Industrial/Commercial Evaporative Coolers
Industrial/Commercial Evaporative Coolers
Specification Guide
Specification Guide
J
G
S
J
Q
F
X
Q
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
SAS/SAD 100B SAS/SAD 10012B SAS/SAD 150B SAS/SAD 15012B
* All measurements in inches.
ABLEINDEX
specific MasterCool model
E
D
A
E
D
W
TOPVIEW
D
45
45 48 48
1
/4
1
/4
DUCT
OPENING
A
3
21
21
/4
3
21
21
/4
7
26
26
/8
7
26
26
/8
WET MODULE NUMBER
100W
10012W
150W
15012W
CABINET
H
W
44
63 67
44
66
54
70
54
3
/8
3
/8
5
/8
5
/8
HOW TO USE
THIS INDEX
Using the cooling
requirement variables of
Cooling Feet per Minute
and External Static
Pressure (shown as inches
of water), locate the
required and its
corresponding page
number. Turn to the
indicated page for specific
Performance Data and
Sizing Tables. Follow the
Sizing Instructions on the
front inside cover to
determine the MasterCool
product for any cooling
installation.
SAS
OUTLET
C
N
A
D
T
R
H
Y
C
SAD OUTLETSAD OUTLET
N
P
B
U
M
W
WEIV EDISWEIV TNORF
C
(SAS)
B
19
3
13
/4
19
3
13
/4
13
7
16
/8
13
7
16
/8
INDEX TABLE
INDEX TABLE
SAS/SAD 100 PAGE 2
SAS/SAD 10012 PAGE 4
SAS/SAD 150 PAGE 6
SAS/SAD 15012 PAGE 8
AS/AD 100 PAGE 1
AS/AD 10012 PAGE 3
AS/AD 150 PAGE 5
AS/AD 15012 PAGE 7
AS/AD/AU 20012 PAGE 9
DUCT
LOCATION
U
(SAD)
P
(SAD)
11
/32 /32 /16 /16
1
21
/32
11
1
21
/32
5
2
19
/32
5
2
19
/32
MODEL
& PAGE NO.
E
5
29
11
/8
/32
5
29
11
/8
/32
11
7
10
/16
/32
11
7
/16
/32
10
PERFORMANCE
0"
CFM
5377 59
18
6774
5371
5911
6767 7072
7783 8910
N/A N/A
6997 7702 8817
N/A N/A
7745 8524 9758
11569
7431 8178 9362
11099 11405
13057 15480 17719
11375 13020 15438 17672
16267 19286 22077 24301
DRAIN
LOCATION
G
F
1
1
22
12
/2
1
1
22
16
/2
1
1
24
12
/8
1
1
24
16
/8
0.1"
CFM
121
5 5
684 574
6
5064 5627 6513
6622 7372 8548 9476
N/A
6539 7286 8455 9375
N/A
7530 8333 9596
11463
7255 8024 9235
11001 10892
12600 15082 17364
10905 12604 15084 17360
15716 18820 21670 23929
WET
MODULE
/2
18
/2
22
/2
18
/2
22
Certified Air Delivery At Various Increments Of Static Pressure (Inches Static Pressure Water Gauge)
0.2"
CFM
4863 5451 6366
4794 5375 6286
6203 6987 8205 9159
N/A
6087 6876 8091 9044
N/A
7275 8109 9407
11285
7052 7842 9075
10868 10463
12204 14735 17050
10482 12225 14749 17060
15200 18371 21270 23562
J
1
/2
1
/2
1
/2
1
/2
CFM
11121
10736 10064
11844 14410 16756
10079 11865 14434 16777
14696 17943 20888 23204
0.3"
4605 5215 6164
4536 5142 6076
5769 6602 7870 8855
N/A
5603 6450 7734 8719
N/A
7004 7868 9204
6835 7649 8914
MEDIA
DIMENSION
Y
X
3
5
36
44
/4
/8
3
5
44
36
/4
/8
3
48
46
/8
3
46
48
/8
0.4"
0.5"
CFM
CFM
058
4336
4 4734
4980
751
5
5956
4269
3985 4663
4907
5666
5872
4777
5298
5764
6199
7182
7533
8244
8555
N/A
N/A
5051
4415
5994
5477
7359
6961
8389
8043
N/A
N/A
6460
6729
7368
7618
8773
8990
10773
10950
6376
6611
7244
7450
8572
8744
10457
10598
9276
9671
11153
11497
13810
14106
16214
16479
9678
9265
11514
11165
14133
13838 16242
16505
14190
13665 17092
17518
20142
20514
22528
22866
WATER
SERVICE
M
L
7
/8
5
14
7
5
/8
18
7
5
/8
14
7
5
/8
18
0.6"
CFM
3754 4479 5
537
3667 4399 5456
4201 5285 6812 7924
N/A
3717 4893 6525 7683 9377
6193 7123 8556
10592
6131 7030 8393
10313
8874 10815 13520 15947
8830 10807 13540 15983
13110 16661 19769 22190
ELECTRIC
SERVICE
S
1
5
/2
21
/8
1
5
21
/2
/8
1
5
23
/8
/8
1
5
/8
23
/8
0.7"
CFM
3429 42
09
320
5
3318 4115 5238
3607 4764 6416 7592 9315
3058 4260 6050 7293 9070
5923 6878 8340
10407
5877 6809 8209
10165
8456 10467 13234 15694
8366 10440 13246 15724
12521 16211 19395 21852
5 5 5 5
CFM
10224
10016
10113 12948 15440
10058 12899 15463
11886 15752 19015 21510
Performance shown is for installation type B - free inlet, ducted outlet. Power rating (BHP) does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.
T
5
/32
5
/32
5
/32
5
/32
0.8"
3097
3924 5095
2952 3809 5008
3041 4231 5993 7236 9032
2497 3637 5527 6869 8751
5646 6638 8124
5610 6580 8024
8006
7867
SKID
LOCATIONS
Q
N
3
3
4
/4
4
/4
3
3
4
/4
4
/4
3
3
4
/4
4
/4
3
3
4
/4
4
/4
0.9"
1.0"
CFM
CFM
--
--
3619
3307
4859
4613
2591
2261
3480
3145
4755
4497
2522
2040
3699
3199
5537
5067
6866
6470
8741
8436
2013
1571
3085
2609
4976
4425
6416
5932
8407
8046
5357
5045
6389
6137
7913
7698
10039
9856
5327
5031
6343
6095
7827
7631
9862
9709
7530
7017
9741
9361
12659
12361
15188
14937
7325
6753
9651
9220
12640
12328
15207
14947
11194
10450
15272
14760
18629
18229
21171
20823
R
42 42 52 52
SPECIFICATION GUIDE FOR MODELS:
SAS/SAD 100
SAS/SAD 10012
SAS/SAD 150
SAS/SAD 15012
AS/AD 100
AS/AD 10012
AS/AD 150
AS/AD 15012
AS/AD/AU 20012
OINTSDVANTAGE
A
1. CONSTRUCTION
used for cabinet panels and other load bearing components. Vacuum­formed ABS plastic water reservoirs and thick polystyrene evaporative media shields keep water from coming into contact with the steel cabinet for long-lasting durability.
2. EVAPORATIVE MEDIA
evaporative media is treated to ensure a high water absorption rate and to resist biological degradation.
3. FINISH
shaft, and pulley) are chemically treated and covered with an electrostatically-applied polyester finish at a thickness of 1 to 1.5 mil to protect the cooler from scratches and corrosion. This finish meets or exceeds requirements for the following tests:
All steel components (excluding the blower wheel,
P
Heavy gauge galvanized steel is
The cellulose paper of the
1000-Hour Salt Spray Test-ASTM B117
Abrasion Resistance Test-ASTM 4060-84
Impact Resistance Test-ASTM D2794
2400-Hour Imersion Test-ASTM D870
Adhesion Test-ASTM D3359
Double Inlet Configuration
MODULAR
CONFIGURATIONS
The unique modular design of the
dual inlet side- and down-draft
models are easy to reconfigure for
difficult or customized
installations.
remove
Single Inlet Configuration
connect
INLET UNIT
BLOWER UNIT
INLET UNIT
INLET UNIT
BLOWER UNIT
rotate
INLET UNIT
BLOWER UNIT
MASTERCOOL COOLERS ARE MADE BY THE
BEST:
One of the largest manufacturers of evaporative coolers, Champion Cooler has produced evaporative coolers that deliver high performance results and long-lasting durability for over 40 years. Champion’s engineering, design, and production efforts are directed at the continued manufacture of products that deliver maximum performance with minimum maintenance.
CHAMPION COOLER
NSTRUCTIONSIZING
The performance or Sensible Heat Capacity of any evaporative cooler is a function of both the CFM and the efficiency, which should be considered as part of the sizing process. To help ensure proper sizing of a MasterCool, use the Index on the following page to locate Performance Data and Sizing Tables for a specific MasterCool model. Follow the procedure below to determine the cooler size.
1. Determine design conditions.
Outside Dry-Bulb
Outside Wet-Bulb
Inside Dry-Bulb (TI)
2. Determine the design Sensible
Heat Load (Btuh).
3. Determine the cooler leaving air
temperature (LAT) from the tables.
EXAMPLE
Outside Dry-Bulb = 105
Outside Wet-Bulb = 65
Inside Dry-Bulb = 80
Determine the number of AD100 MasterCool coolers with 2 horsepower motors required to cool 125,000 Btuh heat load. Assume .5" (water) external static pressure.
Using the Sizing T ables, the following information should be calculated:
LAT = 72 CFM = 7368 SHC = 1.08(80-72)7368 = 63,660 Btuh Number of Coolers = 125,000/63,660 = 2
4. Determine CFM from the
performance tables.
5. Calculate Sensible Heat
Capacity of cooler using: SHC =1.08(TI-LAT)CFM
6. Determine the number of
coolers by dividing the Sensible Heat Load by the Sensible Heat Capacity.
S
MM
P
F
P
D
AU OUTLET
Q
AS OUTLET
X
C
J
G
EEA
D
G
Q
N
AD OUTLET
A
W
J
N
TOPVIEW
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
AS/AD 100B AS/AD 10012B AS/AD 150B AS/AD 15012B AS/AD/AU 20012B
WET MODULE NUMBER
100W
10012W
150W
15012W 20012W
CABINET
H
44 44 54 54
1
59
/4
85 93
105
W
82 90
1
/4
1
/4 1
/4
* All measurements in inches.
SPECIFICATIONS PERFORMANCE
MAX
B.H.P.
1
1
2 3 5
/2
OPER.
WGT.
706 710 723 739
MODEL
BELT
A76 B77 B80 B81
AS
MODEL
BELT
A82 B83 B86 B87
CFM
7745 8524 9758
11569
0"
RPM
364 400 458 543
AD
Performance shown is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include drive losses. When the Cooler Model No, Motor H.P.,
& Blower Speed are determined from the SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECTION table below.
