Stop leavening specific ations
CT1SA0040101
Vers. 1.11 3/36
1.2. Interface connections
RS 485
- +
PWM
-
LCD
Sw1
Sw2
Sw5
Sw3Sw4
PWM terminal is a 0/10 Volt (1 kHz) output used for the phase cut control of the evaporator fans. This control is
enabled by a parameter. For more details about its functioning see paragraphs 16.4 and 23.2.
Sw6
2. USER INTEFACE
2.1. Keys
NAME DESCRIPTION
SW1 ON-STANDBY key
SW2 ENTER key
SW3 MENU key
SW4 DECREASE key
SW5 INCREASE key
SW6 START/STOP key
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 4/36
3. GENERAL DESCRIPTION
This card provides the s top-rising cell control. Some automatic program s, a manual program and a cell pre-cooling
cycle are available.
Each automatic program consists of five phases: stop rising, preservation, awakening, rising and slowing down.
The manual program consists of three phases: cooling, heating and climatization.
4. POWER SUPPLY
When the ca rd is on, the s tring “ EVCO s .r .l.” will be shown for eight s ec onds , and then the car d will go in the Off mode,
in stand-by or in a cycle mode, depending on the mode it was in when it was switched off.
The string “EVCO s.r.l.” can be replaced with a neutral string: simply set up parameter P1 = zero.
5. OFF
If the card is on Off mode, the LCD display will show the following string:
Press the ON-STANDBY key to switch the card on.
Press the MENU key to view the firmware ID for three seconds.
Regardless from the mode the card is in, by keeping the ON-STANDBY key pressed for thr ee seconds the card will
return to the Off mode.
OFF_
6. SWITCHING ON
Current date and time will be shown on the display when the card is in standby mode.
The card status after a blackout depends on param eter P10 for the automatic param eters and parameter P12 in the
case of manual programs.
The meaning of the parameter is:
P10 = 0 (P12=0): the current cycle will only resume if the duration of the blackout in question was shorter than the
value set up by way of parameter P9 (P11), otherwise the card will go in standby mode.
P10 = 1 (P12 =1): the current cycle will always start again after a blackout.
02/03/2006
Tue 17:35
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 5/36
7. PRESET CYCLES
The seven automatic cycles are preset for each day of the week:
When the car d is in standby, press START/STOP f or three seconds to automatically start the program related to the
day of the week on which the activation was performed. For instance, if, on a Wednes day, you keep the START/STOP
button pressed for three seconds, program P3 will start automatically.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 6/36
8. MANUAL CYCLE
The manual cycle consists of the following three phases:
• cooling
• heating
• climatization.
Each phase is independent and no automatic switch from a phase to another phase is available.
When the machine is in standby mode, press the MENU k ey and select the MANUAL m enu by way of the INCREASE and
DECREASE keys, as follows:
Press ENTER to access the Manual Cycle setting mode. By way of the INCREASE and DECREASE keys, you can
switch from a phase to another. The cycle phase will be shown on the display, as follows:
Manual
Refrigeration
Press ENTER to select a phase and the following setpoint will be shown on the display:
Press ENTER to access the change mode. The value in question will start blinking. Use the INCREASE and
DECREASE keys to change the value, as follows:
Press ENTER to conf irm the setup value, which will stop blinking. You can now go to the hum idity setpoint (if present)
and change it as follows:
Press ENTER to confirm. The number will stop blinking.
Press MENU to return to the phase selection and change the setpoint of the other phases.
Press START/STOP to run the selected phase; the display will show:
The first line shows that the heating phase of a manual cycle is being running and that it is 13:39.
The second line shows the temper atur e in the cell ( 5°C in this cas e) , whether the use of the humidity probe is enabled and
the humidity percentage measured by the probe (63% in this case).
Press the MENU key to return to the display and set change, if any. By pressing the MENU key again you can view the
current phase. Use the START/STOP keys to start a new phase of the manual cycle.
T= 26°CRH= 80%
T= 27°CRH= 81%
Heating
Heating
T=25°CRH=80%
Manual13:39
T= 5°C%rH= 63%
Menu 01
Manual
Manual
Heating
Heating
Manuale
AirCon
Heating
T= 27°CRG= 80%
Heating
T= 27°CRH= 82%
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 7/36
9. AUTOMATIC CYCLE
There are 7 programs available, P01… P07, and each automatic cycle consists of the following five phases:
• stop rising
• preservation
• awakening
• rising
• slowing down
At the end of each phase, the next phase will start automatically.
