Vibration Limit Switch
Level limit switch for all liquids.
Suitable for use in hazardous areas, food and pharmaceuticals
The function is not affected by flow, turbulence, bubbles,
foam, vibration, bulk solids content or build-up.
The Liquiphant is thus the ideal substitute for float
switches.
FTL50:
Compact design, ideal for mounting in pipes and for
installation in areas difficult to access
FTL51:
With extension pipe up to 3 m
(6 m on request)
FTL50H, FTL51H:
With polished tuning fork and easy-to-clean process
connections and housings for food and pharmaceutical
applications.
High corrosion-resistant AlloyC4 (2.4610) is available for
the fork and process connections for applications in very
aggressive liquids.
EEx ia, EEx de and EEx d protection enable it to be used
in hazardous areas.
Your benefits
• Use in safety systems requiring functional safety
to SIL2/SIL3 in accordance with IEC 61508/
IEC 61511-1
• Large number of process connections to choose from:
universal usage
• Wide variety of electronics, e.g. NAMUR, relay,
thyristor, PFM signal output: the right connection for
Application
The Liquiphant M is a level limit switch for use in all
liquids
– for process temperatures of –50 °C to 150 °C
– for pressures up to 100 bar
– for viscosity up to 10000 mm
– for densities 0.5 g/cm3 or 0.7 g/cm3 other settings
available on request
– foam detection on request
2
/s
every process control system
• PROFIBUS PA protocol:
for commissioning and maintenance
• No calibration: quick, low-cost start-up
• No mechanically moving parts: no maintenance,
no wear, long operating life
• Monitoring of fork for damage: guaranteed function
Level limit detectionMaximum or minimum detection in tanks or pipes containing all kinds of liquids, including use in hazardous
areas, food and pharmaceuticals
L00-FTL5xxxx-11-05-xx-xx-000
Function and system design
Measuring principleThe sensor's fork vibrates at its intrinsic frequency.
This frequency is reduced when covered with liquid. The change in frequency then activates a limit switch.
Modularity
Level limit switch
Liquiphant M FTL with electronic versions
FEL51, FEL52, FEL54
Level sensor
Liquiphant M FTL with electronic versions
FEL55, FEL56, FEL57, FEL58
for connecting to a separate switching unit or
or an isolating amplifier FEL50A
for connecting to PROFIBUS PA segment
FEL51/52/54
FEL55/56/57/58/50A
L00-FTL5xxxx-15-05-xx-xx-000
Ex i
Switching unit
PLC
Isolating
amplifier
Segment
coupler
…
E
X
…
E
X
L00-FTL5xxxx-15-05-xx-en-000
4Endress+Hauser
Page 5
Liquiphant M FTL50(H), FTL51(H)
Electronic versions
for level limit switches
Electronic versions
for level sensor
FEL51:
Two-wire AC version;
Switch the load directly into the power supply circuit via the thyristor.
FEL52:
Three-wire DC version;
Switch the load via the transistor (PNP) and separate connection.
FEL54:
Universal current version with relay output;
Switch the loads via 2 floating change-over contacts.
FEL55:
For separate switching unit; signal transmission 16/8 mA along two-wire cabling.
FEL56:
For separate switching unit; signal transmission L-H edge 0.6…1.0 / 2.2…2.8 mA
to EN 50227 (NAMUR) along two-wire cabling.
FEL58:
For separate switching unit; signal transmission H-L edge 2.2…3.5 / 0.6…1.0 mA
to EN 50227 (NAMUR) along two-wire cabling.
Checking of connecting cabling and other devices by pressing a key on the electronic insert.
FEL57:
For separate switching unit; PFM signal transmission;
Current pulses superposed on the power supply along the two-wire cabling.
Cyclical checking from the switching unit without changing levels.
FEL50A:
For connecting to PROFIBUS PA;
Cyclic and acyclic data exchange acc. to PROFIBUS PA Profile 3.0 Discrete Input
Galvanic isolationFEL51, FEL52, FEL50A:
Between sensor and power supply
FEL54:
Between sensor and power supply and load
FEL55, FEL56, FEL57, FEL58:
See Switching unit connected
DesignFTL50:
Compact
FTL51:
With extension pipe
FTL50H:
Compact, with polished tuning fork and hygienic process connections
FTL51H:
With extension pipe, polished tuning fork and hygienic process connections
Input
Measured variableLevel (limit value)
Measuring range
(detection range)
FTL50:
Depends on mounting point.
FTL51:
Depends on mounting point and the pipe extension. Standard 3000 mmm (up to 6000 mm on request)
3
Product densityAdjustment on the electronic insert > 0.5 g/cm
or > 0.7 g/cm3 (other on request)
Endress+Hauser5
Page 6
Electronic insert FEL51 (AC 2-wire)
Power supplySupply voltage: 19...253 V AC
Power consumption: < 0.83 W
Residual current consumption: < 3.8 mA
Short-circuit protection
FEM51 overvoltage protection: overvoltage category III
Electrical connectionTwo-wire AC connection
Always connect in series with a load!
Check the following:
• The residual current in blocked state
(up to 3.8 mA)
• that for low voltage
– the voltage drop across the load is such
that the minimum terminal voltage at the
electronic insert (19 V) when blocked is
not undershot.
– the voltage drop across the electronics when
switched through is observed
(up to 12 V)
• that a relay cannot de-energise with holding
power below 3.8 mA.
If this is the case, a resistor should be
connected parallel to the relay.
(RC module available on request).
• When selecting the relay, pay attention to
the holding power/rated power
(See "Connectable load")
12
min.
19 V
1A
*
R
L1
NNPE
U~ max. 253 V AC
50/60 Hz
Liquiphant M FTL50(H), FTL51(H)
FEL51
External load R
*
(Ground)
be connectedmust
L00-FTL5xxxx-04-05-xx-en-007
Output signal
Safety modeLevelOutput signalLEDs
green red
I
L
12
I
L
< 3.8 mA
L00-FTL2xxxx-07-05-
xx-xx-000
= load current
(switched through)
= residual current
(blocked)
= lit
= unlit
Max.
Min.
< 3.8 mA
12
I
L
12
< 3.8 mA
12
Signal on alarmOutput signal on power failure or in the event of damaged sensor: < 3.8 mA
Connectable load• For relays with a minimum holding power/rated power > 2.5 VA at 253 V AC (10 mA) or
> 0.5 VA at 24 V AC (20 mA)
• Relays with a lower holding power/rated power can be operated by means of an RC module connected
inparallel
• For relays with a maximum holding power/rated power < 89 VA at 253 V AC or < 8.4 VA at 24 V AC
• Voltage drop across FEL51 max. 12 V
• Residual current with blocked thyristor max. 3.8 mA
• Load switched directly into the power supply circuit via the thyristor.
Transient (40 ms) max. 1.5 A, max. 375 VA at 253 V or max. 36 VA at 24 V (not short-circuit proof)
L00-FTL5xxxx-04-05-xx-xx-001
6Endress+Hauser
Page 7
Liquiphant M FTL50(H), FTL51(H)
Electronics FEL51 (AC, in compact housing)
Power supplySupply voltage: 19...253 V AC
Power consumption: < 0.83 W
Residual current consumption: < 3.8 mA
Short-circuit protection
FEM51 overvoltage protection: overvoltage category III
Electrical connectionTwo-wire AC connection
Always connect in series with a load!
Check the following:
• The residual current in
blocked state (up to 3.8 mA)
• that for low voltage
– the voltage drop across
the load is such that the
minimum terminal voltage
at the electronic insert
(19 V) when blocked is not
undershot.
– the voltage drop across
the electronics when switched
through is
observed (up to 12 V).
• That a relay
cannot de-energise with
holding power below 3.8 mA.
If this is the case, a resistor
should be connected parallel
to the relay.
(RC module available on request).
Connector
FTL5#(H)- #######C3#
FTL5#(H)- #######D3#
(Pg11)
or
FTL5#(H)- #######E3#
(NPT ½")
MAXMIN
(GN/YE)(GN/YE)
1
(BU)
3
(BN)
>19V
R
1.0 A
L1
1
>19V
1.0 A
L1
N
3
R
N
(Ground)
(Ground)
PE
(Ground)
PE
(Ground)
1
(BU)
L1
PE
1
L1
PE
L00-FTL5xxxx-04-05-xx-en-008
>19V
1.0 A
>19V
1.0 A
2
(BK)
R
N
2
R
N
Output signal
Safety modeLevelOutput signalLEDs
green red
I
L
13
I
L
< 3.8 mA
L00-FTL2xxxx-07-05-
xx-xx-000
= load current
(switched through)
= residual current
(blocked)
= lit
= unlit
Max.