D
45
45 48 48 60
1
/4
1
/4
1
/4
DUCT
OPENING
B
A
3
21
21
/4
3
21
21
/4
7
26
26
/8
7
/8
26
26
3
31
31
/4
C
(AS)
3
13
/4
3
13
/4
7
16
/8
7
16
/8
3
18
/4
19
/32
19
/32
13
/16
13
/16
11
/16
DUCT
LOCATION
U
(AD)
P
11
N/A
21
/32
11
N/A
21
/32
5
N/A
19
/32
5
N/A
19
/32
1
24
25
/4
(AU)
29
G
1
12
1
16
1
12
1
16
1
16
WET
MODULE
/2
18
/2
22
/2
18
/2
22
/8
22
J
1
/2
1
/2
1
/2
1
/2
1
/2
DRAIN
LOCATION
F
E
1
5
/2
22
11
/8
1
5
22
11 10 10
14
/32
/2
/8
1
11
24
/8
/16
1
11
24
/8
/16
1
1
30
/8
/4
Certified Air Delivery At .1" Increments Of External Static Pressure (Inches Static Pressure Water Gauge)
CFM
7530 8333 9596
11463
0.1"
373 408 465 549
CFM
7275 8109 9407
11285
0.2" RPMRPM
384 418 473 555
CFM
7004 7868 9204
11121
0.3" RPM
397 429 482 563
0.4"
CFM
6729 7618 8990
10950
RPM
409 441 492 570
CFM
6460 7368 8773
10773
0.5" RPM
422 452 502 578
CFM
6193 7123 8556
10592
0.6" RPM
434 464 512 587
Models AS/AD 100 include the affects of an 8 inch thick evaporative media on the inlet.
DIMENSION
MEDIA
X
3
44
/4
3
44
/4
48 48 60
0.7"
CFM
5923 6878 8340
10407
Y
Y
5
36
5
36
3
46
3
46
5
51
RPM
447 475 522 595
R
/8 /8 /8 /8 /8
10224
H
C
WATER
SERVICE
M
L
7
14
5
/8
7
5
18
/8
7
5
14
/8
7
5
18
/8
7
/8
5
18
0.8" RPM
CFM
5646
460
6638
486
8124
532 603
AD OUTLET
B
ELECTRIC
SERVICE
S
5
7
/8
39
/8
5
7
/8
43
/8
5
1
/8
41
/2
5
1
/8
45
/2
5
5
/8
51
/8
CFM
5357 6389 7913
10039
T
5
5
5
5
5
5
5
5
5
5
0.9"
D
/32 /32 /32 /32 /32
RPM
474 498 542 612
U
BLOWER
WEIV EDISWEIV TNORF
SECTION
SKID
LOCATIONS
Q
N
3
1
/4
4
23
/4
3
1
4
/4
27
/4
3
1
4
/4
23
/4
3
1
4
/4
27
/4
3
1
4
/4
27
/4
1.0"
CFM
5045 6137 7698 9856
R
42 42 52 52
57
RPM
489 510 552 620
1
/4
MOTOR SPECIFICATIONS
H.P.
1 1
1
/2
1
/2
2 2 3 5
MOTORS
SPEED
1 1 1 1 1 1
VOLTS
115/208-230 208-230/460 115/208-230 208-230/460 208-230/460 208-230/460
PHASE
1 3 1 3 3 3
MOTOR
AMPS*
20/11-10
6.6-6/3
24/13.2-12
7.5-6.8/3.4
10.6-9.6/4.8
16.7-7-15.2/7.6
SHAFT
DIA.
5/8 7/8 7/8 7/8
1
1
/8
1
1
/8
MOTOR
WGT(LB)
41 40 49 44 83 87
MOTOR
PART NO.
110459-1 110463-9
110460-1 110464-9 110465-9 110466-9
PUMP PART NO.
110467 110468
Pumps - 2 Required.
VOLTS
115 230
AMPS
1.0
0.58
BLOWER
*Amperage shown is from National Electrical Code. Use amperage shown on motor nameplate to determine motor protector.
SHEAVE SELECTION
MOTOR
H.P.
1-1/2 1-1/2
2 3 5
MAUREY
SHEAVE
D8450 D8450 D8450 D8550 D8600
SHEAVE
BORE
7/8
7/8 1 1/8 1 1/8
AD
MODEL
BELT
A765/8 A76 B77 B80 B81
MODEL
BELT
A82 A82 B83 B86 B87
11
12
391 401 391
401
414
424
482
492
549
559
BLOWER RPM/MOTOR SHEAVE 1/2 TURN DOWN
10
412 434 502 569
422 445 513 580
8
433 443422412 433 455 523 590
79
443 465 533 600
5
6
4
454 464 475 485 496 506 3DI-11 454
464 485 553 620
475 495 563 630
475 543 610
31
2
485
496
506
516
574
584
641
651
CHAMPION-AD
PULLEY-BELT
506 526 594 661
KIT NO.
3DI-10 3DI-15 3DI-20 3DI-25
AS
SIZING TABLES
1-1/2 H.P. MOTOR / CFM-
OUTDOOR DRY BULB
TEMP.
85
95 105 115
LAT
GPH
LAT
GPH
LAT
GPH
LAT
GPH
7745 / 0 75
77 79
15 80 23 82 31
* Static Pressure (inches of water). GPH = Water consumption at design conditions but does not include bleed-off amount. Amount of bleed-off will vary with different water sources, but
6460 / .5 5045 / 1.0
OUTDOOR WET-BULB
75
65
55
77
69
60
8
15
23
78
70
62
13
23
31
80
72
20
31
81
74
26
38
75
65
55
65
76
68
60
7
13 70 20 71 26 73 33
68
5
20
10
78
61
69
10
26
16
79
70
16
21
80
72
21
26
an amount equal to 10% of water consumption at any design condition is considered sufficient for average water. LAT = Cooler Discharge Temperature.
2 H.P. MOTOR / CFM-SP*
7368 / .5 6137 / 1.0
OUTDOOR WET-BULB
75
65
55
77
69
61
8
7
17
25
79
71
62
15
25
33
80
72
22
33
82
74
29
42
55 59
16 60 21
– – – –
8524 / 0
75 77
79 17 81 25 82 33
3 H.P. MOTOR / CFM-SP*
9758 / 0
75
65
55
77
69
60
6
15
22
78
70
62
12
22
29
80
72
19
29
81
74
25
37
75
65
55
77
68
60
9
12
19
79
70
61
19
19
25
81
71
28
25
83
73
38
31
8773 / .5 7698 / 1.0
OUTDOOR WET-BULB
75
65
55
65
55
77
69
61
69
61
9
19
28
17
26
79
71
63
71
63
17
28
38
26
34
81
73
73
26
38
34
83
75
74
34
47
43
75
65
77
69
8
15
79
70
15
23
80
72
23
31
82
74
31
38
5 H.P. MOTOR / CFM-SP*
10773 / .5 9856 / 1.0
OUTDOOR WET-BULB
75
65
55
77
69
62
10
22
33
79
72
64
21
33
44
81
74
31
44
83
76
41
54
55 60
23 62 31
– – – –
11569 / 0 75
77 11 79 22 82 33 84 44
75
65
55
65
55
77
69
61
69
61
10
21
31
19
28
79
71
63
71
63
19
31
41
28
38
81
73
73
28
41
38
83
75
75
38
51
47
WATTS
73 77
GPM (5 FT. HEAD)
4.6
4.6
CHAMPION-AS
PULLEY-BELT
KIT NO.
3DI-31 3DI-30 3DI-35 3DI-40 3DI-45
J
G
S
J
Q
F
E
D
A
SAS
OUTLET
T
R
X
C
E
Q
D
W
N
A
N
D
TOPVIEW
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
SAS/SAD 100B SAS/SAD 10012B SAS/SAD 150B SAS/SAD 15012B
WET MODULE NUMBER
100W
10012W
150W
15012W
CABINET
H
W
44
63 67
44
66
54
70
54
3
/8
3
/8
5
/8
5
/8
* All measurements in inches.
SPECIFICATIONS
MAX B.H.P.
3/4
1
1
1
/2
SAD
OPER.
MODEL
WGT.
BELT
B77
480
B77
483
B77
498
Performance shown is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include drive losses. When the Cooler Model No, Motor H.P.
PERFORMANCE
SAS
MODEL
BELT
CFM
B83 B83 B83
0"
RPM
5377
352
59
388
18
444
6774
, & Blower Speed are determined from the SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECTION table below.
D
45
45 48 48
CFM
1
/4
1
/4
DUCT
OPENING
B
A
3
21
21
/4
3
21
21
/4
7
26
26
/8
7
26
26
/8
C
(SAS)
3
13
/4
3
13
/4
7
16
/8
7
16
/8
19
/32
19
/32
13
/16
13
/16
DUCT
LOCATION
U
(SAD)
P
11
21
/32
11
21
/32
5
19
/32
5
19
/32
(SAD)
29
1
/32
29
1
/32
7
2
/32
7
2
/32
E
5
11
/8
5
11
/8
11
10
/16
11
10
/16
Certified Air Delivery At .1" Increments Of External Static Pressure
5121 5684 6574
0.1" RPM
364 398 453
CFM
4863 5451 6366
0.2" RPM
376 409 463
CFM
4605 5215 6164
0.3" RPM
389 421 472
CFM
4336 4980 5956
0.4" RPM
402 432 482
G
12 16 12 16
MODULE
1
/2
1
/2
1
/2
1
/2
WET
J
18 22 18 22
DRAIN
LOCATION
F
1
22
/2
1
22
/2
1
24
/8
1
24
/8
(Inches Static Pressure Water Gauge)
0.5"
CFM
4058 4734 5751
Models SAS/SAD 100 include the affects of an 8 inch thick evaporative media on the inlet.
RPM
415 444 492
0.6"
CFM
3754 4479 5537
DIMENSION
1
44
/2
1
44
/2
1
/2
1
/2
RPM
430 456 502
H
P
MEDIA
X
3
/4
3
/4
48 48
0.7"
CFM
3429 4209 5320
C
Y
36 36 46 46
RPM
5
/8
5
/8
3
/8
3
/8
448 470 513
SAD OUTLETSAD OUTLET
B
WATER
SERVICE
M
L
7
/8
5
14
7
5
/8
18
7
5
/8
14
7
5
/8
18
0.8"
CFM
3097 3924 5095
W
ELECTRIC
SERVICE
S
1
5
21
/8
1
5
21
/8
1
5
23
/8
1
5
23
/8
RPM
469 485 524
U
/2 /2 /8 /8
CFM
-­3619 4859
T
5 5 5 5
0.9"
5
/32
5
/32
5
/32
5
/32
WEIV EDISWEIV TNORF
RPM
-­503 536
M
SKID
LOCATIONS
Q
N
3
3
4
/4
4
/4
3
3
4
/4
4
/4
3
3
4
/4
4
/4
3
3
4
/4
4
/4
1.0"
RPM
CFM
-­3307 4613
Y
R
42 42 52 52
-­523 548
MOTOR SPECIFICATIONS
H.P.
3/4 3/4 3/4
1 1 1
MOTORS
SPEED
1 2 1 1 2 1
VOLTS
115/208-230
230
208-230/460
115/230
230
208-230/460
PHASE
1 1 3 1 1 3
MOTOR
AMPS*
13.8/7.6-6.9
6.9
3.5-3.2/1.6 16/8
8
4.6-4.2/2.1
SHAFT
DIA.
5/8 5/8 5/8 5/8 5/8 7/8
BLOWER
*Amperage shown is from National Electrical Code. Use amperage shown on motor nameplate to determine motor protector.