When the machine is in standby mode, press the MENU key and select the AUTOMATIC menu by way of the
INCREASE and DECREASE keys, as follows:
Press ENTER to access the automatic cycle selection mode. Use the INCREASE and DECREASE k eys to switch from
a program to another. The program number will be shown on the display, as follows:
Press ENTER to access the selected program -setting m ode. This f unction is available only if parameter P69 = 1. Us e
the DECREASE key to switch from one phase to another. T he display will show the cycle phase and the present setpoint
values:
Press ENTER to enter the change mode; the HOUR will start blinking and you can use the INCREASE and
DECREASE buttons to change it:
Press ENTER to confirm. The number will stop blinking and you can now modify the minutes:
Press ENTER to confirm. The number will stop blinking and you can now modify the temperature:
P2EndProg
P2 Preservation
P2 Rising
12:4530°C80%
P2 Rising
12:4530°C80%
P2 Rising
13:4730°C80%
Automatic
P1
19:45
2°C
Menu 02
Automatic
P2 Rising
13:4530°C80%
P2 Rising
13:5030°C80%
Automatic
P7
P2 Locking
04:00 - 5°C
P2 Awakening
12:3020°C80%
P2 Slowing
20°C70%
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 8/36
P2 Rising
13:5029°C80%
Press ENTER to confirm. The number will stop blinking and you can now modify the humidity setpoint (if present):
P2 Rising
13:5028°C78%
Press ENTER to confirm. The number will stop blinking.
Use the INCREASE and DECREASE buttons to select the other phases and modify their setpoints.
Press MENU to save the progr am and retur n to the previous m enu. Press the ST ART/ST OP k ey to start the program.
The display will show:
This means that, bas ed on the settings done, the program will f inish on 3 April 2006. If this is the desired date for the
end of the program, press the ST ART/STOP key to confirm and s tar t the progr am. Otherwise press ENTER to change the
date of the end of the program. This function is enabled if parameter P70 = 1.
The display will show:
The DAY will start blinking and you can use the INCREASE key to change the date of the end of the progr am. Press
ENTER to confirm the new date, then press the START/STOP key to start the cycle.
EndProg
Mon03/04/06
EndProg 09 :05
Mon03/04/06
P2 Rising
13:5028°C80%
P2 Rising
13:5028°C75%
10. RUNNING AN AUTOMATIC CYCLE
During an automatic cycle the display will show:
This includes the number of the current program , the ongoing phase, the current temperature in the cell and whether
the phase provides probe-humidification, other than the percentage of humidity.
Press the INCREASE key to see both date and time of the c urr ent end of phas e; pres s the INCREASE key to see both
the date and the time of the next end of phase.
The display will show:
Where F0 shows that the program 0 phase is now running, namely the stop phase.
The other phases are identified as follows:
F1 = preservation
F2 = awakening
F3 = rising
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 9/36
P2 Locking
T= 19°C
End F009:00
Mon 03/04/06
F4 = slowing down
Press the MENU key or wait for 10 seconds to return to the previous screen.
Press MENU to see the status of INPUT/OUTPUT:
Press MENU or wait for 5 seconds to return to the previous screen.
Press ENTER to display date and time:
Press MENU or wait for 5 seconds to return to the previous screen.
Press the START/STOP key at any time to stop the cycle. The cycle will remain selected.
08/02/2007
Mar 17:35
CDERVHU
1001100
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 10/36
11. PRE-COOLING CYCLE
You can run a pre-cooling cycle before executing any manual or automatic cycle.
While the m achine is in standby mode, press the MENU key and select the COOL m enu using the INCREASE and
DECREASE keys:
Press ENTER to access the temperature SetPoint change mode, as follows:
Press ENTER to access the change mode. The value in question will start blinking. Use the INCREASE and
DECREASE keys to change the value:
Press ENTER to confirm the setup value; the number will stop blinking. Press the START/STOP key to start the cycle.
With fans managing with output relay (parameter P45 = 0), during a pre cooling, the fans are activated parallel to
compressor.
With the fans pr oportional m anaging (param eter P45 = 1), during a pre c ooling, the fans have the speed s et up by the
parameter P58 when the compressor is on, otherwise the fans are off.
display will show:
The first line shows that a cooling cycle is running and that it is 06:18.
The second line shows that the temperature in the cell is -6°C.
Press MENU to return to SetPoint change.
SetTemperature
-11°C
Cool 06:18
T= -6°C
Menu 03
Cool
SetTemperature
-12°C
SetTemperature
-12°C
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 11/36
12. START DEFROST
While the card is in standby mode you can run a defrost cycle.
While the machine is in standby mode, press the MENU key and select the DEFROST menu using the INCREASE and
DECREASE keys:
Press ENTER to access the defrost request.
Press ENTER to exit the menu. No defrost will start.
Press INCREASE to start a defrost cycle.
NoOk
Menu 04
Defrost
Start?
13. TIME SET
While the machine is in standby, press MENU and select the Set Tim e menu using the INCREASE and DECREASE
keys:
Press ENTER to access the time change mode.
The blinking num ber can be m odified by the INCREASE and DECREASE buttons. Press ENTER to c onfirm and m ove
on to the next setting.
Press MENU to return to the Home Menu.
Menu 05
Set Time
Mon 16/11/06
14:22:46
14. DAYLIGHT SAVING TIME
While the m achine is in standby, press MENU and select the DAYLIGHT SAVING TIME menu using the INCREASE
and DECREASE keys:
Press ENTER to modify the hour.