Min.
< 3.8 mA
13
I
L
12
< 3.8 mA
12
Signal on alarmOutput signal on power failure or in the event of damaged sensor: < 3.8 mA
Connectable load• For relays with a minimum holding power/rated power > 2.5 VA at 253 V AC (10 mA) or
> 0.5 VA at 24 V AC (20 mA)
• Relays with a lower holding power/rated power can be operated by means of an RC module connected
inparallel
• For relays with a maximum holding power/rated power < 89 VA at 253 V AC or < 8.4 VA at 24 V AC
• Voltage drop across FEL51 max. 12 V
• Residual current with blocked thyristor max. 3.8 mA
• Load switched directly into the power supply circuit via the thyristor.
Transient (40 ms) max. 1.5 A, max. 375 VA at 253 V or max. 36 VA at 24 V (not short-circuit proof)
L00-FTL5xxxx-04-05-xx-xx-001a
Endress+Hauser7
Page 8
Electronic insert FEL52 (DC PNP)
Power supplySupply voltage: 10…55 V DC
Ripple: max. 1.7 V, 0…400 Hz
Current consumption: max. 15 mA
Power consumption: max. 0.83 W
Reverse polarity protection
Overvoltage protection FEL52: overvoltage category III
Electrical connectionThree-wire DC connection
Preferably used with programmable
logic controllers (PLC).
DI module as per EN 61131-2.
Positive signal at switching output of
the electronics (PNP);
Output blocked on reaching limit.
Liquiphant M FTL50(H), FTL51(H)
FEL52
12 3
(+)
Output signal
I
L
< 100 μA
L00-FTL2xxxx-07-05-
xx-xx-000
= load current
(switched through)
= residual current
(blocked)
= lit
= unlit
0.5 A
e.g.
Relay
PLC
–
L–
L+
...
U– 10…55 V DC
Safety modeLevelOutput signalLEDs
green red
L++
I
L
13
Max.
< 100 µA
13
L++
I
L
13
Min.
< 100 µA
13
L00-FTL5xxxx-04-05-xx-en-001
L00-FTL5xxxx-04-05-xx-xx-004
Signal on alarmOutput signal on power failure or in the event of damaged sensor: < 100 μA
Connectable load• Load switched via the transistor and separate PNP connection, max. 55 V DC
• Load current max. 350 mA (pulsed overload and short-circuit protection)
• Residual current < 100 μA (with transistor blocked)
• Capacitive load max. 0.5 μF at 55 V, max. 1.0 μF at 24 V
• Residual voltage < 3 V (with transistor switched through)
8Endress+Hauser
Page 9
Liquiphant M FTL50(H), FTL51(H)
Electronics FEL52 (DC PNP, in compact housing)
Power supplySupply voltage: 10…55 V DC
Ripple: max. 1.7 V, 0…400 Hz
Current consumption: max. 15 mA
Power consumption: max. 0.83 W
Reverse polarity protection
Overvoltage protection FEL52: overvoltage category III
Electrical connectionThree-wire DC connection
Preferably used with programmable
logic controllers (PLC).
DI module as per EN 61131-2.
Positive signal at switching
output of the electronics (PNP);
Output blocked on reaching limit.
Connector
FTL5#(H)- #######N3#
(M12x1)
52018763
FTL5#(H)- #######N3#
(M12x1)
52010285 / 52024216
MAXMIN
1
2
3
(BN)
4
(BK)
0.5 A
L–L+
(WT)
(BU)
R
1
2
(WT)
(BU)
L–L+
(BN)
3
4
(BK)
R
0.5 A
Output signal With valve connector or cable tail
FTL5#(H)- #######D3#
(Pg11)
or
FTL5#(H)- #######E3#
(NPT ½")
FTL5#(H)- #######C3#
L–L–L+L+
PEPE
(Ground)(Ground)
(GN/YE)
1
(BU)
3
(BN)
L–L–L+L+
PEPE
(Ground)(Ground)
R
0.5 A
R
0.5 A
2
(BK)
+
–
(GN/YE)
1
(BU)
+
–
Safety modeLevelOutput signalLEDs
green red
11
R
(BN)
R
L00-FTL5xxxx-04-05-xx-en-010
0.5 A
3
0.5 A
22
33
+
–
2
(BK)
+
–
L++
I
L
32
I
L
< 100 μA
L00-FTL2xxxx-07-05-
xx-xx-000
= load current
(switched through)
= residual current
(blocked)
= lit
= unlit
Max.
Min.
L++
< 100 µA
32
L++
I
L
23
L++
< 100 µA
23
L00-FTL5xxxx-04-05-xx-xx-004a
Endress+Hauser9
Page 10
With M12x1 connector 52010285 / 52024216 (without LEDs)
gn
ye
rd
Safety modeLevelOutput signalLEDs
Liquiphant M FTL50(H), FTL51(H)
L00-FTL5xxxx-16-05-
xx-xx-002
Max.
I
L
< 100 μA
= load current
(switched through)
= residual current
(blocked)
= lit
Min.
= unlit
L00-FTL2xxxx-07-05-
xx-xx-000
With M12x1 connector 52018763 (with LEDs)
ye 1
ye 2
L00-FTL5xxxx-16-05-
xx-xx-001
gn
Safety modeLevelOutput signalLEDs
Max.
I
L
< 100 μA
= load current
(switched through)
= residual current
(blocked)
= lit
Min.
= unlit
L00-FTL2xxxx-07-05-
xx-xx-000
L+–
I
L
12
L+–
< 100 µA
12
L+–
I
L
14
L+–
< 100 µA
14
L00-FTL5xxxx-04-05-xx-xx-010
L+–
I
L
12
L+–
< 100 µA
12
L+–
I
L
14
L+–
< 100 µA
14
L00-FTL5xxxx-04-05-xx-xx-011
Signal on alarmOutput signal on power failure or in the event of damaged sensor: < 100 μA
Connectable load• Load switched via the transistor and separate PNP connection, max. 55 V DC
• Load current max. 350 mA (pulsed overload and short-circuit protection)
• Residual current < 100 μA (with transistor blocked)
• Capacitive load max. 0.5 μF at 55 V, max. 1.0 μF at 24 V
• Residual voltage < 3 V (with transistor switched through)
10Endress+Hauser
Page 11
Liquiphant M FTL50(H), FTL51(H)
Electronic insert FEL54 (AC/DC with relay output)
Power supplySupply voltage: 19…253 V AC, 50/60 Hz or 19…55 V DC
Power consumption: max. 1.3 W
Reverse polarity protection
Overvoltage protection FEL54: overvoltage category III
Electrical connectionUniversal current connection with relay output
Power supply:
Please note the different voltage ranges
for AC and DC.
Output:
When connecting an instrument with
high inductance, provide a spark arrester
to protect the relay contact.
A fine-wire fuse (depending on the
load connected) protects the relay
contact on short-circuiting.
Both relay contacts switch simultaneously.
* When jumpered, the relay
output works with NPN logic.
0.5 A
FEL54
12678345
*
Output signal
** See below "Connectable load"
= relay energised
= relay de-energised
= lit
= unlit
L00-FTL2xxxx-07-05-
xx-xx-001
NC
NO
C
a
u
N
L1
L+
U~ 19…253 V AC, 50/60 Hz
U– 19… 55 V DC
PE
(Ground)
L–
...
****
NO
r
a
Safety modeLevelOutput signalLEDs
green red
Max.
Min.
354
354
354
354
687
687
687
687
L00-FTL5xxxx-04-05-xx-xx-005
NC
C
r
u
L00-FTL5xxxx-04-05-xx-xx-002
Signal on alarmOutput signal on power failure or in the event of damaged sensor: relay de-energised
Connectable load• Loads switched via 2 floating change-over contacts (DPDT)
• I~ max. 6 A (EEx d 4 A), U~ max. 253 V AC; P~ max. 1500 VA, cos ϕ = 1, P~ max. 750 VA, cos ϕ > 0.7
•I% max. 6 A (EEx d 4 A) to 30 V, I% max. 0.2 A to 125 V
• When connecting a low-voltage circuit with double isolation according to IEC 1010 the following applies:
total of voltages of relay output and power supply max. 300 V
Endress+Hauser11
Page 12
Electronic insert FEL55 (8/16 mA)
1 2
FEL55
–
EEx ia
+
E
X
E
X
U– 1
1…36 V DC
...
e.g. PLC
Power supplySupply voltage: 11...36 V DC
Power consumption: < 600 mW
Reverse polarity protection
Overvoltage protection FEL55: overvoltage category III
Electrical connectionTwo-wire connection for separate switching unit
For connecting to programmable
logic controllers (PLC).