MOTOR
WGT(LB)
24 29 20 28 29 34
MOTOR
PART NO.
110455 110456 110461 110457 110458
110462-9
BLOWER
MOTORS
SPEED
H.P.
1
1
/2
1
1
/2
PUMP PART NO.
110467 110468
Pumps - 1 Required.
SHEAVE SELECTION
MOTOR
H.P.
3
/4
, 1
3
,1, 1
/4
1
1
1, 1
/2
MAUREY
SHEAVE
8350K
1
8450K
/2
8350
8450K
SHEAVE
BORE
5/8* 5/8* 7/8* 7/8*
SAD
MODEL
BELT
B77 B77 B77 B77
MODEL
BELT
B83 B83 B83 B83
12
303 414 303 414
313 424 313 424
BLOWER RPM/MOTOR SHEAVE 1/2 TURN DOWN
11
10
333
323
445
434
333
323
445
434
343 455 343 455
79
353 465 353 465
6
364 475 364 475
8
5
374 485 374 485
4
384 495 384 495
SAS
*When selecting 1 H.P. motor, be sure to select Pulley-Belt Kit with same pulley bore as shaft size of motor selected.
SIZING TABLES
3/4 H.P. MOTOR / CFM-SP*
OUTDOOR DRY BULB
TEMP.
LAT
85
GPH
LAT
95
GPH
LAT
105
GPH
LAT
115
GPH
5435 / 0 75
77 79
10 81 15 83 21
4118 / .5 2197 / 1.0
OUTDOOR WET-BULB
75
55
65
77
61
69
5
4
15
10
79
63
71
8
21
15
80
73
12
21
82
75
16
26
75
55
65
55
65
76
59
67
60
69
2
5
12
8
77
60
69
62
70
5
7
16
12
79
70
72
7
9
16
80
71
74
9
12
21
* Static Pressure (inches of water). GPH = Water consumption at design conditions but does not include bleed-off amount.
with different water sources, but an amount equal to 10% of water consumption at any design condition is considered sufficient for average water.
LAT = Cooler Discharge Temperature.
VOLTS
1
115/208-230
1
208-230/460
VOLTS
31
394 506 394 506
115 230
2
404 516 404 516
PHASE
1 3
AMPS
1.0
0.58
414 526 414 526
1 H.P. MOTOR / CFM-SP*
4856 / .5 3092 / 1.0
OUTDOOR WET-BULB
75
55
65
77
62
69
6
5
17
11
79
64
72
9
22
17
81
74
14
22
83
76
19
28
75
55
65
77
61
69
3
14
9
78
63
71
6
19
14
80
73
9
19
81
75
13
23
7 9
– – – –
5983 / 0
75 77
79
11 82 17 84 22
MOTOR
AMPS*
20/11-10
6.6-6/3
SHAFT
DIA.
5/8 7/8
WATTS
73 77
CHAMPION-SAD
PULLEY-BELT
KIT NO.
3DI-90
3DI-95 3DI-100 3DI-105
1-1/2 H.P. MOTOR / CFM-SP*
6848 / 0
OUTDOOR WET-BULB
75
55
65
77
60
68
9
6
80
61
70
13
13
9
82
71
19
13
84
73
25
16
75
55
65
77
62
70
6
19
13
79
64
72
11
25
19
81
74
17
25
84
77
22
32
Amount of bleed-off will vary
MOTOR
WGT(LB)
MOTOR
PART NO.
4140110459-1
110463-9
GPM (5 FT. HEAD)
4.6
4.6
CHAMPION-SAS
PULLEY-BELT
KIT NO.
3DI-110 3DI-115 3DI-120 3DI-125
5942 / .5 4639 / 1.0
75
55
65
55
65
77
61
69
61
69
6
4
13
9
17
11
79
63
71
64
71
9
18
13
22
17
81
73
74
13
18
22
83
75
76
18
22
28
S
MM
P
F
P
D
AU OUTLET
G
EEA
D
TOPVIEW
Q
X
C
J
G
Q
N
AS OUTLET
AD OUTLET
A
W
Y
R
H
C
J
N
AD OUTLET
B
U
D
BLOWER
WEIV EDISWEIV TNORF
SECTION
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
AS/AD 100B AS/AD 10012B AS/AD 150B AS/AD 15012B AS/AD/AU 20012B
WET MODULE NUMBER
100W
10012W
150W
15012W 20012W
CABINET
H
44 44 54 54
1
59
/4
85 93
105
DUCT
W
82 90
1
/4
1
/4
1
/4
3
21
/4
45
3
21
/4
45
7
1
26
/8
/4
48
7
1
/8
26
48
/4
3
1
31
60
/4
/4
OPENING
A
D
C
(AS)
B
3
13
21
/4
3
13
21
/4
7
16
26
/8
7
16
/8
26
3
18
31
/4
19
/32
19
/32
13
/16
13
/16
11
/16
DUCT
LOCATION
U
(AD)
P
(AU)
11
N/A
21
/32
11
N/A
21
/32
5
N/A
19
/32
5
N/A
19
/32
1
24
25
/4
G
1
12
1
16
1
12
1
16
1
16
WET
MODULE
/2
18
/2
22
/2
18
/2
22
/8
22
DRAIN
LOCATION
F
E
1
5
/2
22
11
/8
1
5
22
11 10 10
29
14
/32
/2
/8
1
11
24
/8
/16
1
11
24
/8
/16
1
1
30
/8
/4
J
1
/2
1
/2
1
/2
1
/2
1
/2
MEDIA
DIMENSION
Y
X
3
5
36
44
/4
/8
3
5
44
36
/4
/8
3
48
46
/8
3
48
46
/8
5
/8
51
60
WATER
SERVICE
M
L
7
14
5
/8
7
5
18
/8
7
5
14
/8
7
5
18
/8
7
/8
5
18
ELECTRIC
SERVICE
S
5
7
/8
39
/8
5
7
/8
43
/8
5
1
/8
41
/2
5
1
/8
45
/2
5
5
/8
51
/8
5 5 5 5 5
LOCATIONS
N
T
5
23
/32
5
27
/32
5
23
/32
5
27
/32
5
27
/32
SKID
1
/4
1
/4
1
/4
1
/4
1
/4
Q
3
/4
4
3
4
/4
3
4
/4
3
4
/4
3
4
/4
* All measurements in inches.
SPECIFICATIONS PERFORMANCE
AD
MAX
B.H.P.
1
1
2 3 5
/2
OPER.
WGT.
801 805 818 834
MODEL
BELT
A76 B77 B80 B81
AS
MODEL
BELT
A82 B83 B86 B87
CFM
7431 8178 9362
11099
0"
RPM
382 421 482 571
Certified Air Delivery At .1" Increments Of External Static Pressure
CFM
7255 8024 9235
11001
0.1"
390 427 487 575
0.2"
CFM
7052 7842 9075
10868
RPMRPM
400 436 494 581
CFM
6835 7649 8914
10736
0.3" RPM
411 446 502 587
CFM
6611 7450 8744
10598
0.4" RPM
424 457 511 594
Performance shown is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include drive losses. Models AS/AD 10012 include the affects of a 12 inch thick evaporative media on the inlet.
When the Cooler Model No, Motor H.P.
, & Blower Speed are
determined from the SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECT
(Inches Static Pressure Water Gauge)
CFM
6376 7244 8572
10457
0.5" RPM
437 468 520 601
CFM
6131 7030 8393
10313
0.6" RPM
450 480 531 609
CFM
5877 6809 8209
10165
0.7" RPM
464 492 541 617
CFM
5610 6580 8024
10016
0.8" RPM
477 504 551 625
ION table below.
CFM
5327 6343 7827 9862
0.9" RPM
492 517 562 634
1.0"
CFM
5031 6095 7631 9709
R
42 42 52 52
1
57
RPM
507 529 672 643
/4
MOTOR SPECIFICATIONS
H.P.
1 1
1
/2
1
/2
2 2 3 5
MOTORS
SPEED
1 1 1 1 1 1
VOLTS
115/208-230 208-230/460 115/208-230 208-230/460 208-230/460 208-230/460
PHASE
1 3 1 3 3 3
MOTOR
AMPS*
20/11-10
6.6-6/3
24/13.2-12
7.5-6.8/3.4
10.6-9.6/4.8
16.7-15.2/7.6
SHAFT
DIA.
5/8 7/8 7/8 7/8
1
/8
1
1
/8
1
MOTOR
WGT(LB)
41 40 49 44 83 87
MOTOR
PART NO.
110459-1 110463-9
110460-1 110464-9 110465-9 110466-9
PUMP PART NO.
110467 110468
Pumps - 2 Required.
VOLTS
115 230
AMPS
1.0
0.58
WATTS
73 77
BLOWER
*Amperage shown is from National Electrical Code. Use amperage shown on motor nameplate to determine motor protector.
SHEAVE SELECTION
MOTOR
H.P.
1-1/2 1-1/2
2 3 5
MAUREY
SHEAVE
D8450 D8450 D8450 D8550 D8600
SHEAVE
BORE
7/8
7/8 1 1/8 1 1/8
AD
MODEL
BELT
A76 B77 B80 B81
MODEL
BELT
A82A765/8 A82
B83 B86 B87
11
12
391 401 391
401
414
424
482
492
549
559
BLOWER RPM/MOTOR SHEAVE 1/2 TURN DOWN
10
412 434 502 569
422 445 513 580
8
433 443422412 433 455 523 590
79
443 465 533 600
5
6
4
454 464 475 485 496 506 3DI-11 454
464 485 553 620
475 495 563 630
475 543 610
31
2
485
496
506
516
574
584
641
651
CHAMPION-AD
PULLEY-BELT
506 526 594 661
KIT NO.
3DI-10 3DI-15 3DI-20 3DI-25
AS
SIZING TABLES
OUTDOOR
DRY BULB
TEMP.
LAT
85
GPH
LAT
95
GPH
LAT
105
GPH
LAT
115
GPH
1-1/2 H.P . MOTOR / CFM-SP*
6376
/ .5
7431
/ 0
OUTDOOR WET-BULB
75 76
77 17 78 25 79 34
75
65
55
76
67
58
8
17
25
77
68
59
14
25
34
78
69
21
34
79
70
28
42
5031 75
65
55
65
76
67
58
7
14 68 21 69 28 70 35
67
6
21
11
77
59
67
11
28
17
77
68
17
22
78
69
22
28
2 H.P. MOTOR / CFM-SP*
/ 1.0
8178
/ 0
OUTDOOR WET-BULB OUTDOOR WET-BULB
55
75
65
55
57
76
67 17 58 22
58
9
18
28
77
68
59
18
28
37
78
69
– – –
28
37
79
70
37
46
7244 75
76
8 77 16 78 24 79 32
65 67
16 68 24 69 32 70 40
/ .5
3 H.P. MOTOR / CFM-SP*
6095
/ 1.0
9362
75
55
76
58
7
24
77
59
13
32
78
20
79
27
75
65
55
76
67
58
11
13
20
77
68
59
21
20
27
78
69
32
27
79
69
42
33
8572
/ .5
7631
/ 0
75
65
55
65
76
67
58
67
9
21
32
19
77
68
59
68
19
32
42
28
78
69
69
28
42
38
79
70
70
38
53
47
/ 1.0
75
55
65
76
58
67
8
28
17
77
59
68
17
38
25
78
69
25
33
79
70
33
42
5 H.P. MOTOR / CFM-SP*
11099 75
55
76
58
12
25
77
59
25
32
78
37
80
49
10457
/ 0
OUTDOOR WET-BULB
75
65
55
76
67
58
11
25
37
77
68
60
23
37
49
78
70
34
49
79
71
46
62
/ .5
9709
/ 1.0
75
65
55
65
55
76
67
58
67
58
11
23
34
21
32
77
68
59
68
59
21
34
46
32
42
78
69
69
32
46
42
79
71
70
42
57
53
* Static Pressure (inches of water). GPH = Water consumption at design conditions but does not include bleed-off amount. Amount of bleed-off will vary with different water sources, but
an amount equal to 10% of water consumption at any design condition is considered sufficient for average water. LAT = Cooler Discharge Temperature.
