EVCO c-pro nano RACK User Manual

PROGRAMMABLE CONTROLLERS FOR
MONO AND BI-CIRCUIT
COMPRESSOR PACKS
UP TO 4 COMPRESSORS
APPLICATION MANUAL
CODE 144RACKNUE05
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
Important
Read carefully these instructions before installation and use and follow all the directions for the installation and for the electrical connection; keep these instructions together with the tool for future consultation.
The tool must be disposed of according to the local regulation regarding collection of electrical and electronic equipments.
2
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
Contents
1 GENERALITIES............................................................................................................................................ 5
1.1
Description ............................................................................................................................................. 5
2 Applications.................................................................................................................................................... 7
2.1
Application 1a: use of C-PRO NANO RACK (monocircuit compressor pack) ................................... 8
2.2
Application 1b: use of C-PRO MICRO RACK (monocircuit compressor pack) .................................. 9
2.3
Application 2a: use of C-PRO NANO RACK with expansion of I/O C-PRO EXP MICRO (bi-circuit
compressor pack with single condensation).................................................................................................... 10
2.4
Application 2b: use of C-PRO MICRO RACK with expansion of I/O C-PRO EXP MICRO (bi-circuit
compressor pack with single condensation)..................................................................................................... 11
2.5
Application 3a: use of C-PRO NANO RACK with expansion of I/O C-PRO EXP MICRO (bi-circuit
compressor pack with separated condensation). ............................................................................................ 12
2.6
Application 3b: use of C-PRO MICRO RACK with expansion of I/O C-PRO EXP MICRO (bi-
circuit compressor pack with separated condensation). ................................................................................. 13
2.7
Electrical connections of control units................................................................................................. 14
2.8
C-PRO EXP MICRO electrical connection ......................................................................................... 17
3 Elements and fittings network...................................................................................................................... 19
3.1
Example for C-PRO NANO RACK..................................................................................................... 19
3.2
Example for built-in versions of C-PRO MICRO RACK.................................................................... 20
3.3
Example for blind versions of C-PRO MICRO RACK ...................................................................... 21
4 USER INTERFACE..................................................................................................................................... 22
4.1
Display and keyboard........................................................................................................................... 22
4.2
Pages list............................................................................................................................................... 26
4.3
Conditioned visibility........................................................................................................................... 29
5 Configuration parameters............................................................................................................................. 31
5.1
Parameters configuration list................................................................................................................ 32
6 ADJUSTMENTS.......................................................................................................................................... 46
6.1
Configuration of the machine............................................................................................................... 46
6.2
Status of the machine and of the single circuits................................................................................... 47
6.3
Adjustment of the compressors............................................................................................................ 48
6.3.1 Sideband adjustment....................................................................................................................... 48
6.3.2 Neutral zone adjustment................................................................................................................. 49
6.3.3 Sideband adjustment with inverter................................................................................................. 50
6.3.4 Neutral zone adjustment with inverter ........................................................................................... 51
6.4
Management of the compressors.......................................................................................................... 52
6.4.1 Rotation of the compressors........................................................................................................... 52
6.4.2 Management of throttlings ............................................................................................................. 54
6.4.3 Protection timings........................................................................................................................... 55
6.4.4 Safety inputs................................................................................................................................... 55
6.4.5 Inverter configuration..................................................................................................................... 56
6.4.6 Compressors with different power ................................................................................................. 57
6.4.7 Compensation for load losses on the suction line .......................................................................... 58
6.4.8 Throttling of the refrigerating power at high pressures.................................................................. 58
6.5
Adjustment of condensation................................................................................................................. 60
6.5.1 Sideband adjustment....................................................................................................................... 60
6.5.2 Neutral zone adjustment................................................................................................................. 61
6.5.3 Sideband adjustment with inverter................................................................................................. 61
6.5.4 Neutral zone adjustment with inverter ........................................................................................... 62
6.5.5 Single condensation (only bi-circuit) ............................................................................................. 63
6.6
Management of the fans ....................................................................................................................... 63
3
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
6.6.1 Rotation of the fans ........................................................................................................................ 63
6.6.2 Fan timings..................................................................................................................................... 64
6.6.3 Safety inputs................................................................................................................................... 65
6.6.4 Inverter configuration..................................................................................................................... 65
6.7
Various management issues ................................................................................................................. 66
6.7.1 Digital input or supervisor setpoint variation................................................................................. 66
6.7.2 Manual function.............................................................................................................................. 66
6.7.3 Floating condensation management............................................................................................... 67
6.7.4 Temperature probes........................................................................................................................ 67
6.7.5 Restoration of default parameters................................................................................................... 68
6.7.6 Programming key ........................................................................................................................... 68
7 DIAGNOSTICS ........................................................................................................................................... 69
7.1
Manual and automatic alarms............................................................................................................... 69
7.2
Alarms Table........................................................................................................................................ 70
7.3
Alarm relays ......................................................................................................................................... 72
8 List of the MODBUS variables.................................................................................................................... 73
4
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
1 GENERALITIES
1.1 Description
This application uses control units of C-PRO NANO and C-PRO MICRO line for management of a refrigerator compressor pack composed by one or two circuits with maximum number of 4 compressors. The function required to a refrigerator compressor pack’s control system is the management of the compressors for the maintenance of the evaporation pressure up to the wished value; in deeper words it must assure the production of cold, for example for foodstuffs’ conservation. Therefore it is required the continuous generation of cold through an action that must take place without interruptions, unless for normal maintenance operations.C-PRO NANO and C-PRO MICRO control units are extremely careful to these aspects managing all the circuit’s parts with the best possible efficiency (better efficiency output = less operation costs), handling the mechanical tools in the best way, for breakdown reduction (for example less trimming = less mechanical stress). For the control of pressure or temperature it is possible to choose between two setting types:
Sideband Neutral zone
For each circuit the safeties are managed in order to signalize promptly the possible malfunctions. To each safety it is associated a particular alarm that will be signalized in order to identify the type of breakdown. Some alarms will consequently block the mechanical devices in order to avoid further breakdown. Other alarms, as a result, will only signalize without taking any measure over the machine’s operation. The application has a navigable user inteface whereby it is possible defining and setting all the configuration and operation parameters divided into four main levels:
User Maintenance operative Installer Contructor
Each level is protected by a different password. On contructor’s level the user inteface displays a range of editable configuration templates (wizard) that allow to set easily the number of circuits, compressors, fans and the respective safeties that we want to use in order to protect the mechanical devices. There is always a TTL output for the connection to RICS supervision system (through aTTL/RS-485 user interface) or to other BMS.
5
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
C-PRO NANO RACK
C-PRO MICRO RACK
Built-in version
C-PRO MICRO RACK
Blind version
C-PRO MICRO RACK
Open version
6
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
2 Applications
It is possible connecting to the control unit a 6 relays expansion through IntraBus proprietor protocol
It is supposed the management of three types of compressor pack:
1) Application 1: C-PRO NANO RACK or C-PRO MICRO RACK (for monocircuit compressor
packs)
Total of digital outputs = 6 Total of digital inputs = 5 Total of analogue inputs = 4 Total of analogue outputs = 2 PWM (+2 optional ones).
2) Application 2: C-PRO NANO RACK or C-PRO MICRO RACK + C-PRO EXP MICRO
expansion (for bi-circuit compressor packs with single condensation)
Total of digital outputs = 12 Total of digital inputs = 10 Total of analogue inputs = 8 Total of analogue outputs = 2 PWM (+2 optional ones) .
3) Application 3: C-PRO NANO RACK or C-PRO MICRO RACK + C-PRO EXP MICRO
expansion (for bi-circuit compressor packs with separated condensation)
Total of digital outputs = 12 Total of digital inputs = 10 Total of analogue inputs = 8 Total of analogue outputs = 2 PWM (+2 optional ones).
7
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
2.1 Application 1a: use of C-PRO NANO RACK (monocircuit
compressor pack)
According to default setting, C-PRO NANO RACK is configured to manage monocircuit refrigerator compressor packs; the uses shown in the drawing below just refer to default settings.
8
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
2.2 Application 1b: use of C-PRO MICRO RACK (monocircuit
compressor pack)
According to default setting, C-PRO MICRO RACK is configured to manage monocircuit refrigerator compressor packs; the uses shown in the drawing below just refer to default settings.
9
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
2.3 Application 2a: use of C-PRO NANO RACK with expansion of I/O
C-PRO EXP MICRO (bi-circuit compressor pack with single condensation)
According to default setting, C-PRO NANO RACK is configured to manage monocircuit compressor packs; the uses shown in the drawing below refer to an example of bi-circuit compressor pack with single condensation.
The power supplies of C-PRO NANO RACK and of C-PRO EXP MICRO must be galvanically insulated
among them
10
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
2.4 Application 2b: use of C-PRO MICRO RACK with expansion of
I/O C-PRO EXP MICRO (bi-circuit compressor pack with single condensation).
According to default setting, C-PRO MICRO RACK is configured to manage monocircuit compressor packs ; the uses shown in the drawing below refer to an example of bi-circuit compressor pack with single condensation.
The power supplies of C-PRO MICRO RACK and of C-PRO EXP MICRO must be galvanically
insulated among them.
11
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
2.5 Application 3a: use of C-PRO NANO RACK with expansion of I/O
C-PRO EXP MICRO (bi-circuit compressor pack with separated condensation).
According to default setting, C-PRO MICRO NANO is configured to manage monocircuit compressor packs ; the uses shown in the drawing below refer to an example of bi-circuit compressor pack with separated condensation.
The power supplies of C-PRO NANO RACK and of C-PRO EXP MICRO must be galvanically insulated
among them.
12
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
2.6 Application 3b: use of C-PRO MICRO RACK with expansion of I/O
C-PRO EXP MICRO (bi-circuit compressor pack with separated condensation).
According to default setting, C-PRO MICRO RACK is configured to manage monocircuit compressor packs ; the uses shown in the drawing below refer to an example of bi-circuit compressor pack with separated condensation.
The power supplies of C-PRO MICRO RACK and of C-PRO EXP MICRO must be galvanically
insulated among them.
13
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
2.7 Electrical connections of control units
Here follows the layout of control units connection with tables concerning the inputs and outputs meaning.
C-PRO NANO RACK connections
C-PRO MICRO RACK connections
14
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
Connector 1 of C-PRO NANO RACK: Connection for relay outputs ; in brackets the use
that is associated according to default setting
Conn. Abbreviation Description
C1-1 DO4 Normally open contact relay n.4 (fan 2) C1-2 D03 Normally open contact relay n. 3 (fan 1) C1-3 COMMON 1 Common relay n.1,2,3,4 C1-4 DO5 Normally open contact relay n.5 C1-5 DO2 Normally open contact relay n.2 (compressor 2) C1-6 DO1 Normally open contact relay n.1 (compressor 1) C1-7 COMMON 1 Common relay n.1,2,3,4 C1-8 COMMON 1 Common relay n.1,2,3,4
C1-9 COMUNE DO5 Common relay n.5 (not used) C1-10 Not used Not used C1-11 DO6 Normally open contact relay n.6 (global alarm)
Connector 1 of C-PRO MICRO RACK: Connection for relay outputs; in brackets the use
that is associated according to default setting
Conn. Abbreviation Description
C1-1 DO1 Normally open contact relay n.1 (compressor 1)
C1-2 COMMON DO1 Common relay n.1
C1-3 DO2 Normally open contact relay n.2 (compressor 2)
C1-4 COMMON DO2 C Common relay n.2
C1-5 DO3 Normally open contact relay n.3 (fan 1)
C1-6 COMMON DO3 Common relay n.3
C1-7 DO4 Normally open contact relay n.4 (fan 2)
C1-8 COMMON DO4, DO5 Common relay n.4,5
C1-9 DO5 Normally open contact relay n 5 (not used) C1-11 DO6 Normally open contact relay n.6 (global alarm) C1-12 COMMON DO6 Common relay n.6
Connector 2: Connection for the key of parameters upload/download and/or output for RS485
module
15
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
Connector 3: Connector for the anlogical output (optional, not available in the open versions)
Conn. Abbreviation Description( V+I Version)
C3-1 AO2 0-10Vdc
C3-2 GND Common analogue output
C3-3 AO3 4-20mA
Description (I+I Version)
C3-1 AO2 4-20mA
C3-2 GND Common analogue output
C3-3 AO3 4-20mA
Description (V+V Version)
C3-1 AO2 0-10Vdc
C3-2 GND Common analogue output
C3-3 AO3 0-10Vdc
Connector 4: Connector for low tension signals; in brackets the use that is associated according to
default setting
Conn. Abbreviation Description
C4-1 12Vac (Power) Power supply of the tool (12Vac/dc)
C4-2 Not connected Not connected
C4-3 GND Common analogue and digital inputs
C4-4 GND Common analogue and digital inputs
C4-5 AI4 Analogue input n.4 (input for 0/4-20 mA transducer; discharging
pressure)
C4-6 AI3 Analogue input n.3 (input for 0/4-20 mA transducer; suction
pressure) C4-7 AI2 Analogue input n.2 (input for NTC probe; external temperature) C4-8 AI1 Analogue input n.1 (input for NTC probe; room temperature) C4-9 12Vac (Power) Power supply of the tool (12Vac/dc)
C4-10 12Vdc Current transducer and cut-off module power supply (50 mA max.
not protected against short circuits)
C4-11 PWM Pulses output for phase cut module C4-12 DI5 Digital input n.5 (high pressure at discharging staus of circuit 1) C4-13 DI4 Digital input n.4 (thermal protection of fan 2) C4-14 DI3 Digital input n.3 (thermal protection of fan 1) C4-15 DI2 Digital input n.2 (thermal protection of compressor 2) C4-16 DI1 Digital input n.1 (thermal protection of compressor 1)
Connector 5: Connector for the remote keyboard and expansion of I/O
Conn. Abbreviation Description
C5-1 12Vdc Power supply of remote keyboard (12 V DC 50 mA max.; not
protected against short circuits)
(Note: the possible expansion has to be supplied locally ) C5-2 GND Common C5-3 DATA Voltage serial
16
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
2.8 C-PRO EXP MICRO electrical connection
Here follows the layout of connection of C-PRO EXP MICRO expansion with tables concerning the inputs and outputs meaning. Consult the hardware manual for the references about the connection cables’ maximum lenght.
C-PRO EXP MICRO connections
Connector 1: Connection for relay outputs
Conn. Abbreviation Description
C1-1 DO7 Normally open contact relay n.7 C1-2 COMMON DO7 Common relay n.7 C1-3 DO8 Normally open contact relay n.8 C1-4 COMMON DO8 C Common relay n.8 C1-5 DO9 Normally open contact relay n.9 C1-6 COMMON DO9 Common relay n.9 C1-7 DO10 Normally open contact relay n.10 C1-8 COMMON DO10,
Common relay n.10, 11
DO11
C1-9 DO11 Normally open contact relay n.11
C1-11 DO12 Normally open contact relay n.12 C1-12 COMMON DO12 Common relay n.12
Connector 2: Connector for low tension signals
Conn. Abbreviation Description
C2-1 12Vac (Power) Power supply of the tool (12Vac/dc) C2-2 Not connected Not connected C2-3 GND Common analogue and digital inputs C2-4 GND Common analogue and digital inputs C2-5 AI8 Analogue input n.8 (for 4-20 mA transductors) C2-6 AI7 Analogue input n.7 (for 4-20 mA transductors) C2-7 Not connected Not connected C2-8 Not connected Not connected
17
C-PRO NANO RACK AND C-PRO MICRO RACK APPLICATION MANUAL
C2-9 12Vac (Power) Power supply of the tool (12Vac/dc)
C2-10 12Vdc Transducers’ power supply (50 mA max. not protected against short
circuits)
C2-11 PWM Pulses output for phase cut module C2-12 DI10 Digital input n.10 C2-13 DI9 Digital input n.9 C2-14 DI8 Digital input n.8 C2-15 DI7 Digital input n.7 C2-16 DI6 Digital input n.6
Connettore 3: Connector for control unit device
Conn. Abbreviation Description
C3-1 12Vdc Power supply C3-2 GND Common C3-3 DATA Voltage serial
18
3 Elements and fittings network
3.1 Example for C-PRO NANO RACK
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
3.2 Example for built-in versions of C-PRO MICRO RACK
Page 20
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
3.3 Example for blind versions of C-PRO MICRO RACK
Page 21
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
4 USER INTERFACE
4.1 Display and keyboard
There are two interface typologies for the application:
a 4 display interface with 7 Built-In segments. a remote 4 display interface with 7 segments.
They both have 4 keys for navigation/editing of the pages and they are different in the display through icons (built-in) or in the display through led (remote) of some associated sites.
For both typologies there will be a description of the keys and of the leds used by the application, in fact, according to the interface used, it is possible to manage a different quantity of keys and leds.
Local Built-In interface
The built-In interface is integrated directly in the control unit used.
C-PRO NANO RACK
C-PRO MICRO RACK
Built-in version
Page 22
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
In the keyboard there are 4 keys for pages navigation and values editing with the following meaning:
- UP and DOWN: parameters modification in editing; otherwise menu and parameters shift. If we
are in alarms pages display mode, everytime we press it, it makes all the active alarms shift, otherwise it shows the “none” default word in order to signalize the absence of alarms. Keeping UP pressed when the machine is switched on it is possible to change the probe that we want to be default displayed according to the following chart:
LP (o LP1) Suction probe (circuit 1) HP (o HP1) Discharging probe (circuit 1) LP2 Suction probe circuit 2 HP2 Discharging probe circuit 2
If we wanto to change the display, we have to scroll this chart and confirm through SET/ENTER key: the label of the probe selected will flash for a couple of seconds.
- SET / ENTER: confirmation of the value in editing; otherwise entering of controls possibly
associated to the text where there is the cursor. ENTER key, if it is kept pressed for about 2 seconds, allows to access the main menu. If we are in display of an alarm page mode, kept pressed for about 2 seconds, it allows the alarm reset.If we are in alarms pages display mode, everytime we press it, it makes all the active alarms shift, otherwise it shows the "none" default word in order to signalize the absence of alarms.
- STAND-BY / ESC: cancellation of the value in editing; otherwise default page request possibly
associated to the current page.. ESC key, if kept pressed for about 2 seconds, allows to switch on/off the machine. If we press it in the main page, it allows to enter the list of all the active alarms.
The following icons are also used:
1 2
HP LP
1
3
2
4
- Alarm icon : it identifies the possible presence of alarms. If it is switched on it means that there
are some alarms, otherwise it remains switched off. The flashing light signalizes the presence of a new alarm that has not been viewed yet.
- Stand-by icon: associated to ESC key it identifies the machine status :
Switched off: macchine switched on Switched on: machine switched off Flashing slowly: machine switched off by digital input Flashing fastly: machine switched off by supervisor
- Circuit 1 icon: it identifies the status of circuit 1 (TN):
Switched off: circuit switched off or in stand-by mode Switched on: the circuit requires power Flashing slowly: circuit switched off by digital input Flashing fastly: circuit switched off by supervisor
- Circuit 2 icon: it identifies the status of circuit 2 (BT).
