Energenics Wallhugger Series Lint Filter User Manual

1470 Don Street Naples, Florida 34104 Telephone: (239) 643-1711 Fax: (239) 643-6081 Customer Service: (800) 944-1711
Installation & Operation Manual
For ENERGENICS 9002 Control
Wallhugger Series Lint Filter
Table of Contents 1
Description of Lint Filter Operation 2
Receiving and Installation 3
Important Installation Considerations 4
Exhibit A 5
Warnings/Cautions 6
Dimensions and Erection – WH-80 & WH-140 7
Dimensions and Erection – WH-35 & WH-60 8
Piping Requirements 9
Fire Suppression Water System (optional) 10
9002 Control Installation Instructions:
Control Panel (Cover) 9002.0 11 Main Control Box 9002.1 12 Transformer Box 9002.2 13 Pressure Input Box 9002.3 14 Timer Box 9002.3A 15 Main Control Box (Electrical Schematic) 9002.4 16
Maintenance Requirements 17 Parts List 18-19
DESCRIPTION OF LINT FILTER OPERATION
Your new Energenics Lint Filter represents the most advanced features available in the laundry industry to date. The following list the functions and mode of operation:
Blowdown (cleaning) – The Lint Filter will monitor the system backpressure and automatically initiate the blowdown cycle. On the main control the Normal Light will be lit when the system senses airflow from the dryers. As the screen fills with lint the set light will illuminate when the backpressure reaches a set reference (default is .5” w.c.). 30 seconds after the set light illuminating the 6 second blowdown occurs. The setting can be adjusted by the operator by adjusting the pressure input box located on top of the Lint Filter. The adjustment is done by turning a screw at the bottom of the box. 70% of the lint will be removed from the screen even though the dryer(s) may be operating. When the dryer(s) are all off the pressure input box will sense no airflow and will initiate a blowdown signal which will remove 100% of the Lint on the screen. A manual blowdown can also be done by depressing the button on the side of the Lint Filter control. Note that a blowdown cannot occur within 3 minutes of a prior blowdown. This is done to allow the compressed air supply to fully recover.
Optional Excess Pressure Alarm – If for any reason the Lint Filter has not blown down properly (i.e.: compressor turned off) the system will sense a higher backpressure than normal. The excess light on the filter control and the siren and the strobe light both activate. The Filter control will attempt to blowdown every 3 minutes until the excess backpressure condition has terminated. If this condition persist a manual inspection of the lint screen and observation of proper blowdown must be done.
Optional Fire Control System – A normally open sensor located inside of the filter at the top of the inlet will close at 360 degrees F. The control will open the water solenoid, illuminate the strobe as well as energize the siren. The Alarm will be active until 30 seconds after the temperature has dropped bellow 360 degrees F. After 30 seconds the alarm will automatically reset. Inside the control box is a Fire Control test button. Depress the button and the Fire Control will be activated for 30 seconds. The function of the test button is to check the circuit. It does not test the sensor itself. Using a propane torch to the sensor will test the complete system.

Receiving and Installation

Before you sign the Bill of Lading:
1. Receiving- Inspect units inside and out for signs of damage Verify all components are delivered per the Bill of Materials.
Report damage to the carrier IMMEDIATELY. Note ALL damage on the Bill of Lading. This is your responsibility and you must file all claims
The filter is fully assembled and ready for installation. The control, valves, lint bag is in a cardboard box. Make sure both are complete. Per Exhibit A.
2. Installation- Follow instructions attached:
Determine the location with reference to minimum duct work from the tumbler and ease of access for inspection.
If using a lint drop pipe allow enough room for lint to travel down 4’ before the first bend. Max bend angle is 30 degrees.
If using lint bag or container make sure adequate clearance is allowed.
.
Important Installation Considerations
All Energenics Lint Collectors can be mounted indoors or outdoors. If it is mounted outdoors we recommend our Side Discharge or a field installed swept radius elbow (Gooseneck). Do not use a “China type” cap on the discharge. The Pressure transducer should be mounted on top of the filter to prevent condensation running down the tubes into the pressure switch located in the pressure input box. Also, mount the supplied air pressure gauge at the blowdown pipe on top of the filter.
All solenoids should be mounted as practically close to the filter as possible, but always inside the building. This will allow most of the air and water (if equipped with optional Fire Control) piping to remain pressure charged for most efficient operation.
Energenics supplies a reel of wire connected on one end to the Filter Control. In most cases the reel is long enough for most indoor installations. In rare situations the wire is not long enough and must be extended. This is not difficult, but make sure the wire extensions are properly marked for correct termination.
The Filter Control box should be located in a position to be easily seen and in close proximity to personnel. In other words if the Filter Control is located outdoors, 20 feet in the air or in another room away from the laundry personnel, this would be the
Since the Filter uses compressed air it is important that the air receiver (if equipped) be located as close to the filter as possible. The longer the pipe runs the more restrictive. You will need to increase the pipe diameter if the run is very long.
If the installation is a multi-dryer/multi-duct installation it may be necessary to use backdraft dampers to prevent lint backflow into the ducts of turned off dryers. Most dryers have them available as standard equipment or can be ordered to add on.
After everything is mounted and utilities turned on press the manual blowdown button located on the side of the Filter control box and the rotor on the inside the lint filter should spin. Make sure that the air pressure at the filter starts out at 100 and ends at about 60 at the end of the blowdown cycle. If it is too low the rotor won’t turn.
If the Filter is equipped with Fire Suppression the test button is on the inside of the Filter Control. It is on the inside to keep people from pushing the button as they walk by. When the button is pushed the strobe and siren will go on along with the water solenoid valve. The system operates for 5 seconds and turns off automatically.
wrong
location.

Warning and Caution

You have purchased the finest lint filter available for your facility. Please follow these instructions to ensure a safe long life for your filter and facility.
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN AN UNSAFE OPERATING
CONDITION, INCLUDING THE POSSIBILITY OF FIRE.
DO NOT OPERATE ANY DRYER CONNNECTED TO THIS FILTER WITHOUT BEING CERTAIN THE FILTER STARTUP HAS BEEN COMPLETED AND THE FILTER IS IN OPERATING CONDITION.
Insure it is installed in compliance with local codes. Step 1. Install the compressed air (Fire suppression plumbing if ordered), and
piping system(s) including solenoid valves. If the filter is in position, make all final connections.

Step 2. Mount the 9002 control in a visible location on a solid vibration free

surface and connect all components.
Step 3. Provide dedicated electrical service to the transformer and test all systems.
Step 4. Install sheet metal and ducting.

START UP AND OPERATION INSTRUCTIONS

Inspect the filter installation. Is it complete? Review the entire installation requirements prior to startup.
1. Verify the 9002 control wiring.
2. Test the blow down cycle (push manual button on control).
Watch the pressure gauge. It should start at 100psi and should not drop below 80psi during the 6-10 second cycle.
The rotor should turn 6-12 times during blow down. The rotor propulsion is adjustable by increasing the number of horizontal holes on the top horizontal portion of the rotor end.
3. Review maintenance requirements and establish a regular PM schedule.
Loading...
+ 13 hidden pages