No part of this document may be reproduced in any form without the written
permission of the copyright owner.
The contents of this document are subject to revision without notice due to
continued progress in methodology, design and manufacturing. Ericsson shall
have no liability for any error or damage of any kind resulting from the use
of this document.
1/1531-COH 109 2073 Uen H 2006-11-06
Page 3
Contents
Contents
1Introduction1
2Prerequisites1
2.1Documentation1
2.2Tools3
2.3Equipment4
2.4Conditions4
3Procedure5
3.1Unpacking and Checking the Material7
3.2Positioning and Anchoring the Cabinet7
3.3Earth Grounding the Cabinet10
3.4Connecting the External Battery Backup (Optional)11
3.4.1Installing the Temperature Sensor Cable12
3.4.2Installing the External Battery Backup12
3.5Connecting the AC Power16
3.6Installing the Internal Backup Batteries (Optional)28
3.6.1Installing Batteries28
3.6.2Connecting the Batteries30
3.6.3Securing the Batteries33
3.7Connecting Site Transmission from the Transmission
Cabinet (Alternative)35
Note:References to document numbers are found in Section 4 on page 57.
2
1/1531-COH 109 2073 Uen H 2006-11-06
Page 7
2.2Tools
The tools required for the installation of the RBS 3107 are shown in the table
below.
Table 1Tools Required
Product NameDescriptionProduct Number
Personal tool setPersonal toolsLTT 601 135/1
Prerequisites
Tools included in the
personal tool set, needed
for the installation
or
Cordless hammer drill
(2)
Other tools needed
Open-ended wrench
(u-wrench)
(1)
set
LTT 601 139/1
T8 Torx screwdriverLSA 901 43/6
T15 Torx screwdriverLSA 901 43/2
T30 Torx screwdriverLSA 901 43/5
Screwdriver for bitsLSS 103 28/1
Side cutters (side cutting
(1)
pliers)
LSD 901 43/1
Cable cuttersLDK 901 15/1
Cable shield cuttersLDK 901 18/1
Wire stripper 0.2 – 0.6 mmLSD 901 45/1
Spirit levelLMV 901 04/1
Ear protectorsLYB 921 50/1
Eye protectorsLYB 921 51/1
230 V ACLTT 601 146/1Hammer drill
Cordless 230 V ACLTT 601 147/1
Box socket set with ratchet
LTT 601 138/1
wrench
Torque wrench, 0 – 10 Nm
LTT 601 148/1
with T30 torx bit
Torque set, 20 – 100 NmLTT 601 141/1
Torque set, 5 – 25 Nm
LTT 601 140/1
with 3/8 in. socket adapter
Open-ended head (u-key),
24 mm
Open-ended head (u-key),
27 mm
Open-ended head (u-key),
32 mm
(1)
(1)
(1)
LSB 107 12/3
LSB 107 12/4
LSB 107 12/5
Eyebolts, M12SAR 201 120/03
(1) Ericsson name within parentheses.
(2) Hammer drills for voltages other than 230 V AC cannot be ordered from Ericsson.
31/1531-COH 109 2073 Uen H 2006-11-06
Page 8
Installation Instruction
2.3Equipment
The instructions in this document describe the installation, or use, of the
following hardware:
•RBS 3107 cabinet
•Earth grounding kit
•Power cables
•RF cables
•Transmission cables
•Alarm cables
•Site LAN cable
2.4Conditions
The following conditions must be fulfilled before work starts:
Before Going to the Site
Before going to the site, ensure the following:
•Site access permission has been received
•The Site Installation Documentation is available
•All tools and instruments are available
Before Starting the Installation
Before starting the installation, ensure the following:
•The site is prepared according to the Site Installation Documentation
•The existing base frame is undamaged
•The ordered hardware is available
•The AC power supply for the RBS 3107 is installed and tested
•The site earth grounding is installed and tested
•The antenna system is installed and tested
4
1/1531-COH 109 2073 Uen H 2006-11-06
Page 9
3Procedure
This section describes the RBS 3107 installation procedure.
Overview of the RBS 3107
The figure below gives an overview of the RBS 3107.
Procedure
LAN connector
Batteries
RF cable inlet
Temperature sensor
cable connector and
battey cable connector
Figure 1RBS 3107 Overview
ACCU with power cable connection
DF with cable
inlet for transmission,
alarm and GPS,
including OVP
Ground
connector
P014424C
Workflow
The figure below shows the workflow for installing the RBS 3107.
