Endress+Hauser Cerabar S, Deltabar S Operating Instructions Manual

Operating Instructions – Description of device functions
Cerabar S/Deltabar S
Pressure and Differential pressure transmitters
BA303P/00/en/04.05 52027503 valid from Software version 02.00 Hardware version 01.00
Overview documentation Cerabar S/Deltabar S

Overview documentation

Device Documentation Content Note
Cerabar S FOUNDATION Fieldbus Technical Information TI383P Technical data – The documentation is located on the
ToF Tool CD. The CD is enclosed with every device ordered with the "HistoROM/M-DAT" option.
– The documentation is also available
via the Internet. → See: www.endress.com
Operating Instructions BA302P – Identification
– Installation – Wiring – Operation – Commissioning, Description of
Quick Setup menus – Maintenance – Trouble-shooting and spare parts – Appendix: Illustration of menu
Operating Instructions BA303P – Examples of configuration for
pressure, level and flow
measurement – Description of parameters – Trouble-shooting – Appendix: Illustration of menu
Brief Operating Instructions KA252P – Wiring
– Description of operating elements – Operation HistoROM
Deltabar S FOUNDATION Fieldbus Technical Information TI382P Technical data – The documentation is located on the
Operating Instructions BA301P – Identification
– Installation – Wiring – Operation – Commissioning, Description of
Quick Setup menus – Maintenance – Trouble-shooting and spare parts – Appendix: Illustration of menu
Operating Instructions BA303P – Examples of configuration for
pressure, level and flow
measurement – Description of parameters – ’Trouble-shooting – Appendix: Illustration of menu
Brief Operating Instructions KA252P – Wiring
– Description of operating elements – Operation HistoROM
®
/M-DAT
®
/M-DAT
– The documentation is supplied with
the device.
– The documentation is also available
via the Internet. → See: www.endress.com
– The documentation is also available
via the Internet. → See: www.endress.com
– The documentation is supplied with
the device. See cover of the terminal compartment.
ToF Tool CD. The CD is enclosed with every device ordered with the "HistoROM/M-DAT" option.
– The documentation is also available
via the Internet. → See: www.endress.com
– The documentation is supplied with
the device.
– The documentation is also available
via the Internet. → See: www.endress.com
– The documentation is also available
via the Internet. → See: www.endress.com
– The documentation is supplied with
the device. See cover of the terminal compartment.
2 Endress+Hauser
Cerabar S/Deltabar S Table of contents

Table of contents

1 Notes on use . . . . . . . . . . . . . . . . . . . . 4
1.1 Finding function group using graphic representation
(ToF Tool) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Finding parameter description using parameter names
(index) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Graphic representation of function
groups (ToF Tool). . . . . . . . . . . . . . . . . 5
3 Pressure measurement
(FF configuration program). . . . . . . . . . 6
4 Level measurement
(FF configuration program). . . . . . . . . . 7
4. 1 Overview of level measurement . . . . . . . . . . . . . . 7
4. 2 "Linear" level type . . . . . . . . . . . . . . . . . . . . . . . . . 8
4. 3 "Pressure linearized" level type . . . . . . . . . . . . . . 10
4. 4 "Height linearized" level type . . . . . . . . . . . . . . . 14
5 Flow measurement
(FF configuration program). . . . . . . . . 17
10 Description of parameters
(ToF Tool) . . . . . . . . . . . . . . . . . . . . . . 92
11 Trouble-shooting . . . . . . . . . . . . . . . . 151
11.1 Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
11.2 Response of outputs to errors . . . . . . . . . . . . . . . . 159
11.3 Confirming messages . . . . . . . . . . . . . . . . . . . . . . 160
12 Appendix . . . . . . . . . . . . . . . . . . . . . . 161
12.1 Operating menu (ToF Tool) . . . . . . . . . . . . . . . . . 161
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
5. 1 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5. 2 Totalizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6 Description of parameters
(FF configuration program). . . . . . . . . 21
6.1 Deltabar S and Cerabar S block model . . . . . . . . . . 21
6.2 Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.3 Transducer Blocks . . . . . . . . . . . . . . . . . . . . . . . . . 31
6. 4 Analog Input Block (function block) . . . . . . . . . . . . 65
7 Pressure measurement (ToF Tool) . . . 74
8 Level measurement (ToF Tool) . . . . . 75
8.1 Overview of level measurement . . . . . . . . . . . . . . 75
8.2 "Linear" level type . . . . . . . . . . . . . . . . . . . . . . . . 76
8.3 "Pressure linearized" level type . . . . . . . . . . . . . . 80
8.4 "Height linearized" level type . . . . . . . . . . . . . . . . 84
9 Flow measurement (ToF Tool) . . . . . . 89
9.1 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.2 Totalizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Endress+Hauser 3
Notes on use Cerabar S/Deltabar S

