C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Important
Please read these instructions carefully prior to installation and use, and follow all the precautions for installation and
electrical connections; keep these instructions with the device for future consultation.
The device must be disposed of in accordance with local regulations pertaining to the collection of electrical and
electronic appliances.
Page
2
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Table of contents
1 GENERAL INFORMATION......................................................................................................5
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
1 GENERAL INFORMATION
1.1 Description
This application uses C-PRO MEGA and C-PRO GIGA controllers to manage a compressor packs
composed of one, two or three circuits with a maximum number of 8 compressors (if using C-PRO
MEGA controllers) or 12 compressors (if using C-PRO GIGA controllers).
A compressor packs control system is required to manage the compressors in order to maintain the
evaporation pressure at the desired value; more specifically, it must guarantee the production of
cold, for example for the preservation of foodstuffs.
Continuous generation of cold is required for this, using a process which must continue without any
interruptions, except for normal maintenance operations.
The C-PRO MEGA and C-PRO GIGA controllers are dedicated to this process, managing all the
components of the refrigeration circuit, maintaining the required conditions with the greatest
possible efficiency (greater output = lower running costs), with optimal handling of mechanical
components in order to reduce breakdowns (for example, fewer start-ups = less mechanical stress).
Two types of regulation may be selected for controlling pressure or temperature:
⋅ Side Band
⋅ Neutral Zone
Safety devices are managed for each circuit so as to promptly detect any malfunctions. Each safety
device is associated with a particular alarm, which will be triggered in order to identify the type of
fault. The outcome of certain alarms will be to shutdown the relevant mechanical devices, in order
to avoid further faults; others will only indicate the fault, without having any effect on the operation
of the machine.
The application has a navigable user interface, by means of which it is possible to define and set all
configuration and operational parameters. The user interface is subdivided into four main levels:
⋅ User
⋅ Service
⋅ Installer
⋅ System builder
Each level is protected by a separate password. At the system builder level, the user interface
displays a series of modifiable configuration screens (wizards) allowing easy setting of the number
of circuits, compressors, fans and the corresponding safety devices used for the protection of the
mechanical devices. There are also several free-access pages, not password protected, for checking
the operational status of the system at that particular time.
In addition to the aforementioned four levels, there is also a Clock menu (for setting the parameters
associated with the system RTC, such as for example those related to management of the time
bands for variation of the setpoints).
The versions have an integrated 4 x 20 character alphanumeric display, keypad and warning LEDs.
Each version has an optoisolated RS-485 port (for connection to the RICS or other BMS
supervision system) and a non-optoisolated CAN port (for connection to I/O expansion unit).
Page
5
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
C-PRO MEGA
Page
6
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
C-PRO GIGA
Page
7
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2 APPLICATIONS
Using the CAN protocol, it is possible to connect an 8 relay (C-PRO EXP MEGA) or 13 relay
(C-PRO EXP GIGA) expansion module to the controllers.
Management of four different types of control unit is envisaged:
1) Application 1: C-PRO MEGA RACK (for single circuit control units; C-PRO MEGA
RACK preset configuration)
Total No. of digital outputs = 8
Total No. of digital inputs = 10
Total No. of analogue inputs = 8
Total No. of analogue outputs = 4
configuration)
Total No. of digital outputs = 13
Total No. of digital inputs = 12
Total No. of analogue inputs = 8
Total No. of analogue outputs = 4
3) Application 3: C-PRO MEGA RACK + C-PRO EXP MEGA (e.g. for dual circuit
control units)
Total No. of digital outputs = 8 + 8 = 16
Total No. of digital inputs = 10 + 8 = 18
Total No. of analogue inputs = 8 +4 = 12
Total No. of analogue outputs = 4
4) Application 4: C-PRO GIGA RACK + C-PRO EXP GIGA (e.g. for dual circuit control
units)
5) Total No. of digital outputs = 13 +13 = 26
Total No. of digital inputs = 12 +10 = 22
Total No. of analogue inputs = 8 +4 = 12
Total No. of analogue outputs = 4
Page
8
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2.1 Application 1: use of the C-PRO MEGA RACK (single circuit
control unit)
As a preset configuration, the C-PRO MEGA RACK is configured to manage single circuit
compressor packs; the services mentioned in the figure below refer specifically to the preset
configurations.
Page
9
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2.2 Application 2: use of the C-PRO GIGA RACK (dual circuit
control unit with separate condensation)
The C-PRO GIGA RACK is pre-configured to control dual circuit compressor packs; the services
mentioned in the figure below refer precisely to the preset configurations.
Compressors 1 and 2 (and related load increments) appertain to circuit 1; compressors 3 and 4 (and
related load increments) appertain to circuit 2.
Fans 1 and 2 appertain to circuit 1; fans 3 and 4 appertain to circuit 2.
10
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2.3 Application 3: use of the C-PRO MEGA RACK with the C-PRO
EXP MEGA I/O expansion unit (dual circuit control unit with
separate condensation)
The C-PRO MEGA RACK is pre-configured to control single circuit compressor packs; the
services mentioned in the figure below refer to an example of a dual circuit control unit with
separate condensation.
Compressors 1, 2 and 3 appertain to circuit 1; compressors 4, 5 and 6 appertain to circuit 2.
Fans 1, 2 and 3 appertain to circuit 1; fans 4, 5 and 6 appertain to circuit 2.
The C-PRO MEGA RACK and C-PRO EXP MEGA power supplies must be galvanically
isolated from one another.
11
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2.4 Application 4: use of the C-PRO GIGA RACK with the C-PRO
EXP GIGA I/O expansion unit (dual circuit control unit with
separate condensation)
The C-PRO GIGA RACK is factory pre-configured to control dual circuit compressor packs; the
services mentioned in the figure below refer to an example of a dual circuit control unit with
separate condenser, where the controller is used with an I/O expansion unit.
Compressors 1, 2 and 3 appertain to circuit 1; compressors 4, 5 and 6 appertain to circuit 2.
Fans 1, 2 and 3 appertain to circuit 1; fans 4, 5 and 6 appertain to circuit 2.
The C-PRO GIGA RACK and C-PRO EXP GIGA power supplies must be galvanically
isolated from one another.
12
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2.5 Controller electrical connections
The layout relating to the controllers electrical connections is shown below, with tables listing the
meanings of the inputs and outputs.
2.5.1 C-PRO MEGA RACK electrical connections
Page
13
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2.5.2 C-PRO GIGA RACK electrical connections
Page
14
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2.5.3 Input and output identification tables
Card with 12 VDC + 12 VDC dual power supplies
Conn.
C1-1 VCC main card power supply input (+13 VDC)
C1-2 GND main power supply reference
JA-1 VDC active probe power supply (*1)
JA-2 AI 1 No.1 universal analogue input (NTC, PTC, 0..5V, 0..10V, 0..20 mA, 4..20 mA)
JA-3 GND analogue input common ground
JB-1 VDC active probe power supply (*1)
JB-2 AI 2 No.2 universal analogue input (NTC, PTC, 0..5V, 0..10V, 0..20 mA, 4..20 mA)
JB-3 GND analogue input common ground
JC-1 VDC active probe power supply (*1)
JC-2 AI 3 No.3 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JC-3 AI 4 No.4 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JC-4 GND analogue input common ground
JD-1 VDC active probe power supply (*1)
JD-2 AI 5 No.5 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JD-3 AI 6 No.6 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JD-4 AI 7 No.7 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JD-5 AI 8 No.8 configurable analogue input (NTC, 0..20 mA, 4..20 mA)
JD-6 GND analogue input common ground
JE-1 COM digital input common connection
JE-2
JE-3
JE-4 COM digital input common connection
JF-1 COM digital input common connection
JF-2 DI 3 No.3 digital input 12-24 VAC/DC
JF-3 DI 4 No.4 digital input 12-24 VAC/DC
JF-4 DI 5 No.5 digital input 12-24 VAC/DC
JF-5 DI 6 No.6 digital input 12-24 VAC/DC
JF-6 COM digital input common connection
JG-1 COM digital input common connection
JG-2 DI 7 No.7 digital input 12-24 VAC/DC
JG-3 DI 8 No.8 digital input 12-24 VAC/DC
JG-4 DI 9 No.9 digital input 12-24 VAC/DC
JG-5 DI 10 No.10 digital input 12-24 VAC/DC
JG-6 COM digital input common connection
YA-1 VDC power supply output connector (12 VDC)
YA-2 CAN1+ connector for connecting the LOCAL CAN serial port (CAN+)
YA-3 CAN1- connector for connecting the LOCAL CAN serial port (CAN-)
YA-4 GND power supply reference output connector (ground)
JH-1 NC 1 relay No. 1 contact normally closed
JH-2 COM 1 relay No. 1 common connection
JH-3 NO 1 relay No. 1 contact normally open
JI-1 NC 2 relay No. 2 contact normally closed
JI-2 COM 2 relay No. 2 common connection
JI-3 NO 2 relay No. 2 contact normally open
JK-1 COM 3 relay No. 3 common connection
JK-2 NO 3 relay No. 3 contact normally open
Abbre
DI 1 No.1 digital input 12-24 VAC/DC
DI 2 No.2 digital input 12-24 VAC/DC
v.
Description
15
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Conn.
JK-3 COM 4 relay No. 4 common connection
JK-4 NO 4 relay No. 4 contact normally open
JK-5 COM 5 relay No. 5 common connection
JK-6 NO 5 relay No. 5 contact normally open
JL-1 COM 6 relay No. 6 common connection
JL-2 NO 6 relay No. 6 contact normally open
JL-3 COM 7 relay No. 7 common connection
JL-4 NO 7 relay No. 7 contact normally open
JL-5 COM 8 relay No. 8 common connection
JL-6 NO 8 relay No. 8 contact normally open
YC-1 RS485+ connector for connecting the RS485 serial port (RS485+)
YC-2 RS485- connector for connecting the RS485 serial port (RS485-)
YC-3 GND connector for connecting the RS485 serial port (ground)
JM-1 AO 1 No. 1 analogue output (0,5 .. 10 V / 0 .. 20 mA / 4 .. 20 mA)
JM-2 AO 2 No. 2 analogue output (0,5 .. 10 V / 0 .. 20 mA / 4 .. 20 mA)
JM-3 AO 3 No. 3 analogue output (0,5 .. 10 V / 0 .. 20 mA / 4 .. 20 mA)
JM-4 AO 4 No. 4 analogue output (0,5 .. 10 V / 0 .. 20 mA / 4 .. 20 mA)
JM-5 GND analogue output common ground
C2-1 VCC* serial port and optoisolated analogue output secondary power supply input (+15 VDC)
C2-2 GND* secondary power supply reference
Abbre
YB PRG not used
v.
Description
* VDC=12.5 V Imax=200 mA (as the sum of the current for all VDC terminals).
Card with 24 VAC/DC power supply
Conn.
CA-1 VCC main card power supply input (23 V AC/DC)
CA-2 VCC main card power supply input (23 V AC/DC)
Abbre
v.
Description
Warning:
With reference to the “Power supply” entries, the secondary power supply feeds the following
services:
• the analogue outputs
• the standard RS-485 port
• the optional RS-485 port (or RS-232 port).
So that these services are optoisolated, the main power supply and the secondary power supply must
be galvanically isolated from one another.
If the controller is powered with 24 VAC/DC (i.e. by means of the connector hereinafter referred to
as CA), the following services will not be optoisolated:
• the analogue outputs
• the standard RS-485 port
• the optional RS-485 port (or RS-232 port).
16
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Other connectors (not present on the C-PRO MEGA RACK controller)
Conn.
JN-1 NC 9 relay No. 9 contact normally closed
JN-2 COM 9 relay No. 9 common connection
JN-3 NO 9 relay No. 9 contact normally open
JO-1 NC 10 relay No. 10 contact normally closed
JO-2 COM10 relay No. 10 common connection
JO-3 NO 10 relay No. 10 contact normally open
JP-1 COM11 relay No. 11 common connection
JP-2 NO 11 relay No. 11 contact normally open
JP-3 COM12 relay No. 12 common connection
JP-4 NO 12 relay No. 12 contact normally open
JP-5 COM13 relay No. 13 common connection
JP-6 NO 13 relay No. 13 contact normally open
JQ-1 DI11 No. 11 digital input 230 VAC
JQ-2 DI12 No. 12 digital input 230 VAC
JQ-3 CONHV digital input common connection 230 VAC
Abbre
v.
Description
Second RS-485 port (on request)
Conn.
YE-1 RS485- RS 485 - connector for connecting to supervision system
YE-2 RS485+ RS 485 + connector for connecting to supervisor system
YE-3 GND GND connector for connecting to supervision system, via RS485
Abbre
v.
Description
RS-232 port (available on request, as an alternative to the second RS-485 port)
Conn.
YF-1 5Vdc RS 232 9 pole connector YF-2
YF-3
YF-4
YF-5 GND RS 232 9 pole connector YF-6
YF-7 RTS RS 232 9 pole connector -
YF-8 CTS RS 232 9 pole connector -
Abbre
v.
Description
Tx RS 232 9 pole connector - Transmission Signal
Rx RS 232 9 pole connector - Reception Signal
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
JMP3 CAN terminator
Jumper not inserted
Jumper inserted
Termination (120?) not inserted
Termination (120?) inserted
JMP4 Local CAN serial port baud rate selection
A
Jumper A inserted
Jumper B inserted
Baud rate = 20K
B
A
Jumper A inserted
Jumper B not inserted Baud rate = 50K
B
A
Jumper A not inserted
Jumper B inserted
Baud rate = 125K
B
A
Jumper A not inserted
Jumper B not inserted Baud rate = 500K
B
JMP5 RS-485 terminator
Jumper not inserted
Jumper inserted
Termination (120?) not inserted
Termination (120?) inserted
JMP6 Analogue output selection
A
B
C
Jumper A inserted
Jumper B inserted
Jumper C inserted
Jumper D inserted
Output AO1 under current
Output AO2 under current
Output AO3 under current
Output AO4 under current
D
A
B
C
Jumper A not inserted
Jumper B not inserted
Jumper C not inserted
Jumper D not inserted
Output AO1 under tension
Output AO2 under tension
Output AO3 under tension
Output AO4 under tension
D
PLEASE NOTE:
It is not sufficient to merely set the jumper to configure the signal distributed by the analogue
output, the controller machine parameters must also be set (see the chapter “Configuration of the
signal distributed by the analogue output” in the Hardware Manual).
18
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2.6 Preset configurations
The controller preset configurations are reported below.
2.6.1 C-PRO MEGA RACK preset configurations (single circuit compressor packs)
No. 1 digital input
No. 2 digital input
No. 3 digital input
No. 4 digital input
No. 5 digital input
No. 6 digital input
No. 7 digital input
No. 8 digital input
No. 1 digital output
No. 2 digital output
No. 3 digital output
No. 4 digital output
No. 5 digital output
No. 6 digital output
No. 7 digital output
No. 8 digital output
Description
By default – not configured
Suction probe
Supply probe
Description
Description
Compressor 1 thermal
Compressor 2 thermal
Compressor 3 thermal
Compressor 4 thermal
Fan thermal common connection
Fluid level
Low pressure (suction) pressure-switch
High pressure (supply) pressure-switch
Description
Compressor 1
Global alarm relay
Compressor 2
Compressor 3
Compressor 4
Fan 1
Fan 2
Fan 3
Digital inputs
4 compressor thermals
Fan thermal common connections
Fluid level
Low pressure pressure-switch
High pressure pressure-switch
Page
19
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
No. 1 digital input
No. 2 digital input
No. 3 digital input
No. 4 digital input
No. 5 digital input
No. 6 digital input
No. 7 digital input
No. 8 digital input
No. 9 digital input
No. 10 digital input
No. 11 digital input
No. 12 digital input
No. 1 digital output
No. 2 digital output
No. 3 digital output
No. 4 digital output
No. 5 digital output
No. 6 digital output
No. 7 digital output
No. 8 digital output
No. 9 digital output
No. 10 digital output
No. 11 digital output
No. 12 digital output
No. 13 digital output
DI1 No.1 digital input 12-24 VAC/DC
DI2 No.2 digital input 12-24 VAC/DC
DI3 No.3 digital input 12-24 VAC/DC
DI4 No.4 digital input 12-24 VAC/DC
DI5 No.5 digital input 12-24 VAC/DC
DI6 No.6 digital input 12-24 VAC/DC
DI7 No.7 digital input 12-24 VAC/DC
DI8 No.8 digital input 12-24 VAC/DC
PRG not used
Conn.
C1-1 VCC card power supply input (+13 V DC)
C1-2 GND power supply reference
JD-1 VDC active probe power supply (*1)
JD-2
JD-3
JD-4
JD-5
JD-6 GND analogue input common ground
JF-1 COM digital input common connection
JF-2
JF-3
JF-4
JF-5
JF-6 COM digital input common connection
JG-1 COM digital input common connection
JG-2
JG-3
JG-4
JG-5
JG-6 COM digital input common connection
YA-1 VDC power supply output connector (12 VDC)
YA-2 CAN1+ connector for connecting the CAN serial port (CAN+)
YA-3 CAN1- connector for connecting the CAN serial port (CAN-)
YA-4 GND power supply output reference connector (ground)
JH-1 NC 1 relay No. 1 contact normally closed
JH-2 COM 1 relay No. 1 common connection
JH-3 NO 1 relay No. 1 contact normally open
JI-1 NC 2 relay No. 2 contact normally closed
JI-2 COM 2 relay No. 2 common connection
JI-3 NO 2 relay No. 2 contact normally open
JK-1 COM 3 relay No. 3 common connection
JK-2 NO 3 relay No. 3 contact normally open
JK-3 COM 4 relay No. 4 common connection
JK-4 NO 4 relay No. 4 contact normally open
JK-5 COM 5 relay No. 5 common connection
JK-6 NO 5 relay No. 5 contact normally open
JL-1 COM 6 relay No. 6 common connection
JL-2 NO 6 relay No. 6 contact normally open
JL-3 COM 7 relay No. 7 common connection
JL-4 NO 7 relay No. 7 contact normally open
JL-5 COM 8 relay No. 8 common connection
JL-6 NO 8 relay No. 8 contact normally open
C2-1 VCC not used
C2-2 GND not used
23
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
* VDC=12.5 V Imax = 200 mA (as the sum of the current values for all VDC terminals).
Card with 24 V AC/DC power supply
Conn.
CA-1 VCC card power supply input (24 VAC/DC)
CA-2 VCC card power supply input (24 VAC/DC)
Abbre
v.
Description
Other connectors (not present on the C-PRO EXP MEGA expansion unit)
Conn.
