ERL F-PRO 5100 User Manual

Page 1
F-PRO
Feeder Protection Relay
Model 5100
User Manual
Version 4.0 Rev 0
Page 2
Page 3

Preface

Information in this document is subject to change without notice.
Reproduction in any manner whatsoever without the written permission of ERLPhase Power Technologies Ltd. is strictly forbidden.
This manual is part of a complete set of product documentation that includes detailed drawings and operation. Users should evaluate the information in the context of the complete set of product documentation and their particular applications. ERLPhase assumes no liability for any incidental, indirect or consequential damages arising from the use of this documentation.
While all information presented is believed to be reliable and in accordance with accepted engineering practices, ERLPhase makes no warranties as to the completeness of the information.
All trademarks used in association with B-PRO, F-PRO, iTMU, L-PRO, ProLogic, S-PRO, T-PRO, TESLA, TESLA Control Panel, Relay Control Panel, RecordGraph and RecordBase are trademarks of ERLPhase Power Technologies Ltd.
Windows® is a registered trademark of the Microsoft Corporation.
HyperTerminal® is a registered trademark of Hilgraeve.
Modbus® is a registered trademark of Modicon.

Contact Information

ERLPhase Power Technologies Ltd
Website: www.erlphase.com
Technical Support
Tel: 1-204-477-0591
D02416R04.00 F-PRO 5100 User Manual i
Page 4
Page 5

Table of Contents

Preface ......................................................................................i
Contact Information ...................................................................i
Table of Contents ....................................................................iii
Using This Guide ......................................................................v
Version Compatibility.............................................................. vii
1 Overview ................................................................. 1-1
Front View........................................................................ 1-3
Back View ........................................................................ 1-3
Model Options/Ordering................................................... 1-4
2 Setup and Communications.................................. 2-1
Power Supply................................................................... 2-1
IRIG-B Time Input ............................................................ 2-1
Communicating with the Relay (IED) ............................... 2-2
Using HyperTerminal to Access the Relay’s User
Interface........................................................................... 2-5
Setting the Baud Rate...................................................... 2-7
Accessing the Relay’s SCADA Services.......................... 2-8
Communication Port Details ............................................ 2-9
Maintenance Menu ........................................................ 2-12
Firmware Update ........................................................... 2-13
3 Using the IED (Getting Started) ............................ 3-1
Start-up Sequence........................................................... 3-1
Front Panel Display.......................................................... 3-2
Terminal Mode ................................................................. 3-5
View, Change or Service Login........................................ 3-9
Breaker Login................................................................. 3-13
Metering Data ................................................................ 3-14
4 Protection Functions and Specifications ............ 4-1
Protection and Recording Functions................................ 4-1
Demand Metering .......................................................... 4-17
Accumulated Energy (kWh, kVARh metering)............... 4-20
Recording Functions...................................................... 4-26
Logging Functions.......................................................... 4-28
5 Offliner Settings Software..................................... 5-1
Introduction ...................................................................... 5-1
Installing PC Software...................................................... 5-2
D02416R04.00 F-PRO 5100 User Manual iii
Page 6
Table of Contents
Offliner Features .............................................................. 5-2
Handling Backward Compatibility .................................... 5-4
RecordBase View Software ............................................. 5-5
Main Branches from the Tree View.................................. 5-6
Settings From a Record ................................................. 5-19
6 Testing the F-PRO Functions................................ 6-1
7 Installation .............................................................. 7-1
Physical Mounting............................................................ 7-1
AC and DC Wiring............................................................ 7-1
Communication Wiring..................................................... 7-1
Appendix A IED Specifications .............................................A-1
Distance Element Operating Time Curves at Nominal
Frequency ........................................................................A-4
Frequency Element Operating Time Curves....................A-5
Appendix B IED Settings and Ranges..................................B-1
Appendix C Hardware Description .......................................C-1
Appendix D Event Messages ...............................................D-1
Appendix E Modbus RTU Communication Protocol.............E-1
Appendix F DNP3 Communication Protocol......................... F-1
Appendix G Mechanical Drawings........................................G-1
Appendix H Rear Panel Drawings ........................................H-1
Appendix I AC Schematic Drawing........................................ I-1
Appendix J DC Schematic Drawing.......................................J-1
Appendix K Function Logic Diagram ....................................K-1
Appendix L F-PRO Setting Example .................................... L-1
Setting Examples ............................................................. L-2
Switching Setting Groups................................................. L-5
Index..........................................................................................I
iv F-PRO 5100 User Manual D02416R04.00
Page 7

Using This Guide

This User Manual describes the installation and operation of the F-PRO feeder protection relay. It is intended to support the first time user and clarify the de­tails of the equipment.
The manual uses a number of conventions to denote special information:
Example Describes
Start>Settings>Control Panel Choose the Control Panel submenu in the Set-
Right-click Click the right mouse button.
Recordings Menu items and tabs are shown in italics.
tings submenu on the Start menu.
service User input or keystrokes are shown
Text boxes similar to this one Relate important notes and information.
.. Indicates more screens.
Indicates further drop-down menu, click to dis­play list.
Indicates a warning.
in bold.
D02416R04.00 F-PRO 5100 User Manual v
Page 8
Page 9

Version Compatibility

This chart indicates the versions of Offliner Settings, RecordBase View and the User Manual which are compatible with different versions of F-PRO firm­ware.
RecordBase View and Of lier versions of records and setting files. You can use RecordBase View to view records create and edit older setting file versions.
Minor releases (designated with a letter suffix compatibility as their base version. For example. F-PRO firmware v3.1c and Offliner Settings v3.1a are compatible.
produced by any version of F-PRO firmware and Offliner Settings can
F-PRO Firmware/Software Compatibility Guide
fliner Settings are backward compatible with all ear-
- e.g. v3.1a) maintain the same
F-PRO Firmware
v4.0 2 4000 v1.0 or greater
v3.0 2 4000 v1.0 and greater
v3.0 2 v3.0 or greater
v2.0a 2 v2.0 or greater
v2.0 2 v2.0 or greater
v1.0d 1 v1.0b or greater
v1.0c 1 v1.0a or greater
v1.0b 1 v1.0a or greater
v1.0a 1 v1.0a or greater
v1.0 1 v1.0 or greater
Setting File Ver sio n
Compatible Of
fliner Settings
Please contact ERLPhase Customer Service for complete Revision History.
D02416R04.00 F-PRO 5100 User Manual vii
Page 10
Page 11

1 Overview

F-PRO Feeder Protection Relay
Offline Mode - Settings Software
Online Mode - Terminal Mode
F-PRO
Feeder Protection Model 5100
Port 1
Date &
Time
View
Readings
View Logs
Prev
Next
Targ et
Clear Targ et
1999 JUN 07
Relay Functional IRIG-B Functional Service Required Test Mode Alarm
The F-PRO (model 5100) is a microprocessor-based relay providing compre­hensive directional overcurrent protection, reclosing, mete
ring, breaker moni-
toring and recording functions suitable for medium and low voltage lines.
F-PRO has two working modes—online and off
line. In the online mode you can use any communication software package (e.g. Procomm or HyperTermi­nal) to connect to the F-PRO using VT100 terminal emulation. In online mode y
ou can:
• change and review relay
settings
• view event and metering information
• initiate and retrieve recordings, and retrieve setti
In offline mode you can use Offliner Se
ttings and RecordBase View software
ngs
to:
• create and review relay settings
• analyze fault waveforms
• store records
D02416R04.00 F-PRO 5100 User Manual 1-1
In addition to the protection functions F-PRO provides fault recording (96 sample/cycle) to facilitate analysis of the power system after a disturbance has taken place. The triggers for fault recording are established by programming the output matrix and allowing any internal relay function or any external input to initiate recording.
The primary protection provided is overcurrent based. A library for these overcurrent f
unctions provides commonly used IEEE and IEC inverse curves. Because the curves are equation-driven, you can choose to enter an equation parameter directly, creating other overcurrent shapes as needed. All overcurrent functions are provided with directional control, if required, using the ERLPhase method of positive sequence control.
Page 12
1 Overview
To provide a complete package of protection and control, F-PRO provides oth­er functions such as:
• ring bus capability to protect and monitor
lines connected to ring schemes Current inputs are labelled Main and Aux inputs to denote the breaker ring current inputs. Use F-PRO with straight single breaker line schemes by us­ing the main current inputs
• breaker failure detection and monitoring
• 2 completely dedicated four shot reclosers devices 79 Main and 79 Aux to control line re
closing needs along with device 25C Sync Check/Dead Bus/
Dead Line supervision
• low set overcurrent functions for e
ach breaker as well as for the summated
line currents that include phase, neutral and negative sequence functions
• Watt, VAR flow detectors as well a
s undervoltage, overvoltage and over/ under frequency functions (Freq ROC) to provide protection for issues such as inter-tie protection needs
• ProLogic provide a flexible way to addres
s special protection needs. Ten
ProLogic statements are provided
• Breaker Logic, Group Logic, Demand Metering
Source
Feeder
Feeder
PT (3 ph)
Analog Inputs 4 Analog Voltages 1 Three-phase Input 1 Single-phase Input 6 Analog Currents 2 Three-phase Inputs
Ring Bus
CT 2
CT 1
Aux.
PT (1 ph)
Main
Protected Feeder
50LS-2
50LS-1
THD
50LS-1
50LS-2
Feeder
Outputs 12 Output Contacts 1 Relay Inoperative Alarm Contact
Inputs 9 External Inputs
59-1 59-2 27-1 27-2
Trend Recording (Primary) Real Power (MW In and Out) Reactive Power (MVAR In and Out) 3 Phase Voltages (Va, Vb, Vc) 3 Phase Currents (Ia, Ib, Ic) Real Energy (MWh In and Out) Reactive Energy (MVARh In and Out) THD Level (%) System Frequency
Figure 1.1: F-PRO Line Diagram
50BF
50BF
Rec
79Aux
79
Main
25C
Rec
Σ
Rec
50/51/
67
60 81-1
Fault Recording 4 Voltages 6 Currents 97 Unique Events
50N/51N
67
46/
50/51/
67
81-2 81-3
21P
Metering
81-4
Metering (Front Display) Primary Pos. Sequence Volts, Amps, Primary Watts and VARs Frequency THD (Total Harmonic Distortion) PF (Power Factor) Primary Phase Voltage, Current, Phase Angle (A, B, C) Peak Demand MW, MVAR In and Out Phase Currents Energy Values MWh In and Out MVARh In and Out 3I0
32P 32Q
Rec
1-2 F-PRO 5100 User Manual D02416R04.00
Page 13

Front View

1. Front display of time, alarms, relay target and metering
2. Relay target LED (red)
3. LEDs indicating status of relay
4. Communications serial Port 1 for laptop computer
5. Clear target push button
6. Push buttons to manipulate information on LCD display
F-PRO
Feeder Protection Relay Model 5100
Relay Functional
IRIG-B Functional
Service Required
Test Mode
Alarm
Port 1
NextView
Readings
View Logs
Previous
456
Target
Clear
Target
2000 Jan 07 11:49:54
Date &
Time
1 2
3
VA VB VC N
Main AC Line Currents
Main AC Volts
Power Supply
300 301 302 303 305 306 307 308 309 310 312311 313 314 315 316 317 318 319 320 321 322 323 324 326 327 328 329 330 331 332 333325
Case
Ground
231 232 233
Relay
Inoperative
Output Relay Contracts
200 201 202 203 204 205 206 207 208 209 210 212211 213 214 215 216 217 218 219 220 221 222 223 224 226 227 228 229 230225
External Inputs
100 101 102 103 104 105 106 107 108 109 110 112111 113 114 115 116 117
+ - + - + - + - + - + - + - + - + -
234 235
Port 4
Unused
Port 3
SCADA
IRIG-B
1 2 3456 987
Out 1 Out 2 Out 3
Out 4 Out 5 Out 6 Out 7 Out 8 Out 9 Out 10
Out 11
Out 12
I1 A I1 B I1 C I2 A I2 B
I2 C
I3 A I3 B I3 C I4 A I4 B
+ -
VA VB
I4 C
VC
7. Port 5 - 10BaseT Ethernet Port/Internal Modem (optional)
8. External clock, IRIG-B modulated or unmodulated
9. Port 2 - Direct/Modem RS-232 Port
10. Port 3 - SCADA
11. Port 4 - unused
12. Case ground
13. 9 programmable external inputs (1 to 9)
14. This row contains 2 distinct areas from left to right: 12 programmable output relay contacts and relay inoperative contact
15. This row contains 3 distinct areas from left to right: 6 ac current inputs 4 ac voltage inputs Power supply
13
14
15
Output Contacts
In. Freq.
Aux.AC Line Currents AC Currents Inputs
Nominal
48-250 Vdc
120 Vac
Aux. AC Volts
Unused
N
Sync AC
Volts
125Vdc125Vdc 125Vdc 125Vdc 125Vdc 125Vdc 125Vdc 125Vdc 125Vdc
Port 2
Direct/Modem
Port 5
VN
Unused
7 8 9 10 11 12
1 Overview
Figure 1.2: F-PRO Front View

Back View

Figure 1.3: F-PRO Back View
D02416R04.00 F-PRO 5100 User Manual 1-3
Page 14
1 Overview

AC Current and Voltage Inputs

F-PRO is provided with terminal blocks for up to 6 ac currents and 4 phase-to­neutral voltages.
Each of the current input circuits has polarity (•) marks.
A complete schematic of current and voltage circuits is shown, for details see “AC Schematic Drawing” in Appendix I and “DC Schematic Drawing” in Appendix J.

External Inputs The F-PRO relay contains 9 programmable external inputs. External dc voltage

of either 48/125 volts or 125/250 volts nominal are possible depending on the range provided.

Output Relay Contacts

The F-PRO relay has 12 output relay contacts. Each contact is programmable and has breaker tripping capability. All output contacts are isolated from each other. The output contacts are closed for a minimum of 100 ms after operation.

Relay Inoperative Alarm Output

If the relay becomes inoperative, then the Relay Inoperative Alarm output con­tact closes and all tripping functions are blocked.

Model Options/Ordering

F-PRO is available as a horizontal mount, for details see “Mechanical Draw­ings” in Appendix G.
F-PRO is available with an internal modem card or internal network card.
The CT inputs are 1 A nominal or 5 A nominal. The external inputs are 48/125 Vdc or 125/250 Vdc. The system base frequency is either 50 Hz or 60 Hz.
All of the above options must be specified at the time of ordering.
1-4 F-PRO 5100 User Manual D02416R04.00
Page 15

2 Setup and Communications

Power Supply

A wide range power supply is standard. The nominal operating range is 48–250 Vdc, 120 Vac, 50/60 Hz. To protect against possible short circuit in the supply use an inline fuse or circuit breaker with a 5 A rating. Make the chassis ground connection to ensure proper operation and safety.
There are no power switches on the relay. When the ed, the relay starts its initialization process and takes about plete showing the green Relay Functional LED.

