset/repaired exclusively by the installer/maintenance
technician.
3.5 PRODUCT IDENTIFICATION
The product is identified by the plate (2).
3.6 TECHNICAL SPECIFICATIONS
The B614 is an electromechanical barrier with a E614
electronic board fitted. The B614 must be installed
on the specific foundation plate and set onto a plinth.
RH/LH barrier B614 makes it possible to build a right
hand or left hand barrier without modifying the
barrier body.
The barrier will be installed with the door towards
Li
the inside of the property.
The barrier is defined by observing it from the door
side:
- RH barrier (right): the beam closes towards the
right (in a clockwise direction)
- LH barrier (left): the beam closes towards the left
(in an anticlockwise direction)
Irreversible system To allow manual operation, the
release manoeuvre must be performed.
Encoder B614 is fitted with an encoder. The encoder
constantly detects the precise position of the beam
and makes it possible to manage the end of stroke
and slowing downs stored with the set up.
Anticrushing operation The encoder allows the board
to create the anticrushing feature:
- the recognition of an obstacle during closure cau-
ses the manoeuvre to be reversed
- the recognition of an obstacle during opening
causes the beam to stop.
Adjustable end of stroke The barrier is fitted with an
adjustable mechanical end of opening and closing
stroke feature.
Equipment A rectangular or round beam can be
installed. The components necessary for the installation and the optional equipment are listed in the
dedicated sections.
Balancing system The balancing spring must be used
FAAC. The single or double spring depending on the
length and configuration of the installed beam must
be fitted in the definite fitting positions.
The balancing system is important for safety reasons
!
to ensure the stability and control of the beam during
movement and keep it operating properly over time.
Master-Slave Configuration To install two barriers that
open in opposite directions it is necessary to create
the Master-Slave configuration.
5 Symbols: markings on product
Risk of crushing between the moving parts. Present
on the balancer
Risk of cutting, crushing or shearing of fingers or a
hand between the beam and the barrier body. It must
be placed on the trunk by the installation engineer.
"DANGER OF AUTOMATIC MOVEMENT" (not supplied) It must be
placed on the trunk by the installation engineer.
IDENTIFICATION NUMBER
Month/year of production +
progressive number for the
month of production
Example:
01160001
••••••
made in:
January 2018
progressive:
0001
ENGLISH
Translation of the original instructions
B614 11 732998 - Rev.A
2
6 Technical data
B614 220-240 V ~B614 115 V ~
Power supply voltage220-240 V~ 50/60 Hz115V~ +/-10% 50/60 Hz
Electric motor24 V
Max power165 W165 W
Max torque300 Nm300 Nm
Opening time (80°)
- beam 3 m
- beam 5 m
Use frequency Continuous use Continuous use
Ambient operating temperature-20 °C to +55 °C-20 °C to +55 °C
Protection ratingIP 55 (control board) - IP 44IP 55 (control board) - IP 44
Dimensions (L x D x H)247 x 357 x 1163 mm247 x 357 x 1163 mm
ENGLISH
Weight40 kg40 kg
FAAC foundation plate
Dimensions (L x H)230 x 305 mm
3.7 MANUAL OPERATION
- Performing the release manoeuvre when there is
!
no electrical power.
- Performing the release manoeuvre only when the
beam is at a standstill.
- During manual handling, accompany the beam
slowly for the entire stroke. Do not let the beam
travel freely.
- Do not leave the barrier unblocked: after carrying
Translation of the original instructions
out the manual movement, restore automatic
operation.
"
< 2 sec.
< 3 sec.
"
24 V
< 2 sec.
< 3 sec.
FAAC beamBeam length
Rectangular beam1.35 ... 4.85 m max
Round beam1.40 ... 5.20 m max
RELEASE PROCEDURE
1. 3 Open the lock cover. Insert the key and turn it
once anticlockwise until it stops (1).
2. Move the barrier manually.
3. Restore the operation.
OPERATION RESTORATION
1. 3 Insert the key and turn it twice clockwise
until it stops (2).