GPM (5 FT. HEAD)
4.6
4.6
CHAMPION-AS
PULLEY-BELT
KIT NO.
3DI-31 3DI-30 3DI-35 3DI-40 3DI-45
J
G
S
J
Q
F
E
D
A
SAS
OUTLET
T
R
X
C
E
Q
D
W
N
A
N
D
TOPVIEW
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
SAS/SAD 100B SAS/SAD 10012B SAS/SAD 150B SAS/SAD 15012B
WET MODULE NUMBER
100W
10012W
150W
15012W
CABINET
H
W
44
63 67
44
66
54
70
54
3
/8
3
/8
5
/8
5
/8
* All measurements in inches.
SPECIFICATIONS
OPER.
WGT.
527 530 545
SAD
MODEL
BELT
B77 B77 B77
MAX
B.H.P.
3/4
1
1
1
/2
Performance shown is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include drive losses.
When the Cooler Model No, Motor H.P.
PERFORMANCE
SAS
MODEL
BELT
CFM
B83
5371
B83 B83
6767
0"
RPM
362 359
5911
457
& Blower Speed are determined from the SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECTION table b
D
45
45 48 48
CFM
5064 5627 6513
1
/4
1
/4
DUCT
OPENING
B
A
3
21
21
/4
3
21
21
/4
7
26
26
/8
7
26
26
/8
C
(SAS)
3
13
/4
3
13
/4
7
16
/8
7
16
/8
19
/32
19
/32
13
/16
13
/16
DUCT
LOCATION
U
(SAD)
P
11
21
/32
11
21
/32
5
19
/32
5
19
/32
(SAD)
29
1
/32
29
1
/32
7
2
/32
7
/32
2
E
11 11
11
10
11
10
LOCATION
5
22
/8
5
22
/8
24
/16
24
/16
DRAIN
F
1
12
/2
1
16
/2
1
12
/8
1
16
/8
G
1
/2
1
/2
1
/2
1
/2
MODULE
Certified Air Delivery At .1" Increments Of External Static Pressure (Inches Static Pressure Water Gauge)
CFM
4536 5142 6076
0.3"
RPM
397 431 484
CFM
4269 4907 5872
0.4"
0.5"
RPM
410 441 494
CFM
3985 4663 5666
RPM
423 453 503
CFM
3667 4399 5456
Models SAS/SAD 10012 include the affects of a 12 inch thick evaporative media on the inlet.
0.1"
374 410 466
CFM
4794 5375 6286
0.2"
RPMRPM
386 420 475
WET
J
1
18
/2
1
22
/2
1
18
/2
1
/2
22
0.6"
RPM
439 465 513
H
C
SAD OUTLETSAD OUTLET
P
MEDIA
DIMENSION
Y
X
3
5
36
44
/4
/8
3
5
44
36
/4
/8
3
48
46
/8
3
48
46
/8
0.7"
RPM
CFM
3318
458
4115
479
5238
523
B
WATER
SERVICE
M
L
7
/8
5
14
7
5
/8
18
7
5
/8
14
7
5
/8
18
0.8"
RPM
CFM
2952 3809 5008
U
W
ELECTRIC
SERVICE
S
1
5
21
/8
1
5
21
/8
1
5
23
/8
1
5
23
/8
CFM
481
2591
495
3480
534
4755
/2 /2 /8 /8
T
5
5
5
5
5
5
5
5
0.9"
WEIV EDISWEIV TNORF
/32 /32 /32 /32
RPM
507 514 546
M
SKID
LOCATIONS
Q
N
3
3
4
/4
4
/4
3
3
4
/4
4
/4
3
3
4
/4
4
/4
3
3
4
/4
4
/4
1.0"
RPM
CFM
2261
534
3145
536
4497
560
elow.
Y
R
42 42 52 52
MOTOR SPECIFICATIONS
H.P.
3/4 3/4 3/4
1 1 1
MOTORS
SPEED
1 2 1 1 2 1
VOLTS
115/208-230
230
208-230/460
115/230
230
208-230/460
PHASE
1 1 3 1 1 3
MOTOR
AMPS*
13.8/7.6-6.9
6.9
3.5-3.2/1.6 16/8
8
4.6-4.2/2.1
BLOWER
AD 10012
*Amperage shown is from National Electrical Code.
Use amperage shown on motor nameplate to determine motor protector.
SHEAVE SELECTION
SAS
MOTOR
H.P.
3
/4
, 1
1
3
1
, 1,
/4
1
1
/2
1, 1
MAUREY
SHEAVE
8350K 8450K
/2
8350
8450K
SHEAVE
BORE
5/8* 5/8* 7/8* 7/8*
SAD
MODEL
BELT
B77 B77 B77 B77
MODEL
BELT
B83 B83 B83 B83
303 414 303 414
*When selecting 1 H.P. motor, be sure to select Pulley-Belt Kit with same pulley bore as shaft size of motor selected.
12
SHAFT
DIA.
5/8 5/8 5/8 5/8 5/8 7/8
11
313 424 313 424
MOTOR
WGT(LB)
24 29 20 28 29 34
MOTOR
PART NO.
110455 110456 110461 110457 110458
110462-9
BLOWER
MOTORS
SPEED
H.P.
1
/2
1 1
1
1
/2
1
PUMP PART NO.
110467 110468
VOLTS
115/208-230 208-230/460
VOLTS
115 230
PHASE
1 3
AMPS
1.0
0.58
MOTOR
AMPS*
20/11-10
6.6-6/3
SHAFT
DIA.
WATTS
73 77
MOTOR
WGT(LB)
5/8 7/8
GPM (5 FT. HEAD)
41 40
MOTOR
PART NO.
110459-1 110463-9
4.6
4.6
Pumps - 1 Required.
BLOWER RPM/MOTOR SHEAVE 1/2 TURN DOWN
10
323 434 323 434
333 445 333 445
8
343 455 343 455
79
353 465 353 465
6
364 475 364 475
5
374 485 374 485
4
384 495 384 495
CHAMPION-SAD
PULLEY-BELT
31
2
394
404 516 404 516
414 526 414 526
506 394 506
KIT NO.
3DI-90
3DI-95 3DI-100 3DI-105
CHAMPION-SAS
PULLEY-BELT
KIT NO.
3DI-110 3DI-115 3DI-120 3DI-125
SIZING TABLES
OUTDOOR DRY BULB
TEMP.
85
95 105 115
* Static Pressure (inches of water). GPH = Water consumption at design conditions but does not include bleed-off amount. Amount of bleed-off will
vary with different water sources, but
3/4 H.P. MOTOR / CFM-SP*
4007 / .5 2120 / 1.0
OUTDOOR WET-BULB
75
65
55
76
67
58
6
6
12
17
77
68
59
12
17
23
78
69
12
23
79
70
16
29
75
65
55
65
76
67
58
66
2
12
13
76
68
59
67
5
17
23
77
69
68
7
16
78
70
68
9
20
11
LAT
GPH
LAT
GPH
LAT
GPH
LAT
GPH
5377 / 0
75 76
77 12 78 17 79 23
an amount equal to 10% of water consumption at any design condition is considered sufficient for average water.
1 H.P. MOTOR / CFM-SP*
5917 / 0
75
65
76
67
7
6
13
77
68
9
13
19
78
69
19
25
79
71
25
32
OUTDOOR WET-BULB
55 58
19 59 25
– – – –
55 57
5
58
7 9
4712 / .5 2970 / 1.0 75
76 77
10 78 15 79 20
75
65
55
65
76
67
58
67
6
5
13
19
10
77
68
59
68
7
15
20
10
78
69
68
10
20
13
78
70
69
13
25
16
1-1/2 H.P. MOTOR / CFM-SP*
5761 / .5 4447 / 1.0
OUTDOOR WET-BULB
75
65
55
76
67
59
7
6
14
22
77
69
60
12
22
29
78
70
18
29
80
71
25
36
65
55
67
58
12
18
68
60
18
25 70 25 71 31
55 58
16 58 13
– – – –
6761 / 0 75
76 77
14 79 22 80 29
75 76
5 77 10 78
15
79
19
LAT = Cooler Discharge Temperature.
55
65
58
67
15
10
59
68
19
15
69
19 70
24
S
MM
P
F
P
D
AU OUTLET
Q
AS OUTLET
X
C
J
G
EEA
D
G
Q
N
AD OUTLET
A W
J
N
TOPVIEW
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
AS/AD 100B AS/AD 10012B AS/AD 150B AS/AD 15012B AS/AD/AU 20012B
WET MODULE NUMBER
100W
10012W
150W 15012W 20012W
CABINET
H
44 44 54 54
1
/4
59
85 93
105
W
82 90
1
/4
1
/4 1
/4
* All measurements in inches.
SPECIFICATIONS
OPER.
WGT.
854 867 883 919
AD
MODEL
BELT
B90 B92 B93 B95
MAX
B.H.P.
2 3 5
1
/2
7
Performance shown is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include drive losses.
When the Cooler Model No, Motor H.P.,
PERFORMANCE
AS
MODEL
BELT
B96 B100 B100 B101
CFM
11405 13057 15480 17719
0"
RPM
317 363 430 492
10892 12600 15082 17364
& Blower Speed are determined from the SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECTION table below.
D
45
45 48 48 60
1
/4
1
/4
1
/4
DUCT
OPENING
B
A
3
21
21
/4
3
21
21
/4
7
26
26
/8
7
26
26
/8
3
31
31
/4
C
(AS)
19
3
13
/4
19
3
13
/4
13
7
16
/8
13
7
16
/8
11
3
18
/4
U
/32
21
/32
21
/16
19
/16
19
/16
DUCT
LOCATION
(AD)
P
(AU)
11
N/A
/32
11
N/A
/32
5
N/A
/32
5
N/A
/32
29
1
24
25
/4
G
1
12
1
16
1
12
1
16
1
16
WET
MODULE
/2
18
/2
22
/2
18
/2
22
/8
22
J
DRAIN
LOCATION
F
E
1
5
22
11
11 10 10
14
/32
/2
/8
1
5
22
/2
/8
1
11
24
/8
/16
1
11
24
/8
/16
1
1
30
/8
/4
Certified Air Delivery At .1" Increments Of External Static Pressure (Inches Static Pressure Water Gauge)
CFM
0.1"
328 373 439 500
CFM
10463 12204 14735 17050
0.2"
RPMRPM
338 381 446 507
CFM
10064 11844 14410 16756
0.3"
RPM
347 390 454 513
0.4"
CFM
9671 11497 14106 16479
RPM
357 398 461 520
CFM
9276
11153 13810 16214
0.5"
RPM
367 406 468 526
CFM
8874 10815 13520 15947
0.6"
RPM
378 415 475 532
Models AS/AD 150 include the affects of an 8 inch thick evaporative media on the inlet.