Case Grounding You must ground the relay to station ground using the case-grounding terminal

at the back of the View on page 1-3.
WARNING!
To ensure safety and proper operation you must connect the relay to
station ground using the rear grounding terminal on the relay.
the
relay, for details see for details see Figure 1.3: F-PRO Back
power supply is connect-
40 seconds to com-

IRIG-B Time Input

The relay is equipped to handle modulated or unmodulated GPS satellite time IRIG-B signals. The IRIG-B time signal is connected to the BNC connection on the back of the relay. When the IRIG-B signal is provided to the relay and is enabled in the settings through the user interface, the IRIG-B functional LED comes on and the relay clock is referenced to this signal. No settings are re­quired to differentiate between modulated or unmodulated signals; this is au­tomatically detected by the relay.
You enable or disable the IEEE 1344 extension in Utilities>Setup>Time, for details see “Utilities” on page 3-14. The enabled mode allows the year to be received from the IRIG-B signal. If the available IRIG-B signal
Ground the relay even when testing.
Do not rely on the rack mounting screws to provide case grounding.
the terminal mode settings
has no year extension, this setting should be disabled.
D02416R04.00 F-PRO 5100 User Manual 2-1
Page 16
2 Setup and Communications

Communicating with the Relay (IED)

You can connect to the relay to access its user interface and SCADA services:
• direct serial link (user interface and SCADA)
• external or internal modem link (user interface only)
• ethernet network link (user interface and SCADA)

Direct Serial Link

Port 2 - direct/modem
F-PRO
Feeder Protection Model 5100
Date &
Readings
Time
1999 JUN 07
View
View
Prev
Logs
Port 1
Relay Functional IRIG-B Functional
Target
Service Required Test Mode
Next
Clear Target
Alarm
Port 1
Serial Extension Cable
Relay Port 1 or rear Port 2
to PC Serial Port
Laptop PC
Figure 2.1: Direct Serial Link
The relay has three serial ports that provide direct access to its user interface and SCADA services.
All of the relay’s serial ports (Ports 1, 2 and 3) are configured as EIA
RS-232 Data Communications Equipment (DCE) devices with female DB9 connec­tors. This allows them dard straight-through male-to-female serial cable, for pin-out,
to be connected directly to a PC serial port with a stan-
for details see
“Communication Port Details” on page 2-9.
The relay’s user interface is accessed through a ulation program running on a PC. To create a direc lay and your computer, connect the seri
al cable (provided) between your
standard VT-100 terminal em-
t serial link between the re-
computer's serial port and Port 1 on the relay’s front panel. Port 2 on the relay’s back panel can also be used for direct serial access, provided the port is not configured for modem use. When connected, run the terminal emulation soft­ware on your computer to establish the communication link, for details see “Using HyperTerminal to Access the Relay’s User Interface” on page 2-5.
The relay’s Modbus and DNP3 SCADA services can be accessed via a direct serial
link to Port 3 on the relay's back panel, for details see “Accessing the Re-
lay’s SCADA Services” on page 2-8.
2-2 F-PRO 5100 User Manual D02416R04.00
Page 17
Modem Link -
External
Modem
Telephone
System
Analog
Telephone
Line
Modem Adapter
Supplied by ERLPhase
DB-9-Male-Male
Modem Cable
(as supplied with modem)
Modem Adapter
Port 2 - Direct/Modem
Analog
Telephone
Line
F-PRO
Feeder Protection Model 5100
Port 1
Date & Time
View
Readings
View Logs
Prev
Next
Target
Clear Target
1999 JUN 07
Relay Functional IRIG-B Functional Service Required Test Mode Alarm
External
2 Setup and Communications
Modem Cable
(as supplied with modem)
Modem Adapter
Port 2 - Direct/Modem
F-PRO
Feeder Protection Model 5100
1999 JUN 07
Target
Next
View
View
Prev
Date &
Clear
Readings
Logs
Time
Target
Relay Functional IRIG-B Functional Service Required Test Mode Alarm
Port 1
External
Analog
Telephone
Line
Telephone
System
Analog
Telephone
Line
Modem
Modem Adapter
Supplied by ERLPhase
DB-9-Male-Male
Figure 2.2: External Modem Link
The relay’s user interface can also be accessed through a telephone link be­tween the relay and your computer, using an external modem.
Connect the serial port on the external modem to
the Port 2 on the relay's back panel. Both devices are configured as RS-232 DCE devices with female con­nectors, so the cable between the relay a
nd the modem requires a crossover and a gender change. Alternatively, you can use the ERLPhase modem port adapter provided with the relay to make Port 2 appear the same as a PC’s serial port. A standard modem-to-PC serial cable can then be used to connect the modem and the relay, for pin-out details see “Communication Port Details” on page 2-9.
Connect the modem to an analog telephone line or switc
h using a standard RJ-
11 connector.
To work with a modem, the relay’s Port 2 must be appropriately configured. Log into the rel
ay through a direct serial link, go to the Utilities>Setup>Ports screen, and set the Port 2 Modem option to Yes. The Baud Rate should be set as high as possible - most modems will handle 57,600 bps. The Initialize set­ting lets you set the control nection session. The factory defaults are: “M0S0=0&B1” for
codes sent to the modem at the start of each con-
an external
modem and “M0S0=0” for an internal modem.
D02416R04.00 F-PRO 5100 User Manual 2-3
Page 18
2 Setup and Communications
Modem Link ­Internal

Network Link

Port 5 - RJ-11 modem
F-PRO
Feeder Protection Model 5100
1999 JUN 07
Next
View
View
Prev
Date &
Readings
Logs
Time
Analog
Telephone
Line
Relay Functional IRIG-B Functional
Target
Service Required Test Mode
Clear Target
Alarm
Port 1
Telephone
System
Analog
Telephone
Line
Desktop Computer
Figure 2.3: Internal Modem Link
The relay’s user interface can also be accessed through a telephone link be­tween the relay and your computer using an opti
onal internal modem. If the modem has been installed, Port 5 on the rear panel will be labelled “INTER­NAL MODEM.”
Connect the relay’s Port 5 to an analog telephone
line or switch using a stan-
dard RJ-11 connector.
When an internal modem is installed, the relay’
s Port 2 is used to interface to the modem internally. Appropriate Port 2 settings are configured at the factory when the internal modem is installed. The factory defaults are: “M0S0=0&B1” for an external modem and “M0S0=0” for an internal modem.
PC with TCP/IP
TCP/IP
Network
10BaseT
Port 5 - RJ-45
Network
F-PRO
Feeder Protection Model 5100
Relay Functional IRIG-B Functional
1999 JUN 07
Target
Service Required Test Mode
Next
View
View
Prev
Date &
Clear
Readings
Logs
Time
Target
Alarm
Port 1
Figure 2.4: Network Link
You can access both the relay’s user interface and DNP3 SCADA services si­multaneously through the same network port with an
optional Ethernet TCP/IP LAN link. If the Ethernet option has been installed, Port 5 on the rear panel will be labelled “NETWORK.”
The user interface accessed through the LAN is the same as that available through
a direct serial connection or a modem link, but requires the use of a Telnet client on your PC. The HyperTerminal program, which is included in Windows XP and is also available separately as HyperTerminal PE, provides Telnet services. To select Telnet, go to HyperTerminal’s Properties dialog box and set the Connect Using field to TCP/IP (Winsock). If this option is not avail-
2-4 F-PRO 5100 User Manual D02416R04.00
Page 19
2 Setup and Communications
able in the pick list, you require a newer version of HyperTerminal (v1.2 or greater). Alternatively, you can use any Telnet program that fully supports VT­100 terminal emulation and z-modem file transfer.
DNP3 SCADA services can also be accessed over the LAN, for details see “Accessing the Relay’s SCADA Services” on page 2-8.
Connect Port 5 to the Ethernet LAN using an appropriate 10BaseT cable with an RJ-45 connector. The relay supports 10 Mbit Ethernet, although a dual speed 10/100 Ethernet hub or switch can be used.
By default, the relay is assigned an IP address of 192.168.1.100. If this address is not suitable, it may be modified using the relay’s , for details see
“Using Hy-
perTerminal to Access the Relay’s User Interface” on page 2-5.

Using HyperTerminal to Access the Relay’s User Interface

Change settings, view measured values and retrieve data from the relay using its user interface. This section describes how to configure a standard Windows VT-100 terminal program on your PC for use with the relay.
The computer must be connected to the relay by one of its serial, modem or Ethernet communication ports, for details see (IED)” on page 2-2.
The relay user interface is accessed using a standard VT-100 terminal style program on your computer eliminating the need for specialized user interface software. Any terminal program that fully supports VT-100 emulation and pro vides z-modem file transfer services can be used. The HyperTerminal program is used here as an example.
Configure your terminal program as described in the table below and link it to the appropriate serial port, modem or TCP/IP socket on your computer.
“Communicating with the Relay
-
Terminal Program Setup
Baud rate
Data bits
Parity
Stop bits
Flow control
Function, arrow and control keys
Emulation
D02416R04.00 F-PRO 5100 User Manual 2-5
For a direct serial link, the baud rate must match that of the relay serial port. For a modem link, the baud rate refers only to the link between your computer and its own modem. Refer to “Setting the Baud Rate” on page 2-7 for further information
8
None
1
Hardware or Software. Hardware flow control is recommended. The relay automatically supports both on all its serial ports.
Terminal keys
VT100
Page 20
2 Setup and Communications
Terminal Program Setup
Font Use a font that supports line drawing (e.g. Terminal or MS Line Draw).
If the menu appears outlined in odd characters, the font you have selected is
not supporting line drawing characters.
To initiate the connection with the relay, use HyperTerminal’s Call>Connect function.
When the connection is established, press Enter in the
terminal window to
bring up the following login prompt:
Instructions on logging in and running the user interface are given in “Terminal Mode” on page 3-5.
If you see incorrect characters on a direct
serial connection, it may mean there
is a mismatch between the relay’s baud rate and that of the PC.
Ending a User Inte
rface Session
Use the Quit function in the relay’s user menu to end a session. This will close the interface and require the next user to log in to the relay.
The relay automatically ends a session when it detec
ts the disconnecting of a direct serial cable or a modem hang-up. For other types of connections (e.g. se­rial switches or Ethernet) you are advised to
use the Quit function to ensure the
interface is closed and login protection is activated.
2-6 F-PRO 5100 User Manual D02416R04.00
Page 21
2 Setup and Communications

Setting the Baud Rate

The baud rate of the relay's serial ports can be shown on the relay’s front panel display. From the main Date & Time display, press the Next button.

Direct Serial Link For a direct serial connection, both the relay and your computer must be set to

the
same baud rate.
To change the baud rate of a relay serial port:
1 Access the relay’s user interface through any of the available ports
2 Log in to the user interface and go to the Utili
details see “Terminal Mode” on page 3-5.
3 Select the desired baud rate for the appropriate port by toggling through the
options using
the Space or Enter keys. Save the new setting with the F2 key.
The message “New communications settings loaded” will appear.
The new baud rate will be used on that
To change the baud rate on your computer’s serial port:
port the next time you log in to it.
1 From within HyperTerminal, bring up the Properties dialogue, press the
Configure button and set the baud rate field to the desired value.
2 Save the changes.
ties>Setup>Ports menu, for
Modem Link Unlike a direct serial link, the baud rates for a modem link do not have to be
the same on your computer and on the relay. The modems automatically nego­tiate an optimal baud rate for their communication.
The baud rate set on the relay only affe nicates with the modem. Similarly, the
cts the rate at which the relay commu-
baud rate set in HyperTerminal only af­fects the rate at which your computer communicates with its modem. Details on how to s
et these respective baud rates are described above, except that you modify the Port 2 baud rate on the relay and the properties of the modem in Hy­perTerminal.
D02416R04.00 F-PRO 5100 User Manual 2-7
Page 22
2 Setup and Communications

Accessing the Relay’s SCADA Services

The relay supports DNP3 (Level 2) and Modbus SCADA protocols as a stan­dard feature on all relays. DNP3 is available through a Ethernet LAN on top of either TCP or UDP protocols. The Modbus implemen­tation supports both RTU (binary) or A direct serial link.
The relay’s Port 3 is dedicated for use with Port 3 uses standard RS-232 signalling. An external RS-232<->RS-485 con­verter can also be used to connect to an RS-485 network.
For details on connecting to serial Port 3 see “Communicating with the Relay (IED)” on page 2-2 and “Communication Port Details” on page 2-9.
The DNP3 protocol can also be run across the optional Ethernet LAN. Both DNP o to the Ethernet LAN see “Network Link” on page 2-4.
Complete details on the Modb the Appendices, “Modbus RTU Communication Protocol” in Appendix E and “DNP3 Communication Protocol” in Appendix F respectively.
ver TCP and DNP over UDP are supported. For details on connecting
us and DNP3 protocol services can be found in
direct serial link or the
SCII modes and is available through a
Modbus or DNP3 serial protocols.

Protocol Selection To select the desired SCADA protocol, login

access the Utilities>Setup>SCADA menu. Select the protocol and set the cor­responding parameters.
The DNP3 LAN/WAN - TCP and UDP options are only available if the
ptional Ethernet LAN port installed.
rs are set using the Utilities>Setup>Ports

Communication Parameters

unit has an o
Port 3’s communication paramete menu in relay’s user interface. Both the baud rate and the parity bit can be con­figured. The number of data bits and stop bits are the selected SCADA protocol. Modbus ASCII uses 7 data bits. Modbus RTU and DNP Serial use 8 data bits. All protocols use 1 stop bit except in the case where either Modbus protocol is used with no parity; this uses 2 stop bits, as defined in the Modbus standard.