JN-1 NC 9 relay No. 9 contact normally closed
JN-2 COM 9 relay No. 9 common connection
JN-3 NO 9 relay No. 9 contact normally open
JO-1 NC 10 relay No. 10 contact normally closed
JO-2 COM10 relay No. 10 common connection
JO-3 NO 10 relay No. 10 contact normally open
JP-1 COM11 relay No. 11 common connection
JP-2 NO 11 relay No. 11 contact normally open
JP-3 COM12 relay No. 12 common connection
JP-4 NO 12 relay No. 12 contact normally open
JP-5 COM13 relay No. 13 common connection
JP-6 NO 13 relay No. 13 contact normally open
JQ-1
JQ-2 DI10 No. 10 digital input 230 VAC
JQ-3 CONHV digital input common connection 230 VAC
Abbre
DI9 No. 9 digital input 230 VAC
v.
Description
Jumper and LED meanings
JMP3 CAN terminator
Jumper not inserted
Jumper inserted
Termination (120?) not inserted
Termination (120?) inserted
JMP4 Local CAN serial port baud rate selection
A
Jumper A inserted
Jumper B inserted
Baud rate = 20K
B
A
Jumper A inserted
Jumper B not inserted Baud rate = 50K
B
A
Jumper A not inserted
Jumper B inserted
Baud rate = 125K
B
A
Jumper A not inserted
Jumper B not inserted Baud rate = 500K
B
PLEASE NOTE:
The C-PRO MEGA RACK and the C-PRO GIGA RACK are configured by default to be able to
work with an expansion unit (with standard configuration) and with a user interface (with standard
24
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
configuration) by simply connecting the network components. For further information please refer
to the chapter “CAN connection” in the Hardware Manual.
Page
25
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
3 COMPONENT NETWORK AND ACCESSORIES
3.1 Example
Page
26
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
4 USER INTERFACE
4.1 Display and keypad
For the application there is an interface integrated with the controller (hereinafter referred to as
“built-in”).
It has a 4x20 character alphanumeric display, offer a range of keys for navigation/editing pages and
several LEDs for viewing certain associated events.
The keypad has 6 page navigation and value editing keys with the following functions:
- UP and DOWN: alters the parameters in editing mode; otherwise, it is used for moving the
cursor
- LEFT and RIGHT: displays the screens in succession
- ENTER: confirms the value displayed in editing mode; otherwise, it runs any commands
associated with the text at the cursor point. If pressed for approx. 2 seconds while viewing
an alarm page, it allows the alarm to be reset. If viewing the alarm pages, each press scrolls
through the active alarms.
- ESC: cancels the present value if in editing mode; otherwise, it recalls any default page
associated with the current page. If the ESC key is pressed and held for approx. 2 seconds, it
allows the machine to be switched on/off.
There are also an additional 3 function keys:
- K0 = ALL: enters the alarm pages if pressed and held for approx. 2 seconds. Pressing mutes
the buzzer.
- K1: not used
- K2: enters the application clock menu.
Page
27
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
There are also 3 LEDs:
- L0 associated with the K0 key, identifies whether there are any alarms.
Off: there are no alarms.
Flashing slowly: indicates the presence of new alarms
Flashing rapidly: indicates that alarm pages are being viewed.
On: all active alarms have been viewed
- L2 associated with the K2 key, identifies the status of the RTC and the
time bands:
Off: no signals.
Flashing rapidly: indicates there is an ERTC clock alarm.
Flashing slowly: indicates that the compressor or fan setpoint is
changed within the time bands.
On: indicates that the compressor and fan setpoint are both changed
within the time bands.
- LEsc associated with the ESC key, identifies the status of the machine:
Off: machine off
On: machine on
Flashing slowly: machine switched off by digital input
Flashing rapidly: machine switched off by supervisor system.
4.2 Page list
This section will introduce the application’s main pages and menus. As already mentioned, the main
menu is subdivided into four levels: user, service, installer and system builder, plus a menu for
managing the functions associated with the system clock and certain free-access pages.
The menu structure is as follows:
⋅ Clock menu
⋅ General menu
⋅ User menu (Level 1, level 1 password)
⋅ Service menu (Level 2, level 2 password)
o Service menu – operations branch
o Service menu – manual branch
o Service menu - input/output branch
⋅ Installer menu (Level 3, level 3 password)
o Installer menu - settings branch
o Installer menu – compressor branch
o Installer menu fans branch
o Installer menu - safety devices branch
o Installer menu - miscellaneous branch
⋅ System builder menu (Level 4, level 4 password)
o System builder menu – systems branch (configuration wizards)
o System builder menu – hardware branch
o Installer menu – parameters branch
Page
28
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Password
Each menu (besides the clock menu which is always accessible) is associated with a level which
affects accessibility.
Each level also has an associated password allowing access to the various functions present in that
specific menu. Once the correct password has been entered, the protected functions will be
accessible. Correctly entering a password has two effects:
⋅ it unlocks the associated level
⋅ it unlocks the sub-levels
Each level password may be altered from the level itself or from superior levels. For example, from
the system builder level, all the passwords for the underlying levels will be modifiable by using the
appropriate page.
Here is an example from the system builder menu password page.
The range of permissible values for passwords is: -999 / 9999.
If no actions are executed within the current page, then after 4 minutes, the inserted password
expires, and it is necessary to insert it once more.
Clock menu
This menu contains the functions associated with the system RTC:
⋅ setting the clock
⋅ enabling the compressor/fan time bands
⋅ setting the time bands
⋅ setting the offsets to the main setpoints for each time band
This menu is not password-protected, and may be accessed by pressing the K2 key on the user
interface for approx. 2 seconds.
Status pages
There are pages that are not password-protected and may accessed and browsed by simply using the
LEFT and RIGHT keys.
These pages display the status of the circuits, compressors, inverters, probes, the power supplied
and requested, and other general information. These pages cannot be edited.
When the machine is on and running, the main page is the following:
from which it is possible to access the status pages for the individual circuits, by pressing ENTER
at the “>” for the corresponding circuit, or by navigating using the LEFT and RIGHT keys, it is
possible to view the status of the compressors, fans and inverters.
29
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Stato circuito
Funzioni attive su circuito
Set Point e V
alore delle sonde di pressione
The first page for each circuit:
contains information on the circuit’s current status and active functions:
hp:
tC:
dC:
sC:
tF
dF:
sF:
refrigeration power increments
Compressor time band function
Compressor set point variation from a digital input
Compressor set point variation by supervisor system
Fan time band function
Fan set point variation from a digital input
Fan set point variation by supervisor system
The function is active if the relevant code is visible on the page.
General menu
The general menu has no level, and is the access point for all other system menus.
It is possible to view this menu, from any point within the user interface, by pressing and holding
the ENTER key for approx. 2 seconds. From this page, it is possible to select into which menu to
move by moving the “screen highlight” above the indicators “>>>” and pressing the ENTER key
for conformation.
Pressing the ESC key within this menu returns to the default start page if the machine is on, or the
OFF page if the machine is switched off.
User menu
The user menu is a level 1 menu, i.e. it is necessary to insert the user level password, or higher, in
order to be able to view/modify the parameters in this branch.
It is possible to select which circuit to access in order to modify the setpoints and the secondary
setpoint offset, or to set several general configuration parameters in the “Miscellaneous” section.
Within this page, as may be seen from the figure, a “v” character is displayed in the top right of the
screen. This is not an error, but a sign to indicate to the user that the page information continues, i.e.
pressing the DOWN (or UP depending on where the screen highlight is) key moves to the content
Page
30
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
not yet visible on the page itself. In this specific case, once the screen highlight is on the third
circuit line, pressing DOWN moves the display to the next screen:
Service menu
The user menu is a level 2 menu, i.e. it is necessary to insert the service level password, or higher,
in order to be able to view/modify the parameters in this branch.
In this menu, it is possible to view the status of the various devices, inputs and outputs used by the
application.
Entering the OPERATION menu displays/enables features relating to compressor and fan operation.
For example, the operation times, the status of the relevant alarms and the maximum acceptable
time threshold.
In the MANUAL menu, it is possible to manually/automatically set the compressors and fans and
whether outputs can be forced in order to test functionality
In the I/O STATUS menu it is possible to view all the properties involved with the application inputs
and outputs:
⋅ digital input/output status
⋅ analogue output status
⋅ probe calibration…
Installer menu
The installer menu is a level 3 menu, i.e. it is necessary to insert the installer or system builder
password in order to be able to view/modify the parameters in this branch.
The installer menu contains all the parameters pertaining to the configuration of all the machine
functions (alarms, settings, logic, type of rotation,…).
31
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
In the REGULATION menu it is possible to set/view the parameters relating to the side band and
neutral zone thermoregulations for compressors, fans and any inverters, for each circuit:
⋅ type of regulation
⋅ setpoints
⋅ differentials
⋅ times
⋅ offsets
In the COMPRESSORS and FANS menu it is possible to set the parameters pertaining to device
management:
⋅ power of the individual compressors (if used)
⋅ type of rotation
⋅ increment logic
⋅ times
⋅ floating condensation parameters
⋅ high pressure pressure-switch alarm prevention parameters
The SAFETY DEVICES menu contains all the parameters pertaining to the alarms and management
of the safety devices for the compressors and fans
⋅ enabling
⋅ signal delays
⋅ reset type…
The MISCELLANEOUS menu contains other general parameters:
⋅ full-scale values for the transducers
⋅ Modbus communication
⋅ activations On/Off.
⋅ temperature probe activation
⋅ digital input and supervisor system secondary setpoint activation
⋅ analogue input type
⋅ refrigerant gas (when using temperature probes)
⋅ suction line compensation
⋅ password
From the DEFAULTS menu it is possible to restore the default values for all the application
parameters. This menu is only accessible with the machine switched off.
System builder menu
The system builder menu is a level 4 menu, i.e. it is necessary to insert the system builder level
password in order to be able to view/modify the parameters in this branch. Furthermore, this menu
is only accessible with the machine switched off.
This menu contains all the machine configuration parameters that decide the mode of operation and
which functions to activate, or restrict, depending on the system builder’s needs.
32
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
The SYSTEM menu contains a system configuration “Wizard” for configuring a number of circuits,
activating unique condensation, the use of inverters, the number of compressors and increments, the
number of fans, the number of safety devices to be used and the use of any expansion units. A page
summarising the relays and selected digital inputs is presented for configuration purposes,
indicating whether an expansion unit should be used, if selected.
The HARDWARE menu contains all the parameters for setting the positions to which the various
devices are connected.
⋅ Compressor digital output position
⋅ Fan digital output position
⋅ Alarm digital input/output position
Such characteristics are collected in a separate submenu in order to distinguish compressors, fans
and safety devices.
Setting the positions of the various alarm inputs also enables their operation. Indeed, an alarm is
only enabled if the parameter, identifying its physical position on the terminal, is set and is other
than zero. If it is desired not to use an alarm, simply leave the corresponding parameter at the value
zero.
The same management is used to manage the four alarm relays. If the position parameters are equal
to zero, then the relays are disabled.
The PARAMETERS menu contains other machine configuration parameters:
⋅ type of control unit (only for viewing on the pages)
⋅ home page
⋅ passwords for all four levels
Firmware version
Keep pressed the UP+DOWN buttons for 2 seconds and enter in to the section info page.
Proj
(Project)
No. 291 No. 1008
Version 4 Version 7
Release 0 Release 0
Firmware
33
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
4.3 Conditioned visibility
Conditioned visibility allows hiding certain parameters and status information on the basis of the
configuration of certain parameters. For example, by setting neutral zone type regulation, the side
band regulation parameters will be automatically hidden when viewing the pages, or, even more
importantly, by setting a single circuit machine, all the parameters for the second and third circuit
will no longer be visible. At the user interface level, all the parameters and status information that is
not of interest will be replaced by dots “….” On the 4 x 20 character alphanumeric display, and will
not be editable.
This feature makes configuration, maintenance and use of the machine simpler. During
configuration, once the system type and characteristics are selected, the unused parameters will no
longer be accessible. During maintenance, it will be possible to test the functions of the devices
effectively configured in the system. During normal use, the number of parameters and the status
information to be displayed by means of the user interface is significantly less than the total that can
be configured; this all makes the user interface more legible, speeds up setting or finding the correct
parameter, and above all prevents the user from setting parameters that might cause malfunctions.
The configuration parameter table shows the parameters subject to conditioned visibility, along with
the conditions deciding their exclusion.
Page
34
Code
PT00
PT01..04
PT11..14
PT21..24
PT31..34
PT50
PT51..54
PT61..64
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
5 CONFIGURATION PARAMETERS
All the parameters managed by the application are listed below. For each parameter there is also a
brief description, the range of values admissible, the units of measurement, the recommended
default value and the menu in which it may be found. The menus are structured according to the
following logic:
⋅ OR : clock menu
⋅ UT : user menu
⋅ MA: service menu
o MA-F: service menu – operations branch
o MA-M: service menu – manual branch
o MA-IO: service menu - input/output branch
⋅ IS : installer menu
o IS-RC: installer menu – compressor settings branch
o IS-RF: installer menu – fan settings branch
o IS-C: installer menu – compressor branch
o IS-F: installer menu - fans branch
o IS-S: installer menu - safety devices branch
o IS-V: installer menu - miscellaneous branch
⋅ CO : system builder menu
o CO-W: system builder menu – systems branch (configuration wizards)
o CO-Hw: system builder menu – hardware branch
o CO-Pa: installer menu – parameters branch
Parameters table
Parameter
Enable
compressor time
bands
Comp. time band
(1..4)
Compressor time
band offset
(1..4) Circuit 1
Compressor time
band offset
(1..4) Circuit 2
Compressor time
band offset
(1..4) Circuit 3
Enable fan time
bands
Fan time band
(1..4)
Fan time band
offset (1..4)
Enables compressor time
band management
Sets the four compressor
time bands
Sets the offsets to the
compressor setpoints in
relation to the 4 time bands.
Circuit 1
Sets the offsets to the
compressor setpoints in
relation to the 4 time bands.
Circuit 2
Sets the offsets to the
compressor setpoints in
relation to the 4 time bands.
Circuit 3
Enables fan time band
management
Sets the four fan time bands
Sets the offsets to the fan
setpoints in relation to the 4
Description
CLOCK MENU PARAMETERS – Time band management
Default
NO
0.0 PC12
0.0 PC32
0.0 PC52
NO
0.0 PF12
Min
NO (0) YES (1)
OR
NO (0) YES (1)
OR
Max
PC13
PC33
PC53
PF13
Uo
M
OR
Bar
Bar
Bar
OR
Bar
Menu
OR
OR
OR
OR
Visible if PG01
> 1
Visible if PG01
> 2
Notes
Page
35
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
PT71..74
PT81..84
SPC1
PUC1
PUC4
SPC2
PUC2
PUC5
SPC3
PUC3
PUC6
SPF1
PUF1
PUF4
SPF2
Circuit 1
Fan time band
offset (1..4)
Circuit 2
Fan time band
offset (1..4)
Circuit 3
time bands. Circuit 1
Sets the offsets to the fan
setpoints in relation to the 4
time bands. Circuit 2
Sets the offsets to the fan
setpoints in relation to the 4
time bands. Circuit 3
Sets the setpoint value for
the compressor suction
probe
Sets the offset value for use
of secondary setpoint from
the compressor digital input
Sets the offset value for use
of secondary setpoint from
compressor supervisor
Sets the setpoint value for
the compressor suction
probe
Sets the offset value for use
of secondary setpoint from
the compressor digital input
Sets the offset value for use
of secondary setpoint from
compressor supervisor
Sets the setpoint value for
the compressor suction
probe
Sets the offset value for use
of secondary setpoint from
the compressor digital input
Sets the offset value for use
of secondary setpoint from
compressor supervisor
Sets the setpoint value for
the fan supply probe
Sets the offset value for use
of secondary setpoint from
fan digital input
Sets the offset value for use
of secondary setpoint from
fan supervisor
Sets the setpoint value for
the fan supply probe
USER MENU PARAMETERS
0.0 PF32
0.0 PF52
1.0 PC12
0.0 -20.0 20.0 Bar
0.0 -20.0 20.0 Bar
1.0 PC32
0.0 -20.0 20.0 Bar
0.0 -20.0 20.0 Bar
1.0 PC52
0.0 -20.0 20.0 Bar
0.0 -20.0 20.0 Bar
15.0 PF12
0.0 -20.0 20.0 Bar
0.0 -20.0 20.0 Bar
15.0 PF32
PF33
PF53
PC13
PC33
PC53
PF13
PF33
Visible if PG01
Bar
OR
> 1 and
PG30 = 0
Visible if PG01
Bar
OR
> 2 and
PG30 = 0
Bar
UT
UT
UT
Bar
UT
UT
UT
Bar
UT
UT
UT
Bar
UT
UT
UT
Bar
UT
Visible if PG01
> 1
Visible if PG01
> 1
Visible if PG01
> 1
Visible if PG01
> 2
Visible if PG01
> 2
Visible if PG01
> 2
Visible if PG01
> 1 and
PG30 = 0
Page
36
PUF2
PUF5
SPF3
PUF3
PUF6
PSd1
PM00
PM01..10
PM31
PM32
PM40
PM41..50
PM71
PM72
PM90
PSd2
PM11..20
Fan secondary
setpoint offset
Circuit 2
Fan sup.
secondary
setpoint offset
Circuit 2
Fan setpoint
Circuit 3
Fan secondary
setpoint offset
Circuit 3
Fan sup.
secondary
setpoint offset
Circuit 3
User PSd
Compressor
operational time
alarm threshold
Compressor
operation
time (1..10)
Compressor
operation
time (11-12)
Fan operational
time alarm
threshold
Fan operation
time (1..10)
Fan operation
time (11-12)
Last maintenance
date
Service PSd
Enable
compressor
(1..10)
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Sets the offset value for use
of secondary setpoint from
fan digital input
Sets the offset value for use
of secondary setpoint from
fan supervisor
Sets the setpoint value for
the fan supply probe
Sets the offset value for use
of secondary setpoint from
fan digital input
Sets the offset value for use
of secondary setpoint from
fan supervisor
User level password
Sets the maximum
compressor operation time
limit. Beyond this limit, the
relevant alarm will be
tripped
Operation times for each
compressor
Operation times for each
compressor
Sets the maximum fan
operation time limit.