Switched off: circuit switched off or in stand-by Switched on: : the circuit requires power Flashing slowly: circuit switched off by digital input Flashing fastly: circuit switchec off by supervisor
Page 23
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
- LP icon: it is active when the value of suction probe is displayed. If it flashes with alarm
icon switched on, it indicates the intervention of low pressure alarms on suction circuit or suction probe not-connected.
- HP icon: it is active when the value of discharging probe is displayed. If it flashes with
alarm icon switched on, it indicates the intervention of high pressure alarms on discharging circuit or discharging probe not-connected.
- Fans icon: it identifies the fans’ status. If it is switched on, it means that at least one fan is
switched ton, otherwise it remains switched off. If it flashes it means that at least one fan is switched on in manual function status.
- Compressors icon: it identifies the compressors’ status. If it is switched on, it means that at least one
compressor is switched on, otherwise it remains switched off. If it flashes it means that at least one compressor is switched on in manual function status. This display is alternative to the one of 1,2,3,4 icons (parameter PH51).
- Maintenance icon: it identifies maintenance request. If it is switched on it means that at least one
compressor or one fan has been manually switched on, if it flashes it means that at least one compressor or one fan has overcome the number of operation hours, otherwise it remains switched off.
- °C icon: it identifies the unit of measurement chosen. If it is switched on it indicates the
temperature selection.
- Bar icon: it identifies the unit of measurement chosen. If it is switched on it indicates the
pressure selection.
- 1,2,3,4 icons : they identify the status of the single compressors. If they are switched on, it means
that the compressor is working, if they flash slowly it means that the compressor is in alarm status, if they flash quickly there is a timing signal in progress for the next switching on or off, Otherwise they remain switched off. These icons are enabled to parameter PH51 .
Page 24
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Remote terminals
V LEDi
Panel version
V WALL
Wall version
In the keyboard there are 4 keys for pages navigation and values editing with the following meaning:
- UP and DOWN: parameters modification in editing; otherwise shift of the cursor. UP key, if it is
pressed for about 2 seconds during the display of an alarm, allows the alarm reset. If it is pressed it makes all the active alarms shift, otherwise it shows the “none” default word in order to signalize the absence of alarms.
- SET / ENTER: value confirmation in editing; otherwise entering of controls possibly associated
to the text where there is the cursor. ENTER key, if it is pressed for about 2 seconds, allows to enter the main menu.
- STAND-BY / ESC: cancellation of the value in editing; otherwise default page request possibly
associated to the current page.. ESC key, if kept pressed for about 2 seconds, allows to switch on/freeze the machine. If we press it in the main page, it allows to enter the list of all the active alarms.
The following leds are also used: :
- L1 = summer led: it identifies the status of circuit 1 (TN).
Switched off: circuit switched off or in stand-by Switched on: the circuit requires power Flashing slowly: circuit switched off by digital input Flashing fastly: circuit switched off by supervisor
- L3 = winter led: it identifies the status of circuit 2 (BT).
Switched off: circuit switched off or in stand-by Switched on: : the circuit requires power Flashing slowly: circuit switched off by digital input Flashing fastly: circuit switched off by supervisor
Page 25
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
- L4 = compressor leds: it identifies the status of the compressors. If it is switched on it means that at least
one compressor is switched on, otherwidse it remains switched off. If it flashes it means that at least one compressor is switched on or in manual function.
- L6 = alarm led: it identifies the possible presence of alarms. If it is switched on, it means that there
are alarms, otherwise it remains switched off. The flashing light signalizes the presence of a new alarm that has not been viewed yet.
4.2 Pages list
In this paragraph there will be a presentation of the main pages and of the menus contained in the
application manual. Like previously explained, the general menu is divided into four levels: user, maintenance operative, installer,constructor.
The structure of the menu is the following:
General Menu
User menu (Level 1) Maintenance Operative Menu (Level 2)
o Maintenance operative menu operation field o Maintenance operative menu manual field o Maintenance operative menu input/output field
Installer Menu (Level 3)
o Installer menu adjustments field o Installer menu compressor field o Installer menu fans field o Installer menu safeties field o Installer menu variety field
Constructor Menu (Level 4)
o Constructor menu plant field (configuration wizard) o Constructor menu hardware field o Constructor menu parameters field
Password
To each menu it is associated a level that conditions the accessibility to the various menus. To each level it is associated a password that allows to enter the various features in that particular menu, once the correct password is typed, the protected features will be able to be entered. Typing correctly a password, we have two effects:
unblocking of the correlated level unblocking of the sublevels
Each level password can be modified from the same level or from superior levels. For example from constructor level all the passwords of lower levels will be able to be modified using the proper page. The range of values that can be set by the password is -999 / 9999. If no key is pressed after 4 minutes, the password expires and it is necessary to set it again.
Main page
The main screen is different if the machine status is switched on or off:
- if the machine is switched off, the word OFF is displayed, or OFFd if the cause of the switching
off is due to supervision. If the cause of the switching off is the missing consent by digital input or OFFS if the cause of switching off is due to supervision
- if the machine is switched on, the value of suction pressure is displayed (or the label
probe is damaged or not-connected)
With the machine switched on, through UP/DOWN keys, it is possible to see the values of the various probes.
Err if the
Page 26
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Besides it is possible to see only the icons. In case of two-circuit machine, pressing UP key for about two seconds, it is possible to change over to alternate display of suction pressures of the two circuits.
General Menu
The general menu does not have any level and it is the point for entering all the other system’s menus.
USEr (USER Menu) MAin (MAINTENANCE OPERATIVE Menu) InSt (INSTALLER Menu) CoSt (CONSTRUCTOR Menu) StAt (Information on power required and supplied)
It is possible to see this menu from any point of the user interface, keeping ENTER key pressed for about 2 seconds. From this page it is possible to choose which menu go to through UP and DOWN keys and pressing ENTER key in order to confirm. Pressing ESC key from this menu we come back to the initial page if the machine is switched on or to OFF page if the machine is switched off.
User Menu
The user menu is of level 1, it is then necessary to insert the user level or higher level password in order to see/modify the parameters in this branch.
Cir1 (CIRCUIT 1 Menu) Cir2 ( CIRCUIT 2 Menu) PSd1 (USER Password)
It is possible to choose on which circuit we want to modify the setpoints and the offsets for the secondary setpoint.
Maintenance Operative Menu
The maintenance operative menu is of level 2 it is then necessary to insert the maintenance operative level or higher level password in order to see/modify the parameters in this branch.
Func (OPERATION Menu) MAnu (MANUAL Menu) CAL (CALIBRATION Menu) I-O ( I/O STATUS Menu) PSd2 (MAINTENANCE OPERATIVE Menu)
In this menu it is possible to see the status of the various devices, inputs and outputs used by the application. Entering MAINTENANCE OPERATIVE menu it is possible to see/enable characteristics concerning compressors and fans’ operation. For example the operation hours, the habilitation of the respective alarm and the maximum limit of acceptable hours.
Under MANUAL Menu it is possible to set the compressors and fans in manual/automatic mode and it is possible to force their outputs in order to test their functionality. In CALIBRATION Menu it is possible to set the correction to bring to analogue inputs in order to counterbalance the offsets due to probes’ wiring and positioning. In I/O STATUS Menu it is possible to see directly the inputs and the physical outputs of the card.
Page 27
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Installer Menu
The installer menu is of level 3, it is then necessary to insert the installer level or builder password in order to see/modify the parameters in this branch.
reG1 ( CIRCUIT 1 SETTINGS Menu) reG2 ( CIRCUIT 2 SETTINGS Menu ) CoMP (COMPRESSORS Menu) FAn (FANS Menu) SEcu (SECURITIES Menu ) Par (VARIOUS PARAMETERS Menu) MAP (PARAMETERS MAPS Menu ) PSd3 (INSTALLER Password Menu )
In installer menu there are all the parameters concerning the configuration of all the functions (alarms, adjustments, logics, rotation type, … ) of the machine.
In ADJUSTMENTS it is possible to adjust/see the parameters concerning the sideband and neutral zone thermoregulations for compressors and fans.
In COMPRESSORS and FANS menu it is possible to set the parameters concerning devices management:
rotation logic of divisions times…
In SECURITIES menu there are all the parameters regarding the alarms and securities management for compressors and fans
habilitations delays in signalling reinforcement type…
In VARIOUS PARAMETERS there are other general parameters regarding Modbus communication management, the bottom values for transducers and other habilitations that can be adjusted.
The PARAMETERS MAPS menu can be reached only from the machine in OFF status. In this menu it is possible to restore the factory parameters and to save or reload the parameters from a programming flashdrive key. After every operation it is necessary to switch off and switch on again the tool.
Page 28
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Constructor Menu
The constructor menu is of level 4, it is necessary then to insert the constructor level password in order to see/modify the parameters in this branch. Besides it can be reached only from the machine in OFF status.
ConF ( CONFIGURATION Menu) Hard (HARDWARE INPUTS/OUTPUTS Menu) ) PSd4 (CONSTRUCTOR Password)
This menu contains all the machine’s configuration parameters that decide its operation way and which functions habilitating or inhibiting according to the constructor’s needs.
The CONFIGURATION menu contains a plant configuration “wizard” to set the number of circuits, the presence of compressors or fans controlled through inverter, the number of compressors and respective divisions, the number of fans and the number of safeties to be used.
HARDWARE menus contain all the parameters for adjustment of positions to which connecting the various devices.
Compressors’ digital outputs position Fans’ digital outputs position Inverter position to be connected to analogue outputs Alarms’ digital inputs/outputs position
Note: Adjusting the positions of alarm’s various inputs, their functionality is set as well. In fact an alarm is enabled only if the parameter that identifies its physical position on the clamp is set and is different from zero. If we do not want to use an alarm, just let the corresponding parameter in zero value. The same management is used for outputs management, for example of alarm relays: if the parameters are equal to zero, the controls of the relays are disabled.
Firmware and project versions
Press buttons UP and DOWN at the same time 2 s; later, press ENTER when the label InFo is shown. The display will show in succession the information on the project and firmware versions of the controller, as follows: Project number <-> Project version <-> Project revision <-> Firmware number <-> Firmware version <-> Firmware revision. To scroll the information, use buttons UP and DOWN. To go back to the application pages, press button ESC.
4.3 Conditioned visibility
The conditioned visibility allows to hide configuration parameters and status according to particular configurations. For example: if the kind of regulation is Neutral Zone, configuration parameters about Side Band will automatically be hidden. Another example: if you have set the controller in order to control a mono-circuit compressor pack, all configuration parameters about the second circuit will automatically be hidden. In other words, all not relevant configuration parameters will not be shown by the user interface. This function make easier the set up, the maintenance and the use of the controller. During the configuration, once chosen the kind of compressor pack, not relevant configuration parameters will not be accessible. During the maintenance, you can test the device really present.
Page 29
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Last but not least, conditioned visibility allows to avoid showing plenty of parameters; the display will only show relevant configuration parameters. In the configuration parameters table, one has signalled configuration parameters which visibility depends on this function and the condition setting the visibility.
Page 30
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
5 Configuration parameters
Here are listed all the parameters managed by the application. For each parameter it is also provided a brief description of the range of values that can be admitted, of units of measurement, of default value in charge and of the menu where it is. Menus are structured according the following logic:
UT : user menu
o UT-C1: setpoint section circuit 1 o UT-C2: setpoint section circuit 2
MA: maintenance operative menu
o MA-F: operation section o MA-M: manual section o MA-CA: calibration section o MA-IO: input/output section
IS : installer menu
o IS-R1: setting section circuit 1 o IS-R2: setting section circuit 2 o IS-C: compressor section o IS-F: fans section o IS-S: safeties section o IS-V: various parameters section o IS-D: default maps section
CO : constructor menu
o CO-W: plant configuration section (wizard) o CO-Hw: hardware configuration section
Page 31
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
5.1 Parameters configuration list
Code Parameter description Default Min Max U.M. Menu Notes
SPC1
PUC1
PUC4
SPF1
PUF1
PUF4
SPC2
PUC2
PUC5
SPF2
PUF2
PUF5
PSd1 Modify the password on User level 0 -999 9999 UT
PM00
PM01 .. .. PM04
PM40
PM41 .. .. PM44
PM91
PM92
PM93
PM11 .. .. PM14
PM21 .. .. PM24
PM37
PM38 If it is in manual operation, it forces the 0 0 100.0 % MA-M Visibile if
Set the setpoint value for the suction probe of the compressors (circuit 1) Set the offset value by digital input for the use of compressors’ secondary setpoint (circuit 1) Ses the offset value by supervision for the use of compressors’ secondary setpoint (circuit 1) Set the setpoint value for the discharging probe of the fans (circuit 1) It sets the offset value from digital input for the use of fans’ secondary setpoint (circuit
1) Set the offset value by supervision for the use of fans’ secondary setpoint (circuit 1)
Set the setpoint value for the suction probe of the compressors (circuit 2) Set the offset value by digital input for the use of compressors’ secondary setpoint (circuit 2) Set the offset value by digital input for the use of compressors’ secondary setpoint (circuit 2) Set the setpoint value for the discharging probe of the fans (circuit 2) Set the offset value by digital input for the use of fans’ secondary setpoint (circuit 2) Set the offset value by digital input for the use of fans’ secondary setpoint (circuit 2)
Set in tens the maximum limit of compressors’ operation hours. Beyond this limit the respective alarm will go off.
Represent in tens the compressors’ operation hours. One for each compressor.
Set in tens the maximum limit of fans’ operation hours. Beyond this limit the respective alarm will go off.