DIMENSION
1
44
/2
1
44
/2
1
/2
1
/2
1
/2
CFM
8456 10467 13234 15694
MEDIA
X
3
/4
3
/4
48 48 60
0.7"
RPM
Y
36 36 46 46
51
390 424 482 538
Y
5 5 3 3 5
R
/8 /8 /8 /8 /8
5 5 5 5 5
CFM
8006 10113 12948 15440
H
C
WATER
SERVICE
M
L
7
14
/8
7
18
/8
7
14
/8
7
18
/8
7
18
/8
0.8"
RPM
403 434 489 544
AD OUTLET
B
ELECTRIC
SERVICE
S
5
7
/8
39
/8
5
7
/8
43
/8
5
1
/8
41
/2
5
1
/8
45
/2
5
5
/8
51
/8
CFM
7530
9741 12659 15188
5 5 5 5 5
0.9"
D
T
5
/32
5
/32
5
/32
5
/32
5
/32
RPM
418 444 496 550
U
BLOWER
WEIV EDISWEIV TNORF
SECTION
SKID
LOCATIONS
Q
N
3
1
4
/4
23
/4
3
1
4
/4
27
/4
3
1
4
/4
23
/4
3
1
4
/4
27
/4
3
1
4
/4
27
/4
1.0"
CFM
7017
9361 12361 14937
R
42 42 52 52
57
/4
RPM
436 456 504 557
1
MOTOR SPECIFICATIONS
H.P.
7
2 2 3 5
1
/2
MOTORS
SPEED
1 1 1 1 1
VOLTS
115/208-230 208-230/460 208-230/460 208-230/460 208-230/460
PHASE
1 3 3 3 3
MOTOR
AMPS*
24/13.2-12
7.5-6.8/3.4
10.6-9.6/4.8
16.7-15.2/7.6
24.2-22/11
SHAFT
DIA.
7/8 7/8
1
1
/8
1
1
/8
3
1
/8
MOTOR
WGT(LB)
49 44 83 87
121
MOTOR
PART NO.
110460-1
110464-9 110465-9 110466-9 110470-9
PUMP PART NO.
110467 110468
Pumps - 2 Required.
VOLTS
115 230
AMPS
1.0
0.58
WATTS
BLOWER
*Amperage shown is from National Electrical Code. Use amperage shown on motor nameplate to determine motor protector.
SHEAVE SELECTION
MOTOR
H.P.
2 2 3 5
7-1/2
MAUREY
SHEAVE
D8400 D8450 D8450 D8550 D8600
SHEAVE
BORE
7/8
7/8 1 1/8 1 1/8 1 3/8
AD
MODEL
BELT
B90 B90 B92 B93 B95
MODEL
BELT
B96
B96 B100 B100 B101
12
291 347 347 403 459
BLOWER RPM/MOTOR SHEAVE 1/2 TURN DOWN
11
299 356 356 412 468
10
308 364 364 420 476
316 373 373 429 485
8
325 381 381 437 493
79
333 390 390 446 502
6
342 398 398 454 510
5
350 407 407 463 519
31
367 424 424 480 536
2
376 432 432 488 544
4
359 415 415 471 527
CHAMPION-AD
384 441 441 497 553
PULLEY-BELT
KIT NO.
3DI-50 3DI-52 3DI-56 3DI-60 3DI-65
AS
SIZING TABLES
OUTDOOR DRY BULB
TEMP.
85
95 105 115
* Static Pressure (inches of water). GPH = Water consumption at design conditions but does not include bleed-off amount. Amount of bleed-off will vary with different water sources, but
11902
75 77
LAT
12
GPH
79
LAT
23
GPH
81
LAT
35
GPH
83
LAT
47
GPH
an amount equal to 10% of water consumption at any design condition is considered sufficient for average water. LAT = Cooler Discharge Temperature.
9697 / .5 7347 / 1.0
/ 0
OUTDOOR WET-BULB
75
65
55
69
61
23
35
71
63
35
47 73 47 74 59
55
65
77
60
68
10
19
29
78
70
62
19
29
39
80
72
29
39
82
73
39
49
75
65
77
68
7
15
78
69
15
22
79
71
22
29
81
72
29
37
2 H.P. MOTOR / CFM-SP*
3 H.P. MOTOR / CFM-SP*
11669 / .5 9775 / 1.0
OUTDOOR WET-BULB
75
65
55
77
69
61
11
26
39
79
71
63
23
39
52
81
73
34
52
82
75
46
66
55 59
22 61 29
– – – –
13626 / 0 75
77 13 79 26 81 39 83 52
5 H.P. MOTOR / CFM-SP*
16154 / 0
75
65
55
77
69
61
10
23
34
79
71
62
20
34
46
80
72
29
46
82
74
39
57
75
65
55
77
60
69
15
20
29
79
70
62
30
29
39
82
72
46
39
84
74
61
49
14468 / .5 12915 / 1.0
OUTDOOR WET-BULB
75
65
55
65
55
77
69
62
69
61
14
30
46
28
42
79
72
64
71
63
28
46
61
42
55
81
74
73
42
61
55
83
76
75
55
76
69
75 77
13 79 25 81 38 83 50
7-1/2 H.P . MOT OR / CFM-SP*
18493 / 0 75
65
55
77
69
61
17
25
38
80
71
63
34
38
50
82
73
51
50
84
75
68
63
16996 / .5 15626 / 1.0
OUTDOOR WET-BULB
55
65
62
70 34
51 64
72 51
68
74
68
77
85
75 77
16 80 32 82 48 84 64
75
65
65
55
70
62
32
48
72
64
48
64 74 64 76 79
55
77
69
62
15
30
44
79
72
64
30
44
59
82
74
– – – –
44
59
84
76
59
74
GPM (5 FT. HEAD)
73 77
4.6
4.6
D 150
CHAMPION-AS
PULLEY-BELT
KIT NO.
3DI-70 3DI-72 3DI-75 3DI-80 3DI-86
J
G
S
J
Q
F
E
D
A
SAS
OUTLET
T
R
H
X
C
C
E
Q
D
W
N
A
N
D
TOPVIEW
SAD OUTLETSAD OUTLET
P
B
U
M
W
WEIV EDISWEIV TNORF
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
SAS/SAD 100B SAS/SAD 10012B SAS/SAD 150B SAS/SAD 15012B
WET MODULE NUMBER
100W
10012W
150W
15012W
CABINET
H
W
44
63 67
44 54
66 70
54
3
/8
3
/8
5
/8
5
/8
D
45
45 48 48
1
/4
1
/4
DUCT
OPENING
B
A
3
21
21
/4
3
21
21
/4
7
26
26
/8
7
26
26
/8
DUCT
LOCATION
U
(SAD)
C
(SAS)
19
3
13
/32
/4
19
3
13
/32
/4
13
7
16
/16
/8
13
7
16
/16
/8
P
(SAD)
29
11
1
21 21
19 19
/32
/32
29
11
1
/32
/32
7
5
2
/32
/32
7
5
2
/32
/32
E
11
11 10 10
5
/8
5
/8
11
/16
11
/16
DRAIN
LOCATION
F
1
22
/2
1
22
/2
1
24
/8
1
24
/8
G
1
12
1
16
1
12
1
16
WET
MODULE
/2
18
/2
22
/2
18
/2
22
J
1
/2
1
/2
1
/2
1
/2
MEDIA
DIMENSION
Y
X
3
5
36
44
/4
/8
3
5
44
36
/4
/8
3
48
46
/8
3
48
46
/8
WATER
SERVICE
M
L
7
5
/8
14
7
5
/8
18
7
5
/8
14
7
5
/8
18
ELECTRIC
SERVICE
S
1
5
21
/8
1
5
21
/8
1
5
23
/8
1
5
23
/8
5
/2
5
/2
5
/8
5
/8
LOCATIONS
N
T
5
4
/32
5
4
/32
5
4
/32
5
4
/32
3
/4
3
/4
3
/4
3
/4
SKID
* All measurements in inches.
SPECIFICATIONS PERFORMANCE
SAD
MAX
B.H.P.
3/4
1
1 1/2
2 3
OPER.
WGT.
584 593 608 612 624
MODEL
BELT
B90 B90 B90 B90 B92
SAS
MODEL
BELT
B96 B96 B96 B96
B100
CFM
7072 7783 8910
N/A N/A
0"
RPM
275 302
346 N/A N/A
CFM
6622 7372 8548 9476
Certified Air Delivery At .1" Increments Of External Static Pressure
CFM
5769 6602 7870 8855
N/A
0.3" RPM
308 333 374 406
N/A
CFM
5298 6199 7533 8555 N/A
0.4" RPM
321 343 382 414 N/A
N/A
0.1"
287 314 356 390
N/A
CFM
6203 6987 8205 9159
N/A
0.2" RPMRPM
298 324 365 399
N/A
(Inches Static Pressure Water Gauge)
CFM
4777 5764 7182 8244
N/A
0.5" RPM
336 355 391 421
N/A
CFM
4201 5285 6812 7924
N/A
0.6" RPM
355 369 401 430 N/A
CFM
3607 4764 6416 7592 9315
0.7" RPM
378 386 412 438 486
CFM
3041 4231 5993 7236 9032
0.8" RPM
402 406 424 448 493
CFM
2522 3699 5537 6866 8741
0.9" RPM
424 427 439 459 500
CFM
2040 3199 5067 6470 8436
Performance shown is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include drive losses. Models SAS/SAD 150 include the affects of an 8 inch thick evaporative media on the inlet.
When the Cooler Model No, Motor H.P.
, & Blower Speed are determined from the SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECTION table b
elow.
MOTOR SPECIFICATIONS
H.P.
3/4 3/4 3/4
1 1
1 1 1
1
/2
1
/2
MOTORS
SPEED
1 2 1 1 2 1 1 1
VOLTS
115/208-230
230
208-230/460
115/230
230
208-230/460
115/208-230
208-230/460
PHASE
1 1 3 1 1 3 1 3
MOTOR
AMPS*
13.8/7.6-6.9
6.9
3.5-3.2/1.6 16/8
8
4.6-4.2/2.1
20/11-10
6.6-6/3
SHAFT
DIA.
5/8 5/8 5/8 5/8 5/8 7/8 5/8 7/8
MOTOR
WGT(LB)
24 29 20 28 29 34 41 40
MOTOR
PART NO.
110455 110456 110461 110457 110458
110462-9
110459-1
110463-9
BLOWER
*Amperage shown is from National Electrical Code. Use amperage shown on motor nameplate to determine motor protector.
BLOWER
Pumps - 1 Required.
MOTORS
SPEED
H.P.
2
1
2
1
3
1
PUMP PART NO.