Beyond this limit, the
relevant alarm will be
tripped
Operation times for each fan
Operation times for each fan
Sets the last date on which
system maintenance was
carried out
Service level password
Enables manual/automatic
operation of each
compressor:
M: manual
A: normal operation
SERVICE MENU PARAMETERS
0.0 -20.0 20.0 Bar
0.0 -20.0 20.0 Bar
15.0 PF52
0.0 -20.0 20.0 Bar
0.0 -20.0 20.0 Bar
0 -999 9999 UT
20000 0 500000
0 0 500000
0 0 500000
20000 0 500000
0 0 500000
0 0 500000
MA-F
0 -999 9999 MA-F
A
A (0)
PF53
M (1)
Bar
Hou
Hou
Hou
Hou
Hou
Hou
MA-F
rs
MA-F
rs
MA-F
rs
MA-F
rs
MA-F
rs
MA-F
rs
MA-M
UT
UT
UT
UT
UT
Visible if PG01
> 1 and
PG30 = 0
Visible if PG01
> 1 and
PG30 = 0
Visible if PG01
> 2 and
PG30 = 0
Visible if PG01
> 2 and
PG30 = 0
Visible if PG01
> 2 and
PG30 = 0
Compressors 1
to 10;
Visibility
Compressors
11 and 12;
Visibility
Fans 1 to 10;
Visibility
Fans 11 and 12;
Visibility
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
In manual operation, this
sets the number of forced
compressor steps
Enables manual/automatic
operation of each
compressor:
M: manual
A: normal operation
In manual operation, this
sets the number of forced
compressor steps
In manual operation, this
forces the compressor with
the circuit 1 inverter
In manual operation, this
forces the compressor with
the circuit 2 inverter
In manual operation, this
forces the compressor with
the circuit 3 inverter
Enables manual/automatic
operation of each fan:
M: manual
A: normal operation
In manual operation, this
forces the fans to be
switched on and off:
S: fan off
A: fan on
Enables manual/automatic
operation of each fan:
M: manual
A: normal operation
In manual operation, this
forces the fans to be
switched on and off:
S: fan off
A: fan on
In manual operation, this
forces the fan with the
circuit 1 inverter
In manual operation, this
forces the fan with the
circuit 2 inverter
In manual operation, this
forces the fan with the
circuit 3 inverter
Circuit 1 suction probe
calibration
Circuit 2 suction probe
calibration
Minimum suction setpoint
value pertaining to the
compressors of circuit 1
Maximum suction setpoint
value pertaining to the
compressors of circuit 1
Sets the type of regulation
for controlling the circuit 1
compressors
Integral time Ti for side
band regulation of circuit 1
compressors
Proportional band Bp for
side band regulation of
circuit 1 compressors
Zone value for neutral zone
regulation of circuit 1
compressors
Differential, for neutral zone
regulation, within which the
calculation for the
insertion/release time of the
subsequent step varies.
Circuit 1
Minimum insertion time for
subsequent compressor step
( circuit 1 neutral zone reg.)
Maximum insertion time for
subsequent compressor step
( circuit 1 neutral zone reg.)
Minimum release time for
subsequent compressor step
( circuit 1 neutral zone reg.)
Maximum release time for
subsequent compressor step
( circuit 1 neutral zone reg.)
Differential for compressor
regulation with circuit 1
inverter
Suction setpoint offset for
circuit 1 inverter regulation
INSTALLER MENU PARAMETERS
0.0 -9.9 9.9 Bar MA-IO
0.0 -9.9 9.9 Bar MA-IO
0.0 -9.9 9.9 Bar MA-IO
0.0 -9.9 9.9 Bar MA-IO
0.0 -9.9 9.9 Bar MA-IO
0.0 -9.9 9.9 Bar MA-IO
0.1 PH01
2.5 SPC1
Neutral
Zone (1)
600 0 999 Sec IS-RC
0.5 0 20.0 Bar IS-RC
0.5 0 20.0 Bar IS-RC
0.5 0 20.0 Bar IS-RC
20 0 PC21
Side
Band (0)
SPC1
PH02
Neutral
Zone (1)
Bar IS-RC
Bar IS-RC
IS-RC
Sec IS-RC
60 PC20
999 Sec IS-RC
10 0 PC23
Sec IS-RC
60 PC22
999 Sec IS-RC
0.5 0.0 20.0 Bar IS-RC
0.0 -20.0 20.0 Bar IS-RC
Visible if PG01
> 2
Visible if PG01
> 1 and PG30 =
0
Visible if PG01
> 2 and PG30 =
0
Visible if PC14
= 0
Visible if PC14
= 0
Visible if PC14
= 1
Visible if PC14
= 1
Visible if PC14
= 1
Visible if PC14
= 1
Visible if PC14
= 1
Visible if PC14
= 1
Visible if PG12
= 1
Visible if PG12
= 1
Page
39
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Inverter comp.
speedup
Circuit 2
Inverter
compressor time
of the compressor.
Minimum compressor value
with circuit 1 inverter
Compressor speedup time
with circuit 1 inverter
Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 1
neutral zone reg.)
Minimum suction setpoint
value pertaining to the
compressors of circuit 2
Maximum suction setpoint
value pertaining to the
compressors of circuit 2
Sets the type of regulation
for controlling the circuit 2
compressors
Integral time Ti for side
band regulation of circuit 2
compressors
Proportional band Bp for
side band regulation of
circuit 2 compressors
Zone value for neutral zone
regulation of circuit 2
compressors
Differential, for neutral zone
regulation, within which the
calculation for the
insertion/release time of the
subsequent step varies.
Circuit 2
Minimum insertion time for
subsequent compressor step
( circuit 2 neutral zone reg.)
Maximum insertion time for
subsequent compressor step
( circuit 2 neutral zone reg.)
Minimum release time for
subsequent compressor step
( circuit 2 neutral zone reg.)
Maximum release time for
subsequent compressor step
( circuit 2 neutral zone reg.)
Differential for compressor
regulation with circuit 2
inverter
Suction setpoint offset for
circuit 2 inverter regulation
of the compressor.
Minimum compressor value
with circuit 2 inverter
Compressor speedup time
with circuit 2 inverter
Inverter ramp. Time taken
for the inverter to go from
0.0 0.0 100.0 % IS-RC
0 0 999 Sec IS-RC
10 0 999 Sec IS-RC
Visible if PG12
= 1
Visible if PG12
= 1
Visible if PG12
= 1
0.1 PH01
SPC2
Bar IS-RC
2.5 SPC2
PH02
Bar IS-RC
Neutral
Zone (1)
600 0 999 Sec IS-RC
Side
Band (0)
Neutral
Zone (1)
IS-RC
0.5 0 20.0 Bar IS-RC
0.5 0 20.0 Bar IS-RC
0.5 0 20.0 Bar IS-RC
20 0 PC41
Sec IS-RC
60 PC40
999 Sec IS-RC
10 0 PC43
Sec IS-RC
60 PC42
999 Sec IS-RC
0.5 0.0 20.0 Bar IS-RC
0.0 -20.0 20.0 Bar IS-RC
0.0 0.0 100.0 % IS-RC
0 0 999 Sec IS-RC
10 0 999 Sec IS-RC
Visible if PG01
> 1
Visible if PG01
> 1
Visible if PG01
> 1
Visible if PG01
> 1 and PG34 =
0
Visible if PG01
> 1 and PG34 =
0
Visible if PG01
> 1 and PG34 =
1
Visible if PG01
> 1 and PG34 =
1
Visible if PG01
> 1 and PG34 =
1
Visible if PG01
> 1 and PG34 =
1
Visible if PG01
> 1 and PG34 =
1
Visible if PG01
> 1 and PG34 =
1
Visible if PG01
> 1 and PG16 =
1
Visible if PG01
> 1 and PG16 =
1
Visible if PG01
> 1 and PG16 =
1
Visible if PG01
> 1 and PG16 =
1
Visible if PG01
> 1 and PG16 =
Page
40
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
PC52
PC53
PC54
PC56
PC57
PC58
PC59
Circuit 2
Compressor min.
setpoint
Circuit 3
Compressor
max. setpoint
Circuit 3
Compressor
regulation
Circuit 3
Compressor
integral time
Circuit 3
Compressor
proportional
band. Circuit 3
Comp. zone
Circuit 3
Comp. zone
differential
Circuit 3
the minimum value to the
maximum value ( circuit 2
neutral zone reg.)
Minimum suction setpoint
value pertaining to the
compressors of circuit 3
Maximum suction setpoint
value pertaining to the
compressors of circuit 3
Sets the type of regulation
for controlling the circuit 3
compressors
Integral time Ti for side
band regulation of circuit 3
compressors
Proportional band Bp for
side band regulation of
circuit 3 compressors
Zone value for neutral zone
regulation of circuit 3
compressors
Differential, for neutral zone
regulation, within which the
calculation for the
insertion/release time of the
subsequent step varies.
Circuit 3
1
0.1 PH01
SPC3
Bar IS-RC
2.5 SPC3
PH02
Bar IS-RC
Neutral
Zone (1)
600 0 999 Sec IS-RC
0.5 0 20.0 Bar IS-RC
Side
Band (0)
Neutral
Zone (1)
IS-RC
0.5 0 20.0 Bar IS-RC
0.5 0 20.0 Bar IS-RC
Visible if PG01
> 2
Visible if PG01
> 2
Visible if PG01
> 2
Visible if PG01
> 2 and
PC54 = 0
Visible if PG01
> 2 and
PC54 = 0
Visible if PG01
> 2 and
PC54 = 1
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Minimum insertion time for
subsequent compressor step
( circuit 3 neutral zone reg.)
Maximum insertion time for
subsequent compressor step
( circuit 3 neutral zone reg.)
Minimum release time for
subsequent compressor step
( circuit 3 neutral zone reg.)
Maximum release time for
subsequent compressor step
( circuit 3 neutral zone reg.)
Differential for compressor
regulation with circuit 3
inverter
Suction setpoint offset for
circuit 3 inverter regulation
of the compressor.
Minimum compressor value
with circuit 3 inverter
Compressor speedup time
with circuit 3 inverter
Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 3
neutral zone reg.)
Type of rotation used for
compressor management:
0: FIFO
1: LIFO
2: FIFO+HR
3: LIFO+HR
Sets the increment trigger
mode:
0: CpCp_pCpC
1: CCpp_ppCC
2: CpCp_ppCC
3: CCpp_pCpC
Sets the relay logic used for
the compressor increments:
0: NC = normally closed
(e.g. Copeland)
1: NO = normally open (e.g.
Feeders)
20 0 PC61
60 PC60
999 Sec IS-RC
10 0 PC63
60 PC62
999 Sec IS-RC
0.5 0.0 20.0 Bar IS-RC
0.0 -20.0 20.0 Bar IS-RC
0.0 0.0 100.0 % IS-RC
0 0 999 Sec IS-RC
10 0 999 Sec IS-RC
FIFO
CpCp_pCpC
NO
FIFO (0)
CpCp_pCpC
(0)
NC (0)
LIFO +
HR (3)
CCpp_pCpC
(3)
NO (1)
Sec IS-RC
Sec IS-RC
IS-C
IS-C
IS-C
Visible if PG01
> 2 and
PC54 = 1
Visible if PG01
> 2 and
PC54 = 1
Visible if PG01
> 2 and
PC54 = 1
Visible if PG01
> 2 and
PC54 = 1
Visible if PG01
> 2 and
PG22 = 1
Visible if PG01
> 2 and
PG22 = 1
Visible if PG01
> 2 and
PG22 = 1
Visible if PG01
> 2 and
PG22 = 1
Visible if PG01
> 2 and
PG22 = 1
42
Page
PC04
PC05
PC06
PC07
PC08
PC09
PC10
PC11
PC31
PC51
PC69
PC70
PC71
PC72
TMinOn
TMinOff
TOnOn
TOnOther
TOffOther
TOnParz
TOffParz
Comp. probe
error Circuit 1
Comp. probe
error Circuit 2
Comp. probe
error Circuit 3
TRestart
Enable HP
prevention
HP prevention
C1 limit SP
HP prevention
C2 limit SP
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Minimum time for which
the compressor must remain
on, even if switching off
requested
Minimum time for which
the compressor must remain
off, even if switching on
requested
Minimum time that must
elapse before the same
compressor can be switched
on.
Minimum time that must
elapse before another
compressor can be switched
on
Minimum time that must
elapse before another
compressor can be switched
off
Minimum time between
switching on of increments
Minimum time between
switching off of increments
Number of compressors that
will be forced if an alarm
occurs on the circuit 1
suction probe
Number of compressors that
will be forced if an alarm
occurs on the circuit 2
suction probe
Number of compressors that
will be forced if an alarm
occurs on the circuit 3
suction probe
Minimum compressor
switch on wait time
following a system
reset/black-out
Enable compressor
increments at high pressure
0: NO
1: YES
Set compressor increment
pressure (circuit 1)
Set compressor increment
pressure (circuit 2)
10 0 999 Sec IS-C
120 0 999 Sec IS-C
360 0 999 Sec IS-C
20 0 999 Sec IS-C
20 0 999 Sec IS-C
20 0 999 Sec IS-C
20 0 999 Sec IS-C
1 0 PG11
1 0 PG15
1 0 PG21
0 0 999 Sec IS-C
0 (NO)
0 (NO)
22.0 PH03
22.0 PH03
1 (SI)
PH04
PH04
Bar IS-C
Bar IS-C
IS-C
IS-C
IS-C
IS-C
Visible if PG01
> 1
Visible if PG01
> 2
Visible if PG01
> 1
Page
43
PC73
PC74
PC75
PC76
PC78
PC81
PC82
PC83
PC84
PC85
PC86
PC87
PC88
PC89
PC90
PC91
PC92
PF12
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
HP prevention
C3 limit SP
HP prevention
differential
HP prevention
hold time
HP prevention
percentage
Side band step
overlap
Comp. 1 power Compressor 1 power output
Comp. 2 power Compressor 2 power output
Comp. 3 power Compressor 3 power output
Comp. 4 power Compressor 4 power output
Comp. 5 power Compressor 5 power output
Comp. 6 power Compressor 6 power output
Comp. 7 power Compressor 7 power output
Comp. 8 power Compressor 8 power output
Comp. 9 power Compressor 9 power output
Comp 10
power
Comp 11
power
Comp. 12 power
Fan min. setpoint
Circuit 1
Set compressor increment
pressure (circuit 3)
Comp. increment pressure
differential
Minimum comp. increment
hold time
Increment percentage
Compressor side band step
overlap factor
Compressor 10 power
output
Compressor 11 power
output
Compressor 12 power
output
Minimum supply setpoint
value pertaining to the
circuit 1 fans
22.0 PH03
4.0 0.1 10.0 Bar IS-C
0 0 999 Min IS-C
50 0 100 % IS-C
0 0 100 % IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1 0 5000 kW IS-C
1.0 PH03
PH04
Bar IS-C
SPF1
Bar IS-RF
Visible if PG01
> 2
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
Visible if PG03
= 1;
Visibility
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
Page
44
PF13
PF14
PF16
PF17
PF18
PF20
PF24
PF25
PF26
PF27
PF28
PF32
PF33
PF34
PF36
PF37
Fan max,
setpoint
Circuit 1
Fan regulation
Circuit 1
Fan integral time
Circuit 1
Fan proportional
band. Circuit 1
Fan zone
Circuit 1
Fan TOn/TOff
Circuit 1
Fan inverter
differential
Circuit 1
Fan inverter SP
offset.
Circuit 1
Fan inverter
minimum
Circuit 1
Fan inverter
speedup
Circuit 1
Fan inverter time
Circuit 1
Fan min. setpoint
Circuit 2
Fan max,
setpoint
Circuit 2
Fan regulation
Circuit 2
Fan integral time
Circuit 2
Fan proportional
band. Circuit 2
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Maximum supply setpoint
value pertaining to the
circuit 1 fans
Sets the type of regulation
for controlling the circuit 1
fans
Integral time Ti for side
band regulation of circuit 1
fans
Proportional band Bp for
side band regulation of
circuit 1 fans
Zone value for neutral zone
regulation of circuit 1 fans
Next fan insertion/release
time ( circuit 1 neutral zone
reg.)
Differential for fan
regulation with circuit 1
inverter
Suction setpoint offset for
circuit 1 inverter regulation
of the fan.
Minimum fan value with
circuit 1 inverter
Fan speedup time with
circuit 1 inverter
Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 1
neutral zone reg.)
Minimum supply setpoint
value pertaining to the
circuit 2 fans
Maximum supply setpoint
value pertaining to the
circuit 2 fans
Sets the type of regulation
for controlling the circuit 2
fans
Integral time Ti for side
band regulation of circuit 2
fans
Proportional band Bp for
side band regulation of
circuit 2 fans
25.0 SPF1
Side
Band (0)
Band (0)
600 0 999 Sec IS-RF
0.5 0 20.0 Bar IS-RF
1.0 0 20.0 Bar IS-RF
10 0 999 Sec IS-RF
0.5 0.0 20.0 Bar IS-RF
0.0 -20.0 20.0 Bar IS-RF
0.0 0.0 100.0 % IS-RF
2 0 999 Sec IS-RF
10 0 999 Sec IS-RF
1.0 PH03
25.0 SPF2
Side
600 0 999 Sec IS-RF
0.5 0 20.0 Bar IS-RF
Side
Band (0)
Side
Band (0)
PH04
Neutral
Zone (1)
SPF2
PH04
Neutral
Zone (1)
Bar IS-RF
IS-RF
Bar IS-RF
Bar IS-RF
IS-RF
Visible if PF14
= 0
Visible if PF14
= 0
Visible if PF14
= 1
Visible if PF14
= 1
Visible if PG42
= 1
Visible if PG42
= 1
Visible if PG42
= 1
Visible if PG42
= 1
Visible if PG42
= 1
Visible if PG01
> 1 and PG30 =
0
Visible if PG01
> 1 and PG30 =
0
Visible if PG01
> 1 and PG30 =
0
Visible if PG01
> 1 and PG30 =
0 and
PF34 = 0
Visible if PG01
> 1 and PG30 =
0 and
PF34 = 0
Page
45
PF38
PF40
PF44
PF45
PF46
PF47
PF48
PF52
PF53
PF54
PF56
PF57
PF58
PF60
Fan zone
Circuit 2
Fan TOn/TOff
Circuit 2
Fan inverter
differential
Circuit 2
Fan inverter SP
offset.
Circuit 2
Fan inverter
minimum
Circuit 2
Fan inverter
speedup
Circuit 2
Fan inverter time
Circuit 2
Fan min. setpoint
Circuit 3
Fan max,
setpoint
Circuit 3
Fan regulation
Circuit 3
Fan integral time
Circuit 3
Fan proportional
band. Circuit 3
Fan zone
Circuit 3
Fan TOn/TOff
Circuit 3
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Zone value for neutral zone
regulation of circuit 2 fans
Next fan insertion/release
time ( circuit 2 neutral zone
reg.)
Differential for fan
regulation with circuit 2
inverter
Suction setpoint offset for
circuit 2 inverter regulation
of the fan.
Minimum fan value with
circuit 2 inverter
Fan speedup time with
circuit 2 inverter
Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 2
neutral zone reg.)