Represent in tens the fans’ operation hours. One for each fan
Set the last date when plant’s maintenance has been done Set the last date when plant’s maintenance has been done Set the last date when plant’s maintenance has been done Enable the compressor’s manual/automatic operation: Manu: manual Auto: normal function One for each compressor If it is in manual function, it sets the number of steps to be forced to the compressor One for each compressor If it is in manual function, it forces the compressors’ inverter value of circuit 1
1.0 PC12 PC13 Bar UT-C1
0.0 -20.0 20.0 Bar UT-C1
0.0 -20.0 20.0 Bar UT-C1
15 PF12 PF13 Bar UT-C1
0.0 -20.0 20.0 Bar UT-C1
0.0 -20.0 20.0 Bar UT-C1
1.0 PC32 PC33 Bar UT-C2
0.0 -20.0 20.0 Bar UT-C2
0.0 -20.0 20.0 Bar UT-C2
15 PF32 PF33 Bar UT-C2
0.0 -20.0 20.0 Bar UT-C2
0.0 -20.0 20.0 Bar UT-C2
hours
2000 0 9999
0 0 9999
2000 0 9999
0 0 9999
2006 2000 2064 n MA-F
1 1 12 n MA-F
1 1 31 n MA-F
Auto Auto (0)
0 0 3 n MA-M
0 0 100.0 % MA-M
Page 32
Manu
(1)
x
10
hours
x
10
hours
x
10
hours
x
10
- MA-M
MA-F
MA-F
MA-F
MA-F
Visibile if
PG01 > 1
Visibile if
PG01 > 1
Visibile if
PG01 > 1
Visibile if
PG01 > 1
Visibile if
PG01 > 1
Visibile if
PG01 > 1
Visibility
*1
Visibility
*2
Visibility
*1
Visibility
*1
Visibile if
PG12 = 1
PM51.. .. PM54
PM61.. .. PM64
PM77
PM78
PM81
PM82
PM83
PM84
PM85
PM86
PSd2
PC12
PC13
PC14
PC16
PC17
PC18
PC19
PC20
PC21
PC22
PC23
PC24
PC25
PC26
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
compressors’ inverter value of circuit 2 PG16 = 1
and PG01
> 1
Enable the fan’s manual/automatic function:(Manu: manual Auto: normal function
Auto Auto (0)
Manu
(1)
- MA-M
Visibility
*2
One for each compressor. If it is in Manual function it forces the switch on/off of the fan ( 0: it switches fan
0 0 1 - MA-M
Visibility
*1 off, 1 : it switches fan on) One for each fan If it is in manual function, it forces the fans’ inverter value of circuit 1
0 0 100.0 % MA-M
Visibile if
PG42 = 1
Visibile if
If it is in manual function, it forces the fans’ inverter value of circuit 2
0 0 100.0 % MA-M
PG46 = 1
and PG01
> 1 and
PG30 = 0
Calibration of circuit 1’s suction probe of compressors
Calibration of circuit 2’s suction probe of compressors
Calibration of circuit 1’s suction probe of fans
0.0 -10.0 10.0 Bar MA-CA
0.0 -10.0 10.0 Bar MA-CA
0.0 -10.0 10.0 Bar MA-CA
Visibile if
PG01 > 1
Visibile if Calibration of circuit 2’s suction probe of fans
0.0 -10.0 10.0 Bar MA-CA
PG01>1
and
PG30 = 0
Calibration of room temperature suction probe Calibration of external temperature suction probe It modifies the password on Maintenance Operative level Minimum value of suction setpoint of circuit 1 compressors Maximum value of suction setpoint of circuit 1 Set the regulation type for management of circuit 1 compressors Integral time for sideband adjustment of circuit 1 compressors Proportional band for sideband adjustment of circuit 1 compressors Value of the Zone for neutral zone adjustment of circuit 1 compressors Differential for neutral zone operation of circuit 1 where the calculation of switching
0.0 -10.0 10.0 °C MA-CA
0.0 -10.0 10.0 °C MA-CA
0 -999 9999 n MA-F
0.1 PH01 SPC1 Bar IS-R1
2.5 SPC1 PH02 Bar IS-R1
Neutral
zone (1)
Sideban
d (0)
Neutral zone(1)
- IS-R1
600 0 999 Sec IS-R1
0.5 0 20.0 Bar IS-R1
0.5 0 20.0 Bar IS-R1
0.5 0 20.0 Bar IS-R1
Visibile if
PC14 = 0
Visibile if
PC14 = 0
Visibile if
PC14 = 1
Visibile if
PC14 = 1 on/off time of a further step varies. Minimum time of insertion for the further step of circuit 1 compressors (Neutral zone) Maximum time of insertion for the further step of circuit 1 compressors (Neutral zone) Minimum time of release for the further step of circuit 1 compressors (Neural zone) Maximum time of release for the further step of circuit 1 compressors (Neural zone) Differential for inverter operation of circuit 1 compressors Offset ,in relation to the suction setpoint, for inverter operation of circuit 1
20 0 PC21 Sec IS-R1
60 PC20 999 Sec IS-R1
10 0 PC23 Sec IS-R1
60 PC22 999 Sec IS-R1
0.5 0.0 20.0 Bar IS-R1
0.0 -20.0 20.0 Bar IS-R1
Visibile if
PC14 = 1
Visibile if
PC14 = 1
Visibile if
PC14 = 1
Visibile if
PC14 = 1
Visibile if
PG12 = 1
Visibile if
PG12 = 1 compressors Minimum value of the inverter of circuit 1 compressors
0.0 0.0 100.0 % IS-R1
Visibile if
PG12 = 1
Page 33
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
PC27
PC28
SpeedUp time for the inverter of circuit 1 compressors Time within which the inverter changes from minimum value to its maximum value for the neutral zone adjustments of circuit 1
0 0 999 Sec IS-R1
10 0 999 Sec IS-R1
Visibile if
PG12 = 1
Visibile if
PG12 = 1
compressors
PF12
PF13
PF14
PF16
PF17
PF18
PF20
PF24
PF25 PF26
PF27
PF28
Minimum value of discharging setpoint of circuit 1 fans Maximum value of discharging setpoint of circuit 1 fans Set the regulation type for management of circuit 1 fans Integral time of the sideband adjustment of circuit 1 fans Proportional band for the sideband adjustment of circuit 1 fans Value of the Zone for neutral zone adjustment of circuit 1 fans Insertion / release time for the next fan in neutral zone adjustment Differential for the inverter adjustment of circuit 1 fans Offset in relation to the suction setpoint for inverter adjustment of circuit 1 fans Minimum value of the inverter of circuit 1 fans SpeedUp time for the inverter of circuit 1 fans Time within which the inverter changes from minimum value to its maximum value for the neutral zone adjustments of circuit 1
1.0 PH03 SPF1 Bar IS-R1
25.0 SPF1 PH04 Bar IS-R1
Sideband(
0)
Sideban
d (0)
Neutal
zone(1)
- IS-R1
600 0 999 Sec IS-R1
0.5 0 20.0 Bar IS-R1
1.0 0 20.0 Bar IS-R1
10 0 999 Sec IS-R1
0.5 0.0 20.0 Bar IS-R1
0.0 -20.0 20.0 Bar IS-R1
0.0 0.0 100.0 % IS-R1
2 0 999 Sec IS-R1
10 0 999 Sec IS-R1
Visibile if
PF14 = 0
Visibile if
PF14 = 0
Visibile if
PF14 = 1
Visibile if
PF14 = 1
Visibile if
PG42 = 1
Visibile if
PG42 = 1
Visibile if
PG42 = 1
Visibile if
PG42 = 1
Visibile if
PG42 = 1
fans
PC32
PC33
PC34
Minimum value of suction setpoint of circuit 2 fans Maximum value of suction setpoint of circuit 2 fans It sets the regulation type for management of circuit 2 compressors
0.1 PH01 SPC2 Bar IS-R2
2.5 SPC2 PH02 Bar IS-R2
Neutral
zone (1)
Sideban
de (0)
Neutral
zone (1)
- IS-R2
Visible if
PG01 > 1
Visible if
PG01 > 1
Visible if
PG01 > 1
Visible if
PC36
IT integral time of the sideband adjustment of circuit 2 compressors
600 0 999 Sec IS-R2
PG01 > 1
and PC34 = 0 Visible if
PC37
PB proportional band for the sideband adjustment of circuit 2 compressors
0.5 0 20.0 Bar IS-R2
PG01 > 1
and PC34 = 0 Visible if
PC38
Value of the Zone for neutral zone adjustment of circuit 2 compressors
0.5 0 20.0 Bar IS-R2
PG01 > 1
and PC34 = 1 Visible if PG01 > 1
and PC34 = 1
PC39
Differential for the neutral zone adjustment of circuit 2, within which the calculation for switching on/off of a further step varies
0.5 0 20.0 Bar IS-R2
Visible if
PC40
Minimum time of insertion for the further step of circuit 2 compressors (Neutral zone)
20 0 999 Sec IS-R2
PG01 > 1
and PC34 = 1 Visible if
PC41
Maximum time of insertion for the further step of circuit 2 compressors (Neutral zone)
60 0 999 Sec IS-R2
PG01 > 1
and PC34 = 1
PC42 Minimum time of release for the further 10 0 999 Sec IS-R2 Visible if
Page 34
PC43
PC44
PC45
PC46
PC47
PC48
PF32
PF33
PF34
PF36
PF37
PF38
PF40
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
step of circuit 2 compressors (Neutral zone) PG01 > 1
and PC34 = 1 Visible if
Maximum time of release for the further step of circuit 2 compressors (Neutral zone)
Differential for the inverter adjustment of circuit 2 compressors
Offset in relation to the suction setpoint for inverter adjustment of circuit 2 compressors
Minimum value of the inverter of circuit 2 compressors
SpeedUp time for the inverter of circuit 2 compressors
Time within which the inverter changes from minimum value to its maximum value for the neutral zone adjustments of circuit 2 compressors
Minimum value of discharging setpoint of circuit 2 fans
Maximum value of discharging setpoint of circuit 2 fans
Set the adjustment type for management of circuit 2 fans
IT integral time of the sideband adjustment of circuit 2 fans
PB proportional band for the sideband adjustment of circuit 2 fans
Value of the Zone for neutral zone adjustment of circuit 2 fans
Insertion / release time for the next fan in neutral zone adjustment of circuit 2
60 0 999 Sec IS-R2
0.5 0.0 20.0 Bar IS-R2
0.0 -20.0 20.0 Bar IS-R2
0.0 0.0 100.0 % IS-R2
0 0 999 Sec IS-R2
10 0 999 Sec IS-R2
1.0 PH03 SPF2 Bar IS-R2
25.0 SPF2 PH04 Bar IS-R2
Sideband
(0)
600 0 999 Sec IS-R2
0.5 0 20.0 Bar IS-R2
1.0 0 20.0 Bar IS-R2
10 0 999 Sec IS-R2
Sideban
d (0)
Neutral
zone (1)
- IS-R2
PG01 > 1
and PC34 = 1 Visible if PG01 > 1
and PG16 = 1 Visible if PG01 > 1
and PG16 = 1 Visible if PG01 > 1
and PG16 = 1 Visible if PG01 > 1
and PG16 = 1 Visible if PG01 > 1
and PG16 = 1 Visible if PG01 > 1
and PG30 = 0 Visible if PG01 > 1
and PG30 = 0 Visible if PG01 > 1
and PG30 = 0 Visible if PG01 > 1
and PG30 = 0
and
PF34 = 0 Visible if PG01 > 1
and
PG30 = 0
and
PF34 = 0 Visible if PG01 > 1
and
PG30 = 0
and
PF34 = 1 Visible if PG01 > 1
and
PG30 = 0
and
PF34 = 1
Page 35
PF44
PF45
PF46
PF47
PF48
PC01
PC02
PC03
PC04
PC05
PC06
PC07
PC08
PC09
PC10
PC11
PC31
PC69
PC70
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Differential for the inverter adjustment of circuit 2 fans
Offset in relation to the suction setpoint for inverter adjustment of circuit 2 fans
Minimum value of the inverter of circuit 2 fans
SpeedUp time for the inverter of circuit 2 fans
Time within which the inverter changes from minimum value to its maximum value for the neutral zone adjustments of circuit 2 fans
Type of rotation used for compressors management: 0: FIFO 1: LIFO 2: FIFO + hours of operation 3: LIFO + hours of operation Set the trigger way of the throttlings: 0: CppCpp / ppCppC 1: CCpppp / ppppCC 2: CppCpp / ppppCC 3: CCpppp / ppCppC Set the logic of relays used for the throttlings of the compressors: 0: NC (norm. close). P. es Copeland 1: NO (norm.open). P. es. Feeders Minimum time during which the compressor must remain switched on even if the switching off is required Minimum time during which the compressor must remain switched off even if the switching on is required Minimum time that must elapse between two switching on of the same compressor Minimum time that must elapse between the switching on of two different compressors Minimum time that must elapse between the switching off of two different compressors Minimum time between the switching on of the throttlings Minimum time between the switching off of the throttlings Number of compressors that will be forced if there is an alarm over the suction probe of circuit 1
Number of compressors that will be forced if there is an alarm over the suction probe of circuit 2
Timeout of compressors’starting from reset mode Enable compressors’ throttlings at high pressures 0: NO 1: YES
0.5 0.0 20.0 Bar IS-R2
0.0 -20.0 20.0 Bar IS-R2
0.0 0.0 100.0 % IS-R2
2 0 999 Sec IS-R2
10 0 999 Sec IS-R2
0 = FIFO 0 3 n IS-C
0 =
Cpp_Cpp
1=NO 0 1 - IS-C
10 0 999 Sec IS-C
120 0 999 Sec IS-C
360 0 999 Sec IS-C
20 0 999 Sec IS-C
20 0 999 Sec IS-C
20 0 999 Sec IS-C
20 0 999 Sec IS-C
1 0
1 0
0 0 999 sec IS-C
0 (NO) 0 1 - IS-C
Page 36
0 3 - IS-C
PG11
PG15
n IS-C
n IS-C
Visible if PG01 > 1
and PG46 = 1 Visible if PG01 > 1
and PG46 = 1 Visible if PG01 > 1
and PG46 = 1 Visible if PG01 > 1
and PG46 = 1 Visible if PG01 > 1
and PG46 = 1
Visible if PG01 > 1
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
PC71
PC72
PC74
PC75 PC76 Throttling percentage value 50 0 100 % IS-C PC78
PC81 Power supplied by compressor 1 0 0 1000 kW IS-C
PC82 Power supplied by compressor 2 0 0 1000 kW IS-C
PC83 Power supplied by compressor 3 0 0 1000 kW IS-C
PC84 Power supplied by compressor 4 0 0 1000 kW IS-C
PF01
PF02
PF07
PF08
PF11
PF31
PF71 Enable floating condensation 0 = No 0 1 - IS-F PF72 Delta of condensation temperature 0.0 -20.0 20.0 °C IS-F PF73 Minimum limit of consensation setpoint 30.0 10.0 PF74 °C IS-F PF74 Maximum limit of consensation setpoint 40.0 PF73 45.0 °C IS-F
PF78
PH01
PH02
PH03
PH04
Set compressors’ throttlings pressure (circuit 1)
Set compressors’ throttlings pressure (circuit 2)
Differential of compressors’ throttlings pressure Minimum time for compressors’ throttlings maintenance
Compressors’ sideband steps overlapping factor (sideband)
Rotation used for fans management: 0: FIFO 1: LIFO 2: FIFO + hours of operation 3: LIFO + hours of operation Set if fans regulation happens only if at least one compressor is switched on on Minimum time that must elapse between the switching on of two different fans Minimum time that must elapse between the switching off of two different fans Number of fans that will be forced if there is an alarm over the discharging probe of circuit 1 .
Number of fans that will be forced if there is an alarm over the discharging probe of circuit 2.
Fans’ sideband steps overlapping factor (sideband) Set the minimum value of steps-bottom for the suction probe Set the maximum value of steps-bottom for the suction probe Set the maximum value of steps-bottom for the discharging probe Set the maximum value of steps-bottom for the discharging probe
22.0 PH03 PH04 Bar IS-C
22.0 PH03 PH04 Bar IS-C
4.0 0.1 10.0 Bar IS-C
2 0 999 Min IS-C
0 0 100 % IS-C
0 = FIFO 0 3 n IS-F
0 = No 0 1 - IS-F
2 0 999 Sec IS-F
2 0 999 Sec IS-F
1 0 PG41 N IS-F
1 0 PG45 N IS-F
0 0 100 % IS-F
-0.5 -10.0 PH02 Bar IS-V
7.0 PH01 45.0 Bar IS-V
0.0 -10.0 PH04 Bar IS-V
30.0 PH03 45.0 Bar IS-V
Page 37
Visible if PG01 > 1
Visibile if
PG03 = 1
and
visibility
Visibile if
PG03 = 1
and
visibility
Visibile if
PG03 = 1
and
visibility
Visibile if
PG03 = 1
and
visibility
Visible if PG01 > 1
and PG30 = 0
*1
*1
*1
*1
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
PH05
PH07
PH08
PH09
PH10 PH11 Modbus address of the card 1 1 247 n IS-V PH12 PH13 ModBu parity (0=none, 1=Odd, 2=Even) 2 0 2 n IS-V
PH14 StopBit ModBus (0=1bit, 1=2bit) 0 0 1 n IS-V
PH15 Restore the default of parametes‘ factory No No (0) Si (1) -
PH17
PH18
PH19
PH20
PH21
PH23
PH24
PH25
PH26
PH31
Enable the machine switching on/off pressing ESC/Stand- by key Enable the machine switching on/off from digital output Enable the single circuit’s switching on/off from respective digital output Enable the machine switching on/off from supervisor Enable the single circuits’ switching on/off by supervisor
Baud Rate of communication for the card (1=2400, 2=4800, 3=9600, 4=19200)
Set the logic of digital inputs used for alarms management: 0: Normally open NO 1: Normally close NC Set the logic of relays used for alarms 0: Normally openNO 1: Normally close NC Set the logic of digital inputs used for the management of the following functions:
- OnOff Remote global
- OnOff Remote circuits
- secondary setpoint of compressors
-secondary setpoint of fans 0: Normally open NO 1: Normally closet NC Compressors inverter consent digital output command logic =0: Energized contact-100% consent enabled =1: Energized contact-100% consent disabled Fans inverter consent digital output command logic =0: Energized contact-100% consent enabled =1: Energized contact-100% consent disabled Set the habilitation of the probe for detection of room temperature Set the habilitation of the probe for detection of external temperature Set the habilitation of secondary setpoint function by digital input Set the habilitation of secondary setpoint function by supervisor Set the type of coolant used (temperature­pressure conversion) 0: No coolant 1: R22 2: R134a 3: R404A 4: R407C
Si No (0) Si (1) - IS-V
No No (0) Si (1) - IS-V
No No (0) Si (1) - IS-V
No No (0) Si (1) - IS-V
No No (0) Si (1) - IS-V
3 1 4 n IS-V
(MAP)
NC NO (0) NC (1) - IS-V
NO NO (0) NC (1) - IS-V
NO NO (0) NC (1) - IS-V
0 0 1 - IS-V
0 0 1 - IS-V
0 = No 0 1 - IS-V
0 = No 0 1 - IS-V
0 = No 0 1 - IS-V
0 = No 0 1 - IS-V
3
R404A
Page 38
0 6 - IS-V
IS-D
Wait that the value
0 is reread
at the end
restoring
of
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
5: R410A 6: R507 Set the unit of measurement of temperature:
PH32
PH33
PH35
PH36 Load losses compensation factor 0.2 0.1 5.0 Bar IS-V
PH40
PH43
PH44
PH50
PH51
PH52
PA01 PA02 Enable the alarm of fans’ operation hours No No (0) Si (1) - IS-S PA03 PA04 Set the detection delay of expansion alarm 5 0 999 Sec IS-S
PA05 Set the activation delay of liquid level alarm 90 0 999 Sec IS-S PA06
PA07
PA08
PA09
PA10
PA11
PA12
PA14
PA15
PA16
0: °Celsius 1: °Fahrenheit Set the unit of measurement of pressure: 0: Bar 1: psi Enable load losses compensation on suction line (neutral zone) 0: NO 1: YES
Set the display in pressure or temperature 0: Pressure 1: Temperature Set the type of A/3 universal analogue input 2: NTC 3: 0-20mA 4: 4-20mA 5: reserved Set the type of A/4 universal analogue 2: NTC 3: 0-20mA 4: 4-20mA 5: reserved Set the display with the icons only 0: NO 1: YES Set the display of numeric icons 0: NO 1: YES Set the display of Evco icon 0: NO 1: YES Enable the alarm of compressors’ operation hours
Set the activation delay of high pressure suction alarms
Set the detection delay of the alarms over suction and discharging probes Set the activation delay of low pressure discharging alarm Set the activation delay of low pressure suction alarms Set the activation delay of compressor’s thermal alarm Set the activation delay of common diffrerential oil alarm and for compressors Set the rearmament type for high pressure discharging alarm Set the rearmament type for compressor’s thermal alarm Set the rearmament type for compressor’s differential oil Set the setpoint for low pressure alarm over suction probe of circuit 1 Set the differntial for low pressure alarm over suction probe of circuit 1
0 (°C) 0 1 - IS-V
0 (Bar) 0 1 - IS-V
0 (NO) 0 1 - IS-V
0 0 1 - IS-V
4
4-20mA
4
4-20mA
1 (SI) 0 1 - IS-V
1 (SI) 0 1 - IS-V
1 (SI) 0 1 - IS-V
No No (0) Si (1) - IS-S
1 0 999 Sec IS-S
5 0 240 Sec IS-S
30 0 999 Sec IS-S
30 0 999 Sec IS-S
0 0 999 Sec IS-S
10 0 999 Sec IS-S
M A (0) M (1) - IS-S
M A (0) M (1) - IS-S
M A (0) M (1) - IS-S
0.5 PH01 PA17 Bar IS-S
0.5 0.0 20.0 Bar IS-S
2 5 - IS-V
2 5 - IS-V
Page 39
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
PA17
PA18
PA19
PA20
PA21
PA22
PA23
PA25
PA26
PA27
PA28
PA29
PA30
PA31
PA32
PSd3 Set the password of Installer level 0 -999 9999 n IS-V PG01 Set the number of circuits of the machine 1 1 2 n CO-W PG02 Enable the presence of the expansion 0 = No No (0) Si (1) - CO-W PG03
PG04 PG05 Set the thermal security of the compressors 1 = Si 0 1 - CO-W
PG11 Set the number of compressors of circuit 1 2 0 4 n CO-W PG12
PG15 Set the number of compressors of circuit 2 0 0 4 n CO-W
PG16
PG30
PG32 Enable the thermal security of the fans 1 = Si 0 1 - CO-W PG41 Set the number of fans of circuit 1 2 0 4 n CO-W PG42 Enable the fans' inverter of circuit 1 0 = No No (0) Si (1) - CO-W
PG45 Set the number of fans of circuit 2 0 0 4 n CO-W
Set the setpoint for high pressure alarm over suction probe of circuit 1 Set the differntial for high pressure alarm over suction probe of circuit 1 Set the setpoint for low pressure alarm over discharging probe of circuit 1 Set the differntial for low pressure alarm over discharging probe of circuit 1 Set the setpoint for high pressure alarm over discharging probe of circuit 1 Set the differntial for high pressure alarm over discharging probe of circuit 1 Set the rearmament type for fan’s thermal alarm
Set the setpoint for low pressure alarm over suction probe of circuit 2 Set the differntial for low pressure alarm over suction probe of circuit 2 Set the setpoint for high pressure alarm over suction probe of circuit 2 Set the differntial for high pressure alarm over suction probe of circuit 2
Set the setpoint for low pressure alarm over discharging probe of circuit 2
Set the differntial for high pressure alarm over discharging probe of circuit 2
Set the setpoint for high pressure alarm over discharging probe of circuit 2
Set the differntial for high pressure alarm over discharging probe of circuit 2
Enable the management of different compressors with different power Set the number of throttlings for each compressor
Enable the inverter of compressors of circuit 1
Enable the inverter of compressors of circuit 2 Set the singular condensation for the group of the fans
4.0 PA15 PH02 Bar IS-S
0.5 0.0 20.0 Bar IS-S
2.0 PH03 PA21 Bar IS-S
0.5 0.0 20.0 Bar IS-S
20.0 PA19 PH04 Bar IS-S
1.0 0.0 20.0 Bar IS-S
M A (0) M (1) - IS-S
0.5 PH01 PA27 Bar IS-S
0.5 0.0 20.0 Bar IS-S
4.0 PA25 PH02 Bar IS-S
0.5 0.0 20.0 Bar IS-S
2.0 PH03 PA31 Bar IS-S
0.5 0.0 20.0 Bar IS-S
20.0 PA29 PH04 Bar IS-S
1.0 0.0 20.0 Bar IS-S
0 = No No (0) Si (1) - CO-W
0 0 2 n CO-W
0 = No No (0) Si (1) - CO-W
0 = No No (0) Si (1) - CO-W
0 = No 0 1 - CO-W
Visible if PG01 > 1 Visible if PG01 > 1 Visible if PG01 > 1 Visible if PG01 > 1 Visible if PG01 > 1