110467 110468
VOLTS
115/208-230 208-230/460 208-230/460
VOLTS
115 230
PHASE
1 3 3
AMPS
1.0
0.58
MOTOR
AMPS*
24/13.2-12
7.5-6.8/3.4
10.6-9.6/4.8
WATTS
SHAFT
DIA.
7/8 7/8
1
1
/8
73 77
MOTOR
WGT(LB)
49 44 83
GPM (5 FT. HEAD)
4.6
4.6
Q
3
/4
4
3
4
/4
3
4
/4
3
4
/4
1.0"
RPM
MOTOR
PART NO.
110460-1 110464-9 110465-9
Y
R
42 42 52 52
443 448 456 471 509
SHEAVE SELECTION
MOTOR
H.P.
3
, 1
/4
1
3
1
/4
,1,
1
1
, 2
/2
1, 1
1
/2
, 2
1
3
MAUREY
SHEAVE
8350K 8450K
/2
8350
8450K
8550 8550
SHEAVE
BORE
5/8* 5/8* 7/8* 7/8*
7/8
1 1/8
MODEL
BELT
B90 B90 B90 B90 B90 B92
SAS
MODEL
BELT
B96 B96 B96 B96 B96
B100
12
253 347 253 347 403 403
BLOWER RPM/MOTOR SHEAVE 1/2 TURN DOWN
11
261 356 261 356 412 412
10
269 364 269 364 420 420
278 373 278 373 429 429
8
287 381 287 381 437 437
79
296 390 296 390 446 446
6
304 398 304 398 454 454
5
313 407 313 407 463 463
31
330 424 330 424 480 480
2
338 432 338 432 488 488
4
321 415 321 415 471 471
CHAMPION-SAD
PULLEY-BELT
347 441 347 441 497 497
SAD
*When selecting 1 H.P. motor, be sure to select Pulley-Belt Kit with same pulley bore as shaft size of motor selected.
SIZING TABLES
OUTDOOR DRY BULB
TEMP.
85
95 105 115
3/4 H.P. MOTOR / CFM-SP*
4777
/ .5
7072
/ 0
OUTDOOR WET-BULB
75 77
LAT
GPH
79
LAT
14
GPH
81
LAT
21
GPH
83
LAT
28
GPH
* Static Pressure (inches of water). GPH = Water consumption at design conditions but does not include bleed-off amount. Amount of bleed-off will vary with different water sources, but
75
65
55
77
69
61
7
14
21
78
71
63
21
28
80
73
14
28
82
75
18
35
an amount equal to 10% of water consumption at any design condition is considered sufficient for average water. LAT = Cooler Discharge Temperature.
2040 /1.0
75
65 68
5
70
9
14 72 18 73 23
65
55
76
68
60
2
9
14
78
69
62
5
18
79
71
7
81
72
9
11
1 H.P. MOTOR / CFM-SP*
7783
/ 0
OUTDOOR WET-BULB OUTDOOR WET-BULB
55
75
65
55
59
77
69
5
7
61
7
9 –
9
– – –
62
8
15
23
79
72
64
15
23
30
82
74
23
30
84
76
30
38
5764
75 77
6 79 11 81 17 82 22
65 69
11 71 17 72 22 74 28
/ .5
55 61
17 62 22
– – – –
3199 /1.0
75 76
3
78
7 79 10 81 14
1-1/2 H.P. MOTOR / CFM-SP*
8910
65
55
75
68
59
78
7
10
69
61
80
10
14
17
71
82
14
25
72
84
17
34
7182
/ 0
75
65
55
77
70
62
8
17
25
79
72
64
14
25
34
81
74
20
34
83
77
27
42
/ .5
5067
75
65
55
65
77
69
61
7
14 71 20 73 27 75 34
68
5
20
79
63
70
9
27
14
80
72
14
19
82
73
19
23
2 H.P. MOTOR / CFM-SP*
9476 /.1
/ 1.0
9
75
55
77
60
9
14
80
62
17
19
82
26
84
34
OUTDOOR WET-BULB
65
55
70
62
17
26
72
64
26
34
74
34
77
43
8244
75 77
8 80 15 82 23 84 31
65 70
15 72 23 74 31 76 39
/ .5
6470
/ 1.0
75
55
65
55
77
62
69
61
6
23
12
18
79
64
71
63
12
31
18
24
81
73
18
24
83
75
24
30
CHAMPION-SAS
KIT NO.
3DI-130 3DI-135 3DI-140 3DI-145 3DI-155 3DI-161
3 H.P. MOTOR / CFM-SP*
9315
OUTDOOR WET-BULB
75
– – – –
75
65
55
77
– – – – – – – –
9
80
17
82
26
84
34
PULLEY-BELT
KIT NO.
3DI-165 3DI-170 3DI-175 3DI-180 3DI-185 3DI-190
/ .7
8436
/ 1.0
75
65
55
65
77
70
62
70
8
17
26
15
80
72
64
72
15
26
34
23
82
74
74
23
34
31
84
77
76
31
43
39
55 62
23 64 31
– – – –
S
MM
P
F
P
D
AU OUTLET
G
EEA
D
TOPVIEW
Q
X
C
J
G
Q
N
AS OUTLET
AD OUTLET
A
W
Y
R
H
C
J
N
AD OUTLET
B
U
D
BLOWER
WEIV EDISWEIV TNORF
SECTION
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
AS/AD 100B AS/AD 10012B AS/AD 150B AS/AD 15012B AS/AD/AU 20012B
WET MODULE NUMBER
100W
10012W
150W
15012W 20012W
CABINET
H
44 44 54 54
1
59
/4
85 93
105
W
82 90
1
/4
1
/4 1
/4
D
45
45 48 48 60
1
/4
1
/4
1
/4
DUCT
OPENING
B
A
3
21
21
/4
3
21
21
/4
7
26
26
/8
7
/8
26
26
3
31
31
/4
DUCT
LOCATION
U
(AS)
19
/32
19
/32
13
/16
13
/16
11
/16
21 21
19 19
25
(AD)
11
/32
11
/32
5
/32
5
/32
1
/4
P
24
(AU) N/A N/A N/A N/A
29
/32
C
3
13
/4
3
13
/4
7
16
/8
7
16
/8
3
18
/4
E
11
11 10 10
14
5
/8
5
/8
11
/16
11
/16
1
/4
DRAIN
LOCATION
F
1
/2
22
1
22
/2
1
24
/8
1
24
/8
1
30
/8
G
1
12
1
16
1
12
1
16
1
16
WET
MODULE
/2
18
/2
22
/2
18
/2
22
/8
22
J
1
/2
1
/2
1
/2
1
/2
1
/2
MEDIA
DIMENSION
Y
X
3
5
36
44
/4
/8
3
5
44
36
/4
/8
3
48
46
/8
3
48
46
/8
5
/8
51
60
WATER
SERVICE
M
L
7
14
5
/8
7
5
18
/8
7
5
14
/8
7
5
18
/8
7
/8
5
18
ELECTRIC
SERVICE
S
5
7
/8
39
/8
5
7
/8
43
/8
5
1
/8
41
/2
5
1
/8
45
/2
5
5
/8
51
/8
5 5 5 5 5
LOCATIONS
N
T
5
23
/32
5
27
/32
5
23
/32
5
27
/32
5
27
/32
SKID
1
/4
1
/4
1
/4
1
/4
1
/4
Q
3
/4
4
3
4
/4
3
4
/4
3
4
/4
3
4
/4
* All measurements in inches.
SPECIFICATIONS PERFORMANCE
MAX
B.H.P.
2 3 5
7-1/2
OPER.
WGT.
967 980 996
1032
MODEL
BELT
B90 B92 B93 B95
AS
MODEL
BELT
B96 B100 B100 B101
CFM
11375 13020 15438 17672
0"
RPM
303 346 410 470
AD
Performance shown is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include drive losses. Models AS/AD 15012 include the affects of a 12 inch thick evaporative media on the inlet.
When the Cooler Model No, Motor H.P., & Blower Speed are
Certified Air Delivery At .1" Increments Of External Static Pressure (Inches Static Pressure Water Gauge)
CFM
10079 11865 14434 16777
0.3" RPM
0.1"
CFM
10905 12604 15084 17360
314 356 419 477
0.2"
CFM
10482 12225 14749 17060
RPMRPM
324 365 427 484
determined from the SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECTION table below.
335 375 435 491
0.4"
CFM
9678 11514 14133 16505
RPM
346 384 443 498
0.5"
CFM
9265 11165 13838 16242
RPM
356 393 450 505
CFM
8830 10807 13540 15983
0.6" RPM
368 403 458 512
CFM
8366 10440 13246 15724
0.7" RPM
380 413 466 519
CFM
7867 10058 12899 15463
0.8" RPM
394 423 474 526
CFM
7325
9651 12640 15207
0.9" RPM
409 433 482 532
1.0"
CFM
6753
9220 12328 14947
R
42 42 52 52
1
57
RPM
426 445 490 539
/4
MOTOR SPECIFICATIONS
H.P.
7
2 2 3 5
1
/2
MOTORS
SPEED
1 1 1 1 1
VOLTS
115/208-230 208-230/460 208-230/460 208-230/460 208-230/460
PHASE
1 3 3 3 3
MOTOR
AMPS*
24/13.2-12
7.5-6.8/3.4
10.6-9.6/4.8
16.7-15.2/7.6
24.2-22/11
SHAFT
DIA.
7/8 7/8
1
1
/8
1
/8
1
3
1
/8
MOTOR
WGT(LB)
49 44 83 87
121
MOTOR
PART NO.
110460-1 110464-9 110465-9 110466-9 110470-9
PUMP PART NO.
110467 110468
Pumps - 2 Required.
VOLTS
115 230
AMPS
1.0
0.58
BLOWER
*Amperage shown is from National Electrical Code. Use amperage shown on motor nameplate to determine motor protector.
SHEAVE SELECTION
MOTOR
H.P.
2 2 3 5
7-1/2
MAUREY
SHEAVE
D8400 D8450 D8450 D8550 D8600
SHEAVE
BORE
7/8
7/8 1 1/8 1 1/8 1 3/8
AD
MODEL
BELT
B90 B90 B92 B93 B95
AS
MODEL
BELT
B96
B96 B100 B100 B101
12
291 347 347 403 459
11
299 356 356 412 468
BLOWER RPM/MOTOR SHEAVE 1/2 TURN DOWN
10
308 364 364 420 476
316 373 373 429 485
325 381 381 437 493
79
8
333 390 390 446 502
6
342 398 398 454 510
5
350 407 407 463 519
4
359 415 415 471 527
31
2
367
376
424
432 432
424 480
488
536
544
CHAMPION-AD
384 441 441 497 553
PULLEY-BELT
KIT NO.
3DI-50 3DI-52 3DI-56 3DI-60 3DI-65
SIZING TABLES
OUTDOOR DRY BULB
TEMP.