Press the INCREASE and DECREASE keys to change the hour. Press ENTER to confirm.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 12/36
Daylight Saving
Menu 06
Sun 17:52
+1
Press MENU to return to the Home Menu.
15. LANGUAGE SELECTION
While the machine is in standby, press MENU and select the Language menu using the INCREASE e DECREASE
keys:
Press ENTER. The display will show this message, in the first language available:
Use the INCREASE and DECREASE keys to acces s the other languages . When the desired language appears on the
display, press ENTER to confirm it or the MENU key to exit without changing the configuration.
Menu 07
Language
Language
Italiano
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 13/36
16. SETUP MENU
While the m achine is in standby, press MENU and select the SETUP menu using the INCREASE and DECREASE
keys:
When you press ENTER, you will be asked to enter the necessary password to access the setup submenus.
Select your password using the INCREASE and DECREASE keys and press ENTER.
The default password is -19.
If your password is correct, the first submenu will be displayed; otherwise you will exit from the menu.
Press MENU to return to the Home Menu.
The submenu windows are:
Press the INCREASE and DECREASE keys to scroll through all submenus on the display.
Press ENTER to access each submenu.
Press the MENU key to go back to the Home Menu.
Setup 01
Parameters
Setup 02
Input/Output
Setup 03
Reset
Setup 04
Fans Min Max
Password0
Menu 08
Setup
Set
Parameters setup
Inputs and Outputs status
Default values reset
Min and Max Fans speed
Setup
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 14/36
16.1. Parameters
Press ENTER to access the parameter setup mode.
The first line of the display shows the first parameter with its current value and its unit of measurement.
Use the INCREASE and DECREASE keys to scroll through all the control parameters.
Press ENTER to access the parameter change:
Use the INCREASE and DECREASE keys to change the parameter value. Press ENTER to confirm.
Press the MENU key to go back to the Home Menu.
P01 = -5°C
P01 = -5°C
-5
16.2. Inputs/Outputs
Press ENTER to access the input/output display mode and use the INCREMENT and DECREMENT keys to scroll
through the quantities to be displayed:
DI1 Digital Input 1 status
DI2 Digital Input 2 status
FAN fans speed
C compressor
D defrost
E solenoid valve or
light
R resistances
V fans
H steam generator
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 15/36
16.3. Default parameter reset
Press ENTER to access the request for the default parameter reset.
Press ENTER to exit the menu without resetting the parameters.
Press the INCREASE key to reset the parameters.
Restore?
NoOk
16.4. Fan speed adjustment
Press ENTER to access the fan speed adjustm ent function, where you can select the minim um and max imum speed
and the minimum speed during the dehumidification phase (present only if the humidity probe has been selected).
Use the INCREASE and DECREASE keys to scroll through the submenus. Press ENTER to enable the value change:
The value will start blinking and you can change it by pressing the INCREASE and DECREASE keys.
Press ENTER to confirm the value.
Press the MENU key to go back to the Home menu.
Min speed
0%
Min speed
16%
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 16/36
17. STEAM GENERATOR
There is an output available to activate a steam generator. T his output will be switched on for every phase requiring
the humidification phase, apart from any P32 parameter value (selection of the humidification mode).
If parameter P72 has value 0, opening the door will result in no ef fe ct; if par am eter P72 has value 1, when the door
is opened the steam generator will be switched off.
If you are using a pot inside the cell, it is advisable not to connect this output and to control the pot through the
humidifier output.
18. HUMIDIFICATION
Opening the door will immediately switch off the Humidification output.
There are three control m odes for cell hum idity generation and control, which can be selected by setting parameter
P32 (see the following paragraphs).
18.1. Humidification without humidity probe
By setting P32 = 1 or 2, the humidity probe will be enabled and the humidification control will occur as follows.
P32 = 1A time control without the probe will occur. Two parameters are used, P34 and P35. Parameter P34
establishes the complete duration of the humidifier on/off cycle while P35 defines the duration of the
humidifier activation cycle when a humidity percentage equal to 100% has been set.
Example:
P34 = 60 seconds and P35 = 50 seconds, setup percentage = 60%
The humidifier is ac tive for 30 sec onds (60% of param eter P35) and then stays off for 30 s econds (P34-
60% of P35). The cycle then starts again.
% P35
P34
Inizio fase
Humidity injection is interrupted if the tem perature in the cell is lower than the value determined by parameter P31 for
both the manual and automatic cycles.
P32 = 2A time control for a maximum of 10 minutes will occur. During the program setting, you will have to
choose a number between 0 and 10, meaning the m inutes of humidif ication. Parameter P33 determ ines
the pause between two humidifier-on cycles. The hum idif ier will rem ain on for the preset tim e and then go
stay off for the pause period (param eter P33). The cycle will then start again. If the pause time is 0, the
humidifier will always remain on, regardless of the preset time.