and PG30 = 0 Visible if PG01 > 1
and PG30 = 0 Visible if PG01 > 1
and PG30 = 0 Visible if PG01 > 1
and PG30 = 0
Visible if PG01 > 1 Visible if PG01 > 1
Visible if PG01 > 1
and PG30 = 0
Page 40
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
PG46 Enable the inverter of fans of circuit 2 0 = No No (0) Si (1) - CO-W
Set the digital output position for compressor 1
HC01
HC02
HC03
HC04
HC11
HC12
HC13
HC14
HC21
HC22
HC23
Or Set the inverter compressor consent position for circuit 1 (if circuit 1 inverter is enabled) Set the digital output position for compressor 2 Or Set the inverter compressor consent position for circuit 2 (if circuit 2 inverter is enabled) Set the digital output position for compressor 3 Or Set the inverter compressor consent position for circuit 3 (if circuit 3 inverter is enabled) Set the digital output position for compressor 4 Or Set the inverter compressor consent position for circuit 4 (if circuit 4 inverter is enabled)
Set the digital output position for the throttling 1 of compr.1
Set the digital output position for the throttling 1 of compr. 2
Set the digital output position for the throttling 1 of compr.3
Set the digital output position for the throttling 1 of compr.4
Set the digital output position for the throttling 2 of compr.1
Set the digital output position for the throttling 2 of compr.2
Set the digital output position for the throttling 2 of compr.3
1 0 14 n CO-Hw
2 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
Visible if PG01 > 1
and PG30 = 0
(13)
PWM1
Consent
(14)
PWM2
Consent
Visibility
(12 if
expansion
is
enabled);
visibility
*1
(12 if
expansion
is
enabled);
visibility
*1
(12 if
expansion
is
enabled);
visibility
*1
(12 if
expansion
is
enabled);
visibility
*1
(12 if
expansion
is
enabled);
visibility
*1
(12 if
expansion
enabled);
visibility
*1
(12 if
expansion
is
enabled);
Page 41
HC24
HC31
HC32
HF01
HF02
HF03
HF04
HF31
HF32
HA01
HA11
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Set the digital output position for the throttling 2 of compr.4
Set the analogue output position that is associated to the inverter of circuit 1’s compressors
Set the analogue output position that is associated to the inverter of circuit 2’’s compressors
Set the digital output position for fan 1 Or Set the inverter fan consent position for circuit 1 (if circuit 1 inverter is enabled) Set the digital output position for fan 2 Or Set the inverter fan consent position for circuit 2 (if circuit 2 inverter is enabled) Set the digital output position for fan 3 Or Set the inverter fan consent position for circuit 3 (if circuit 3 inverter is enabled) Set the digital output position for fan 4 Or Set the inverter fan consent position for circuit 4 (if circuit 4 inverter is enabled)
Set the position of the analogue output associated with fan inverter of circuit 1
Set the position of the analogue output associated with fan inverter of circuit 2
Set the positions of the digital output associated with the global alarm signal
Set the position of the digital output
0 0 6 (12) n CO-Hw
2 0 3 n CO-Hw
0 0 3 n CO-Hw
3 0 6 (12) n CO-Hw
4 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
1 0 3 n CO-Hw
0 0 3 n CO-Hw
6 0 6 (12) n CO-Hw
0 0 6 (12) n CO-Hw
visibility
*1
(12 if
expansion
is
enabled);
visibility
*1
The 2nd
and 3rd
outputs
need AO
expansion;
visible if
PG12 = 1
The 2nd
and 3rd
outputs
need AO
expansion;
visible if
PG01 > 1
and PG16 = 1
(13)
PWM1
Consent
(14)
PWM2
Consent
Visibility
2
*
The 2nd
and 3rd
outputs
need AO
expansion;
visible if
PG42 = 1
The 2nd
and 3rd
outputs
need AO
expansion;
visible if
PG01 > 1
and PG42 = 1
and PG30 = 0
(12 if
expansion
is enabled)
(12 if
expansion
Page 42
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
HA21
Hd01
Hd02
Hd03
Hd11
Hd12
Hd13
Hd14
Hd15
Hd16
Hd21
Hd22
Hd23
associated with the alarm signals of circuit 1
Set the position of the digital output associated with the alarm signals of circuit 1
Set the position of the digital input for the Global On/Off Switch
Set the position of the digital input relative to the secondary setpoint for the management of the compressors
Set the position of the digital input relative to the secondary setpoint for the management of the fans
Set the position of the digital input for the On/Off Switch for Circuit 1
Set the position of the digital input associated with the liquid level alarm of circuit 1
Set the position of the digital input associated with the low pressure alarm on the suction pressure regulator of circuit 1
Set the position of the digital input associated with the high pressure alarm on the discharge pressure regulator of circuit 1
Set the position of the digital input associated with the oil differential alarm for compressors of circuit 1
Set the position of the digital input associated with the common thermal alarm for the fans of circuit 1
Set the position of the digital input for the On/Off Switch for Circuit 2
Set the position of the digital input associated with the liquid level alarm of circuit 2
Set the position of the digital input associated with the low pressure alarm on the suction pressure regulator of circuit 2
0 0 6 (12) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
5 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
is enabled)
Visibile if
PG01 > 1
(10 if
expansion
is enabled)
(10 if
expansion
is enabled)
(10 if
expansion
is enabled)
(10 if
expansion
is
enabled))
(10 if
expansion
is enabled)
(10 if
expansion
is enabled)
(10 if
expansion
is enabled)
(10 if
expansion
is enabled)
(10 if
expansion
is enabled)
(10 if
expansion
is enabled); visibile if PG01 > 1
(10 if
expansion
is enabled); visibile if PG01 > 1
(10 if
expansion
is enabled);
Page 43
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
visibile if
PG01 > 1
Set the position of the digital input
Hd24
Hd25
Hd26
Hd41
Hd42
Hd43
Hd44
Hd81
Hd82
Hd83
Hd84 0 0 5(10) n CO-Hw (10 if
associated with the high pressure alarm on the discharge pressure regulator of circuit 2
Set the position of the digital input associated with the oil differential alarm for compressors alarm of the circuit 2
Set the position of the digital input associated with the common thermal alarm for the fans of circuit 2
Set the position of the digital input associated with the thermal alarm for compressor 1
Set the position of the digital input associated with the thermal alarm for compressor 2
Set the position of the digital input associated with the thermal alarm for compressor 3
Set the position of the digital input associated with the thermal alarm for compressor 4
Set the position of the digital inputs associated with the thermal alarm for fan 1
Set the position of the digital inputs associated with the thermal alarm for fan 2
Set the position of the digital inputs associated with the thermal alarm for fan 3
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
1 0 5(10) n CO-Hw
2 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
3 0 5(10) n CO-Hw
4 0 5(10) n CO-Hw
0 0 5(10) n CO-Hw
(10 if
expansion
is enabled); visibile if PG01 > 1
(10 if
expansion
is enabled); visibile if PG01 > 1
(10 if
expansion
is enabled); visibile if PG01 > 1
(10 if
expansion
is enabled);
visibility
*1
(10 if
expansion
is enabled);
visibility
*1
(10 if
expansion
is enabled);
visibility
*1
(10 if
expansion
is enabled);
visibility
*1
(10 if
expansion
is enabled);
visibility
*2
(10 if
expansion
is enabled);
visibility
*2
(10 if
expansion
is enabled);
visibility
*2
Page 44
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Set the position of the digital inputs associated with the thermal alarm for fan 4
PSd4 Constructor password 0 -999 9999 n CO-Pa
expansion
is enabled);
visibility
*2
Note. Once the parameters of the machine have been configured and at each modification of the configuration parameters, it is advised to shut off and restart the system to allow the motherboard to correctly configure itself..
(*1) Conditioned visibility compressor. Parameter visible if the compressor has been configured; in other words: if the sum of the parameters indicating the number of compressors for each circuit (enabled) PG11, PG15 is bigger or equal to the compressor indicated.
(*2) Conditioned visibility fan.
Parameter visible if the fan has been configured; in other words: if the sum of the parameters indicating the number of fans for each circuit (enabled) PG41, PG45 is bigger or equal to the fan indicated.
Page 45
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
6 ADJUSTMENTS
6.1 Configuration of the machine
Using a wizard (Constructor menu), it is possible to configure the machine with help. The first choice involves the number of circuits (1 or 2) through the parameter PG01; in the case of a bi-circuit, the choice of condensation type, either singular or separate (PG30), becomes important as does the presence or absence of expansion (PG02). These 3 parameters define the type of machine and the hardware that supports it, as is shown in the following table.
Machine type
Presence of expansion
AI1
AI2
AI3 Suction pressure
AI4
Mono-circuit
(predefined)
NO NO YES NO YES
Environment
(Room)
temperature
* Discharge temperature
External
temperature
temperature
Suction pressure
Discharge
Suction pressure
pressure
AI7 - -
AI8 - - - Number of
digital outputs Number of digital inputs
6 6 12 6 12
5 5 10 5 10
(*) Note: Temperature is transformed into pressure by selecting the type of cooling (coolant) gas that is used (parameter PH31).
Using the same wizard, the number of compressors and fans for each circuit are also set, as is the presence of the inverter for the compressors and fans, the number of throttlings and safety measures for the compressors and the activation of the fans. A check will verify whether the necessary hardware resources for the machine type are sufficient or not, generating an eventual AH01 hardware configuration alarm.
Note: Enabling the inverter for the adjustment of the compressors, the FIRST compressor will be the one controlled by the inverter, while any other subsequent compressors will be sealed (without throttlings) and will be controlled by digital relay output. Similarly, enabling the inverter for the adjustment of the fans, the FIRST fan will be the one controlled by the inverter, while any other subsequent fan with be controlled by digital relay output. For each inverter it must be configured the position of the device activation consent digital outputs.
Bi-Circuit with
singular condensation
Environment
(Room)
temperature
External
External
temperature
Suction pressure
C1
Suction pressure
C2
Discharge
pressure
C1
C2
Bi-Circuit with
separate condensation
* Discharge
temperature C1
* Discharge
temperature C2
Suction pressure
C1
Suction pressure
C2
-
Environment
(Room)
temperature
External
temperature
Suction pressure
C1
Suction pressure
C2
Discharge
pressure C1
Discharge
pressure C2
Page 46
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
6.2 Status of the machine and of the single circuits
There are multiple procedures for turning on/shutting off the unit or the single circuit:
1) By using the appropriate On/Off button (function enabled by parameter PH05)
Turning On – push the ESC button for about 2 seconds: if all other enabled conditions are present, the machine will go to “ON”. Shutting Off – push the ESC button for about 2 seconds: the machine will go to “OFF”.
2) By using the On/Off by digital input command (function enabled by parameter PH07 for the machine
and PH08 for the circuits) Turning On – close the remote On/Off contact; if all the other enabled conditions are present, the machine or single circuit will go to “ON”. Turning Off – if the remote On/Off contact is open, the machine or single circuit will go to “OFF by digital input”, represented with the saying “OFFd”.
3) Using the supervision protocol (function enabled by parameter PH09 for the machine and PH10 for the
circuits) Turning On – activate the “on” by protocol status: if all the other enabled conditions are present, the machine or single circuit will go to “ON”. Turning Off – if the “on” by protocol status is deactivated, the machine or the single circuit will go to “OFF by supervision protocol”, represented with the saying “OFFS”.
The On/Off by button status has the priority over the other two methods, indeed, the Off by digital input and by supervision protocol states can be reached only if the machine is on.
A machine that is turned off by digital input will be able to:
1 pass to the Off by button status (by pressing the appropriate button) 2 pass to the Off by supervisor status (if the digital input is open and if the Off by supervisor status is set) 3 turn on (if the digital input is closed and the Off by supervisor status is not set)
A machine that is turned off by supervision protocol will be able to:
4 pass to Off by button status (by pressing the appropriate button) 5 pass to the Off by digital input status (if it is set by means of the supervisor and if the digital input is
open)
6 turn on (if the digital input is closed and the Off by supervisor status is not set)
The machine’s On/Off button is the ESC button. The remote On/Off inputs (when they are present) are configured by means of the appropriate parameters:
1 Hd01 = position of remote On/Off digital input for the machine 2 Hd11 = position of remote On/Off digital input for circuit 1 3 Hd21 = position of remote On/Off digital input for circuit 2
Page 47
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
6.3 Adjustment of the compressors
Checking the suction pressure of the compressors implies the management of the compressors to reach and maintain a certain operating pressure value: according to the type of check (sideband adjustment or neutral zone adjustment) and the use or lack thereof of the inverter for a finer adjustment, four types of adjustment are considered.
6.3.1 Sideband adjustment
The sideband check uses the characteristics of the PI regulators (proportional and integral) or of the P regulators (proportional) to establish when to plug in or unplug the compressors being used, in order to regularize, within the differential range, the turning on or off of the various devices. The parameters relative to the first circuit are the following:
1 SPC1 = Setpoint compressors (SP) 2 PC14 = Type of adjustment = 0 3 PC16 = Integral time (TI) 4 PC17 = Sideband (BP) 5 PG11 = Number of compressors 6 PG04 = Number of throttlings
The number of compressors and the number of throttlings supplies the Maximum Number of Steps with which the proportional band is divided. The purpose of the Proportional +Integral adjustment is to obtain a null error in this type of scheme.
The image above shows the behavior of the proportional band adjustment (SP, SP +BP). Based on the value of the suction pressure, the adjustment adds or subtracts the number of steps that are required of the compressors. In this adjustment, the band is entirely moved above the setpoint.
It is possible to choose whether the check will refer to the PI or only to the P adjustment, by setting the parameter for the integral action, which is the integration time (Ti). Specifically, if this parameter is set to a value of zero, the adjustment is only proportional, otherwise it also becomes integral. The Ti corresponds to the time needed by the integral action to be equal to the proportional action, given the hypothesis of a constant error: the speed of this action is proportionally linked to the value of the integration time. The default parameter is worth 600 seconds, and so the adjustment takes advantage of the proportional + integral characteristic.
Through the PC78 Sideband steps overlapping factor, it is possible to improve the behavior of this type of adjustment, which requires wide proportional bands in order to be stable, by modifying the subdivision of the adjustment band of adjustment between the steps:
Steps
Max steps
Suction
SP SP + BP
Page 48
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Gradini
Rilascio
Inserimento
PC78 %
SP SP + BP
Max Gradini
Aspirazione
Steps will be loaded at PC78% of the proportional band; the steps will be unloaded at 100 – PC78% of the proportional band. If for example PC78 has value 60%, the steps will be loaded between 60% of the proportional band and its maximum value (100%); steps will be unloaded between 40% of the proportional band and its minimum value (0%). It appears clear that by using such a division of the steps as indicated in the image, the interval of activity of each single step is higher than the classical geometrical division, with the clear advantage that the proportional band may be diminished, to favor a higher precision of adjustment, and/or the activations of the steps occur less frequently, that is, the breakaways of the compressors decrease, favoring the mechanical duration of the compressors themselves.
6.3.2 Neutral zone adjustment
This adjustment implies the definition of a neutral zone in which no decision of activation or deactivation will be made, which means that no breakaways will be required for any device.
The parameters relative to the first circuit are the following:
7 SPC1 = Setpoint compressors (SP) 8 PC14 = Type of adjustment = 1 9 PC18 = Neutral Zone (NZ) 10 PC19 = Differential outside the neutral zone (diff) 11 PC20 = Minimum time of Turn-on (TOnMin) 12 PC21 = Maximum time of Turn-on (TOnMax) 13 PC22 = Minimum time of shutdown (TOffMin) 14 PC23 = Maximum time of shutdown (TOffMax)
Outside the neutral zone, the turn-on or shutdown requests for the various steps supplied by the compressors will follow this logic:
1 Turn-on: when the pressure of suction exceeds the threshold value setpoint + neutral zone 2 Shutdown: when the pressure goes below the setPoint
In this type of adjustment, the neutral zone is found entirely to the right of the setPoint.
TOnMax TOffMax
Switching on Switching off
TOffMin Neutral zone
TOnMin
SP SP + e SP + Zona + diff SP - diff
Page 49
Suction
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
As we can see from the figure, the adjustment foresees the setting of certain timings within which, depending on the zone, the turn-on and shutdown requests for the various steps must be adjusted to work according to established time intervals. Based on the difference between the actual suction pressure value and the reference value, the times will vary proportionally according to the values set. The reference value mentioned represents, according to the case, the right and left limit of the neutral zone with the addition of another differential (which can be set through a parameter) within which the proportional variation of the time in question will be found. At the limits of the adjustment, the values of the turn-on and shutdown times are the maximum and minimum times that are established by the parameter. To render the request time constant during the turn-on phase, it is enough to set the NZ TOnMin and the NZ TOnMaz parameters to the same value. The same thing is true for the shutdown phase.
6.3.3 Sideband adjustment with inverter
This check adds an inverter adjustment to the normal sideband adjustment; in order to do this, it is necessary to set some parameters relative to the inverter device that is to be used, besides enabling its use.
The parameters relative to the first circuit are the following:
- SPC1 = Setpoint compressors (SP)
- PC14 = Type of adjustment = 0
- PG12 = Activation of the inverter
- PC24 = Inverter differential (DI)
- PC25 = Inverter offset with respect to the suction setPoint (OFSI)
- PC26 = Minimum value of inverter (MinI)
- PC27 = SpeedUp Time
Inverter
100.00 %
MinI
SP + OFSI SP + OFSI + DI
Pressure
Based on the measured value from the suction probe, the output of the regulator will assume different values. If the value measures with the probe is less than or equal to the SP + OFSI value, the output of the regulator assumes the value 0. If the value measured with the probe is between the SP + OFSI value and the SP + OFSI + DI, the output of the regulator will assume a value which is proportional to the value of the suction probe. If the suction probe assumes a value which is higher than or equal to the SP + OFSI + DI value, the output of the inverter will assume maximum value. If the MinI parameter has been set, at every turn-on the inverter will maintain that value as a starting value. If the parameter for the speedUp time has been set, at every breakaway point the inverter will assume maximum value for the seconds described by this parameter. The range of values that the inverter output can assume lies between 0 and 100 percentage points, with two decimal numbers.
Page 50
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
out inverter
The use of this adjustment on the principal compressor is not linked to the adjustment of the other compressors, since the two functions are independent from each other.
