SOLENOID DRIVEN METERING PUMPS
WITH DIAPHRAGM
OPERATING MANUAL
This operating instructions contains safety information that if ignored can endanger life or result in serious injury.
Read these instructions carefully before use and keep them for future reference. The original instruction is in Italian. All non-Italian instructions are translations of the original instruction.
Information and specifications on this manual could be uncorrect or could have printing errors. Specifications are subject to change without notice.
Version: R1-11-13
NORME CE EC RULES (STANDARD EC) NORMAS DE LA CE
Direttiva Basso Voltaggio Low Voltage Directive Directiva de baja tensión
Direttiva EMC Compatibilità Elettromagnetica EMC electromagnetic compatibility directive EMC directiva de compatibilidad electromagnética
Norme armonizzate europee nell’ambito della direttiva European harmonized standards underdirective Las normas europeas armonizadas conforme a la directiva
K METERING PUMP IS TESTED AND CERTIFIED BY WQA TO NSF/ANSI 50 AND 61 FOR MATERIALS SAFETY.
2006/95/CE
2004/108/CE
2006/42/CE
ICON
2

GENERAL SAFETY GUIDELINES

Operating, installing, or maintaining the unit in any way that is not covered in this manual could cause death, serious personal injury, or damage to the equipment.
This manual use the following safety message icon:
Danger! Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Warning!
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Important - A practice not related to personal injury or additional information.
Cross reference - An instance which refers to related information elsewhere in the same document

PURPOSE OF USE AND SAFETY

METERING PUMP IS INTENDED FOR CHEMICAL DOSING.
Do not use in explosive area (EX). Do not use with flammable chemicals. Do not use with radioactive chemicals.
Use after a proper installation.
Use the pump in accordance with the data and specifications printed on the label.
Do not modify or use in a manner inconsistent with the provisions of the operating manual.
Keep the pump protected from sun and water. Avoid water splashes.
In emergencies the pump should be switched off immediately. Disconnect the power cable from the power supply.
When using pump with aggressive chemicals observe the regulations concerning the transport and storage of aggressive fluids.
When installing always observe national regulations.
Manufacturer is not liable for any unauthorized use or misuse of this product that may cause injury, damage to persons or materials.
Pump must be accessible at all times for both operating and servicing. Access must not be obstructed in any way.
Feeder should be interlocked with a no-flow protection device.
Pump and accessories must be serviced and repaired by qualified and authorized personnel only.
Before any operation:
always read chemical Material Safety Data Sheet (MSDS);
always wear protective clothing;
always discharge the liquid end before servicing the pump.
empty and rinse the liquid end before work on a pump which has been used with hazardous or unknown chemicals.
This equipment requires regular maintenance to ensure potability requirements of the water and maintenance of improvements as declared by the manufaturer.
Feeder should be interlocked with a no-flow protection device to automatically shut-off the pumps when there is no flow!
Adequate measures shall be taken to prevent cross connection of chemicals!
Chemical feeding must be stopped during backwash cycles and periods of noflow as these conditions may introduce the potential for chemical overdosing. Not doing so may result in elevated chemical concentrations and hazerdous gas introduction into the pool or spa.
3

ENVIRONMENTAL SAFETY

Work area
Always keep the pump area clean to avoid and/or discover emissions.
Recycling guidelines
EWC code: 16 02 14
Always recycle according to these guidelines:
1. If the unit or parts are accepted by an authorized recycling company, then follow local recycling
laws and regulations.
2. If the unit or parts are not accepted by an authorized recycling company, then return them to
the nearest representative.
Waste and emissions regulations
Observe these safety regulations regarding waste and emissions:
• Dispose appropriately of all waste.
• Handle and dispose of the dosed chemical in compliance with applicable environmental
regulations.
• Clean up all spills in accordance with safety and environmental procedures.
• Report all environmental emissions to the appropriate authorities.

LABEL

Distributor
CODE: pump code MODEL: pump model
PUMP’S DATA
S/N: serial number

SPARE PARTS

Fig. 1. Product label.

QR code
For spare parts orders or any other communication, refer to the pump’s label. Code (CODE) and serial number (S / N) uniquely identify the pump.

Fig. 2. WQA label.

THIS METERING PUMP IS TESTED AND CERTIFIED BY WQA TO NSF/ANSI 50 AND 61 FOR MATERIALS SAFETY.
Data matrix
4
Transportation and storage
A not suitable transportation or storage can cause damages.
Use origianal box to pack the pump.
Observe storage conditions also for transportation.
Although packed, always protect the unit against humidity and the action of chemicals.
Before return the dosing pump to the manufacturer Repair service, drain the chemical from pump head and rinse it. Refer to Shutdown procedure.
Fill the PRODUCT SERVICE REPAIR FORM and send it with the dosing pump. Repair service is not accepted if PRODUCT SERVICE REPAIR FORM is missing.
DO NOT TRASH PACKAGING. USE IT TO RETURN THE PUMP.
Transportation and storage temperature ..... 10 ÷ 50°C (32 ÷ 122°F)
Umidity ...................................................... 95% relative humidity (not condensed)