% P35
P34
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 17/36
T On
Inizio fase
P33
T On
P33
Where T On is the preset number of minutes of activation.
Humidity injection is inhibited if the temperature in the cell is lower than the value determ ined by parameter P31 for
both the automatic and manual cycles.
18.2. Humidification with humidity probe
You can enable the humidity probe by setting parameter P32 = zero.
The humidifier output switching on/off follows the following curve.
Setpoint
Setpoint-zm
Setpoint-zm-ist
Setpoint-zm-bp
Sonda Umidità
tempo
Umidificazione
Zona a reg. Propor
Zona a reg. Propor
Where:
Setpoint is the preset humidity setpoint
Zm is the dead zone for humidification (parameter P38)
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 18/36
bp is the proportional adjustment band (parameter P39)
ist is the humidification adjustment hysteresis (parameter P37)
This function is always active during the awakening, ris ing and slowing down phases, but it can also be enabled for the
stop and preservation phases by way of parameter P36.
Regarding the manual cycle, the humidification is only active during the heating and climatization phase.
In case the temperature in the cell is lower than parameter P31, the humidification function will be disabled.
If you are using a pot in the cell, the humidifier control time must be set in minutes and parameter P41 must be = 1.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 19/36
19. DEHUMIDIFICATION
This function is always active when the humidity probe is enabled. By setting parameter P32 = zero, the humidity probe
will be enabled. Dehumidification occurs by using the solenoid valve and the compressor switching on or by setting
parameter P71 = 2, when output K3 can be used to control a humidity extraction fan or a dehumidifier..
19.1. Dehumidification with compressor
This type of dehumidification is possible when parameter P71 is different from 2.
The graphs below display the management modes.
Case 1
Setpoint
Setpoint+zm+ist
Setpoint+zm
Setpoint
Elettrovalvola
Compressore
On
Off
On
Off
P44
P29
Sonda Umidità
tempo
The solenoid valve is switched on for a per iod of time determined by parameter P44. If within this time the humidity
probe drops below the setpoint + dead zone value, the solenoid valve will switch off and the com press or will switch on for
the ‘on’ enforced time determined by parameter P29.
If the probe drops below the setpoint + dead zone value before time P44 is over, the solenoid valve will switch off and
the compressor will switch on for the period of time determined by parameter P29.
If parameter P71 is set at 1 (output K3 does not manage the s olenoid valve, only the light in the cell), dehumidific ation
will only require the compressor, which will be activated P44 seconds after the dehumidification request.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 20/36
Case 2
Setpoint
Setpoint+zm+ist
Setpoint+zm
Setpoint
Elettrovalvola
Compressore
On
Off
On
Off
P44
P29
Sonda Umidità
tempo
The solenoid valve is switched on for a per iod of time determined by parameter P44. If within this time the humidity
probe drops below the setpoint + dead zone value, if the setpoint + dead zone value is not reached within this time, the
solenoid valve will remain on and even the com press or will switch on until the setpoint + dead zone value is reached, then
the solenoid valve will go off and the compressor will remain on for the ‘on’ enforced time determined by parameter P29.
If the temperature in the cell is lower than parameter P31, dehumidification will be disabled.
If parameter P71 = 1 (output K3 does not m anage the solenoid valve, only the light in the cell), dehumidification will
only require the compressor, which will be activated P44 seconds after the dehumidification request.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 21/36
19.2. Dehumidification without compressor
If parameter P71 is set at 2, when the humidity probe exceeds the preset setpoint output K3 is activated for the
dehumidification, as illustrated in the graph below.
Setpoint
Setpoint+zm+ist
Setpoint+zm
Setpoint
Deumidificatore
On
Off
Sonda Umidità
tempo
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 22/36
20. CELL TEMPERATURE ADJUSTMENT
Refer to the following graphic for the resistance and compressor switching on/off.
Both compressor and resistance activation are always enabled for all phases.
Setpoint+zmf+istf
Setpoint+zmf
Setpoint
Setpoint-zmc
Setpoint-zmc-istc
Temperatura
Cella
tempo
Resistenze
Compressore
On
Off
On
Off
Where:
Setpoint is the adjustment setup set for the ongoing phase
zmf is the cold dead zone for the ongoing phase
istf is the cold adjustment hysteresis (parameter P15)
zmc is the hot dead zone for the ongoing phase
istc is the hot adjustment hysteresis (parameter P21)
Never switch on resistances during the stop and preservation phases of an automatic cycle or during the refrigeration
phase of a manual cycle. Resistances must be switched on for a minimum time, determined by parameter P30.