1/1531-COH 109 2073 Uen H 2006-11-06
5
Page 10
Installation Instruction
Figure 2RBS 3107 Installation Workflow
6
1/1531-COH 109 2073 Uen H 2006-11-06
Page 11
3.1Unpacking and Checking the Material
Do!
Tip risk! This equipment has a high center of gravity without all units installed.
Secure the equipment before opening the door.
This section contains information on unpacking and checking the material.
The RBS 3107 cabinet is transported in a crate.
Note:Maximum cabinet weight is 350 kg (excluding batteries).
Procedure
1.Examine the packaging for damage. If it has been damaged, then
immediately inform the transport company.
2.Check that the items delivered correspond to the packing list. For more
information, see Site Installation Documentation
3.Unpack the cabinet.
Note:Allow the cabinet to remain on the pallet until required for
installation.
4.Dispose of the crate in accordance with local regulations.
3.2Positioning and Anchoring the Cabinet
Note:Before installing the cabinet the site must be prepared for routing
cables. All external cables, such as antenna and transmission cables,
are installed from below, that is, through openings in the bottom of
the cabinet.
To attach the cabinet to the existing base frame, do the following:
Note:The lifting device must be capable of lifting at least 400 kg.
1.Ensure that all packing is removed from the cabinet.
2.Unscrew the five bolts under the upper edge of the cabinet, as shown in the
figure below, using a hexagon 6 mm bit and a ratchet wrench.
3.Pull the cabinet roof a few centimeters towards the cabinet door, then lift it
straight up.
1/1531-COH 109 2073 Uen H 2006-11-06
7
Page 12
Installation Instruction
Figure 3Roof and Cabinet Attachment
4.Screw the four M12 eyebolts into the top of the cabinet, as shown in the
figure below. Tighten them finger-tight.
Figure 4Eyebolt Attachment
5.Attach lifting straps to the eyebolts and lift the cabinet.
Note:The angle of the lifting strap at the hook must not be more than 90
as shown in the figure below. (This is equivalent to the angles
between the lifting strap and the cabinet roof being at least 45
,
.)
6.Position the cabinet and lower it into the place for installation.
Note:Ensure that cabinet is level in all directions.
8
1/1531-COH 109 2073 Uen H 2006-11-06
Page 13
Procedure
Figure 5Cabinet Lifting
7.Remove the lifting straps and eyebolts.
8.Insert four washers and M16 locking bolts and tighten them to the
appropriate torque (depending on the material to which the cabinet is
attached), using a torque wrench and a 24 mm Open-ended head.
9.Attach the roof by pushing it straight backwards. Screw in the five bolts
and tighten them to a torque of 8 Nm, using a 6 mm hexagon bit and a
torque wrench.
1/1531-COH 109 2073 Uen H 2006-11-06
9
Page 14
Installation Instruction
Figure 6Cabinet and Roof Attachment
3.3Earth Grounding the Cabinet
Do!
Products not connected to ground risk being damaged by overvoltage or
overcurrent. Always connect products to ground according to instructions.
For general information about earth grounding principles, see Grounding
Guidelines for RBS Sites.
For information about installing earth grounding, see Grounding Material
Installation Instruction.
To connect the earth grounding cable to the RBS 3107, do the following:
1.Remove the six screws holding the Distribution Frame (DF) in place, using
a T30 Torx screwdriver, and push it to the left as shown in the figure below.
10
1/1531-COH 109 2073 Uen H 2006-11-06
Page 15
Procedure
Note:Ensure that the factory-installed cables attached to the rear of each
Overvoltage Protection (OVP) module are not loosened.
Figure 7Earth Grounding Cable
2.Route the earth grounding cable from the site Main Earth Terminal (MET)
to the cabinet earth grounding point.
3.Remove the M8 nut and washer.
4.Connect the earth grounding cable according to the figure above. The
washer must be placed between the cable lug and the nut. Tighten the nut
to 15 Nm, using a torque wrench and a 13 mm socket.
Note:Do not put back the DF yet. The opening is needed for the installation
of the AC mains cable described in section Section 3.5 on page
16. Furthermore, both sides of the DF must be available during the
installation of transmission, alarm, and GPS solution cables. See
Section 3.7 on page 35, Section 3.9 on page 49 and Section 3.10 on
page 53.
3.4Connecting the External Battery Backup (Optional)
This section describes how to connect external battery backup to the DC filter,
if external battery backup is used. The DC filter is located below the ACCU.