AI module 4...20 mA to EN 61131-2.
Output signal jump from high to low
current on limit.
EEx ia
Liquiphant M FTL50(H), FTL51(H)
FEL55
12
X
E
Output signal
~ 16 mA
~8 mA
L00-FTL2xxxx-07-05-
xx-xx-000
= 16 mA ± 5 %
= 8 mA ± 6 %
= lit
= unlit
E
X
–
+
...
U– 1
1…36 V DC
e.g. PLC
L00-FTL5xxxx-04-05-xx-en-000
Safety modeLevelOutput signalLEDs
green red
+
~16 mA
21
Max.
+
~8 mA
21
+
~16 mA
21
Min.
+
~8 mA
21
L00-FTL5xxxx-04-05-xx-xx-006
Signal on alarmOutput signal on power failure or in the event of damaged sensor: < 3.6 mA
Connectable load• R = (U - 11 V) : 16.8 mA
• U = connection voltage: 11…36 V DC
Example:
PLC with 250 Ω loop powered input
250 Ω = (U – 11V) / 16, 8 mA
4,2 [Ω/Α] = U – 11 V
U = 15,2 V
12Endress+Hauser
Page 13
Liquiphant M FTL50(H), FTL51(H)
Electronic insert FEL56 (NAMUR L-H edge)
Power supplyPower consumption: < 6 mW bei I < 1 mA; < 38 mW bei I = 2,2...4 mA
Connection data interface: IEC 60947-5-6
Electrical connectionTwo-wire connection for separate switching unit
For connecting to isolating amplifiers
acc. to NAMUR (IEC 60947-5-6),
e.g. FXN421, FXN422, FTL325N,
FTL375N or Commutec SIN100,
SIN110 from Endress+Hauser.
Output signal jump from low
to high current on limit.
(L-H edge)
12
FEL56
Output signal
Connecting to multiplexer:
Set clock time to min. 2 s.
EEx ia
X
E
H
I
L
–
+
Isolating amplifier
to
IEC 60947-5-6
(NAMUR)
E
X
Safety modeLevelOutput signalLEDs
green red
0.6 …
+
1.0 mA
Max.
21
2.2 …
+
2.8 mA
21
L00-FTL5xxxx-04-05-xx-en-004
L00-FTL5xxxx-07-05-
xx-xx-002
= lit
= flashes
= unlit
Min.
0.6 …
+
1.0 mA
21
2.2 …
+
2.8 mA
21
L00-FTL5xxxx-04-05-xx-xx-003
Signal on alarmOutput signal in the event of damaged sensor: > 2.2 mA
Connectable load• See Technical Data of isolating amplifier connected according to IEC 60947-5-6 (NAMUR)
Endress+Hauser13
Page 14
Liquiphant M FTL50(H), FTL51(H)
Electronic insert FEL58 (NAMUR H-L edge)
Power supplyPower consumption: < 6 mW bei I < 1 mA; < 38 mW bei I = 2,2...4 mA
Connection data interface: IEC 60947-5-6
Electrical connectionTwo-wire connection for separate switching unit
For connecting to isolating amplifiers
acc. to NAMUR (IEC 60947-5-6),
e.g. FXN421, FXN422, FTL325N,
FTL375N or Commutec SIN100,
SIN110 from Endress+Hauser.
Output signal jump from high
to low current on limit.
(H-L edge)
12
FEL58
Output signal
Additional function:
Test key on the electronic insert.
Pressing the key breaks the connection
to the isolating amplifier.
Note!
!
For Ex-d applications, the additional function
can only be used if the housing is not exposed
to an explosive atmosphere.
Connecting to multiplexer:
Set clock time to min. 2 s.
Safety modeLevelOutput signalLEDs
Max.
EEx ia
H
I
L
–
+
Isolating amplifier
to
IEC 60947-5-6
(NAMUR)
2.2 …
+
3.5 mA
21
0.6 …
+
1.0 mA
21
X
E
E
X
L00-FTL5xxxx-04-05-xx-en-002
green yellow
2.2 …
+
3.5 mA
21
0.6 …
+
1.0 mA
21
L00-FTL5xxxx-04-05-xx-xx-007
L00-FTL5xxxx-07-05-
xx-xx-002
= lit
= flashes
= unlit
Min.
Signal on alarmOutput signal in the event of damaged sensor: < 1.0 mA
Connectable load• See Technical Data of isolating amplifier connected according to IEC 60947-5-6 (NAMUR)
• Connection also to isolating amplifiers which have special safety circuits (I > 3.0 mA)
14Endress+Hauser
Page 15
Liquiphant M FTL50(H), FTL51(H)
Electronics FEL58 (NAMUR H-L edge,
in compact housing)
Power supplyPower consumption: < 6 mW bei I < 1 mA; < 38 mW bei I = 2,2...4 mA
Connection data interface: IEC 60947-5-6
Electrical connectionTwo-wire connection for separate switching unit
For connecting to isolating
amplifiers acc. to
NAMUR (IEC 60947-5-6),
e.g. FXN421, FXN422,
FTL325N, FTL375N
or Commutec SIN100,
SIN110 from Endress+Hauser.
Output signal jump from high
to low current on limit.
(H-L edge)
Connector
FTL5#(H)- #######N3#
(M12x1)
52018763
FTL5#(H)- #######N3#
(M12x1)
52010285 / 52024216
MAXMIN
2
(WT)
3
(BU)
–
1
(BN)
4
(BK)
1
2
3
(BN)
4
(BK)
–+
(WT)
(BU)
+
Output signal
Additional function:
If the test magnet is held
against the marking on the
nameplate, the output signal
is inverted.
Connecting to multiplexer:
Set clock time to min. 3 s.
The NAMUR interface has
a defined power consumption.
Thus, it is not possible to use
the M12 connector with
integrated LED (52018763).
FTL5#(H)- #######D3#
(Pg11)
or
FTL5#(H)- #######E3#
(NPT ½")
FTL5#(H)- #######C3#
(BU)
1
3
–
+
1
3
(BN)
+
–
(BU)
1
+
1
+
Safety modeLevelOutput signalLEDs
green yellow
2.2…
+–
3.5 mA
13
Max.
0.6…
+–
1.0 mA
13
2
–
2
(BK)
–
L00-FTL5xxxx-04-05-xx-en-009
2.2…
+–
3.5 mA
12
0.6…
+–
1.0 mA
12
L00-FTL5xxxx-04-05-xx-xx-007a
L00-FTL5xxxx-07-05-
xx-xx-002
= lit
= flashes
= unlit
Min.
Signal on alarmOutput signal in the event of damaged sensor: < 1.0 mA
Connectable load• See Technical Data of isolating amplifier connected according to IEC 60947-5-6 (NAMUR)
• Connection also to isolating amplifiers which have special safety circuits (I > 3.0 mA)
Endress+Hauser15
Page 16
Electronic insert FEL57 (PFM)
Power supplySupply voltage: 9,5...12,5 V DC
Current consumption: 10...13 mA
Power consumption: < 150 mW
Reverse polarity protection
Electrical connectionTwo-wire connection for separate switching unit
For connecting to switching units
Nivotester FTL320, FTL325P,
FTL370, FTL372, FTL375P
(also with cyclical checking)
Commutec SIF101, SIN111
from Endress+Hauser.
Output signal jump of PFM signal
from high to low frequency
when sensor is covered.
Switching between minimum/maximum
safety in the Nivotester.
Additional function "cyclical checking":
After interruption of the power supply,
a test cycle is activated which checks
the sensor and electronics without any
change in level.
Approved for overfill protection acc. to WHG,
Germany.
The following can be switched at the
electronic insert:
– Standard (STD):
for low corrosive liquids;
simulation approx. 8 s
tuning fork exposed – covered – exposed.