Included into package

5
QUANTITY CONTENT K PLUS K CL PLUS K CO PLUS
n. 4 ø6 dibbles
n. 4
4,5 x 40 self tapping screws
n. 1 5 X 20 delayed fuse
n. 1
n. 1
level probe with axial foot filter (PVDF)
0,3 bar injection valve (PVDF)
m 2 delivery hose (PVDF)
m 2 suction hose (PE)
m 2
venting hose (PVC 4x6 transparent)
m 2,5 input signal cable
n.1 operating manual

DESCRIPTION

K PLUS

NSF/ANSI 61

K CO PLUS

NSF/ANSI 61

K CL PLUS

K PLUS is a constant or proportional dosing pump with level control for chemical feeding into water.
In Constant dosing mode pump doses a constant quantity regularly as configured by the user. In Proportional dosing mode pump doses a quantity proportionally to an input signal, digital (voltage free contact) or current (mA).
Working modes available:
constant
constant with 1-10 pulses divider
multiplier with 1-10 pulses divider
divider with 1-10 pulses divider
divider with 1-100 pulses divider
divider with 1-1000 pulses divider
mA current signal (0/4 mA = 0 pulses: 20mA = max pulses)
Flow rate is determined by the stroke length and by the stroke speed. The stroke length is adjustable from 0 to 100% using the stroke length adjustment knob. However dosing accuracy is guarantee within an adjustment range from 30% to 100%.
K CO PLUS works in constant mode.
The pump can be set to work in
constant
constant with 1-10 speed reducer.
K CL PLUS works in constant mode and has got level control.
NSF/ANSI 61
Self venting: KA PLUS
NSF/ANSI 61
6
The pump can be set to work in
constant
constant with 1-10 speed reducer.
KA is the K version with self-venting pump head. Self-venting pump head must be used when using chemicals that produce gas (i.e. hydrogen peroxide, ammonium, sodium hypoclorite at particular conditions). For connections Self-Venting pump head installation”.

Fig. 3. K PLUS - KA PLUS

1
2
3
4
5
K PLUS- detail on pump head with manual venting
Venting knob
Delivery valve
To manual venting hose
Suction valve
KA PLUS - detail on self venting pump head mod. LA, MA, NA
To self venting hose
Delivery valve
Suction valve
Level probe input
External signal input
Power supply
7

Features

Power Supply Fuse 230 VAC (180-270 VAC) 115 VAC (90-135 VAC) 24 VAC (20-32 VAC)
- 50/60 Hz 1 A
- 50/60 Hz 500 mA
- 50/60 Hz 2 A
12 VDC (10-16 VDC) 2 A
Environment temperature .........................10 ÷ 45°C (55 ÷ 113°F) - 50/60 Hz
Chemical temperature ..............................0 ÷ 50°C (32 ÷ 122°F) - 50/60 Hz
Transportation and storage temperature ...10 ÷ 50°C (55 ÷ 122°F) - 50/60 Hz
Installation class ......................................II
Pollution level ..........................................2
Audible noise ...........................................73,4 dbA (silenced: 70,4 dbA; ultrasilenced: 69,4 dbA)
Protection degree .....................................IP 65
Working UR % .......................................... 85% at t 40 °C; 70% at 50 °C (no condensing water)
Max installation height .............................1,5 m
Capacity .................................................. Table 1 and 2

Tab. 1. Capacity (manual and self venting models)

cc per
stroke *
min max
cc per
stroke *
min max
max
l/h
max
l/h
Flow
Flow
Min GPH
Min GPH
Max GPH
Max GPH
Mod.
K PLUS
1802 0,06 2 0,000016 0,53 0,06 0,19
1504 0,11 4 0,000029 1,06 0,11 0,37
1005 0,14 5 0,000037 1,32 0,14 0,46
0808 0,22 8 0,000058 2,11 0,22 0,74
0510 0,28 10 0,000074 2,64 0,28 0,93
0501 0,28 1 0,000008 0,3 0,03 0,09
0218 0,50 18 0,00013 4,76 0,50 1,67
Mod.
KA PLUS
1801 0,03 1 0,000008 0,26 0,03 0,09
1503 0,08 3 0,000021 0,79 0,08 0,28
103.5 0,10 3,5 0,000026 0,92 0,10 0,32
085.5 0,15 5,5 0,000040 1,45 0,15 0,51
057.5 0,21 7,5 0,000055 1,98 0,21 0,69
0213 0,37 13 0,000098 3,43 0,37 1,20
* cc per stroke: referred to cc/stroke with stroke length knob on 100%.
cc/h
cc/h
min
min
CAPACITY
pulse/
min
180
180
180
180
180
180
180
pulse/
min
180
180
180
180
180
180
Max
pressure
bar PSI
18 261
15 217
10 145
8 116
5 72
5 72
2 29
Max
pressure
bar PSI
18 261
15 217
10 145
8 116
5 72
2 29
peak Amps
(A)
230
115
VAC
VAC
2.7 1.45
2.7 1.45
2.7 1.45
2.7 1.45
2.7 1.45
2.7 1.45
2.7 1.45
peak Amps
(A)
230
115
VAC
VAC
2.7 1.45
2.7 1.45
2.7 1.45
2.7 1.45
2.7 1.45
2.7 1.45
Delivery
(PVDF)
Delivery
(PVDF)
Suction
hose
4 x 6 4 x 6 L
4 x 6 4 x 6 L
4 x 6 4 x 6 L
4 x 6 4 x 6 L
4 x 6 4 x 6 L
4 x 6 4 x 6 L
6 x 8 6 x 8 M
hose
4 x 6 4 x 6 LA
4 x 6 4 x 6 LA
4 x 6 4 x 6 LA
4 x 6 4 x 6 LA
4 x 6 4 x 6 LA
6 x 8 6 x 8 MA
hose
Suction
hose
Pump
head
Pump
head
8