Diagnostics Protocol monitor utilities are available

nication difficulties such as incompatible
to assist in resolving SCADA commu-
baud rate or addressing. The utilities can be access through the Maintenance user interface, for details see “Mainte­nance Menu” on page 2-12.
to the relay’s user interface and
determined automatically by
2-8 F-PRO 5100 User Manual D02416R04.00
Page 23

Communication Port Details

Port Location Function
1 Front Panel RS-232 Data Communication Equipment (DCE) female DB9.
2 Rear Panel RS-232 DCE female DB9.
3 Rear Panel RS-232 DCE female DB9.
2 Setup and Communications
Used for user interface access thro
Default Setting: 38,400 baud, 8 data bits, no parity, 1 stop bit.
Used for:
• User interface access thr
• User interface access through an external modem. The optional ERLPhase Mode nal Equipment (DTE) to simplify co modem.
Default Setting: 9,600 baud, 8 data bits, no parity, 1 stop bit.
Port 2 is disabled if the relay is equipped with an internal modem
see Port 5).
(
Used for SCADA communication.
Default Setting: 9,600 baud, 8 data bits, no parity, 1 stop bit.
m Adapter converts this port to a Data Termi-
ugh a direct serial connection.
ough a direct serial connection.
nnection to an external
4 Rear Panel Not used
5 Rear Panel RJ-11/RJ-45 receptacle.
When equipped with optional internal modem:
• Used for user interface access through modem.
When equipped with optional internal Ethernet card:
• User interface access.
• DNP SCADA access.
Default Ethernet IP address: 192.168.1.100.
D02416R04.00 F-PRO 5100 User Manual 2-9
Page 24
2 Setup and Communications
Signal Name
DCD  1
RxD  2
TxD 3
DTR 4
Common 5
DSR  6
RTS 7
CTS  8
No connection 9
Direction
PC<-> Relay
Pin # on the Relay
Port
Notes:
• Relay is DCE, PC is DTE
• Pins 1 and 6 are tied together internal to the relay
Male DB-9 Cable End for Relay
Port
Female DB-9 Cable End for
Computer Port
Pin # on Cable Pin # on Cable
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
2-10 F-PRO 5100 User Manual D02416R04.00
Page 25
2 Setup and Communications
Signal Name
DCD 1
RxD 2
TxD 3
DTR 4
Common 5
DSR 6
RTS 7
CTS 8
No connection 9
Direction
Modem <-> Relay
Pin # on the Modem
Ad
apter
Notes:
• Relay (with modem adapter) is DTE,
modem is DCE
• Pins 1 and 6 are tied together internal to the relay
D02416R04.00 F-PRO 5100 User Manual 2-11
Page 26
2 Setup and Communications

Maintenance Menu

The relay has a Maintenance Menu that can be accessed by connection through a VT-100 terminal emulator (such as the HyperTerminal program). Using ei­ther direct serial or modem connection:
1 Use the terminal program to connect to
2 Select Ent
Figure 2.5: Login prompt
3 Login as “maintenance” in lower case.
4 Relay responds with "password" prompt.
the serial port, either through direct
serial link or modem.
er, the relay responds with a login prompt.
Figure 2.6: Maintenance password prompt
5 Enter password.
6 A menu appears as below.
Figure 2.7: Maintenance menu
Commands 1, 4, 5, 6, 7 and 10 are Port 1 access only.
2-12 F-PRO 5100 User Manual D02416R04.00
Page 27
2 Setup and Communications

Firmware Update

Modify IP address Modifies the LAN IP address when equipped with an
View system diagnostic Displays the internal status log.
Retrieve system diagnostics Automatically packages up the inter
Restore settings Use this menu to force the system back to default values, if
Force hardware reset Manually initiates a hardware reset. Note that the communi-
View network statistics View IP, TCP and UDP statistics when equipped with inter-
Monitor SCADA Shows real time display of SCADA data.
Enable/disable Modem Enables or disables the internal modem.
optional internal 10BaseT Ethernet card.
nal status log plus set-
ting and setup information and downloads it in compressed
to your computer. This file can then be sent to our cus-
form tomer support to help diagnose a problem.
spect a problem due to the unit’s settings, calibration
you su and/or setup parameters.
cation link is immediately lost and cannot be re-established
e unit completes its start-up.
until th
nal 10BaseT Ethernet card.
The relay has an update login that can be accessed by a connection through a VT100 terminal emulator (such as HyperTerminal). This login is available only from Port 1.
1 Use the terminal program to connect to Port 1.
2 Select Ent
3 Login as update in
er, the terminal responds with a login prompt.
lower case.
4 Relay responds with "password" prompt.
Figure 2.8: Firmware Update password prompt
5 Enter password.
The firmware update is used to update
the relay’s software with maintenance or enhancement releases. Please see the B-PRO Firmware Update Procedure documentation that comes with the firmware update for instructions on how to update the firmware.
D02416R04.00 F-PRO 5100 User Manual 2-13
Page 28
Page 29

3 Using the IED (Getting Started)

F-PRO Feeder Protection Relay
Offline Mode - Settings Software
Online Mode - Terminal Mode
F-PRO
Feeder Protection Model 5100
Port 1
Date &
Time
View
Readings
View Logs
Prev
Next
Targ et
Clear Targ et
1999 JUN 07
Relay Functional IRIG-B Functional Service Required Test Mode Alarm

Start-up Sequence

The following initialization sequence takes place:
Test Mode—red LED on 2 seconds after power applied
Relay Functional—green LED on 5 seconds after power applied
Front Display—on 30 seconds after power applied
Test Mode—red LED off 40 seconds after power applied
When the relay is powered up, the normal sequenc
e of LED operation is Test Mode followed by Relay Functional and IRIG-B Functional (if available), dis­play on, then Test Mode off. The
entire sequence takes about 40 seconds.
Ways to interface with F-PRO:
• Front panel display
• Terminal Mode
• Offliner Settings software
D02416R04.00 F-PRO 5100 User Manual 3-1
Page 30
3 Using the IED (Getting Started)
Date &
Time
View
Readings
View Logs
Previous Next
Target
Clear
Target
Pri V 0.0 kV ph - ph I 0.0 A line
Display LED Lights
Push Buttons
Relay Functional
IRIG-B Functional
Service Required
Test Mode
Alarm

Front Panel Display

View or change settings using Terminal Mode or loading a setting file from Offliner Setting.

LED Lights

The front panel display is the fastest a
nd easiest way of getting information
from the relay.
Figure 3.1: Front Panel Display
The line display, the six LED lights and the six push buttons provide selective information about the relay.
Relay Functional
Indicates when the relay is functional. When the Relay Functional gre
en LED goes on, the rear Relay Inoperative contact changes to an
open and the protective functions become functional.
IRIG-B Functional Indicates the presence of a valid IRIG-B time signal.
Service Required Indicates the relay needs service. This LED can be the same state as
Test Mod e Occurs when the relay output contact
3-2 F-PRO 5100 User Manual D02416R04.00
Relay Functional LED or can be of the opposite state depending on
the the nature of the problem.
The following items bring up this LED:
• DSP failure - protection difficulties within the relay.
• Communication failure within the relay.
• Internal relay problems.
s are intentionally blocked.
Possible reasons are:
• Relay initialization on start-up
• User interface processor has reset and is being tested. You cannot communicate with the relay through the ports until the front display becomes a the red Target LED remains off after this start-up unless the relay had unviewed target messages.
Output contacts are controlled from the Util
ctive and the Test Mode LED goes out. Normally,
ities menu.
Page 31
3 Using the IED (Getting Started)

Push Buttons

ALARM Occurs when an enabled relay function picks up.
Target Indicates that a fault has taken place.
Date &Time Pressing the Date &Time button displays the date and time stored on
View Readings Pressing the View Readings button obtains metering information about
View Logs Pressing the View Logs button displays the target information if a relay
Previous/Next Scroll through the menu by pressing Previous and Next.
Clear Target When a fault takes place, the red target light appears. You can select a
The red Alarm LED should be off if there are no inputs to the relay. If the Alarm LED is on, check the e play by pressing the V
An event message with date and time is presented in the display.
the relay. If the time is incorrect, connect to a PC in Terminal Mode and go to Utilities>Setup>Time to make the change or connect to the IRIG­B plug at the back of the relay. The front display time and date is auto­matically updated.
The green IRIG-B Functional LED comes on. The relay accepts either modulated o IRIG-B such as time skew for different time zones are available when you establish communication with the PC.
the feed
oper
setting Clear Target button to view all target information. If many faults have been stored, you may need to push this button several times. Clearing the target light does not clear the target information from the relay log.
The relay holds all target messages during a pow and restart. Pressing the Clear Target push button displays any targets not previously viewed on the front display and clears the Target LED after the last target has been viewed.
Peak Demand Reset
Energy Reset
r unmodulated IRIG-B signals automatically. Options using
er, for details see “Display” on page 3-4.
ation has occurred, for details see “Display” on page 3-4.
option to reset the target light after a short time delay. Use the
iew Logs button.
vent log messages on the front dis-
er supply shutdown
D02416R04.00 F-PRO 5100 User Manual 3-3
Page 32
3 Using the IED (Getting Started)
Date &
Time
View
Readings
View Logs
Previous Next
Target
Clear
Target
2000 JUL 07 13:22:07
View Readings
View Logs
Pri V 0.0 KV ph–ph I 0.0 A line
2000Jun28 19:34:31.331 50LS-1 Main ABC: Trip

Display

Figure 3.2: Line Display Examples
Line Display Messages
PRI V, I, P, Q
Va, Ia magnitude and angle
Vb, Ib magnitude and angle
Vc, Ic magnitude and angle
3IO magnitude and angle
Frequency and THD
Power Factor
Fault location, trip date and time of all functions involved.
Peak Demand
Energy In and Out
3-4 F-PRO 5100 User Manual D02416R04.00
Page 33

Terminal Mode

3 Using the IED (Getting Started)
1 Establish terminal mode connection, for details see “Using HyperTerminal
to Access the Relay’s User Interface” on page 2-5.
2 Login as one of v
iew, breaker, change, service, breaker, or secadmin.
(lower case). These five login names provide different levels of permission.
3 When connection is established and the
terminal mode program appears on your screen, the following prompt should appear. If it doesn’t appear, press Enter.
4 If login is successful, the Main Menu appears as follows:
- for vie
w, change or service login
- for breaker login
- for secadmin login
5 If login is unsuccessful, the Status Message will appear as follows:
Unit allows 7 unsuccessful login attempts before locking out the Access Level for 5 minutes. Any attempts to login into locked out Access Level will fail. Ac­cess lockout and lockout period are Access Le
vel specific, i.e. if an Access
Level is locked out, the other Access Levels remain unaffected.
D02416R04.00 F-PRO 5100 User Manual 3-5
Page 34
3 Using the IED (Getting Started)
If the box around the menu does not appear as above, change the font in your terminal program to one that supports line draw charac­ters, e.g. terminal fonts.
If there are incorrect characters in the display, improper line feeds or
rased portions, the baud rate is too high for the quality of the com-
une munication link. Use the Util
ities>Setup>Ports menu to reduce the re-
lay’s baud rate. The new rate is in effect at the next connection.
The relay supports four user access levels that control what relay functions are available to you. The current access level is always shown in the centre of the Main Menu heading.
To change the Access Level either login again using the desired access level as yo
ur login name. To change between view, breaker, change and service Ac-
cess Level you can also use the Main Menu>Acce
ss menu.
Access level
view view lowest
change change middle
service service highest
breaker breaker middle
secadmin secadmin security
maintenance maintenance maintenance
update update update Firmware update
Login name
Level/ function
Authorized functions
View settings, on-line readings and logs and to list and u cannot affect the operation of the controller.
Do all of the above, plus change the set­tings and delete records.
Do all of the above 2 categories, plus cali­brate the analog inputs, manually control output auxiliar
View breaker log and breaker metering. Reset the breaker logic count and I2t val­ues.
Change passwords. View/change Syslog configuration.
Configure IP address, subnet mask, default gatew Restore default configuration/settings/cali­bration. Enable/disable modem. View/retrieve system diagnostics.
pload records. At this level you
y relays.
ay IP address.
Service access is only available through a local, front port connection (Port 1).

Login Passwords

Individual passwords for all Access Levels are available to prevent or limit ac­cess to the IED. Passwords are mandatory. Units arrive
from the factory with
default passwords installed. Default passwords are as follows:
3-6 F-PRO 5100 User Manual D02416R04.00
Page 35
Access Level/Login name Default password
3 Using the IED (Getting Started)
view
change
service
breaker
secadmin
maintenance
update
view
change
service
breaker
secadmin
maintenance
update
You can only change the passwords from the service level through the Access menu minimizing the chance that a password is changed casually and provides a means of resolving situations where a password has been forgotten.
The following rules are applied, when firmware is upgraded to a version with secadmin login for the first time
• the current password is preserved, if A
• a default password is assigned to an Access Level, if Access Level doe password assigned to/associated with it.
ccess Level has a password assigned to it;
s not have a
D02416R04.00 F-PRO 5100 User Manual 3-7
Page 36
3 Using the IED (Getting Started)

Terminal Mode Menus

Use the right and left arrow keys and the enter key to move around in the ter­minal mode screen. The mouse does not work in VT100 terminal mode. Items from the menu a tivating it using the <Enter> key. As a short-cut
re selected by moving the highlight to the desired item and ac-
, use the first letter of the menu
item to access it directly.
Key Function
<F2> Accept or Freeze or Execute
<F3> Quit or Exit
<F4> Copy Group
<Esc> Back to previous menu level
The menu tree consists of a series of sub-menus, for details see Figure 3.3: Terminal Mode Menus for view, change and service login on page 3-9.
The Enter key allows you to toggle through a abled. The Enter key toggles forward through the
list of selections, i.e. enabled/dis-
list, while the space bar moves backward through the list. In this manner you do not have to scroll through the entire list to get back to a previous selection, you can use the space bar.
For certain lists a pick box appears when there is a long list of selections to
e from, for example, ProLogic inputs. You can scroll though these boxes
chos with the arrow keys or the Enter key. Use the F2 key to make a selection or F3 to leave.
3-8 F-PRO 5100 User Manual D02416R04.00
Page 37
Calibrate
Main VA, VB, VC
Main IA, IB, IC,
Output Contacts
Aux IA, IB, IC.
Sync V
Toggle 1-12
Erase
Records
Event Log
Trends
Demand
Peak
Energy
Breaker
3 Using the IED (Getting Started)
VIEW
Access
Setup
Time
Setup
Event Log
List
Records
Analog
MeteringId QuitAccessUtilities
Access
CHANGE
BREAKER
Ports
SCADA
Maintenance
Diagnostics
Maintenance
Analog
Analog Inputs
Line Quantities
Demand
Fault
Trend
Recording
I/O
Logic
Access
d
Calibrate
Outputs
Control Virtual Inputs
Erase
Demand
Demand
Logic
Protection
I*I*t
Event
Recording
Energy
Peak
ProLogic
Setting Groups
Virtual Inputs
Recording
Diagnostics
Breaker Logic
F-PRO Settings
50/51
Transfer Diagnostics
Modbus
Protection Functions
50LS
50BF
50/51..
Identification
Relay
Comment
Analog Input Names
Identification..
F-PRO System Parameters
Setting Group 1
Setting Group 2
Setting Group 3
50/51
50N/51N
46-50/46-51
Sync Check & 79
25/27/59 Sync Check
79
Sync Check & 79..
5927608132
External Input Names
Output Contact Names
Setting Group 4
Setting Group 5
21P
Setting Group Names
Virtual Input Names
Setting Groups 1 – 8
Feeder Parameters
Setting Group 6
Setting Group 7
Setting Group 8
Recording
THD Alarm
Breaker Logic
Breaker Logic 1 – 10
ProLogic
ProLogic 1 – 10
Protection Functions..
Demand/Trend Metering
I*I*t
Breaker Logic..
ProLogic..
Group Logic..
Output Matrix..
Output Matrix #1 (50LS, 50BF, 25/27/59 Sync Check, 79)
Output Matrix #2 50/51, 50N/51N, 46-50/46-51)
Output Matrix #3 (32, 27, 59, 60, 81, THD, Aux Fail)
Output Matrix #4 (External Inputs)
Output Matrix #5 (ProLogic)
Output Matrix #6 (BkrLogic)
Output Matrix #7 (Virtual Inputs 1–15)
Group Logic
Group Logic 1 – 16
Output Matrix #8 (Virtual Inputs 16–30)
Settings
Active
Group
Load
Settings
from
Offliner
to
Offliner
Retrieve
Figure 3.3: Terminal Mode Menus for view, change and service login
D02416R04.00 F-PRO 5100 User Manual 3-9
Page 38
3 Using the IED (Getting Started)
Figure 3.4: Terminal Mode Menu for Breaker login
Figure 3.5: Terminal Mode Menus for secadmin login
3-10 F-PRO 5100 User Manual D02416R04.00
Page 39
3 Using the IED (Getting Started)
ID Settings Metering Records Event Log Utilities Access Quit

View, Change or Service Login

The Main Menu display for view, change or service login is:
ID Provides the device serial number, software version, required settings version,
nominal system values and external input board rating. There are no user set­tings here.
Settings Submenus: Active Group, Settings, Load from Offl
Allows input of all the setting informat menus to change relay setti
ngs related to protection functions, when settings
ion for the relay. Includes all the sub-
are changed they are not saved until you confirm the changes—Save and Load Setting Changes Now? [y/n].