1/1531-COH 109 2073 Uen H 2006-11-06
11
Page 16
Installation Instruction
3.4.1Installing the Temperature Sensor Cable
This section describes how to connect the temperature sensor cables to the
DC filter.
1.
Ensure that the temperature sensor
cable on the upper side of the DC
filter is connected as shown in the
figure.
Route the cable on the left-hand side
of the cabinet, well separated from
other cables, and connect it to the
BFU.
BFUBFU
2.
Loosen the screws and lift up the DC filter.
3.
Connect the temperature sensor
cable from the external batteries to
the D-sub connector of the DC filter.
Note: The figure shows the bottom
of the DC filter.
3.4.2Installing the External Battery Backup
This section describes how to connect the power cables from the external
battery backup to the DC filter.
P015179B
12
1/1531-COH 109 2073 Uen H 2006-11-06
Page 17
Procedure
Caution!
Improper handling of batteries can result in the batteries short-circuiting, which
can result in serious injury due to high energy levels. Exercise the necessary
care when working with batteries.
1.
Ensure that the positive (+) cable is disconnected from the external batteries
before following the instruction below.
2.
Remove the bottom cover plate of the DC filter and the cable glands.
3.
Insert and connect the stripped
cables from the external batteries to
the DC filter.
Note: The figure shows the bottom
of the DC filter.
4.
Position the correct side of the cable clamps for the cross-sectional area of
the cable in accordance with the table below.
Put back the bottom cover plate and tighten the screws.
8.
Position the DC filter and tighten the screws.
9.
Connect the earth grounding cable to the RBS as shown in the figure below.
Tighten the nut to a torque of 15 Nm.
Figure 8Earth Grounding Cable
10.
Connect the earth grounding, temperature sensor, and signal cables to the
RBS.
11.
Connect the battery cable to EXT BATT.
141/1531-COH 109 2073 Uen H 2006-11-06
Page 19
Outddoor RBS
BFU
CU*
Temperature sensor
(electically isolated)
BBU
Battery
−
48 V
+24 V
Procedure
DC filter
L <10 m
Temperature
sensor signal
*CU = temerature sensor port
P016172B
Figure 9Cable Routing
Note:It is important that the cables are positioned according to the figure
below.
Figure 10Cable Layout
1/1531-COH 109 2073 Uen H 2006-11-06
Bonding
35 mm
2
Signal
DC DC-return
×
min. 2 50 mm
2
P016173A
15
Page 20
Installation Instruction
3.5Connecting the AC Power
This section contains instructions for connecting the AC power.
Danger!
Electric shock risk. Avoid both direct and indirect contact with parts connected
to mains power as this is likely to be fatal. Switch off the mains power before
starting work.
Danger!
Improper electrical installation may cause fire or electric shock that is likely to
be fatal. Only a qualified and authorized electrician is permitted to install or
modify electrical installations.
Stop!
Do not install or modify AC or DC powered equipment unless you are a
qualified and authorized electrician. Improper installation work can seriously
damage the equipment.
1.Ensure the following:
That the AC power is switched off at the source.
That the AC mains switch and all circuit breakers on the Alternating Current
Connection Unit (ACCU) are in their OFF positions.
16
That all the switches on Power Distribution Units (PDU) are in their OFF
positions.
That the switches on the Battery Fuse Unit (BFU) are off.
That the DF is removed so that there is easy access to the power cable.
1/1531-COH 109 2073 Uen H 2006-11-06
Page 21
Procedure
2.Remove the ACCU front cover, by unscrewing the three screws, using a T8
Torx screwdriver, and hook the plate off as shown in the figure below.
Figure 11ACCU Front Cover Removal
3.Route the power cable through the cable inlet as shown in the figure below.
4.Strip the cable sheath of the power cable to an appropriate length, using
cable shield cutters.
5.Strip about 10 mm of the power cable conductors, using a wire stripper.
6.Connect the cable conductors to the terminal blocks. Tighten the screws to
a torque of 5 Nm, using a torque wrench and a 5.5 mm flat bit.
7.Tighten the cable gland by hand.
1/1531-COH 109 2073 Uen H 2006-11-06
17
Page 22
Installation Instruction
Figure 12Power Cable Connection
8.Check that the terminal block jumper and the jumpers on the terminal
stands are correctly set for the AC power system to be used. If not correctly
set, connect the jumpers according to the circuit diagram inside the front
cover. The alternatives are also shown below.
Note:The protective earth connection (marked PE in the figures) is not
interrupted by the mains switch.