– Extended (EXT):
for highly corrosive liquids;
simulation approx. 41 s
tuning fork exposed – covered – corroded –
exposed.
The check is activated and monitored at the
switching unit.
EEx ia
PFM
50 /
150 Hz
Liquiphant M FTL50(H), FTL51(H)
FEL57
12
X
E
E
X
–+
78
3334
3738
d4d2
z4z2
z6d6
21
Nivotester
FTL320
FTL325P 1CH
FTL325P 3CH
FTL370/372
FTL375P 1CH
Input 1
FTL372
FTL375P 2CH
Input 2
FTL375P 3CH
Input 3
Commutec S
SIF101, SIF111
L00-FTL5xxxx-04-05-xx-en-003
16Endress+Hauser
Page 17
Liquiphant M FTL50(H), FTL51(H)
Switching behaviour of the connected device:
Output signal
Fail-safe mode
set at
switching unit
Max.
Max.
Max.
Max.
Min.
Min.
Min.
Min.
Setting
at FEL57
STD
EXT
STD
EXT
STD
EXT
STD
EXT
Fork
free
free
covered
covered
free
free
covered
covered
Switching status of relay in switching unit
on = energisedoff = de-energised
Test startEnd of test start
(power off)(power on)
>3s
on
on
off
off
off
off
on
on
off
off
off
off
~3son
~3son
~3son
~3son
~5soff
~5soff
off
off
~5soff
*
~7soff
*
~5soff
*
~5soff
*
~2son
~2son
~3son
on
~35son
~2soff
~35soff
off
~30son
on
off
~3soff
L00-FTL5xxxx-05-05-xx-en-000
on
on
* De-energised on power supply failure
Please note this switching response and function of the plant, especially when replacing a Liquiphant with an
EL17Z or FEL37 electronic insert by a Liquiphant M with the FEL57 electronic insert.
Safety modeLevelOutput signal
(PFM)
150 Hz
LEDs
green yellow
= lit
50 Hz
L00-FTL5xxxx-04-05-xx-xx-008
L00-FTL2xxxx-07-05-
xx-xx-000
= unlit
Signal on alarmOutput signal on power failure or in the event of damaged sensor: 0 Hz
Connectable load• Floating relay contacts in the connected switching unit Nivotester FTL320, FTL325P, FTL370, FTL372,
FTL375P or Commutec SIF101, SIF111
• For contact load see the Technical Data of the switching unit
Endress+Hauser17
Page 18
Electronic insert FEL50A (PROFIBUS PA)
Electrical connectionTwo-wire connection for power supply and data transfer
Liquiphant M FTL50(H), FTL51(H)
For connecting to PROFIBUS PA
Additional functions:
– Digital communication enables the
representation, reading and editing
of the following parameters:
Fork frequency, switch-on frequency,
switch-off frequency, switch-on time and
switch-off time, status, measured value,
density switch.
– Matrix locking possible
– Switch to WHG mode possible
(WHG approval).
– For a detailed description see BA198F
– You can also visit
www.profibus.com for more information
12
PA–PA +
...
U– 9…32 V DC
Segment coupler
FEL50A
–
–
PROFIBUS PA
–
–
X
E
E
X
L00-FTL5xxxx-04-05-xx-en-005
PC with Commuwin II
Proficard or Profiboard
Segment coupler
PROFIBUS DP
X
E
PROFIBUS PA
E
X
PLC
L00-FTL5xxxx-04-05-xx-en-006
18Endress+Hauser
Page 19
Liquiphant M FTL50(H), FTL51(H)
Output signal
SettingLevelLEDs
not
inverted
= litinverted
= unlit
L00-FTL2xxxx-07-05-
xx-xx-000
Signal on alarm• Failure information can be opened using the following interfaces:
Yellow LED flashing, status code, diagnostic code; see BA198F
FEL50A
greenyellow
OUT_D = 0
PA bus signal
OUT_D = 1
PA bus signal
OUT_D = 1
PA bus signal
OUT_D = 0
PA bus signal
L00-FTL5xxxx-04-05-xx-xx-009
Endress+Hauser19
Page 20
Connection and function
Liquiphant M FTL50(H), FTL51(H)
Connecting cables• Electronic inserts: cross-section max. 2.5 mm2; strand in ferrule to DIN 46228
• Protective earth in housing: cross-section max. 2.5 mm
2
• External equipotential bonding connection on housing: cross-section max. 4 mm
Fail-safe modeMinimum/maximum residual current safety selectable on electronic insert
(with FEL57 on Nivotester only)
Max. = maximum safety:
The output switches to the power fail response when the fork is covered
For use with overfill protection for example
Max. = minimum safety:
The output switches to the power fail response when the fork is exposed
For use with dry running protection for example
Switching timeWhen fork is covered: approx. 0.5 s
When fork is exposed: approx. 1.0 s
Other switching times on request
Additionally configurable for PROFIBUS PA: 0.5...60 s
Switch-on behaviourWhen switching on the power supply, the output assumes the alarm signal.
After max. 3 s it assumes the correct switching mode (Exception: FEL57)
Performance characteristics
2
Reference operating
conditions
Ambient temperature: 23 °C
Medium temperature: 23 °C
Product density: 1 g/cm
3
(water)
Viscosity: 1 mm2/s
Medium pressure p
: 0 bar
e
Sensor mounting: vertical from above
Density switch: to > 0.7
Maximum measured errorSpecified by mounting position: max. +/–1 mm
Repeatability0.1 mm
HysteresisApprox. 2 mm
Influence of medium
Max. +1.8…–2.8 mm (–50…+150 °C)
temperature
3
Influence of product densityMax. +4.8…–3.5 mm (0.5…1.5 g/cm
)
Influence of medium pressureMax. 0…–2.5 mm (–1…64 bar)
Switchpoint
for
reference conditions
13 mm
L00-FTL5xxxx-06-05-xx-en-000
20Endress+Hauser
Page 21
Liquiphant M FTL50(H), FTL51(H)
Operating conditions
InstallationInstallation instructions
Switch pointson the sensor depend on the mounting position, with reference to water,
3
density 1 g/cm
, 23 °C, pe 0 bar.
4mm
13 mm
Mounting from aboveMounting from belowMounting from the side
!
Examples of mountingExamples of mounting with regard to the viscosity ν of the liquid and the amount of build-up
Note!
The switchpoints of the Liquiphant M are at other positions to those of the previous version Liquiphant II.
Optimum mounting, without problem even with high viscosity:
Position the fork so that the narrow edge of the tines is vertical.
This ensures that the liquid can run off easily.
4mm
L00-FTL5xxxx-06-05-xx-xx-001
L00-FTL5xxxx-11-05-xx-xx-001
Vertical from aboveFlush-mounted from the side
Endress+Hauser21
Page 22
Liquiphant M FTL50(H), FTL51(H)
With build-up on the tank walls:
* Ensure that there is sufficient distance between the build-up expected on the tank wall and the fork.
*
*
L00-FTL5xxxx-11-05-xx-xx-002
Vertical from aboveProtruding into the tank from the side
2
Mounting positions with low viscosity (up to 2000 mm
* Deburr the nozzle surfaces
/s):
*
Mounting in piping from 2"
Fluid velocities up to 5 m/s for viscosity 1 mm2/s and density 1 g/cm3.
(Check the function for other operating conditions.)
*
min. 25
(min. 1 in)
L00-FTL5xxxx-11-05-xx-en-003
L00-FTL5xxxx-11-05-xx-xx-004
22Endress+Hauser
Page 23
Liquiphant M FTL50(H), FTL51(H)
Support the Liquiphant M FTL51(H)
in the event of high dynamic loads.
