Evo H12, H16, H19, H22 Installation & Servicing Instructions Manual

Advanced High Efficiency Boilers
Installation & Servicing Instructions
See reverse for evo HE Users Guide
Manufactured exclusively for Wolseley Centers Ltd. by Ideal Boilers
For details of document amendments, refer to page 3
H12, H16, H19, H22
(V3 Flue System)
Wall mounted, balanced flue, fanned gas boiler
Packaged Boiler Contents have been
checked by Operator Number.......
October 2009 UIN 203323 A05
2
evo HE H - Installation & Servicing
DOCUMENT AMENDMENTS
Relevant Installation changes implemented in this book from Mod Level .............A04 (Apr 08) to A05 (Oct 09)
Page 4, Table 2 - Performance Data
• New SEDBUK figure for H12 boiler.
Page 7, Optional Extra Kits
• Addition of Concentric flue Screw Retaining Kit & Adjustable Flue Support Bracket
Page 16, Frame 12 - Determining the Flue Lengths and Packs Required
• New flue kit added.
• Notes - Item 4 added.
• Note added at bottom of page ref. support bracket
Page 18, Frame 18 - Terminal Wall Seal Assembly / Position
• New frame added ref. positioning of terminal wall seal
Page 19, Frame 21 - Flue Extension Ducts
• Item no. 3 added.
Page 20, Frame 24 - Condensate Pipe Termination Configurations
• Update drawing 1 and note added ref BS6798
Page 29, Frame 37 - Pictorial Wiring Diagram
• Updated drawing showing removal of bracket from spark generator
Page 42, Frame 65 - Combustion Chamber Insulation Replacement
• Updated Frame to reflect new insulation.
Page 48, Frame 76 - H9/L9 Heat Exchanger Overheat
• New flow chart.
Page 49 - Short Parts List
• New updated parts list
Page 52 - Code of Practice
• New Code of Practice Guidelines added.
Wolseley Centers Ltd. reserve the right to vary specification without notice
evo HE H - Installation & Servicing
3
GENERAL
Table 1 - Boiler Data
Boiler Size H12, H16, H19, H22
1
Gas supply type and connection 2H-G20-20 mbar Rc
Injector size Stereomatic 5.6mm dia. (HE 12 5.8mm dia).
Flow connection 22mm copper
Return connection 22mm copper
Flue terminal diameter mm (in.) 100 (4)
Maximum static water head m (ft.) 30.5 (100)
Minimum static water head m (ft.) 0.45 (1.5)
Electrical supply 230 V ~ 50 Hz
Boiler power consumption 38W
Fuse rating External: 3A Internal: T3.15A L250 V
Water content litre (gal.) 1.7 (0.37)
Packaged weight kg (lb.) 38 (84)
Maximum installation weight kg (lb.) 31 (68)
Boiler size Height mm (in.) 582 (23)
Width mm (in.) 390 (15)
Depth mm (in.) 278 (11)
/2 (1/2" BSP Female)
Table 2 - Performance Data
Boiler Size H12 Max H16 Max H19 Max H22 Max H12 min H16-22 Min
Boiler input 'Q' = Nett CV kW 12.2 16.4 19.5 22.6 9.8 9.1
Btu/h 41,600 56,000 66,500 77,100 33,400 31,000
Gross CV kW 13.5 18.2 21.6 25.1 10.9 10.1
Btu/h 46,000 62,100 73,800 85,600 37,200 34,400
Gas consumption l/s (cu.ft/h) 0.35 (44.2) 0.47 (59.9) 0.56 (71.1) 0.65 (82.5) 0.28 (35.6) 0.26 (33.3)
o
Boiler output 'P' = 70
C Mean water kW 12.0 16.1 19.0 22.0 9.3 8.8
temperature Btu/h 40,900 55,000 65,000 75,000 31,800 30,000
o
C Mean water kW 12.7 16.8 20.0 23.3 10.5 9.6
40
temperature Btu/h 43,300 57,400 68,300 79,500 35,900 32,800
Seasonal efficiency (SEDBUK) * Band A [90.3 ]% [90.4 ]% [90.3]% [9 0.2]%
NOx classification Class 5
* The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings.
The test data from which it has been calculated have been certified by a notified body.
Key to symbols
Note.
Gas consumption is calculated using a calorific value of
38.7 MJ/m3 (1038 Btu/ft3) gross or 34.9 MJ/m3 (935 Btu/ft3) nett. To obtain the gas consumption at a different calorific value:-
a. For l/s - divide the gross heat input (kW) by the gross
C.V. of the gas (MJ/m
3
)
b. For ft3/h - divide the gross heat input (Btu/h) by the
gross C.V. of the gas (Btu/ft3)
GB = United Kingdom IE = Ireland (Countries of destination)
PMS = Maximum operating pressure of water
C
13 C33 C53
= A room sealed appliance designed for connection via
ducts to a horizontal or vertical terminal which admits fresh air to the burner and discharges the products of combustion to the outside through orifices which, in this case, are concentric. The fan is up stream of the combustion chamber.
I
= An appliance designed for use on 2nd Family gas, Group
2H
H only.
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning
of this appliance, care should be taken when handling edges of sheet steel components.
4
evo HE H - Installation & Servicing
GENERAL
evo HE
Natural Gas only
Boiler size G.C. Appliance No. PI No.
(Benchmark No.)