Minimum supply setpoint
value pertaining to the
circuit 3 fans
Maximum supply setpoint
value pertaining to the
circuit 3 fans
Sets the type of regulation
for controlling the circuit 3
fans
Integral time Ti for side
band regulation of circuit 3
fans
Proportional band Bp for
side band regulation of
circuit 3 fans
Zone value for neutral zone
regulation of circuit 3 fans
Next fan insertion/release
time ( circuit 3 neutral zone
reg.)
1.0 0 20.0 Bar IS-RF
10 0 999 Sec IS-RF
0.5 0.0 20.0 Bar IS-RF
0.0 -20.0 20.0 Bar IS-RF
0.0 0.0 100.0 % IS-RF
2 0 999 Sec IS-RF
10 0 999 Sec IS-RF
1.0 PH03
25.0 SPF3
Side
Band (0)
600 0 999 Sec IS-RF
0.5 0 20.0 Bar IS-RF
1.0 0 20.0 Bar IS-RF
10 0 999 Sec IS-RF
Side
Band (0)
SPF3
PH04
Neutral
Zone (1)
Bar IS-RF
Bar IS-RF
IS-RF
Visible if PG01
> 1 and PG30 =
0 and
PF34 = 1
Visible if PG01
> 1 and PG30 =
0 and
PF34 = 1
Visible if PG01
> 1 and PG30 =
0 and
PG46 = 1
Visible if PG01
> 1 and PG30 =
0 and
PG46 = 1
Visible if PG01
> 1 and PG30 =
0 and
PG46 = 1
Visible if PG01
> 1 and PG30 =
0 and
PG46 = 1
Visible if PG01
> 1 and PG30 =
0 and
PG46 = 1
Visible if PG01
> 2 and PG30 =
0
Visible if PG01
> 2 and PG30 =
0
Visible if PG01
> 2 and PG30 =
0
Visible if PG01
> 2 and PG30 =
0 and
PF54 = 0
Visible if PG01
> 2 and PG30 =
0 and
PF54 = 0
Visible if PG01
> 2 and PG30 =
0 and
PF54 = 1
Visible if PG01
> 2 and PG30 =
0 and
PF54 = 1
Page
46
PF64
PF65
PF66
PF67
PF68
PF01
PF02
PF07
PF08
PF11
PF31
PF51
PF71
Fan inverter
minimum
Circuit 3
Fan inverter SP
offset.
Circuit 3
Fan inverter
minimum
Circuit 3
Fan inverter
speedup
Circuit 3
Fan inverter time
Circuit 3
Fan rotation
Enable
compressor
regulation
TOnOther
TOffOther
Fan probe error
Circuit 1
Fan probe error
Circuit 2
Fan probe error
Circuit 3
Enable floating
condensation
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Differential for fan
regulation with circuit 3
inverter
Suction setpoint offset for
circuit 3 inverter regulation
of the fan.
Minimum fan value with
circuit 3 inverter
Fan speedup time with
circuit 3 inverter
Inverter ramp. Time taken
for the inverter to go from
the minimum value to the
maximum value ( circuit 3
neutral zone reg.)
Type of rotation used for
fan management:
0: FIFO
1: LIFO
2: FIFO + time
3: LIFO + time
If enabled, allows selection
of fan regulation, only if at
least one compressor is on
Minimum time that must
elapse before another fan
can be switched on
Minimum time that must
elapse before another fan
can be switched off
Number of fans that will be
forced if an alarm occurs on
the circuit 1 supply probe
Number of fans that will be
forced if an alarm occurs on
the circuit 2 supply probe
Number of fans that will be
forced if an alarm occurs on
the circuit 3 supply probe
Enables floating
condensation for fan
management
0.5 0.0 20.0 Bar IS-RF
0.0 -20.0 20.0 Bar IS-RF
0.0 0.0 100.0 % IS-RF
2 0 999 Sec IS-RF
10 0 999 Sec IS-RF
LIFO
FIFO
FIFO (0)
NO
NO (0) YES (1)
2 0 999 Sec
2 0 999 Sec
1 0 PG41
1 0 PG45
1 0 PG51
NO
NO (0) YES (1)
+ time
(3)
Visible if PG01
> 2 and PG30 =
0 and
IS-F
PG52 = 1
Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1
Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1
Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1
Visible if PG01
> 2 and PG30 =
0 and
PG52 = 1
IS-F
IS-F
IS-F
IS-F
Visible if PG01
IS-F
IS-F
IS-F
> 1 and
PG30 = 0
Visible if PG01
> 2 and
PG30 = 0
Page
47
PF72
PF73
PF74
PF78
PH01
PH02
PH03
PH04
PH05
PH06
PH07
PH08
PH09
PH10
PH11
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Floating
condensation
offset
Set floating
condensation
min.
Set floating
condensation
max.
Side band step
overlap
Minimum fullscale suction
Maximum fullscale suction
Minimum fullscale supply
Maximum fullscale supply
System ON/OFF
from keypad
Circuit ON/OFF
from keypad
System ON/OFF
from DI
Circuits ON/OFF
from DI
System ON/OFF
from supervisor
Circuits ON/OFF
from supervisor
Modbus address Card Modbus address
Floating condensation
temperature variation offset
Minimum floating
condensation limit value
Maximum floating
condensation limit value
Fan side band step overlap
factor
Sets the minimum full-scale
value for the suction probe
Sets the maximum full-scale
value for the suction probe
Sets the minimum full-scale
value for the supply probe
Sets the maximum full-scale
value for the supply probe
Enables switching the
machine on/off by pressing
the ESC key
Enables switching circuits
on/off by pressing the
relevant key
Enables switching the
machine on/off from the
digital input
Enables switching circuits
on/off from the relevant
digital input
Enables switching the
machine on/off from the
supervisor
Enables switching circuits
on/off from the supervisor
0.0 -20.0 20.0 °C
30.0 10.0 45.0 °C
40.0 10.0 45.0 °C
0 0 100 % IS-F
-0.5 -10.0 PH02
7.0 PH01
0.0 -10.0 PH04
30.0 PH03
YES
NO (0) YES (1)
45.0 Bar IS-V
45.0 Bar IS-V
Bar IS-V
Bar IS-V
IS-V
IS-F
IS-F
IS-F
NO
NO (0) YES (1)
IS-V
NO
NO (0) YES (1)
IS-V
NO
NO (0) YES (1)
IS-V
NO
NO (0) YES (1)
IS-V
NO
1 1 247 IS-V
NO (0) YES (1)
IS-V
Page
48
PH12
PH13
PH14
PH15
PH20
PH21
PH23
PH24
PH25
PH26
PH31
PH32
PH33
PH35
Modbus baud
rate
Modbus parity
Modbus stop bit
Restore default
parameters
Compressors
inverter consent
logic
Fans inverter
consent logic
Enable
environment
temp. probe
Enable external
temp. probe
Enable
secondary
setpoint from DI
Enable
secondary
setpoint from
supervisor
Refrigerant
Temperature
UoM
Pressure UoM
Enable suction
load
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Card communication baud
rate
0: 1200 KBit
1: 2400 KBit
2: 4800 KBit
3: 9600 KBit
4: 19200 KBit
Modbus parity
0: None
1: Odd
2: Even
Modbus stop bit
0: 1 stop bit
1: 2 stop bits
This restores the factory
default settings if activated
Command logic digital
output for compressors
inverter consent
= 0: Energized contact
= 1: Energized contact
Command logic digital
output for fans inverter
consent
= 0: Energized contact
= 1: Energized contact
Enables the probe (AI07)
for measuring environment
temperature
Enables the probe (AI08)
for measuring the external
temperature
Enables the secondary
setpoint function from the
digital input
Enables the secondary
setpoint function from the
supervisor
Sets the type of refrigerant
used (temperature-pressure
conversion)
0: No refrigerant
1: R22
2: R134a
3: R404A
4: R407C
5: R410A
6: R507
Sets the units of
measurement for
temperature:
0: °C
1: °F
Sets the units of
measurement for pressure:
0: Bar
1: psi
Enables compensation for
loss of load over the suction
9600
(3)
Even
(2)
1
(0)
NO
NO NO (0) NC (1) - IS-V
NO NO (0) NC (1) - IS-V
NO
NO
NO
NO
3
R404A
0 (°C)
0 (Bar)
0 (NO)
1200
(0)
None
(0)
1
(0)
NO (0) YES (1)
NO (0) YES (1)
NO (0) YES (1)
NO (0) YES (1)
NO (0) YES (1)
0 6 IS-V
0 (°C)
0 (Bar)
0 (NO)
19200
(4)
Even
(2)
2
(1)
IS-V
1 (°F)
1 (psi)
1 (SI)
IS-V
IS-V
IS-V
IS-V
IS-V
IS-V
IS-V
IS-V
IS-V
IS-V
Page
49
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
compensation
line (neutral zone)
0: NO
1: YES
Page
50
PH36
PH40
PH43
PH44
PH45
PH47
PH53
PSd3
PH17
PH18
PH19
Suction load
compensation
offset
Measurement
unit
AI1 probe type
AI2 probe type
AI3_4 probe
type
AI5_6 probe
type
Buzzer enable
Installer PSd
DI alarm logic
DO alarm logic
Other DI logic
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Load loss compensation
factor
Sets the display for
temperature or pressure
0: Pressure
1: Temperature
Sets the type of AI01
analogue input:
2: NTC
3: 0-20mA
4: 4-20mA
Sets the type of AI02
analogue input:
2: NTC
3: 0-20mA
4: 4-20mA
Sets analogue input type for
AI03 and AI04:
2: NTC
3: 0-20mA
4: 4-20mA
Sets analogue input type for
AI05 and AI06:
2: NTC
3: 0-20mA
4: 4-20mA
Enables the buzzer to sound YES (1) NO (0) YES (1)
Installer level password
Sets the digital input alarm
logic used for controlling
the alarms:
0: Normally open NO
1: Normally closed NC
Sets the logic for the relays
used for the alarms
0: Normally open NO
1: Normally closed NC
Sets the digital input alarm
logic used for controlling
the following functions:
- Global remote OnOff
- Circuit remote OnOff
- compressor/fan secondary
setpoint
0: Normally open NO
1: Normally closed NC
ALARM PARAMETERS
0.2 0.1 5.0 Bar IS-V
0
(Pres.)
4
4-20mA
4
4-20mA
4
4-20mA
4
4-20mA
0
(Pres.)
2 4 IS-V
2 4 IS-V
2 4 IS-V
2 4 IS-V
1
(Temp.)
0 -999 9999 IS-V
NC
NO (0)
NC (1)
NO
NO (0)
NC (1)
NO
NO (0)
NC (1)
IS-V
IS-V
IS-S
IS-S
IS-S
Visible if
PG01 > 1
Visible if
PG01 > 2
Page
51
PA01
PA02
PA03
PA04
PA05
PA06
PA07
PA08
PA09
PA10
PA11
PA12
PA13
PA14
PA23
PA15
PA16
PA17
PA18
PA19
PA20
PA21
PA22
PA25
PA26
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Enable
compressor
operation time
alarm
Enable fan
operation time
alarm
> 1
Visible if PG01
> 1 and PG30 =
0
Visible if PG01
> 1 and PG30 =
0
Visible if PG01
> 1 and PG30 =
0
Visible if PG01
> 1 and PG30 =
0
Visible if PG01
> 2
Visible if PG01
> 2
Visible if PG01
> 2
Visible if PG01
> 2
Page
53
PA39
PA40
PA41
PA42
PH16
PG01
PG02
PG03
PG04
PG05
PG11
PG12
PG15
PG16
PG21
C3 supply LP
alarm setpoint
C3 supply LP
alarm diff.
C3 supply HP
alarm setpoint
C3 supply HP
alarm diff.
Compressor
safety device
type
Circuit number
Enable
expansion
Enable
differently
powered
compressors
Number of
increments per
compressor
Number of safety
devices per
compressor
Number of
compressors for
Circuit 1
Circuit 1 inverter
comp. enable
Number of
compressors for
Circuit 2
Circuit 2 inverter
comp. enable
Number of
compressors for
Circuit 3
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Enables the compressor
with circuit 3 inverter
Sets unique condensation
for the fan unit
Enables the fan thermal
safety device
Sets the number of fans for
SYSTEM BUILDER MENU PARAMETERS – Compressor and fan digital output positions
circuit 1
Enables the fan with circuit
1 inverter
Sets the number of fans for
circuit 2
Enables the fan with circuit
2 inverter
Sets the number of fans for
circuit 3
Enables the fan with circuit
3 inverter
Sets the type of control unit
for the first circuit*:
0: 1: BT
2: TN
3: AT
Sets the type of control unit
for the second circuit:
0: 1: BT
2: TN
3: AT
Sets the type of control unit
for the third circuit:
0: 1: BT
2: TN
3: AT
Selects the home page to be
displayed at machine
startup:
0: Global
1: Circuit1
2: Circuit 2*
3: Circuit 3*
System builder level
password
NO
NO (0)
SO (0)
NO
NO (0) YES (1)
YES
NO (0) YES (1)
2 0 12 CO-W
NO
NO (0) YES (0)
2 0 12 CO-W
NO
NO (0) YES (0)
0 0 12 CO-W
NO
NO (0) YES (0)
- - (0) AT (3)
- - (0) AT (3)
- - (0) AT (3)
Global
(0)
0 -999 9999 CO-Pa
Global
(0)
Circuit 3
(3)
CO-W
CO-W
CO-W
CO-W
CO-W
CO-W
CO-Pa
CO-Pa
CO-Pa
CO-Pa
Visible if PG01
> 2
Dual – triple
circuits only
Default = 3
Max = 8
on C-PRO
MEGA RACK
Default = 0
Max = 8
on C-PRO
MEGA RACK;
Visible if PG01
> 1 and PG30 =
0
Visible if PG01
> 1 and PG30 =
0
Max = 8
on C-PRO
MEGA RACK;
Visible if PG01
> 2 and PG30 =
0
Visible if PG01
> 2 and PG30 =
0
* In the case of
a single circuit
system the
parameter sets
the system type
Visible if PG01
> 1
Visible if PG01
> 2
* If PH27=2.3
and the relevant
circuit is not
enabled,
assume a
default value of
“0”
55
Page
HC01
HC11
HC21
HC31
HC02
HC12
HC22
HC32
HC03
HC13
HC23
HC33
C1 comp. DO
position
C1 increment 1
DO position
C1 increment 2
DO position
C1 increment 3
DO position
Compressor C2
DO position
C2 increment 1
DO position
C2 increment 2
DO position
C2 increment 3
DO position
Compressor C3
DO position
C3 increment 1
DO position
C3 increment 2
DO position
C3 increment 3
DO position
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Sets the position of the
digital output for
compressor 1
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 1
Sets the position of the
increment 2 digital output
for compressor 1
Sets the position of the
increment 3 digital output
for compressor 1
Sets the position of the
digital output for
compressor 2
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 2
Sets the position of the
increment 2 digital output
for compressor 2
Sets the position of the
increment 3 digital output
for compressor 2
Sets the position of the
digital output for
compressor 3
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 3
Sets the position of the
increment 2 digital output
for compressor 3
Sets the position of the
increment 3 digital output
for compressor 3
1 0 13 (26) CO-Hw
2 0 13 (26)
0 0 13 (26)
0 0 13 (26)
3 0 13 (26)
4 0 13 (26)
0 0 13 (26)
0 0 13 (26)
5 0 13 (26)
6 0 13 (26)
0 0 13 (26)
0 0 13 (26)
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Default = 0
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Default = 0
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Default = 4
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Default = 0
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
Page
56
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
HC04
HC14
HC24
HC34
HC05
HC15
HC25
HC35
HC06
HC16
HC26
HC36
HC07
HC17
Compressor C4
DO position
C4 increment 1
DO position
C4 increment 2
DO position
C4 increment 3
DO position
Compressor C5
DO position
C5 increment 1
DO position
C5 increment 2
DO position
C5 increment 3
DO position
Compressor C6
DO position
C6 increment 1
DO position
C6 increment 2
DO position
C6 increment 3
DO position
Compressor C7
DO position
C7 increment 1
DO position
Sets the position of the
digital output for
compressor 4
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 4
Sets the position of the
increment 2 digital output
for compressor 4
Sets the position of the
increment 3 digital output
for compressor 4
Sets the position of the
digital output for
compressor 5
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 5
Sets the position of the
increment 2 digital output
for compressor 5
Sets the position of the
increment 3 digital output
for compressor 5
Sets the position of the
digital output for
compressor 6
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 6
Sets the position of the
increment 2 digital output
for compressor 6
Sets the position of the
increment 3 digital output
for compressor 6
Sets the position of the
digital output for
compressor 7
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
7
8 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0
13 (26)
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
Default = 5
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Default = 0
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
Page
57
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
HC27
HC37
HC08
HC18
HC28
HC38
HC09
HC19
HC29
HC39
HC10
HC20
HC30
C7 increment 2
DO position
C7 increment 3
DO position
Compressor C8
DO position
C8 increment 1
DO position
C8 increment 2
DO position
C8 increment 3
DO position
Compressor C9
DO position
C9 increment 1
DO position
C9 increment 2
DO position
C9 increment 3
DO position
Compressor C10
DO position
C10 increment 1
DO position
C10 increment 2
DO position
for compressor 7
Sets the position of the
increment 2 digital output
for compressor 7
Sets the position of the
increment 3 digital output
for compressor 7
Sets the position of the
digital output for
compressor 8
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 8
Sets the position of the
increment 2 digital output
for compressor 8
Sets the position of the
increment 3 digital output
for compressor 8
Sets the position of the
digital output for
compressor 9
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 9
Sets the position of the
increment 2 digital output
for compressor 9
Sets the position of the
increment 3 digital output
for compressor 9
Sets the position of the
digital output for
compressor 10
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 10
Sets the position of the
increment 2 digital output
for compressor 10
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
0 0 13 (26)
CO-Hw
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
Page
58
HC40
HC50
HC51
HC52
HC53
HC60
HC61
HC62
HC63
HF01
HF02
HF03
C10 increment 3
DO position
Compressor C11
DO position
C11 increment 1
DO position
C11 increment 2
DO position
C11 increment 3
DO position
Compressor C12
DO position
C12 increment 1
DO position
C12 increment 2
DO position
C12 step 3 DO
position
Fan 1 DO
position
Fan 2 DO
position
Fan 3 DO
position
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Sets the position of the
increment 3 digital output
for compressor 11
Sets the position of the
digital output for
compressor 11
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 11
Sets the position of the
increment 2 digital output
for compressor 11
Sets the position of the
increment 3 digital output
for compressor 11
Sets the position of the
digital output for
compressor 12
Or compressor inverter
consent position
Sets the position of the
increment 1 digital output
for compressor 12
Sets the position of the
increment 2 digital output
for compressor 12
Sets the position of the step
3 digital output for
compressor 12
Sets the position of the
digital output for fan 1
Or fan inverter consent
position
Sets the position of the
digital output for fan 2
Or fan inverter consent
position
Sets the position of the
digital output for fan 3
Or fan inverter consent
position
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
10 0 13 (26)
11 0 13 (26)
12 0 13 (26)
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Default = 6
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Default = 7
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Default = 8
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*¹
*²
*²
*²
Page
59
HF04
HF05
HF06
HF07
HF08
HF09
HF10
HF11
HF12
HA01
HA11
HA21
HA31
Fan 4 DO
position
Fan 5 DO
position
Fan 6 DO
position
Fan 7 DO
position
Fan 8 DO
position
Fan 9 DO
position
Fan 10 DO
position
Fan 11 DO
position
Fan 12 DO
position
Global alarm DO
position
Circuit 1 alarm
DO pos.