* Additional temperature range for devices with a temperature spacer or flameproof bushing
Ambient temperature limits–50…+70 °C (function with restricted data)
Endress+Hauser23
Page 24
Storage temperature–50…+80 °C
*
p
e
bar
si)
T
p
°C
(°F)
64
(928)
–50
(–58)
150
(300)
0
(32)
–1
(–14.5)
100
(1450)
Climate classClimate protection to IEC 68, Part 2-38, Fig. 2a
Degree of protection• Polyester, steel and aluminium housings: IP66/IP67 to EN 60529
• Aluminium housing (EEx d, EEx de): IP66/IP68 to EN 60529 (1 m, 24 h)
• Compact housing:
– IP65 with valve connector Pg11/NPT ½
– IP66/68 with 5m cable tail
– IP66/68 with M12x1 connector (52010285) 316L (metal);
– IP69k with connector (52024216), elbowed / L= 5 m, without build-in LEDs
– IP69k with connector (52018763), elbowed / L= 5 m, with build-in LEDs
Vibration resistanceTo IEC 68, Part 2-6 (10…55 Hz, 0.15 mm, 100 cycles)
Electromagnetic compatibilityInterference emission to EN 61326, Electrical Equipment Class B
Interference immunity to EN 61326; Annex A (Industrial) and NAMUR Recommendation NE 21 (EMC)
Liquiphant M FTL50(H), FTL51(H)
Medium conditions
Medium temperature range–50…+150 °C; for exceptions, see "Process connections"
Thermal shockMax. 120 °C/s
Medium pressure p
Test pressurepe = 64 bar:
e
(–58)
–50
p
e
bar
(p(psi)
100
(1450)
(928)
(–14.5)
64
–1
0
(32)
* Allowed pressure rating by selecting the "100 bar" option (see "Product structure" code 060)
Exceptions see "Process connections"
max. 100 bar (1.5 times the medium pressure p
); no function during test pressure
e
Burst pressure of diaphragm 200 bar
pe = 100 bar:
max. 150 bar (1.5 times the medium pressure p
); no function during test pressure
e
Burst pressure of diaphragm 400 bar
*
150
(300)
T
°C
(°F)
p
L00-FTL5xxxx-05-05-xx-xx-003
State of aggregationLiquid
24Endress+Hauser
Page 25
Liquiphant M FTL50(H), FTL51(H)
Density0.7 g/cm3 = delivery status
0.5 g/cm3* adjustable over switches
* Density settings for the compact housing on request
2
ViscosityMax. 10000 mm
/s
Solids contentMax. ø5 mm
Mechanical construction
DesignSummary of all electrical and mechanical versions
Plug-in electronic inserts to mount in the housing
FEL51*:
FEL52*:
FEL54:
FEL55:
FEL56:
L00-FTL5xxxx-03-05-xx-xx-000
* Electronics also available as compact housing. The electronics cannot be exchanged!
FEL58*:
FEL57:
FEL50A:
Two-wire AC connection
Three-wire DC connection PNP
Universal current connection, 2 relay outputs
Output 16/8 mA for separate switching unit
Output 0.6…1.0 / 2.2…2.8 mA for separate switching unit (NAMUR)
Output 2.2…3.5 / 0.6…1.0 mA for separate switching unit (NAMUR)
Output 150/50 Hz, PFM, for separate switching unit (Nivotester)
Digital communication PROFIBUS PA
G ¾, DIN ISO 228/I
R ¾, EN10226
NPT ¾, ANSI B 1.20.1
(AF 32)
G 1, DIN ISO 228/I
R 1, EN10226
NPT 1, ANSI B 1.20.1
(AF 41)
Diverse
hygienic and aseptic
connections
Flanges to DIN, ANSI, JIS
from DN 25 / 1"
Endress+Hauser25
Page 26
Liquiphant M FTL50(H), FTL51(H)
Dimensions in mm
(1 mm = 0,0394 in)
Sensors
Compact,
with extension pipe up to 3 m (to 6 m on request)
or special length "L II" (see also page 30)
Bushings
Temperature spacer and flameproof bushing
Housing and sensor FTL50(H)
Compact housing
Compact Length L Length L II
L00-FTL5xxxx-03-05-xx-xx-018
pe = 64 bar64 bar64 bar
100 bar100 bar
L00-FTL5xxxx-03-05-xx-xx-005
1.2.3.
40
30
1. 5 m cable
2. M12 connector
3. Pg11/NPT ½ connector
Polyester housing
232
166
ø40
32 AF
ø85max. 76
199
133
ø40
max. 155
32 AF
*
141
206
*
L00-FTL5xxxx-06-05-xx-en-008
17.5
L00-FTL5xxxx-06-05-xx-xx-004
ø40
32 AF
max. 40.7
26Endress+Hauser
Page 27
Liquiphant M FTL50(H), FTL51(H)
Steel housing
Aluminium housing
ø76max. 64
max. 150
*
L00-FTL5xxxx-06-05-xx-xx-005
max. 65
ø80
max. 173
ø21.5
max. 60
*
10
L00-FTL5xxxx-06-05-xx-xx-006
~25
!
Aluminium housing
with separate
max. 65
max. 97
connection compartment
max. 190
*
L00-FTL5xxxx-06-05-xx-xx-007
* see "Process connections"
Note!
The switchpoints of the Liquiphant M are at other positions to those of the previous version Liquiphant II.
Bushings: temperature spacer, flameproof bushing
Temperature spacer
Provides sealed insulation
for the vessel and normal ambient
temperatures for the housing.
Flameproof bushing
Protects the housing from pressures
up to 100 bar if the sensor is damaged.
Provides sealed insulation
for the vessel and normal ambient
temperatures for the housing.
Vessel
insulation
additional length
140 mm
L00-FTL5xxxx-11-05-xx-en-000
Endress+Hauser27
Page 28
Process connections for FTL50(H) and FTL51(H)
Liquiphant M FTL50(H), FTL51(H)
Process connectionDimensionsAccessoriesPressure
Temperature
G ¾
DIN ISO 228/l
with defined
GQ2
GQ5
32 AF
66.5
max. 100 bar
max. 150 °C
50.5
thread start
With elastomer
flat seal to DIN 7603:
supplied
G ¾
DIN ISO 228/l
with defined
thread start
For flush-mounted
installation in
welding neck
GQ2
GQ5
32 AF
L00-FTL5xxxx-06-05-xx-en-001
66.5
50.5
L00-FTL5xxxx-06-05-xx-en-001
Welding neck
(with defined
thread start)
with silicone O-ring
Endress+Hauser
52001052
In conformity with
FDA*
max. 25 bar
max. 150 °C
max. 40 bar
max. 100 °C
See "Accessories"
G 1
DIN ISO 228/l
GR2
GR5
41 AF
69
50.5
max. 100 bar
max. 150 °C
With elastomer
flat seal to DIN 7603:
supplied
L00-FTL5xxxx-06-05-xx-en-002
G 1
DIN ISO 228/l
with defined
thread start
With seal surface
for flush-mounted
installation in
welding neck
GW2
41 AF
80
61.3
L00-FTL5xxxx-06-05-xx-en-003
Welding neck
(with defined
thread start)
with silicone O-ring
Endress+Hauser
52001051
In conformity with
FDA*
max. 25 bar
max. 150 °C
max. 40 bar
max. 100 °C
See "Accessories"
NPT ¾
ANSI B 1.20.1
GM2
GM5
32 AF
(66.5)
50.5
In conformity with
FDA*
max. 100 bar
max. 150 °C
or
R ¾
EN10226
NPT 1
ANSI B 1.20.1
GE2
GE5
GN2
GN5
41 AF
L00-FTL5xxxx-06-05-xx-en-004
(69)
50.5
In conformity with
FDA*
max. 100 bar
max. 150 °C
or
R 1
EN10226
Flanges
ANSI B 16.5
EN 1092-1
(DIN 2527 B)
JIS B2220
GF2
GF5
A##
B##
C##
F##
N##
L00-FTL5xxxx-06-05-xx-en-005
66.5
Seal
according to design
installed on site
In conformity with
FDA*
See nominal pressure
of flange, however
max. 100 bar
max. 150 °C
K##
L00-FTL5xxxx-06-05-xx-xx-008
* FDA approved materials according to 21 CFR Part 177.1550/2600
28Endress+Hauser
Page 29
Liquiphant M FTL50(H), FTL51(H)
Process connectionDimensionsAccessoriesPressure
Temperature
Tri-Clamp
1 ½" = ø50.5 mm
2" = ø64.0 mm
ISO 2852
Threaded pipe joint
DN 32
DN 40
DN 50
DIN 11851
TC2
TE2
MA2
MC2
ME2
66.5
L00-FTL5xxxx-06-05-xx-xx-009
66.5
Clamping ring and
front seal
installed on site
In conformity with
FDA*
Sealing ring with collar,
installed on site
In conformity with
FDA*
max. 16 bar
max. 120 °C
max. 2 bar
max. 150 °C
DN 32, DN 40:
max. 40 bar to 100 °C
max. 25 bar to 140 °C
DN 50:
max. 25 bar
with screw cap
Flush-mounted for 1"
welding neck
Factory standard
Endress+Hauser with
silicone seal
and screw cap:
supplied
EE2
L00-FTL5xxxx-06-05-xx-xx-010
55.5
L00-FTL5xxxx-06-05-xx-xx-011
Welding neck
(fork can be
positioned)
Endress+Hauser
52001047
In conformity with
FDA*
max. 140 °C
max. 40 bar
max. 100 °C
max. 25 bar
max. 150 °C
See "Accessories"
Aseptic
DN 50
DIN 11864-1
Form A
for pipe DIN 11850
HE2
66.5
Sealing ring,
installed on site
In conformity with
FDA*
max. 25 bar
max. 140 °C
with screw cap
DRD
With clamped flange
SMS
2"
(DN 51)
with screw cap
Varivent
for piping
≥ DN 65
≥ O.D. 3"
≥ I.P.S. 3"
PE2
UE2
WE2
ø68
L00-FTL5xxxx-06-05-xx-xx-012
66.5
L00-FTL5xxxx-06-05-xx-xx-013
66.5
L00-FTL5xxxx-06-05-xx-xx-014
56.5
Welding flange with
PTFE flat seal
(fork can be
positioned)
Endress+Hauser
52002041
In conformity with
FDA*
See "Accessories"
(or installed on site)
Sealing ring,
installed on site
In conformity with
FDA*
Clamping ring and
O-ring seal,
installed on site
In conformity with
FDA*
max. 40 bar
max. 100 °C
max. 25 bar
max. 150 °C
max. 25 bar
max. 140 °C
See specification as per
Tuchenhagen VARIVENTInline housing but:
max. 25 bar
max. 150 °C
L00-FTL5xxxx-06-05-xx-xx-015
* FDA approved materials according to 21 CFR Part 177.1550/2600
Endress+Hauser29
Page 30
Sensor length L for FTL51 and FTL51H,
depending on process connection
148...3000 mm (6...115 in); special version (TSP) on request up to 6000 mm (235 in)
Note!
