Extech 380353 Operating Manual

User's Manual
High Voltage Megohmmeter
Analog Insulation Tester plus AC Voltage and Continuity Tests
Warranty
EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects in parts and workmanship for one year from date of shipment (a six month limited warranty applies on sensors and cables). If it should become necessary to return the instrument for service during or beyond the warranty period, contact the Customer Service Department at (781) 890-7440 ext. 210 for authorization or visit our website at www.extech.com (click on ‘Contact Extech’ and go to ‘Service Department’ to request an RA number). A Return Authorization (RA) number must be issued before any product is returned to Extech. The sender is responsible for shipping charges, freight, insurance and proper packaging to prevent damage in transit. This warranty does not apply to defects resulting from action of the user such as misuse, improper wiring, operation outside of specification, improper maintenance or repair, or unauthorized modification. Extech specifically disclaims any implied warranties or merchantability or fitness for a specific purpose and will not be liable for any direct, indirect, incidental or consequential damages. Extech's total liability is limited to repair or replacement of the product. The warranty set forth above is inclusive and no other warranty, whether written or oral, is expressed or implied.
Introduction
Congratulations on your purchase of Extech’s High Voltage Megohmmeter. This meter is geared toward high voltage insulation testing applications such as appliance testing. In addition to Megohmmeter (Insulation Resistance) measurements, low resistance and AC Voltage can be measured. This professional meter, with proper care, will provide years of safe reliable service.
Safety
1. Circuits under test must be de-energized and isolated before connections are made (except for voltage measurements).
2. Circuit connections must not be touched during a test. Use extreme caution when working near bare conductors and bus bars. Accidental contact with conductor could result in electrical shock.
3. Use caution when working near voltages above 60VDC or 30VACrms.
4. After insulation tests, capacitors must be discharged.
5. Test leads (including alligator clips) must be in good working order, clean and without broken or cracked insulation.
6. When servicing, use only specified replacement parts.
International Safety Symbols
Rated Environmental Conditions
Caution, refer to this manual before using this meter
Dangerous Voltages
Meter is protected throughout by double or reinforced insulation
Indoor use only
Installation Category III
Pollution degree 2
Altitude up to 2000 meters
Ambient conditions: Temperature: 32 to 104
o
F (0 to 40oC); RH: 80% max.
2
Model 380353 V1.4 02/05
Specifications
General specifications
Display Taut band multi-scale analog display with status indicators
Live circuit indicator LED lights when live circuit is sensed
Withstand voltage Meets IEC-1010 safety requirements for Cat. III 600V
Power source Eight (8) 1.5 AA cells
Power consumption Megohmmeter: 190mA; Continuity: 120 mA (approx.)
Fuse protection 250V (1A) for Insulation Resistance and Continuity Tests
Operating conditions 32 to 104oF (0 to 40oC); < 80% RH
Dimensions 6.7 x 6.5 x 3.6” (170 x 165 x 92mm)
Weight 2.1 lbs (970g)
Standards
Low Resistance
Range Accuracy Overload Protect.
0 to 50
Open Circuit V: approx 600mV, Short circuit A: approx. 240mA
AC Voltage
Range Accuracy Line Frequency
600VAC ± 5% of full scale 40Hz to 1kHz
Insulation Resistance / Megohmmeter
Voltage (±10%) Range Accuracy
250VDC 500VDC
1000VDC
and zero adjust
C
C
±5% of reading 250V
0 to 50M 0 to 100M 0 to 400M
Short circuit current: 2mA, Overload Protection: 250V
± 5% of reading
3
Model 380353 V1.4 02/05