MINERAL REDUCTION SYSTEM FOR FOODSERVICE APPLICATIONS
INTRODUCTION
The Everpure MRS-600HE High Efficiency RO System is
a pre-engineered, preassembled Reverse Osmosis (RO)
solution designed to provide high purity water for multiple
applications such as premium espresso, coffee, blended
beverages and steam. It combines a number of water
treatment technologies into one easy-to-install package,
providing superior reduction in total dissolved solids (TDS)
which can foul or scale water
using equipment.
Initial System Production
Water production depends on supply water pressure and
temperature. See Performance section (page 13) for
normalized production.
Influent Water Characteristics
Allowable operating range of various water properties within which the MRS-600HE System will function properly.
Total Dissolved Solids (TDS)pHFree ChlorineTurbidityIronBacterial Quality
NOTE: The MRS-600HE System does NOT include on-board particulate or organic reduction filtration. Incoming water supplies that do not meet the influent water characteristics
requirements will require the addition of pretreatment equipment prior to the MRS-600HE System. Do not connect the MRS-600HE System after any other water filtration system, unless
specifically provided or specified. System performance may be affected if requirements are not met, including system output and cartridge changeout frequency.
The Everpure 2SR-BW Water Conditioning Cartridge contains media that reduces the scaling tendency of hard water minerals
found in many water supplies, extending RO membrane life.*
The dual-head booster pump increases the inlet pressure to maintain consistent permeate production, plus eliminates
back-pressure on the permeate output. This innovative approach to both boosting and eliminating back-pressure maximizes
system efficiency.
The Everpure MR-600, MR-600-1 or MR-600F RO Membrane Cartridge contains a semi-permeable reverse osmosis membrane. It’s here that most of the dissolved impurities are separated from the water and flushed down the drain. The water
that is able to pass through the membrane, which is very low in dissolved impurities, is referred to as permeate, RO water, or
product water.
Once the RO water is produced, it is stored in the 6-gallon (22.7 l) RO water storage tank. This tank serves two (2) key functions;
1) it acts as a buffer between the system and the connected equipment, providing ample volumes of water instantaneously,
2) it reduces the on-off cycling of the RO system which produces better quality water and prolongs the system’s life.
4. 6-Gallon (22.7 l) RO water storage tank
5. Control system with power supply
*Everpure 2SR-BW Water Conditioning Cartridge not performance tested or certified by NSF.
FILTRATION & PROCESSING SOLUTIONS
EVERPURE MRS600HEII SYSTEM ORIGINAL INSTRUCTIONS
SAFETY INSTRUCTIONS
The appliance is only to be installed in locations where its use, maintenance and cleaning is
restricted to trained adult personnel. No one should play with the appliance.
The appliance is intended to be permanently connected to the water mains and not
connected by a hose-set.
The appliance is not suitable for installation in an area where a water jet could be used and
must not be cleaned by a water jet.
Prior to performing any service on a pressurized vessel/tank, eye protection,
ear protection and other suitable personal protection equipment should be worn. Isolate
the water system and de-pressurize it. Drain the water that is inside the tank by opening the
drain valve or by other means. Once the water has been drained , relieve the air pressure by
depressing the pin on the Schrader valve.
Grounding Instructions: This appliance must be grounded. In the event of a malfunction
or breakdown, grounding will reduce the risk of electric shock by providing a path of least
resistance for electric current. This appliance is equipped with a cord having an appliancegrounding conductor and a grounding plug. The plug must be plugged into an appropriate
outlet that is installed and grounded in accordance with all local codes and ordinances. If
the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard.
Improper connection of the appliance-grounding conductor can result in a
risk of electric shock. Check with a qualified electrician or service representative if you are in
doubt whether the appliance is properly grounded. Do not modify the plug provided with the
appliance; if it will not fit in the outlet, have a proper outlet installed by a qualified technician.
INSPECTION
The MRS-600HE System includes all the necessary fittings for installation. Lengths of 3/8" (9.5 mm) tubing have been provided
for connecting to the wastewater / drain connection. Supply lines and distribution piping / tubing are not included.
The MRS-600HE System is packaged as a complete unit in one carton. At a minimum, you should have the following:
PartsQuantity
1. Plate mounted processor assembly
Dual-head pump
Cartridge heads
Controller & power supply
Storage tank
2. Wall mount bracket1
3. MR-600, MR-600-1 or MR-600F RO cartridge1
4. 2SR-BW cartridge1
5. Parts Kit1
Inspect the carton for damage. Carefully unpack and inspect each item. Report any damage to freight carrier immediately and
retain all packaging materials.