1 Notes on use

Sections 3 to 6 describe operation by means of an FF configuration program. In FOUNDATION Fieldbus, all the device parameters are categorised depending on their functional properties and tasks and assigned to the Resource Block, the Transducer Blocks and the function blocks. The parameters of the Resource Block, the Transducer Blocks and the Analog Input Block are described in Section 6. For a parameter description of other function blocks, such as the PID or Discrete Output Block, see Operating Instructions BA013S "FOUNDATION Fieldbus Overview" or the FOUNDATION Fieldbus Specification. Sections 3 to 5 describe typical configuration examples.
Sections 7 to 10 describe operation by means of the Endress+Hauser ToF Tool operating program. Section 10 describes all the parameters in the order as they appear in the menu. Sections 7 to 9 describe typical configuration examples.
Sections 1.1 and 1.2 tell you how you can find a certain parameter description more easily.

1.1 Finding function group using graphic representation (ToF Tool)

All the function groups are shown in table form in Section 2. The page reference/link takes you to the function group in question. In Section 10, all the parameters of a function group are compiled in a table.

1.2 Finding parameter description using parameter names (index)

The index lists all the parameters in alphabetical order. The page reference/link takes you to the parameter in question.
4 Endress+Hauser

Cerabar S/Deltabar S Graphic representation of function groups (ToF Tool)

2 Graphic representation of function groups
(ToF Tool)
!
Note! The "Flow" measuring mode is only available for the Deltabar S differential pressure transmitter. The groups marked with "*" are only displayed for Deltabar S.
1st selection level 2nd selection level (groups) Function groups Description,
see Page
QUICK SETUP Pressure → 92 QUICK SETUP Level → 94 QUICK SETUP Flow * → 96 OPERATING MENU → SETTINGS POSITION ADJUSTMENT → 98
BASIC SETUP Pressure 99BASIC SETUP Level 101BASIC SETUP Flow * 125EXTENDED SETUP Pressure 129EXTENDED SETUP Level 129EEXTENDED SETUP Flow * 130LINEARISATION 132TOTALIZER SETUP * 134DISPLAY 136
TRANSMITTER INFO INFO 138
TRANSMITTER DATA 138PROCESS CONNECTION 139SENSOR DATA 140
PROCESSINFO PROCESS VALUES pressure 142
PROCESS VALUES level 143PROCESS VALUES flow * 144
PEAK HOLD INDICATOR 144OPERATING 146DIAGNOSTICS SIMULATION
MESSAGES 149
USER LIMITS 150
148
Endress+Hauser 5

Pressure measurement (FF configuration program) Cerabar S/Deltabar S

3 Pressure measurement
(FF configuration program)
!
Note!
• The device is configured for the Pressure measuring mode as standard. The measuring range and the unit in which the measured value is transmitted, as well as the digital output value of the Analog Input Block OUT, correspond to the data on the nameplate.
• See also Operating Instructions BA301P Deltabar S, Section 6.7 "Differential pressure measurement" or Operating Instructions BA302P Cerabar S, Section 6.5 "Pressure measurement".
• For a description of the parameters mentioned, see – Page 33, Pressure Transducer Block – Page 65, Analog Input Block.
Description
1 Deltabar S: before configuring the device for your
application, the pressure piping must be cleaned and the device filled with fluid. See Operating Instructions BA301P, Section 6.7.
2 Open the Pressure Transducer Block and set the block
mode to OOS.
3 Carry out position adjustment if necessary.
You have the following ways of carrying out position adjustment:
• By means of the "Pos. zero adjust" method, see Operating Instructions BA301P or BA302P, Section 6.4.
• By means of the parameters – PRESSURE_1_ACCEPT_ZERO_INSTALL_
OFFSET/POS. ZERO ADJUST (Page 38) or
– PRESSURE_1_ACCEPT_INSTALL_OFFSET/
POS. INPUT VALUE (Page 38) or
– PRESSURE_1_INSTALL_OFFSET/CALIB. OFFSET
(Page 38).
4 Select the measuring mode if necessary:
• Select the "No linearization" option by means of the LINEARIZATION parameter.
• Select the "Differential pressure", Gauge pressure" or "Absolute pressure" option, depending on the sensor, by means of the PRIMARY_VALUE_TYPE parameter.
5 Set the Pressure Transducer Block to the "Auto" block
mode.
6 If necessary, use the Analog Input Block to configure the
CHANNEL parameter ( Page 67), L_TYPE parameter ( Page 69), XD_SCALE parameter ( Page 73) and OUT_SCALE parameter ( Page 71).
7Result:
The measuring device is ready for pressure measurement.
+
P01-PMD75xxx-19-xx-xx-xx-000
!
Note!
• You can select another pressure unit by means of the CAL_UNIT parameter (Page 34). This
parameter also allows you to specify a customer-specific unit.
6 Endress+Hauser