: 4 compressors with
Example: 4 compressors with 1 inverter
Steps
Max steps
Steps
Max steps
Pressure
SP SP + BP
Inverter
100.00 %
Pressure
SP SP + BP
MinI
Pressure
SP + OFSI SP + OFSI + DI
6.3.4 Neutral zone adjustment with inverter
This check adds an inverter type adjustment to a normal neutral zone adjustment; in order to do this, it is necessary to set some parameters relative to the inverter device that will be used, besides enabling its use. The parameters relative to the first circuit are the following:
- SPC1 = Setpoint compressors (SP)
- PC14 = Type of adjustment = 1
- PG12 = Activation inverter
- PC26 = Minimum value of inverter (MinI)
- PC27 = SpeedUp Time
- PC28 = Time or ramp of inverter (TI)
The adjustment varies according to the zone (neutral, turn-on or shutdown) in which the regulator is found. In the neutral zone, the inverter is not subjected to any variation and no compressors are turned on or off. In the turn-on zone:
- as soon as it is required, the inverter is activated.
- the value of the inverter changes according to the time TI set by the parameter. This represents the time
needed by the ramp of the inverter to go from the minimum value to the maximum value.
- when the inverter reaches the required maximum value, another step is required of the compressors.
- once the request is accomplished the value of the inverter is restored to the minimum value (MinI if
different from zero)
- If the turn-on zone remains, the cycle restarts.
If the turn-on request remains, all the compressors are turned on one by one, and at the end, the value of the inverter is brought to the maximum value. In the shutdown zone:
- as soon as it is required, the output of the inverter is brought to the minimum value, according to the TI.
- when the inverter reaches the minimum value, the compressors are required to shut down another step.
- once the request for a shutdown is completed, if the shutdown zone remains, the value of the inverter is
restored to the maximum value and the cycle restarts.
Page 51
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
out inverter
If the request for a shutdown remains, all the compressors are shut down, one by one, and at the end the value of the inverter is brought to zero.
If the MinI parameter has been set, at every turn-on the inverter will keep that value as the starting value. If the parameter for the speedUp time has been set, at every breakaway the inverter will assume the maximum value for the seconds described by this parameter.
Steps
: 4 compressors with
3
2
1
Out-band. Switching on
Steps
4
Inverter
Pressure
Example: 4 compressors with 1 inverter
3
2
1
Pressure
100.00 %
Pressure
Out-band. Switching on
6.4 Management of the compressors
The program is able to manage up to a maximum of 4 compressors of equal power, divided into circuits and up to 2 throttlings for each compressor. To each compressor, certain digital inputs for safety measures and digital outputs for turn-on/shutdown and for potential throttlings may be associated.
The main configuration parameters are the following:
- PG01 = Circuit number
- PG11 = Number of compressors circuit 1
- PG15 = Number of compressors circuit 2
- PG04 = Number of throttlings
- PG05 = Activation of compressor safety measures
The management of the compressors occurs through a setPoint and a differential that can be set by a parameter and the reading of a pressure on the suction probe. Turn-on/shutdown is ensured by a thermo-adjustment and by certain timings that protect the various breakaways.
6.4.1 Rotation of the compressors
The rotation of the compressors is a procedure that makes it possible to balance as much as possible the number of functioning hours and the number of breakaways for each compressor. The rotation only refers to the compressors and not to the single throttlings, it does not involve potential compressors that have been subject to
Page 52
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
an alarm or that are in manual function mode and it is able to dynamically turn on other compressors if one or more are subject to a state of alarm. Through the PC01 parameter, the program is able to manage 4 types of rotation: FIFO, LIFO, FIFO + hours, LIFO + hours.
1) FIFO
Follows the logic “First In First Out”, or in other words, the first compressor that turns on will then be the first that must shut off. This logic could initially lead to a large difference in the hours of operation among the various compressors, but after an initial phase, the hours should approximately be equal. Example. Turn-on : C1 . C2 . C3 . C4 Shutdown: C1 . C2 . C3 . C4
This type of rotation has a particular feature in the case where all the compressors configured in the system do not turn on; in fact, if, for example, the first compressor turns on and then shuts off, the next compressor to turn on will be the second. The last compressor that shut off is memorized and the next one in sequence is turned on so that the same compressor is not always used and thus all the configured parts are taken advantage of in the best possible way.
Example with 4 compressors Turn-on : C1 . C2 . Shutdown: C1 . C2 . Turn-on : C3. C4. Shutdown: C3. C4. Turn-on : C1 . C2 . C3. C4. Shutdown: C1 . C2 . C3. C4.
2) LIFO
Follows the logic “Last In First Out”, or in other words, the last compressor turned on will be the first to be turned off. Example. Turn-on : C1 . C2 . C3 . C4 Shutdown: C4 . C3 . C2 . C1 The turn-on order will always begin with the C1 compressor.
3) FIFO + hours of operation
This rotation promotes the comparison of the hours of operation of the various compressors. During turn-on, the compressor with the least number of hours of operation will be favored, while during shutdown, the compressor with the greatest number of hours will be favored. In the case where a choice must be made among compressors that have the same number of hours, a FIFO rotation takes effect, in such a way as to in any case guarantee a rotation, even when there are the same number of hours of operation. Example. 1 Turn-on : C1(3 hours) . C2(3 hours) . C3(3 hours) . C4(3 hours) Shutdown: C1(3 hours) . C2(3 hours) . C3(3 hours) . C4(3 hours) Example. 2 Turn-on : C1(1 hour) . C2(3 hours) . C3(3 hours) . C4(5 hours) Shutdown: C4(5 hours) . C2(3 hours) . C3(3 hours) . C1(1 hour)
4) LIFO + hours of operation
This rotation promotes the comparison of the hours of operation of the various compressors. During turn-on, the compressor with the least number of hours of operation will be favored, while during shutdown, the compressor with the greatest number of hours will be favored. In the case where a choice must be made among compressors that have the same number of hours, a LIFO rotation takes effect.
Page 53
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Example. 1 Turn-on : C1(3 hours) . C2(3 hours) . C3(3 hours) . C4(3 hours) Shutdown: C4(3 hours) . C3(3 hours) . C2(3 hours) . C1(3 hours) Example. 2 Turn-on : C1(1 hour) . C2(3 hours) . C3(3 hours) . C4(5 hours) Shutdown: C4(5 hours) . C3(3 hours) . C2(3 hours) . C1(1 hour)
6.4.2 Management of throttlings
The program is capable of managing up to 4 throttled compressors. Throttling a compressor means distributing its total load over various steps, improving its function and decreasing the number of breakaways so as to ensure that the machine lasts longer.
Number of throttlings
It is possible to choose, using the parameter PG04, one or two throttlings of equal power for each compressor. Each compressor will have the same number of throttlings available. The configurations possible for the number of throttlings per compressor are clearly limited by the number of available digital outputs.
Throttling logic
If compressors subjected to throttling are being used, it is possible, through the use of the PC03 parameter, to choose the logic of operation of the outputs dedicated to throttling:
- If set to zero, the outputs will be normally excited (closed) and will be opened to request more
power: NC logic Copeland.
- If set to one, the outputs will normally not be excited (open) and will be closed to request more
power: NO logic Feeders.
Turn-on/Shutdown Mode
In the case where compressors subjected to throttling are used, the PC02 parameter makes it possible to set the turn-on/shutdown mode of the throttlings. If set to zero:
Turn-on: CppCppCpp. The program favors the complete turn-on of the single compressor before passing to the next one. Shutdown: ppCppCppC. The program favors the compete shutdown of the single compressor before passing to the next one.
If set to one:
Turn-on: CCCpppppp. The program favors first the turn-on of all compressors and only following this, will it act on the throttlings. Shutdown: ppppppCCC. The program favors first the shutdown of all the throttlings and only at the end will it shut down all the compressors.
Note. In this last case, the logic in turn-on and shutdown of the single throttlings follows this logic (example with 3 compressors): Turn-on compressors : C1 . C2 . C3 Turn-on throttlings : p1C1 . p1C2 .p1C3 / p2C1 . p2C2 . p2C3 Shutdown throttlings : p2C3 . p2C2 . p2C1 / p1C3 . p1C2 . p1C1
Page 54
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
6.4.3 Protection timings
Below, there is a list of all the timings related to the management of the compressors.
Neutral Zone Timings
These parameters serve to adjust the time intervals of the requests for turn-on and shutdown of the various steps supplied by the compressors:
Minimum time request for turn-ons Maximum time request for turn-ons Minimum time request for shutdowns Maximum time request for shutdowns
For these parameters, refer to the description in paragraph 2.2.2.
Protection timings
These times serve to protect the mechanical instruments from the various breakaways to which they are subjected.
PC04 – Minimum time turn-on of compressors. Once activated, the compressor will stay on for this amount of time before it can be shut off.
PC05 – Minimum time shutdown of compressors. Minimum amount of time that must pass after the last shutdown before the compressor can be turned on again.
PC06 – Minimum time between turn-ons of same compressor. Establishes the minimum amount of time that must pass between two turn-ons of the same compressor.
PC07 – Minimum time between turn-ons of different compressors. Establishes the minimum amount of time that must pass between the turn-on of one compressor and the next. If enabled, this serves to avoid simultaneous breakaways.
PC08 – Minimum time between shutdowns of different compressors. Establishes the minimum amount of time that must pass between the shutdown of one compressor and the next.
PC09 – Minimum time turn-on of throttlings. Establishes the minimum amount of turn-on time between the throttlings of a compressor.
PC10 – Minimum time shutdown of throttlings. Establishes the minimum amount of shutdown time between the throttlings of a compressor.
PC27 (PC47) – speedUp time. If adjustment with inverter is set, this parameter, if different from zero, allows the inverter output to remain at maximum level (100.00%) at each request for the turn-on of a new step.
6.4.4 Safety inputs
The program foresees the management of 1 safety “thermal compressor” input for each compressor. For this input, it is possible to set the type of reset (automatic or manual) and the intervention delay, through the use of parameters. To enable the alarms related to these safety measures, besides setting the parameters mentioned above as needed, it is also necessary to set the positions in which the digital inputs will be connected relative to the various types of alarm from the menu Constructor -> Hardware. In the case where there is no wish to set the alarm, all that is needed is to set the parameter mentioned above to the value of 0.
Page 55
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
6.4.5 Inverter configuration
For each inverter used in the plant must be selected also the related digital output position for the command/consent at the inverter start; For the configuration the same parameters of the compressor digital outputs are used, parameters HC01, HC02, HC03, HC04. The inverter is virtually the first compressor of each circuit; this means that, depending of the compressors and circuits number, the right parameter must be set, by following below logic:
Signle Circuit: The inverter (if enabled) is virtually the compressor 1; it is neccessary to configure the
parameter of the first compressor, this means that parameter HC01 must be always configured.
Two circuits: The inverter of circuit 1 (if enabled) is virtually the compressor 1 (this means that
parameter HC01 must be configured), and the circuit 2 inverter (if enabled) is virtually the first compressor after the circuit 1 compressors.
Note. The PH20 parameter modifies the logic for the inverter consent (managed by relay or by PWM).
Configuration examples.
1) N°1 Circuit (PG01=1), n°2 Compressors (PG11=2), Inverter enabled (PG12=1). A correct configuration is:
HC01 = 1 -> Digital output for the inverter consent
HC02 = 2 -> Digital output for the hermetic compressor command HC31 = 1 -> Analog output for the inverter command
2) N°2 Circuits (PG01=2), n°2 Compressors for each circuit (PG11=2, PG15=2), Inverters enabled (PG12=1, PG16=1). A correct configuration is:
HC01 = 1 -> Digital output for the circuit 1 inverter consent
HC02 = 2 -> Digital output for the circuit 1 hermetic compressor command
HC03 = 3 -> Digital output for the circuit 2 inverter consent
HC04 = 4 -> Digital output for the circuit 2 hermetic compressor command HC31 = 1 -> Analog output for the circuit 1 inverter command HC32 = 2 -> Analog output for the circuit 2 inverter command
3) N°2 Circuits (PG01=2), n°1 Circuit 1 compressor, n°2 Circuit 2 compressors (PG11=1, PG15=3), Only circuit 2 inverter enabled (PG12=0, PG16=1). A correct configuration is:
HC01 = 1 -> Digital output for the circuit 1 first hermetic compressor command
HC02 = 2 -> Digital output for the circuit 2 inverter consent
HC03 = 3 -> Digital output for the circuit 2 first hermetic compressor command HC04 = 4 -> Digital output for the circuit 2 second hermetic compressor command HC31 = 1 -> Analog output dor the circuit 1 inverter command HC32 = 2 -> Analog output dor the circuit 2 inverter command
4) N°2 Circuits (PG01=2), n°1 Circuit 1 compressor, n°3 Circuit 2 compressors (PG11=1, PG15=3), Inverters enabled (PG12=1, PG16=1). A correct configuration is:
HC01 = 1 -> Digital output for the circuit 1 inverter consent HC02 = 2 -> Digital output for the circuit 2 inverter consent
HC03 = 3 -> Digital output for the circuit 2 first hermetic compressor command HC04 = 4 -> Digital output for the circuit 2 second hermetic compressor command HC31 = 1 -> Analog output dor the circuit 1 inverter command HC32 = 2 -> Analog output dor the circuit 2 inverter command
Page 56
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Inverter consent with PWM
In some applications it can be necessary to command the consent of the inverters with a PWM output configuring 0% or 100%. To use this option is necessary to operate with the same logic used in the previous examples on the parameters HC0x, configuring the values according to this rule:
HC01 = 13 -> Defines that the PWM output on the controller is used for the consent
of the compressor with inverter of circuit 1
HC0x = 14 -> Defines that the PWM output on the controller is used for the consent
of the compressor with inverter or circuit 2
Note. Configurino the value 13 or 14, is used the related PWM, this means that the possibile parameters HC31, HC32, HF31, HF32 should not be configured as PWM.
6.4.6 Compressors with different power
The management of compressors with different power could be useful to be able to more precisely regulate the establishment of the final value compared to the configured setpoint. To use this management, the related parameter, enable compressors of different power (PG03), must be enabled and the parameters that represent the power of each compressor whose utilization is desired in the system must be set. The software calculates the maximum power able to be expressed from the single powers of the compressors; according to the requirements of the regulators it calculates the best combination of compressors to deliver the requested power. For a better regulation, the internal resolution of the step is multiplied by three; in this way, by using compressors with different power, there are more combinations that can match the exact power requested by the regulator. At each variation of the request, the combination of compressors is recalculated in such a way as to produce a power to be delivered that is equal or greater than that requested. Compressors manually disabled, in alarm and under protections will not take part to the computation.
Note. Enabling this function, compressors subjected to throttling or compressors with inverters are not able to be used.
Sideband Adjustment
Based on the parameters of adjustment (paragraph 2.3.1), the application will calculate the power necessary to return the pressure/temperature detected in the proximity of the desired setpoint. The required power will be calculated based on the proportional regulator or proportional + integral, while the power supplied will be given by the combination of powers of the compressors that more closely exceeds what is required.
Neutral Zone Adjustment
Based on the zone where the regulator is found, a new sequence of compressors to activate is calculated, and more precisely:
- In the neutral zone: the combination remains unchanged.
- In the turn-on zone: the combination of compressors is recalculated in order to guarantee a power that is
greater than that supplied by the previous combination.
- In the shutdown zone: the combination of compressors is recalculated in order to guarantee a power that
is inferior to that supplied by the previous combination.
The recalculation of the combinations occurs based on the timings of the neutral zone: refer to paragraph 2.3.2.
Example
Consider 3 compressors of different power and a sideband adjustment of a proportional type, with these parameters:
Page 57
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Setpoint = 0.5 bar Proportional band = 2.0 bar Power Compressor 1 = 3 kW Power Compressor 2 = 5 kW Power Compressor 3 = 10 kW
Measured Pressure
(bar)
0.5 - 0
0.6 0.9 X 3
1.0 4.5 X 5
1.3 7.2 X X 8
1.6 9.9 X 10
1.7 10.8 X X 13
2.0 13.5 X X 15
2.3 16.2 X X X 18
2.5 18 (max) X X X 18 (max)
Power Required
(kW)
Compressor 1
(3 kW)
Compressor 2
(5 kW)
Compressor 3
(10 kW)
Power Delivered
(kW)
Applying the formula of calculation for the required power, these values are obtained. Below the setpoint, the power delivered is null, above the setpoint, the power delivered is at the maximum.
6.4.7 Compensation for load losses on the suction line
In certain systems, it may be necessary to decrease the suction setpoint with the increase in the yield of coolant, to compensate for the losses of pressure along the suction line. Users, which should operate at a constant evaporation pressure, will in essence find themselves working at higher pressures when there is a higher need for cold temperatures, and vice versa. This means that, in order to guarantee the production of coldness at the desired temperature even with loads in the proximity of the nominal values, one must work with a setpoint that is appreciably lower even at partial loads, when it wouldn’t be necessary. The compensation works by introducing an offset that is able to be set, which lowers the setpoint gradually at each call of cold steps; it appears evident that this function acts with the intention of increasing the efficiency of the system, making it possible to choose a higher setpoint for lower loads. Through the PH35 parameter this function is enabled, which leads to a lowering of the setpoint by a factor of compensation for each step inserted and to an increase in the setpoint by the same value for each step released. This function is able to be activated only with adjustment in the neutral zone.
6.4.8 Throttling of the refrigerating power at high pressures
To prevent the intervention of the high condensation pressure regulator and the resultant blockage in cold production, it is possible to reduce the refrigerating power and subsequently the power of exchange at the condenser, lowering in this way the condensation pressure. This reduction is possible only with circuits that are subjected to throttling (with at least two compressors or with a compressor equipped with throttling devices). The parameters related to the first circuit for this function are the following:
- PC70 = Enables throttling at high pressures
- PC71 = Setpoint limit for pressure regulator check of condensation
- PC74 = Differential for pressure regulator check
- PC75 = Minimum maintenance time for pressure regulator throttling
- PC76 = Percentage value of throttling
Page 58
pressure
e
nabling
PC75
PC75
t
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Disch.
Set
Set-Diff
Throttling
Page 59
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
6.5 Adjustment of condensation
The management of condensation foresees control through discharge pressure fans: according to the type of control (sideband control or neutral zone control) and according to the use or disuse of the inverter for a finer adjustment, four types of adjustment are considered.
6.5.1 Sideband adjustment
Sideband control uses the characteristics of the PI regulators (proportional and integral) or the P regulators (proportional) to establish when to plug in or unplug the fans used, in order to regulate the turn-on or the shutdown of the various devices inside the differential band. The parameters relative to the first circuit are the following:
- SPF1 = Setpoint fans (SP)
- PF14 = Type of adjustment = 0
- PF16 = Integral time (TI)
- PF17 = Lateral band (BP)
- PG41 = Number of fans
The number of fans supplies the Maximum Number of Steps with which the proportional band is divided. The purpose of the PI adjustment is to obtain a null error in this scheme.
The above figure shows the behavior of the band adjustment (SP, SP +BP). Based on the value of the discharge pressure, the adjustment adds or subtracts the number of fans to be requested. In this adjustment, the band is found entirely on the setPoint.
It is possible to choose if the control will refer to the PI adjustment or only to the P adjustment, by setting the parameter for the integral action, which is the integration time (Ti). Specifically, if this parameter is set to the value of zero, the adjustment is only proportional, otherwise, it also becomes integral. The Ti corresponds to the time needed by the integral action to become equal to the proportional action, in the hypothesis of a constant error: the speed of such action is proportionally linked to the value of the integration time. The default parameter is 600 seconds, so the adjustment uses the proportional + integral characteristic.
