ETC P-OCC-SR, P-OCC, P-OCC-HC Installation Manual

Page 1
ETC Installation Guide
Unison Paradigm® Occupancy Sensor
Occupancy Sensor Installation Guide Page 1 of 8 Electronic Theatre Controls, Inc.
Corporate Headquarters  Middleton, Wisconsin, USA  Tel +608 831 4116  Service: (Americas) service@etcconnect.com London, UK  Tel +44 (0)20 8896 1000  Service: (UK) service@etceurope.com Rome, IT  Tel +39 (06) 32 111 683 Service: (UK) service@etceurope.com Holzkirchen, DE  Tel +49 (80 24) 47 00-0

Service: (DE) techserv-hoki@etcconnect.com
Hong Kong  Tel +852 2799 1220 Service: (Asia) service@etcasia.com Web: www.etcconnect.com
 Copyright © 2016 ETC. All Rights Reserved.
Product information and specifications subject to change
. ETC intends this document to be provided in its entirety.
7184M2160  Rev C Released 2016-07
Overview
The Unison Paradigm® Occupancy Sensor is a ceiling mounted sensor that utilizes passive infrared (PIR) technology, providing reliable vacancy and occupancy detection for lighting control. Paradigm Occupancy Sensors integrate with Paradigm lighting control systems, providing energy efficient lighting control solutions.
Each sensor is available in neutral white or black finish. Lens masks are provided to allow customized occupancy detection fields as required by each installation.
Wire Specification
The Paradigm Occupancy Sensor utilizes LinkConnect to power the sensor and to provide data to and from the connected Paradigm control system. LinkConnect is topology-free and polarity independent. You can install your data runs in any desired combination of bus, star, loop, and home-run. ETC recommends using Belden 8471 (or equivalent) wire. The total combined length of a LinkConnect wire run may not exceed 1,640 feet (500m), with a maximum distance of 1,312 feet (400m) between any two devices.
All control wiring should be installed and terminated by a qualified installer and should follow standard wiring installation practices and meet local codes. Leave approximately 10 inches (254mm) of wiring in the junction box or tied back in the ceiling to allow for wiring connections and future service needs.
Note:
ETC requires that all sensors be grounded by using a 14 AWG (2.5mm
2
) ESD drain wire.
The Paradigm Occupancy Sensor provides 360 degree coverage of the installed location and is available in three models:
P-OCC-SR- Occupancy Sensor with small room lens covers 450 sq. ft. at 8 ft. (41.8m
2
at 2.4m) / 800 sq. ft. at
12 ft (74.3m2 at 6.65m).
P-OCC - Occupancy Sensor with standard room lens covers 1,800 sq. ft. at 8 ft. (167m
2
at 2.4m)/ 3,000 sq. ft.
at 12 ft. (279m2 at 6.65m).
P-OCC-HC - Occupancy Sensor with high ceiling lens covers 350 sq. ft. at 12 ft. (32.5m
2
at 2.4m)/ 7,000 sq. ft.
at 40 ft. (650m2 at 12.2m)
Page 2
ETC Installation Guide
Occupancy Sensor
Occupancy Sensor Installation Guide Page 2 of 8 Electronic Theatre Controls, Inc.
Installation Environment
Paradigm Occupancy Sensors are intended for installation to a finished ceiling surface, ceiling tile mounted, attached to a round fixture junction box or single-gang RACO switch box. The sensor operates in ambient temperatures of -10°C to 40°C, non-condensing humidity.
ETC recommends paying special attention to the installation environment:
• The sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets, shelves, hanging light fixtures, etc.
• Do not install the sensor within eight feet from an HVAC airflow duct / vent.
• Install the sensor where it cannot easily sense movement in areas outside of the intended space, such as hallways, glass partitions, or adjacent rooms. If the installation location cannot avoid these conditions, portions of the lens can be masked to block the sensor view of these undesired areas. Reference Lens Masking on page 5.
Parts and Supplies
The following parts and supplies are included with the Unison Paradigm® Occupancy Sensor ordered:
Installation
The Paradigm Occupancy Sensor is provided with a twist-lock mounting plate that can be mounted to a junction box, finished ceiling or soft ceiling tile. Determine the installation method and follow the detailed instructions:
See “Junction Box Installation” on page 3.
See “Soft Ceiling Tile Installation” on page 4.
• soft ceiling tile adapter • 3 position WAGO connectors
• LinkConnect & ESD ground wire pigtails
• 2 each screws, 6-32 x 3/4” and 1 3/4”
• 3 each lens masks (spare)
Note:
The LinkConnect pigtail and WAGO connectors (provided) are only required when the sensor is installed in series with other stations or sensors. If you are not continuing the data run, direct termination on the control board is recommended.
Page 3
ETC Installation Guide
Occupancy Sensor
Occupancy Sensor Installation Guide Page 3 of 8 Electronic Theatre Controls, Inc.