H12 41 397 96 87 BP 34
H16 41 397 86 87 BP 34
H19 41 397 93 87 BP 34
H22 41 397 94 87 BP 34
Destination Countries: GB, IE
CONTENTS
Air Supply ....................................................................... 9
Benchmark Commissioning Checklist ..................... 58
Boiler Clearances ......................................................... 6
Boiler Exploded Diagram ............................................ 14
Electrical Connections ............................................... 29
Electrical Supply ........................................................... 9
Electrical Systems Diagrams .................................... 31
Extension Ducts - Fitting ............................................. 21
Fault Finding ................................................................. 47
Flow Wiring Diagram .................................................. 31
Flue Fitting .............................................................. 17-21
Flue Installation Requirements .................................... 8
Gas Safety Regulations ................................................ 7
Gas Supply ..................................................................... 8
Initial Lighting .............................................................. 33
Installation ............................................................. 14-34
Mandatory Requirements .............................................7
Safe Handling ................................................................ 7
Servicing ................................................................ 35-46
Short List of Parts ....................................................... 51
Terminal Guards ............................................................ 9
Thermostatic Radiator valves .................................... 9
Water and Systems .............................................. 10-13
Water Connections ..................................................... 29
Water Treatment ......................................................... 13
Wiring Diagrams ......................................................... 31
For GB, to comply with Building Regulations Part L1 (Part 6 in Scotland) the boiler should be fitted in accordance with the manufacturer's instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be demonstrated by completing and signing the Benchmark Commissioning Checklist.
Before installing this boiler, read the Code of Practice Sheet at the rear of this book.
BENCHMARK COMMISSIONING CHECKLIST DETAILS
Boiler Page
Make and model ....................................................... 5
Appliance serial no. on data badge ....... Front Cover
SEDBUK No. % ......................................................... 4
Controls
Time and temperature control to heating ............. 32
Time and temperature control to hot water .......... 32
Heating zone valves .............................................. n/a
TRV's ......................................................................... 9
Auto bypass ..............................................................9
Boiler interlock .......................................................... 9
For all boilers
Flushing to BS.7593 .............................................. 13
Inhibitor .................................................................. 13
Central heating mode
Heat input ................................................to be calculated
Burner operating pressure .................................... n/a
Central heating flow temp. ...... measure and record
Central heating return temp. ... measure and record
For combination boilers only
Scale reducer ......................................................... n/a
Hot water mode
Heat input ............................................................... n/a
Max. operating burner pressure ..............................n/a
Max. operating water pressure .............................n/a
Cold water inlet temp ............................................n/a
Hot water outlet temp. ........................................... n/a
Water flow rate at max. setting ..............................n/a
For condensing boilers only
Condensate drain .................................................. 22
For all boilers: complete, sign & hand over to customer
For assistance see Technical Helpline on the back page
Page
NOTE TO THE INSTALLER:
THE BENCHMARK COMMISSIONING
CHECKLIST AND LEAVE THESE
INSTRUCTIONS WITH APPLIANCE
evo HE H - Installation & Servicing
COMPLETE
5
GENERAL
1
BOILER WATER CONNECTIONS
The boiler flow and return pipes are supplied fitted to the boiler ready for top connection
Notes.
a. For the heating loads in excess of 60,000 Btu/h, 28mm (1") flow
and return pipes should be used to and from the boiler.
b. This appliance is NOT suitable for use with a direct hot water
cylinder.
2
BOILER CLEARANCES all dimensions in mm (in.)
The following minimum clearances must be maintained for operation and servicing.
Additional space will be required for installation, depending upon site conditions.
Side and Rear Flue
a Provided that the flue hole is cut accurately, e.g. with a core drill,
the flue can be installed from inside the building where wall thicknesses do not exceed 600mm (24"). Where the space into which the boiler is going to be installed is less than the length of flue required the flue must be fitted from the outside.
Installation from inside ONLY
b. If a core boring tool is to be used inside the building the space in
which the boiler is to be installed must be at least wide enough to accommodate the tool.
REAR FLUE ONLY
MIN. Top clearance required = 145 mm (5 3/4")
nm7291
SIDE FLUE ONLY
Horizontal length of flue Top clearance from centre line of boiler required (MIN.)
to outside wall Dim. A
0.5 m 160 mm (6
1.0 m 170 mm (6
1.5 m 185 mm (7 1
2.0 m 200 mm ( 7 7/8")
2.5 m 210 mm (8 1
3.0 m 225 mm (8 7/8")
3.5 m 235 mm (9
4.0 m 250 mm (10 7/8")
4.5 m 260 mm (10
5.0 m 275 mm (10 13/16")
5.5 m 290 mm (11
6.0 m 300 mm (11 13/16")
5/16")
11/16)
/4")
/4")
1/4")
1/4")
3/8")
nm7292
Front clearance
The minimum front clearance when built in to a cupboard is 5mm (1/4") from the cupboard door but 450mm (17 3/4") overall clearance is still required, with the cupboard door open, to allow for servicing.
6
nm8778
* Bottom clearance
after installation can be reduced to 5mm in an adequately ventilated enclosed cupboard. However, 100mm must be available for servicing.
evo HE H - Installation & Servicing
GENERAL
INTRODUCTION
The evo HE range of boilers are a fully automatically controlled,
wall mounted, low water content, balanced flue, fanned, condensing gas boiler. It has full modulating central heating outputs of :
H12 9.3 kW (32,000 Btu/h) to 12 kW (41,000 Btu/h).
H16 8.8 kW (30,000 Btu/h) to 16.1 kW (55,000 Btu/h).
H19 8.8 kW (30,000 Btu/h) to 19.0 kW (65,000 Btu/h).