Settings

Includes all the submenus to create a relay settings pertaining to protection functions. When these settings are made or changed, you can load them into the relay. Allows input of all settings information.
Settings submenus: Identification, F-PRO System Parameters, Setting Group 1 to 8, Recording.
Identification..
Relay Serial Number, Software Version, Relay ID, Line Name, Station
Name, Station Number and Location.
Comments Enter any appropriate comment.
Analog Input Names Name inputs, Main VA, VB, VC, Main IA, IB, IC, Aux IA, IB, IC, Sync
External Inputs Names
V.
Name external inputs 1 to 9.
iner, Retrieve to Offliner
Output Contact Names
Setting Group Names Name setting groups 1 to 8
Virtual Input Names Name virtual inputs 1 to 30
Name auxiliary relay output contacts 1 to 12.
The following characters are not allowed in the above setting parameters: “ ”, “\”, “/”, “:”, “*”, “?”, “|”, “"“, “<“, and “>”.
Load From Offliner
You can download the settings file into the relay using the terminal mode menu.
1 On the Window’s desktop, double-click F-PRO Of
initial Offliner Settings screen appears.
2 Enter the required settings.
3 Save the settings to a file on your PC.
D02416R04.00 F-PRO 5100 User Manual 3-11
fliner Settings icon. The
Page 40
3 Using the IED (Getting Started)
4 Start the Terminal Mode of F-PRO, login as change or service, then access
the Settings menu and activate Load from Offliner function.
5 Reply Yes to
6 In your terminal program, initiate transfer of
the “Ready to load remote setting.” prompt.
the setting file created in step 2 above. (For example, with Window’s HyperTerminal, you would select Transfer, then Send File. Browse to find the file, then select Open and fi­nally, Se
7 When the file has been transferred,
nd.
verified and loaded, a message “New
settings loaded and secure” is displayed.
A “serial number discrepancy” message may appear. This is to en­sure that you are aware of the exact relay to which the settings are being loade
d. If this happens, check the relay serial number using the terminal mode ID menu item. Type this serial number into the F-PRO Serial No. box in the Identification tab display area of Offlin-
tings. Alternately you may check the Ignore Serial Number
er Set check box to bypass serial number supervision.
Retrieve To Offliner
To transfer the relay’s current settings to the PC do the following:
1 Navigate to Se
2 Select Ent
ttings>Retrieve To Offliner.
er.
3 The relay asks you if you wish to continue. Select Y for yes.
4 The file is sent to the directory d
efined by the HyperTerminal menu Trans-
fer>Receive File.
When using HyperTerminal use Z-modem (no crash recovery), files are
received and auto incremented.

Metering Submenus: Analog, I/O, Logic, for more details about

metering see “Metering
Data” on page 3-17.
Analog
Analog Inputs Provides secondary values of the ac analog voltages and currents.
Line Quantities Provides primary voltage kV phase to phase of each line.
Demand Demand
I*I*t Displays the accumulated I*I*t value and I*I*t value for the last oper-
I/O
Logic
3-12 F-PRO 5100 User Manual D02416R04.00
Energy Peak
ation.
Displays the state of the external inputs and the output contacts.
Page 41
Protection Protection Functions.
3 Using the IED (Getting Started)
ProLogic Provides the present status of the internal logic states. When a logic
level becomes active, it
Setting Group Displays current active Setting Group and Group Logic.
Virtual Inputs Provides the present status of the virtual in
logic level becomes active, its state changes from low to high.
s state changes from low to high.
put logic states. When a

Records Submenus - List, Fault Recording, Trend Recording and Event Recording.

Contains the means for initiating
List Lists all records.
Fault Recording Creates fault records.
Trend Recording Creates trend records.
Event Recording Creates event records.
Retrieve Records from the Relay
and examining recordings.
To retrieve records from the relay do the following:
1 Navigate to Records>List and
2 Select Records using the s
press Enter; a records list appears.
pace bar and select R. (You can also press Enter to retrieve a record directly.) The record will be saved in the directory spec­ified by the terminal emulation program.
When using HyperTerminal if “Use receiving protocol:” is set to “Z modem with Crash Reco
very”, file transfers are skipped by Hyper-
Terminal if the record already exists in the downloads folder.
When using HyperTerminal use Z-modem (no crash recovery), files
received and auto incremented.
are
Delete Records from the Relay
To delete records from the relay do the following:
1 Navigate to Records>List and
2 Select the records for deletion with the space bar and select D. The sele
records will be deleted.

Event Log The event log lists events stored

events logged is available, for details see “Event Messages” in Appendix D.
If an event triggered a record, then an (R) is displayed by the event.
press Enter.
cted
in the relay. A complete list of the types of
D02416R04.00 F-PRO 5100 User Manual 3-13
Page 42
3 Using the IED (Getting Started)

Utilities Sub-menus: Setup, Maintenance, Diagnostics.

Setup
Time - set manual time, IRIG-B skew control. Requires change or service acce
ss level.
Maintenance
Diagnostics
Ports - change Baud rates on communication ports. Requires change or
SCADA – select which SCADA protocol (Modbus or DNP3) to run on the SC such as address or timeout. Requires change or service access level.
Calibrate – calibrate all 10 analog ac.
Outputs – close and open output contacts independent of the asso­ciated relay functions. Requires service access level.
Control Virtual Inputs – set, re-set and pulse width is 1 second. Latched virtual inputs reset after pulse command has executed. Requires change or access level.
Erase – use submenus Records and Event Log records from the relay memory. Reset Demand Metering, I
Breaker Logic counts. Requires change or service access level.
Transfer Diagnostics – transfers relay d diagnostic file can be sent to us for analysis.
service access level.
ADA port. Configure parameters for the selected protocol
Requires service access level.
virtual inputs. Pulse
s to erase these
iagnostic file to the PC. The
2
t and
Modbus – allows Modbus Communications to enter Mode. Follow directions on the screen. Programming done using the Modicon Modbus Protocol Reference Guide PI-MBUS-300 Rev. G published by Modicon, Inc., dated November 1994. For details see “Modbus RTU Communication Protocol” in Appendix E.
its Diagnostic
3-14 F-PRO 5100 User Manual D02416R04.00
Page 43
3 Using the IED (Getting Started)
Breaker Log Metering Reset Quit

Access Submenus: View Access, BREAKER Access, CHANGE Access.

view Changes the access level to view. Allows you read-only access to
relay information.
breaker Changes the access level to breaker.
change Changes the access level to change. Allows you to modify settings
and delete r
ecords.

Quit Selecting this option ends serial port communication with the relay.

Breaker Login

The Main Menu display for the breaker login is:
The Main Menu display for breaker login is:

Breaker Log The breaker log provides a log of breaker monitoring events.

Metering The metering quantities provided are breaker logic and I*I*t. F

tion of those quantities see “Breaker Logic” on page 4-15 and “I*I*t” on page 4-16.

Reset Use Reset to preset/reset the brea

Passwords

Password update
ker logic count and the I*I*t.
Password Update includes the submenus for all Access Levels passwords up­dates.
or an explana-
View
Change
Service
Breaker
Secadmin
Maintenance
Update
Password update for view login
Password update for ch
Password update for service login
Password update for b
PAssword update for secad
Password update for m
Password update for up
ange login
reaker login
min login
aintenance login
date login
D02416R04.00 F-PRO 5100 User Manual 3-15
Page 44

Syslog Syslog Configuration

Syslog Configuration submenu allows configuration of Syslog server commu­nication parameters as well as Syslog message (see section 8 “Cyber Security”).
selection of “Host Name” field value in the unit
Modes of Syslog server operation are defi
Mode Description
Disabled
UDP
Communication with Syslog server is disabled
UDP protocol is used for communication w
ned in the table below:
ith Syslog server
“IP Address” parameter defines Syslog server IP Address.
“Port” parameter defines Syslog server IP port for
receiving Syslog messages.
“Host Name” parameter values are as follows
Host Name Description
Unit IP Address
Unit Serial Number
Unit ID
Unit IP Address is used for Syslog message "Host Name" field
Unit Serial Number is used for Syslog message "H
Unit ID is used for Syslog message "Host Name" field
ost Name" field

Quit Selecting this option ends serial port communication with the relay.

Page 45

Metering Data

3 Using the IED (Getting Started)

Front Panel Metering

The quantities provided on the front panel display include:
• Positive sequence L-L voltage
• Positive sequence line current
• Line MW, MVAR
• Positive sequence frequency
• THD
• Power Factor
• Primary line to neutral voltages and currents
• Primary 3IO current
• Peak MW In/Out, MVAR In/Out, Ia, Ib, Ic
• MWh In/Out
• MVARh In/Out
All quantities are in primary unless otherwise noted.

TUI Metering The TUI provides the following metering quantities.

Analog/Analog Inputs
Displays all secondary values (magnitude and angle) of the voltage and current analog inputs.
Analog/Line Quantities
Displays the positive sequence L-L voltage, positive sequence line current, real and reactive power, positive sequence voltage frequency, THD, power factor and 3IO current. All values are in primary quantities. These are also available from the front panel.
Analog/Demand/Demand
Displays the current values of the demand metering quantities. Includes MW In/Out, MVAR In/Out, ABC phase voltages, ABC phase currents, frequency and THD, as well as, time of last reset.
Analog/Demand/Energy
Displays the current value of accumulated MWh and MVARh, as well as, the date of the last preset/reset.
Analog/Demand/Peak
Displays the peak value of the following quantities: MW In/Out, MVAR In/ Out, ABC phase feeder currents, as well as the time of occurence.
Analog/I*I*t
Displays the valus of I2t for the last breaker operation, the total accumulated
2
t, the last preset/reset I2t value and the accumulated I2t set limit for both the
I main and auxiliary breakers.
D02416R04.00 F-PRO 5100 User Manual 3-17
Page 46
3 Using the IED (Getting Started)
I/O
Displays the status of all external inputs and output contacts.
Logic/Protection
Displays the status of all internal logic, including alarm and trip states of all the relay elements.
Logic/ProLogic
Displays the status of all ProLogic.
Logic/Setting Groups
Displays the current active setting group as well as the current state of all the group logics.
Logic/Virtual Inputs
Displays the current state of all virtual inputs.
Logic/Breaker Logic
Displays the state of all breaker logics as well as the operation count. Also dis­plays the last time the count was preset/reset.
3-18 F-PRO 5100 User Manual D02416R04.00
Page 47

4 Protection Functions and Specifications

Protection and Recording Functions

This section describes the equations and algorithms that define the F-PRO pro­tection functions. The inverse time overcurren where their pickup level has been exceeded. Devices 27, 59, 50LS, 50BF, 81, 50, 50N, 46050, 32 and ProLogic have user-settable intentional delay. When an alarm occurs, the front alarm LED turns on and an output contact closes, if you have selected this option in the output matrix settings. The alarm indica­tion resets when the function is allowed to reset.
t functions have an alarm output

50/51/67 Phase Overcurrent

Phase Overcurrent provides protection to the line. You can define forward, re­verse or non-directional control on either 50 or 51 functions.
You can apply inverse and instantaneous ov
ercurrent protection on the line currents with this function. If ac current inputs are applied to the relay from ring bus breakers, this current is summated to represent the total line current and is used with this overcurrent function. You can set directional control of 50/51. If voltage is lost, the element becomes non-directional.
The fault location allows
Device 51 provides three IEC inverse time curve t
the function to initiate a fault location if it operates.
ypes, three IEEE inverse time curve types of overcurrent protection and one user-defined curve. The equation and the parameters of Device 50/51/67 are listed below.
ProLogic control can be used to supervise
the inverse time integration of the
51.
Table 4.1: IEC and IEEE Curves
# Characteristic A B p TR
1
2
IEC Standard Inverse 0.14 0 0.02 13.50
IEC Very Inverse 13.5 0 1.0 47.30
3
4
5
6
7
IEC Extremely Inverse 80.0 0 2.0 80.00
IEEE Moderately Inverse 0.0103 0.0228 0.02 0.97
IEEE Very Inverse 3.922 0.0982 2.0 4.32
IEEE Extremely Inverse 5.64 0.0243 2.0 5.82
User-defined
0.001 to
100.0
0.0 to
10.0
0.01 to
10.0
0.1 to
00.0
1
* These constants are copied from the IEEE standards; they are not given in the IEC standard.
D02416R04.00 F-PRO 5100 User Manual 4-1
Page 48
TI TMS B
A
I
Pickup
------------------


p
1–
-----------------------------------
+=
TI
TR
I
Pickup
------------------


2
1–
-----------------------------------
TMS
=
4 Protection Functions and Specifications
For I > pickup For I < pickup
50/51 Phase Overcurrent
50 Enable/disable
Directional Forward, reverse, non-directional
Pickup 0.25 to 50.00 (5 A)
Pickup Delay 0.01 to 99.99 seconds
0.05 to 10.00 (1 A)
0.00 to 99.99 (non-directional)
51 Enable/disable
Directional Forward, reverse, non-directional
Pickup 0.25 to 50.00 (5 A)
Curve Type For details see “IEC and IEEE Curves” on page 4-1
TMS 0.01 to 10.00
A 0.0010 to 1000.0000
B 0.0000 to 10.0000
p 0.01 to 10.00
TR 0.10 to 100.00
Initiate Fault Location Enable/disable
ProLogic Control Enable/disable
0.05 to 10.00 (1 A)
4-2 F-PRO 5100 User Manual D02416R04.00
Page 49
4 Protection Functions and Specifications
T 3 I0TMS A
B
3I 0
IPickup
--------------------


p
1–
--------------------------------------
+=
T 3 I0TMS
TR
3IO
IPickup
--------------------


2
1–
--------------------------------------
=

50N/51N/67 Neutral Overcurrent

Neutral overcurrent provides protection for line-to-ground faults. You can de­fine forward, reverse or non-directional control on either 50N or 51N func­tions. All the curve definitions are the
same as the phase overcurrent except
that this function uses 3I0 rather than phase current. The equation is:
For 3I0 > pickup For 3I0 < pickup
The Curve Type selection allows you to use a number of curves available in this menu. All of these curve types are generated by the equation shown at the bottom of the screen. If you choose a user-selectable curve, it can be created using the parameters A, B and p.
The characteristic of the overcurrent function ca
n be rescaled by clicking on the characteristics using the right mouse key and by making a box around the area of interest. The characteristic can be printed by pressing the Print Graph option.
50N/51N Neutral Overcurrent
50N Enable/disable
Directional Forward, reverse, non-directional
Pickup 0.25 to 50.00 (5 A)
Pickup Delay 0.01 to 99.99 seconds
51N Enable/disable
Directional Forward, reverse, non-directional
Pickup 0.25 to 50.00 (5 A)
Curve Type For details see “IEC and IEEE Curves” on page 4-1
TMS 0.01 to 10.00
A 0.0010 to 1000.0000
B 0.0000 to 10.0000
p 0.01 to 10.00
TR 0.10 to 100.00
Initiate Fault Location Enable/disable
ProLogic Control Enable/disable
0.05 to 10.00 (1 A)
0.00 to 99.99 (non-directional)
0.05 to 10.00 (1 A)