Tab. 2. Capacity (compressed air model)

CAPACITY
Flow cc per
Modello
K AC PLUS
* cc per stroke: referred to cc/stroke with stroke length knob on 100%.
min
max
cc/h
1018 0.6 18 0.16 4.7 0.6 2 10 145 6 x 8 6 x 8 M
Min
l/h
GPH
Max GPH
stroke *
min max
Max
pressure
bar PSI
Delivery
hose
(PVDF)
Suction
hose
Pump
head

Manual stroke length adjustment

Materials

Max cc/stroke ( Construction Materials and Technical info) are referred to cc/stroke with stroke length knob on 100%. The stroke length knob adjusts the pump capacity. Press and rotate the knob when the pump is powered.
Dosing accuracy is guarantee within an adjustment range from 30% to 100%.
Note:if knob isn’t on 100% position then the pump will dose at pressure greater than the one declared on label.
✓ : standard ✗: options available
PVDF PP PPV0 PMMA PVC PE CE VETRO PTFE SS FKM B EPDM WAX SI
BOX
PUMP HEAD
DIAPHRAGM
BALLS
SUCTION HOSE
DELIVERY HOSE
VENTING HOSE
O RING
LEVEL PROBE/ FOOT FILTER
LEVEL PROBE CABLE
9

INSTALLATION

How to install metering pump

5 steps to install and start-up the pump:
1. Pump location
2. Piping connections (hoses, level probe, injection valve)
3. Wirings
4. Pump priming
5. Programming and start-up
The operator must be aware of safety precautions to prevent physical injury.

User health and safety

The work area

Pump location

POWER SUPPLY DISCONNECTION Disconnect power supply before you perform any installation or maintenance tasks. Failure to disconnect power will result in serious physical injury.
SAFETY EQUIPMENT Use safety equipment according to the company regulations. Use this safety equipment within the work area:
• Helmet
• Safety goggles (with side shields)
• Protective shoes
• Protective gloves
• Gas mask
THE WORK AREA Observe these regulations and warnings in the work area:
• Always keep the work area clean.
• Pay attention to the risks presented by gas and vapors in the work area.
• Avoid all electrical dangers. Pay attention to the risks of electric shock or arc flash hazards.
• Avoid water splashs and direct sun!
Pump must be installed on a stable support at a max 1,5 mt height from tank’s bottom.
Injection point must be higher than tank to avoid accidental chemical injection.
Otherwise, connect a multifunction valve on delivery pipeline.
INSTALLATION PUMP GUIDELINES
Install the pump
- in a safety place and fixed to the table / wall to avoid vibration problems;
- in an easy accessible place;
- in horizontal position.

Requirements for product positioning

10
Use only hoses compatibles with product to dose. See “Chemical compatibility table” page 31. If dosing product is not listed please consult full compatibility table or contact chemical’s manufacturer.
REQUIREMENTS FOR PRODUCT POSITIONING Only use fasteners of the proper size and material. Replace all corroded fasteners. Make sure that all fasteners are properly tightened and that there are no missing fasteners.

Fig. 4. Installation

1 - Dosing Pump 2 - Suction Hose 3 - Delivery Hose 4 - Injection Valve 5 - Air discharge 6 - Level Probe 7 - Foot Filter 8 - Power Cable 9 - Stand-by/alarm (if any)
4
3
8
9
1
Max 1,5 mt
2
5
6
7
11

PIPING CONNECTIONS

Foot filter / Level probe (included only in some models)
Level probe is assembled with a foot filter that avoid sediments priming probles. Install level probe on the bottom of the tank. Connect BNC level probe to the pump BNC input.
Warning: If there is a mixer installed into tank, install a suction lance instead of level probe / foot filter.
In case of replacement of level probe parts, follow the diagram below.

Fig. 5. Level probe assembling diagram.

STEP 5
STEP 4
INSERT RING AS SHOWN
STEP 3
A CLICK
STEP 2
INSERT FLOATER
INSERT PROBE
WITH N.O. CONTACT
UNTIL TO HEAR
STEP 1
INSERT RING AS SHOWN
12