Ref No:
DATE:
PAGE: ISSUE:
evolution
EVC-H HEAT DETECTOR
INSTRUCTION MANUAL
NOV 2003
of46
NISM/EVC-H/01
01
Section 7 - MAINTENANCE AND CLEANING
Maintenance:
The EVC-H detector is a high quality product engineered
for reliability. In order to obtain optimum performance,
periodic maintenance is required. If proper preventative
maintenance is not carried out, there is a likelihood of
malfunction, including false alarms.
Servicing:
Servicing of the system should be carried out in accordance with the requirements of BS 5839 Part 1, Fire
Detection and Alarm Systems for Buildings: Code of
Practice for System Design, Installation and Servicing.
The maintenance procedures described below, should
be conducted with the following frequency:
One month after installation: Routine Inspection
and every 3 months
thereafter.
Every 6 months: Operational Test.
Every 12 months: Functional Test and
Cleaning.
All above frequencies of maintenance are dependent on
ambient conditions.
Routine Inspection:
i) Ensure that the detector head is secure and undam-
aged.
ii) Check that the heat entry apertures are in no way
obstructed.
iii) Ensure that the surface of the detector’s outer cover
is clean. If there are deposits due to the presence of oil
vapour, dust etc, then the detector should be cleaned in
accordance with the cleaning instructions detailed later
in this manual. It may be advisable to ensure that such
cleaning is conducted regularly in future.
iv) Ensure that no equipment which may generate
excessive heat has been installed in the vicinity of the
detector since the last routine inspection. If such
equipment has been installed, then you should notify
the Safety Officer or other competent authority that its
presence may cause false alarms.
Operational Test
The purpose of the Operational Test is to confirm the
detector’s correct operation in response to a heat
condition.
i) Take any necessary precautions at the control panel
to limit the sounding of the alarm sounders/bells and
any fire service summoning device.
ii) Test the detector with heat from a warm air gun
designed for heat detector testing (e.g. 'No Climb - Solo'
heat sensor tester). Check that the detector gives an
alarm condition within 10-20 seconds depending upon
the detector grade and the applied air temperature.
Check that the LED indicator on the detector illuminates.
N.B. Hot air blowers sold for paint stripping, soldering pipes etc, generate sufficient heat to damage the
detector and should not be used for testing heat
detectors.
iii) After the detector has given the alarm condition,
reset the detector from the control. It may be necessary to allow some short time to elapse before resetting
the detector, to allow any residual heat from the test to
disperse.
iv) Before proceeding to the next detector, ensure that
the detector just tested does not re-operate due to the
presence of residual heat.
Functional Test:
The Functional Test checks the detectors operation.
These detectors may be returned to our factory for
Functional Testing.
Cleaning:
Note: The sensor head should NOT be disassembled.
i) Carefuly remove the heat detector from its base.
ii) Use a soft, lint-free cloth, moistened with alcohol for
sticky deposits, to clean the plastic cover.
iii) Using a soft bristle brush (e.g. an artists paintbrush)
carefully brush between the vanes and thermistor in a
linear motion away from the apertures on the plastic
case.
iv) Ensure that no debris is left on or around the thermistor once cleaning is complete.
v) If the unit needs further cleaning or is damaged or
corroded, please return the complete detector to Nittan
(UK) Ltd. for service.