As for the compressors, even with the sideband adjustment of the fans it is possible to improve the behavior of the adjustment band, using the parameter PF78 Sideband steps overlapping factor.
Fans
Max fans
Discharging
SP SP + BP
Page 60
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
6.5.2 Neutral zone adjustment
This adjustment implies the definition of a neutral zone in which no decision of activation or deactivation is made, which means that there will be no requests for breakaways of any devices.
The parameters relative to the first circuit are the following:
- SFC1 = Setpoint fans (SP)
- PF14 = Type of adjustment = 1
- PF18 = Neutral Zone (NZ)
- PF19 = Differential outside the neutral zone (diff)
- PF20 = Time of turn-on/shutdown (ToutNZ)
Outside the neutral zone, the requests for turn-on or shutdown of the configured fans will follow this logic:
- Turn-on: when the discharge pressure exceeds the threshold value setPoint + Neutral Zone
- Shutdown: when the pressure becomes less than the setPoint
In this adjustment, the neutral zone is found entirely to the right of the setPoint.
ToutNZ ToutNZ
Neutral zone
SP SP + Zone
Switching on Switching off
Discharging
As you can see from the figure, the adjustment implies the setting of two times, within which, depending on the zone, the requests for turn-on and shutdown of the various steps must be managed to ensure the establishment of proper time intervals. If we are in the shutdown zone, every shutdown request must wait for ToutNZ seconds before it is fulfilled. Instead, in the case of the turn-on zone, every turn-on request will have to wait for ToutNZ seconds before it is fulfilled.
6.5.3 Sideband adjustment with inverter
This check adds an inverter adjustment to the normal sideband adjustment; in order to do this, it is necessary to set some parameters relative to the inverter device that will be used, besides activating its use. The parameters relative to the first circuit are the following:
- SPF1 = Setpoint fans (SP)
- PF14 = Type of adjustment = 0
- PG42 = Inverter activation
- PF24 = Differential inverter (DI)
- PF25 = Inverter offset with respect to the suction setPoint (OFSI)
- PF26 = Minimum value of inverter (MinI)
- PF27 = Time of speedUp
Page 61
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Inverter
100.00 %
MinI
SP + OFSI SP + OFSI + DI
Pressure
Based on the value measured by the discharge probe, the output of the regulator will assume different values. If the value measured by the probe is less than or equal to the value SP + OFSI, the output of the regulator will assume the value of 0. If the value measured by the probe is between the value SP + OFSI and the value SP + OFSI + DI, the output of the regulator will assume a value that is proportional to the value of the discharge probe. If the discharge probe assumes a value that is higher than or equal to the value SP + OFSI + DI, the output of the inverter will assume maximum value. If the MinI parameter has been set, at every turn-on, the inverter will keep that value as the starting value. If the parameter for the speedUp time has been set, at every breakaway, the inverter will assume the maximum value for the seconds described by this parameter. The range of the values that the inverter output may assume lies between 0 and 100 percentage points, with two decimal numbers. The use of this adjustment on the main fan is not linked to the adjustment of the other fans, since the two functions are independent.
6.5.4 Neutral zone adjustment with inverter
This check adds an inverter adjustment to the normal neutral zone adjustment; in order to do this, it is necessary to set some parameters relative to the inverter device that will be used, besides activating its use. The parameters relative to the first circuit are the following:
31 SPF1 = Setpoint fans (SP) 32 PF14 = Type of adjustment = 1 33 PG42 = Inverter activation 34 PF26 = Minimum value of inverter (MinI) 35 PF27 = Time of speedUp 36 PF28 = Time or ramp of inverter (TI)
The adjustment varies according to the zone (neutral, turn-on or shutdown) in which the regulator is found. In the neutral zone, the inverter does not go through any change and no fans are turned on or off. In the turn-on zone:
9 as soon as it is requested, the inverter is activated. 10 the value of the inverter changes according to the time TI set by the parameter. This represents the time
needed by the ramp of the inverter to go from the minimum value to the maximum value.
11 when the inverter reaches the maximum value, the other fans are requested one by one.
If the turn-on zone remains, all the fans are turned on, one by one, and the value of the inverter stays at the maximum. In the shutdown zone:
12 as soon as it is requested, the output of the inverter is brought to the minimum value, depending on the
TI.
13 when the inverter reaches the minimum value, the fans are required to turn off, one by one.
If the request for shutdown remains, all the fans are turned off, one by one, and the value of the inverter stays at zero. If the MinI parameter has been set, at every turn-on, the inverter will keep that value as the starting value.
Page 62
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
If the parameter for the speedUp time has been set, at every breakaway, the inverter will assume the maximum value for the seconds described by this parameter.
6.5.5 Single condensation (only bi-circuit)
Single condensation makes it possible to perform the ventilation process through only one circuit. For this input, it is possible to set the type of resetting (automatic or manual) through the parameters. By setting the parameter PG30 single condensation activation, the number of circuits for the fans is forced to one, while the number of circuits chosen for the compressors remains unchanged. The single condensation will deactivate all the characteristics (alarms, fans, inverter,…) that are relative to the second circuit for the management of the fans.
6.6 Management of the fans
The program is able to manage up to a maximum of 4 fans. To each fan, a digital safety input and a digital turn­on/shutdown output may be associated.
The main configuration parameters are the following:
- PG01 = Number of circuits
- PG41 = Number of fans circuit 1
- PG45 = Number of fans circuit 2
- PG32 = Activation fan safety
The number of fans that are directly controlled by the digital output is further limited by the number of compressors (throttled or not), which means by the number of digital outputs remaining after the configuration of the compressors. It is possible to use a single condensation, which is a condensation only on one circuit, by setting the relative PG30 parameter. The management of the fans occurs through a setPoint and a differential that can be set by a parameter and the reading of a pressure on the discharge probe. Turn-on/shutdown is ensured by a thermo-adjustment and by several timings that protect the various breakaways.
6.6.1 Rotation of the fans
The rotation of the fans is a procedure that makes it possible to balance as much as possible the number of hours of operation and of breakaways for every device. The rotation does not involve any fans in a state of alarm or in manual mode and it makes it possible to dynamically turn on others if one or more of them go into a state of alarm. Using the PF01 parameter, the program is able to manage 4 types of rotation: FIFO, LIFO, FIFO + hours, LIFO + hours.
1) FIFO
It follows the “First In First Out” logic, which means the first fan turned on will be the first one that will have to shut down. This logic could initially lead to a large difference in the hours of operation among the various fans, but after an initial phase, these will almost be the same. Example. Turn-on : F1 . F2 . F3 . F4 Shutdown: F1 . F2 . F3 . F4
This type of rotation has a peculiarity in the case where all the fans configured in the system do not turn-on; in fact, if, for instance, the first fan is turned on and then it shuts down, the next fan to be turned on will be the second. The last fan turned off is memorized in order to turn on the next fan in the sequence, so that the same fan is not used, taking advantage in this way of all the configured condenser items.
Page 63
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Example with 4 fans. Turn-on : F1 . F2 . Shutdown: F1 . F2 . Turn-on : F3. F4. Shutdown: F3. F4. Turn-on : F1 . F2 . F3. F4. Shutdown: F1 . F2 . F3. F4.
2) LIFO
It follows the “Last In First Out” logic, which means that the last fan turned on will be the first one to be shut down. Example. Turn-on : F1 . F2 . F3 . F4 Shutdown: F4 . F3 . F2 . F1 The turn-on order will always start from the C1 compressor.
3) FIFO + hours of operation
This rotation favors the confrontation of the hours of operation of the various fans. During turn-on, the one with the fewest number of hours of operation will be favored, while during shutdown, the one with the highest number of hours will be favored. If it is necessary to choose among fans with the same number of hours, a FIFO rotation is activated so that a rotation is ensured even in the case of similar hours of operation. Example. 1 Turn-on : F1(3 hours) . F2(3 hours) . F3(3 hours) . F4(3 hours) Shutdown: F1(3 hours) . F2(3 hours) . F3(3 hours) . F4(3 hours)
Example. 2 Turn-on : F1(1 hours) . F2(3 hours) . F3(3 hours) . F4(5 hours) Shutdown: F4(5 hours) . F2(3 hours) . F3(3 hours) . F1(1 hour)
4) LIFO + working hours
This rotation favors the confrontation of the hours of operation of the various fans. During the turn-on phase, the one with the fewer number of hours of operation will be favored, while during shutdown, the one with the highest number of hours will be favored. If it is necessary to choose among fans with the same number of hours, a LIFO rotation is activated, to ensure a rotation even in the case of the same number of hours of operation. Example. 1 Turn-on : F1(3 hours) . F2(3 hours) . F3(3 hours) . F4(3 hours) Shutdown: F4(3 hours) . F3(3 hours) . F2(3 hours) . F1(3 hours)
Example. 2 Turn-on : F1(1 hour) . F2(3 hours) . F3(3 hours) . F4(5 hours) Shutdown: F4(5 hours) . F3(3 hours) . F2(3 hours) . F1(1 hours)
6.6.2 Fan timings
A list of all the timings relative to the management of the compressors is indicated below
Neutral Zone Timings
These parameters are useful to the organize the turn-on and shutdown request for the several condensation devices so as to establish certain time intervals.
Minimum turn-on request time. Minimum shutdown request time.
For these parameters, refer to the description made in paragraph 2.4.2.
Page 64
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Protection timings
These times serve to protect the fans from the various breakaways to which they are subjected.
PF07 – Minimum time between turn-ons of different fans. Establishes the minimum amount of time that must pass between the turn-on of one fan and the next. If it is set, it makes it possible to avoid simultaneous breakaways.
PF08 – Minimum time between shutdowns of different fans. Establishes the minimum amount of time that must pass between the shutdown of one fan and the next. If it is set, it makes it possible to avoid simultaneous breakaways. PF27, PF47 – speedUp time. If inverter adjustment is set, this parameter, if different from zero, makes it possible for the inverter output to remain at the maximum value (100.00 %), each time that the turn-on of a new fan is required.
6.6.3 Safety inputs
The program foresees the management of a single “thermal fan” safety measure for each of the fans configured in the application. The activation of this characteristic is managed by the parameter PG32 enable fan safety. To enable the “thermal fan” alarms, besides setting the appropriate parameter, the positions in which the digital inputs related to the various fans selected will be connected must also be set using the menu Constructor -> Hardware. If there is no wish to set the alarm, it is sufficient to set the parameter mentioned above to the value of 0.
6.6.4 Inverter configuration
For each inverter used in the plant must be selected also the related digital output position for the command/consent at the inverter start; For the configuration the same parameters of the fans digital outputs are used, parameters HF01, HF02, HF03, HF04. The inverter is virtually the first fan of each circuit; this means that, depending of the fans and circuits number, the right parameter must be set, by following below logic:
Signle Circuit: The inverter (if enabled) is virtually the fan 1; it is neccessary to configure the parameter
of the first fan, this means that parameter HF01 must be always configured.
Two circuits: The inverter of circuit 1 (if enabled) is virtually the fan 1 (this means that parameter HF01
must be configured), and the circuit 2 inverter (if enabled) is virtually the first fan after the circuit 1 fans.
Inverter consent with PWM
In some applications it can be necessary to command the consent of the inverters with a PWM output configuring 0% or 100%. To use this option is necessary to operate with the same logic used in the previous examples on the parameters HC0x, configuring the values according this rule:
HC01 = 13 -> Defines that the PWM output on the controller is used for the consent
of the fan with inverter circuit 1
HC0x = 14 -> Defines that the PWM output on the controller is used for the consent
of the fan with inverter circuit 2
Note. Configuring the value 13 or 14, the related PWM is used, this means that the possibile parameters HC31, HC32, HF31, HF32 should not be configured as PWM.
The choice and the configuration of the fan inverters parameters is the same for the compressors, but the parameters PH21, HF01, HF02, HF03 and HF04 are used (look at paragraph 6.4.5)
Page 65
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
6.7 Various management issues
6.7.1 Digital input or supervisor setpoint variation
It is sometimes important to reduce the energy consumption of the compressors or the noise level of the fans (for example at night). The program foresees, both for compressors and fans, the possibility of managing a parameter, PUC1 (PUC2) offset secondary setPoint compressors and PUF1 (PUF2) offset secondary setPoint fans, which, based on the state of a digital input (different for compressors and fans), sums an offset to the main setpoint in order to allow it to vary. It is possible to set the logic for the digital input by acting on the parameter PH19 Logic Other DI (the same parameter for the logic of the digital input on/off). To set this function, the parameter PH25 enable secondary digital input setpoint must be activated and the position in which the digital input related to the compressors and the one related to the fans will be connected must be set. If this value is not set, the function will remain disabled. Similarly, activating the parameter PH26 enable secondary supervisor setpoint, it is possible to use the relative offsets both for the compressors and for the fans.
6.7.2 Manual function
The program makes it possible to set a manual function for compressors and fans. In this state, the devices do not participate either in the rotations or in the calculation of thermo-adjustment, though they are still sensitive to possible alarms. The manual functioning of the devices is useful when functional tests must be run on the machine to test integrity and proper functioning.
Compressors
The manual functioning or lack thereof of the compressors is guaranteed by the parameter PM1x enable compressor:
- If it is set to the Auto value, it defines the normal functioning of the device
- If it is set to the Manu value, it disables the compressor and leads to manual functioning.
A compressor that is functioning manually does not participate in the adjustments and may be forced into the number of steps that it is able to supply by acting on the property PM2x compressor forcing (present in the menu Maintenance -> Forcing of Compressors). The number of steps that a compressor functioning manually can supply is limited to the number of throttlings that have been set in the configuration of the machine. As was stated previously, the compressor is in any case still sensitive to alarms and related consequences. To restore the compressor to normal use, the parameter PM1x enable compressor must be reset to the Auto value, otherwise the compressor in question will continue to function manually and will not heed the turn-on and/or shutdown requests calculated by the adjustment set.
Fans
The manual functioning or lack thereof of the fans is guaranteed by the parameter PM5x enable fan:
- If it is set to the Auto value, it defines the normal functioning of the device
- If it is set to the Manu value, it disables the fan and leads to manual functioning.
A fan that is functioning manually does not participate in the adjustments and may be forced to turn on/shut down by acting on the property PM6x fan forcing (present in the menu Maintenance -> Forcing of Fans). As was stated previously, the fan is in any case still sensitive to alarms and related consequences. To restore the fan to normal use, the parameter PM5x enable fan must be reset to the Auto value, otherwise the fan in question will continue to function manually and will not heed the turn-on and/or shutdown requests calculated by the adjustment set.
Page 66
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Inverters
When it is an inverter that must be manually forced, the procedure is slightly different. Recall that the inverter is virtually the first compressor of each circuit, therefore before being able to correctly perform the procedure, the correct compressor must be changed to manual, in other words:
- 1 Circuit: The inverter (if enabled) is compressor 1; in order to switch the inverter to manual
functioning, it is necessary to switch the first compressor to manual functioning.
- 2 Circuits: The inverter of circuit 1 (if enabled) is compressor 1 and the inverter of circuit 2 (if
enabled) is the first compressor following the compressors of circuit 1; to switch the inverters to manual functioning, it is necessary to switch these compressors to manual functioning.
Once the manual functions have been correctly set, it is possible to force the inverters using the specific parameter: PM37 (PM38) compressor inverter forcing.
In order to correctly configure this characteristic, it is sufficient to enable at least one compressor/fan inverter; depending on the type enabled, the other type will be automatically excluded by the analogue outputs.
The management and the forcing procedure of the fan inverters is the same as that for the compressor inverters.
6.7.3 Floating condensation management
Makes it possible to modify the working setpoint of the fans depending on the external temperature. To enable this function, the following parameters must be set in the menu Installer -> Various:
- enable external temperature probe (PH24)
- enable floating condensation (PF71)
- delta Condensation temperature (PF72): offset of condensation temperature (linked to the type of
condenser module used)
- inferior limit Condensation temperature (PF73): minimum value of the condensation temperature
(owing to the need to guarantee a minimum temperature of the lubricating oil)
- upper limit Condensation temperature (PF74): maximum value of the condensation value, beyond
which the fans no longer modulate and therefore reach the maximum.
The new setpoint will be given by the external temperature summed to the parameter delta temperature. The values of this new set, converted to pressure, are in any case limited by the variation range of the condensation setpoint.
Note. By enabling this function, the condensation setpoint parameters of the single circuits no longer have any effect on the adjustment of the condensation; in fact, the setpoint used will be a function of delta T and of the external temperature.
6.7.4 Temperature probes
The application is capable of managing a maximum of two auxiliary temperature probes: environment probe and external probe. To make use of these two temperature transducers, their activation parameters, enable environment temperature probe and enable external temperature probe, must be set. Each of the two probes is associated with a probe alarm, which is set off when the probe is disconnected or broken; the activation of this alarm is associated with the parameter of probe activation. By activating the probes, the related alarm is also activated. In the case of no activation, the screens will display the value of 0.
Page 67
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
6.7.5 Restoration of default parameters
Through the “Parameter restoration” procedure, it is possible to restore all the parameters of the system to the default values. This function is simple to activate by acting on the value of the appropriate parameter PH15 present in the Map menu, accessible only when the machine is turned off; setting it to “1”, the system will automatically see to the restoration of all parameters. Following this operation, it is necessary to unplug the machine and then plug it back in to avoid malfunctions.
6.7.6 Programming key
It is possible to save the value of all system parameters in the programming key and to then to copy this information to one or more compatible instruments. The saving or restoration process may be performed while the machine is on, connecting the key to the programming connector.
To save a particular parameter map in the key:
- access the Map menu and select “Stor” using the UP or DOWN buttons
- Push the SET (ENTER) button: the transfer of the parameters to the
key is highlighted by the blinking of the appropriate led
- Wait for the blinking to end; if the led is green, the operation
terminated correctly, otherwise the led is red
To copy a parameter map from the key to an instrument:
- access the Map menu and select “rESt” using the UP or DOWN
buttons
- Push the SET (ENTER) button: the transfer of the parameters from the
key to the instrument is highlighted by the blinking of the appropriate led
- Wait for the blinking to end: if the led is green, the operation terminated correctly, otherwise the led is red
Note: the key is able to save information relating to the product and its related version, in such a way as to allow for the transfer of parameter maps only between instruments that are compatible with each other.
Page 68
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
7 DIAGNOSTICS
The application is able to manage a series of alarms related to system compressors, fans, circuits and functions. Depending on the various types of alarm, it is possible to configure their resetting (if manual or automatic), a possible delay in signal and certain actions to perform in specific circumstances. When one or more alarms are active, the alarm icon on the screens blinks. To visualize the various alarms, the menu “Alar” must be visualized from the main page using the ESC key and then ENTER must be pressed. To scroll through the various active alarms, it is necessary to again hit the ENTER key: the alarms will be shown in the order of importance, as they are listed in the table of alarms in paragraph 3.2. All the digital inputs related to the alarms are managed by the parameter Alarm Logic that takes on the following meaning:
- If set to “NO”, the inputs will be normally un-excited (open): N.O. logic
- If set to “NC”, the inputs will be normally excited (closed): N.C. logic
7.1 Manual and automatic alarms
As mentioned previously, there are two types of alarms, those that are reset manually and those that are reset automatically. With some alarms there is the possibility of setting the type of reset that most suits the needs of the user through a certain parameter (Alarm reset).