18
1/1531-COH 109 2073 Uen H 2006-11-06
Page 23
Procedure
Figure 13ACCU Connection Terminals and Jumper Positions
Three-Phase + PEN, 346/200 - 433/250 V AC (Factory Setting)
Figure 14
1/1531-COH 109 2073 Uen H 2006-11-06
19
Page 24
Installation Instruction
One-Phase + Neutral + Protective Earth, 200 - 250 V AC
Figure 15
One-Phase + PEN, 200 - 250 V AC
Figure 16
201/1531-COH 109 2073 Uen H 2006-11-06
Page 25
Three-Phase + Neutral + Protective Earth, 346/200 - 433/250 V AC
Figure 17
Procedure
Three-Phase + Neutral + Protective Earth, 208/120 - 220/127 V AC
The picture below is valid for BMG 980 26/2 up to R-state R1D.
Figure 18ACCU R1D
1/1531-COH 109 2073 Uen H 2006-11-06
21
Page 26
Installation Instruction
The picture below is valid for BMG 980 26/2 from R-state R1E and on.
P015920A
Figure 19ACCU R1E
Three-Phase + PEN, 208/120 - 220/127 V AC
The picture below is valid for BMG 980 26/2 up to R-state R1D.
Figure 20ACCU R1D
22
1/1531-COH 109 2073 Uen H 2006-11-06
Page 27
The picture below is valid for BMG 980 26/2 from R-state R1E and on.
Figure 21ACCU R1E
Procedure
P015921A
Three-Phase + Protective Earth, 200 - 240 V AC
The picture below is valid for BMG 980 26/2 up to R-state R1D.
Figure 22ACCU R1D
1/1531-COH 109 2073 Uen H 2006-11-06
23
Page 28
Installation Instruction
The picture below is valid for BMG 980 26/2 from R-state R1E and on.
P015922A
Figure 23ACCU R1E
Three-Phase + Neutral + Protective Earth, 200/100 - 240/120 V AC
The picture below is valid for BMG 980 26/2 up to R-state R1D.
Figure 24ACCU R1D
24
1/1531-COH 109 2073 Uen H 2006-11-06
Page 29
The picture below is valid for BMG 980 26/2 from R-state R1E and on.
Figure 25ACCU R1E
Procedure
P015920A
Three-Phase + PEN, 200/100 - 240/120 V AC
The picture below is valid for BMG 980 26/2 up to R-state R1D.
Figure 26ACCU R1D
1/1531-COH 109 2073 Uen H 2006-11-06
25
Page 30
Installation Instruction
The picture below is valid for BMG 980 26/2 from R-state R1E and on.
P015921A
Figure 27ACCU R1E
Two-Phase + Neutral + Protective Earth, 200/100 - 240/120 V AC
9.Disconnect all power connectors from the front of the ACCU.
10. Ensure that the AC mains switch and the circuit breakers are all in OFF
position.
11. Put back the ACCU front cover.
12. Switch on site power.
13. Switch on ACCU main switch.
14. Switch on the circuit breaker for the Climate Unit (CLU).
15. Measure the output AC voltage from the CLU output connector, using
a digital multimeter.
16. Switch off the circuit breaker for the CLU.
17. Repeat Step 14 on page 27 to Step 16 on page 27 for each circuit breaker
and output connector for Power Supply Unit (PSU) 1, PSU 2, and PSU 3
respectively.
18. If any of the output voltages are outside the 190 – 260 V AC range,
switch off the site power and ACCU mains switches and check the ACCU
strapping before proceeding.
Note:To prevent personal injury or damage to equipment, never connect
19. Check that the output voltage at the service outlet is the same as the local
single-phase voltage.
20. Connect all power connectors to the front of the ACCU.
1/1531-COH 109 2073 Uen H 2006-11-06
a PSU to an ACCU output that is outside the 190 – 260 V AC range.
27
Page 32
Installation Instruction
3.6Installing the Internal Backup Batteries (Optional)
This section describes how to install batteries on the battery shelf inside the
RBS cabinet.
Caution!
Improper handling of batteries can result in the batteries short-circuiting, which
can result in serious injury due to high energy levels. Exercise the necessary
care when working with batteries.
3.6.1Installing Batteries
To install the batteries, do the following:
1.Attach the securing straps at the front and back of the battery shelf. Let the
strap buckles hang down from the front. See figure below.