The switchpoints of the Liquiphant M are at other positions to those of the previous version Liquiphant II.
Special length "L II":
With vertical mounting from above the same switchpoint as for the Liquiphant II
FTL360, FTL365, FDL30, FDL35
"L II" depends on process connection:
115 mm for flanges and flange-like process connections
99 mm for threads NPT and R (BSPT)
118 mm for threads G 1 (BSP 1)
115 mm for threads G ¾ (BSP ¾)
104 mm for flush-mounted 1" (Endress+Hauser)
WeightsSee "Product structure"
Material–Wetted parts:
Process connection and extension pipe: AISI 316L (1.4435) or 2.4610 (AlloyC4)
Tuning fork: AISI 316L (1.4435) or 2.4610 (AlloyC4)
– Flat seal for process connection G ¾ or G 1: elastomer fibre, asbestos-free
– Polyester housing: PBT-FR
with PBT-FR cover or with PA12 cover with sight glass,
Cover seal: EPDM
– Compact housing: valve connector or M12 connector
– Cable gland: polyamide or brass, nickel-plated
– Temperature spacer: AISI 316L (1.4435)
– Flameproof bushing: AISI 316L (1.4435)
30Endress+Hauser
Page 31
Liquiphant M FTL50(H), FTL51(H)
Process connections– Parallel thread G ¾, G 1 to DIN ISO 228/I with flat seal to DIN 7603
– Tapered thread R ¾, R 1 to EN10226
– Tapered thread ¾ -14 NPT, 1 - 11½ NPT to ANSI B 1.20.1
– Flush-mounted with welding neck to factory standard Endress+Hauser (G ¾, G 1)
– Flush-mounted with welding neck to factory standard Endress+Hauser (1"),
Sensor can be positioned
– Tri-Clamp 1½", 2" to ISO 2852
– Threaded pipe joint DN 32, 40, 50 to DIN 11851
– Aseptic connection DN 50 to DIN 11864-1 Form A for pipe DIN 11850
– SMS connection 2" (DN 51)
–DRD flange
– Varivent
®
DN 50 (50/40) to factory standard Tuchenhagen
– Flanges to EN/DIN from DN 25, for standards see "Product structure", to ANSI B 16.5 from 1",
to JIS B2220 (RF)
Human interface
Electronic inserts
With FEL51, FEL52, FEL54, FEL55:
• 2 switches for safety mode and density change,
• green LED to indicate operational status,
• red LED to indicate the switching status,
flashes in the event of corrosion damage
on sensoror if the electronics are defect
With FEL56:
• 2 switches for safety mode and density change,
• green LED flashes to indicate operational status,
• red LED to indicate the switching status,
flashes in the event of corrosion damage
on sensor or if the electronics are defect
With FEL57:
• 2 switches for density change and cyclical checking,
• green LED to indicate operational status,
• yellow LED to indicate the covered status,
flashes in the event of corrosion damage
on sensor or if the electronics are defect
With FEL58:
• 2 switches for safety mode and density change,
• green LED
– flashes quickly to indicate operational status,
– flashes slowly to indicate corrosion damage
at the sensor or if the electronics are defect,
• yellow LED to indicate the switching status,
Test key – breaks the cable connection
L1 N
12
Connecting terminalLEDsSwitches
FEL51
U~
19...253V AC
50/60Hz
Max1
2
Min
I max : 350mA
>0,7
>0,5
L00-FTL5xxxx-03-05-xx-en-001
L00-FTL5xxxx-03-05-xx-xx-013
With FEL50A:
• 8 switches for configuring the device address,
• green LED to indicate operational status,
pulsing to indicate communication;
PA– PA+
FEL50A
Address
ON
OFF
12345678
SW
HW
• yellow LED to indicate the switching status,
flashes in the event of corrosion damage on sensor
or if the electronics are defect
Connecting terminalLEDsSwitches
12
L00-FTL5xxxx-03-05-xx-en-002
Endress+Hauser31
Page 32
Compact housingsFunction test with test magnet
Versions AC, DC-PNP and NAMUR:
During the test, the current state of the electronic switch is reversed.
Performing the test
Hold the test magnet against the marking on the nameplate:
Liquiphant M FTL50(H), FTL51(H)
The switching status is changed.
Light signals
Versions AC and DC-PNP with valve connector or cable tail
gngn
AC/DCNAMUR
rd
L00-FTL5xxxx-19-05-xx-xx-001
ye
L00-FTL5xxxx-07-05-xx-xx-005
Green light (gn) light up (AC/DC):
Liquiphant M is connected to the power supply and is operational.
Green light (gn) flashing (NAMUR):
Liquiphant M is connected to the power supply and is operational.
Red light (rd) lights up (AC/DC):
MAX application mode (overfill protection): sensor is immersed in liquid.
MIN application mode (dry running protection): sensor is not immersed in liquid.
Yellow light (ye) lights up (NAMUR):
MAX application mode (overfill protection): sensor is not immersed in liquid.
MIN application mode (dry running protection): sensor is immersed in liquid.
Red light (rd) flashing (AC/DC):
Liquiphant M has detected a fault.
32Endress+Hauser
Page 33
Liquiphant M FTL50(H), FTL51(H)
rd
gn
ye
Version NAMUR and DC-PNP with M12x1 round connector 316L
ye
rd
gn
Green light (gn) lights up (DC-PNP):
Liquiphant M is connected to the power supply and is operational.
L00-FTL5xxxx-07-05-xx-xx-003
Green light (gn) flashing with 1 Hz (NAMUR):
Liquiphant M is connected to the power supply and is operational.
Yellow light (ye) lights up (DC-PNP):
Sensor is immersed in liquid.
Yellow light (ye) lights up (NAMUR):
MAX application mode (overfill protection): sensor is not immersed in liquid.
MIN application mode (dry running protection): sensor is immersed in liquid.
Red light (rd) flashing (DC-PNP):
Liquiphant M has detected a fault.
Green light (gn) flashing with 0.3 Hz (NAMUR):
Liquiphant M has detected a fault.
Endress+Hauser33
Page 34
Version DC-PNP with M12x1 round connector 316L
Liquiphant M FTL50(H), FTL51(H)
ye 1
ye 2
gn
Green light (gn) lights up:
Liquiphant M is connected to the power supply and is operational.
Yellow light (ye 1) lights up:
MAX application mode (overfill protection): sensor is not immersed in liquid.
MIN application mode (dry running protection): sensor is not immersed in liquid.