Manual alarms
In the case that a manual alarm presents itself:
- The alarm icon begins to blink
By hitting the ENTER key in the “Alar” menu, the code of the alarm that was first activated is displayed. Once the conditions that triggered the alarm are reversed, it is possible to manually reset the alarm. To do this:
- go to the page of the alarm to be reset
- hold down the ENTER key for about 2 seconds.
At this point, if there are no other alarms, the page indicating “none” will appear, the alarm icon will shut off and the machine will return to its normal functioning, or the code of the next alarm that has been activated will be displayed. The consequences deriving from an active manual alarm will remain valid until the user proceeds to cancel the alarm message.
Automatic alarms
In the case that an automatic alarm presents itself:
- The alarm icon begins to blink
Hitting the ENTER key in the “Alar” menu, the code of the alarm that was first activated is displayed. Once the conditions that triggered the alarm are reversed, the resetting and the cancellation of the alarm message are restored automatically without the user having to intervene. The consequences that derive from an active automatic alarm will remain valid until the causes that triggered the alarm are not reversed.
Page 69
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
7.2 Alarms Table
A list of all the alarms that are managed by the application is given below. The order of presentation is the same as the order with which the alarms present themselves when they are active.
Code Description of the alarms Type Consequence Notes
EN01 Communication expansion error Auto Visualization Delay able to be set
- Num. comp. ON able to be set
ES01 Suction probe C1 broken or disconnected Auto
ES02 Discharge probe C1 broken or disconnected Auto
ES03 Suction probe C2 broken or disconnected Auto
ES04 Discharge probe C2 broken or disconnected Auto
AC21 Thermal compressor 1 Set OFF comp. 1 Delay able to be set AC22 Thermal compressor 2 Set OFF comp. 2 Delay able to be set AC23 Thermal compressor 3 Set OFF comp. 3 Delay able to be set AC24 Thermal compressor 4 Set OFF comp. 4 Delay able to be set AC01 Hours of operation compressor 1 Auto Visualization AC02 Hours of operation compressor 2 Auto Visualization AC03 Hours of operation compressor 3 Auto Visualization AC04 Hours of operation compressor 4 Auto Visualization AF21 Thermal fan 1 Set OFF fan 1 AF22 Thermal fan 2 Set OFF fan 2 AF23 Thermal fan 3 Set OFF fan 3 AF24 Thermal fan 4 Set OFF fan 4 AF01 Hours of operation fan 1 Auto Visualization AF02 Hours of operation fan 2 Auto Visualization AF03 Hours of operation fan 3 Auto Visualization AF04 Hours of operation fan 4 Auto Visualization AL31 High discharge pressure C1 Auto ON all fans AL36 High suction pressure C1 Auto ON all comp. Delay able to be set AL41 Low discharge pressure C1 Auto OFF all fans Delay able to be set * AL46 Low suction pressure C1 Auto OFF all comp. Delay able to be set * AL11 High discharge pressure pressure regulator C1 Set OFF all comp. AL21 Low suction pressure pressure regulator C1 Auto OFF all comp. Delay able to be set * AL61 Liquid level C1 Manu Visualization Delay able to be set ACC1 Common oil differential C1 Set Visualization Delay able to be set AFC1 Common thermal fans C1 Set Visualization
- Inverter forced to 100% (if required and if the only compressor in the circuit)
- Num. fan ON able to be set
- Inverter forced to 100% (if required and if the only fan in the circuit)
- OFF throttling HP circuit 1 (if enabled)
- Num. comp. ON able to be set
- Inverter forced to 100% (if required and if the only compressor in the circuit)
- Num. fan ON able to be set
- Inverter forced to 100% (if required and if the only fan in the circuit)
- OFF throttling HP circuit 2 (if enabled)
Delay able to be set
Delay able to be set
Delay able to be set
Delay able to be set
Page 70
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
AL32 High discharge pressure C2 Auto ON all fans AL37 High suction pressure C2 Auto ON all comp. Delay able to be set AL42 Low discharge pressure C2 Auto OFF all fans Delay able to be set AL47 Low suction pressure C2 Auto OFF all comp. Delay able to be set AL12 High discharge pressure pressure regulator C2 Set OFF all com. AL22 Low suction pressure pressure regulator C2 Auto OFF all comp. AL62 Liquid level C2 Manu Visualization Delay able to be set ACC2 Common oil differential C2 Set Visualization Delay able to be set AFC2 Common thermal fans C2 Set Visualization ES07 Environment probe broken or disconnected Auto Visualization ES08 External probe broken or disconnected Auto Visualization AH01 Hardware configuration alarm Auto Visualization
(*) The low-pressure alarms are not active when the machine is off, while all the others are.
Page 71
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
7.3 Alarm relays
The program has the possibility of managing up to three alarm relays. The activation of each of these devices is linked to the setting or lack thereof of the relative DO alarm position parameter. For activation, it is sufficient to set this value to a value that is different than zero; if the zero value is maintained, the alarm relay is not used. A list of the three relays, with their relative parameter, is presented below:
- A general alarm relay – Global DO alarm position
- An alarm relay for circuit 1 - DO alarm position circuit 1
- An alarm relay for circuit 2 - DO alarm position circuit 2
Through the relative parameter, it is possible to establish the polarity (NO or NC) of the various alarm outputs.
Page 72
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
8 List of the MODBUS variables
It is possible to check the application through a supervisor, using the Modbus protocol. The communication occurs through a serial TTL interface, which is already integrated in the controller; we suggest using the external TTL/RS-485 interface (the interface is not supplied with the instrument). The various parameters that are exported by the application in the three versions of the application are reported below.
Modbus Table
REGISTER VARS LIST
Id Name Value Min Max Description Mode
bit00=DI01, bit01=DI02, bit02=DI03, bit03=DI04, bit04=DI05, bit05=DI06, bit06=DI07,
257 PackedDI 0 0 65535
385 PackedDO 0 0 65535
513 AI_Pressure_SuctionC1 - - - Bar R/W 514 AI_Pressure_SupplyC1 - - - Bar R/W 515 AI_Pressure_SuctionC2 - - - Bar R/W 516 AI_Pressure_SupplyC2 - - - Bar R/W 517 AI_EnvironmentProbe - - - _C R/W 518 AI_ExternalProbe - - - _C R/W 641 CmpInverter_Circuit1 0.00 0.00 100.00 % R/W 642 FanInverter_Circuit1 0.00 0.00 100.00 % R/W 643 CmpInverter_Circuit2 0.00 0.00 100.00 % R/W 644 FanInverter_Circuit2 0.00 0.00 100.00 % R/W
769 PackedAlarm1 0 0 65535
bit07=DI08, bit08=DI09, bit09=DI10, bit10=free, bit11=free, bit12=free, bit13=free, bit14=free, bit15=free bit00=DO01, bit01=DO02, bit02=DO03, bit03=DO04, bit04=DO05, bit05=DO06, bit06=DO07, bit07=DO08, bit08=DO09, bit09=DO10, bit10=DO11, bit11=DO12, bit12=free, bit13=free, bit14=free, bit15=free
bit00=EN01, bit01=ES01, bit02=ES02, bit03=ES03, bit04=ES04, bit05=free,
R/W
R/W
R/W
Page 73
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
bit06=free, bit07=free, bit08=AC21, bit09=AC22, bit10=AC23, bit11=AC24, bit12=AC01, bit13=AC02, bit14=AC03, bit15=AC04 bit00=AF21, bit01=AF22, bit02=AF23, bit03=AF24, bit04=AF01, bit05=AF02, bit06=AF03,
770 PackedAlarm2 0 0 65535
bit07=AF04, bit08=A031,
R/W
bit09=A036, bit10=A041, bit11=A046, bit12=A011, bit13=A021, bit14=A061, bit15=ACC1 bit00=AFC1, bit01=free, bit02=A032, bit03=A037, bit04=A042, bit05=A047, bit06=A012,
771 PackedAlarm3 0 0 65535
bit07=A022, bit08=A062,
R/W
bit09=ACC2, bit10=AFC2, bit11=free, bit12=ES07, bit13=ES08, bit14=AH01,
bit15=free 1025 OnOffBySuperv 0 0 1 R/W 1026 OnOffBySuperv_Circuit1 0 0 1 R/W 1027 EnableSecSP_bySup_Cmp_Circuit1 0 0 1 R/W 1028 EnableSecSP_bySup_Fan_Circuit1 0 0 1 R/W 1029 OnOffBySuperv_Circuit2 0 0 1 R/W 1030 EnableSecSP_bySup_Cmp_Circuit2 0 0 1 R/W 1031 EnableSecSP_bySup_Fan_Circuit2 0 0 1 R/W
0=OFF key, 1281 StatusMachine 0 0 3
1=OFF dig,
2=OFF sup,
R/W
3=ON
0=disab,
1=OFF, 2=OFF 1282 StatusCircuit1 0 0 6
dig, 3=OFF
R/W sup, 4=ON, 5=ALL
1283 Cmp_actualSetPoint_Circuit1 - -145.0 625.5 Bar R/W 1284 Fan_actualSetPoint_Circuit1 - -145.0 625.5 Bar R/W 1285 CmpInv_actualSet_Circuit1 - -145.0 625.5 Bar R/W 1286 FanInv_actualSet_Circuit1 - -145.0 625.5 Bar R/W 1287 PowerRequested_Circuit1 0 0 100 % R/W
Page 74
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
1288 PowerSupplied_Circuit1 0 0 100 % R/W
0=disab, 1=OFF, 2=OFF
1289 StatusCircuit2 0 0 6
dig, 3=OFF
R/W sup, 4=ON, 5=ALL
1290 Cmp_actualSetPoint_Circuit2 - -145.0 625.5 Bar R/W 1291 Fan_actualSetPoint_Circuit2 - -145.0 625.5 Bar R/W 1292 CmpInv_actualSet_Circuit2 - -145.0 625.5 Bar R/W 1293 FanInv_actualSet_Circuit2 - -145.0 625.5 Bar R/W 1294 PowerRequested_Circuit2 0 0 100 % R/W 1295 PowerSupplied_Circuit2 0 0 100 % R/W 1537 SPC1_Cmp_SetPoint_Circuit1 1.0 -145.0 625.5 Bar R/W 1538 PUC1_Cmp_SPOffset_ByDig_Circuit1 0.0 -290.0 290.0 Bar R/W 1539 PUC4_Cmp_SPOffset_BySup_Circuit1 0.0 -290.0 290.0 Bar R/W 1540 SPF1_Fan_SetPoint_Circuit1 15.0 -145.0 625.5 Bar R/W 1541 PUF1_Fan_SPOffset_ByDig_Circuit1 0.0 -290.0 290.0 Bar R/W 1542 PUF4_Fan_SPOffset_BySup_Circuit1 0.0 -290.0 290.0 Bar R/W 1543 SPC2_Cmp_SetPoint_Circuit2 1.0 -145.0 625.5 Bar R/W 1544 PUC2_Cmp_SPOffset_ByDig_Circuit2 0.0 -290.0 290.0 Bar R/W 1545 PUC5_Cmp_SPOffset_BySup_Circuit2 0.0 -290.0 290.0 Bar R/W 1546 SPF2_Fan_SetPoint_Circuit2 15.0 -145.0 625.5 Bar R/W 1547 PUF2_Fan_SPOffset_ByDig_Circuit2 0.0 -290.0 290.0 Bar R/W 1548 PUF5_Fan_SPOffset_BySup_Circuit2 0.0 -290.0 290.0 Bar R/W 1549 PM00_ManutHourCmp ( Low ) 2000.0 0.0 9999.0 hours x 10 R/W 1550 PM00_ManutHourCmp ( High ) 1551 PM0x_HoursCmp[0] ( Low ) 0.0 0.0 9999.0 R/W 1552 PM0x_HoursCmp[0] ( High ) 1553 PM0x_HoursCmp[1] ( Low ) 0.0 0.0 9999.0 R/W 1554 PM0x_HoursCmp[1] ( High ) 1555 PM0x_HoursCmp[2] ( Low ) 0.0 0.0 9999.0 R/W 1556 PM0x_HoursCmp[2] ( High ) 1557 PM0x_HoursCmp[3] ( Low ) 0.0 0.0 9999.0 R/W 1558 PM0x_HoursCmp[3] ( High ) 1559 PM1x_En_Manual_Cmp[0] 0 0 1 R/W 1560 PM1x_En_Manual_Cmp[1] 0 0 1 R/W 1561 PM1x_En_Manual_Cmp[2] 0 0 1 R/W 1562 PM1x_En_Manual_Cmp[3] 0 0 1 R/W 1563 PM2x_V_suppStepsCmp[0] 0 0 3 R/W 1564 PM2x_V_suppStepsCmp[1] 0 0 3 R/W 1565 PM2x_V_suppStepsCmp[2] 0 0 3 R/W 1566 PM2x_V_suppStepsCmp[3] 0 0 3 R/W 1567 PM37_Forz_Cmp_Inverter1 0.00 0.00 100.00 % R/W 1568 PM38_Forz_Cmp_Inverter2 0.00 0.00 100.00 % R/W 1569 PM40_ManutHourFan ( Low ) 2000.0 0.0 9999.0 hours x 10 R/W 1570 PM40_ManutHourFan ( High ) 1571 PM4x_HoursFan[0] ( Low ) 0.0 0.0 9999.0 R/W 1572 PM4x_HoursFan[0] ( High ) 1573 PM4x_HoursFan[1] ( Low ) 0.0 0.0 9999.0 R/W 1574 PM4x_HoursFan[1] ( High ) 1575 PM4x_HoursFan[2] ( Low ) 0.0 0.0 9999.0 R/W 1576 PM4x_HoursFan[2] ( High ) 1577 PM4x_HoursFan[3] ( Low ) 0.0 0.0 9999.0 R/W 1578 PM4x_HoursFan[3] ( High ) 1579 PM5x_En_Manual_Fan[0] 0 0 1 R/W 1580 PM5x_En_Manual_Fan[1] 0 0 1 R/W 1581 PM5x_En_Manual_Fan[2] 0 0 1 R/W 1582 PM5x_En_Manual_Fan[3] 0 0 1 R/W 1583 PM6x_V_suppStepsFan[0] 0 0 1 R/W 1584 PM6x_V_suppStepsFan[1] 0 0 1 R/W
Page 75
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
1585 PM6x_V_suppStepsFan[2] 0 0 1 R/W 1586 PM6x_V_suppStepsFan[3] 0 0 1 R/W 1587 PM77_Forz_Fans_Inverter1 0.00 0.00 100.00 % R/W 1588 PM78_Forz_Fans_Inverter2 0.00 0.00 100.00 % R/W 1589 PM81_Calibration_SuctionC1 0.0 -19.0 19.0 Bar R/W 1590 PM82_Calibration_SupplyC1 0.0 -19.0 19.0 Bar R/W 1591 PM83_Calibration_SuctionC2 0.0 -19.0 19.0 Bar R/W 1592 PM84_Calibration_SupplyC2 0.0 -19.0 19.0 Bar R/W 1593 PM85_Calibration_EnvProbe 0.0 -19.0 19.0 _C R/W 1594 PM86_Calibration_ExtProbe 0.0 -19.0 19.0 _C R/W 1595 PM91_Last_maintenanceYEAR 2006 2006 2070 R/W 1596 PM92_Last_maintenanceMONTH 1 1 12 R/W 1597 PM93_Last_maintenanceDAY 1 1 31 R/W
0=FIFO,
1598 PC01_Cmp_Rotation_Type 0 0 3
1=LIFO, 2=FIFO+Hr,
R/W 3=LIFO+Hr
0=CpCp/pCpC,
1599 PC02_Cmp_ModeCCpp_Type 0 0 3
1=CCpp/ppCC, 2=CpCp/ppCC,
R/W 3=CCpp/pCpC
1600 PC03_Cmp_LoadStepsLogic 1 0 1
0=N.C., 1=N.O.