During the awakening and rising phases, the temper ature inc reas e is adj usted by dividing the temper ature ar ea by n steps
(which are preset by means of param eter s P24 and P25) s o that the heating will be gradual according to setpoints that are
close to the desired value, as follows:
If the temper ature in the cell is 5°C at the awakening start, the setpoint that has been preset for the awakening phas e is
25°C, the number of steps is 4 and the duration of the phase is 40 m inutes; resistances work for 10 m inutes at the 10°C
temperature setpoint, for 10 m inutes at the 15°C temperature setpoint, for 10 m inutes at the 20°C temperature setpoint
and for the last 10 minutes at the 25°C temperature setpoint.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 23/36
Compressor ac tivation may be enforced at the beginning of the awakening and rising phases ; the duration of such
enforced activation is determined by parameter P29.
Compressor activation is subject to the safety times (parameters P26, P27 and P28)
21. SOLENOID VALVE
Only present if P71 = 0. When P71 = 0, P44 must be configured correctly.
The solenoid output is always activated together with the compressor, except for when compressor activation is
enforced, which happens at the beginning of the awakening and rising phases (the solenoid will remain disabled). The
solenoid is also used whenever the cell requires dehumidification (see paragraph 19).
22. LIGHTS
The light output (present if param eter P71 has value 1) will be switched on when you open the door and switched off
when you close the door.
23. EVAPORATOR FAN CONTROL
You can choose the fan control output from one of the relay outputs and a phase cut output. This is done by means of
parameter P45. If P45 = 0, fan c ontrol will be perform ed by output LOAD5. In this case, you can also establis h whether is
subject to the activation of the compressor and/or the resistances or if they must always remain on. If P45 = 1, a
proportional adjustment through the phase cut will be chosen.
23.1. Relay output control (P45 = 0)
If you select the control simultaneous mode, fans will be activated at the same time as the compressor and/or
resistances, but will be switched off with a delay determined by parameter P54. During the pauses, in case of
simultaneous operation, fans will be cyclically switched on according to the value of two parameters (P55 and P56).
Example of simultaneous operation subject to the compressor.
Compressore
Ventole Evap
P54
If parameters P55 e/or P56 are = zero, fans will remain off.
Pause/working time will always be reset when a cycle is started.
Opening the door will immediately switch off the fans.
P56P56P55P55
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 24/36
23.2. Phase cut control (P45 = 1)
Refer to the following graphic regarding the fans.
Setpoint+zmf
Setpoint
Setpoint-zmc
Temperatura Cella
tempo
Vel Max
Ventilazione
Vel Min
Where:
Setpoint is the preset adjustment setpoint for the ongoing phase
zmf is the cold dead zone for the ongoing phase
zmc is the hot dead zone for the ongoing phase
Based on the temperature in the cell regarding the setpoint, fans will be kept at the maximum speed or will be
proportionally adjusted according to the difference between the cell temperature and the setpoint.
The minimum speed (equal for all phases) is configurable by the parameter P57.
The maximum speed is c onf igur able f or eac h phase ( f or manual or automatic cycle) by the parameters P79, P80, P81,
P82, P83, P84, P85, P86.
If a dehumidification cycle starts during the fan proportional adjustment, the minimum speed will no longer be
determined by parameter P57 but by parameter P59 and the fans will remain on even if the door is opened.
24. DEFROST
Defrost is active only during the stop and preservation phases of the automatic cycle and during the refrigeration phase
of the manual cycle. It can also be switched on by selecting its own menu. Both the automatic and the manual defrost will
only occur if the evaporator probe temperature is lower than parameter P60.
The defrost mode is subject to parameter P73:
If parameter P73 = 0, during the defrost output K2 will be switched on.
If parameter P73 = 1, during the defrost both output K1 and output K2 will be switched on.
Fans are activated according to the value of parameter P64.
The defrost cycle, if automatic, is repeated regularly (parameter P61), and each defrost cycle may finish as follows:
•as soon as the parameter P62 time elapses
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 25/36
•alternatively, when the evaporator probe is higher than parameter P60.
All defrost cycles will be interrupted when passing from the preservation phase to the awakening phase of an automatic
cycle.
At the end of the defrost cycle, you must wait for the end of the dripping tim e (parameter P63) before switching the
compressor on, and for the end of the fan stop time (parameter P63+P64) before switching the fans on.
Regarding compressor activation, safety time (parameters P26, P27 and P28) is still the priority.
Opening the door will not stop the compressor, but will cause the fans to go off, regardless of P64.
25. SIGNALS AND ALARMS
Both visual and acoustic signals will be given in case of malfunction. Below is the complete list of alarms/signals.
Cell probe
In case of a probe breakdown, a cell probe alarm will be given: the buzzer will sound and the display will show an error.
The ongoing cycle will be interrupted and all outputs will be switched off. Press any key to silence the buzzer. The cycle
will resume as soon as the error disappears.
Safety thermostat
The thermostat input is set by parameter P8:
P8= 0: thermostat alarm on = open contact
P8= 1: thermostat alarm on = closed contact
As soon as the card detects an alarm: the buzzer will sound and the following alarm will be shown on the display:
The ongoing cycle will be interrupted and all outputs will be switched off . Press any key to silence the buzzer. As soon
as the error disappears, press the ON-STANDBY key to reset the card.