H22 8.8 kW (30,000 Btu/h) to 22.0 kW (75,000 Btu/h).
Due to the high efficiency of the boiler a plume of water vapour will form at the flue terminal during operation depending on external conditions.
The boiler casing is of white painted mild steel with the user controls capable of being mounted remotely from the boiler, if the option is required.
The heat exchanger is of cast aluminium.
Note.
These boilers cannot be used on systems which include gravity circulation.
The boilers are suitable for connection to fully pumped, open vented or sealed water systems. Adequate arrangements for completely draining the system by provision of drain cocks MUST be provided in the installation pipework.
SAFE HANDLING
This boiler may require 2 or more operatives to move it to its installation site, remove it from its packaging base and during movement into its installation location. Manoeuvring the boiler may include the use of a sack truck and involve lifting, pushing and pulling.
Caution should be exercised during these operations. Operatives should be knowledgeable in handling techniques
when performing these tasks and the following precautions should be considered:
Grip the boiler at the base.
Be physically capable.
Use PPE as appropriate, e.g. gloves, safety footwear. During all manoeuvres and handling actions, every attempt
should be made to ensure the following unless unavoidable and/or the weight is light.
Keep back straight.
Avoid twisting at the waist.
Avoid upper body/top heavy bending.
Always grip with the palm of the hand.
Use designated hand holds.
Keep load as close to the body as possible.
Always use assistance if required.
OPERATION
When there is a demand for heat, the heating system is supplied at the selected temperature of between 30oC and 82oC.
The boiler features a comprehensive diagnostic system which gives detailed information on the boiler status when operating, and performance of key components to aid commissioning and fault finding.
OPTIONAL EXTRA KITS
Flue Extension Ducts (1000mm long up to 6m)
Flue Finishing Kit
o
90
Elbow Kit (maximum 4 elbows per installation).
45o Elbow Kit (maximum 4 elbows per installation).
Concentric Flue Screw Retaining Kit
Roof Flue Kit (to a maximum of 7.5m)
Powered Vertical Flue Kit 5m primary and 17m secondary is a typical maximum length. For alternative maximum lengths refer to Powered Vertical Instructions.
High Level Flue Outlet Kits
Flue Deflector Kit
Weather Collar
Horizontal Flue Terminal 600mm long.
Remote User Control Kit
Boiler Stand-off Kit
Siphon Kit
Condensate Pump Kit
• Adjustable Flue Support Bracket
SAFETY
Current Gas Safety (Installation and Use) Regulations or rules in force.
The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a Gas Safe Registered Engineer. It must be carried out in accordance with the relevant requirements of the:
Gas Safety (Installation and Use) Regulations
The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building Regulations (northern Ireland).
The Water Fittings Regulations or Water byelaws in
Scotland.
The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Registered Gas Installer (RGII) and installed in accordance with the current edition of I.S.813 "Domestic Gas Installations", the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
Detailed recommendations are contained in the following British Standard Codes of Practice:
BS. 5440:1 Flues (for gas appliances of rated input not
exceeding 70 kW).
BS. 5440:2 Ventilation (for gas appliances of rated input not
exceeding 70 kW).
BS. 5449 Forced circulation hot water systems.
BS. 5546 Installation of gas hot water supplies for
domestic purposes (2nd Family Gases).
BS. 6798 Installation of gas fired hot water boilers of rated
input not exceeding 60 kW.
BS. 6891 Low pressure installation pipes.
Health & Safety Document No. 635
The Electricity at Work Regulations, 1989.
The manufacturer’s notes must NOT be taken, in any way, as overriding statutory obligations.
IMPORTANT. These appliances are CE certificated for safety and performance. It is, therefore, important that no external control devices, e.g. flue dampers, economisers etc., are directly connected to these appliances unless covered by these Installation and Servicing Instructions or as otherwise recommended by Wolseley Centers Ltd. in writing. If in doubt please enquire.
Any direct connection of a control device not approved by Wolseley Centers Ltd. may invalidate the certification and the normal appliance warranty. It could also infringe the Gas Safety Regulations and the above regulations.
evo HE H - Installation & Servicing
7
GENERAL
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation panels, which can cause irritation to the skin. No asbestos, mercury or CFCs are included in any part of the boiler or its manufacture.
LOCATION OF BOILER
The boiler must be installed on a flat and vertical wall, capable of adequately supporting the weight of the boiler and any ancillary equipment.
The boiler may be fitted on a combustible wall and insulation between the wall and the boiler is not necessary, unless required by the local authority.
For electrical safety reasons there must be no access from the back of the boiler.
The boiler must not be fitted outside.
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should be fitted in accordance with the Institute of Gas Engineering document IGE/UP/7:1998.
Bathroom Installations
This appliance is rated IP20.
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE (BS.7671) Wiring Regulations and, in Scotland, the electrical provisions of the building regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. For Ireland reference should be made to the current ETCI rules for electrical installations and I.S.813:2002.
If the appliance is to be installed in a room containing a bath or shower then, providing water jets are not going to be used for cleaning purposes (as in communal baths/showers), the appliance must be installed in Zone 2, as detailed in BS.7671.
Compartment Installations
A compartment used to enclose the boiler should be designed and constructed specially for this purpose. An existing cupboard or compartment may be used, provided that it is modified for the purpose.
In both cases details of essential features of cupboard / compartment design, including airing cupboard installation, are to conform to the following:
z BS. 6798. (No cupboard ventilation is required - see “Air
Supply” for details).
z The position selected for installation MUST allow adequate
space for servicing in front of the boiler.
z For the minimum clearances required for safety and
subsequent service see the wall mounting template and Frame 2. In addition, sufficient space may be required to allow lifting access to the wall mounting plate.