2. Check that manual movement is inhibited.
3. Remove the key and close the cover.
1
B614 12 732998 - Rev.A
2
3
3.8 COMPONENT IDENTIFICATION
Standard equipment on the barrier body (4):
1 Bearing trunk
2 Drive shaft
3 Beam release device (triangular key)
4 Top cover
5 Door with lock
6 E614 control board
7 E614 control board cover
8 Balancer/ upper spring fixing
9 Electromechanical gearmotor with Encoder
10 Slot for lower spring fixing
11 Limit switches
B614 beam side
1
2
3
ENGLISH
B614 door side
6
7
4
8
5
9
10
B614 13 732998 - Rev.A
Translation of the original instructions
11
11
4
3.9 INSTALLATION COMPONENTS
The installation requires the following FAAC components supplied separately (5):
1 Foundation plate
2 Rectangular or round beam (the reflecting paper for round
beam are supplied separately)
3 Fixing pocket for the installed beam (rectangular or round)
4 Single or double balancing spring
3.10 OPTIONAL ACCESSORIES
For the FAAC accessories for the B614 see the chapter
§ 9.
ENGLISH
1
Foundation plate
2
Rectangular beam
3
Pocket for rectangular
beam
Round beam
Pocket for round beam
Adhesive reflectors for
Translation of the original instructions
4
Single springDouble spring
B614 14 732998 - Rev.A
round beam
5
4. INSTALLATION REQUIREMENTS
4.1 MECHANICAL REQUIREMENTS
The mechanical structural components must comply
with the requirements of EN 12604:2002. Before
installing the automation, the suitability of the mechanical requirements must be established and any work
that is necessary in order to meet them carried out.
The essential mechanical requirements are as follows:
Firm ground to support the weight of the barrier with
!
flat, horizontal paving. There must be no chance of
water accumulating in the installation area.
The thresholds and protrusions of the paving must
be appropriately shaped in order to prevent the risk
of sliding or slipping.
For the creation of detection loops, refer to the specific
instructions.
Presence of a safety area between the wall (or other
fixed element) and the end of the beam, to protect
against the risk of persons becoming trapped/
crushed.
Presence of safety areas between the fixed and
moving parts to prevent hands from being crushed.
For the minimum dimensions to prevent crushing/
shearing of body parts, refer to EN 349. For the
safety distances required to prevent danger zones
being reached, refer to ISO 13857.
Presence of enough working space needed for the installation manoeuvres and subsequent maintenance
operations, bearing in mind the opening of the service
door and the positioning/removal of the cabinet and
any other elements.
Absence of fixed or mobile obstacles to the movement of the beam (e.g.: branches, overhead cables,
ceilings).
If the installation area presents the possibility of vehicle impact, provide adequate protective structures to
protect the barrier body.
230
360
300
1163
860
ENGLISH
305
360
385
1163
Translation of the original instructions
860
230
B614 15 732998 - Rev.A
305
6
4.2 ELECTRICAL SYSTEM
Always shut off the power supply before performing
F
any work. If the disconnect switch is not in view,
apply a warning sign stating “WARNING - Maintenance in Progress”.
The electrical system must comply with applicable
!
legislation in the country of installation.
Use components and materials with CE marking
which are compliant with the Low Voltage Directive
2014/35/EU and EMC Directive 2014/30/EU.
The power supply line for the automation must be
fitted with a multi-pole circuit breaker, with a suitable
tripping threshold, a contact opening distance of at
ENGLISH
Translation of the original instructions
least 3 mm and a breaking capacity that complies
with current regulations.
The power supply for the automation must be fitted
with a 30 mA differential switch.
The metal parts of the structure must be earthed.
Check that the protective earthing system complies with applicable regulations in the country of
installation.
The electrical cables of the automation system must
be of a size and insulation class that is compliant
with current legislation and laid in appropriate rigid
or flexible conduits, either above or below ground.
Use separate conduits for the power supply and the
12-24 V control devices / accessories cables.
In the case of a Master-Slave configuration, a cable
conduit has to be installed for the cables that connect
the two electronic boards.
Check buried cable plans to ensure that there are no
other electrical cables in proximity to the planned
digging/drilling locations to prevent the risk of
electrocution.
Check that there are no pipes in the vicinity as well.
The external electronic board must be housed in an
enclosure that has a minimum IP 44 protection rating
and fitted with a lock or another type of device to prevent access by unauthorised persons. The enclosure
must be located in an accessible and non-hazardous
area and at least 30 cm from the ground. The cable
outlets must face downwards.