46/50/51/67 Negative Sequence Overcurrent

D02416R04.00 F-PRO 5100 User Manual 4-3
Negative Sequence Overcurrent provides protection for any unbalanced faults.
nctions 46-50/46-51/67 are similar to 50N/51N/67 except they use negative
Fu
Page 50
4 Protection Functions and Specifications
TI2 TMS B
A
I2
Pickup
------------------


p
1–
-----------------------------------
+=
TI2 TMS
TR
I2
Pickup
------------------


2
1–
-----------------------------------
=
sequence current to drive their algorithms. You can define forward, reverse or non-directional control on either 46-50 or 46-51 functions. All the curve defi­nitions are the same as the P function uses the negative sequence current (I2) rather than phase current. The equation is:
For I
46-50/46-51N Negative Sequence Overcurrent
46-50 Enable/disable
Directional Forward, reverse, non-directional
Pickup 0.25 to 50.0 (5 A)
hase Overcurrent. The only difference is that this
> pickup For I2 < pickup
2
0.05 to 10.0 (1 A)
Pickup Delay 0.01 to 99.99 seconds
46-51 Enable/disable
Directional Forward, reverse, non-directional
Pickup 0.25 to 50.0 (5 A)
Curve Type For details see “IEC and IEEE Curves” on page 4-1
TMS 0.01 to 10.00
A 0.0010 to 1000.0000
B 0.0000 to 10.0000
p 0.01 to 10.00
TR 0.10 to 100.00
Initiate Fault Location Enable/disable
ProLogic Control Enable/disable
0.00 to 99.99 (non-directional)
0.05 to 10.0 (1 A)
4-4 F-PRO 5100 User Manual D02416R04.00
Page 51
4 Protection Functions and Specifications

50LS Low Set Overcurrent

F-PRO provides 2 sets of definite time delay overcurrent protection functions on each breaker: 50LS-1 Main, 50LS-2 Main, 50LS-1 Aux and 50LS-2 Aux. You can set the logic gate to either an AND or an OR gate to detect all 3 phases or any phase (of the 3 phases) overcurrent conditions. The definite time delay can be set to 0.0 for a instantaneous trip.
Auxiliary definite time delay functions are available to monitor main and aux­iliary CT currents.
50LS-1 Main
50 IMainA 50 IMainB 50 IMainC
50LS-1 Aux
50 IAuxA 50 IAuxB 50 IAuxC
101
105
100
104
T
T
Figure 4.1: 50LS Low Set Overcurrent
50 Low Set Overcurrent
50LS-2 Main
50 IMainA 50 IMainB 50 IMainC
O
50LS-2 Aux
50 IAuxA 50 IAuxB 50 IAuxC
O
102
103
106
107
T
O
T
O
50LS Main Enable/disable
Pickup 0.1 to 50.0 amps (5 A)
0.02 to 10.00 amps (1 A)
Pickup Delay 0.00 to 99.99 seconds
50LS Aux Enable/disable
Pickup 0.1 to 50.0 amps (5 A)
0.02 to 10.00 amps (1 A)
Pickup Delay 0.00 to 99.99 seconds
D02416R04.00 F-PRO 5100 User Manual 4-5
Page 52
4 Protection Functions and Specifications
50 IMainA (fixed 0.2 amps) 50 IMainB (fixed 0.2 amps) 50 IMainC (fixed 0.2 amps)
T1
0
108
109
Breaker failure Initiator (from Output Matrix)
T2
0
Output1
Output2
50 IAuxA (fixed 0.2 amps) 50 IAuxB (fixed 0.2 amps) 50 IAuxC (fixed 0.2 amps)
T1
0
110
111
Breaker failure Initiator (from Output Matrix)
T2
0
Output1
Output2

50BF Breaker Failure

There are two sets of breaker failure pro 50BF Auxiliary – one for each breaker. When breaker failure is initiated by a trip or other internal logic (user-settable through the output matrix) and the breaker current still exists, two timers (T1 and T2 – user-settable) are started. After these timers are timed out, and if the current still exists indicating a breaker failure, the output of this function is set high. Use the two outputs of this function to trip another trip coil or the next level of breakers, such as bus breakers. The breaker failure protection logic diagram is shown below. Phase current supervision is fixed at 4% of I nominal and is shown for a 5 A relay.
Figure 4.2: 50BF Main Breaker Failure
tection functions, 50BF Main and
Figure 4.3: 50BF Aux Breaker Failure
50BF Breaker Failure
Main Enable/disable
Pickup Delay 1 0.01 to 99.99 seconds
Pickup Delay 2 0.01 to 99.99 seconds
Auxiliary Enable/disable
Pickup Delay 1 0.01 to 99.99 seconds
Pickup Delay 2 0.01 to 99.99 seconds
4-6 F-PRO 5100 User Manual D02416R04.00
Page 53
4 Protection Functions and Specifications
Z
posmem
V
posmem
I
pos
---------------------
=
R
jx
Forward
Reverse
90°
Line Z Angle
Line Impedance

Directional Element The directional element of F-PRO uses the memory-polarized, voltage-based

positive sequence impedance (Z
pos mem
) to determine the fault direction.
This impedance is defined as:
where V
is the memorized positive sequence voltage calculated from the
pos mem
polarization voltage signals, Figure 4.5: Effect of the Ring Filter on page 4-7, and I
is the positive sequence line current.
pos
Va
Vb
Vc Vc_polarization
Figure 4.4: Vpos_mem Calculation
Ring Filter
Ring Filter
Ring Filter
Va_polarization
Vb_polarization
Sequence
Component
Filter
Vpos_mem
The effect of the Ring Filter (implemented in software) is to retain voltage in­formation even if the voltage is
severely depressed by a fault.
Fault
Voltage
Ring Filter
Memory Voltage
Figure 4.5: Effect of the Ring Filter
D02416R04.00 F-PRO 5100 User Manual 4-7
Figure 4.6: Directional Element
Page 54
4 Protection Functions and Specifications
The principle of the directional element is shown above. If Z
pos mem
falls into the light gray area, Forward, it indicates a forward fault; and if it falls into the dark gray, Reverse area, a reverse fault is declared.
This directional element is used for directional overcurrent protection. No user settings are needed for this function.
Directional Control for Overcurrent Functions in F-PRO
The positive sequence memory voltage is also used to provide directional con­trol to the overcurrent functions within the F-PRO relay. In this case, the pos­itive sequence memory voltage and the positive sequence line current difference angles are compared to determine the directionality. For example, if the relay is set to directional mode, it allows the overcurrent function to operate if fault currents are towards the line and directions within 90 degrees of the line angle. For details see
Figure 4.6: Directional Element on page 4-7.
For the directional control used on the overcurrent relays, a 30 cycle memory action is used on the positive sequence voltage. This memory action takes place only if a fault causes the positive sequence memory voltage to be above 2 volts secondary within the relay. If the positive sequence memory voltage goes below 2 volts, the directional control of the overcurrent reverts to a non directional characteristic, allowing it to operate and trip. For system faults that are not bolted three-phase faults that cause all phase-to-neutral voltages to go to zero, directional control are maintained because the positive sequence volt age does not go to zero.
-

25/27/59 Sync Check The relay can bring in voltages from both line and bus PTs. The Sync Check

function, if enabled, looks at the voltage steady state angle between the bus and the line PT voltage. If this angle is within a plus/minus specified value, (+/- 1 to 50 degree magnitude range of setting available), the function enables a def inite time delay pickup (user-selectable 0 to 99.99 seconds) after which time an output is produced. The line sync reference voltage is taken from a bus and/ or a line source; F-PRO uses one single-phase-to-neutral voltage. Settings within the relay allow the single-phase quantity to be offset from Phase A of the line PT by 0 to 330 degrees in 30 degree increments. The Dead Main Live Sync, Live Main De ad Sync and Dead Main Dead Sync l og ic functions can u se fixed values of main and sync positive secondary voltages to determine the sync check condition. The voltage is fixed at 20 volts secondary, voltages be low 20 volts are declared a dead state and voltages above 20 volts are declared a live state.
When enabled, this function checks that the voltage angle between the Main ac volts PT and bus sync ac volts PT voltages are within a specified value. Use this function to ensure that closing a line to a system results in acceptable pow er flow. The function uses three voltages from the Main PT and a single voltage from the Sync PT to make the angle measurement.
The dead main dead sync logic is based on fixed voltages less than 20 volt sec­onds. i.e. The line or bus is declared dead if its voltage is less than that value. The Sync PT Phase is settable in System Parameters from 0 to 330 degrees in steps of 30 degrees.
-
-
-
4-8 F-PRO 5100 User Manual D02416R04.00
Page 55
4 Protection Functions and Specifications
126
50 Ia main 50 Ib main
79 Block (Output Matrix)
50 Ic main
(Low set 0.2A fi xed)
123
51 Alarm
51N Alarm
51/46 Alar m
146
Sync Control (setting)
134
130
127
128
124
79 Initiator (output matrix)
125
0
TDI
Immediately Bl ock the Whole Functi on All timer and Output are reset to 0, i.e. Reset to the initial condition
+
T1
TD
0
TDB
Enable
0
TD
TP
0
142
135
131
T2
TD
Enabl e
TP
0
143
138
139
136
132
129
T3
TD
Enabl e
TP
0
144
140
137
133
130
T4
TD
Enable
TP
0
144
140
25/27/59 Sync Check
25 Sync Check Enable/disable
Maximum Voltage 60.0 to 138.0 volts secondary

79Main/79Aux Recloser

Minimum Voltage 40.0 Mi
nimum Voltage Maximum Voltage -0.1
115 volts secondary
Angle Difference 1.0 to 50.0 degrees
Pickup Delay 0.00 to 99.99 seconds
Main/Aux
Enable Dead Main Live Aux. (DMLA) Enable/disable
Enable Live Main Dead Aux. (LMDA) Enable/disable
Enable Dead Main Dead Aux. (DMDA) Enable/disable
F-PRO includes a four shots recloser with sync check supervision. After four tries, the recloser is locked out until the feeder returns to normal by manual op­eration. i.e. The feeder has been on with a load greater than the low set setting
r a certain amount of time.
fo
79Main and 79Aux are identical except the
inputs are different. For device 79
initiate and block functions are defined in the output matrix.
Ring bus applications provide two
separate reclosers.
Figure 4.7: 79 Main Recloser
D02416R04.00 F-PRO 5100 User Manual 4-9
Page 56
4 Protection Functions and Specifications
59 Va Main 59 Vb Main 59 Vc Main
T
O
OR
Gate Switch (Setting)
AND
79 Recloser
79 Recloser
Number of Shots 1 to 4
First Reclose (T1) 0.02 to 99.99 seconds
Second Reclose (T2) 1.00 to 99.99 seconds
Third Reclose (T3) 1.00 to 99.99 seconds
Fourth Reclose (T4) 1.00 to 99.99 seconds
Close Time (Tp) 0.01 to 1.00 seconds
Lockout Time (TD) 0.00 to 99.99 seconds
Initial Reset (TDI) 0.00 to 99.99 seconds
Block Reset (TDB) 0.00 to 99.99 seconds
Sync Control Enabled Enable/disable
Enable/disable
59 Overvoltage The F-PRO has a definite time delay main overvoltage function. This function
looks at all three phase-to-neutral voltages to determine an overvoltage condi­tion. The logic gate can be set to either
AND or OR gate to detect all 3 phase or any phase (of the 3 phases) overvoltage conditions. The definite time delay can be set to 0.0 for a instantaneous trip.
4-10 F-PRO 5100 User Manual D02416R04.00
Figure 4.8: 59 Overvoltage

59 Overvoltage

59-1 Enable/disable
Gate Switch AND or OR
Pickup 1.0 to 138.0 volts
Pickup Delay 0.00 to 99.99 seconds
59-2 Enable/disable
Gate Switch AND or OR
Pickup 1.0 to 138.0 volts
Pickup Delay 0.00 to 99.99 seconds
Page 57
4 Protection Functions and Specifications
27 Va Main 27 Vb Main 27 Vc Main
T
O
OR
Gate Switch (Setting)
AND
207
206
197
10 s
0.0
59 VMainA (fixed 0.5 PU) 59 VMainB (fixed 0.5 PU) 59 VMainB (fixed 0.5 PU)
Loss of Potential
27 Undervoltage The F-PRO has a definite time main undervoltage function. The function looks
at the phase-to-neutral voltage of all three phases to make a determination of an undervoltage condition. The logic gate can be set to either AND or OR gate to detect all 3 phase or any phase (of the 3 phases) undervoltage conditions. The definite time delay can be set to 0.0 for a instantaneous trip.
Figure 4.9: 27 Undervoltage

27 Undervoltage

27-1 Enable/disable
Gate Switch AND or OR

60 Loss of Potential

Pickup 1.0 to 120.0 volts
Pickup Delay 0.00 to 99.99 seconds
27-2 Enable/disable
Gate Switch AND or OR
Pickup 1.0 to 120.0 volts
Pickup Delay 0.00 to 99.99 seconds
Figure 4.10: 60 Loss of Potential
This function detects the loss of potential from either one or two phases of a PT and issues an alarm.
60 Loss of Potential Enable/disable
D02416R04.00 F-PRO 5100 User Manual 4-11
Pickup Delay 10.00 seconds fixed
Page 58
4 Protection Functions and Specifications
T
O
Frequency (Hz)

81 Frequency

The relay has four frequency devices available set to operate either at a fixed level of under-frequency, a fixed level of over­frequency or at a rate of change level (df/dt). The df/dt function can be set to operate for a positive rate of change or a negative rate of change. Each frequen­cy element has a definite time delay setting to create fixed level of positive sequence voltage of 0.25 pu or 5 volts whichever is greater provides an undervoltage inhibit on each element.
Four frequency elements are provided, se fixed level to rate of change.
Figure 4.11: Frequency Fixed Level
df/dt (Hz/s)
Figure 4.12: Frequency Rate of Change
. Each frequency element can be
a time delayed output. A
ttable from over/under frequency,
T
O
81 Over/Under Frequency
81-1 Disabled/Fixed Level/Rate of Change
Pickup 50.000 to 59.995 or 60.005 to 70.000 (fixed level)
-10.0 to -0.1 or 0.1 to 10.0 (rate of change)
Pickup Delay 0.05 to 99.99 seconds (fixed level)
0.20 to 99.99 seconds (rate of change)
81-2 Disabled/Fixed Level/Rate of Change
Pickup 50.000 to 59.995 or 60.005 to 70.000 (fixed level)
-10.0 to -0.1 or 0.1 to 10.0 (rate of change)
Pickup Delay 0.05 to 99.99 seconds (fixed level)
81-3 Disabled/Fixed Level/Rate of Change
Pickup 50.000 to 59.995 or 60.005 to 70.000 (fixed level)
Pickup Delay 0.05 to 99.99 seconds (fixed level)
81-4 Disabled/Fixed Level/Rate of Change
Pickup 50.000 to 59.995 or 60.005 to 70.000 (fixed level)
Pickup Delay 0.05 to 99.99 seconds (fixed level)
0.20 to 99.99 seconds (rate of change)
-10.0 to -0.1 or 0.1 to 10.0 (rate of change)
0.20 to 99.99 seconds (rate of change)
-10.0 to -0.1 or 0.1 to 10.0 (rate of change)
0.20 to 99.99 seconds (rate of change)
4-12 F-PRO 5100 User Manual D02416R04.00
Page 59
4 Protection Functions and Specifications

32P/32Q Directional Power

F-PRO provides directional real power and reactive power protection. Set the pickup setting to a positive value (trip on forward power flow away from bus) or a negative value (trip on reverse power flow into bus).
You can set either a real (32P) and a re
active (32Q) direction. The values are set by specifying the pickup current. This value is set to positive values to de­tect power flow from the bus and to negative values to detect power flow
into
the bus.
32 Directional Power
32P Enable/disable
Pickup [-15.00, -0.25] to [15.00, 0.25] A (real)
Pickup Delay 0.00 to 99.99 s
32Q Enable/disable
Pickup [-15.00, -0.25] to [15.00, 0.25] A (reactive)
Pickup Delay 0.00 to 99.99 s

21P Phase Distance The relay has two mho phase distance elements. Each element includes a for-

ward reach and delta current supervisor setting. The
element output is only
available as a ProLogic.
21 Phase Distance
21P Enable/disable
Forward Reach 0.05 to 66.00 ohms
Delta Current Supervision 0.2 to 50.0 A
THD Alarm This function checks and picks the highest THD in any of the six current inputs
(if ring bus configuration is enabled). It only checks the three main current in­puts for highest THD, if ring bus configuration is disabled.