LAT
85
GPH
LAT
95
GPH
LAT
105
GPH
LAT
115
GPH
2 H.P. MOTOR / CFM-SP*
11375 / 0 75
76 12 77 25 78 37 79 49
9265 / .5 6753 / 1.0
OUTDOOR WET-BULB
75
65
55
65
55
76
67
58
67
58
10
25
37
20
30
77
68
59
68
59
20
37
49
30
40
78
69
69
30
49
40
79
70
70
40
61
51
75 76
8 77 15 77
23
78
30
65 67
15 67 23 68 30 69 38
3 H.P. MOTOR / CFM-SP*
11165 / .5 9220 / 1.0
OUTDOOR WET-BULB OUTDOOR WET-BULB
75
65
55
76
67
58
12
28
42
77
68
59
24
42
56
78
69
36
56
79
70
48
70
55 57
23 58 30
– – – –
13020 / 0
75 76
14 77 28 78 42 79 56
5 H.P. MOTOR / CFM-SP*
15438 / 0
75
65
55
76
67
58
10
24
36
77
68
59
20
36
48
78
69
30
48
79
70
40
60
75
65
55
76
67
58
16
20
30
77
68
59
33
30
40
78
69
49
40
80
70
66
50
13838 / .5 12328 / 1.0 75
65
55
76
67
58
15
33
49
77
68
60
30
49
66
78
70
45
66
79
71
59
82
75
65
55
76
67
58
13
30
45
77
59
68
27
59
45
78
69
40
59
79
70
53
74
7-1/2 H.P . MOT OR / CFM-SP*
17672 / 0
OUTDOOR WET-BULB
75
65
65
55
67
58
27
40
68
59
40
53
69
53
70
67
55
76
67
59
17
33
50
77
69
60
33
50
67
79
70
50
67
80
71
67
83
16242 / .5 14947 / 1.0
75 76
17 77 33 79 52 80 69
75
65
55
65
55
76
67
59
67
58
16
35
52
32
48
77
69
60
68
60
32
52
69
48
64
78
70
70
48
69
64
80
71
71
64
87
80
– – – –
* Static Pressure (inches of water). GPH = Water consumption at design conditions but does not include bleed-off amount. Amount of bleed-off will vary with different water sources, but
an amount equal to 10% of water consumption at any design condition is considered sufficient for average water. LAT = Cooler Discharge Temperature.
WATTS
73 77
GPM (5 FT. HEAD)
4.6
4.6
CHAMPION-AS
PULLEY-BELT
KIT NO.
3DI-70 3DI-72 3DI-75 3DI-80 3DI-86
J
G
S
J
Q
F
E
D
A
SAS
OUTLET
T
R
H
X
C
C
E
Q
D
W
N
A
N
D
TOPVIEW
SAD OUTLETSAD OUTLET
P
B
U
W
WEIV EDISWEIV TNORF
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
SAS/SAD 100B SAS/SAD 10012B SAS/SAD 150B SAS/SAD 15012B
WET MODULE NUMBER
100W
10012W
150W
15012W
CABINET
H
44
63 67
44 54
66 70
54
W
3
/8
3
/8
5
/8
5
/8
D
45
45 48 48
1
/4
1
/4
DUCT
OPENING
B
A
3
21
21
/4
3
21
21
/4
7
26
26
/8
7
26
26
/8
DUCT
LOCATION
U
(SAS)
13 13 16 16
(SAD)
P
19
/32
19
/32
13
/16
13
/16
(SAD)
29
11
1
21 21
19 19
/32
/32
29
11
1
/32
/32
7
5
2
/32
/32
7
5
2
/32
/32
C
3
/4
3
/4
7
/8
7
/8
E
11
11 10 10
5
/8
5
/8
11
/16
11
/16
DRAIN
LOCATION
F
1
22
/2
1
22
/2
1
24
/8
1
24
/8
G
1
12
1
16
1
12
1
16
WET
MODULE
/2
18
/2
22
/2
18
/2
22
J
1
/2
1
/2
1
/2
1
/2
MEDIA
DIMENSION
Y
X
3
5
36
44
/4
/8
3
5
44
36
/4
/8
3
48
46
/8
3
48
46
/8
WATER
SERVICE
M
L
7
5
/8
14
7
5
/8
18
7
5
/8
14
7
5
/8
18
ELECTRIC
SERVICE
S
1
5
21
/8
1
5
21
/8
1
5
23
/8
1
5
23
/8
/2 /2 /8 /8
T
5
5
/32
5
5
/32
5
5
/32
5
5
/32
LOCATIONS
N
3
4
/4
3
4
/4
3
4
/4
3
4
/4
* All measurements in inches.
SPECIFICATIONS
MAX B.H.P.
3/4
1
1
/2
1
2 3
SAD
OPER.
MODEL
WGT.
BELT
B90
645
B90
649
B90
665
B90
669
B92
681
Performance shown is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include drive losses. Models SAS/SAD 15012 include the affects of a 12 inch thick evaporative media on the inlet. When the Cooler Model No, Motor H.P
PERFORMANCE
SAS
MODEL
BELT
CFM
B96 B96 B96 B96
B100
0"
RPM
6997
267
7702
294
8817
336
N/A
N/A
N/A
N/A
., & Blower Speed are determined
Certified Air Delivery At .1" Increments Of External Static Pressure (Inches Static Pressure Water Gauge)
CFM
6539 7286 8455 9375 N/A
0.1"
278 303 345 378 N/A
0.2" RPMRPM
CFM
6087
289
6876
314
8091
353
9044
386
N/A
N/A
from the SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECTION table below.
CFM
5603 6450 7734 8719
N/A
0.3" RPM
301 324 363 394 N/A
CFM
5051 5994 7359 8389
N/A
0.4" RPM
315 336 372 402 N/A
CFM
4415 5477 6961 8043
N/A
0.5" RPM
332 349 382 411 N/A
0.6"
CFM
3717 4893 6525 7683 9377
RPM
353 364 393 420 466
CFM
3058 4260 6050 7293 9070
0.7" RPM
376 383 405 430 474
CFM
2497 3637 5527 6869 8751
0.8" RPM
398 404 419 440 482
CFM
2013 3085 4976 6416 8407
0.9" RPM
419 425 435 452 490
M
SKID
Q
3
4
3
4
3
4
3
4
CFM
1571 2609 4425 5932 8046
/4 /4 /4 /4
1.0"
Y
R
42 42 52 52
RPM
436 444 453 465 499
MOTOR SPECIFICATIONS
H.P.
3/4 3/4 3/4
1 1
1 1 1
1
/2
1
/2
MOTORS
SPEED
1 2 1 1 2 1 1 1
VOLTS
115/208-230
230
208-230/460
115/230
230
208-230/460
115/208-230
208-230/460
PHASE
1 1 3 1 1 3 1 3
MOTOR
AMPS*
13.8/7.6-6.9
6.9
3.5-3.2/1.6 16/8
8
4.6-4.2/2.1
20/11-10
6.6-6/3
SHAFT
DIA.
5/8 5/8 5/8 5/8 5/8 7/8 5/8 7/8
MOTOR
WGT(LB)
24 29 20 28 29 34 41 40
MOTOR
PART NO.
110455 110456 110461 110457 110458
110462-9
110459-1
110463-9
BLOWER
*Amperage shown is from National Electrical Code. Use amperage shown on motor nameplate to determine motor protector.
BLOWER
Pumps - 1 Required.
MOTORS
SPEED
H.P.
2
1
2
1
3
1
PUMP PART NO.
110467 110468
VOLTS
115/208-230 208-230/460 208-230/460
VOLTS
115 230
PHASE
1 3 3
AMPS
1.0
0.58
MOTOR
AMPS*
24/13.2-12
7.5-6.8/3.4
10.6-9.6/4.8
SHEAVE SELECTION
MOTOR
H.P.
3
/4
, 1
3
/4
, 1
,1
1
1
, 2
1, 1
/2
1
, 2
1
/2
3
MAUREY
SHEAVE
8350K
1
8450K
/2
8350
8450K
8550 8550
SHEAVE
BORE
5/8* 5/8* 7/8* 7/8*
7/8
1 1/8
SAD
MODEL
BELT
B90 B90 B90 B90 B90 B92
MODEL
BELT
B96 B96 B96 B96 B96
B100
12
253 347 253 347 403 403
BLOWER RPM/MOTOR SHEAVE 1/2 TURN DOWN
11
261 356 261 356 412 412
10
269 364 269 364 420 420
278 373 278 373 429 429
8
287 381 287 381 437 437
79
296 390 296 390 446 446
6
304 398 304 398 454 454
5
313 407 313 407 463 463
31
330 424 330 424 480 480
2
338 432 338 432 488 488
4
321 415 321 415 471 471
CHAMPION-SAD
PULLEY-BELT
347 441 347 441 497 497
SAS
*When selecting 1 H.P. motor, be sure to select Pulley-Belt Kit with same pulley bore as shaft size of motor selected.
SIZING TABLES
OUTDOOR
DRY BULB
TEMP.
85
95 105 115
LAT
GPH
LAT
GPH
LAT
GPH
LAT
GPH
6997 / 0
75 76
77 15 78 23 79 30
* Static Pressure (inches of water). GPH = Water consumption at design conditions but does not include bleed-off amount. Amount of bleed-off will vary with different water sources, but
4415 / .5 1571 / 1.0
OUTDOOR WET-BULB
75
65
55
76
67
58
8
15
23
77
68
59
10
23
30
78
69
14
30
79
70
19
38
75
65
55
65
76
67
58
4
68 14 69 19 70 24
66
2
9
13
76
59
66
4
19
76
66
5
76
67
7
an amount equal to 10% of water consumption at any design condition is considered sufficient for average water. LAT = Cooler Discharge Temperature.
3/4 H.P. MOTOR / CFM-SP*
1 H.P. MOTOR / CFM-SP*
7702 / 0
55 56
4
56
5 7 9
OUTDOOR WET-BULB OUTDOOR WET-BULB
75
65
55
76
67
5 7
– – – –
58
8
16
25
77
68
60
16
25
33
78
70
25
33
80
71
33
41
5477 / .5 2609 / 1.0
75 76
77 12 78 18 79 24
75
65
55
65
76
67
58
6
12 68 18 69 24 70 30
66
3
18
6
76
59
67
6
24
9
78
68
9
12
78
68
12
15
1-1/2 H.P. MOTOR / CFM-SP*
6961 / .5 4425 / 1.0
75
65
55
76
67
59
7
19
28
77
69
60
15
28
37
78
70
22
37
79
71
30
47
55
65
58
67
22
15
59
68
30
22 69 30 70 37
55 57
58 12
9
– – – –
8817 / 0
75 76
9 77 19 79 28 80 37
2 H.P. MOTOR / CFM-SP*
9375 / .1
75 76
77 10 78
15
79
19
75
65
55
76
67
58
10
5
10
15
77
68
59
20
15
19
79
69
30
19
80
70
41
24
8043 / .5 5932 / 1.0
OUTDOOR WET-BULB OUTDOOR WET-BULB
75
65
55
76
67
59
20
30
77
69
60
17
30
41
78
70
26
41
80
71
34
51
75
65
55
65
55
76
67
58
67
9
17
26
68
60
26
34 70 34 71 43
58
6
13
19
77
68
59
13
19
26
78
69
19
26
79
70
26
32
SHAFT
MOTOR
DIA.
WGT(LB)
7/8 7/8
1
/8
1
WATTS
GPM (5 FT. HEAD)
73 77
CHAMPION-SAS
KIT NO.