R/W
1601 PC04_Cmp_TminOn 10 0 999 sec R/W 1602 PC05_Cmp_TminOff 120 0 999 sec R/W 1603 PC06_Cmp_TonOn 360 0 999 sec R/W 1604 PC07_Cmp_TonOther 20 0 999 sec R/W 1605 PC08_Cmp_ToffOther 20 0 999 sec R/W 1606 PC09_Cmp_TonLoadStep 20 0 999 sec R/W 1607 PC10_Cmp_ToffLoadStep 20 0 999 sec R/W 1608 PC11_Cmp_OnErrorProbe_Circuit1 1 0 4 R/W 1609 PC12_Cmp_MinSetPoint_Circuit1 0.1 -145.0 625.5 Bar R/W 1610 PC13_Cmp_MaxSetPoint_Circuit1 2.5 -145.0 625.5 Bar R/W
1611 PC14_Cmp_RegulationType_Circuit1 1 0 1
0 = Sideband, 1 = Neutral Zone
R/W
1612 PC16_Cmp_PI_Ti_Circuit1 600 0 999 Sec R/W 1613 PC17_Cmp_PI_Diff_Circuit1 0.5 0.0 290.0 Bar R/W 1614 PC18_Cmp_NZ_Zone_Circuit1 0.5 0.0 290.0 Bar R/W 1615 PC19_Cmp_NZ_DiffOutZone_Circuit1 0.5 0.0 290.0 Bar R/W 1616 PC20_Cmp_NZ_TOnMin_Circuit1 20 0 999 Sec R/W 1617 PC21_Cmp_NZ_TOnMax_Circuit1 60 0 999 Sec R/W 1618 PC22_Cmp_NZ_TOffMin_Circuit1 10 0 999 Sec R/W 1619 PC23_Cmp_NZ_TOffMax_Circuit1 60 0 999 Sec R/W 1620 PC24_Cmp_Inverter_Diff_Circuit1 0.5 0.0 290.0 Bar R/W 1621 PC25_Cmp_Inverter_OffsetSP_Circuit1 0.0 -290.0 290.0 Bar R/W 1622 PC26_Cmp_Min_Inverter_Circuit1 - 0.00 100.00 % R/W 1623 PC27_Cmp_Inverter_TSpeedUp_Circuit1 0 0 999 Sec R/W 1624 PC28_Cmp_InverterTime_Circuit1 10 0 999 Sec R/W 1625 PC31_Cmp_OnErrorProbe_Circuit2 1 0 4 R/W 1626 PC32_Cmp_MinSetPoint_Circuit2 0.1 -145.0 625.5 Bar R/W 1627 PC33_Cmp_MaxSetPoint_Circuit2 2.5 -145.0 625.5 Bar R/W
1628 PC34_Cmp_RegulationType_Circuit2 1 0 1
0 = Sideband, 1 = Neutral Zone
R/W
1629 PC36_Cmp_PI_Ti_Circuit2 600 0 999 Sec R/W 1630 PC37_Cmp_PI_Diff_Circuit2 0.5 0.0 290.0 Bar R/W 1631 PC38_Cmp_NZ_Zone_Circuit2 0.5 0.0 290.0 Bar R/W 1632 PC39_Cmp_NZ_DiffOutZone_Circuit2 0.5 0.0 290.0 Bar R/W 1633 PC40_Cmp_NZ_TOnMin_Circuit2 20 0 999 Sec R/W 1634 PC41_Cmp_NZ_TOnMax_Circuit2 60 0 999 Sec R/W 1635 PC42_Cmp_NZ_TOffMin_Circuit2 10 0 999 Sec R/W
Page 76
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
1636 PC43_Cmp_NZ_TOffMax_Circuit2 60 0 999 Sec R/W 1637 PC44_Cmp_Inverter_Diff_Circuit2 0.5 0.0 290.0 Bar R/W 1638 PC45_Cmp_Inverter_OffsetSP_Circuit2 0.0 -290.0 290.0 Bar R/W 1639 PC46_Cmp_Min_Inverter_Circuit2 - 0.00 100.00 % R/W 1640 PC47_Cmp_Inverter_TSpeedUp_Circuit2 0 0 999 Sec R/W 1641 PC48_Cmp_InverterTime_Circuit2 10 0 999 Sec R/W 1642 PC69_RestartTimeout 0 0 999 Sec R/W 1643 PC70_EnablePart 0 0 1 R/W 1644 PC71_SetPressurePartCircuit1 22.0 -145.0 625.5 Bar R/W 1645 PC72_SetPressurePartCircuit2 22.0 -145.0 625.5 Bar R/W 1646 PC74_DifftPressurePart 4.0 0.1 10.0 Bar R/W 1647 PC75_MinTimePart 2 0 999 Min R/W 1648 PC76_PartLimit 50 0 100 % R/W 1649 PC78_OverloadSteps_Cmp 0 0 100 % R/W 1650 PC8x_CmpPower[0] 0 0 5000 kW R/W 1651 PC8x_CmpPower[1] 0 0 5000 kW R/W 1652 PC8x_CmpPower[2] 0 0 5000 kW R/W 1653 PC8x_CmpPower[3] 0 0 5000 kW R/W
0=FIFO,
1654 PF01_Fan_Rotation_Type 0 0 3
1=LIFO, 2=FIFO+Hr,
R/W 3=LIFO+Hr
1655 PF02_Fan_EnRegulationByCmp 0 0 1
0=CPP_CPP, 1=CC_PPPP
R/W
1656 PF07_Fan_TOnOther 2 0 999 Sec R/W 1657 PF08_Fan_TOffOther 2 0 999 Sec R/W 1658 PF11_Fan_OnErrorProbe_Circuit1 1 0 4 R/W 1659 PF12_Fan_MinSetPoint_Circuit1 1.0 -145.0 625.5 Bar R/W 1660 PF13_Fan_MaxSetPoint_Circuit1 25.0 -145.0 625.5 Bar R/W
1661 PF14_Fan_RegulationType_Circuit1 0 0 1
0 = Sideband, 1 = Neural Zone
R/W
1662 PF16_Fan_PI_Ti_Circuit1 600 0 999 Sec R/W 1663 PF17_Fan_PI_Diff_Circuit1 0.5 0.0 290.0 Bar R/W 1664 PF18_Fan_NZ_Zone_Circuit1 1.0 0.0 290.0 Bar R/W 1665 PF20_Fan_NZ_TOnOff_Circuit1 10 0 999 Bar R/W 1666 PF24_Fan_Inverter_Diff_Circuit1 0.5 0.0 290.0 Bar R/W 1667 PF25_Fan_Inverter_OffsetSP_Circuit1 0.0 -290.0 290.0 Bar R/W 1668 PF26_Fan_Min_Inverter_Circuit1 - 0.00 100.00 % R/W 1669 PF27_Fan_Inverter_TSpeedUp_Circuit1 2 0 999 Sec R/W 1670 PF28_Fan_InverterTime_Circuit1 10 0 999 Sec R/W 1671 PF31_Fan_OnErrorProbe_Circuit2 1 0 4 R/W 1672 PF32_Fan_MinSetPoint_Circuit2 1.0 -145.0 625.5 Bar R/W 1673 PF33_Fan_MaxSetPoint_Circuit2 25.0 -145.0 625.5 Bar R/W
1674 PF34_Fan_RegulationType_Circuit2 0 0 1
0 = Sideband, 1 = Neural Zone
R/W
1675 PF36_Fan_PI_Ti_Circuit2 600 0 999 Sec R/W 1676 PF37_Fan_PI_Diff_Circuit2 0.5 0.0 290.0 Bar R/W 1677 PF38_Fan_NZ_Zone_Circuit2 1.0 0.0 290.0 Bar R/W 1678 PF40_Fan_NZ_TOnOff_Circuit2 10 0 999 Sec R/W 1679 PF44_Fan_Inverter_Diff_Circuit2 0.5 0.0 290.0 Bar R/W 1680 PF45_Fan_Inverter_OffsetSP_Circuit2 0.0 -290.0 290.0 Bar R/W 1681 PF46_Fan_Min_Inverter_Circuit2 - 0.00 100.00 % R/W 1682 PF47_Fan_Inverter_TSpeedUp_Circuit2 2 0 999 Sec R/W 1683 PF48_Fan_InverterTime_Circuit2 10 0 999 Sec R/W 1684 PF71_EnableFloatingCond 0 0 1 R/W 1685 PF72_FloatingCond_Offset - -20.0 20.0 _C R/W 1686 PF73_FloatingCond_SetMin 30.0 10.0 45.0 _C R/W 1687 PF74_FloatingCond_SetMax 40.0 10.0 45.0 _C R/W 1688 PF78_OverloadSteps_Fan 0 0 100 % R/W 1689 PA01_En_Alarm_ManutHourCmp 0 0 1 R/W
Page 77
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
1690 PA02_En_Alarm_ManutHourFan 0 0 1 R/W 1691 PA03_HighPressureSuction_Delay 1 0 999 Sec R/W 1692 PA04_ExpOffline_Delay 5 0 999 Sec R/W 1693 PA05_LiquidLevel_Delay 90 0 999 Sec R/W 1694 PA06_ProbeError_Delay 5 0 240 Sec R/W 1695 PA07_LowPressureSupply_Delay 30 0 999 Sec R/W 1696 PA08_LowPressureSuction_Delay 30 0 999 Sec R/W 1697 PA09_ThermalCmp_Delay 0 0 999 Sec R/W 1698 PA10_OilDiffCmp_Delay 10 0 999 Sec R/W
1699 PA11_PressureSwitchSupply_ResetType 1 0 1
1700 PA12_ThermalCmp_ResetType 1 0 1
1701 PA14_OilDiffCmp_ResetType 1 0 1
0=Auto, 1=Man 0=Auto, 1=Man 0=Auto, 1=Man
R/W
R/W
R/W
1702 PA15_SetPoint_LP_Suction_C1 0.5 -145.0 625.5 Bar R/W 1703 PA16_Diff_LP_Suction_C1 0.5 0.0 290.0 Bar R/W 1704 PA17_SetPoint_HP_Suction_C1 4.0 -145.0 625.5 Bar R/W 1705 PA18_Diff_HP_Suction_C1 0.5 0.0 290.0 Bar R/W 1706 PA19_SetPoint_LP_Supply_C1 2.0 -145.0 625.5 Bar R/W 1707 PA20_Diff_LP_Supply_C1 0.5 0.0 290.0 Bar R/W 1708 PA21_SetPoint_HP_Supply_C1 20.0 -145.0 625.0 Bar R/W 1709 PA22_Diff_HP_Supply_C1 1.0 0.0 290.0 Bar R/W
1710 PA23_ThermalFan_ResetType 1 0 1
0=Auto, 1=Man
R/W
1711 PA25_SetPoint_LP_Suction_C2 0.5 -145.0 625.5 Bar R/W 1712 PA26_Diff_LP_Suction_C2 0.5 0.0 290.0 Bar R/W 1713 PA27_SetPoint_HP_Suction_C2 4.0 -145.0 625.5 Bar R/W 1714 PA28_Diff_HP_Suction_C2 0.5 0.0 290.0 Bar R/W 1715 PA29_SetPoint_LP_Supply_C2 2.0 -145.0 625.5 Bar R/W 1716 PA30_Diff_LP_Supply_C2 0.5 0.0 290.0 Bar R/W 1717 PA31_SetPoint_HP_Supply_C2 20.0 -145.0 625.5 Bar R/W 1718 PA32_Diff_HP_Supply_C2 1.0 0.0 290.0 Bar R/W 1719 PH01_Pressure_Min_Suction -0.5 -145.0 625.5 Bar R/W 1720 PH02_Pressure_Max_Suction 7.0 -145.0 625.5 Bar R/W 1721 PH03_Pressure_Min_Supply 0.0 -145.0 625.5 Bar R/W 1722 PH04_Pressure_Max_Supply 30.0 -145.0 625.5 Bar R/W 1723 PH05_En_OnOffByKey 1 0 1 R/W 1724 PH07_En_OnOffByDI 0 0 1 R/W 1725 PH08_En_OnOffByDI_Circuit 0 0 1 R/W 1726 PH09_En_OnOffBySuperv 0 0 1 R/W 1727 PH10_En_OnOffBySuperv_Circuit 0 0 1 R/W 1728 PH11_Modbus_Address 1 1 247 R/W
1=2400,
1729 PH12_Modbus_Baud 3 0 4
2=4800, 3=9600,
R/W 4=19200
1730 PH13_Modbus_Parity 2 0 2
0=None, 1=Odd, 2=Even
R/W
1731 PH14_Modbus_StopBit 0 0 1 0=1 bit, 1=2 bit R/W 1732 PH15_SetDefault_Par 0 0 1 R/W 1733 PH17_Logic_DI_Alarm 1 0 1 R/W 1734 PH18_Logic_DO_Alarm 0 0 1 R/W 1735 PH19_Logic_DI_Other 0 0 1 R/W 1736 PH23_En_EnvironmentProbe 0 0 1 R/W 1737 PH24_En_ExternalProbe 0 0 1 R/W 1738 PH25_En_OffsetSetPoint_FromDig 0 0 1 R/W 1739 PH26_En_OffsetSetPoint_FromSup 0 0 1 R/W
1740 PH31_RefrigerationType 3 0 6
0=none, 1=R22,
R/W
Page 78
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
2=R134a, 3=R404A, 4=R407C, 5=R410A, 6=R507
1741 PH32_Temp_UM 0 0 1 0=_C, 1=_F R/W 1742 PH33_Press_UM 0 0 1 0=Bar, 1=psi R/W 1743 PH35_EnSuctionCompensation 0 0 1 R/W 1744 PH36_OffsetSuctionCompensation 0.2 0.1 5.0 Bar R/W 1745 PH40_Pressure_or_Temperature 0 0 1 R/W 1746 PH43_Select_UniversalAI3 4 2 5 R/W 1747 PH44_Select_UniversalAI4 4 2 5 R/W 1748 PH50_OnlyIcons 0 0 1 R/W 1749 PH51_EnableNumericIcons 1 0 1 R/W 1750 PH52_EnableEvcoIcon 1 0 1 R/W 1751 PG01_CircuitsNumber 1 1 2 R/W 1752 PG02_En_Expansion 0 0 1 R/W 1753 PG03_DifferentCapacitiesCmp 0 0 1 R/W 1754 PG04_LoadStepsNumber 0 0 2 R/W 1755 PG05_Cmp_SecuritiesNumber 1 0 1 R/W 1756 PG11_CmpNumber_Circuit1 2 0 4 R/W 1757 PG12_Cmp_Enable_Inverter_Circuit1 0 0 1 R/W 1758 PG15_CmpNumber_Circuit2 0 0 4 R/W 1759 PG16_Cmp_Enable_Inverter_Circuit2 0 0 1 R/W 1760 PG30_En_UniqueCondenser 0 0 1 R/W 1761 PG32_Fan_EnSecurities 1 0 1 R/W 1762 PG41_FansNumber_Circuit1 2 0 4 R/W 1763 PG42_Fan_Enable_Inverter_Circuit1 0 0 1 R/W 1764 PG45_FansNumber_Circuit2 0 0 4 R/W 1765 PG46_Fan_Enable_Inverter_Circuit2 0 0 1 R/W 1766 HC0x_Pos_DO_Cmp[0] 1 0 14 R/W 1767 HC0x_Pos_DO_Cmp[1] 2 0 14 R/W 1768 HC0x_Pos_DO_Cmp[2] 0 0 14 R/W 1769 HC0x_Pos_DO_Cmp[3] 0 0 14 R/W 1770 HC1x_Pos_DO_Cmp_LS1[0] 0 0 12 R/W 1771 HC1x_Pos_DO_Cmp_LS1[1] 0 0 12 R/W 1772 HC1x_Pos_DO_Cmp_LS1[2] 0 0 12 R/W 1773 HC1x_Pos_DO_Cmp_LS1[3] 0 0 12 R/W 1774 HC2x_Pos_DO_Cmp_LS2[0] 0 0 12 R/W 1775 HC2x_Pos_DO_Cmp_LS2[1] 0 0 12 R/W 1776 HC2x_Pos_DO_Cmp_LS2[2] 0 0 12 R/W 1777 HC2x_Pos_DO_Cmp_LS2[3] 0 0 12 R/W 1778 HC31_Pos_AO_InvCmp1 2 0 3 R/W 1779 HC32_Pos_AO_InvCmp2 0 0 3 R/W 1780 HF0x_Pos_DO_Fan[0] 3 0 14 R/W 1781 HF0x_Pos_DO_Fan[1] 4 0 14 R/W 1782 HF0x_Pos_DO_Fan[2] 0 0 14 R/W 1783 HF0x_Pos_DO_Fan[3] 0 0 14 R/W 1784 HF31_Pos_AO_InvFan1 1 0 3 R/W 1785 HF32_Pos_AO_InvFan2 0 0 3 R/W 1786 HA01_Pos_DO_GlobalAlarm 6 0 12 R/W 1787 HA11_Pos_DO_AlarmCircuit1 0 0 12 R/W 1788 HA21_Pos_DO_AlarmCircuit2 0 0 12 R/W 1789 Hd01_Pos_DI_Remote_OnOff 0 0 10 R/W 1790 Hd02_Pos_DI_CmpSecSP 0 0 10 R/W 1791 Hd03_Pos_DI_FanSecSP 0 0 10 R/W 1792 Hd11_Pos_DI_Remote_OnOff_C1 0 0 10 R/W 1793 Hd12_Pos_DI_LiquidLevel_Circuit1 0 0 10 R/W 1794 Hd13_Pos_DI_LowPressSwitchSuction_Circuit1 0 0 10 R/W 1795 Hd14_Pos_DI_HighPressSwitchSupply_Circuit1 5 0 10 R/W
Page 79
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
1796 Hd15_Pos_DI_CommonOilDiff_Circuit1 0 0 10 R/W
Hd16_Pos_DI_CommonThermalOverloadFan_Cir
1797
cuit1 1798 Hd21_Pos_DI_Remote_OnOff_C2 0 0 10 R/W 1799 Hd22_Pos_DI_LiquidLevel_Circuit2 0 0 10 R/W 1800 Hd23_Pos_DI_LowPressSwitchSuction_Circuit2 0 0 10 R/W 1801 Hd24_Pos_DI_HighPressSwitchSupply_Circuit2 0 0 10 R/W 1802 Hd25_Pos_DI_CommonOilDiff_Circuit2 0 0 10 R/W
Hd26_Pos_DI_CommonThermalOverloadFan_Cir 1803
cuit2 1804 Hd4x_Pos_DI_ThermalOverloadCmps[0] 1 0 10 R/W 1805 Hd4x_Pos_DI_ThermalOverloadCmps[1] 2 0 10 R/W 1806 Hd4x_Pos_DI_ThermalOverloadCmps[2] 0 0 10 R/W 1807 Hd4x_Pos_DI_ThermalOverloadCmps[3] 0 0 10 R/W 1808 Hd8x_Pos_DI_ThermalOverloadFans[0] 3 0 10 R/W 1809 Hd8x_Pos_DI_ThermalOverloadFans[1] 4 0 10 R/W 1810 Hd8x_Pos_DI_ThermalOverloadFans[2] 0 0 10 R/W 1811 Hd8x_Pos_DI_ThermalOverloadFans[3] 0 0 10 R/W 1812 PH20_LogicCmdInverter_Comp 0 0 1 R/W 1813 PH21_LogicCmdInverter_Fan 0 0 1 R/W
0 0 10 R/W
0 0 10 R/W
Page 80
C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
C-PRO NANO RACK and C-PRO MICRO RACK application manual
1.05 version , February 2011. Code 144RACKNUE05. File 144RACKNUE05.pdf.
The present publication is the exclusive property of Evco, which absolutely prohibits its reproduction and publication, if not clearly authorized by Evco itself. Evco does not assume any responsibility with regards to the characteristics, the technical data and the potential errors present in the present document or which may occur when using it. Evco cannot be considered responsible for the damages caused by not respecting the warnings. Evco has the right to modify the material, without warning and at any time, without affecting its essential characteristics of functionality and security.
Page 81
HEADQUARTERS Evco
Via Mezzaterra 6, 32036 Sedico Belluno ITALY Tel. 0437-852468 Fax 0437-83648 info@evco.it www.evco.it
FOREIGN HEADQUARTERS Control France
155 Rue Roger Salengro, 92370 Chaville Paris FRANCE Tel. 0033-1-41159740 Fax 0033-1-41159739 control.france@wanadoo.fr
Latin Evco
Larrea, 390 San Isidoro, 1609 Buenos Aires ARGENTINA Tel. 0054-11-47351031 Fax 0054-11-47351031 evcolatina@anykasrl.com.ar
Pacific Evco
59 Premier Drive Campbellfield, 3061, Victoria Melbourne, AUSTRALIA Tel. 0061-3-9357-0788 Fax 0061-3-9357-7638 everycontrol@pacific.com.au
Evco Russia
111141 Russia Moscow 2-oy Proezd Perova Polya 9 Tel. 007-495-3055884 Fax 007-495-3055884 info@evco.ru
Every Control do Brasil
Rua Marino FÈlix 256, 02515-030 Casa Verde S„o Paulo S_O PAULO BRAZIL Tel. 0055-11-38588732 Fax 0055-11-39659890 info@everycontrol.com.br
Every Control Norden
Cementv‰gen 8, 136 50 Haninge SWEDEN Tel. 0046-8-940470 Fax 0046-8-6053148 mail2@unilec.se
Every Control Shangai
B 302, Yinhai Building, 250 Cao Xi Road, 200235 Shangai CHINA Tel. 0086-21-64824650 Fax 0086-21-64824649 evcosh@online.sh.cn
Every Control United Kingdom
Unit 19, Monument Business Park, OX44 7RW Chalgrowe, Oxford, UNITED KINGDOM Tel. 0044-1865-400514 Fax 0044-1865-400419 info@everycontrol.co.uk
Loading...