Circuit 2 alarm
DO pos.
Circuit 3 alarm
DO pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Sets the position of the
digital output for fan 4
Or fan inverter consent
position
Sets the position of the
digital output for fan 5
Or fan inverter consent
position
Sets the position of the
digital output for fan 6
Or fan inverter consent
position
Sets the position of the
digital output for fan 7
Or fan inverter consent
position
Sets the position of the
digital output for fan 8
Or fan inverter consent
position
Sets the position of the
digital output for fan 9
Or fan inverter consent
position
Sets the position of the
digital output for fan 10
Or fan inverter consent
position
Sets the position of the
digital output for fan 11
Or fan inverter consent
position
Sets the position of the
digital output for fan 12
Or fan inverter consent
position
Sets the position of the
global alarm relay
Sets the position of alarm
relay for circuit 1
Sets the position of alarm
relay for circuit 2
Sets the position of alarm
relay for circuit 3
13 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
0 0 13 (26)
9 0 13 (26) CO-Hw
0 0 13 (26) CO-Hw
0 0 13 (26) CO-Hw
0 0 13 (26) CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
Default = 0
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Max = 8(16)
on C-PRO
MEGA RACK;
Visibility
Default = 2
Max = 8(16)
on C-PRO
MEGA RACK
Max = 8(16)
on C-PRO
MEGA RACK
Max = 8(16)
on C-PRO
MEGA RACK;
Visible if PG01
> 1
Max = 8(16)
on C-PRO
MEGA RACK;
Visible if PG01
> 2
*²
*²
*²
*²
*²
*²
*²
*²
*²
Page
60
Hd01
Hd02
Hd03
Hd11
Hd12
Hd13
Hd14
Hd15
Hd16
Hd21
Hd22
Hd23
Global OnOff DI
position
Comp. sec. setP
DI position
Fan sec. setP DI
position
C1 OnOff DI
position
C1 fluid level
alarm DI pos.
C1 suction LP
alarm DI pos.
C1 supply HP
alarm DI pos.
C1 comp. oil
diff. alarm DI
pos.
C1 comp. fan
thermal alarm DI
pos.
C2 OnOff DI
position
C2 fluid level
alarm DI pos.
C1 suction LP
alarm DI pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
SYSTEM BUILDER MENU PARAMETERS – Other hardware digital input/output positions
Sets the position of the
system global on/off digital
input
Sets the position for
compressor management
secondary setpoint digital
input
Sets the position for fan
management secondary
setpoint digital input
Sets the position of the
circuit 1 on/off digital input
Sets the position of the
circuit 1 fluid level alarm
digital input
Sets the position of the
circuit 1 suction pressureswitch low pressure alarm
digital input
Sets the position of the
circuit 1 supply pressureswitch high pressure alarm
digital input
Sets the position of the
circuit 1 compressor oil
differential alarm digital
input
Sets the position of the
circuit 1 common fan
thermal alarm digital input
Sets the position of the
circuit 2 on/off digital input
Sets the position of the
circuit 2 fluid level alarm
digital input
Sets the position of the
circuit 2 suction pressureswitch low pressure alarm
digital input
0 0 12 (22) CO-Hw
0 0 12 (22)
0 0 12 (22)
0 0 12 (22) CO-Hw
7 0 12 (22)
9 0 12 (22)
11 0 12 (22)
0 0 12 (22)
5 0 12 (22)
0 0 12 (22) CO-Hw
8 0 12 (22)
10 0 12 (22)
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
Max =10(18)
on C-PRO
MEGA RACK
Max =10(18)
on C-PRO
MEGA RACK
Max =10(18)
on C-PRO
MEGA RACK
Max =10(18)
on C-PRO
MEGA RACK
Default = 6
Max =10(18)
on C-PRO
MEGA RACK
Default = 7
Max =10(18)
on C-PRO
MEGA RACK
Default = 8
Max =10(18)
on C-PRO
MEGA RACK
Max =10(18)
on C-PRO
MEGA RACK
Max =10(18)
on C-PRO
MEGA RACK
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 1
Default = 0
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 1
Default = 0
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 1
Page
61
Hd24
Hd25
Hd26
Hd31
Hd32
Hd33
Hd34
Hd35
Hd36
Hd41
C2 supply HP
alarm DI pos.
C2 comp. oil
diff. alarm DI
pos.
C2 comp. fan
thermal alarm DI
pos.
C3 OnOff DI
position
C3 fluid level
alarm DI pos.
C3 suction LP
alarm DI pos.
C3 supply HP
alarm DI pos.
C3 comp. oil
diff. alarm DI
pos.
C3 comp. fan
thermal alarm DI
pos.
Comp. 1 thermal
DI pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Sets the position of the
circuit 2 supply pressureswitch high pressure alarm
digital input
Sets the position of the
circuit 2 compressor oil
differential alarm digital
input
Sets the position of the
circuit 2 common fan
thermal alarm digital input
Sets the position of the
circuit 3 on/off digital input
Sets the position of the
circuit 3 fluid level alarm
digital input
Sets the position of the
circuit 3 suction pressureswitch low pressure alarm
digital input
Sets the position of the
circuit 3 supply pressureswitch high pressure alarm
digital input
Sets the position of the
circuit 3 compressor oil
differential alarm digital
input
Sets the position of the
circuit 3 common fan
thermal alarm digital input
Sets the position of the
compressor 1 thermal alarm
digital input
12 0 12 (22)
0 0 12 (22)
CO-Hw
CO-Hw
6 0 12 (22)
CO-Hw
0 0 12 (22) CO-Hw
0 0 12 (22)
CO-Hw
0 0 12 (22)
CO-Hw
0 0 12 (22)
0 0 12 (22)
CO-Hw
CO-Hw
0 0 12 (22)
CO-Hw
1 0 12 (22)
CO-Hw
Default = 0
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 1 and PG30 =
0
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 1
Default = 0
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 1 and PG30 =
0
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 2
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 2
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 2
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 2 and PG30 =
0
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 2
Max =10(18)
on C-PRO
MEGA RACK;
Visible if PG01
> 2 and PG30 =
0
Max =10(18)
on C-PRO
MEGA RACK;
Visibility *¹
Page
62
Hd42
Hd43
Hd44
Hd45
Hd46
Hd47
Hd48
Hd49
Hd50
Comp. 2 thermal
DI pos.
Comp. 3 thermal
DI pos.
Comp. 4 thermal
DI pos.
Comp. 5 thermal
DI pos.
Comp. 6 thermal
DI pos.
Comp. 7 thermal
DI pos.
Comp. 8 thermal
DI pos.
Comp. 9 thermal
DI pos.
Comp. 10
thermal DI pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Sets the position of the
compressor 2 thermal alarm
digital input
2 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 3 thermal alarm
digital input
3 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 4 thermal alarm
digital input
4 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 5 thermal alarm
digital input
0 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 6 thermal alarm
digital input
0 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 7 thermal alarm
digital input
0 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 8 thermal alarm
digital input
0 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 9 thermal alarm
digital input
0 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 10 thermal
0 0 12 (22)
CO-Hw
Max
=10(18) on
Page
63
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Hd51
Hd52
Hd61
Hd62
Hd63
Comp. 11
thermal DI pos.
Comp. 12
thermal DI pos.
Compressor 1
pressure-switch
DI pos.
Compressor 2
pressure-switch
DI pos.
Compressor 3
pressure-switch
DI pos.
alarm digital input
Sets the position of the
compressor 11 thermal
alarm digital input
Sets the position of the
compressor 12 thermal
alarm digital input
Sets the position of the
compressor 1 pressureswitch alarm digital input
Sets the position of the
compressor 2 pressureswitch alarm digital input
Sets the position of the
compressor 3 pressureswitch alarm digital input
C-PRO
MEGA
RACK;
Visibility *¹
Max
0 0 12 (22)
CO-Hw
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Max
0 0 12 (22)
CO-Hw
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Max
=10(18) on
0 0 12 (22)
CO-Hw
C-PRO
MEGA
RACK;
Visibility *¹
Max
0 0 12 (22)
CO-Hw
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Max
0 0 12 (22)
CO-Hw
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Page
64
Hd64
Hd65
Hd66
Hd71
Hd72
Hd73
Hd74
Hd75
Hd76
Compressor 4
pressure-switch
DI pos.
Compressor 5
pressure-switch
DI pos.
Compressor 6
pressure-switch
DI pos.
Compressor 1 oil
diff. DI pos.
Compressor 2 oil
diff. DI pos.
Compressor 3 oil
diff. DI pos.
Compressor 4 oil
diff. DI pos.
Compressor 5 oil
diff. DI pos.
Compressor 6 oil
diff. DI pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Sets the position of the
compressor 4 pressureswitch alarm digital input
0 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 5 pressureswitch alarm digital input
0 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Sets the position of the
compressor 6 pressureswitch alarm digital input
0 0 12 (22)
CO-Hw
Max
=10(18) on
C-PRO
MEGA
RACK;
Visibility *¹
Max
=10(18) on
Position of the compressor 1
oil differential alarm digital
input
0 0 12 (22)
CO-Hw
C-PRO
MEGA
RACK;
Visibility *¹
Max
=10(18) on
Position of the compressor 2
oil differential alarm digital
input
0 0 12 (22)
CO-Hw
C-PRO
MEGA
RACK;
Visibility *¹
Max
=10(18) on
Position of the compressor 3
oil differential alarm digital
input
0 0 12 (22)
CO-Hw
C-PRO
MEGA
RACK;
Visibility *¹
Max
=10(18) on
Position of the compressor 4
oil differential alarm digital
input
0 0 12 (22)
CO-Hw
C-PRO
MEGA
RACK;
Visibility *¹
Max
=10(18) on
Position of the compressor 5
oil differential alarm digital
input
0 0 12 (22)
CO-Hw
C-PRO
MEGA
RACK;
Visibility *¹
Position of the compressor 6
oil differential alarm digital
0 0 12 (22)
CO-Hw
Max
=10(18) on
Page
65
Hd81
Hd82
Hd83
Hd84
Hd85
Fan 1 thermal DI
pos.
Fan 2 thermal DI
pos.
Fan 3 thermal DI
pos.
Fan 4 thermal DI
pos.
Fan 5 thermal DI
pos.
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
input
C-PRO
MEGA
RACK;
Visibility *¹
Max =10(18)
Sets the position of the fan 1
thermal alarm digital input
Sets the position of the fan 2
thermal alarm digital input
Sets the position of the fan 3
thermal alarm digital input
Sets the position of the fan 4
thermal alarm digital input
Sets the position of the fan 5
thermal alarm digital input
0 0 12 (22)
0 0 12 (22)
0 0 12 (22)
0 0 12 (22)
0 0 12 (22)
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
*²
*²
*²
*²
*²
Page
66
Hd86
Hd87
Hd88
Hd89
Hd90
Hd91
Hd92
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Max =10(18)
Fan 6 thermal DI
pos.
Fan 7 thermal DI
pos.
Fan 8 thermal DI
pos.
Fan 9 thermal DI
pos.
Fan 10 thermal
DI pos.
Fan 11 thermal
DI pos.
Fan 12 thermal
DI pos.
Once machine parameters are configured, and every time configuration parameters are modified, it is
recommended the system be switched off and restarted in order to allow the card to configure itself correctly.
Sets the position of the fan 6
thermal alarm digital input
Sets the position of the fan 7
thermal alarm digital input
Sets the position of the fan 8
thermal alarm digital input
Sets the position of the fan 9
thermal alarm digital input
Sets the position of the fan
10 thermal alarm digital
input
Sets the position of the fan
11 thermal alarm digital
input
Sets the position of the fan
12 thermal alarm digital
input
0 0 12 (22)
0 0 12 (22)
0 0 12 (22)
0 0 12 (22)
0 0 12 (22)
0 0 12 (22)
0 0 12 (22)
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
CO-Hw
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
Max =10(18)
on C-PRO
MEGA RACK;
Visibility
NOTES:
(*¹) Compressor visibility conditional.
Parameter visible if the compressor is configured: i.e. if the sum of the parameters indicating
the number of compressors per circuit (enabled) PG11, PG15, PG21 is greater than or equal
to the compressor in question.
(*¹) Fan visibility conditional.
Parameter visible if the fan is configured: i.e. if the sum of the parameters indicating the
number of fans per circuit (enabled) PG41, PG45, PG51 is greater than or equal to the fan in
question.
The Default values for certain parameters vary depending on which controller is being used; the
differences are highlighted in the parameter table Notes field.
*²
*²
*²
*²
*²
*²
*²
Page
67
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
6 REGULATIONS
6.1 Machine configuration
A Wizard (System builder menu) allows assisted configuration of the machine. The first choice
refers to the number of circuits (1, 2 or 3) by means of parameter PG01; in the case of dual and
triple circuit machines, the selection of the type of condensation, single or separate, (PG30) and the
presence, or otherwise, of an expansion unit (PG02) are also important. These 3 parameters define
the type of machine and the hardware supported, in accordance with the following table:
Machine type Single-circuit Dual-circuit Triple-circuit
Single
condensation
Probe AI 1
Probe AI 2
Probe AI 3
Probe AI 4
Probe AI 5
Probe AI 6
Probe AI 7
Probe AI 8
Analogue
output AO 1
Analogue
output AO 2
Analogue
output AO 3
Analogue
output AO 4
Number of
digital inputs
Number of
digital outputs
Suction pressure*³
n.r.
Supply pressure*
-
-
- -
- - -
Environment
temperature
External
temperature
Compressor with
inverter
Fan with inverter
12 (22)*
13 (26)*
-
-
¹
¹
C1 suction
pressure*³
³
C1 supply
pressure*
C2 suction
pressure*³
C2 supply
pressure*
Environment
temperature
External
temperature
Compressor with
inverter C1
Compressor with
inverter C2
Fan with
inverter C1
Fan with inverter
12 (22)*
13 (26)*
NO
C2
³
³
¹
¹
YES
C1 suction
pressure*³
Supply pressure*
C2 suction
pressure*³
C3 suction
pressure*³
Environment
temperature
External
temperature
Compressor with
inverter C1
Compressor with
inverter C2
Fan with inverter
12 (22)*
13 (26)*
-
C1
- - Fan with inverter
¹
¹
C1 suction
pressure*³
³
C1 supply
pressure*
C2 suction
pressure*³
C2 supply
pressure*
C3 suction
pressure*³
C3 supply
pressure*
Environment
temperature
External
temperature
Compressor /
Fan with inverter
Compressor /
Fan with inverter
Compressor / Fan
with inverter C3 *
12 (22)*
13 (26)*
NO
C1 *
C2 *
³
Supply pressure*
³
³
Environment
temperature
temperature
Compressor /
Fan with inverter
²
Compressor with
²
inverter C2 *
Compressor with
²
inverter C3 *
¹
¹
(*¹) If there is an expansion unit, the number of digital inputs and outputs increases, and it is
possible
to configure more hardware, depending on requirements.
(*²) In triple-circuit machines, inverter use is exclusively between compressors and fans.
(*³) The probes can also measure temperature by changing the relevant driver parameters: PH43,
PH44, PH45, PH47. Temperature is transformed into pressure by selecting the type of refrigerant
gas used (parameter PH31).
YES
C1 suction
pressure*³
C2 suction
pressure*³
-
C3 suction
pressure*³
-
External
C1 *
²
12 (22)*
13 (26)*
¹
¹
³
²
²
68
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
The same wizard also sets the number of compressors and fans for each circuit, the presence of an
inverter, compressors and fans, the number of increments and compressor safety devices and
enables fan safety devices.
Note: Enabling the inverter for the compressors regulation, the FIRST compressor will be that
commanded by the inverter, the other following compressors will be hermetic type (without
capacity stages) and will be commanded by a relay digital output.
Likewise, enabling the inverter for the fans regulation, the FIRST fan will be that commanded by
the inverter, the other following fans will be commanded by a relay digital output.
For each inverter in necessary to configure the digital outputs position for the consent at device
activation.
6.2 Machine and individual circuit status
There are several procedures for switching the unit or individual circuits on/off:
1) Using the relevant On/Off key (parameter enabled function)
Machine/circuit on: press and hold the relevant key for approx. 2 seconds: if all other
enabled conditions are present, the machine or individual circuit will be switched “ON”.
Machine/circuit off: press and hold the relevant key for approx. 2 seconds: the machine or
individual circuit will be switched “OFF”.
2) Using the digital inputOn/Off command (parameter enabled function)
Machine/circuit on: close the remote On/Off contact: if all other enabled conditions are
present, the machine or individual circuit will be switched “ON”.
Machine/circuit off: if the remote On/Off contact is open, the machine or individual circuit
is switched “OFF by digital input” (indicated by the wording “OFF_D” for the individual
circuit status).
3) By means of the supervision protocol (parameter enabled function)
Machine/circuit on: activate the on state by means of the protocol: if all other enabled
conditions are present, the machine or individual circuit will be switched “ON”.
Machine/circuit off: if the on state is deactivated from the protocol, the machine or
individual circuit is switched “OFF by supervision protocol” (indicated by the wording
“OFF_S” for the individual circuit status).
The status of “On/Off by key” overrides the other two, indeed, the “On/Off by digital input and
supervision protocol” statuses can only be achieved when the machine is switched on using the
appropriate key.
A machine that is switched off by digital input can:
⋅ be switched to the OFF status by key (by pressing the ESC key).
⋅ be switched to the OFF by supervisor state if fulfilling the “OFF by digital input”
conditions, and the “OFF by supervisor” status is set.
⋅be switched to the ON state if fulfilling the “OFF by digital input” conditions, and the “OFF
by supervisor” status is not set.
A machine that is switched off by supervision protocol can:
⋅ be switched to the OFF status by key (by pressing the ESC key).
⋅ be switched to the “OFF by digital input state” if fulfilling the “OFF by supervisor”
conditions, and the “OFF by digital input” status is tripped.