Evaporator probe
A probe breakdown will c ause an Evaporator Probe breakdown Alarm : the buzzer will sound and the following alarm
will start blinking on the display:
The ongoing cycle will be interrupted and all outputs will be switched off. Press any key to silence the buzzer. The cycle
will resume as soon as the error disappears.
High Temperature in the Evaporator
When P75=1, the high tem perature alarm of the evaporator is enabled; if the evaporator probe reaches the value of
P74, the evaporator high temperature alarm will go off. The buzzer will sound and the display will show:
ALL CellSensor
ALL Thermostat
ALL EvapSensor
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 26/36
ALL Evap High T
Qualsiasi ciclo in corso viene blocc ato e tutte le uscite disattivate. Il buzzer si può tacitare premendo qualsiasi tasto.
Alla scomparsa dell’errore premere il tasto ON-STANDBY per riarmare la scheda.
Humidity probe
A probe breakdown causes a hum idity probe breakdown alarm the buzzer will sound and the following alarm word will
be blinking on display:
ALL HumiditySensor
The ongoing cycle will be interrupted and all outputs will be switched off. Press any key to silence the buzzer. The cycle
will resume as soon as the error disappears.
This signal is valid only if the humidity probe has been enabled by means of parameter P32.
Door micro switch
The door micro switch input is set through parameter P7:
P7 = 0: closed door = closed contact
P7 = 1: closed door = open contact
Each time the door is opened, the words ‘open door’ will start blinking:
Door open
When the door is opened during a quick cooling cycle, the fan, the resistances and the humidifier will stop; the
compressor and the steam generator will go off if parameter P72 has value 1 (otherwise they will remain on).
The buzzer will sound; press any key to silence it. The signal will automatically disappear as soon as the door is closed.
If parameter P71 has value 1, every time you open the door the light will be switched on.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 27/36
RTC malfunction
In case of RTC m alfunction, an RTC alarm will be shown; the buzzer will sound and the following alarm message will
start blinking on display:
ALL RTC
The ongoing cycle will be interrupted and all outputs will be switched off. Press any key to silence the buzzer.
Access the Time Set menu and set the RTC current values: the card will return to the standby mode.
EEPROM alarm
In case of discrepancies in the data saved in Eeprom, an Eeprom alarm will be displayed; the buzzer will sound and the
following alarm message will start blinking on the display:
ALL EEPROM
The ongoing cycle will be interrupted and all outputs will be switched off. Press any key to silence the buzzer. Press the
ON-STANDBY key to reset the card: the card will return to the standby mode.
Note: After an Eeprom alarm occurs, all parameters will be reset to the default values.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 28/36
26. CONFIGURATION PARAMETERS
26.1. List of Parameters
NAME DESCRIPTION MIN MAX DEF UNIT
General Configurations
Display selection if power on
P1
0 = none
1= EVCO s.r.l.
P2 0 = Cel sius 1 = Fahrenheit 0 1 0 --P3 Cel l probe offset -15 15 0 °C
P4 Evaporator probe offset -15 15 0 °C
P5 Humidity probe lower threshold 0 P6 0 %
P6 Humidity probe upper threshold P5 200 100 %
Input polarity for door contac t
P7
0 = NC
1 = NO
LV input polarity for thermostat
P8
0 = NC
1 = NO
P9 Power down duration for automatic program res et 1 60 15 minutes
P10
P11 Power down duration for manual program res et 1 60 15 minutes
P12
Selection after power down for automati c program
0 = an automatic cycl e starts again only if power down is less than P 9 minutes
1 = an automatic cycl e al ways s t arts again
Status selecti on af ter power down for the manual program
0 = a manual cycle start s again only if power down is less than P11 mi nut es
1 = a manual cycle always start s again
0 1 1
0 1 0
0 1 1
0 1 1
0 1 1
---
---
---
---
---
Setpoint
P13 Cold Min setpoint -30 P14 -3 °C
P14 Cold Max setpoint P13 90 15 °C
P15 Cold hysteresis 2 10 3 °C
P16 Cold dead zone for refrigeration, stop and preservation 0 10 1 °C
P17 Cold dead zone for heating, awakening and risi ng 0 10 3 °C
P18 Cold dead zone for clim at i zation and slowing down 0 10 1 °C
P19 Hot Min setpoint 0 P20 0 °C
P20 Hot Max setpoint P19 90 35 °C
P21 Hot hysteresis 2 10 3 °C
P22 Hot dead zone for heating, awakening and ris i ng 0 10 1 °C
P23 Hot dead zone for clim atization and slowing down 0 10 3 °C