SELECTING A LOCATION
Locate the system in an area that is convenient to the inlet water supply and drain facilities, with access for routing the product
water tubing / piping to the equipment. Install in a dry location, away from all forms of corrosive and / or flammable materials.
Consider ease of access for servicing when selecting a location. Evaluate the mounting surface for its ability to properly
support the weight of the processor when in operation [Approximately 90 lbs. (40.8 kg.)].
1
2 EVERPURE MRS600HEII SYSTEM ORIGINAL INSTRUCTIONS
• Plumbing Connections:
Inlet / Outlet: 3/8" (9.5 mm) OD tube (“push-in” quickconnect), 3/8” (9.5 mm) barb or 1/2” (12.7 mm) barb
Reject: 3/8” (9.5 mm) OD tube (“push-in” quickconnect)
Tank Drain: 3/8" (9.5 mm) OD tube
(“push-in” quick-connect)
* Blend system not performance tested or certified by NSF®.
• Electrical - Rated Voltage & Power Cord Plug Type:
System Part No. EV9970-38, EV9970-85:
100 – 120VAC/50 – 60Hz - NEMA 5 – 15P
System Part No. EV9970-47:
220 – 240VAC/50 – 60Hz - CEE 7/7
System Part No. EV9970-50:
220 – 240VAC/50 – 60Hz - AS 3112
• Power Input:
Standby: 25 Watts (25W)
Flush: 60 watts (60W)
Run / Fill: 210 Watts (210W)
• Branch Circuit Protection:
10 AMP (10A) Minimum. To minimize personnel shock
hazards, install on a GFI, RCD, or equivalent protected
circuit.
TOOLS, MATERIALS & SPECIAL EQUIPMENT REQUIRED
In most cases, common hand tools and plumbing materials suitable for use with RO water are all that is needed for installing
the system. The system setup and calibration requires special equipment:
• Compressed air supply 60 psi (4.1 bar, 0.41 MPa)
minimum with Schrader® style air chuck and pressure
gauge
• Two (2) - 32 ounce or 1,000 ml graduated containers
• Stopwatch
NOTE: Please read this entire manual prior to installing and operating the system.
NOTE: Consult with your local building inspector for approval and required permits to install this system. Additional equipment
such as backflow prevention devices, seismic restraint equipment, air gaps, etc., may be required. Installation must
meet all local and national codes.
• TDS meter
• Utility knife
• Eyedropper
• 5.25% household bleach or equivalent disinfectant
PREINSTALLATION CHECKLIST
1. Can the unit be mounted within a reasonable distance of the water supply and drain facilities?
2. Is there an un-switched receptacle available for powering the system?
3. Is there adequate clearance and support to install the unit and permit access for maintenance? The total system weight
will vary based on model and storage tank selected. See Dimensions and Operating Weights (page 13) for approximate
operating weights.
4. Does the inlet water supply meet the requirements listed in the table under Influent Water Characteristics (page 1)?
5. Is there a minimum of 25 psi (1.7 bar, 0.17 MPa) pressure on a consistent basis?
SYSTEM ASSEMBLY
Do not use screws smaller than #12 (5.5 mm) for mounting the processor.
Mounting surface may require reinforcement to support processor safely. Hollow
walls, drywall and other non-structural surfaces are not suitable unless reinforced.
Processor Assembly Mounting
1. The MRS-600HE System has been provided with a wall mount bracket to allow greater installation flexibility and ease of
processor placement. If the wall mount bracket is not suitable for this specific application, the processor backplate has
four (4) mounting holes [two (2) keyhole slots, two (2) standard] on 16" (406.4 mm) centers for securing it directly to a
vertical surface.
2. Refer to Figure 9 (page 18) for dimensional information. Use this as your guide to determine the wall mount bracket
and / or processor location. If NOT installing the wall mount bracket, go to step 5.
3. Refer to Figure 1 (next page) for mounting bracket details. Position the top row of holes 19⁄16" (39.7 mm) above the top of
the processor when installed. Install the wall mount bracket to a suitable vertical surface. Use no less than four (4)- #12
(5.5 mm) fasteners to secure the bracket to the surface.
3 EVERPURE MRS600HEII SYSTEM ORIGINAL INSTRUCTIONS
SYSTEM ASSEMBLY, continued
16X .33
THRU
8.4
Figure 1. Wall Mount Bracket.