Junction Box Installation
Step 2: If you are installing the sensor in series with other sensors
or stations (continuing the data run), use the provided
LinkConnect pigtail, ESD ground pigtail and WAGO connectors to make the terminations. If you are not continuing the data run, proceed to step 3.
a: Strip 3/16” (5mm) of insulation from each installed LON
wire.
b: Open the three terminal levers on a WAGO connector
and insert the installed (typically black) Belden 8471 LinkConnect wire, the black lead from the sensor pigtail, and the continuing Belden 8471 (typically black) wire into
the terminals. c: Close the levers onto the wires. d: Repeat the above for the installed (typically white) Belden
8471 LinkConnect wire and the remaining pigtail from
the sensor, and repeat for the ESD ground wires. Use a
new WAGO connector for each termination type.
Step 3: Orient the smooth side of the mounting plate to the junction
box and pull the Belden 8471 and the 14 AWG (2.5mm
2
) ESD ground wire from the junction box through the provided holes near the center of the mounting plate.
Step 4: Secure the mounting place to the junction box using the screws
provided (both short and long screws are included for convenience).
terminate
wires here
Step 1: Pull the Belden 8471 (or equivalent)
and 14 AWG (2.5mm
2
) ground wire
to the junction box.
in
s
t
a
l
le
d c
o
n
trol
w
ire
i
n
st
a
l
l
e
d con
trol
wire
t
o
ne
x
t st
ati
on
sensor pigtail
Page 4
ETC Installation Guide
Occupancy Sensor
Occupancy Sensor Installation Guide Page 4 of 8 Electronic Theatre Controls, Inc.
Step 5: Strip each wire 5/16” (8mm) and terminate the white, black,
and green (ground) wires to the terminal block located on the sensor control board. Torque each termination to 3.1-3.5 in-lb.
a: Terminate the white incoming wire to terminal A. b: Terminate the black incoming wire to terminal B. c: Terminate the green wire to the ground terminal.
Step 6: Attach the sensor to the mounting plate by aligning the tabs on
the sensor with the slots on the mounting plate, then twist clockwise until the two are locked into place.
Soft Ceiling Tile Installation
Step 1: Pull the Belden 8471 (or equivalent) and 14 AWG (2.5mm2)
ground wire to the installation location.
Step 2: Orient the smooth side of the mounting plate to the ceiling tile
and insert the soft ceiling tile adapter through the two small holes near the center of the mounting plate.
Step 3: Poke the adapter tines through the ceiling tile, then bend each
tine over in opposite directions for a secure fit.
poke the adapter through the ceiling tile, then bend
it over for a secure fit.
LinkConnect pigtail and
WAGO connectors
(optional use)
terminate
wires here
Page 5
ETC Installation Guide
Occupancy Sensor
Occupancy Sensor Installation Guide Page 5 of 8 Electronic Theatre Controls, Inc.
Step 4: If you are installing the sensor in series with other sensors
or stations (continuing the data run), use the provided LinkConnect pigtail, ESD ground wire pigtail and WAGO connectors to make the terminations. If you are not continuing the data run, proceed to step 5.
a: Strip 3/16” (5mm) of insulation from each installed wire. b: Open the three terminal levers on a WAGO connector
and insert the installed (typically black) Belden 8471 LinkConnect wire, the black lead from the sensor pigtail, and the continuing Belden 8471 (typically black) wire into
the terminals. c: Close the levers onto the wires. d: Repeat the above for the installed (typically white) Belden
8471 LinkConnect wire and the remaining pigtail from
the sensor, as well as the ESD ground wires using a new
WAGO connector for each termination type.
Step 5: Create a hole for wire pass-through in the ceiling tile by poking
through the center hole or oblong hole of the mounting plate, then pull the wires through.
Step 6: Strip each wire 5/16” (8mm) and terminate the white, black,
and green (ground) wires to the LON terminal block located on the sensor control board. Torque each termination to 3.1-3.5 in-lb.
a: Terminate the white incoming wire to terminal A. b: Terminate the black incoming wire to terminal B. c: Terminate the green wire to the labeled ground terminal.
Step 7: Attach the sensor to the mounting plate by aligning the tabs on
the sensor with the slots on the mounting plate, then twist clockwise until the two are locked into place.
Lens Masking
Lens masks are provided in the packaging for your convenience.
in
s
tal
le
d c
o
n
trol
w
ire
i
n
st
a
l
l
e
d control
wire
t
o
ne
x
t st
ati
on
sensor pigta
il
Step 1: As needed, trim the lens mask to fit
the desired area to be blocked.
Step 2: Gently press down on the sensor
lens, which will give only slightly, and insert the lens mask.
Step 3: Rotate the lens mask around the
dome to block the required area from occupancy sensing.
Page 6
ETC Installation Guide
Occupancy Sensor
Occupancy Sensor Installation Guide Page 6 of 8 Electronic Theatre Controls, Inc.