28
Figure 30Securing Strap Attachment
1/1531-COH 109 2073 Uen H 2006-11-06
Page 33
Procedure
Note:The four batteries to be installed are referred to as battery 1, 2, 3, or 4
respectively. The numbers refer to the battery positions on the battery
shelf, where battery 1 is installed on the far left, followed by batteries 2,
3, and 4 in order. See Figure 34 on page 31.
2.Remove the protective caps of each battery.
3.Attach the adhesive pads, shown in the figure below, to the right-hand
sides of batteries 1 and 3.
Figure 31Adhesive Pad Attachment
4.Attach the temperature sensor holder to battery 2. Remove the inner part
of the holder and attach it according to the figure below.
Figure 32Temperature Sensor Holder
Note:For each battery the rear strap end must be brought over the battery
to the front.
5.Place battery 1 on the far left of the shelf.
1/1531-COH 109 2073 Uen H 2006-11-06
29
Page 34
Installation Instruction
6.Place battery 2, that is, the battery with the temperature sensor holder,
next to battery 1.
7.Attach the temperature sensor to the holder on battery 2. See figure below.
8.Connect the other end of the temperature sensor cable to the BFU. See
figure below.
Figure 33Battery Temperature Sensor Connections
9.Put battery 3 into the next position.
10. Put battery 4 into the last position on the shelf.
3.6.2Connecting the Batteries
This section describes how to connect inter-block connectors, gas-evaporating
tubes, and cables to the batteries.
1.Note:If the tools used are not insulated, then do not let them touch any
metal parts of the cabinet.
Attach the inter-block connectors between the batteries as shown in the
figure below. Tighten the bolts to a torque of 8 Nm, using a torque wrench
and a 13 mm socket.
30
1/1531-COH 109 2073 Uen H 2006-11-06
Page 35
Procedure
Figure 34Inter-Block Connections
2.Remove the screw from the mounting hole for a gas-evaporating tube. The
hole is positioned in the cabinet floor as shown in the figure below.
3.Screw the angled nipple into the hole.
4.Attach the end cap on the leftmost battery (battery 1) as shown in the
figure below.
5.Attach the gas-evaporating tubes between the batteries as shown in below.
6.Attach the gas-evaporating tube between the nipple and the rightmost
battery (battery 4) as shown in the figure below.
1/1531-COH 109 2073 Uen H 2006-11-06
31
Page 36
Installation Instruction
Figure 35Gas-Evaporating Tubes
7.Make sure that the battery cable is not yet connected to the BFU.
8.Connect the blue end of the battery cable to the minus pole of the leftmost
battery (battery 1) as shown in the figure below. Tighten the bolt to a torque
of 8 Nm, using a torque wrench and a 13 mm socket.
9.Connect the red end of the battery cable to the plus pole of the rightmost
battery (battery 4) as shown in the figure below. Tighten the bolt to a torque
of 8 Nm, using a torque wrench and a 13 mm socket.
32
1/1531-COH 109 2073 Uen H 2006-11-06
Page 37
Procedure
Figure 36Battery Cable Connections
3.6.3Securing the Batteries
This section describes how to secure the batteries on each shelf.
1.Place the protective caps over the battery poles as shown in the figure
below.
1/1531-COH 109 2073 Uen H 2006-11-06
33
Page 38
Installation Instruction
Figure 37Protective Caps
2.Tighten the securing straps firmly in stages as shown in the figure below.
Note:Do not let the metal buckles touch any metal parts of the batteries.
1
4
5
3
2
P009234C
Figure 38Securing Straps
34
3.Connect the battery cable to the BFU. See figure below.
1/1531-COH 109 2073 Uen H 2006-11-06
Page 39
Procedure
Note:It is recommended that the cables be attached to the handles of
the batteries, using cable ties.
Figure 39Battery to BFU Connection
3.7Connecting Site Transmission from the Transmission
Cabinet (Alternative)
This section describes how to connect the RBS 3107 to the transmission
system on site. The external transmission cables are routed through and earth
grounded in cable glands that are mounted in cable entries in the Distribution
Frame (DF). This is necessary to comply with the Electromagnetic Compatibility
(EMC) requirements.
The cable connections depend on the transmission alternative chosen for the
specific site. For more information, see the Site Installation Documentation.
The choice of instructions to follow depends on the type of transmission to be
connected to the cabinet. The three transmission options are as follows:
Note:The DF must be loosened to enable access from underneath.
To connect a shielded twisted pair cable to an Overvoltage Protection (OVP)
module, do the following:
Note:The instructions describe the connections to one connection block of
an OVP module.