THD Alarm

THD Alarm Enable/disable
Pickup 5.0 to 100.0%

Fault Locator When a fault occurs and the line trips, the fault locator calculates the fault type

and the distance to the fault. This information is available from the front dis­play of the relay or through terminal UI,
or SCADA. Enable or disable the fault locator through 50/51, 50N/51N and 46/50/51 respectively. Define the func­tions initiating the fault location when sett
ing.
D02416R04.00 F-PRO 5100 User Manual 4-13
Page 60
4 Protection Functions and Specifications
T
O
A
B
C
D
E
Op 1
Op 2
Op 3
Op 4
Op 5

ProLogic ProLogic Control Statements

Using ProLogic, F-PRO can pick any of the protection functions or external in­puts and place them into Boolean-like statements functions to generate one ProLogic statement; ten statements are possible. The results from these statements are mapped to output contacts using the output matrix.
Special ProLogic inputs are:
• Output relay #12 as an input to ProLogic.
The ProLogic control statements are PRO can use any of the protection functions or external inputs combined with logic gates to create a ProLogic control statement. The possible gates are AND, NAND, OR, NOR, XOR, NXOR, and LATCH. The control can be time delay pickup and or time delay dropout, and can drive the front panel target LED. Ten ProLogic control statements outputs are available and can be used in the output matrix to customize the relay to your specific needs. Inputs to ProLogic are all the elements plus previous ProLogic statements for logic nesting usage.
The example shows A to E inputs are status lectable. Each ProLogic output can be given a s time delay.
. ProLogic handles up to five
used to create Boolean-like logic. The F-
points of devices that are user-se-
pecific name, pickup and reset
Figure 4.13: ProLogic
ProLogic Setting Functions
Name Give the ProLogic a meaningful name
Pickup Delay Delay time from pickup to operate
Dropout Delay Delay time from dropout to a ProLogic status of low
A, B, C, D, E Relay elements as input statements
Operators Boolean-type logic gates
4-14 F-PRO 5100 User Manual D02416R04.00
Page 61
4 Protection Functions and Specifications

Breaker Monitoring The F-PRO breaker monitoring feature allows you to monitor the feeder break-

er(s) in detail. An accumulated I*I*t function
and ten user-definable logic statements can be used to determine the status of breaker wear and breaker per­formance.
Breaker monitoring can be configured for me anism time, trip coil energized time, operations count, fault operatio
asuring the clearing time, mech-
ns or other user-defined conditions. Different users may require different feature sets to monitor the breaker. The breaker monitoring functions are realized through the Breaker Logic functions.
All associated breaker monitoring values are
available in the terminal UI and SCADA interfaces. You can reset or preset all associated breaker monitoring values from the terminal UI interface. You can only reset all associated breaker monitoring values from the terminal SCADA interfaces.
Breaker Logic
The Breaker Logic function is similar to a ProLogic function, but includes some additional features specifically for breaker monitoring allowing different users to design their own breaker monitoring features by building different breaker logic statements. Breaker Logic has additional timers on every output of the logic statement, a total of four timers are available; a counter (including settable count limit) is available in the last logic gate position. The front panel Alarm LED can be enabled, and the logged message can be configured either when one of the four timers has expired or when the counter limit has been ex­ceeded. A total of 10 Breaker Logic functions are
available in the F-PRO.
The terminal UI and SCADA interfaces shows the status of each breaker logic and associate
d counter. The terminal UI also includes the time of last reset/pre-
set.
Figure 4.14: Breaker Logic
For examples of breaker condition monitoring using Breaker Logic see “Set­ting Examples” in Appendix L.
D02416R04.00 F-PRO 5100 User Manual 4-15
Page 62
4 Protection Functions and Specifications
I*I*t
F-PRO has an accumulated I2t function used for monitoring the wear of the breaker due to fault interruption. This function is available for both the main breaker and the auxiliary breaker. The I ation and stored in the non-volatile memory; seconds. A fixed maximum write time of 20 seconds prevents the I from constantly writing to non-volatile memory. Therefore if the start signal is held on for longer than 20 seconds the accumulator will stop accumulating and stop writing to the flash memory. The output I in the event log, the output is not available in the output matrix or in the Pro­Logic input list.
The terminal UI and SCADA interfaces will show the accumulated value of eac include the time of last reset/preset.
The following figure shows the I is started when the trip coil of the breaker is energized (breaker starts to open), and will be stopped when the trip coil of the breaker is de-energized. The cur­rent that is used for accumulation is the and C. An event message will be generated when the accumulated I above the limit.
h breaker I
2
t value is accumulated for every oper-
the write time interval will be 0.5
2
t function
2
t function will only be available
2
t function and value of last operation. The terminal UI will also
2
t function's logic diagram. The accumulation
maximum current among Phase A, B
2
t value is
EI/PL For Trip Coil Energi zation
Logic 1 enabl es accumulati on to occur
Figure 4.15: I*I*t
IA
IBICMAX
enable accumulation
I^2T Accumulator
Read
FLASH
Wr i t e
4-16 F-PRO 5100 User Manual D02416R04.00
Page 63

Demand Metering

The F-PRO has a demand metering feature which calculates the following quantities:
• 3 phase real power send (MW)
• 3 phase real power receive (MW)
• 3 phase reactive power send (MVAR)
• 3 phase reactive power receive (MVAR)
• A Phase Current (A Pri)
• B Phase Current (A Pri)
• C Phase Current (A Pri)
• A Phase Voltage (V Pri, L-N)
• B Phase Voltage (V Pri, L-N)
• C Phase Voltage (V Pri, L-N)
• Frequency (in Hz)
• THD (in%)
You can select from three calculation types, integrating, rolling and thermal. They are
4 Protection Functions and Specifications
described in detail below.
Figure 4.16: Integrating Demand Meter
Integrating demand meter is a linear average of the quantity over the demand interval. Each new value only becomes available at the end of each time inter­val. The average is calculated from samples
taken every 0.5 seconds during the demand interval. Therefore, the equation for calculating what the demand quantity will be is based on the following equation:
New demand value = Sum of the samples during the demand interval / (120*Demand Interval Setting)
1.0 PU
01 23 45
Figure 4.17: Step Power Input
time(minutes)
D02416R04.00 F-PRO 5100 User Manual 4-17
Page 64
012345
time(minutes)
1.0 PU
4 Protection Functions and Specifications
time(minutes)
1.0 PU
01234
5
Figure 4.18: Integrating Demand Meter
Figure 4.17: Step Power Input on page 4-17 shows the input signal, which is a magnitude of zero and then suddenly goes to an instantaneous level unit, i.e. a step change function.
Figure 4.18: Integrating Demand Meter on page 4-18 shows the integrating de­mand meter, i.e. the demand val end of the demand interval (setting, it's 5 minutes for this example). The re­sponse for integrating demand meter is shown in the
Time (min.) 1 2 3 4 5 6
Demand (% of Input) 0 0 0 0 100 100
of 1.0 per
ue will not be calculated or updated until the
following table:

Rolling Demand Meter

Rolling demand, also called “sliding window”, is a process by which intervals are divided into a fixed number of subintervals. Instead of calculating demand only at the end of each interval, the calculation is performed at the end of each subinterval, and totaled and averaged for the interval. The subinterval is 1 min­ute (fixed) in F-PRO relay. The calculation is the same
as the Integrating De-
mand Meter.
Figure 4.19: Rolling Demand Meter on page 4-18 shows the rolling demand meter response to the input of Figure 4.17: Step Power Input on page 4-17. The demand value is calculated and updated on each subinterval (one minute). The average ca
lculation is performed over the demand internal (setting, equal 5 minutes for this example). The response to the input shown in figure 1 for roll­ing demand meter is shown in the f
Time (min.) 1 2 3 4 5 6
Demand (% of Input) 20 40 60 80 100 100
ollowing table:
Figure 4.19: Rolling Demand Meter
4-18 F-PRO 5100 User Manual D02416R04.00
Page 65
4 Protection Functions and Specifications

Thermal Demand Meter

The thermal demand meter is described in this section. Again, use the step change power input from Figure 4.17: Step Power Input on page 4-17 as an ex­ample.
1.0 PU
0.90 PU
time(minutes)
01234
Figure 4.20: Thermal Demand
R
Vin
Figure 4.21: RC Circuit
5
C
Vout
Figure 4.20: Thermal Demand on page 4-19 shows the thermal model of de­mand calculation. It acts like a RC circuit as shown in Figure 4.21: RC Circuit on page 4-19. The output voltage will never reach the final value until the ti goes to infinity, however, we define it in this way i
t will reach the 90% of the
me
input when the elapsed time is equal to the Demand Interval (5 minutes for this example). The thermal demand will reach 99% of the input when the time is twice of the demand interval, as shown in the table below. The equation for this response is Vout = Vin*(1-e-t/), where  is the time constant and it is equal to
2.17147241 minutes. The thermal demand meter data will be calculated and updated every half-second. The following table shows the response of the ther­mal demand.
Time (min.) 1 2 3 4 5 6 7 8 9 10
36.9 60.1 74.8 84.1 90 93.6 96 97.4 98.4 99

Peak Demand Quantities

Demand (%
f Input)
o
Peak Demand quantities will be derived from the Demand/Trend quantities. A total of 7 Peak Demand Quantities will be metered:
• 3 Phase Real Power Out (MW)
• 3 Phase Real Power In (MW)
• 3 Phase Reactive Power Out (MVAR)
• 3 Phase Reactive Power In (MVAR)
• A Phase Feeder Current IA (A Pri)
• B Phase Feeder Current IB (A Pri)
D02416R04.00 F-PRO 5100 User Manual 4-19
Page 66
4 Protection Functions and Specifications
• C Phase Feeder Current IC (A Pri)
The peak demand quantities are available from the front panel display, the TUI metering and SCADA. Peak Demand quantities can be reset from the front panel, TUI or SCADA. The peak value of the above quantities and the time of occurrence are displayed.

Accumulated Energy (kWh, kVARh metering)

For the accuracy and the consistency, the method of the energy calculation is the same regardless of the demand type. (rolling, integration, thermal). There are four accumulated energy quantities. They are:
• 3 Phase real energy OUT (MWh)
• 3 Phase real energy IN (MWh)
• 3 Phase reactive energy OUT (MVARh)
• 3 Phase reactive energy IN (MVARh)
The accumulated energy quantities are calculated by the integration of the av­erage power over the elapsed time. This calculation is carried out once per min­ute, however the actual power is sampled every half second and averaged every minute (120 samples).
The accumulated energy quantities are stored in the non-volatile memory to avoid the data loss on power down.
When the accumulated energy quantities exceed 98000 MWh/MVARh they are reset to zero. A reset on one energy quantity will only reset it's own value, not the other energy quantities. All reset actions will be logged in the event log.
4-20 F-PRO 5100 User Manual D02416R04.00
Page 67

Group Logic Group Logic Control Statements

The F-PRO relay has eight setting groups (SG). You can change all relay set­ting parameters except the physical connections such as input or output param­eters in each setting group. Setting group changes are performed by using any one of the 16 available Group Logic statements per setting group. The Group Logic statements are similar to the ProLogic statements with the following ex ceptions—the sole function is to activate one of the eight setting groups and the processing is in a slower half second cycle. Group Logic input statements are driven from ProLogic, any external input, previous Group Logic statements or virtual inputs. Each Group Logic statement includes five inputs (with Boolean statements), one latch state and one pickup delay timer. The active setting group (ASG) is viewed from the Terminal Mode, the front panel or from a re cord stored by the relay (the active setting group is stored with the record).
Group Logic Processing
The sixteen Group Logic statements reside in a slower processing thread with­in the relay protection algorithms. The processing cycle happens once every half second (0.5 second). When using ProLogic statements remember that a latch or dropout timer should be used if the initiating condition does not last at least 0.5 seconds. In the example following, we will create a definite pulse length using ProLogic. For details see L.
4 Protection Functions and Specifications
-
-
“F-PRO Setting Example” in Appendix
Default Setting Group
The relay uses Setting Group 1 as the factory default setting group and retains the current active setting group in memory. This allows the relay to use the last active setting group prior to interruption of relay power as the default setting group following power up.
D02416R04.00 F-PRO 5100 User Manual 4-21
Page 68
4 Protection Functions and Specifications
Active Group
Screen
Change or Service
View
Access
Level
F2
Yes
Validate User I/P
Invalid
Error
Msg
Any Key
Valid
View Only ­select <F2>
or <F3> to
continue
Confirm
Setting
Change
ASG
modied
System
refreshes AG
Screen
No
System
changes AG
Yes
System cancels
AG change
No
Quit
Settings
User
Decision
Satus
Msg
Any Key
Change Active Group
You can at any time change the active setting group. When you initiate a set­ting group change, this change group change. The terminal UI is used to change the active setting group. To view a snapshot of the group logic data select F2 prior to making any modifi­cation to the Active Setting Group input. The following is the flow of events that
takes precedence over an automatic setting
can occur in the Active Group Screen.
4-22 F-PRO 5100 User Manual D02416R04.00
Page 69
4 Protection Functions and Specifications
s
Settings Saved
You can change the active setting group while saving setting changes or load­ing settings from Offliner. The relay prompts you for vate— you can keep the current setting group or
a setting group to acti-
switch to a new setting group
following the settings save.
The following is the flow of
events that can occur in the Editing Settings
Screen.
Edit
Settings
B
Access
Level
View
<F3> Quit
<Enter> view
Change or Service
Exit
Select Copy
Group
System
opens Copy
SG Screen
CR or Space
System
updates Copy
SG x to SG y and waits for
User I/P
System cancels
SG x to SG y
No
System copies
SG x to SG y
Copy
group
Confirm
Setting
Copy
Yes
Quit
User
Selects
Settings
User
Enters
Settings
Ye
Accept
Changes
Accept
Changes
Confirm
A
Setting
Load
Yes
System
Saves all
Changes
System asks
user for SG
to activate
SG to
No
Quit
Quit
without
Save
No
System
keeps
Changes
Activate
Satus
Msg
Any Key
Yes
System In
Entry Level
No
A
B
Settings
D02416R04.00 F-PRO 5100 User Manual 4-23
Page 70
4 Protection Functions and Specifications
The following is the flow of events that can occur in the Load Settings Screen.
Load
Settings
Access
Level
View
Change or Service
receives user
System Saves
System opens
Load Setting
System
file
SG to
Activate
System
processes
user file
File
Correct
Yes
all Changes
Screen
No
No
Confirm
Setting
Load
Yes
System
Timeout
Yes
No
Status
Msg
Any Key
Settings
4-24 F-PRO 5100 User Manual D02416R04.00
Page 71
4 Protection Functions and Specifications
Manual Settings Change
Relay configuration changes during a user-initiated manual setting; the change does not disrupt the relay protection functions. The relay logs an acceptance of the change request and puts the new setting file in service. When the new set­ting file is queued the relay loads the new setting configuration for protection functions to
the protection processor. The relay loads the new name definitions for indication and recording functions to the interface processor. When the re­lay has completed loading the ancillary settings for indication purposes
to the interface processor, an event is logged to show completion of the request. There is some lag time during the load request and the completion of the re­quest where the interface processor vious setting file for approximately five seconds. The ancillary setti
associates ancillary functions with the pre-
ng information includes channel or ProLogic and Group Logic statements names, front panel target light activation rules and record initiation rules.
The protection processor does not have any interruption in service.
Automatic Settings Change
Relay configuration changes during a relay-initiated setting; change does not disrupt the relay protection functions. Since the relay setting file does not change, the interface processor uses the new setting group ancillary setting in­formation at the same time as the prote ting group. An event is logged to show when
ction processor switches to the new set-
the new setting group is in
service.
D02416R04.00 F-PRO 5100 User Manual 4-25
Page 72
4 Protection Functions and Specifications

Recording Functions

The F-PRO has recording and logging functions to allow you to analyze faults and to review the operation of the overall protection scheme.