GAS SUPPLY
The local gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas. An existing service pipe must NOT be used without prior consultation with the local gas supplier. The boiler MUST be installed on a gas supply with a governed meter only.
A gas meter can only be connected by the local gas supplier or by a Gas Safe Registered Engineer. In IE by a Registered Gas Installer (RGII).
An existing meter should be checked, preferably by the gas supplier, to ensure that the meter is adequate to deal with the rate of gas supply required.
It is the responsibility of the Gas Installer to size the gas installation pipework in accordance with BS6891:2005. Whilst the principle of the 1:1 gas valve ensures the evo H range is
8
able to deliver it’s full output at inlet pressures as low as 14mb, other gas appliances in the property may not be as tolerant. When operating pressures are found to be below the minimum meter outlet of 19mb these should be checked to ensure this is adequate for correct and safe operation.
Allowing for the acceptable pressure loss of 1mb across the installation pipework, it can be assumed that a minimum permitted operating pressure of 18mb will be delivered to the inlet of the appliance. (Reference BS 6400-1 Clause 6.2 Pressure Absorption).
The integral appliance isolation valve and boiler pipework could further reduce the operating pressure by up to 1.5mb when measured at the inlet test point on the appliance gas valve. Therefore it has been identified that an operating pressure as low as 16.5mbar could be measured at the appliance inlet pressure test point on the gas valve.
IMPORTANT.
Installation pipes MUST be fitted in accordance with BS. 6891. In IE refer to I.S.813:2002. Pipework from the meter to the boiler MUST be of an adequate size.
The complete installation MUST be tested for gas tightness and purged as described in the above code.
FLUE INSTALLATION
Pluming will occur at the terminal so terminal positions which would cause a nuisance should be avoided.
The flue must be installed in accordance with the recommendations of BS.5440-1:2000. In IE refer to I.S.813:2002.
The following notes are intended for general guidance.
1. The boiler MUST be installed so that the terminal is exposed
to external air.
2. It is important that the position of the terminal allows the free
passage of air across it at all times.
3. Minimum acceptable spacing from the terminal to obstructions
and ventilation openings are specified in Table 3.
Table 3 - Balanced Flue Terminal Position
Flue Terminal Positions
1. Directly below, above or alongside an opening
window, air vent or other ventilation opening. 300m m (1 2" )
2. Below guttering, drain pipes or soil pipes. 25mm ( 1")*
BS5440-1 2000 75mm (3")
3. Below eaves. 25mm (1")*
BS5440-1 2000 200mm (8")
4. Below balconies or a car port roof. 25mm (1")*
BS5440-1 2000 200mm (8")
5. From vertical drain pipes or soil pipes. 25mm (1")*
BS5440-1 2000 150mm (6")
6. From an internal or external corner or to a 25mm (1")* boundary along side the terminal. BS5440-1 2000 300mm (12")
7. Above adjacent ground, roof or balcony level. 300mm (12")
8. From a surface or a boundary facing the terminal. 600mm (24")
9. From a terminal facing a terminal. 1,200mm (48")
10. From an opening in a car port
(e.g. door or window) into dwelling. 1,200mm (48")
11. Vertically from a terminal on the same wall. 1,500mm (60")
12. Horizontally from a terminal on the wall. 300mm (12")
Vertical Terminals
13. Above the roof pitch with roof slope of all angles. 300mm (12")
Above flat roof. 300mm (12")
14. From a single wall face. 300mm (12") From corner walls. 300mm (12")
* Only one reduction down to 25mm is allowable per installation otherwise BS5440-1 2000 dimensions must be followed.
Min. Spacing*
evo HE H - Installation & Servicing
GENERAL
4. Where the lowest part of the terminal is fitted less than 2m
(6'6") above a balcony, above ground or above a flat roof to which people have access, then the terminal MUST be protected by a purpose designed guard.
Ensure that the guard is fitted centrally.
Terminal guards are available from boiler suppliers. Ask for TFC Flue Guard Model No. K6 (round plastic-coated). In case of difficulty contact:
Grasslin (UK) Ltd. Tel. +44(0) 01732 359 888 Tower House, Vale Rise Fax. +44(0) 01732 354 445 Tonbridge. kent TN9 1TB www.ffc.ukco.com
5. The flue assembly shall be so placed or shielded as to prevent ignition or damage to any part of any building.
6. The air inlet/products outlet duct and the terminal of the boiler MUST NOT be closer than 25mm (1") to combustible material. Detailed recommendations on the protection of combustible material are given in BS.5440-1:2000. In IE refer to I.S.813:2002.
IMPORTANT.
It is absolutely ESSENTIAL to ensure, in practice, that products of combustion discharging from the terminal cannot re-enter the building or any other adjacent building through ventilators, windows, doors, other sources of natural air infiltration, or forced ventilation / air conditioning.
If this should occur the appliance MUST be turned OFF, labelled as 'unsafe' until corrective action can be taken.
TERMINAL
The terminal assembly can be adapted to accommodate various wall thicknesses. Refer to Frame 14.
AIR SUPPLY
It is NOT necessary to have a purpose-provided air vent in the room or internal space in which the boiler is installed. Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed, due to the low surface temperatures of the boiler casing during operation; therefore the requirements of BS 6798, Clause 12, and BS 5440:2 may be disregarded. In IE the requirements of I.S.813:2002 may be disregarded.