The conduit fittings and the cable glands must prevent
the entry of moisture, insects and small animals.
Protect extension connections using junction boxes
with an IP 67 protection rating or higher.
The overall length of the BUS cables must not exceed
100 m.
The barrier must always be visible to prevent it from
being hit accidentally; an adequate lighting system
is required.
It is recommended to install a flashing light in a visible
position to indicate when it is moving.
For the creation of detection loops, refer to the relative
instructions.
The control accessories must be positioned in areas
that are always accessible and not dangerous for
the user. It is recommended to position the control
accessories within the field of view of the automation.
If an emergency stop button has been installed, it
must be EN13850 compliant.
Comply with the following heights from the ground:
- control accessories = minimum 150 cm
- emergency buttons = maximum 120 cm
If the manual controls are intended to be used by
disabled or infirm persons, highlight them with
suitable pictograms and make sure that these users
are able to access them.
B614 16 732998 - Rev.A
4.3 EXAMPLE SYSTEM
The example is purely an illustration and is only one of the possible applications of the B614.
!
Example systemMinimum wire cross section
1 Barrier B614
2 Mains power supply3G 1.5 sq. mm
3 Circuit breaker
4 Key button
5 Flashing light
6 BUS 2easy photocells2 x 0.5 sq. mm
7 Foot traffic route
4
56
3
ENGLISH
67
1
2
B614 17 732998 - Rev.A
2
Translation of the original instructions
7
5. MECHANICAL INSTALLATION
Carry out the work with the power supply discon-
F
nected.
5.1 TOOLS REQUIRED
The installation must comply with Standards
!
EN 12453 and EN 12445.
Mark off the work site and prohibit access/transit. Before the barrier is fixed to the foundation there
are risks of tripping and falls.
When working in the box there are risks of cutting,
shearing, crushing hands due to the presence of
moving parts. Until the installation is completed,
the partially installed barrier must always be left
blocked and with the door and upper lid always
ENGLISH
Translation of the original instructions
closed to prevent access to the electronic parts and
the moving mechanical pars.
Never install the beam before fixing the barrier body
and checking it.
Until the installation is complete, never leave the barrier unguarded with the beam fitted. If the beam is
fitted, the barrier must be locked with the beam open.
If installation is outside, it must be done in good
weather without rain or gusts of wind. If it is
raining, an adequate shelter for the barrier must be
made until the mechanical and electronic installation
is complete.
Never manage the barrier by holding the board holder.
Spanner
8-13-17-19
Allen key
4-6
Level
TOOL with TORQUE ADJUSTMENT
Where necessary for safety, a torque wrench with the
specified tightening torque will be shown.
FASTENING TORQUE VALUE
The torque wrench and the tightening torque in Nm
is shown in the figures. E.g.: HEX WRENCH 6 set at
2.5 Nm
2.5
Nm
6
B614 18 732998 - Rev.A
5.2 INSTALLING THE FOUNDATION PLATE
RISKS
PERSONAL PROTECTIVE EQUIPMENT
Carry out the work with the power supply discon-
F
nected.
The barrier must be installed with the base plate
!
- The foundation schematic appended to this manual
gives the characteristics of the foundation as pure
approximations. The schematic considers the barrier
applied to the maximum limits indicated in this
manual and under the most arduous conditions. The
installation engineer is responsible for the evaluation
of the foundation materials and dimensions on the
basis of the characteristics of the ground and place
of installation. Perform structural calculations
where necessary.
1. Make the hole in the ground. Fill it with concrete,
allowing the cable conduits to protrude.
2. (8) Assemble the base plate.
3. (9) Immerse the base plate in the foundation
leaving the surface exposed.
The plate must be in the centre of the plinth.
!
The hole for the cables to pass through must correspond with the orientation planned for the barrier
(barrier side, door side).
The cable conduits must protrude from the hole in the
plate by approximately 20 cm.
Check the plate is horizontal using a spirit level.
Clean the concrete off the surface of the plate and
the nuts with washers so they can be removed when
necessary.
4. Wait for the concrete to set.
22 mm
ENGLISH
8
Translation of the original instructions
beam side
B614 19 732998 - Rev.A
B614 door
side
9
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.