1.Ensure that the DF is not fastened in place, and that the space beneath it is
accessible. See Section 3.3 on page 10.
2.Remove the rubber sealing in the DF cable entry closest to the OVP
module to be used.
3.Insert the cable gland and tighten it with a 20 mm open-ended wrench.
See 1 in the figure below.
4.Pass at least 170 mm of the cable through the cable gland. See 2 in the
figure below.
36
1/1531-COH 109 2073 Uen H 2006-11-06
Page 41
Procedure
Figure 41Cable Gland Attachment and Cable Routing
5.Strip 170 mm of the outer layer of insulation from the cable, using a wire
stripper. See figure below.
6.Leave 12 mm of the outer screen.
Note:The cable screen must be earth grounded at the DF.
7.Strip 5 mm of the insulation from the ends of the wires.
1/1531-COH 109 2073 Uen H 2006-11-06
37
Page 42
Installation Instruction
Figure 42Stripping Lengths
8.Connect each wire to the terminal block of the OVP module, using a small
screwdriver (<2.5 mm) to open the terminal connectors. See relevant figure
below depending on the OVP variant used.
P014488B
Figure 43Wire Connections Variant 1
38
1/1531-COH 109 2073 Uen H 2006-11-06
Page 43
Procedure
P016851A
Figure 44Wire Connections Variant 2
9.Attach the correct wires to the appropriate connectors in the terminal block.
Note:See the Site Installation Documentation for more information on
the transmission connections.
Figure 45OVP Module Connection Points
10. Pull the cable back through the cable gland and clamp it by screwing the
cable gland together from underneath. See figure below.
Note:Make sure that the outer screen is in contact with the earth
1/1531-COH 109 2073 Uen H 2006-11-06
grounding of the cable gland.
39
Page 44
Installation Instruction
Figure 46Secured Cable with Screen
11. Make a note of the cable data on the cover of the OVP Module.
12. Reinsert the six screws in the DF and tighten them with a T30 Torx
screwdriver.
One coaxial cable consisting of two coaxial parts is connected to one
connection block of an OVP module.
1/1531-COH 109 2073 Uen H 2006-11-06
Page 45
Procedure
•Single coaxial cables
Two coaxial cables are connected to one connection block of an OVP
module.
To connect a coaxial cable to an Overvoltage Protection (OVP) module, do
the following:
Note:The instructions describe the connections to one connection block of
an OVP module.
1.Ensure that the DF is not fastened in place, and that the space beneath it is
accessible. See Section 3.3 on page 10.
2.Remove the rubber sealing in the DF cable entry closest to the OVP
module to be used.
Note:If single coaxial cables are used, then two cable inlets are needed
for connection to one connection block of an OVP module.
3.Insert the cable gland and tighten it with a 20 mm open-ended wrench.
See 1 in the figure below.
4.Pass at least 170 mm of the cable through the cable. See 2 in the figure
below.
Figure 48Cable Gland Attachment and Cable Routing
5.Strip 170 mm of the outer layer of insulation from the cable, using a wire
stripper. See figure below.
1/1531-COH 109 2073 Uen H 2006-11-06
41
Page 46
Installation Instruction
6.If the cable is of dual coaxial type, then leave 12 mm of the outer screen
and strip 15 mm of the insulation of each conductor as shown in the figure
below.
7.Strip 5 mm of the insulation from the ends of the inner conductors.
8.Prepare at least 25 mm of the screens by twisting them as shown in the
figure below.
9.Attach both the screens and two jumpers (thin copper wires) to a single
crimp terminal, as shown in the figure below.
42
Figure 49Stripping Lengths
10. Connect each wire to the terminal block of the OVP module, using a small
screwdriver (<2.5 mm) to open the terminal connectors. See relevant figure
below depending on the OVP variant used.
1/1531-COH 109 2073 Uen H 2006-11-06
Page 47
Procedure
Figure 50Wire Connections Variant 1
Figure 51Wire Connections Variant 2
P014488B
P016851A
11. Attach the wires and screens to the appropriate connectors in the terminal
block.
Note:See the Site Installation Documentation for more information on
12. Attach the single crimp terminal to the cable lug of the OVP module.
1/1531-COH 109 2073 Uen H 2006-11-06
the transmission connections.
43
Page 48
Installation Instruction
Figure 52OVP Module Connection Points
13. Pull the cable back through the cable gland and clamp it by screwing the
cable gland together from underneath. See figure below.
Note:Make sure that the outer screen is in contact with the earth
grounding of the cable gland.