Yellow light (ye 2) lights up:
MAX application mode (overfill protection): sensor is immersed in liquid.
MIN application mode (dry running protection): sensor is immersed in liquid.
L00-FTL5xxxx-07-05-xx-xx-004
Green light (gn) lights up, both yellow lights (ye 1+2) do not light up:
Liquiphant M has detected a fault.
Operating conceptOnsite configuration
34Endress+Hauser
Page 35
Liquiphant M FTL50(H), FTL51(H)
+
Certificates and approvals
General approvalsFor Liquiphant M FTL50H, FTL51H the following approvals are available:
• EHEDG: Certification (from TNO, The Netherlands), Report No. V99.394
• 3A: 3A Certificate (USA), Authorization No. 459
!
#
Process connectionsOrder Code
+
L00-FTL5xxxx-01-05-xx-xx-001
Flush-mounted G ¾, G1 (with welding neck)GQ2, GW2X
Tri-Clamp 2" (special seal from Hyjoin Limited, UK)TE2X
Threaded pipe jointMA2, MC2, ME2X
Flush-mounted (fork can be positioned)EE2X
AsepticHE2X
DRDPE2X
SMSUE2X
®
Varivent
Note!
For CIP (Clean in Place) and SIP (Sterilize in Place) processes the pressure and temperture specifications of the
process connections must be observed.
Warning!
To avoid risk of contamination, install according to the "Hygienic Equipment Design Criteria (HDC)" as stated
in the Subgroup Design Principles of the EHEDG, Doc. 8, July 1993. The flow of liquid during cleaning is
important and should be in compliance with HDC.
WE2X
Other certificatesSee "Ordering information"
Combination
of housings and
electronic inserts
Based on the various certificates, permissible combinations of housings *) and electronic inserts are given in
the following table.
*) Abbreviations: Polyester = PBT, Steel 316L = St., Aluminium = Alu
Aluminium housing with separate connection compartment = Alu/sep
G ATEX II 1/2 G, EEx ia IIC T6PBT, St., Alu, Alu/sep.FEL55/56/57/58/50A
ATEX II 1/2 G, EEx ia IIC T6
ATEX II 1/2 D, T80°C
H ATEX II 1G, EEx ia IIC T6FEL55/56/57/58/50A
JATEX II 1G, EEx ia IIC T6, WHGFEL55/56/57/58/50A
IATEX II 1/2 G, EEx deAlu/sep.FEL51/52/54,
KATEX II 1/2 G, EEx d IIC T6AluFEL51/52/54,
LATEX II 1/2 G, EEx d IIC T6, WHGAluFEL51/52/54,
PFM, IS, Cl. I, II, III, Div. 1, Gr. A-GPBT, St., Alu, Alu/sep.
Q FM, XP, Cl. I, II, III, Div. 1, Gr. A-GAlu
RFM, NI, Cl. I, Div. 2, Gr. A-DSt., Alu, Alu/sep.
U CSA, General PurposeSt., Alu, Alu/sep.
SCSA, IS, Cl. I, II, III, Div. 1, Gr. A-GPBT, St., Alu, Alu/sep.
TCSA, XP, Cl. I, II, III, Div. 1, Gr. A-GAlu
VTIIS Ex ia IIC T3PBT, St., AluFEL57
WTIIS Ex d IIB T3AluFEL52/54
YOther certificate
(for non-hazardous area)
St., Alu, Alu/sep.FEL55/56/57/58/50A
FEL55/56/57/58/50A
FEL55/56/57/58/50A
FEL55/56/57/58/50A
FEL55/56/57/58
with NPT cable entry
with NPT cable entry
with NPT cable entry
PBT
with NPT cable entry
with NPT cable entry
PBT
with NPT cable entry
with NPT cable entry
with NPT cable entry
PBT, St., Alu, Alu/sep.FEL51/52/54,
FEL51/52/54,
FEL55/56/57/58
FEL51/52/54,
FEL55/56/57/58
FEL55/56/57/58
FEL51/52/54,
FEL55/56/57/58
FEL51/52,
FEL55/56/57/58
FEL55/56/57/58
FEL51/52/54,
FEL55/56/57/58
FEL55/56/57/58/50A
!
Note!
on polyester housing (PBT), electric connecting cables run in pipes:
Do not screw cable entries firmly to the piping. Use flexible connections (e.g. with armoured hose).
If the piping is used for earthing then ensure that there is a continuous electrical connection.
!
Note!
Despite the additional Dust-Ex-certificate, the FTL5x(H) is to be used as a liquid limit switch only.
36Endress+Hauser
Page 37
Liquiphant M FTL50(H), FTL51(H)
!
Ordering information
Note!
This overview does not mark options wich are mutually exclusive.
Product structure
Liquiphant M
FTL50
FTL51
DesignBasic weight
FTL50Compact0.6 kg
FTL51With extension pipe0.6 kg
10Approval:
A Non-hazardous area
B ATEX II 3 GEEx nC II T6Overfill protection to WHG (Germany)
ATEX II 3 DT 85 °C*
C ATEX II 3 GEEx nA II T6Overfill protection to WHG (Germany)
ATEX II 3 DT 85 °C*
D Non-hazardous area Overfill protection to WHG (Germany)
E ATEX II 1/2 GEEx de IIC T6Overfill protection to WHG (Germany)
F ATEX II 1/2 G EEx ia IIC T6Overfill protection to WHG (Germany)
ATEX II 1/2 D T 80 °C*
G ATEX II 1/2 GEEx ia IIC T6
ATEX II 1/2 D T 80 °C*
H ATEX II 1 GEEx ia IIC T6
I ATEX II 1/2 G EEx de IIC T6
J ATEX II 1 GEEx ia IIC T6Overfill protection to WHG (Germany)
K ATEX II 1/2 G EEx d IIC T6
L ATEX II 1/2 G EEx d IIC T6Overfill protection to WHG (Germany)
P FMIS, Class I, II, IIIDivision 1, Group A-G
Q FMXP, Class I, II, IIIDivision 1, Group B-G, for E5 housing Group A-G
R FMNI, Class IDivision 2, Group A-D
S CSAIS, Class I, II, IIIDivision 1, Group A-G
T CSAXP, Class I, II, IIIDivision 1, Group A-G
U CSAGeneral Purpose
VTIISEx ia IIC T3
W TIISEx d IIB T3
XTIISEx ia IIC T6
7 TIISEx d IIC T3
8 TIISEx d IIC T6
Y Special version
*) not valid for PBT
20Process Connection: Additional weight
Note!