The hydraulic resistance of the boilers, at MAXIMUM OUTPUT, with an 11 Graph 1.
Graph 1 - Water flow rate and pressure loss
o
C (20 oF) temperature differential, is shown in
1.0
0.5
Pressure Drop Across Boiler
(metres water)
8.8 11.7 14.7 17.6 20.5 Boiler Output (kW)
Ecl 1603
23.4
BOILER CONTROL INTERLOCKS
Wolseley Centers Ltd. recommend that heating systems
utilising full thermostatic radiator valve control of temperature in individual rooms should also be fitted with a room thermostat controlling the temperature in a space served by radiators not fitted with such a valve as stated in BS. 5449.
Central heating systems controls should be installed to ensure the boiler is switched off when there is no demand for heating or hot water.
When thermostatic radiator valves are used, the space heating temperature control over a living / dining area or hallway having a heating requirement of at least 10% of the boiler heat output should be achieved using a room thermostat, whilst other rooms are individually controlled by thermostatic radiator valves. However, if the system employs thermostatic radiator valves on all radiators, or two port valves without end switches, then a bypass circuit must be fitted with an automatic bypass valve to ensure a flow of water should all valves be in the closed position.
WATER CIRCULATION SYSTEM
IMPORTANT.
A minimum length of 1 metre of copper pipe MUST be fitted to both flow and return connections from the boiler before connection to any plastic piping.
For the types of system and correct piping procedure see Frames 1, and 3 to 8.
The central heating system should be in accordance with BS.6798 and, in addition, for smallbore and microbore systems, BS.5449.
WATER TREATMENT - see Frame 9
The hot water storage cylinder MUST be of the indirect type and should preferably be manufactured of copper.
Single feed, indirect cylinders are not recommended and MUST NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating nor are they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of the useful heating surface, should be lagged to prevent heat loss and any possible freezing - particularly where pipes run through roof spaces and ventilated underfloor spaces.
The boiler must be vented.
evo HE H - Installation & Servicing
ELECTRICAL SUPPLY
WARNING.
This appliance must be earthed.
Wiring external to the appliance MUST be in accordance with the current I.E.E. (BS.7671) Wiring Regulations and any local regulations which apply. For Ireland reference should be made to the current ETCI rules for electrical installations.
The point of connection to the mains should be readily accessible and adjacent to the boiler.
NOTE: THE FAN VOLTAGE IS 325V DC
CONDENSATE DRAIN - Refer to Frames 23 & 44
A condensate drain is provided on the boiler. This drain must be connected to a drainage point. All pipework and fittings in the condensate drainage system MUST be made of plastic - no
other materials may be used.
IMPORTANT.
Any external runs must be insulated.
The drain outlet on the boiler is standard 21.5mm (3/4”) overflow pipe.
9
GENERAL
3
OPEN VENT SYSTEM REQUIREMENTS
The system should be vented directly off the boiler flow pipe, as close to the boiler as possible. The cold feed entry should be inverted and MUST be positioned between the pump and the vent, and not more than 150mm (6") away from the vent connection.
Note. Combined feed and vent pipes may also be fitted.
There should be a minimum height 450mm (18") of open vent above the cistern water level. If this is not possible refer to Frame 5. The vertical distance between the highest point of the system and the feed/expansion cistern water level MUST not be less than 450 mm (18"). The pump must be fitted on the flow side of the boiler.
A suitable pump is a domestic circulator capable of providing a maximum 11 whole of the heating circuit open (e.g. Grundfos UPS 15/50, 15/60 or equivalent). With the minimum flow circuit allowed by the controls the differential must not exceed 25 oC. (18oC for the H16)
The vertical distance between the pump and feed/expansion cistern MUST comply with the pump manufacturer's minimum requirements, to avoid cavitation. Should these conditions not apply either lower the pump position or raise the cistern above the minimum requirement specified by Wolseley Centers Ltd. The isolation valves should be fitted as close to the pump as possible.
o
C (20oF) temperature differential across the boiler with the
Return & flow connections
load 30 - 60 = 22 mm load 70 - 80 = 28 mm
4
SCHEMATIC PIPEWORK AND SYSTEM BALANCING
The boiler does not normally need a bypass but at least some radiators on the heating circuit, of load at least 10% of the minimum boiler output, must be provided with twin lockshield valves so that this minimum heating load is always available (see footnote re. thermostatic radiator valves).
Balancing
1. Set the programmer to ON for both CH
and HW. Turn the cylinder thermostat down. Close the manual or thermostatic valves on all radiators, leaving the twin lockshield valves (on the radiators referred to above) in the open position. Turn up the room thermostat and adjust these lockshield valves to give boiler flow and return temperatures not more than
o
C apart. These valves should now be
20 left as set.
2. Open all manual or thermostatic radiator valves and adjust the lockshield valves on remaining radiators to give around
o
11
C temperature drop at each radiator.
3. Turn up the cylinder thermostat and adjust the cylinder balancing valve so that the cylinder achieves a maximum flow consistent with adequate flow to the radiators. Check that with only the domestic hot water loop in circuit a differential temperature of 20 the boiler is not exceeded.
4. Adjust room and cylinder thermostats and programmer to NORMAL settings.
o
C across
10
evo HE H - Installation & Servicing
GENERAL
Non-return
valve
Automatic
air vent
Hose unions
Additional stop valve
Hose connector
Hosepipe
(disconnect
after filling)
Double check valve
assembly
(note direction of flow)
Temporary hose
(disconnect
after filling)
ecl6060
5
LOW HEAD AND LARGE SYSTEMS WITH EXTENSIVE PIPE RUNS - OPEN VENT
This arrangement is useful for large systems where radiators at the extremities are difficult to vent. This can lead to pumping over with conventional feed and vent arrangements.