Page
69
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
⋅be switched to the ON state if fulfilling the “OFF by supervisor” conditions, and the “OFF
by digital input” condition is not met.
The machine On/Off key is the ESC key, pressed for approx. 2 seconds.
The remote On/Off inputs (if present) are configured by means of the relevant parameters.
Page
70
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
6.3 Compressor regulation
Control of compressor suction pressure envisages the management of the latter in order to reach and
maintain a defined working pressure value: depending on the type of control (side band or neutral
zone) and the use, or otherwise, of inverters for fine adjustment, four types of regulation are
envisaged.
6.3.1 Side band regulation
Side band control exploits the characteristics of PI (proportional and integral) or P (proportional)
regulators to establish when to insert or disengage the compressors used, so as to regularise, within
the differential band, the switching on and off of the various devices. The purpose of PI regulation
is to have no error in full operation.
The parameters defining this regulation are as follows:
⋅ Integral time (IT)
⋅ Proportional band (PB)
⋅ Side band suction SetPoint (SP)
Steps
Max Steps
Suction pressure
SP SP + BP
The above figure shows the behaviour of band regulation (SP, SP + PB). Depending on the suction
pressure value, regulation adds or removes the number of steps to request from the compressors.
Under such regulation, the band is displaced above the setpoint.
It is possible to select whether control will refer to PI or just P regulation, by either setting the
parameter for integral action, namely the integration time (TI), or otherwise. In the specific case
where this parameter is set to the value zero, regulation is proportional only, otherwise, it is also
integral. Ti corresponds to the time necessary for integral action, assuming constant error, to
equalise the proportional action: the speed of this action is proportional to the integration time
value. The default parameter is greater than zero, hence, by default, regulation exploits the
proportional-integral characteristic.
Page
71
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
The PC78 Sideband step overlap parameter allows improvements in the behaviour of this type of
regulation, which requires broad proportional bands in order to be stable, thus modifying the
subdivision of the regulation band between steps:
Steps
Release
PC78 %
SP SP + BP
100 - PC78 %
Insertion
Max Steps
Suction
The insertion of steps occurs at PC78% of the proportional band, while release occurs at 100 – PC78% of the band; if for example PC78 = 60%, steps are inserted between 60% and the maximum
value (100%) of the proportional band PB, and in the same way released between 40% and the
minimum value (0%) of the same band PB.
It is obvious that by using step division, as indicated in the figure, the activity interval of each
individual step is greater with respect to standard geometric division, with the obvious advantage
that the proportional band may be reduced, in favour of greater regulation accuracy, and/or the
activation of the steps occurs with reduced frequency, or reduced compressor start-ups, to the
benefit of the mechanical lifespan of the same.
6.3.2 Neutral zone regulation
This type of regulation envisages the definition of a neutral zone, within which no activation or
deactivation decision will be taken, i.e. startup operations will not be requested for any of the
devices.
The parameters defining this regulation are as follows:
⋅ Neutral zone (NZ)
⋅ Out of zone differential (Diff)
⋅ Side band suction SetPoint (SP)
Outwith said neutral zone, device on or off requests for the various steps provided by the
compressors will follow this logic:
⋅ Switch on : When the suction pressure exceeds the setPoint + Neutral Zone threshold
⋅ Switch off : when the pressure drops below the setPoint
In this type of regulation, the neutral zone is displaced to the right of the setPoint.
As may be deduced from the figure, regulation envisages setting times, within which, depending on
NZ_TOnMax NZ_TOffMax
Switching on Switching off
NZ_TOffMin Neutral zone
SP SP + ZN SP + ZN + Diff SP - Diff
72
Page
NZ_TOnMin
Suction pressure
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
the zone, the on and off requests for the various steps must be timed. The relevant parameters are as
follows:
⋅ Minimum switch-on time (NZ_TOnMin)
⋅ Maximum switch-on time (NZ_TOnMax)
⋅ Minimum switch-off time (NZ_TOffMin)
⋅ Maximum switch-off time (NZ_TOffMax)
On the basis of the suction pressure value approaching the reference value, the times will vary
proportionally according to the values set. Depending on the circumstances, the reference value
mentioned represents the right and left limit of the neutral zone with the addition of a further
differential (settable by means of a parameter) within which will be the proportional variation for
the time in question.
At the regulation limits, the on and off time values are the maximum and minimum times set by the
parameter. To make the request time constant during switching on, simply set parameters
NZ_TOnMin and NZ_TOnMax to the same value. The same applies for switching off.
6.3.3 Side band regulation with inverter
This type of control introduces inverter control to normal side band control, and in order to do this it
is essential to set several parameters relating to the inverter device it is intended to use, in addition
to enabling its use. The parameters in question are the following:
⋅ Inverter differential (ID)
⋅ Inverter enabling
⋅ Inverter offset with respect to the suction setPoint (OFSI)
⋅ Minimum inverter value (MinI)
⋅ SpeedUp time
⋅ Side band suction SetPoint (SP)
Inverter
100.00 %
MinI
SP + OFSI SP + OFSI + DI
Pressure
The regulator output will assume different values depending on the value measured by the suction
probe.
If the value measured by the probe is less than or equal to the value of SP + OFSI, the regulator
output assumes the value 0.
If the value measured by the probe is between the value of SP + OFSI and the value of SP + OFSI +
ID, the regulator output will assume a value proportional to the suction probe value.
In the case where the suction probe assumes a value greater than or equal to the value of SP + OFSI
+ ID, the inverter output will assume the maximum value.
In the case where the parameter MinI has been set, then with each switching on, the inverter will
maintain that value as the starting value.
Where the speedUp time parameter is greater than zero, with each startup, the inverter will assume
the maximum value for the number of seconds set by this parameter.
Page
73
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
The range of values the inverter output may assume is comprised of between 0 and 100 percentage
points, with two decimal places.
By enabling the inverter, for a given number of compressors, one step is lost, which will be replaced
by regulation with inverter on the first compressor.
Below is given an example of how to change regulation with the presence of an inverter.
This type of control introduces inverter control to normal neutral zone control, and in order to do
this it is essential to set several parameters relating to the inverter device it is intended to use, in
addition to enabling its use. The parameters in question are the following:
⋅ Inverter enabling
⋅ Minimum inverter value (MinI)
⋅ Inverter time (IT)
⋅ SpeedUp time
⋅ neutral zone suction setPoint
Regulation varies according to the zone (neutral, on or off) in which the regulator is located.
74
Page
Steps
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
In the neutral zone, the inverter undergoes no changes and the compressors are neither switched on
or off.
In the on zone:
⋅ the inverter is activated as soon as requested.
⋅ the inverter value varies according to the time TI set by the parameter. This represents the
time required for the inverter ramp to change from the minimum value to the maximum
when the inverter reaches the maximum value another compressor is requested
⋅ on completion, the inverter value is reset to the minimum value (MinI if other than zero)
⋅ In the case where the on zone is still ongoing, the cycle is restarted once more.
If the on request remains ongoing, one or all of the compressors are switched on and the inverter
value finally reaches its maximum.
In the off zone:
⋅ as soon as requested, the inverter output is adjusted, according to TI, to the minimum value.
⋅ when the inverter reaches the minimum value, switching off another compressor is required
⋅ having completed the request, in the case where the off zone remains, the inverter value is
restored to the maximum value and the cycle restarted once more.
If the switch off request remains ongoing, one or all of the compressors are switched off and the
inverter value finally reaches zero.
In the case where the parameter MinI has been set, then with each switching on, the inverter will
maintain that value as the starting value.
Where the speedUp time parameter is greater than zero, the inverter assumes the maximum value
for the time in seconds described by said parameter, each time the regulation switches from the
neutral zone to the switch on zone.
6.4 Compressor management
The program is capable of managing up to a maximum of 12 compressors (8 if a C-PRO MEGA is
used) of equal, or different nominal power, divided over three circuits; in the case of equal nominal
power, it is also possible to manage up to 3 increment devices per compressor. The safety device
75
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
digital inputs and digital outputs for switching on/off and any increment devices, may be associated
with each compressor.
The compressors are managed by means of a setPoint and differential that can be set by means of a
parameter, and by reading a pressure value from the suction probe. Switching on/off is guaranteed
by a thermoregulation device and by certain times settings, protecting the various startup
operations.
6.4.1 Compressors per circuit
Depending on machine type, there are precise configurations relating to the compressors to be used
for each circuit.
Single-circuit
All 12 (8 if using C-PRO MEGA) compressors can be used without limitations. Indeed the circuit is
unique.
Dual-circuit and triple-circuit
The sum of the compressors used in the two/three circuits, including the inverters, must not exceed
12 (8 if using C-PRO MEGA); which is the maximum number of compressors managed by the
program.
The digital outputs and inputs assigned to the compressors and the corresponding operation alarms
are correctly assigned on the basis of the above guidelines.
Please note. By enabling the inverter for compressor regulation, the FIRST compressor (for each
circuit) will be the one controlled by the inverter, while any other additional compressors will be
hermetic in nature (without increment functionality) and will be controlled by digital outputs using
relays.
6.4.2 Compressor status
Each compressor has an associated compressor state, which identifies its relative status during
system operation.
A compressor can assume 7 different states:
Disabled: the compressor has not been configured for the system. In this state, the user interface
displays the symbol “ - ”.
1. Off: the compressor is off. In this state, the user interface displays the message “OFF”.
2. Awaiting switch off: the compressor is about to be switched off, and is currently waiting
protective device waiting times. In this state, the user interface flashes the message
“WOFF”.
3. On: the compressor is on. In this state, the user interface displays the message “ON”.
4. Awaiting switch on: the compressor is about to be switched on, and is currently waiting
protective device waiting times. In this state, the user interface flashes the message “WON”.
Page
76
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
5. Alarm: the compressor is off and in the alarm state. In this state, the user interface displays
the message “ALL”.
6. Manual: the compressor is in manual operational mode. In this state, the user interface
displays the message “MAN”.
In any case, a manually functioning compressor is sensitive to any alarms, in this case, the status
will be that of Alarm.
6.4.3 Compressor rotation
Compressor rotation is a procedure that allows the number of operating hours and start-ups for each
compressor to be balanced as much as possible.
Rotation only involves compressors and not the individual increments. It does not involve any
compressors in the alarm state or operating manually, and is capable of dynamically switching on
other compressors, should one or more of them switch to the alarm state.
In all the rotation types managed, any compressors restored from the alarm state or operating
manually, will be inserted at the top of the list of compressors to be switched on. They will have
maximum priority with respect to the other compressors, altering the switch on and switch off
sequence. Rotation type is set by means of the parameter Compressor Rotation (PC01).
The program can manage 4 types of rotation: FIFO, LIFO, FIFO + time, LIFO + time.
1) FIFO
This follows “First In First Out” logic, i.e. the first compressor switched on will be the first
switched off. Initially, this logic might leads to a large difference in operational hours between the
various compressors, but after an initial phase, this should more or less balance out.
FIFO rotation has one peculiarity. If, for example, the first compressor is switched on and then off,
the next compressor to be switched on will be the second. The last compressor switched off will be
remembered so as to then switch on the next in sequence, thus avoiding always using the same and
so better exploiting all the configured resources.
Example with 4 compressors:
Switch on : C1 . Switch off : C1 .
Switch on : C2 . C3 . Switch off : C2 . C3 .
This type of rotation seeks to balance the number of switch on and off operations for the
compressors configured.
2) LIFO
This follows “Last In First Out” logic, i.e. the last compressor switched on will be the first to be
switched off.
Example.
Switch on : C1 . C2 . C3 . C4 … . C12
Page
77
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Switch off : C12 . … C4 . C3 . C2 . C1
3) FIFO + time of operation
This type of rotation functions by considering the number of operating hours for each compressor.
Startup will switch on the compressor with the least operating hours, while shut down will switch
off the compressor with the most operating hours.
In the case where a selection must be made between compressors with the same number of hours,
then a FIFO rotation is implemented, so as to thus guarantee rotation of the configured compressors.
The same rules described previously are also valid for FIFO rotation.
Time based rotation seeks to balance the number of operating hours of the compressors present in
the system.
4) LIFO + time of operation
This type of rotation functions by considering the number of operating hours for each compressor.
Startup will switch on the compressor with the least operating hours, while shut down will switch
off the compressor with the most operating hours.
In the case where a selection must be made between compressors with the same number of hours,
then a LIFO rotation is implemented, so as to thus guarantee rotation of the configured
compressors.
Switch on : C1(1 hour) . C2(3 hours) . C3(3 hours) . C4(5 hours)
Switch off : C4(5 hours) . C3(3 hours) . C2(3 hours) . C1(1 hour)
Time based rotation seeks to balance the number of operating hours of the compressors present in
the system.
Please note. If the type of rotation is changed with the machine running, it is necessary to switch
the machine off and then on in order to avoid malfunctions.
6.4.4 Increment management
Incrementing a compressor means distributing the overall load over several increments, thus
improving operation and reducing the number of startup operations, in order to prolong the lifespan
of the mechanical device.
The program is capable of managing up to 12 incremented compressors (with appropriate
limitations), or up to 12 non-incremented compressors.
Page
78
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Increment number
By means of the appropriate parameter (PG04), it is possible to select one, two or three equal
powered increments for each of the configured compressors.
Each compressor will have the same number of available increments.
Possible configurations for the number of increments per compressor depend on what hardware is
being used, and the presence, or otherwise, of an expansion unit.
Example 1 - C-PRO GIGA (13 available relays) :
⋅ From 1 to 3 compressors, maximum of 3 increments
⋅ From 1 to 4 compressors, maximum of 2 increments
⋅ From 1 to 6 compressors, maximum of 1 increment
⋅ From 1 to 12 compressors, no increments
Example 2 - C-PRO GIGA + ExpansionPro 1 (26 available relays) :
⋅ From 1 to 6 compressors, maximum of 3 increments
⋅ From 1 to 8 compressors, maximum of 2 increments
⋅ From 1 to 12 compressors, maximum of 1 increment (or none)
Please note. If one of the compressor inverters is selected, it will not be possible to use incremented
compressors, i.e. the compressor increment parameter is forced to a value of zero.
Increment logic
If incremented compressors are being used, then it is possible, by means of this parameter (PC03),
to select the operational logic of the outputs dedicated to incrementing:
⋅If set to NC the outputs will be normally energised (closed) and will be opened in order to
request greater power: Copeland type logic.
⋅If set to NO the outputs will be normally de-energised (open) and will be closed in order to
request greater power: Feeders type logic.
Switching on/off mode
In the case where incremented compressors are being used, this parameter (PC02) allows the
increment switch on/off mode to be set.
If set to “0”:
Switch on : CppCppCpp. The program favours the complete switching on of individual
compressors prior to moving to the following compressor.
Switch off : ppCppCppC. The program favours the complete switching off of individual
compressors prior to moving to the following compressor.
If set to “1”:
Switch on : CCCpppppp. The program favours first of all switching on all compressors, and
only then acting on the increments.
Switch off : ppppppCCC. The program favours first of all switching off all steps and only
then finally switching off the compressors.
If set to “2”:
Switch on : CppCppCpp. The program favours the complete switching on of individual
compressors prior to moving to the following compressor.
Switch off : ppppppCCC. The program favours first of all switching off all increments and
only then finally switching off the compressors.
If set to “3”:
Switch on : CCCpppppp. The program favours first of all switching on all compressors, and
only then acting on the increments.
Page
79
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Switch off : ppCppCppC. The program favours the complete switching off of individual
compressors prior to moving to the following compressor.
With CCCpppppp type switching on and ppppppCCC type switching off, the individual step switch
on/off logic follows this example (example for 3 compressors):
Compressor switch on : C1 . C2 . C3
Increment switch on : p1C1 . p1C2 .p1C3 / p2C1 . p2C2 . p2C3 / p3C1 . p3C2 . p3C3
Increment switch off : p3C3 . p3C2 .p3C3 / p2C3 . p2C2 . p2C1 / p1C3 . p1C2 . p1C1
6.4.5 Protective device timings
All the timings pertaining to compressor management are listed below
Neutral zone timings
These parameters are used to time the switching on and off requests for the various steps provided
by the compressors.
Minimum required switch on time - TOnMin
Maximum required switch on time - TOnMax
Minimum required switch off time - TOffMin
Maximum required switch off time - TOffMax
For these parameters, please refer to the description given in section 2.3.2.
Protective device timings
These times are required to protect the mechanical devices from the various startup operations to
which they are subjected.
TMinOn – Minimum compressor switch on time (PC04). Once activated, the compressor will
remain on for this amount of time, before being able to be switched off.
TMinOff – Minimum compressor switch off time (PC05). Minimum elapsed time since the last
switch off before the compressor can be switched on once more.
TOnOn – Minimum same compressor switch on time (PC06). This establishes the minimum time
that must elapse before the same compressor can be switched on.
TOnOther – Minimum different compressor switch on time (PC07). This establishes the minimum
time that must elapse before the subsequent compressor can be switched on. If greater than zero,
this allows avoiding any simultaneous startup operations.
TOffOther – Minimum different compressor switch off time (PC08). This establishes the minimum
time that must elapse before the subsequent compressor can be switched off. If greater than zero,
this allows avoiding any simultaneous startup operations.
TOnParz – Minimum step switch on time (PC09). This establishes the minimum switch on time
between compressor steps.
TOffParz – Minimum step switch off time (PC10). This establishes the minimum switch off time
between compressor steps.
Page
80
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
SpeedUp time. If regulation by means of inverter is set, then this parameter, if other than zero, keeps
the inverter output at maximum value (100.0%) with each new step switch on request.
6.4.6 Startup delay from reset
By means of the parameter PC69 – TRestart in the Installer ->Compressors menu, it is possible to
delay compressor startup each time the controller is reset; for example, following a black-out
caused by a power cut.
6.4.7 Safety device inputs
The program envisages the management of 3 safety devices, with relevant alarms, managed by
means of 4 possible combinations. Based on the parameter safety device number (PG05) the
number of safety devices can be selected, and by means of the parameter safety device type (PH16)
the appropriate combination for the application can be selected. The three safety devices managed
are as follows:
The four combinations implemented are described in the following table.
ParameterTypeDelayReset
0 None - -
1 Thermal
Thermal
2
High/low pressure pressure-switch Immediate
Thermal
3
Oil differential
4
Thermal + oil differential + pressureswitch
Configurable Configurabl
e
Configurable Configurabl
e
Configurabl
e
Configurable Configurabl
e
Configurable Configurabl
e
- -
The “compressor thermal” safety device manages all 12 compressors and is enabled by setting two
parameters:
Safety device number: 1 / 2 / 3
Safety device type: 1 / 2 / 3 / 4
The “compressor oil differential” safety device manages up to a maximum of 6 compressors and is
enabled by setting two parameters as follows:
Safety device number: 2 / 3
Safety device type: 3 / 4
Page
81
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
The “compressor high/low pressure pressure-switch” safety device manages up to a maximum of 6
compressors and is enabled by setting two parameters as follows:
Safety device number: 2 / 3
Safety device type: 2 / 4
To enable the alarms associated with these safety devices, besides setting the above-described
parameters, it is also essential to set the positions where the digital inputs relating to the various
alarm types will be connected from within the System builder ->Hardware menu. Where there is no
desire to set an alarm, simply set the parameter to the value 0.