P24 Number of steps for resistance adjustment in the awakening phase 1 10 3 --P25 Number of steps for resistance adjustment in the rising phase 1 10 3 ---
Compressor Timing
P26 Delay between two successi ve compressor activat i ons 0 60 2 minutes
P27 Delay between compressor activation and switch-off 0 60 2 mi nutes
P28 Compressor switch-on delay from power on 0 255 2 minutes
P29
Compressor enforced switc hi ng on duration at the awakening, rising and slowing
down phase start
0 60 0
minutes
Resistance Timing
P30 Resistance ac t i vation minimum time 0 255 0 seconds
Humidification and dehumidification
P31 Cell temperature lower limit for humidifi cation/dehumidific ation 0 90 10 °C
P32
P33 Pause time if P32 = 2 0 60 10 mi nuts
P34 Humidification cycle duration if P32 = 1 30 600 60 seconds
P35 Max. humidification t i me if P32 = 1 0 P34 30 s econds
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 29/36
Humidity control mode
0 = with humidity probe
1 = time cycles bas ed on t he setup percentage
2 = one-minute steps
0 2 0
__
Enables the humidifi cation cycle during the stop phas es of rising and
P36
P37 Hysteresis f or humidification 1 100 5 %
P38 Humidifica t i on dead zone 0 100 2 %
P39 Proportional Adjust ment Band for Humidif i cation 0 20 10 %
P40 Cycle time f or Humidification Proport i onal Adjustment 1 255 30 seconds/minutes
P41
P42 Dehumidification hysteresis 1 100 5 %
P43 Dehumidific at i on dead zone 0 100 13 %
P44 Duration of Dehumidification attempt with solenoid valve 1 255 1 seconds
preservation phases
0 = disabled
1 = enabled
Time base for Cycle Time in proportional regulation humidifying
0 = seconds
1 = minutes
---
0 1 0
---
0 1 0
Fans
P45
P46
P47
P48
P49
P50
P51
P52
P53
P54 Evaporator fan off delay in simultaneous operation 0 255 1 minutes
P55 Evaporator fan working tim e i n simultaneous operation 0 255 3 minutes
P56 Evaporator fan pause time in simultaneous operat i on 0 255 1 minutes
P57 Evaporator fan minimum speed 0 100 0 %
P58 Evaporator fan speed during pre cooli ng cycle P57 100 100 %
P59 Evaporator fan minimum speed during dehumidi f i cation P57 100 20 %
Evaporator Fan Proportional Adjustment Enabling
0 = ON/OFF adjustment
1 = proportional adjustment
Evaporator fan operation for rising s top
0 = simultaneous operation
1 = continuous operation
Evaporator fan operation for preservation
0 = simultaneous operation
1 = continuous operation
Evaporator fan operation for awakening
0 = simultaneous operation
1 = continuous operation
Evaporator fan operation for rising
0 = simultaneous operation
1 = continuous operation
Evaporator fan operation for slowing down
0 = simultaneous operation
1 = continuous operation
Evaporator fan operation for refrigeration
0 = simultaneous operation
1 = continuous operation
Evaporator fan operation for heating
0 = simultaneous operation
1 = continuous operation
Evaporator fan operation for climatization
0 = simultaneous operation
1 = continuous operation
0 1 0
0 1 0
0 1 0
0 1 1
0 1 1
0 1 1
0 1 0
0 1 1
0 1 1
--
--
--
--
--
--
--
--
--
Defrost
P60 Evaporator temperature for defrost end -40 99 2 °C
P61
P62 Defrost cycle max. duration 1 120 30 minutes
P63 Dripping time 0 30 2 minutes
P64 Fan status during the defrost cycle 0 1 0 -P65 Fan stop duration after dri ppi ng 0 15 3 minutes
Time between two consecutive defrost cycles
0 = no defrost will be repeated
0 10 6
ore
Cooling
P66 Minimum setpoint for cooling -30 P67 -3 °C
P67 Maximum setpoint for cooling P66 30 10 °C
P68 Cooling preset P66 P67 2 °C
Program setting and change
P69 Enable program setting 0 1 1 -P70 Enable program change 0 1 1 --
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 30/36
P71 K3 management: 0 = solenoid valve; 1= light; 2 = dehum i di fication 0 2 1 -P72
P73 Defrost mode: 0 = resistances; 1 = hot gas 0 1 1 --
P74 Evaporator high temperat ure al arm 0 70 55 °C
P75 Enable evaporator high tem perat ure al arm: 0 = not enabled; 1= enabled 0 1 1 -P79 Maximum evaporator fans s peed i n heating P57 100 100 %
P80 Maximum evaporator fans speed in air conditioningP57 100 100 %
P81 Maximum evaporator fans speed in blockP57 100 100 %
P82 Maximum evaporator fans speed in preservationP57 100 100 %
P83 Maximum evaporator fans speed in awakingP57 100 100 %
P84 Maximum evaporator fans speed in risingP57 100 100 %
P85 Maximum evaporator fans speed in slowing downP57 100 100 %
P86 Maximum evaporator fans speed in coolingP57 100 100 %
Compressor managem ent with door open: 0 = no effect; 1 = switch of f
compressor
0 1 0 --
NOTE
• Check the compressor protection time, as it is zero by default.