44
Figure 53Cable Secured
14. Make a note of the cable data on the cover of the OVP Module.
15. Reinsert the six screws in the DF and tighten them with a T30 Torx
screwdriver.
To connect a coaxial cable to an Overvoltage Protection (OVP) module, do
the following:
1.Ensure that the DF is not fastened in place, and that the space beneath it is
accessible. See Section 3.3 on page 10.
2.Remove the rubber sealing in the DF cable entry closest to the OVP
module to be used.
3.Insert the cable with its cable gland (1) and tighten it with a 20 mm
open-ended wrench (2). See figure below.
Note:The cable is a dual coaxial cable, that is, the cable consists of two
coaxial parts.
1/1531-COH 109 2073 Uen H 2006-11-06
45
Page 50
Installation Instruction
1
2
P014941A
Figure 55Cable Gland Attachment and Cable Routing
4.Push both connectors of the dual coaxial cable on to the connectors of
the OVP module.
46
P014942A
Figure 56Cable Connections
Note:Make sure that the outer screen is in contact with the earth grounding
of the cable gland.
1/1531-COH 109 2073 Uen H 2006-11-06
Page 51
Procedure
Figure 57Cable Connections
5.Make a note of the cable data on the cover of the OVP Module.
6.Reinsert the six screws in the DF and tighten them with a T30 Torx
screwdriver.
3.7.4Connecting Transmission Cables, Fiber Optic - Alternative 4
Note:Handle the fiber optic cables with care and do not exceed the minimum
bending radius of 35 mm.
1.Ensure that the DF is not fastened in place, and that the space beneath
it is accessible.
2.Remove the rubber sealing in the DF cable entry closest to the OVP
module to be used.
3.Remove the end nut from the fixed cable gland on the fiber optic cable and
pass the cable through one the of cable inlets as shown in the figure above.
4.Remove the rubber sealing from the cable entry to be used.
5.Insert the cable gland in of the DF cable entry as shown in the figure above.
6.Reattach the nut and tighten it, using a 26 mm open-ended wrench.
1/1531-COH 109 2073 Uen H 2006-11-06
47
Page 52
Installation Instruction
Figure 58Fiber Optic Cables
7.Route the cables inside the cabinet and connect them to the ET-M4 board,
ET-MC41s board or Digital Cross-Connect (DXX).
3.8Connecting Site Transmission from Transmission
Equipment Installed in the RBS (Alternative)
Transmission equipment can be installed internally in the RBS 3107 cabinet.
There are a several options. The solutions recommended and supported by
Ericsson are described in the following document:
Transmission Configurations and Installation
48
1/1531-COH 109 2073 Uen H 2006-11-06
Page 53
3.9Connecting External Alarms
Procedure
P014435C
Figure 59Possible OVP Module Positions
The DF enables the connection of 12 external alarms, with overvoltage
protection.
To connect an external alarm cable to the RBS 3107, do the following:
Note:The instructions describe the connections to one connection block of
an OVP module.
1.Ensure that the DF is not fastened in place, and that the space beneath it is
accessible. See Section 3.3 on page 10.
2.Remove the rubber sealing in the DF cable entry closest to the OVP
module to be used.
3.Insert the cable gland in the DF cable entry closest to the OVP module to
be used and tighten it with a 20 mm open-ended wrench. See 1 in the
figure below.
4.Pass at least 170 mm of the cable through the cable gland. See 2 in the
figure below.
1/1531-COH 109 2073 Uen H 2006-11-06
49
Page 54
Installation Instruction
Figure 60Cable Gland Attachment and Cable Routing
5.Strip 170 mm of the outer layer of insulation from the cable, using a wire
stripper. See figure below.
6.Leave 12 mm of the outer screen.
Note:The cable screen must be earth grounded at the DF.
7.Strip 5 mm of the insulation from the ends of the wires.
50
1/1531-COH 109 2073 Uen H 2006-11-06
Page 55
170
Procedure
5
12
P014982A
Figure 61Stripping Lengths
8.Connect each wire to the terminal block of the OVP module, using a small
screwdriver (<2.5 mm) to open the terminal connectors. See relevant figure
below depending on the OVP variant used.
Figure 62Wire Connections Variant 1
1/1531-COH 109 2073 Uen H 2006-11-06
P014488B
51
Page 56
Installation Instruction
Figure 63Wire Connections Variant 2
9.Attach the wires to the appropriate connectors in the terminal block.