The number of safety devices that can be used is limited by the number of available digital inputs
(depending on the hardware used) and the number of compressors configured.
Please note. If the number of safety devices is greater than or equal to 1, then the “compressor
thermal” safety device is always selected.
6.4.8 Inverter configuration
For each inverter used must be selected the digital output position for the command/consent to the
inverter start; for the configuration are used the same parameters of the compressors digital outputs,
parameters HC01..HC10, HC50, HC60. The inverter is virtually the first compressor of each circuit,
then according to the quantity of compressors and the quantity of circuits must be set the correct
parameter according to this logic.
- 1 circuit: The inverter (if enabled) is virtually the compressor 1; is necessary to
configure the parameter of the first compressor, then must be always configured the
parameter HC01.
- 2 circuits: The inverter of circuit 1 (if enabled) is virtually the compressor 1 (then,
must be configured the parameter HC01), the inverter of circuit 2 (if enabled) is
virtually the first compressor after the circuit 1 compressors.
- 3 circuits: The inverter of circuit 1 (if enabled) is virtually the compressor 1 (then,
must be configured the parameter HC01), the inverter of circuit 2 (if enabled) is
virtually the first compressor after the circuit 1 compressors, the inverter of circuit 3
(if enabled) is virtually the first compressor after the circuit 1 and 2 compressors.
Note. The parameter PH20 modifies the logic for the inverter consent.
HC01 = 1 -> digital output for the inverter consent
HC02 = 2 -> digital output for the hermetic compressor command
HC31 = 1 -> analog output per the inverter command.
2) N°2 circuits (PG01=2), n° 2 compressors for each circuit (PG11=2, PG15=2), both inverter
enabled (PG12=1, PG16=1). A correct configuration is:
HC01 = 1 -> digital output for the circuit 1 inverter consent
HC02 = 2 -> digital output for the circuit 1 hermetic compressor command
HC03 = 3 -> digital output for the circuit 2 inverter consent
HC04 = 4 -> digital output for the circuit 2 hermetic compressor command
HC31 = 1 -> analog output for the circuit 1 inverter command
HC32 = 2 -> analog output for the circuit 2 inverter command
Page
82
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
PG15=3), only circuit 2 inverter enabled (PG12=0, PG16=1). A correct configuration is:
HC01 = 1 -> digital output for the circuit 1 first hermetic compressor
HC02 = 2 -> digital output per the circuit 2 inverter consent
HC03 = 3 -> digital output for the circuit 2 first hermetic compressor command
HC04 = 4 -> digital output for the circuit 2 second hermetic compressor command
HC31 = 1 -> analog output for the circuit 1 inverter command
HC32 = 2 -> analog output for the circuit 2 inverter command
PG15=3), both inverter enabled (PG12=1, PG16=1). A correct configuration is:
HC01 = 1 -> digital output for the circuit 1 inverter consent
HC02 = 2 -> digital output for thr circuit 2 inverter condent
HC03 = 3 -> digital output for the circuit 2 first hermetic compressor command
HC04 = 4 -> digital output for the circuit 2 second hermetic compressor command
HC31 = 1 -> analog output for the circuit 1 inverter command
HC32 = 2 -> analog output for the circuit 2 inverter command
6.4.9 Compressors of different nominal power
Management of compressors with different nominal power might be useful in order to have more
precise regulation in order to establish the final value at the configured setpoint.
In order to use this type of management, it is essential to enable the relevant parameter, enable compressors of different nominal power (PG03) and set the parameters representing the nominal
power for each of the compressors to be used in the system.
The software calculates the maximum power that can be expressed by the individual nominal power
ratings of each of the compressors, and, on the basis of the requests from the regulators, calculates
the best combination of compressors in order to provide the requested power. For finer regulation,
the resolution within each power step is tripled; this way, with compressors of different nominal
power, there are more combinations that can approach the effective power requested by the
regulators. With each variation in request, the permutation of compressors is recalculated so as to
produce a power output equal to or greater than the request.
In the calculation of the permutation, any compressors that are manually disabled, in alarm states or
in waiting times, are not considered.
Please note. By enabling this function it is not possible to use incremented compressors or
compressors with inverters.
Side band regulation
On the basis of the control parameters, the application will calculate the power necessary to restore
the measured pressure/temperature close to the desired setpoint.
The requested power will be calculated on the basis of a proportional or proportional + integral
regulator, while the power provided will be given by the combination of compressor power outputs
closest to exceeding the request.
Neutral zone regulation
On the basis of the zone in which the regulator is located, a new sequence of compressors to be
activated is calculated, in particular:
Page
83
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
⋅ In the neutral zone: the combination remains unchanged.
⋅ In the on zone: the combination of compressors is recalculated in order to guarantee power
greater than that provided by the previous combination.
⋅In the off zone: the combination of compressors is recalculated in order to guarantee power
less than that provided by the previous combination.
The recalculation of combinations is implemented on the basis of the neutral zone time settings,
please refer to section 6.4.5.
Example
Considering 3 compressors of different nominal power ratings and a side band proportional
regulation device, with the following parameters:
Setpoint = 0.5 bar
Proportional band = 2.0 bar
Compressor 1 power = 3 kW
Compressor 2 power = 5 kW
Compressor 3 power = 10 kW
Measured Pressure
(bar)
0.5 - 0
0.6 0.9 X
1.0 4.5 X
1.3 7.2 X
1.6 9.9 X
1.7 10.8 X
2.0 13.5 X
2.3 16.2 X
2.5 18 (max)
Required Power
(kW)
Compressor 1
(3 kW)
X
Compressor 2
(5 kW)
3
X
Compressor 3
(10 kW)
5
8
X
X
X
X
X
X
Power Delivered
18 (max)
(kW)
10
13
15
18
Below the setpoint, no power is delivered, above the setpoint plus the band, the power delivered is
the maximum available.
6.4.10 Suction line loss of load compensation
In certain systems, it might become necessary to reduce the suction setpoint with increased
refrigerant capacity, in order to compensate for the increased pressure loss along the suction line. In
practice, the services, which should operate at constant evaporation pressure, are forced to operate
higher pressures when the cold requirement is greater, and vice versa. This means that, in order to
guarantee cold production at the desired temperature, even with loads approaching the nominal
values, it is necessary to work with a significantly lower setpoint even at partial loads, when this
should not be necessary. Compensation works by introducing a configurable offset that lowers the
setpoint, gradually, with each demand for cold steps: it is clear that this function has the aim of
increasing system efficiency, allowing the selection of a higher setpoint at low loads.
The parameter PH35 enables this function, lowering the setpoint by a compensation factor (PH36Suction load compensation offset) with each step inserted, and raising the same value with each step
released.
This function can only be activated with neutral zone regulation.
84
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
pressure
enabling
PC75
PC75
t
t
6.4.11 Refrigeration power incrementing at high pressures
In order to avoid tripping the condensation high pressure pressure-switch, with consequent blocking
of cold production, it is possible to reduce the refrigeration power and consequently the power to be
exchanged by the condenser, thus reducing condensation pressure. This reduction is only possible
with incrementable circuits (with at least two compressors or with one compressor with
incrementing devices).
The parameters pertaining to this function are as follows:
⋅ PC70 = Enable high pressure incrementing
⋅ PC71 = Condensation pressure-switch control setpoint limit (Circuit 1)
⋅ PC72 = Condensation pressure-switch control setpoint limit (Circuit 2)
⋅ PC73 = Condensation pressure-switch control setpoint limit (Circuit 3)
⋅ PC74 = Pressure-switch control differential
⋅ PC75 = Minimum pressure-switch increment maintenance time
⋅ PC76 = Percentage increment value
Increment
Supply
Set
Set-Diff
Page
85
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
6.5 Condensation regulation
Condensation management envisages control of the supply pressure using the fans: depending on
the type of control (side band or neutral zone) and the use, or otherwise, of inverters for fine
adjustment, four types of regulation are envisaged.
6.5.1 Side band regulation
Side band control exploits the characteristics of PI (proportional and integral) or P (proportional)
regulators to establish when to insert or disengage the fans used, so as to regularise, within the
differential band, the switching on and off of the various devices. The purpose of PI regulation is to
have no error in full operation.
The parameters defining this regulation are as follows:
⋅ Proportional band (PB)
⋅ Side band supply SetPoint (SP)
⋅ Integral time (IT)
The above figure shows the behaviour of band regulation (SP, SP + PB). Depending on the supply
pressure value, regulation adds or removes the number of steps required by the fans. Under such
regulation, the band is displaced above the setPoint.
It is possible to select whether control will refer to PI or just P regulation, by either setting the
parameter for integral action, namely the integration time (Ti), or otherwise. In the specific case
where this parameter is set to the value zero, regulation is proportional only, otherwise, it is also
integral. Ti corresponds to the time necessary for integral action, assuming constant error, to
equalise the proportional action: the speed of this action is proportional to the integration time
value. The default parameter is greater than zero, hence, by default, regulation exploits the
proportional-integral characteristic.
Like the case with compressors, by means of the parameter PF78 Side band increment overlap,
with side band regulation of fans, it is also possible to improve the behaviour of the regulation band.
6.5.2 Neutral zone regulation
This type of regulation envisages the definition of a neutral zone, within which no activation or
deactivation decision will be taken, i.e. startup operations will not be requested for any of the
devices.
The parameters defining this regulation are as follows:
⋅Neutral zone (NZ)
Fans
Max Fans
Supply pressure
SP SP + BP
Page
86
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
⋅Side band suction SetPoint (SP)
Outwith said neutral zone, device on or off requests for the configured fans will follow this logic:
⋅ Switch on: when the supply pressure exceeds the setPoint + Neutral Zone threshold
⋅ Switch off: when the pressure drops below the setPoint
In this type of regulation, the neutral zone is displaced to the right of the setPoint.
NZ_TOn NZ_TOff
Neutral zone
SP SP + ZN
Switching on Switching off
Supply
As may be deduced from the figure, regulation envisages setting two times, within which,
depending on the zone, the on and off requests for the various steps must be timed. The relevant
parameters are as follows:
⋅ Switch-on time (NZ_TOn)
⋅ Switch-off time (NZ_TOff)
In the case where the system is in the switch off zone, each switch off request will have to wait for
NZ_TOff seconds prior to being fulfilled. While, in the case of the switch on zone, each switch on
request will have to wait NZ_TOn seconds prior to being fulfilled.
6.5.3 Side band regulation with inverter
This type of control introduces inverter control to normal side band control, and in order to do this it
is essential to set several parameters relating to the inverter device it is intended to use, in addition
to enabling its use. The parameters in question are the following:
⋅ Inverter differential (ID)
⋅ Inverter enabling
⋅ Inverter offset with respect to the supply setPoint (OFSI)
⋅ Minimum inverter value (MinI)
⋅ SpeedUp time
⋅ Side band supply SetPoint (Sp)
Inverter
100.00 %
MinI
SP + OFSI SP + OFSI + DI
Pressure
The regulator output will assume different values depending on the value measured by the supply
probe.
If the value measured by the probe is less than or equal to the value of SP + OFSI, the regulator
output assumes the value 0.
87
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
If the value measured by the probe is between the value of SP + OFSI and the value of SP + OFSI +
ID, the regulator output will assume a value proportional to the supply probe value.
In the case where the supply probe assumes a value greater than or equal to the value of SP + OFSI
+ ID, the inverter output will assume the maximum value.
In the case where the parameter MinI has been set, then with each switching on, the inverter will
maintain that value as the starting value.
Where the speedUp time parameter is greater than zero, with each startup, the inverter will assume
the maximum value for the number of seconds described by this parameter.
The range of values the inverter output may assume is comprised of between 0 and 100 percentage
points, with two decimal places.
By enabling the inverter, for a given number of fans, one step is lost, which will be replaced by
regulation with inverter on the first fan.
Below is given an example of how to change regulation with the presence of an inverter.
Example: 4 fans without inverter
Example: 4 fans with 1 inverter
Steps
Max Steps
Steps
Max Steps
Inverter
SP SP + BP
Pressure
100.00 %
SP SP + BP
Pressure
MinI
SP + OFSI SP + OFSI + DI
6.5.4 Neutral zone regulation with inverter
This type of control introduces inverter control to normal neutral zone control, and in order to do
this it is essential to set several parameters relating to the inverter device it is intended to use, in
addition to enabling its use. The parameters in question are the following:
⋅ Inverter enabling
⋅ Minimum inverter value (MinI)
⋅ Inverter time (IT)
⋅ SpeedUp time
⋅ Neutral zone supply SetPoint
Regulation varies according to the zone (neutral, on or off) in which the regulator is located.
In the neutral zone, the inverter undergoes no changes and the fans are neither switched on or off.
In the on zone:
⋅ the inverter is activated as soon as requested.
⋅ the inverter value varies according to the time TI set by the parameter. This represents the
time required for the inverter ramp to change from the minimum value to the maximum.
Pressure
Page
88
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
⋅when the inverter reaches the maximum value one of the other fans is requested.
In the case where the on zone remains ongoing one or all the fans are switched on and the inverter
value remains at maximum.
In the off zone:
⋅ as soon as requested, the inverter output is adjusted, according to TI, to the minimum value.
⋅ when the inverter reaches the minimum value, switching off another fan is requested
If the switch off request remains ongoing, one or all of the fans are switched off and the inverter
value remains at zero.
In the case where the parameter MinI has been set, then with each switching on, the inverter will
maintain that value as the starting value.
Where the speedUp time parameter is greater than zero, the inverter assumes the maximum value
for the time in seconds described by said parameter, each time the regulation switches from the
neutral zone to the switch on zone.
Below is an example of a graph (for the switch on zone) of how regulation varies depending on
whether the fan is configured with an inverter or otherwise.
Unique condensation allows the fan process to be executed using a single circuit. By setting the
parameter enable unique condensation (PG30), the number of fan circuits is forced to one, while
the number of circuits selected for compressors remains unchanged.
In any case, in the case where this function is selected, the maximum number of fans that can be
used remains the maximum number of fans per circuit. Unique condensation will disable all the
features (alarms, fans, inverters, …) pertaining to the second and third fan management circuits.
89
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
6.6 Fan management
The program is capable of managing up to a maximum of 12 fans (8 if using C-PRO MEGA)
divided according to circuit. A digital input for safety devices and a digital output for switching
on/off may be associated with each fan.
The number of fans that can be used is further limited by the number of compressors (and stepped
compressors), i.e. the number of free digital outputs remaining after the compressors have been
configured.
By setting the relevant parameter, it is possible to use a unique condensation device, i.e. achieved
by means of a single circuit.
The fans are managed by means of a set Point and differential that can be set by means of a
parameter, and by reading a pressure value from the supply probe. Switching on/off is guaranteed
by a thermoregulation block and by certain time settings, protecting the various startup operations.
6.6.1 Fans per circuit
Depending on machine type, there are precise configurations relating to the fans to be used for each
circuit.
Single-circuit
All 12 (8 if using C-PRO MEGA) fans can be used without limitations. Indeed the circuit is unique.
Dual-circuit and triple-circuit
The sum of the fans used in the two/three circuits, including the inverters, must not exceed 12 (8 if
using C-PRO MEGA); which is the maximum number of fans managed by the program.
The digital outputs and inputs assigned to the fans and the corresponding operation alarms are
correctly assigned on the basis of the above guidelines.
In the case where it is decided to use condensation on a single circuit (Unique condensation
parameter) the only available and configurable fans will be those of the first circuit.
Please note. By enabling the inverter for fan regulation, the FIRST fan (for each circuit) will be the
one controlled by the inverter, while any other additional fans will be hermetic in nature and will
be controlled by digital outputs using relays.
6.6.2 Fan status
Each fan has an associated fan state, which identifies its relative status during system operation.
A fan can assume 7 different states:
1. Disabled: the fan has not been configured for the system. In this state, the user interface
displays the symbol “ - ”.
2. Off: the fan is off. In this state, the user interface displays the message “OFF”.
3. Awaiting switch off: the fan is about to be switched off, and is currently waiting protective
device waiting times. In this state, the user interface flashes the message “WOFF”.
Page
90
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
4. On: the fan is on. In this state, the user interface displays the message “ON”.
5. Awaiting switch on: the fan is about to be switched on, and is currently waiting protective
device waiting times. In this state, the user interface flashes the message “WON”.
6. Alarm: the fan is off and in the alarm state. In this state, the user interface displays the
message “ALL”.
7. Manual: the fan is in manual operational mode. In this state, the user interface displays the
message “MAN”.
In any case, a manually functioning fan is sensitive to any alarms, in this case, the status will be that
of Alarm.
6.6.3 Fan rotation
Fan rotation is a procedure that allows the number of operating hours and start-ups for each device
to be balanced as much as possible.
Rotation does not involve any fans that are in alarm or manual operation states, and is capable of
dynamically switching on others should one or more be switched to the alarm state.
In all the rotation types managed, any compressors restored from the alarm state or operating
manually, will be inserted at the top of the list of compressors to be switched on. They will have
maximum priority with respect to the other compressors, altering the switch on and switch off
sequence. Rotation type is set by means of the parameter Fan Rotation (PF01).
The program can manage 4 types of rotation: FIFO, LIFO, FIFO + time, LIFO + time.
1) FIFO
This follows “First In First Out” logic, i.e. the first fan switched on will be the first switched off.
Initially, this logic might leads to a large difference in operational hours between the various fans,
but after an initial phase, this should more or less balance out.
Example.
Switch on : F1 . F2 . F3 . F4 … . F12
Switch off : F1 . F2 . F3 . F4 … . F12
FIFO rotation has one peculiarity. If, for example, the first fan is switched on and then off, the next
fan to be switched on will be the second. The last fan switched off will be remembered so as to then
switch on the next in sequence, thus avoiding always using the same and so better exploiting all the
configured resources.
Example with 4 fans:
Switch on : F1 . Switch off : F1 .
Switch on : F2 . F3 . Switch off : F2 . F3 .
Switch on : F4 . F1 . F2 . F3 . Switch off : F4 . F1 . F2 . F3 .
This type of rotation seeks to balance the number of switch on and off operations for the fans
configured.
Page
91
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
2) LIFO
This follows “Last In First Out” logic, i.e. the last fan switched on will be the first to be switched
off.
Example.