3DI-130 3DI-135 3DI-140 3DI-145 3DI-155 3DI-161
3 H.P. MOTOR / CFM-SP*
9377 / .6 8046 / 1.0
75
– – – –
75
55
65
76
10
77
20
79
30
80
41
MOTOR
PART NO.
49
110460-1
44
110464-9
83
110465-9
4.6
4.6
PULLEY-BELT
KIT NO.
3DI-165 3DI-170 3DI-175 3DI-180 3DI-185 3DI-190
75
65
55
65
76
67
59
67
9
20
30
17
77
69
60
68
17
30
41
26
78
70
70
26
41
34
80
71
71
34
51
43
55 58
26 60 34
– – – –
S
MM
P
F
P
D
AU OUTLET
Q
AS OUTLET
X
C
J
G
EEA
D
G
Q
N
AD OUTLET
A
W
J
N
TOPVIEW
DIMENSIONAL DATA*
BLOWER
MODEL
NUMBER
AS/AD 100B AS/AD 10012B AS/AD 150B AS/AD 15012B AS/AD/AU 20012B
WET MODULE NUMBER
100W
10012W
150W
15012W 20012W
CABINET
H
44 44 54 54
1
59
/4
85 93
105
W
82 90
1
/4
1
/4
1
/4
* All measurements in inches.
SPECIFICATIONS PERFORMANCE
MAX
B.H.P.
3 5
1
7
/2
10
OPER.
WGT.
1249 1264 1297 1326
AD
BELT
B100 B100 B103 B103
AS
BELT
B112 B112 B112 B112
BELT
B92 B92 B93 B93
Performance shown is for installation type B - Free inlet, Ducted outlet. Power rating (BHP) does not include drive losses. When the Cooler Model No, Motor H
0"
AU
RPM
CFM
276
16267
327
19286
374
22077
412
24301
.P., & Blower Speed are determined from the SPECIFICATION table above, use this information to select the proper pulley-belt kit from the SHEAVE SELECT
D
45 45
1
48
1
48
1
60
CFM
15716 18820 21670 23929
OPENING
21 21 26
/4
26
/4
31
/4
DUCT
A
3
/4
3
/4
7
/8
7
/8
3
/4
C
(AS)
B
3
13
21
/4
3
13
21
/4
7
16
26
/8
7
16
/8
26
3
18
31
/4
19
/32
19
/32
13
/16
13
/16
11
/16
DUCT
LOCATION
U
(AD)
P
11
N/A
21
/32
11
N/A
21
/32
5
N/A
19
/32
5
N/A
19
/32
1
24
25
/4
(AU)
29
/32
E
11
11 10 10
14
5
/8
5
/8
11
/16
11
/16
1
/4
DRAIN
LOCATION
G
F
1
1
/2
22
12
1
1
22
16
/2
1
1
24
12
/8
1
1
24
16
/8
1
1
30
16
/8
WET
MODULE
/2
18
/2
22
/2
18
/2
22
/8
22
J
1
/2
1
/2
1
/2
1
/2
1
/2
Certified Air Delivery At .1" Increments Of External Static Pressure (Inches Static Pressure Water Gauge)
0.1"
284 334 380 417
CFM
15200 18371 21270 23562
0.2" RPMRPM
292 341 387 423
CFM
14696 17943 20888 23204
0.3" RPM
300 348 393 429
0.4"
CFM
14190 17518 20514 22866
RPM
308 355 399 434
CFM
13665 17092 20142 22528
0.5" RPM
317 361 405 440
CFM
13110 16661 19769 22190
0.6" RPM
Models AS/AD/AU 20012 include the affects of a 12 inch thick evaporative media on the inlet.
325 368 410 445
Y
R
MEDIA
DIMENSION
Y
X
3
5
36
44
/4
/8
3
5
44
36
/4
/8
3
48
46
/8
3
48
46
/8
5
/8
51
60
0.7" RPM
CFM
335
12521 16211
375 416
19395 21852
450
H
C
WATER
SERVICE
M
L
7
14
5
/8
7
5
18
/8
7
5
14
/8
7
5
18
/8
7
/8
5
18
0.8"
CFM
11886 15752 19015 21510
AD OUTLET
B
ELECTRIC
SERVICE
S
5
7
/8
39
/8
5
7
/8
43
/8
5
1
/8
41
/2
5
1
/8
45
/2
5
5
/8
51
/8
RPM
CFM
11194
346
15272
383
18629
422
21171
456
ION table below.
5 5 5 5 5
D
T
5
/32
5
/32
5
/32
5
/32
5
/32
0.9" RPM
U
BLOWER
WEIV EDISWEIV TNORF
SECTION
SKID
LOCATIONS
Q
N
3
1
/4
4
23
/4
3
1
4
/4
27
/4
3
1
4
/4
23
/4
3
1
4
/4
27
/4
3
1
4
/4
27
/4
1.0"
CFM
10450
358
14760
390
18229
428
20823
461
R
42 42 52 52
1
57
RPM
371 399 435 467
/4
MOTOR SPECIFICATIONS
H.P.
7
10
3 5
1
/2
MOTORS
SPEED
1 1 1 1
VOLTS
230/460 230/460 230/460 230/460
PHASE
3 3 3 3
MOTOR
AMPS*
9.6/4.8
15.2/7.6 22/11
28/14
SHAFT
DIA.
1
1
/8
1
1
/8
3
1
/8
3
/8
1
MOTOR
WGT(LB)
83
87 121 138
MOTOR
PART NO.
110465-9 110466-9 110470-9 110482-9
PUMP PART NO.
Pumps - 2 Required.
BLOWER
*Amperage shown is from National Electrical Code. Use amperage shown on motor nameplate to determine motor protector.
SHEAVE SELECTION
MOTOR
H.P.
3 5
7-1/2
10
MAUREY
SHEAVE
D8350 D8400 D8450 D8550
SHEAVE
BORE
1 1/8 1 1/8 1 3/8 1 3/8
AD
MODEL
BELT
B100 B100 B103 B103
MODEL
BELT
B112 B112 B112 B112
MODEL
BELT
B92 B92 B93 B93
7
253 291 347 403
BLOWER RPM/TURNS OPEN OF MOTOR SHEAVE
6
262 300 358 412
1
/2
6
272 310 369 422
5
281 319 381 431
1
/2
5
291 328 392 441
4
300 338 403 450
1
/2
4
309 347 414 459
AU
AS
SIZING TABLES
3 H.P. MOTOR / CFM-SP*
OUTDOOR DRY BULB
TEMP.
85
95 105 115
LAT
GPH
LAT
GPH
LAT
GPH
LAT
GPH
16267 / 0
75 76
18 77 36 78 54 79 72
* Static Pressure (inches of water). GPH = Water consumption at design conditions but does not include bleed-off amount.
13655 / .5 10450 / 1.0
OUTDOOR WET-BULB
75
65
55
65
55
76
67
58
67
58
15
36
54
31
46
77
68
59
68
59
31
54
72
46
61
78
69
60
69
60
46
72
90
61
76
79
70
61
70
60
62
90
107
77
91
but an amount equal to 10% of water consumption at any design condition is considered sufficient for average water.
75
65
76
67
12
24
77
67
24
35
77
68
36
47
78
69
48
59
5 H.P. MOTOR / CFM-SP*
17092 / .5 14760 / 1.0
OUTDOOR WET-BULB OUTDOOR WET-BULB
75
65
55
76
67
58
19
42
63
77
68
59
38
64
84
78
69
60
57
85
106
79
70
61
76
106
127
55
57 35 58 47 59 59 60 71
19286 / 0
75
76 21 77 43 78 64 79 85
7-1/2 H.P. MOTOR / CFM-SP*
22077 / 0
75
65
55
76
67
58
17
38
56
77
68
59
33
57
75
78
69
60
50
76
94
79
70
61
66
95
113
75
65
55
76
67
58
24
33
49
77
68
59
49
49
66
78
69
60
73
66
82
79
70
61
97
82
98
20142 / .5 18229 / 1.0
75
65
55
76
67
58
22
48
72
77
68
59
45
72
96
78
69
61
67
97
120
79
71
62
89
121
144
65
67 44 68 67 69 89 70
111
110 133
55
58 66 59 88 60
61
Amount of bleed-off will vary with different water sources,
110467 110468
75
76 20 77 41 78 61 79 81
101
3
319 356 425 469
65
67 40 68 61 69 81 70
VOLTS
115
230
1
/2
3
328 365 437 478
1
2
338 375 448 488
/2
10 H.P. MOTOR / CFM-SP*
22528 / .5 20823 / 1.0
OUTDOOR WET-BULB
75
65
55
76
67
58
25
53
79
77
68
59
50
80
106
78
69
61
74
106
132
79
71
62
99
133
159
55
58 60 59 80 60
100
61
121
24301 / 0
75
76 27 77 53 78 80 79
107
65
67 49 68 74 69 99 71
123
2
347 384 459 497
55
58 74 59 98 61
123
62
147
AMPS
1.0
0.58
AD
PULLEY-BELT
KIT NO.
3DI-195 3DI-200 3DI-203 3DI-205
75
65
76
67
23
46
77
68
46
69
78
69
69
92
79
70
92
115
55
58 68 59 91 60
114
61
137
WATTS
GPM (5 FT. HEAD)
73 77
AS
PULLEY-BELT
KIT NO.
3DI-210 3DI-215 3DI-218 3DI-220
4.6
4.6
AU
PULLEY-BELT
KIT NO.
3DI-225 3DI-230 3DI-233 3DI-235
CHAMPION COOLER certifies that the evaporative air coolers shown here are licensed to bear
the AMCA Seal. e ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the Certified Ratings Program.
IMITED
L
is warranty is extended to the original purchaser of an evaporative cooler installed and used under normal conditions. It does not cover damages incurred from accident, neglect, or abuse by the owner. Champion Cooler does not authorize any person or representative to assume for the Corporation any other or different liability in connection with this product.
TERMS & CONDITIONS OF WARRANTY
is warranty includes lifetime limited coverage on water reservoir against any leakage due to defects in material. From date of installation, if any original component part provided by Champion Cooler fails due to defect in material or factory workmanship only, Champion Cooler will provide the replacement parts as follows:
• Cabinet components for one year from date of installation
• Evaporative media for two years from date of installation
EXCLUSIONS TO THIS WARRANTY
• Champion Cooler is not responsible for any incidental or consequential damage resulting from any malfunction.
• Champion Cooler is not responsible for any damage received from the use of water softeners, chemicals, descaling material, plastic wrap, or if a motor of a higher horsepower than what is shown on the serial plate is used in the unit.
W
ARRANT Y
• Champion Cooler is not responsible for the cost of service calls to diagnose cause of trouble, or labor charge to repair and/or replace parts.
HOW TO OBTAIN SERVICE UNDER THIS WARRANTY
Contact the Dealer where you purchased the evaporative cooler. If for any reason you are not satisfied with the response from the Dealer, write or call: Customer Service Department, Champion Cooler,
5800 Murray Street, Little Rock, AR 72209, 800-643-8341
or e-mail Champion at: info@championcooler.com.
is limited warranty applies to the original purchaser only.
The New MasterCool® by Champion Cooler, 5800 Murray, Little Rock, AR 72209
800 643-8341 www.championcooler.com
Crafted with Pride in the USA
CSGB -MARCH 2009