• Parameters P5 and P6 are used to establish the humidity probe range. Parameter P5 must be equal to the
humidity percentage corresponding to 4mA and parameter P6 must be equal to the humidity percentage
corresponding to 20mA.
•Check the automatic and manual program humidity setpoint after changing parameter P32
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 31/36
27. APPENDIX
27.1. General Description of the Synoptic
Using the serial RS485 com munication port you can connect a synoptic which will display temperature and hum idity in
the cell and the status of the ongoing program.
The four available models diff er from each other in the dimensions of the display and the position of the LEDs, m ore
precisely:
Code EVC25T007XXX00
DY3
DL1
DL2
DL3
DY1
DL4
DY2
DL9
DL8
DL5DL6DL7
DL10
Temperature/humidity display (DY1, DY2, DY3) H20 mm and synoptic SOFT.
Code EVC25T007XXX02
DY3
DL1
DL2
DY1
DY2
DL9
DL8
DL10
DL11DL12
DL13
DY4
DL11
DL12
DL13
DL3
DL4
DL5
DL6
DL7
DY4
Temperature/humidity display (DY1, DY2, DY3) H20 mm and synoptic HARD.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 32/36
Code EVC25T007XXX01
DY3
DL1
DL2
DL3
DY1
DL4
DY2
DL9
DL8
DL5DL6DL7
DL10
Temperature/humidity display (DY1, DY2, DY3) H13 mm and synoptic SOFT.
Code EVC25T007XXX03
DY3
DL1
DL2
DY1
DY2
DL9
DL8
DL10
DL11DL12
DL13
DY4
DL11
DL12
DL13
DL3
DL4
DL5
DL6
DL7
DY4
Temperature/humidity display (DY1, DY2, DY3) H13 mm and synoptic HARD.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 33/36
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 34/36
27.4. Visualization
DISPLAY DY1
Displays the temperature in the cell.
This is on during the cooling phase of a manual cycle, in the locking phase of the rising and during the preservation
phase of an automatic cycle.
DISPLAY DY2
Displays the relative humidity in the cell.
It will remain on during all phases which require humidity control.
DISPLAY DY3
Displays the temperature in the cell.
This is on during the heating and air conditioning phase of a manual cycle and in the awakening, rising and s lowing
down phases of an automatic cycle.
DISPLAY DY4 UNIT
Displays date and time.
Displays date, month and real time with the card in standby or manual cycle.
Displays date, month and end of cycle time if the ongoing cycle is automatic.
LED SERIES
•MANUAL CYCLE
Cooling
DL1, DL2, DL3, DL4, DL5, DL6 and DL7 on during cooling phase configuration.
DL1, DL2 on, DL3 blinking during cooling phase if the temperature setpoint was not reached.
DL1, DL2, DL3, DL4, DL5, DL6, DL7 on during a cooling phase if the temperature setpoint was reached.
Heating
DL7, DL8, DL9, DL10, DL11 on during heating phase configuration.
DL7, DL8 on, DL9 blinking during heating phase if the temperature setpoint was not reached.
DL7, DL8, DL9, DL10, DL11 on during a heating phase if the temperature setpoint was reached
Air conditioning
DL11, DL12, DL13 on during air conditioning phase configuration.
DL11 on, DL12 and DL13 blinking during air conditioning phase if the temperature setpoint was not reached.
DL11, DL12, DL13 on during an air conditioning phase if the temperature setpoint was reached.
•AUTOMATIC CYCLE
Blocking
DL1, DL2, DL3 on during blocking phase configuration.
DL1, DL2 on, DL3 blinking during blocking phase if the temperature setpoint was not reached.
DL1, DL2, DL3 on during a blocking phase if the temperature setpoint was reached.
Preservation
DL3, DL4, DL5, DL6, DL7 on during preservation phase configuration.
DL4, DL5 on, DL6, DL7 blinking during preservation phase if the temperature setpoint was not reached.
DL4, DL5, DL6, DL7 on during a preservation phase if the temperature setpoint was reached.
Awakening
DL7, DL8, DL9 on during awakening phase configuration.
DL8 on, DL9 blinking during awakening phase if the temperature setpoint was not reached.
DL8, DL9 on on during an wakening phase if the temperature setpoint was reached.
Rising
DL9, DL10, DL11 on during rising phase configuration.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 35/36
DL10 on, DL11 blinking during rising phase if the temperature setpoint was not reached.
DL10, DL11 on during a rising phase if the temperature setpoint was reached.
Slowing down
DL11, DL12, DL13 on during slowing down phase configuration.
DL12 on and DL13 off during slowing down phase if the temper ature setpoint is equal to or higher than the
temperature setpoint of the rising phase.
DL12 off and DL13 on if the temperature setpoint is lower than the preset temperature setpoint for the ris ing
phase.
NOTE: The LEDs which refer to concluded phases will remain on while the next phases are running.
Stop leavening specific ations
CT1SA0040101
Vers. 1.11 36/36
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.