Fault Recording The F-PRO provides high quality fault recording, capturing input signal wave-

forms and external digital inp record also contains the timing of the internal logic produced by the relay (e.g. 51 trip).
The quantities recorded are:
• 10 analog channels: 4 voltages an
the 25th harmonic frequency response
• 9 external digital inputs: @ 96 samples/cycle
• relay internal logic signals: @ 8 samples/cycle
• summation channels

Trend Recording The trend recording provides continuous, slow-speed recording of P, Q, Ener-

gy, V, I, Freq. and THD of the feeder with an adjustable sa to 60 minutes per sample. This same global trend sampling rate is applied to all the trend quantities. The relay stores a fixed number of samples. At the nominal sample period of 5 minutes per sample the F-PRO stores one month of trend records with automatic overwrite of the oldest.
ut states at a rate of 96 samples per cycle. Each
d 6 currents @ 96 samples/cycle, up to
mple period from 5
Sample Interval Trend Record Length
5 minute 30 days
10 minute 60 days
30 minute 180 days
60 minute
360 days

Record Initiation Recording can be initiated automatically by the relay when a fault or abnormal

condition is detected. You can set the relay to initiate a fault record upon acti­vation of any of its trip or alarm functions or on
assertion of any external digital
inputs.
The assignment of fault record
initiation to the various relay functions is done
through the relay’s Output Matrix settings.
A recording can also be initiated manually through the t
erminal user interface.
The command Initiate Fault Recording is available under the Records menu.
4-26 F-PRO 5100 User Manual D02416R04.00
Page 73
4 Protection Functions and Specifications

Record Duration and Extension

The length of each record is determined by the Record Length setting. Fault re­cord lengths can be set between 0.2 and 2.0 seconds. Pre-trigger times are fixed at 10 cycles for fault records and are included as part of the normal record length. A trend recording is for a 30 day period at one sample/5 minutes. You do not need triggers to create a trend record.
The F-PRO automatically extends a record as required to capture consecutive triggers that are close together. If a trigger occurs while a recording is in prog ress, the record is stretched to include the full post-trigger time of subsequent triggers, up to a maximum length—2.0 seconds for fault records. If a trigger occurs before the end of a record caused by a previous trigger, but too late to allow sufficient post-trigger time in a maximum extended record, a new over lapping record is created.
The normal record lengths settings are accessible under the Recording heading of the relay settings, and can be set from either the terminal user interface or the Offliner Settings software.

Event Recording The event recording provides permanent storage of the event log. An event re-

cord can be created automatically or manually. When the event auto save is en­abled an event record is created approximately every 230 events.
A recording can also be initiated manually through the terminal user interface. The command Initiate Event Recording is available under the Records menu.
-
-

Record Storage The F-PRO compresses records on the fly, achieving a typical lossless com-

pression rate of 4:1. As a result, the F-PRO can store up to 30 seconds of fault recordings and a minimum of 30 days of trend recordings in non-volatile stor age. If the storage is full, new records automatically overwrite the oldest, en­suring that the recording function is always available.

Retrieval and Analysis

A listing of stored records is available through the terminal user interface under the Records menu. The listing provides the means to transfer records to a con nected PC and to delete them from storage.
Example:
FPRO-5100-990726-04-2000-06-09 13.17.16.000(Fault)
Records are named by combining the Relay ID setting with the date and time of the initiating record trigger. In the record list, the record type (fault or swing) is shown.
To delete a record from storage, use the up/down cursor keys to select the re­cord, then press <D>. You can also do group deleting and group transferring.
To select multiple records:
1 Select a record.
2 Press the spacebar - a asterisk will appear to the left of the record to indicate
it is selected.
3 Continue selecting and pressing the spacebar until all desired records are
selected.
4 Press <D>. A message asks “Delete all selected files?” shown above. Select
Y for Yes and the files are deleted.
-
-
D02416R04.00 F-PRO 5100 User Manual 4-27
Page 74
4 Protection Functions and Specifications
To transfer a record to your PC, use the up/down cursor keys to select the re­cord, then press r. The record is automatically transferred to
your PC using the PC terminal program’s z-modem file transfer protocol. The record is placed in your terminal program’s default to receive the directory which was set before transfer to an appropriate directory. (e.g. HyperTerminal’s default receive di­rectory is set through the its Transfer menu). When tra
nsferred, the record name remains unchanged and the file extension indicates the record type: “.fpr” for fault, “.fpe” and “.fpt” for trend.
When the transfer has taken place, you can choose
to delete the record or leave
a copy on the relay.

Logging Functions

Event Log The F-PRO maintains a log of events in a 250 entry circular log. Each entry

contains the time of the event plus an event description.
Logged events include trips, alarms, external input a events such as setting changes. Fault location and classification information is included in event messages where appropriate. For example, the event log en­try for a device trip might be:
2000 Nov 21, 15:34:19.832 : 51 ABC 112.3 km: Trip.
The event log can be viewed in
two ways:
ssertions plus internal
Front Panel The front panel display shows events in abbreviated form (Trip
and Alarm events only).
Terminal User Interface The full event log is available through the Event Log menu of the
erminal user interface.
t
This display is a snapshot of the event list which must be manually refreshed to display new events that occur while the display is up.
There is a list of the F-PRO event messages. For details see “Event Messages” in Appendix D.
4-28 F-PRO 5100 User Manual D02416R04.00
Page 75

5 Offliner Settings Software

Setting Tree Setting Area
Figure 5.1: Opening Screen

Introduction

PC System Requi
rements
Use the Offliner Settings software to create relay settings on a PC. Offliner Set­tings provides an easy way to view and manipulate settings.
Hardware
The minimum hardware requirements are:
• 1 GHz processor
• 2 GB RAM
• 20 GB available hard disk space
• USB port
• Serial communication port
Operating System
The following software must be installed and functional prior to installing the applications:
• Microsoft Windows XP Professional Service Pack 3 or
• Microsoft Windows 7 Professional Service Pack 1
D02416R04.00 F-PRO 5100 User Manual 5-1
Page 76
5 Offliner Settings Software

Installing PC Software

Insert the CD-ROM in your drive. The CD-ROM should open automatically. If the CD-ROM does not open automatically, go to Windows Explorer and find the CD-ROM (usually on D drive). Open the F-PRO.exe file to launch the CD­ROM.

Offliner Features

To install the software on your computer, click the de
sired item on the screen. The installation program launches automatically. Installation may take a few minutes to start.
To view the F-PRO User Manual you must have Adobe Acrobat on your com­puter. If you need a copy, download a copy by clicking on Download Adobe Acroba
Anti-virus/Anti-spyware Software
t.
If an anti-virus/anti-spyware software on your local system identifies any of the ERLPhase applications as a “potential threat”, it will be necessary to con­figure your anti-virus/anti-softw ation. Please consult the appropriate
are to classify it as “safe” for its proper oper-
anti-virus/anti-spyware software
documentation to determine the relevant procedure.
The Offliner software includes the following menu and system tool bar.
Help - Help Topics About F-PRO Settings
New Save Copy
Open Cut Paste
Figure 5.2: Top Tool Bar
Too l B ar
Windows Menu
Icon Restore, minimize, close.
File New, open, close, save, save as, print setup.
Edit Undo, cut, copy, paste.
Tools Display and print only enabled protection devices.
Window Cascade, tile, arrange icons.
5-2 F-PRO 5100 User Manual D02416R04.00
Undo
Copy Graph
Copy Setting Group
Print
Show or Hide Left-Hand Side Tree
About
Page 77
Help Help Topics, About F-PRO Settings.
Settings Program Icons
New Create new default settings file.
Open Open any valid settings file.
Save Save current settings file.
Cut Edit function.
Copy Edit function.
Paste Edit function.
Undo Edit function.
Copy Graph Copy to clipboard.
5 Offliner Settings Software

Graphing Protection Functions

Copy Setting Group
Print Print from Output Matrix, any graph or Settings Summary.
Show or Hide Left­Hand Side Tree
About Version number.
Copy from Setting Group X to Setting Group Y.
Show or Hide Left-Hand Side Tree
Grid On/Grid Off
The graph can be viewed with the grid on or off by clicking the Grid On or Grid Off button. A right-click on the trace of the curve gives you the x and y coor dinates.
Print Graph
To print a particular graph, click the Print Graph button.
Zoom on Graphs
Graphs can be zoomed to bring portions of the traces into clearer display. Left­click on any graph and drag to form a small box around the graph area. When you release the mouse, the trace assumes a new Zoom position determined by the area of the zoom coordinates.
To undo the zoom on the graph, click the Refresh button.
-
D02416R04.00 F-PRO 5100 User Manual 5-3
Page 78
5 Offliner Settings Software

Handling Backward Compatibility

Offliner Settings displays the version number in the second pane on the bottom status bar. The settings version is a whole number (v1, v2, v3, v4, etc.).
The Off files and convert older settings files to a newer version. Offliner Settings han­dles forward conversion only; it file.
liner Settings is backward compatible. Open and edit older settings
converts an older setting file to a newer setting
Converting a Settin
gs File

Sending a New Setting File to the Relay

1 Open the setting file you wish to convert.
2 In the File menu, sele
ct Convert to... and then select the version x (where x is the newer version). A dialog box pops up prompting Offliner for a new file name. Use either the same file name or enter a new file name. The con­version process inserts default values for any newly added devices in the new setting file. When t
he conversion is complete, Offliner Settings dis-
plays the new file.
Figure 5.3: Converting Setting Files
1 Make sure the settings version and the
ting file match. The relay will reject the setti
serial number of the relay in the set-
ng file if either the serial num-
ber or the settings version do not match.
A “serial number discrepancy” message may appear. This is to en­sure that you are aware of the exact relay in which settings are to be
loaded. If this happens, check the relay serial number using the terminal mode ID menu item. Type this serial number into the F­PRO Serial No. box in the Identification tab display area of Offliner Settings. Alternately you may check the Ignore Serial Number check box to bypass serial number supervision.
2 Check the serial number and the setting
s version of the relay, for details see “ID” on page 3-11. The Device Serial Number and Required Settings Ver­sion on the Identification screen indicate
the serial number and the settings
version of the relay.
5-4 F-PRO 5100 User Manual D02416R04.00
Page 79
5 Offliner Settings Software

Creating a Setting File from an Older Version

1 Offliner Settings displays a default setting file on start up showing the set-
tings version in the bottom statu shipped with a set of default sample files of older settings versions. The sample file is “v1 sample.fps”. The sample file contains default values of an older settings version. For a new installation these sample files are placed in the default directory C:\Program Files\ERLPhase\F-PRO Offliner Settings, or you can choose the path during the Offliner software installa­tion. If an older version of F-PRO Offliner was previously installed on your
then the default directory may be C:\Program Files\APT\F-PRO Of-
PC, fliner Settings.
2 Open a sample file of the desired version. Use File/Save A
ple file to a new file name. Then edit the save it and load it into the relay.

RecordBase View Software

s bar. As an example F-PRO Offliner is
s to save the sam-
setting file and the serial number,
Figure 5.4: RecordBase View
Use RecordBase View to analyze the records from a relay.
1 Set the receive directory on your terminal program to point to
a convenient directory on your PC’s hard disk or network. For example with HyperTer­minal, select Trans
2 Select one or more records on the relay using the Li
minal Mode’s Records me
3 Initiate transfer of the selected records by selecting R o
fer>Receive File to set the receive directory.
st function in the Ter-
nu.
n the keyboard.
4 Start the RecordBase View program and use the File>Open menu command
to
open the downloaded record files located in the receive directory speci-
fied in step 1.
For further instructions refer to the RecordBase View Manual at the back o
D02416R04.00 F-PRO 5100 User Manual 5-5
f the printed version of this manual.
Page 80
5 Offliner Settings Software
LHS Menu Tree
RHS - Information relating to specific menu Item, accessed by LHS menu or top tabs.
Unique relay serial number
Nominal System Frequency - set to either 50 Hz or 60 Hz
Nominal CT Sec. Current - set to either 1 A or 5 A

Main Branches from the Tree View

Identification The first screen presents all the menu items in the left menu tree. Access the
menu items by clicking on item on the left menu tree.