Position top row of mounting holes 19⁄16" (39.7 mm)
above the top edge of backplate.
20.0 508
17.8 452
16.6 422
15.4 391
14.2 361
5.0 127
3.1 80
4.2 107
4. Prepare to attach the processor to the wall mount bracket. Lift the processor and “hook” the metal lip of the processor
backplate over the lower lip of channel on the wall mount bracket. Go to step 6.
5. Measure and install two (2)- #12 (5.5 mm) minimum fasteners on 16". (406.4 mm) centers to engage the top edge of
the processor backplate, leaving a 1/4" (6.4 mm) gap. Lift the processor and “hook” the keyhole slots on the processor
backplate. Tighten the two (2) fasteners.
6. Install two (2)- #12 (5.5 mm) minimum fasteners in the 2" (50.8 mm) wide slots along the bottom edge of the processor backplate.
Piping / Tubing Connections
1. Refer to Figures 2 (below) and 10 (page 19) for general arrangement views of the piping, with a description of major
components and connection points. These major components and connections will be referred to in the following steps.
2. A parts kit has been provided, which includes valves and tees to configure a system bypass. Assemble the parts to the
system using the example shown in Figure 2 (below).
Figure 2. MRS-600HE System Assembly
Inlet
(From Filter System
Low TDS Outlet
(Steam Equipment)
Reduced TDS Outlet
(Coffee, Espresso, Combi-Oven
MRS-600HE
System
2SR-BW
Conditioning Cartridge
Storage Tank Drain
3/8" (9.5 mm) OD Push-In
MR-600, MR-600-1 or
MR-600F RO Cartridge
RO Reject
3/8" (9.5 mm) OD Push-In
Floor Drain. Maintain air gap per local and national codes
4 EVERPURE MRS600HEII SYSTEM ORIGINAL INSTRUCTIONS
SYSTEM ASSEMBLY, continued
3. Prepare the plumbing to accept the RO system.
Note: The product water tubing / piping and associated fittings connecting the RO product outlet to the equipment being
serviced should be food-grade material that meets NSF® Standard 51, 61, or similar, with a minimum pressure rating
of 100 psi (6.9 bar, 0.69 MPa). The product water may react with metal piping, creating a corrosive condition in addition
to imparting an objectionable taste. Plastic pipe or reinforced beverage tubing are generally very good material choices
for RO water distribution piping. The size of the product water tubing / piping should be 3/8" (9.5 mm) ID minimum.
Distances of 25 feet (7.6 m) or greater from the RO system to the equipment being serviced should be 1/2" (12.7 mm) ID
minimum.
4. Shut off the supply of water to the new or existing filtration system and relieve pressure. Connect a line from the treated
water outlet of the filtration system to the inlet of the MRS-600HE System.
5. Connect the appropriate size and type of tubing / piping and associated fittings to the corresponding MRS-600HE System
outlet connection. Route the line(s) to the equipment being serviced (i.e.; steam, espresso, coffee, etc.). Close the inlet,
outlet and bypass valves. Apply pressure to the existing filtration system and place it back into service.
6. For safety in transit, the storage tank is shipped without a precharge. Locate the Schrader® valve on the storage tank and
precharge to 48 – 50 psi (3.3 - 3.4 bar, 0.33 - 0.34 MPa) with a source of clean, dry air. See Figure 3 (below).
7. Connect a 3/8" (9.5 mm) OD tube to the reject Y-connector (labeled WASTE) located in the lower right corner of the
processor. Route the other end of the tubing to a drain nearby, securing it properly. Allow an air gap at the drain, following
any applicable local and national codes. See Figures 2 (page 4) and 4 (below).
Refer to “Reject to Drain, Maximum” under "RO Production in the Performance
Table" (page 10) to determine the maximum reject (waste) flow rate. Verify the drain has ample
capacity for this waste flow, plus all other sources of waste flow sharing this drain.
“Schrader” Valve Location
Charge to 48 – 50 psi (3.3 – 3.4 bar, 0.33 - 0.34 MPa) with clean, dry air.
Figure 4. Reject Y-Connector DetailFigure 3. Precharging Storage Tank
Waste
Connect waste line to Y-connector
and route to drain. Maintain air gap
per local and national codes.
5 EVERPURE MRS600HEII SYSTEM ORIGINAL INSTRUCTIONS
CONTROL SYSTEM OPERATION
The MRS-600HE System includes a microprocessor based
control system that monitors system conditions and controls
the system operation. A digital display panel provides
operational information and three (3) buttons provide operator
access. To follow is a list of modes and a description of each
function. Use this as a guide during startup, normal operation
and when service is required.
