ETC® Setup Guide
Sensor®3 Ride-thru Option Module Installation Guide
Introduction
This guide illustrates installation of the Sensor®3 Ride-thru Option Modules to the rear of the
CEM3 backplane. The Ride-thru Option Module prevents the CEM3 from shutting down in the
event of a brief drop in supply voltage (brown out).
Installation on an installed CEM3 will require negotiating load wires, terminations wires, and other
obstructions. Use caution when moving, bending or otherwise manipulating existing wires inside of
the rack.
Note:
If you are adding this module while upgrading a dimmer rack to be a Sensor3
CEM3 rack, be sure to attach the dimmer output ribbon cables before following
this procedure. It is very difficult to connect the ribbon cables after the ride-thru
option module has been installed.
Installation Procedure
Step 1: Power down the rack. Before removing dimmer or control modules for service,
de-energize main feed to dimmer rack and follow appropriate Lockout/Tagout
procedures as described in NFPA Standard 70E. It is important to note that
electrical equipment such as dimmer racks can present an arc flash safety
hazard if improperly serviced. This is due to available large short circuit
currents on the feeders of the equipment. Any work on energized equipment
must comply with OSHA Electrical Safe Working Practices.
WARNING:
Step 2: VERIFY that no power is connected to the rack
Step 3: Plug the wire harness into the module making
Step 4: Connect the orange wire harness connector to
Step 5: Locate the holes in the rear of the backplane using a small mirror (included in the kit).
Step 6: Screw the module to the appropriate holes in the rear of the backplane (see
RISK OF ELECTRIC SHOCK! Failure to disconnect all power to the rack
before working in the rack could result in serious injury or death.
by checking voltages for all combinations
between the phase bars, neutral and ground.
sure that the wires run towards the center bulk of
the module (see graphic at right). If attached in
the wrong orientation, the module will not
function.
the appropriate connector on the rear of the
backplane (see illustration next page).
illustration next page).
Corporate Headquarters
London, UK
Rome, IT
Holzkirchen, DE
Hong Kong Rm 1801, 18/F, Tower I Phase 1 Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong Tel +852 2799 1220 Fax +852 2799 9325
Service:
Web:
7140M2160 Rev A Released 2011-02
Sensor3 Ride-thru Option Module Installation Guide Page 1 of 2 Electronic Theatre Controls, Inc.
Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK Tel +44 (0)20 8896 1000 Fax +44 (0)20 8896 2000
Via Pieve Torina, 48, 00156 Rome, Italy Tel +39 (06) 32 111 683 Fax +39 (06) 32 656 990
(Americas) service@etcconnect.com
www.etcconnect.com
3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA Tel +608 831 4116 Fax +608 836 1736
Ohmstrasse 3, 83607 Holzkirchen, Germany Tel +49 (80 24) 47 00-0 Fax +49 (80 24) 47 00-3 00
QSF 4.1.9.1
(UK) service@etceurope.com (DE) techserv-hoki@etcconnect.com
Copyright © 2010 ETC. All Rights Reserved. Product information and specifications subject to change.
(Asia) service@etcasia.com

Setup Guide:
Connect wire harness here
with wires running towards
center of module.
Attach orange
connector from
harness here
Sensor3 Ride-thru Option Board
Sensor3 Ride-thru Option Module Installation Guide Page 2 of 2 Electronic Theatre Controls, Inc.