Power Up and Test
Power Up
For power to be applied to the Paradigm Occupancy Sensor, any additional LinkConnect terminations for the system must also be made. In addition, the Paradigm Architectural Control Processor (P-ACP) and Station Power Module (P-SPM) must be installed in the host DRd or ERn rack enclosure.
When the sensor is powered up the PIR LED will illuminate for one minute for calibration and warm-up, then will return to normal operation and enter walk test mode if desired.
Binding Sensors to Paradigm
The Paradigm Architectural Control Processor (P-ACP) to which this sensor is physically wired to must learn, or be told, the station hardware address (known as a neuron ID). When the sensor is unbound from the connected P-ACP, the service pin LED blinks.
The neuron ID is labeled on the sensor control board and can be manually entered into the configuration using LightDesigner software. Alternatively, the sensor can be identified using the [Service Pin] button (designated with “S” on the button) and by the connected Paradigm ACP using its [LonWorks Connections] menu. Reference the related source documentation, either the
LightDesigner Online Help System or the Unison Paradigm Architectural Control Processor Configuration Manual, specifically the section on Arch Setup
Menu, LonWorks Connections.
Test
Unison Paradigm Occupancy Sensors offer a Walk Test mode which shortens the vacancy / no occupancy timer to 10 seconds, allowing for simple and quick verification of the sensors coverage and range in the installed space.
Walk-Test mode automatically exits and the sensor returns to normal operation after five minutes and can be manually terminated early by pressing the [Walk Test] or [Service Pin] button on the sensor or alternatively by clicking on the “Wink” command in LightDesigner.
Page 7
ETC Installation Guide
Occupancy Sensor
Occupancy Sensor Installation Guide Page 7 of 8 Electronic Theatre Controls, Inc.
Enable Walk Test Mode
Step 1: Prepare the site for configuration.
a: Make certain the sensor and lighting loads are powered
and connected for control by the Paradigm control
system. b: You will need direct access to the Paradigm Occupancy
Sensor in order to place it into walk test mode.
Alternatively, you can invoke the walk test mode by
sending a Wink command from the connected Paradigm
control system. Reference the LightDesigner Online Help
System for instructions to send a Wink command.
Step 2: Press the [Walk Test] button on
the front of the sensor to enable the walk test feature at the sensor. A green LED will begin to flash, indicating the walk test is enabled and the vacancy / no vacancy occupancy timer will be shortened to 10 seconds.
Step 3: Move throughout the space
including corners and areas that may specifically be obscured from line of sight to the sensor. Each time the sensor detects movement, the lens will illuminate red.
Step 4: Adjust the lens masking, if installed, blocking certain areas of
the installed space from sensor detection. See Lens Masking on
page 5.
Step 5: Walk test mode will automatically exit after five minutes from
the time it was enabled. To manually exit the walk test mode, press either of the buttons on the sensor.
Note:
The sensor must be connected and bound to the Paradigm Architectural Control Processor (P-ACP) in order to enable Walk Test Mode. See “Binding Sensors to Paradigm” on page 6.
service
button
service
button
walk test
button
walk test
button
Page 8
ETC Installation Guide
Occupancy Sensor
Occupancy Sensor Installation Guide Page 8 of 8 Electronic Theatre Controls, Inc.
Verify Vacancy Operation
For systems that have been configured for the installed sensor to control specific lighting circuits, walk test mode can also be used to verify vacancy operation.
Step 1: Confirm the installing technician has programmed the lighting
control system.
Step 2: Enable walk test mode using the instruction above (see Enable
Walk Test Mode).
Step 3: With walk test mode enabled, exit the room for 15 seconds to
allow the 10 second timer to expire.
Step 4: Re-enter the room and confirm the configured vacancy / no
occupancy state was properly recalled.
Step 5: Walk test mode will automatically exit after five minutes from
the time it was enabled. To manually exit the walk test mode, press either of the buttons on the sensor.
Note:
When in walk test mode, status LEDs will always behave as indicated above, even if they have been programmed to be off by the system configuration.
High Ceiling side view
0
3.0m
10ft
3.0m
10ft
6.1m
20ft
6.1m
20ft
9.1m
30ft
9.1m
30ft
12.2m
40ft
12.2m
40ft
0
12.2m
40ft
9.1m
30ft
6.1m
20ft
Small Room side view
0
0
1.5m
5ft
1.5m
5ft
3.0m
10ft
3.0m
10ft
4.6m
15ft
4.6m
15ft
6.1m
20ft
6.1m
20ft
8ft
2.4m
10ft
3.0m
12ft
3.7m
Side view
0
1.5m
5ft
1.5m
5ft
3.0m
10ft
3.0m
10ft
4.6m
15ft
4.6m
15ft
6.1m
20ft
0
8ft
2.4m 10ft
3.0m 12ft
3.7m
6.1m
20ft
Loading...