Operational Mode
• INITIAL POWER-UP: When power is first applied to the
system, the panel will display the system identification
with software version. After several seconds, it will
automatically transition to the MAIN SCREEN VIEW.
FIRMWARE 4.08
If the RO water pressure drops below the minimum
allowable pressure setting during DEEP FLUSHING, the
control will terminate the DEEP FLUSHING process and
remain idle until water is drawn. Once water is drawn,
the system returns to normal operation as described in
“PRESSURIZE” mode above.
RE-PRESSURIZE...
XXX PSI (BAR)
• PRESSURE LIMIT WARNING: This message indicates a
fault with the pressure sensing circuit or the detection
of pressure exceeding 114 psi (7.9 bar, 0.79 MPa). See
Troubleshooting Guide on page 15 for guidance on how to
correct this condition.
• MAIN SCREEN VIEW: When the system is in normal
operation and not operating in any of the following
operational modes, the panel will display the storage
tank water pressure.
PRESSURE XXX PSI (BAR)
• PRESSURIZE: When pressure in the storage tank drops
below the pressure “on” setting, the system will start
processing water and refill the storage tank. Once the
pressure in the storage tank rises above the pressure
“off” setting, the system will stop. Storage tank water
pressure will be displayed.
PRESSURIZE...
XXX PSI (BAR)
• DEEP FLUSHING: If the MRS-600HE System remains idle
for the programmed length of time, the control system
will automatically go into DEEP FLUSHING mode. During
this time, there will be flow to drain (reject). Remaining
flush time in seconds and storage tank water pressure
will be displayed.
DEEP FLUSHING...
XXXX S XXX PSI (BAR)
• RE-PRESSURIZE: At the start of the DEEP FLUSHING
operation, the system will repressurize to the normal
tank full pressure, then begin DEEP FLUSHING. Storage
tank water pressure will be displayed.
Under normal conditions, the pressure in the storage
tank will remain above the minimum allowable flush
pressure throughout the DEEP FLUSHING operation.
Once the DEEP FLUSHING operation ends, the system
returns to normal operation, but will not PRESSURIZE
until the storage tank water pressure drops below the
minimum allowable flush pressure. Once it runs and fills,
the system returns to operating within the normal “on”
and “off” pressure settings.
PRESSURE LIMIT
WARNING
Programming Mode
The controller has several user accessible menus. This menu
“loop” allows for adjustment of several variable parameters.
The Controller has three (3) buttons below the display for
these adjustments. In most cases, a description of the button
function is shown in the digital display area.
Once you enter the programming mode, the controller will
save your last entry upon pressing ENTER. If an adjustment
is made without pressing ENTER, the controller returns to
the main screen and the adjustment will not be saved. If a key
is not depressed for about 25 seconds, the controller exits
programming mode and returns to the operational mode.
• Press and hold any key for three (3) seconds to enter
programming mode.
• II – Press the middle key to advance to “FLUSH TIME:
XXX S” screen. Press left or right key to advance to
“PRESSURE UOM: XXX” screen.
• PRESSURE UOM: XXX - This parameter determines
whether psi or BAR will be the unit of measure used to
display the storage tank water pressure. Use the +/- keys
to adjust this value. Press ENTER to save the selected
value and advance to the next screen.
• TANK FULL P: XXX - This parameter determines the
pressure at which RO water production will stop, or turn
“off”. This setting is normally 100 psi (6.9 bar, 0.69 MPa).
Range is 70 – 100 psi (4.8 – 6.9 bar, 0.48 - 0.69 MPa) in five
(5) psi (0.3 – 0.4 bar, 0.03 - 0.04 MPa) increments. Use
the +/- keys to adjust this value. Press ENTER to save the
selected value and advance to the next screen.
• START DIFF.: XXX - This parameter determines the pres-
sure differential between the RO water production start
(“on”) pressure and stop (“off”) pressure. This setting is
normally 20 psi (1.4 bar, 0.14 MPa). Range is 10 – 25 psi
(0.7 – 1.7 bar, 0.07 - 0.17 MPa) in five (5) psi (0.3 – 0.4 bar,
0.03 - 0.04 MPa) increments. Use the +/- keys to adjust
this value. Press ENTER to save the selected value and
advance to the next screen.
6 EVERPURE MRS600HEII SYSTEM ORIGINAL INSTRUCTIONS
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.