For 100 bar process pressure, please select the appropriate option under "Additional option"
GQ2 G ¾316LThread ISO 228
Installation > accessory: welding neck
GQ5 G ¾ AlloyC4Thread ISO 228
GR2G 1 316LThread ISO 2280.2 kg
GR5G 1 AlloyC4Thread ISO 2280.2 kg
GW2 G 1 316LThread ISO 2280.2 kg
Installation > accessory: welding neck
GM2 NPT ¾316LThread ANSI
GM5 NPT ¾AlloyC4Thread ANSI
GN2 NPT 1316LThread ANSI0.2 kg
GN5 NPT 1AlloyC4Thread ANSI0.2 kg
GE2R ¾316LThread EN10226
GE5R ¾AlloyC4Thread EN10226
GF2R 1316LThread EN102260.2 kg
GF5R 1AlloyC4Thread EN102260.2 kg
BA2DN32PN6 A316LFlange EN 1092-1
BB2DN32PN25/40 A316LFlange EN 1092-1
BC2DN40PN6 A316LFlange EN 1092-1
BD2DN40PN25/40 A316LFlange EN 1092-1
BE2DN50PN6 A316LFlange EN 1092-1
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
1.2 kg
2.0 kg
1.4 kg
2.4 kg
1.6 kg
Endress+Hauser37
Page 38
Liquiphant M FTL50(H), FTL51(H)
20Process Connection: Additional weight
BG2DN50PN25/40 A316LFlange EN 1092-1
BH2DN65PN6 A316LFlange EN 1092-1
BJ2DN50PN100 A316L (FTL51)Flange EN 1092-1
BK2DN65PN25/40 A316LFlange EN 1092-1
BM2 DN80PN10/16 A316LFlange EN 1092-1
BN2DN80PN25/40 A316LFlange EN 1092-1
BQ2DN100 PN10/16 A316LFlange EN 1092-1
BR2DN100 PN25/40 A316LFlange EN 1092-1
B12DN80PN100 A316L (FTL51)Flange EN 1092-1
B82DN25PN25/40 A316LFlange EN 1092-1
CA2DN32PN6 B1316LFlange EN 1092-1
CA5DN32PN6AlloyC4 >316LFlange EN 1092-1
CE2DN50PN6 B1316LFlange EN 1092-1
CE5DN50PN6AlloyC4 >316LFlange EN 1092-1
CG2 DN50PN25/40 B1316LFlange EN 1092-1
CG5 DN50PN25/40AlloyC4 >316LFlange EN 1092-1
CJ2DN50PN100 B2316L (FTL51)Flange EN 1092-1
CN2 DN80PN25/40 B1316LFlange EN 1092-1
CN5 DN80PN25/40AlloyC4 >316LFlange EN 1092-1
CQ2 DN100 PN10/16 B1316LFlange EN 1092-1
CQ5 DN100 PN10/16AlloyC4 >316LFlange EN 1092-1
C12DN80PN100 B2316L (FTL51)Flange EN 1092-1
C82DN25PN25/40 B1316LFlange EN 1092-1
C85DN25PN25/40AlloyC4 >316LFlange EN 1092-1
DG2 DN50PN40 B1316LFlange EN 1092-1
DN2 DN80PN40 B1316LFlange EN 1092-1
D82DN25PN40 B1316LFlange EN 1092-1
FG2DN50PN40 C316LFlange EN 1092-1
NG2 DN50PN40 D316LFlange EN 1092-1
AA21¼"150 lbsRF 316/316L Flange ANSI B16.51.2 kg
AB21¼"300 lbsRF 316/316L (FTL51)Flange ANSI B16.52.0 kg
AC2 1½"150 lbsRF 316/316LFlange ANSI B16.51.5 kg
AD2 1½"300 lbsRF 316/316L (FTL51)Flange ANSI B16.52.7 kg
AE22"150 lbsRF 316/316L Flange ANSI B16.52.4 kg
AE52"150 lbsRF AlloyC4 >316/316LFlange ANSI B16.52.4 kg
AF22"300 lbsRF 316/316LFlange ANSI B16.53.2 kg
AG2 2"600 lbsRF 316/316L (FTL51)Flange ANSI B16.54.2 kg
AJ22½"300 lbsRF 316/316L (FTL51)Flange ANSI B16.54.8 kg
AL23"150 lbsRF 316/316LFlange ANSI B16.54.9 kg
AM2 3"300 lbsRF 316/316L (FTL51)Flange ANSI B16.56.8 kg
AN2 3"600 lbsRF 316/316L (FTL51)Flange ANSI B16.5
AP24"150 lbsRF 316/316LFlange ANSI B16.57.0 kg
AQ2 4"300 lbsRF 316/316L (FTL51)Flange ANSI B16.511.5 kg
AR24"600 lbsRF 316/316L (FTL51)Flange ANSI B16.517.3 kg
A821"150 lbsRF 316/316LFlange ANSI B16.51.0 kg
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 B)
(DIN 2527 C)
(DIN 2527)
(DIN 2527 C)
(DIN 2527)
(DIN 2527 C)
(DIN 2527)
(DIN 2527)
(DIN 2527 C)
(DIN 2527)
(DIN 2527 C)
(DIN 2527)
(DIN 2527)
(DIN 2527 C)
(DIN 2527)
(DIN 2526 D)
(DIN 2526 D)
(DIN 2526 D)
(DIN 2512 F)
(DIN2512 N)
3.2 kg
2.4 kg
4.3 kg
4.8 kg
5.9 kg
5.6 kg
7.5 kg
1.4 kg
1.1 kg
1.1 kg
1.5 kg
1.5 kg
2.9 kg
2.9 kg
5.2 kg
5.2 kg
5.3 kg
5.3 kg
1.3 kg
1.3 kg
2.6 kg
2.9 kg
38Endress+Hauser
Page 39
Liquiphant M FTL50(H), FTL51(H)
20Process Connection: Additional weight
KA210 K 25RF 316LFlange JIS B2220
KC2 10 K 40 RF 316LFlange JIS B2220
KE210 K 50 RF 316LFlange JIS B22201.7 kg
KE510 K 50 RF AlloyC4 >316LFlange JIS B22201.7 kg
KL210 K 80 RF 316LFlange JIS B2220
KP210 K 100 RF 316LFlange JIS B2220
TC2DN25-38 (1...1½")316LISO 2852 Tri-Clamp
TE2DN40-51 (2")316LISO 2852 Tri-Clamp0.1 kg
YY9Special version
30Probe Length; Type:
FTL50
AACompact;Ra <3.2 μm/80 grit
IACompact; temperature spacer0.6 kg
QA Compact; pressure tight feed through0.7 kg
FTL51
BB....... mm;316L**Ra <3.2 μm/80 grit
BE....... mm;AlloyC4**Ra <3.2 μm/80 grit
CB....... inch;316L**Ra <3.2 μm/80 grit
CE....... inch;AlloyC4**Ra <3.2 μm/80 grit2.3 kg/100 in
DBLength: type II*; 316LRa <3.2 μm/80 grit0.1 kg
DELength: type II*; AlloyC4Ra <3.2 μm/80 grit0.1 kg
JB....... mm;316L**+ temperature spacer0.9 kg/m
JE....... mm;AlloyC4**+ temperature spacer0.9 kg/m
KB....... inch;316L**+ temperature spacer2.3 kg/100 in
KE....... inch;AlloyC4** + temperature spacer2.3 kg/100 in
LBLength: type II*; 316L+ temperature spacer0.1 kg
LELength: type II*; AlloyC4+ temperature spacer0.1 kg
Technical InformationNivotester FTL370/372, switching units in Racksyst design
for Liquiphant M with electronic insert FEL57
TI198F/00/en
Nivotester FTL320, switching unit in Minipac design
for Liquiphant M with electronic insert FEL57
TI203F/00/en
General instructions for electromagnetic compatibility
(Test procedure, installation recommendation)
TI241F/00/en
Isolating amplifier FXN421/422, switching units for top-hat rail mounting
for Liquiphant M with electronic insert FEL56, FEL58
TI332F/00/en
Liquiphant M FTL51C, wetted parts with highly corrosion-resistant coating
made of ECTFE, PFA or enamel
TI347F/00/en
Isolating amplifier FTL325P, 1 or 3-channel switching units for top-hat rail mounting
for Liquiphant M/S with electronic insert FEL57
TI350F/00/en
Isolating amplifier FTL325N, 1 or 3-channel switching units for top-hat rail mounting
for Liquiphant M/S with electronic insert FEL56, FEL58
TI353F/00/en
Liquiphant S FTL70/71, for medium temperatures up to 280 °C
TI354F/00/en
Isolating amplifier FTL375P, 1 to 3-channel switching units for top-hat rail mounting
for Liquiphant M/S with electronic insert FEL57
TI360F/00/en
Isolating amplifier FTL375N, 1 to 3-channel switching units for top-hat rail mounting
for Liquiphant M/S with electronic insert FEL56, FEL58
TI361F/00/en
Endress+Hauser49
Page 50
Functional Safety (SIL)Liquiphant M/S + Nivotester FTL325P
SD111F/00/en
Liquiphant M/S + Nivotester FTL375P
SD113F/00/en
Liquiphant M/S with FEL58 + Nivotester FTL325N (MAX)
SD161F/00/en
Liquiphant M/S with electronic insert FEL54 (MAX)
SD162F/00/en
Liquiphant M/S with electronic insert FEL52 (MAX)
SD163F/00/en
Liquiphant M/S with electronic insert FEL51 (MAX)
SD164F/00/en
Liquiphant M/S with electronic insert FEL55 (MAX)
SD167F/00/en
Liquiphant M/S with FEL56 + Nivotester FTL325N (MAX)
SD168F/00/en
Liquiphant M/S with FEL58 + Nivotester FTL325N (MIN)
SD170F/00/en
Liquiphant M/S with electronic insert FEL51 (MIN)
SD185F/00/en
Liquiphant M/S with electronic insert FEL52 (MIN)
SD186F/00/en
Liquiphant M/S with electronic insert FEL54 (MIN)
SD187F/00/en
Liquiphant M/S with FEL56 + Nivotester FTL325N (MIN)
SD188F/00/en