The following conditions MUST be observed:
1. The top of the automatic air vent must be below the cold water level.
2. The static water level (cold) must be at least 200mm above the top of the horizontal flow pipe, fitted as shown. The vent connection MUST NOT be made immediately off the top of the boiler as venting is made less efficient.
3. The maximum practical length of 22mm cold feed pipe should be used in order to reduce the effective volume of hot system water expanding into the feed/expansion cistern to a minimum.
All dimensions in mm (in.).
Note. The pump manufacturers' minimum requirements must be complied with.
6
SEALED SYSTEM REQUIREMENTS
Notes.
a. The method of filling, refilling, topping up or flushing
sealed primary hot water circuit from the mains via a temporary hose connection is only allowed if acceptable to the local water authority.
NB. Imperial dimensions are approximate
b. When installing the
filling device, it must be connected as shown to fully comply with the water regulations. This may involve the fitting of an additional WRAS approval isolator valve to the mains supply.
1. General
a. The installation
must comply with the requirements of BS. 6798 and BS. 5449.
b. The installation should be designed to work with
flow temperatures of up to 82
o
C.
c. All components of the system, including the heat
exchanger of the indirect cylinder, must be suitable for a working pressure of 3 bar (45lb/in and temperature of 110oC. Care should be taken in making all connections so that the risk of leakage is minimised.
2. Safety Valve
A spring loaded safety valve complying with the relevant requirements of BS. 6759 must be fitted in the flow pipe as close to the boiler as possible and with no intervening valve or restriction. The valve should have the following features:
evo HE H - Installation & Servicing
2
)
a. A non-adjustable preset lift pressure not exceeding
3bar (45lb/in
2
).
b. A manual testing device.
c. Provision for connection of a discharge pipe.
The valve or discharge pipe should be positioned so that the discharge of water or steam cannot create a hazard to the occupants of the premises or cause damage to electrical components and wiring.
3. Pressure Gauge
A pressure gauge covering at least the range 0-4 bar (0-60 lb/in
2
) must be fitted to the system. The gauge should be easily seen from the filling point and should preferably be connected at the same point as the expansion vessel.
11
GENERAL
SEALED SYSTEM REQUIREMENTS - continued
7
4. Expansion Vessel
a. A diaphragm type expansion vessel must be
connected to a point close to the inlet side of the pump, the connecting pipe being not less than 15 mm
1/2" nominal) size and not incorporating valves of
( any sort.
b. The vessel capacity must be adequate to accept the
expansion of the system water when heated to
o
110
C (230oF).
c. The charge pressure must not be less than the
static water head above the vessel. The pressure attained in the system when heated to 110 F) should be at least 0.35 bar (5 Ib/in2) less than the lift pressure of the safety valve. For guidance on vessel sizing refer to the table in Frame 8.
For further details refer to BS. 5449, BS. 7074:1 and the British Gas Corporation publication 'Material and Installation Specifications for Domestic Central Heating and Hot Water'. For IE refer to the current edition of I.S.813.
5. Cylinder
The cylinder must be either of the indirect coil type or a direct cylinder fitted with an immersion calorifier which is suitable for operating on a gauge pressure of 0.35 bar
2
) in excess of the safety valve setting. Single feed
(5 Ib/in indirect cylinders are not suitable for sealed systems.
6. Make-up Water
Provision must be made for replacing water loss from the system, either:
a. From a manually filled make-up vessel with a readily
visible water level. The vessel should be mounted at least 150 mm (6") above the highest point of the system, and be connected through a non-return valve to the system, fitted at least 300 mm (12") below the make-up vessel on the return side of the domestic hot water cylinder or radiators.
or
b. Where access to a make-up vessel would be difficult
by pre-pressurisation of the system. Refer to 'Filling', below.
7. Mains Connection
There must be no direct connection to the mains water supply or to the water storage tank supplying domestic water, even through a non-return valve, without the approval of the local water authority.
8. Filling
The system may be filled by one of the following
methods:
a. Through a cistern, used for no other purposes, via a
ball valve permanently connected directly to a service pipe and/or a cold water distributing pipe. The static head available from the cistern should be adequate to provide the desired initial system design
o
C (230
pressure. The cold feed pipe from the cistern should include a non-return valve and a stop valve with an automatic air vent connected between them, the stop valve being located between the system and the automatic air vent. The stop valve may remain open during normal operation of the system if automatic water make-up is required.
b. Through a self-contained unit comprising a cistern,
pressure booster pump (if required) and, if necessary, an automatic pressure reducing valve and flow
o
restrictor. The cistern should be supplied through a temporary connection from a service pipe or cold water distributing pipe. This unit may remain permanently connected to the heating system to provide limited automatic water make-up. Where the temporary connection is supplied from a service pipe or distributing pipe which also supplies other draw-off points at a lower level then a double check valve shall be installed upstream of the draw-off point.
c. Through a temporary hose connection from a draw-off
tap supplied from a service pipe under mains pressure. Where the mains pressure is excessive a pressure reducing valve shall be used to facilitate filling.
The following fittings shall form a permanent part of the system and shall be fitted in the order stated:
A stop valve complying with the requirements of BS. 1010, Part 2 (the hose from the draw-off tap shall be connected to this fitting). A test cock. A double check valve of an approved type.