Note:See the Site Installation Documentation for more information on the
alarm cable connections.
Figure 64OVP Module Connection Points
P016851A
52
10. Pull the cable back through the cable gland and clamp it by screwing the
cable gland together from underneath. See figure below.
Note:Make sure that the outer screen is in contact with the earth
grounding of the cable gland.
1/1531-COH 109 2073 Uen H 2006-11-06
Page 57
Figure 65Cable Secured
Procedure
P014491C
11. Make a note of the cable data on the cover of the OVP Module.
12. Reinsert the six screws in the DF and tighten them with a T30 Torx
screwdriver.
3.10Connecting the Ericsson GPS Solution
To install the Ericsson GPS Solution, see the following:
Several antenna connections are possible, depending on the cell configuration,
Filter Unit (FU) type, and so on. For information about antenna connections to
the RBS cabinet, see the Site Installation Documentation.
Note:All earth grounding of RF cables must comply with the instructions in
Grounding Guidelines for RBS Sites. In addition, the MET must be
positioned as close as possible to the cabinet, and the total length of
the earth grounding system from the RF cables through the MET to the
earth grounding point of the cabinet must not exceed 2 meters.
To connect the Radio Frequency (RF) cables between the antenna system
and the RBS 3107 do the following:
1.Remove the two cable inlet parts.
1/1531-COH 109 2073 Uen H 2006-11-06
53
Page 58
Installation Instruction
Figure 66RF Cable Inlet
2.Route the RF cables through the cable inlet.
54
Figure 67RF Cable Routing
Note:Leave the dust caps on unused connectors on FUs. If no dust caps are
found, inform the person in charge that these are needed.
3.Connect the first cable to the lower connector of the left most FU, and
then the next cable to upper connector. Proceed in the same way with
the other FUs. The order is shown in the figure below. Each cable must
be tightened to a torque of 25 Nm, using a torque wrench and a 32 mm
open-ended head.
1/1531-COH 109 2073 Uen H 2006-11-06
Page 59
Procedure
2
1
4
3
6
5
P014479C
Figure 68RF Cables
4.Press each cable into the gasket of the cable inlet in the order indicated
in the figure above.
5.Check that each cable is as straight as possible and make necessary
adjustments. No sharp bends in cables are allowed close to connectors.
Note:Do not exceed the minimum bending radius for the cables.
6.Ensure that the internal cables of the FUs have not been accidentally
loosened.
7.Plug the open holes in the gasket with the supplied plugs.
Note:No holes must be left open.
8.Attach the front part of the cable inlet as shown in the figure above. Tighten
the screws, using T8, T15 and T30 Torx screwdrivers.
3.12Powering Up the RBS
Products not connected to ground risk being damaged by overvoltage or
overcurrent. Always connect products to ground according to instructions.
Do!
551/1531-COH 109 2073 Uen H 2006-11-06
Page 60
Installation Instruction
For details on starting the RBS and checking the installation, see Verification
of Installation at Site.
3.13Performing Concluding Routines
Before leaving the site, complete the following tasks:
1.Clean the site and remove objects such as wrapping paper and cable
offcuts.
2.Dispose of waste in accordance with local regulations.
3.Fill in the Verification Checklist in the Site Installation Documentation binder.
4.Report any faults in accordance with local requirements.
5.Hand over the Site Installation Documentation binder to the person
responsible for the site.
6.Lock all doors and gates to the site.
Environment
Ericsson strongly recommends that installers pay particular attention to the
environment when cleaning the site after RBS installation. In particular, recycle
all waste that can be recycled and sort the rest so that it can be disposed in
accordance with local regulations.
Table 3Recycling and Sorting Waste
Item
Pieces of cable, low metallic content
Cable insulation from crimping, brazing,
or welding
Packing chips
Foam
Recycle or Sort
Sort as plastic
Polystyrene
Bubble plastic
Cable tie clippings
Paper and woodRecycle or sort as paper
Waste metal from cable ladders
Pieces of cable, high metallic content
Nuts bolts, washers, and screws
Recycle or sort as metal
561/1531-COH 109 2073 Uen H 2006-11-06
Page 61
4Related Documents
The following documents are related to these Installation Instructions.
•Personal Health and Safety Information, 124 46-2885
•System Safety Information, 124 46-2886
•Product Handling, 11/1551-HRB 105 102/1
•Grounding Guidelines for RBS Sites, 190 08-EN/LZT 735 0018
•Grounding Material Installation Instruction, 1/1531-CRH 102 130/1