Relay

Figure 5.5: Identification

Identification

Settings Version Indicates the settings version n
Ignore Serial Number Bypass serial number check, if enabled.
Serial Number Available at back of each relay.
Unit ID User-defined up to 20 characters.
Nominal CT Format 5 A or 1 A
Nominal System Frequency 60 Hz or 50 Hz
Comments User-defined up to 20 characters.
Setting Software
Setting Name User-defined up to 20 characters.
Date Created/Modified Indicates the last time settings were entered.
Station
Station Name User-defined up to 20 characters.
Station Number User-defined up to 20 characters.
Location User-defined up to 20 characters.
umber, fixed.
Line User-defined up to 20 characters.
5-6 F-PRO 5100 User Manual D02416R04.00
Page 81
5 Offliner Settings Software
Important Note
Nominal CT Sec. Current can be set to either 5 A or 1 A.
Nominal System Frequency can be set
to either 60 Hz or 50 Hz.
Ensure setting selection matches that of target F-PRO.
The serial number of the relay must match the one in the setting file,
he setting will be rejected by the relay. This feature ensures that
or t the correct setting file is applied to the right relay.
In Settings Version 2 or greater you can choose to ignore the serial number e
nforcement in the identification screen. The relay only checks for proper relay type and setting version if the ignore serial number has been chosen, requires relay firmware version 2.0 or greater.
Analog Inputs
Figure 5.6: Analog Inputs
Analog Inputs screen identifies all the ac voltage and current inputs to the re­lay. These names appear in any fault disturbance
Analog Inputs
Main Voltage MVA, MVB, MVC
Main Current IA1, IB1, IC1
Aux. Current IA2, IB2, IC2
Sync Voltage SV
D02416R04.00 F-PRO 5100 User Manual 5-7
records the F-PRO produces.
Page 82
5 Offliner Settings Software
External Inputs
Figure 5.7: External Inputs
The External Inputs screen allows you to define meaningful names for nine ex­ternal inputs.
External Input Names
1 to 9 User-defined
Output Contacts
Figure 5.8: Output Contacts
The Output Contact Names screen allows you to define meaningful names to the 12 output contacts.
Output Contact Names
Outputs 1 to 12 User-defined
5-8 F-PRO 5100 User Manual D02416R04.00
Page 83
Virtual Inputs
Figure 5.9: Virtual Inputs
Virtual Inputs
Virtual Inputs 1 to 30 User-defined
5 Offliner Settings Software
The relay can control its internal functions and connected devices both locally and remotely. Thirty general purpose logic points are accessible via DNP3 and the terminal UI. The 30 virtual inputs are individually controlled and include a set, reset and pulse function. The latch state is retained during setting changes and relay power down conditions. The 30 virtual inputs conform to DNP3 standards. Use the DNP3 functions such as SBO (select before operate), Direct Operate, or Direct Operate with no acknowledge to control virtual inputs.
Use virtual inputs to:
• control circuit breakers
• enable or disable reclosing
• enable or disable under-frequency load
• change setting groups
• provide interlocking between local/remote supervisory control
shedding
D02416R04.00 F-PRO 5100 User Manual 5-9
Page 84
5 Offliner Settings Software
Setting Groups
Figure 5.10: Setting Groups
The Setting Group Names screen allows you to define meaningful names to the 8 setting groups.
Setting Groups
Setting Groups 1 to 8 User-defined
5-10 F-PRO 5100 User Manual D02416R04.00
Page 85

System Parameters

5 Offliner Settings Software
Figure 5.11: System Parameters
System Parameters
Base MVA 1.0 to 1000.0 MVA (primary)
Phase Rotation ABC or ACB
CT Turns Ratio
Ring Bus Configuration (Aux CT Line Input)
Main CT Turns Ratio 1.0 to 10000.0
Aux CT Turns Ratio 1.0 to 10000.0
PT Turns Ratio
Main PT Turns Ratio 1.0 to 10000.0
Sync PT Turns Ratio 1.0 to 10000.0
Sync PT Phase 0 to 330 degrees
Line
Line to Line Voltage 1.00 to 500.00 kV (Primary)
Distance Units km or miles
Enable/disable
Base MVA
The base MVA is used for recording purposes.
D02416R04.00 F-PRO 5100 User Manual 5-11
Page 86
5 Offliner Settings Software

Record Length

CT Turns Ratio and PT Turns Ratio
The CT and PT ratios are specified for the analog inputs. All CT and PT ratios are specified with a ratio relative to one (i.e. X amps to 1A). The line protection uses the main current and the main voltage to operate. When two sets of CTs (main and auxiliary) are used as line current input (e.g. ring bus application), you must enable the ring bus configuration parameter to inform the relay. If en­abled, the currents from the two
sets of CTs are added to the relay to form the line current. F-PRO uses ac volts from the main PTs for its protections and for the metering functions. A single phase voltage from the bus is connected to sync ac volts to provide voltage for sync checking capability.
Figure 5.12: Record Length
Record Length
Fault Record Length 0.2 to 2.0 seconds
Trend Auto Save Enable/disable
Event Auto Save Enable/disable
The relay has recording and logging functions to analyze faults and to review the operation of the overall protection scheme.
This item identifies the amount of time that e
ach fault record. Prefault is fixed
at 10 cycles.
5-12 F-PRO 5100 User Manual D02416R04.00
Page 87

Setting Groups

5 Offliner Settings Software
Figure 5.13: Setting Groups Comments
The relay has eight setting groups (1 to 8). You can change all relay setting pa­rameters except the physical connections su
ch as input or output parameters in each setting group. Use any one of the 16 available Group Logic Statements per setting group to perform Setting Group changes. The Group Logic state­ments are similar to the ProLogic statements with the followi
ng exceptions, the sole function is to activate one of the eight setting groups and the processing is in a slower half second cycle. Group Logic inputs statements can be driven from ProLogic, any external input, previous Group Logic statements or virtual inputs. Each Group Logic statement includes five inputs (with Boolean state­ments), one latch state and one pickup delay timer.
View the active setting group from the Terminal Mode, from the front panel or from a record stored by the relay (the active setting group is stored with the record).
Feeder Parameters
Figure 5.14: Feeder Parameters
Feeder Parameters
Line
Line to Line Voltage Fixed (from System Parameters)
D02416R04.00 F-PRO 5100 User Manual 5-13
Page 88
5 Offliner Settings Software
Feeder Length 1.0 to 1000.0 km or 0.62 to 621.37 miles
Feeder Impedance
Positive Sequence Impedance 0.05 to 66.00 ohms
Positive Sequence Angle 25.0 to 89.0 degrees
Zero Sequence Impedance 0.05 to 200.00 ohms
Zero Sequence Angle 25.0 to 89.0 degrees
Feeder Parameters permit a parameter entry related to the line voltage, CT ra­tio, PT ratio, line length, line secondary pos
itive and zero sequence impedance.
The relay internally calculates Ko from these values.
Feeder parameters are entered in secondary quantities.
Protection Fun
ctions

Demand/Trend Metering

For detailed descriptions of the protection functions see “Protection Functions and Specifications” on page 4-1.
Figure 5.15: Demand/Trend Metering
Demand/Trend Metering
Demand/Trend Metering Enable/disable
Demand Interval (minutes) 5 to 60 minutes with increments of 5
Demand Meter Type Integrating, rolling or thermal
5-14 F-PRO 5100 User Manual D02416R04.00
Page 89

I*I*t

5 Offliner Settings Software
Figure 5.16: I*I*t
I*I*t
Main Enable/disable
External Input or ProLogic for Trip Disable or External Input or ProLogic
I*I*t Limit
0.1 to 99999.0 (KA)
2
.s
Aux Enable/disable
External Input or ProLogic for Trip Disable or External Input or ProLogic
I*I*t Limit
0.1 to 99999.0 (KA)
2
.s
D02416R04.00 F-PRO 5100 User Manual 5-15
Page 90
5 Offliner Settings Software

ProLogic

Figure 5.17: ProLogic
Apply ProLogic to multiple inputs to create an output based on qualified in­puts. ProLogic enables up to 10 ProLogic
control statements and programs those logics to output contacts. You can name the function being created and set a pickup and dropout delay. Start with input A by selecting any of the relay functions using the list for up to 5 possible inputs. Put these inputs into AND/ OR, NAND/NOR and exclusive logics and latches by clicking on the gate. In­vert the input by clicking on the input line.
The output of ProLogic 1 can be nested into ProLogic 2 and so forth. If desired you
can illuminate the front target LED on operation of this function by en-
abling this feature. The operation of the
ProLogic statements are logged on the
events listing. This logic shows on the view fault records.

Breaker Logic

Figure 5.18: Breaker Logic
5-16 F-PRO 5100 User Manual D02416R04.00
Page 91
5 Offliner Settings Software

Group Logic The sixteen Group Logic statements reside in a slower processing thread with-

in the relay protection algorithms. The proc
essing cycle happens once every half second (0.5 s). When using ProLogic statements you must keep in mind that a latch or dropout timer should be used if the initiating condition does not last at least 0.5 seconds.

Output Matrix

Figure 5.19: Group Logic
Figure 5.20: Output Matrix 1
The output contact matrix determines which function initiates which output re­lay. All output relays have a fixed 0.1 seco
nd stretch time. Functions can also initiate fault recording, recloser blocking, recloser initiation and/or breaker failure initiation.
For a particular function to operate correctly, it must be enabled and must also have its logic output assigned to at least one output contact if it is involved in a tripping function.
D02416R04.00 F-PRO 5100 User Manual 5-17
Page 92
5 Offliner Settings Software

Settings Summary

Print the entire output matrix by selecting File>Print Summary. This printout is produced on two pages.
Figure 5.21: Settings Summary
Select Settings Summary to view and print the relay settings in text form. For details see “IED Settings and Ranges” in Appendix B.
5-18 F-PRO 5100 User Manual D02416R04.00
Page 93

Settings From a Record

The settings on the relay at the time of a recording are included in every record and can be viewed through the RecordBase View analysis software. While viewing a recording in RecordBase View, select the View Setting button to dis­play the settings. RecordBase View will to display the settings in summary form.
If the record contains Setting Groups, the Offliner displays all Setting Groups in the summary. Bold text in (the Setting Group used at the time the record was captured). The setting sum­mary is read-only. To edit the must use File/Save As to save the summary to a file. Then close the summary screen and open the setting file for editing.
5 Offliner Settings Software
automatically launch F-PRO Offliner
the tree view indicates an active Setting Group
setting file associated with the summary, you
Figure 5.22: View Setting Summary in RecordBase View
D02416R04.00 F-PRO 5100 User Manual 5-19
Page 94
Page 95

6 Testing the F-PRO Functions

Testing is required to determine if your relay performs correctly after the set­tings are complete or to determine verification of cases a simple test using three voltage sources and three current sources is ad­equate.
relay settings needed. In most

Calibration The relay is calibrated when it

made within the relay, you may need to do a re-calibration.
Establish the accuracy of equipment used to calibrate the relay be­fore a new calibration is attempted. A source quality of 0.5% or better is requ
To perform a calibration, you must be logged into at the Service access level. Select Utilities>Maintenance>Calibrate. The Cal­ibrate menu leads you through every analog input and prompts you to apply the a
ppropriate quantity.
ired.
leaves the factory; but if component changes are
the relay in Terminal Mode
Figure 6.1: Enter actual applied signal level
D02416R04.00 F-PRO 5100 User Manual 6-1
Page 96
6 Testing the F-PRO Functions
Figure 6.2: Calibration error - out of range
For example, when you select voltage VA for calibration, a prompt appears which asks you which quantity the relay should try to calibrate. If a 66 volt phase-to-neutral quantity is applied to the back VA terminals, 66.0 volts would be indicated as the desired calibration.
In a similar way, you are prompted to go through
all ac analog quantities and provide the information about the injected calibration quantities. You must have a test source to perform the function. Only the magnitude of the analog input requires calibration, not the angle.
When an input analog channel is calibrated, verify the quantity measured by selecting the Me
tering menu and the Analog Quantity submenu. The VA of the ac voltage input is used as a reference quantity by your relay. Therefore, if it is absent, there is not a locked, valid relationship among all of the analog quanti­ties.
Testing the External
uts
Inp
To test the external inputs, the relay is connected to a laptop in the Terminal Mode, in service level, in the I/O sub-menu. This screen displays the status of the Event Input and the Output Contacts. Placing a voltage of 125 Vdc nom. (150 V maximum) to each of the external inputs in turns causes the input to change from Low to High status. These inputs are polarity sensitive. This screen has a 0.5 second update rate.
Testing the Output
Contacts
Relay
The output relays are tested to verify their integrity using the terminal mode Utilities menu and the Output Contacts sub-menu. At this stage the output con­tacts can be closed by pressing Enter key.
This toggles the output contact from Open to Closed. Pressing the Enter key again toggles the contact status to Open again. The output contact status is verified using an ohmmeter. When you exit this sub-menu, all contact status reverts to the open position.
6-2 F-PRO 5100 User Manual D02416R04.00
Page 97

7 Installation

Physical Mounting

Standard 3U The relay is 3 rack units or 5.25 inches high and approximately 12.25 inches

deep. The standard relay is designed for a 19-inch rack. A complete mechani cal drawing is shown, for details see “Mechanical Drawings” in Appendix G.
To install the relay you need the following:
• 19 inch rack
• 4 - #10 screws

AC and DC Wiring

For details see “AC Schematic Drawing” in Appendix I and “DC Schematic Drawing” in Appendix J.

Communication Wiring

EIA-232 All of the relay’s serial ports (Ports 1, 2 and 3) are configured as EIA RS-232

Data Communications Equipment (DCE) devices with female DB9 connec tors. This allows them to be connected directly to a PC serial port with a stan­dard straight-through male-to-female serial cable for pin-out, for details see “Communication Port Details” on page 2-9.
-
-

Ethernet/Modem The relay has an RJ-45 receptacle for accepting a 10BaseT Ethernet connector

or an RJ-11 connector.

IRIG-B Wiring The IRIG-B connector on the back of the relay is BNC type.

D02416R04.00 F-PRO 5100 User Manual 7-1
Page 98
Page 99

8 Cyber Security

System Access Control and Authorisation

Access to B-PRO is protected by login name and password. Each login name is associated with an Access Level. Section 3 “Terminal Mode” provides de tails on the Access Levels and login names.
-

Password Complexity

Password maximum length is 22 characters. Password may contain:
• Lower case letters ( a – z )
• Upper case letters ( A – Z )
• Numeric characters ( 0 – 9 )
• Special characters as follows:
Table 8.1: Special Characters
Character ASCII Decimal Description
! 033 Exclamation mark
“ 034 Quotation mark
# 035 Number sign
$ 036 Dollar sign
% 037 Percent sign
& 038 Ampersand
‘ 039 Apostrophe
( 040 Left parenthesis
) 041 Right parenthesis
* 042 Asterisk
+ 043 Plus sign
, 044 Comma
- 045 Hyphen-minus
. 046 Full stop
/ 047 Slash (Solidus)
: 058 Colon
; 059 Semicolon
< 060 Less-than sign
= 061 Equal sign
> 062 Greater-than sign
? 063 Question mark
D02416R04.00 F-PRO 5100 User Manual 8-1
Page 100
8 Cyber Security
Table 8.1: Special Characters
@ 064 At sign
[ 091 Left Square Bracket
] 093 Right Square Bracket
^ 094 Circumflex accent
_ 095 Low line
| 124 Vertical bar
{ 123 Left Curly Bracket
} 125 Right Curly Bracket
~ 126 Tilde
Special characters other than listed above may currently be used for passwords. However, only the listed characters are guaranteed to be supported in the future.
B-PRO does not inforce password complexity rules. However, password com­pliance to the following comp
lexity rules can be verified, when password is be-
ing updated
• Minimum password length 8 characters.
• At least one upper case character.
• At least one lower case character.
• At least one numerical character.
• At least one special character.

Access Timeout User is automatically logged out after 60 mi

Access Level Block
ing
B-PRO automatically blocks (locks out) Access Level for 5 minutes after 7 un­successful login attempts. Lock-out of one ability of the others.
Authorization by Acce
ss Level
Each Access Level is assigned a set of functions authorized for it. The set of functions is pre-defined and cannot be changed. Six Access Levels are defined. Access Level list and set of functions associated with each level are described in section 3 “Terminal Mode”.
nutes of inactivity.
Access Level does not affect avail-
8-2 F-PRO 5100 User Manual D02416R04.00
Loading...