• Thoroughly flush out the whole of the system with cold water, without the pump in position.
• With the pump fitted, fill and vent the system until the pressure gauge registers 1.5 bar (21.5lb/in
2
).
Examine for leaks.
• Check the operation of the safety valve by manually raising the water pressure until the valve lifts. This should occur within ± 0.3 bar (± 4.3lb/in
2.
) of the
preset lift pressure.
• Release water from the system until the initial system design pressure is reached.
• Light the boiler and heat the system to the maximum working temperature. Examine for leaks.
• Turn off the boiler and drain the system while still hot.
• Refill and vent the system.
• Adjust the initial pressure to the required value.
Sizing procedure for expansion vessels: The volume of the expansion vessel (litres) fitted to a sealed system shall not be less than that given by the table on the following page, multiplied by a factor of 0.8 (for flow temperatures of less than 83 C).
12
o
evo HE H - Installation & Servicing
GENERAL
8
SEALED SYSTEM REQUIREMENTS - continued
Safety valve setting 3.0 bar 2.5 bar 2.0 bar
Vessel charge and initial 0.5 1.0 1.5 0.5 1.0 1.5 0.5 1.0 system pressure bar bar bar bar bar bar bar bar
Total water content of system Expansion vessel volume litres
litres
25 2.1 2.7 3.9 2.3 3.3 5.9 2.8 5.0
50 4.2 5.4 7.8 4.7 6.7 11.8 5.6 10.0
75 6.3 8.2 11.7 7.0 10.0 17.7 8.4 15.0
100 8.3 10.9 15.6 9.4 13.4 23.7 11.3 20.0
125 10.4 13.6 19.5 11.7 16.7 29.6 14.1 25.0
150 12.5 16.3 23.4 14.1 20.1 35.5 16.9 30.0
175 14.6 19.1 27.3 16.4 23.4 41.4 19.7 35.0
200 16.7 21.8 31.2 18.8 26.8 47.4 22.6 40.0
225 18.7 24.5 35.1 21.1 30.1 53.3 25.4 45.0
250 20.8 27.2 39.0 23.5 33.5 59.2 28.2 50.0
275 22.9 30.0 42.9 25.8 36.8 65.1 31.0 55.0
300 25.0 32.7 46.8 28.2 40.2 71.1 33.9 60.0
Multiplying factors for
other system volumes 0.0833 0.109 0.156 0.094 0.134 0.237 0.113 0.20
9
WATER TREATMENT
The evo HE boiler range has an ALUMINIUM alloy heat exchanger
IMPORTANT.
The application of any other treatment to this product may render the guarantee of
Wolseley Centers Ltd. invalid.
Wolseley Centers Ltd.
Treatment in Central Heating systems.
recommend water treatment in accordance with the Benchmark Guidance Notes on Water
Wolseley Centers Ltd. recommend the use of FERNOX-COPAL or MB1 or GE Betz Sentinel X100 inhibitors and
associated water treatment, which must be used in accordance with the manufacturers' instructions. For further information contact:
Fernox Manufacturing Co. Ltd Cookson Electronics Forsyth Road Sheerwater Woking Surrey GU21 5RZ Tel: +44 (0) 1799 521133
Notes
1. It is most important that the correct concentration of the water treatment product is maintained in accordance with the manufacturers' instructions.
2. If the boiler is installed in an existing system any unsuitable additives MUST be removed by thorough cleansing.
BS. 7593:2006 details the steps necessary to clean a domestic central heating system.
Sentinel Performance Solutions The Heath Business & Technical Park Runcorn Cheshire WA7 4QX Tel: 0800 389 4670 www.sentinel-solutions.net
3. In hard water areas, treatment to prevent lime scale may be necessary - however, the use of artificially softened water is NOT permitted.
4. Under no circumstances should the boiler be fired before the system has been thoroughly flushed.
Salamander Engineering Ltd The Heath Business & Technical Park Runcorn Cheshire WA7 4QX Tel: +44 (0) 121 3780952
evo HE H - Installation & Servicing
13
nm8779b
40
94
40
10
INSTALLATION
INSTALLATION
BOILER ASSEMBLY - Exploded view
LEGEND
1. Front casing panel.
2. Sealing panel.
3. Sump cover plate.
4. Bottom casing panel.
5. Flue sensing nipple.
6. Return pipe.
7. Flow pipe.
8. Flue manifold.
10. Interpanel.
11. Burner assy.
12. Combustion chamber
Insulation.
13. Heat exchanger.
14. Injector & housing.
15. Venturi assy.
16. Fan assy.
17. Gas pipe assy.
19. Gas control valve assy.
20. Fan bracket assy.
21. Orifice plate.
22. Flue thermistor.
23. Control thermistor.
24. Overheat thermostat.
25. Ignition electrode.
26. Flame detection electrode.
32. 'S' trap.
33. Control assy.
40. Spark generator.
44. Wall mounting plate.
53. Turret gasket kit.
94. Ignition lead.
14
evo HE H - Installation & Servicing
INSTALLATION
11
UNPACKING
The boiler is supplied fully assembled in one Pack A, together with a telescopic flue assembly for lengths up to 595mm, rear or side flue outlet, in Pack B.
Unpack and check the contents.