Switch on : F1 . F2 . F3 . F4 … . F12
Switch off : F12 . … F4 . F3 . F2 . F1
3) FIFO + time of operation
This type of rotation functions by considering the number of operating hours for each fan. Startup
will switch on the fan with the least operating hours, while shut down will switch off the fan with
the most operating hours.
In the case where a selection must be made between fans with the same number of hours, then a
FIFO rotation is implemented, so as to thus guarantee rotation of the configured fans. The same
rules described previously are also valid for FIFO rotation.
Time based rotation seeks to balance the number of operating hours of the fans present in the
system.
4) LIFO + time of operation
This rotation favours comparing the operating times of the various fans. During startup, the fan with
the least operating hours will be favoured, while shut down will favour the fan with the most
operating hours.
In the case where a selection must be made between fans with the same number of hours, then a
LIFO rotation is implemented, so as to thus guarantee rotation of the configured fans. The same
rules described previously are also valid for LIFO rotation.
Time based rotation seeks to balance the number of operating hours of the fans present in the
system.
6.6.4 Protective device timings
All the timings pertaining to compressor management are listed below
Page
92
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Neutral zone timings
These parameters are used to time the switching on and off requests for the various condensation
devices.
Minimum switch on/off request time - TOn/Off
For these parameters, please refer to the description given in section 2.5.2.
Protective device timings
These times are required to protect the fans from the various startup operations to which they are
subjected.
TOnOther – Minimum different fan switch on time (PF07). This establishes the minimum time that
must elapse before the subsequent fan can be switched on. If greater than zero, this allows avoiding
any simultaneous startup operations.
TOffOther – Minimum different fan switch off time (PF08). This establishes the minimum time that
must elapse before the subsequent fan can be switched off. If greater than zero, this allows avoiding
any simultaneous startup operations.
SpeedUp time. If regulation by means of inverter is set, then this parameter, if other than zero, keeps
the inverter output at maximum value (100.0%) each time another fan switch on is requested.
6.6.5 Safety device inputs
The program envisages the management of a single “fan thermal” safety device for each of the fans
configured within the application. Enabling or disabling this characteristic is managed by the
parameter enable fan safety device (PG08).
In order to enable the “fan thermal” alarms, besides setting the relevant parameter, it is also
essential to set the positions where the digital inputs pertaining to the various selected fans will be
connected, from within the System builder -> Hardware menu. Where there is no desire to set an
alarm, simply set the parameter to the value zero.
6.6.6 Inverter configuration
For each inverter used must be selected a position of the digital output for the command/consent to
the inverter start; for the configuration are used the same parameters of the fans digital ouputs,
parameters HF01..HF12. The inverter is virtually the first fan of each circuit, then, according to the
quantity of fans and the quantity of circuit must be set the correct parameter, according to this logic.
- 1 circuit: The inverter (if enabled) is virtually the fan 1; is necessary to configure the
first fan parameter, then must be configured always the parameter HF01.
- 2 circuits: The circuit 1 inverter (if enabled) is virtually the fan 1 (then, must be set
the parameter HF01), the circuit 2 inverter (if enabled) is virtually the first fan after
the circuit 1 fans
- 3 circuits: The circuit 1 inverter (if enabled) is virtually the fan 1 (then, must be set
the parameter HF01), the circuit 2 inverter (if enabled) is virtually the first fan after
the circuit 1 fans, the inverter of circuit 3 (if enabled) is virtually the first fan after
the circuit 1 and circuit 2 fans.
The selection of working modality and function setup of the parameters for the fans inverters is the
same for the compressors one, but are used the parameters PH21, HFxx (look at paragraph 6.4.8)
Page
93
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
6.7 Miscellaneous controls
6.7.1 Inverter configuration (compressors/fans)
If selected, the inverter is always the first compressor in each circuit:
⋅ 1 Circuit: the inverter (if enabled) is compressor 1
⋅ 2 Circuits: the circuit 1 inverter (if enabled) is compressor 1, and the circuit 2 inverter (if
enabled) is the first compressor configured on the second circuit
⋅3 Circuits: the circuit 1 inverter (if enabled) is compressor 1, the circuit 2 inverter (if
enabled) is the first compressor configured on the second circuit, and the circuit 3 inverter
(if enabled) is the first compressor configured on the third circuit
The inverter is included in the number of compressors or fans configured by parameter for
each circuit.
Example 1
1 Circuit
Compressor inverters YES
5 Compressors
0 Steps
Fan inverters NO
3 Fans
Example 1 configuration parameters:
CircuitNumber 1
Enable Circuit 1 Compressor Inverter YES
Number of Compressors for Circuit 1 6
Number of Compressor Steps 0
Enable Circuit 1 Fan Inverter NO
Number of Fans for Circuit 1 3
Depending on the single/dual/triple-circuit version, there are limitations on the use of inverters:
Single-circuit:
⋅ One compressor inverter (Analogue output 1)
⋅ One fan inverter (Analogue output 3)
Dual-circuit:
⋅ Two compressor inverters (Analogue outputs 1 - 2)
⋅ Two fan inverters (Analogue outputs 3 -4)
Triple-circuit:
⋅ Three compressor inverters (Analogue outputs 1 – 2 - 3) or
⋅ Three fan inverters (Analogue outputs 1 – 2 - 3)
⋅ Three compressor inverters (Analogue outputs 1 - 2 - 3) and one fan inverter (Analogue
output 4) in the case of unique condensation
In the case of the triple-circuit version, the inverters are exclusive: it is only possible to select those
pertaining to compressors, or those pertaining to fans. Management of a combination of both types
Example 2
1 Circuit
Compressor inverters NO
5 Compressors
2 Steps
Fan inverters NO
3 Fans
Example 2 configuration parameters:
CircuitNumber 1
Enable Circuit 1 Compressor Inverter NO
Number of Compressors for Circuit 1 5
Number of Compressor Steps 2
Enable Circuit 1 Fan Inverter NO
Number of Fans for Circuit 1 3
94
Page
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
is not possible. To correctly configure this feature, simply enable at least one compressor/fan
inverter, depending on the type enabled, the other type will be automatically excluded from the
analogue outputs.
The only case where it is possible to use both compressor inverters and fan inverters is when the
parameter unique condensation (PG30) is set; in this case, the last analogue output (AO04) may be
used as the sole fan inverter.
Note 1. If a compressor inverter is selected, it is not possible to use incremented compressors, and
vice versa.
Note 2. If a compressor inverter is selected, it is not possible to use compressors with different
nominal power ratings, and vice versa.
6.7.2 Compressor time bands
By means of the parameter enable compressor time bands (PT00) it is possible to enable the time
band function. The program provides up to four different bands with related offsets (different for
each circuit) to be summed up to the main suction setpoint.
Depending on the time band, on the basis of the current time, the program will automatically sum
the circuit offsets to the suction setpoint, outwith the selected bands, the setpoint will remain at the
value set by the parameter.
Time band configuration is based on 4 parameters (different for each circuit) for the setpoint offsets
and an additional four parameters (general) for the time band settings:
⋅ Time band 1 start - Circuit band 1 offset (1,2,3)
⋅ Time band 2 start - Circuit band 2 offset (1,2,3)
⋅ Time band 3 start - Circuit band 3 offset (1,2,3)
⋅ Time band 4 start - Circuit band 4 offset (1,2,3)
Hence, the time bands will be defined thus:
1. Time band 1 start ÷ Time band 2 start
2. Time band 2 start ÷ Time band 3 start
3. Time band 3 start ÷ Time band 4 start
4. Time band 4 start ÷ Time band 1 start
Where less than the four envisaged bands are set, in order to guarantee correct management
operation, it is essential to set the remaining band start parameters to the value of the last set band,
and obviously set the relevant offset to zero.
Example 1. Four time bands. Assuming a suction setpoint = 1.0 bar
Band start Offset Setpoint Description
02:00:00 +0.3 1.3 bar From 02:00:00 to 07:15:00
07:15:00 +0.1 1.1 bar From 07:15:00 to 15:13:00
15:30:00 -0.5 0.5 bar From 15:30:00 to 23:00:00
23:00:00 -0.2 0.8 bar From 23:00:00 to 02:00:00
Example 2. Two time bands. Assuming a suction setpoint = 1.0 bar
Page
95
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
Band start Offset Setpoint Description
02:00:00 +0.3 1.3 bar From 02:00:00 to 07:15:00
07:15:00 +0.1 1.1 bar From 07:15:00 to 02:00:00
07:15:00 0 1.0 bar 07:15:00 0 1.0 bar -
During an ERTC alarm (clock alarm), the time band function is automatically disabled and LED L2
on the display stays on, until the alarm is reset.
When the clock is within a time band, i.e. when the main suction setpoint is altered by the related
band offset, LED L2:
⋅ Flashes rapidly if there is an ERTC clock alarm.
⋅ Flashes slowly if only one of the compressor and fan setpoints is altered.
⋅ Remains on if both setpoints are altered by the time bands.
⋅ Remains off if there is no condition.
To enter time band management, press and hold display key K2 for approx. 2 seconds.
6.7.3 Fan time bands
By means of the parameter enable fan time bands (PT50) it is possible to enable the time band
function. The program provides up to four different bands with related offsets (different for each
circuit) to be summed up to the main supply setpoint.
Depending on the time band, on the basis of the current time, the program will automatically sum
the circuit offsets to the supply setpoint, outwith the selected bands, the setpoint will remain at the
value set by the parameter.
Time band configuration is based on 4 parameters (different for each circuit) for the setpoint offsets
and an additional four parameters (general) for the time band settings:
⋅ Time band 1 start - Circuit band 1 offset (1,2,3)
⋅ Time band 2 start - Circuit band 2 offset (1,2,3)
⋅ Time band 3 start - Circuit band 3 offset (1,2,3)
⋅ Time band 4 start - Circuit band 4 offset (1,2,3)
Hence, the time bands will be defined thus:
1. Time band 1 start ÷ Time band 2 start
2. Time band 2 start ÷ Time band 3 start
3. Time band 3 start ÷ Time band 4 start
4. Time band 4 start ÷ Time band 1 start
Where less than the four envisaged bands are set, in order to guarantee correct management
operation, it is essential to set the remaining band start parameters to the value of the last set band,
and obviously set the relevant offset to zero.
Management is the same as for compressor time bands, please refer to the previous section for any
further clarification.
When the clock is within a time band, i.e. when the main supply setpoint is altered by the related
band offset, LED L2:
⋅Flashes rapidly if there is an ERTC clock alarm.
Page
96
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
⋅ Flashes slowly if only one of the compressor and fan setpoints is altered.
⋅ Remains on if both setpoints are altered by the time bands.
⋅ Remains off if there is no condition.
To enter time band management, press and hold display key K2 for approx. 2 seconds.
6.7.4 Digital input setpoint alteration
For both compressors and fans, the program envisages the possibility of managing the compressor
DI secondary setPoint offset and fan DI secondary setPoint offset parameters, which, depending on
the digital input status (different for compressors and fans) sum an offset to the main setpoint in
order to allow variation. It is possible to set the digital input logic by altering the parameter Other DI logic (PH19, itself a parameter relating to the digital input on/off logic).
To set this function, it is necessary to configure the parameter DI enabling secondarysetpoint (PH25) and set the position where the digital input relating to the compressors and relating to fans
will be connected. If this value is not set, the function will remain disabled.
6.7.5 Supervisor setpoint alteration
For both compressors and fans, the program envisages the possibility of managing the compressor
SUP secondary setPoint offset and fan SUP secondary setPoint offset parameters, which, depending
on the state of a variable set by the supervision protocol (different for compressors and fans) sum
the adjusted offset to the main setpoint in order to allow variation.
To set this function it is necessary to configure the parameter supervisor secondary setpoint enabling (PH26) and the status enable by means of the exported variable. If this value is not set, the
function will remain disabled.
6.7.6 Manual operation
The program allows setting a manual compressor and fan function. In this state, devices do not
participate in rotations nor in the calculation of thermoregulation, however, they are sensitive to any
alarms.
Manual operation of devices is useful when functional tests must be conducted on the machine, in
order to test the integrity and correct operation of the mechanical components.
Compressors
Manual or other operation of the compressors is guaranteed by the parameter compressor enable:
⋅ If set to the value “A” it defines the normal behaviour of the device
⋅ If set to the value “M” it disables the compressor and switches it to manual operation.
A manually functioning compressor does not participate in regulations, and may be forced into the
number of steps it is capable of providing (even over its increments, where configured) by setting
the parameter compressor forcing (found in the Service -> Compressor forcing menu). The number
of steps a manually functioning compressor can provide is limited to the number of increments that
have been set during machine configuration.
As already mentioned, the compressor is, in any case, sensitive to alarms and the relevant
consequences.
Page
97
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
To restore the compressor to normal use, it is necessary to reset the parameter compressor enable to
the value “A” (Automatic), otherwise, the compressor in question will continue to operate in
manual mode, not fulfilling the switch on and/or off requests calculated by the selected regulation.
Fans
Manual or other operation of the fans is guaranteed by the parameter fan enable:
⋅ If set to the value “A” it defines the normal behaviour of the device
⋅ If set to the value “M” it disables the fan and switches it to manual operation.
A manually functioning fan does not participate in regulations, and may be forced into switching
on/off by setting the property fan forcing (present in the Service -> Fan forcing menu).
As already mentioned, the fan is, in any case, sensitive to alarms and the relevant consequences.
To restore the fan to normal use, it is necessary to once more restore the parameter fan enable to the
value “A” (Automatic), otherwise, the fan in question will continue to operate in manual mode, not
fulfilling the switch on and/or off requests calculated by the selected regulation.
Inverters
In the case where it is desired to manually force an inverter, the procedure is slightly different from
that for normal compressors or fans.
If selected, the inverter is virtually the first compressor for each circuit, thus before being able to
correctly execute the procedure, it is necessary to set the correct compressor to manual, depending
on how the system has been configured.
Once manual enabling has been correctly set, it is possible to force, with a value of between 0.0%
and 100.0%, the inverter for each circuit by means of the parameters:
Management and the forcing procedure for fan inverters is the same as that for compressors.
6.7.7 Floating condensation management
This allows modification of the fan operating setpoint on the basis of the external temperature. To
enable this function, it is necessary to set (from the installer -> Miscellaneous menu) the
parameters:
⋅ enable external temperature probe (PH24)
⋅ enable floating condensation (PF71)
⋅ Temperature offset (PF72): condensation temperature offset (associated with the type of
condenser module used)
⋅set floating condensation Min (PF73): minimum condensation value, guaranteeing correct
lubrication
⋅set floating condensation Max (PF74): maximum condensation value, in order to avoid
modulations with high external temperatures
The new setpoint will be given by the external temperature added to the parameter delta temperature. The values of this new set, converted into pressure, are in any case limited by the
range of variation for the condensation setpoint.
Please note. By enabling this function, the condensation setpoint parameters of the individual
circuits no longer have any effect on condensation regulation, indeed the setpoint used will be a
function of delta T and the external temperature.
Page
98
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
6.7.8 Temperature probes
The application is capable of managing up to two auxiliary temperature probes: environment probe
and external probe.
In order to take advantage of these two temperature transducers, it is necessary to enable (from the
installer -> Miscellaneous menu) the parameters:
⋅ enable environment temperature probe (PH23)
⋅ enable external temperature probe (PH24)
Each of the two probes is associated with a probe alarm, which trips should the probe be
disconnected or damaged, and enabling of this alarm is associated with the enabling parameter for
the relevant probe; enabling the probes also enables the related alarms. If these are not enabled, a
series of dots appears on the displays.
6.7.9 Last maintenance date
In the service -> Operation menu there is a page offering the option to store the date of the most
recent system maintenance. By pressing “Update” the old date will be automatically set to the
current date, thus also updating the parameter PM90 representing precisely the last maintenance
date.
6.7.10 Restore default parameters
By means of the “Restore parameters” procedure, it is possible to restore all system parameters to
the default values. This function may be simply activated by setting the value of the specific
parameter (PH15), where, by setting it to “Yes” the system will automatically reset all parameters.
The parameter will briefly assume the value “Yes” and then return to the value “No”, after this
change of state, the parameter reset procedure is complete.
The procedure can only be activated with the machine switched off.
Following this operation, it is necessary switch the machine off and then on again in order to avoid
malfunctions, in that inconsistencies in the calculation algorithms might occur.
Page
99
C-PRO MEGA RACK & C-PRO GIGA RACK APPLICATION MANUAL
7 DIAGNOSTICS
The application is capable of managing a series of alarms relating to the system compressors, fans,
circuits and functions. Based on the various alarm types, it is possible to configure resets (manual or
automatic), possible signalling delays and the actions to be executed in specific cases.
When several alarms are active, display LED L0 flashes (even with the machine off) and the buzzer
sounds if the machine is switched on.
In order to view the alarm pages, press and hold key K0 for approx. 2 seconds.
To scroll through the active alarms, simply press the ENTER key, the alarms are shown in order of
priority, just as they are listed in the alarm table in section 7.2.
All alarms are monitored, even with the machine switched off, hence, even with the machine off, by
using the K0 key, it is possible to view the active alarms, and LED L0 flashes. The buzzer (if
parameter enabled) only sounds when the machine is on.
The alarms may only be managed by one of the two interfaces, exclusively. Once the alarm pages
have been entered, the controller only accepts commands from the device that initiated the
procedure. In any case, the pages are shown simultaneously on both displays.
To inform the user that alarm pages are being displayed on one of the two interfaces, the L0 LED
flashes rapidly.
To exit from management of one view and move to another, exit from the alarm pages: press the
ESC key, or this will occur after 60 seconds if no other keys have been pressed.
Exiting an alarm page by pressing the ESC key, or by waiting 60 seconds for timeout, returns the
user to the main page of the application.
All digital inputs relating to alarms are managed by the parameter Alarm DI logic (PH17) which
assumes the following significance:
⋅ If set to “NO”, the inputs will normally be de-energised (open): N.O. logic
⋅ If set to “NC”, the inputs will normally be energised (closed): N.C. logic
7.1 Manual and automatic alarms
The program is capable of managing two types of alarms, those that are manually reset, and those
that are automatically reset. Certain alarms have the possibility for setting, by means of a parameter
(alarm reset), the type of reset best suited to the user’s needs.
7.1.1 Manual alarms
In the case where a manual alarm occurs:
⋅ LED L0 begins flashing
⋅ the buzzer begins to sound at a high frequency (if the machine is on)
Pressing and holding the K0 key for approx. 2 seconds enters the description page for the active
alarm.
Once the conditions responsible for causing the alarm are resolved it is possible to manually reset
the alarm. To do this:
⋅ go to the page for the alarm to be reset
⋅ press and hold the ENTER key for approx. 2 seconds.
Page
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.