Pack A Contents
A The boiler
B Wall mounting template
on cardboard
C Wall mounting plate
D 1 year guarantee form
E These Installation & Servicing
User’s Instructions
F Hardware pack
B
A
nm7890
C
D
E
F
INSTALLATION
Hardware Pack
A 50mm x No.14 wood screws - 3 off
B Wall plugs (TP2B ) - 3 off
C Mains connector - 1 off
B Pack Contents
A Telescopic flue terminal
B Flue turret
C Rubber Terminal Wall Seal
D Screw
E Sealing Tape
A
nm8464
B
A
D
B
E
C
C
isfu8751d
evo HE H - Installation & Servicing
15
INSTALLATION
12
PACKAGING REMOVAL
1. Ensure the boiler is stood correctly, as marked on
the carton.
2. Cut and remove the strapping.
3. Fold back the top flaps to gain access to the wall
mounting plate, literature and wall mounting template. (located on protective packaging piece).
4. Remove the instructions and read thoroughly before unpacking the product.
INSTALLATION
5. Remove the hardware pack and keep in a safe
place.
6. When ready for installation lift off the outer sleeve.
7. Remove the top protection packing/template and
save for further use.
8. Remove the two packaging ends.
3
7
nm8231
8
6
5
13
BOTTOM PANEL REMOVAL
1. To remove the front panel remove the 2 screws from the
bottom panel.
2. Lift the front panel up and off the top pegs.
3. To remove the bottom panel remove the 2 screws.
4. Pull the RH side of the panel down. Slide it to the right
and withdraw.
nm7819
3
1
16
evo HE H - Installation & Servicing
INSTALLATION
Wall Thickness X
160 mm
160 + S = 193mm
nm8943
195mm
195mm
Wall Thickness X
Side flue length L
14
DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED
IMPORTANT. The boiler MUST be installed in a vertical position.
FLUE KITS
Pack B - supplied as standard. Finishing Kit - supplied as an optional extra. Pack D - optional extension kit for side flue or rear flue outlet. Screw Kit - Optional kit for mechanical fixing of flue joints
Refer to 'Flue Extension Ducts'
Note. MAXIMUM FLUE LENGTHS:
HORIZONTAL FLUE - 6M ROOF FLUE KIT - 7.5M POWERED VERTICAL FLUE KIT - 5M PRIMARY AND 17M SECONDARY IS A TYPICAL
MAXIMUM LENGTH. For alternative maximum lengths
O
90
ELBOW KIT 60/100 (EQUIVALENT FLUE LENGTH RESISTANCE = 1M) 45O ELBOW KIT 60/100 (EQUIVALENT FLUE LENGTH RESISTANCE = 0.6M) MINIMUM HORIZONTAL FLUE LENGTHS - TELESCOPIC TERMINAL = 370MM
(Centre Line of turret to outside of wall terminal) - ONE PIECE TERMINAL = 285MM
refer to Powered Vertical Instructions.
Dimension X - Wall thickness.
Dimension L - Wall thickness plus boiler spacing.
Dimension S - Stand-off frame depth = 33mm.
SIDE FLUE
REAR FLUE
Notes.
1. When extension ‘D’ packs are used the flue duct MUST be
inclined at 1.5 degrees to the horizontal to allow condensate to drain back into the boiler and out through the condensate drain.
2. If the telescopic ‘B’ pack or horizontal flue terminal (600 long) only are used, they may be mounted horizontally. The 1.5 degrees is taken care of by the inclination of the flue within the air pipe
3. If the boiler is to be installed with downward piping routed behind the boiler then the optional stand-off kit should be used. Care must be taken when cutting the ducts and marking the wall to suit this condition.
4. Only use water as a lubricant during assembly.
It is recommended that a support bracket is fitted for every 1 metre of extension pipe used and also at every joint to ensure pipes are held at the correct angle. If a slip joint coupling is used then a support bracket must be used to secure the collar.
evo HE H - Installation & Servicing
Total Flue length dimension Flue
(measuring from CL of turret to outside wall)
Rear flue Side flue Extra packs
dim. X+160 dim. L+195 required
Up to 595 mm Up to 595 mm none
Up to 1545 mm Up to 1545 mm Pack D - 1 off
Up to 2495 mm Up to 2495 mm Pack D - 2 off
Up to 3445 mm Up to 3445 mm Pack D - 3 off
Up to 4395 mm Up to 4395 mm Pack D - 4 off
Up to 5345 mm Up to 5345 mm Pack D - 5 off
Up to 6000 mm Up to 6000 mm Pack D - 6 off
FLUE OUTLET
17
15
nm9287
V - See Diagram Below
Extended centre line
155
FLUE ASSEMBLY - Exploded View
An optional flue duct extension kit is required for wall thicknesses greater than :
Side 395mm
Rear 435mm
LEGEND
1. Duct assembly.
2. Flue turret.
3. Turret gasket.
4. M5 x 10 pozi screw.
5. Turret clamp.
INSTALLATION
1
Rear flue arrangement shown
16
WALL MOUNTING TEMPLATE
The wall mounting template is located on the internal top protective packaging.
Note.
The template shows the positions of the fixing holes and the rear flue hole centre for standard installation. Care MUST be taken to ensure the correct holes are drilled.
1. Tape template into the selected position. Ensure squareness by hanging a plumbline as shown.
2. If fitting a side flue extend the flue centre line onto the side wall and measure in 155mm for standard installation.
Note. If using stand-off kit distance increases to 188mm.
3. Mark onto the wall the following:
a The wall mounting plate screw positions (choose one
from each side with preference to top holes).
b. The position of the flue duct hole (see diagram below).
Note. Mark the centre of the hole as well as the
circumference.
4. Remove the template from the wall.
nm8752
FLUE OUTLET
18
nm8731
evo HE H - Installation & Servicing
Loading...
+ 42 hidden pages