Cerabar S/Deltabar S Level measurement (FF configuration program)

4 Level measurement
(FF configuration program)

4. 1 Overview of level measurement

Measuring task Measured variable
selection
The measured variable is in direct proportion to the measured pressure.
The measured variable is not in direct proportion to the measured pressure as, for example, with containers with a conical outlet. A linearisation table must be entered for the calibration.
– Two measured variables are
required or
– The container shape is given
by value pairs, such as height and volume.
The 1st measured variable %­height or height must be in direct proportion to the measured pressure. The 2nd measured variable volume, mass or % must not be in direct proportion to the measured pressure. A linearisation table must be entered for the 2nd measured variable. The 2nd measured variable is assigned to the 1st measured variable by means of this table.
– % (level) – Level –Volume –Mass
– Pressure and % – Pressure and volume – Pressure and mass
– Height and volume – Height and mass – Height and % –%-height and volume –%-height and mass –%-height and %
LEVEL_TYPE/ LEVEL MODE
Linear Calibration without reference
Pressure linearized – Calibration with reference
Height linearized – Calibration without reference
Description Measured value display
pressure – dry calibration, see Page 8, Section 4.2.1
pressure: semiautomatic entry of linearisation table, see Page 10, Section 4.3.1
– Calibration without reference
pressure: manual entry of linearisation table, see Page 12, Section 4.3.2
pressure: dry calibration and manual entry of linearisation table, see Page 14, Section
4.4.1
The measured value display and the PRIMARY_VALUE and MEASURED_LEVEL_AFTER_ SIMULATION/LEVEL BEFORE LIN. parameters show the measured value.
The measured value display and the PRIMARY_VALUE parameter display the measured value.
The measured value display and the PRIMARY_VALUE parameter display the 2nd measured value (volume, mass or %). The MEASURED_LEVEL_ AFTER_SIMULATION/LEVEL BEFORE LIN parameter displays the 1st measured value (% height or height).
Endress+Hauser 7
Level measurement (FF configuration program) Cerabar S/Deltabar S

4. 2 "Linear" level type

4.2.1 Calibration without reference pressure – dry calibration

!
Example:
In this example, the volume in a tank should be measured in m and the maximum height is 4 m. The density of the fluid is 1 kg/dm
3
. The maximum volume is 5 m3
3
. The device is mounted below
the level lower range value.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• This is a theoretical calibration, i.e. the tank volume, tank height and density of the fluid are known.
Note!
• See also Operating Instructions BA301P Deltabar S or Operating Instructions BA302P Cerabar S, Section 6.6 "Level measurement".
• For a description of the parameters mentioned, see – Page 33, Pressure Transducer Block – Page 65, Analog Input Block.
Description
1 Deltabar S: before configuring the device for your
application, the pressure piping must be cleaned and the device filled with fluid. See Operating Instructions BA301P, Section 6.6.1.
2 Open the Pressure Transducer Block and set the block
mode to OOS.
3 You have the following ways of carrying out position
adjustment:
• By means of the "Pos. zero adjust" method, see Operating Instructions BA301P or BA302P, Section
6.4.
• By means of the parameters – PRESSURE_1_ACCEPT_ZERO_INSTALL_
OFFSET/POS. ZERO ADJUST (Page 38) or
– PRESSURE_1_ACCEPT_INSTALL_OFFSET/
POS. INPUT VALUE (Page 38) or
– PRESSURE_1_INSTALL_OFFSET/CALIB. OFFSET
(Page 38).
4 Select the measuring mode if necessary:
• Select the "No linearization" option by means of the LINEARIZATION parameter.
• Select the "Volume" option by means of the PRIMARY_VALUE_TYPE parameter.
5 Select a pressure unit via the CAL_UNIT parameter, here
mbar for example.
6 Select the "Linear" option by means of the
LEVEL_TYPE/LEVEL MODE parameter.
7 Select the "Volume" option by means of the
MEASURAND_LINEAR/LIN. MEASURAND parameter.
8 Select a volume unit via the VOLUME_UNIT/UNIT
VOLUME parameter, here m
9 Select the "Dry" option by means of the
LEVEL_ADJUST_MODE/CALIBRATION MODE parameter. See also the following note, point 3.
10 Enter the value for density via the
LEVEL_ADJUST_DENSITY/ADJUST DENSITY and DENSITY_UNIT parameters, here 1 kg/dm example.
11 Enter the tank volume via the
LEVEL_TANK_VOLUME/TANK VOLUME parameter,
3
here 5 m
for example.
3
for example.
3
for
3
V = 5 m
kg
ρ = 1
3
dm
P01-PMP75xxx-19-xx-xx-xx-003
Fig. 1: Calibration without reference pressure –
dry calibration
1 See Table, Step 10. 2 See Table, Step 11. 3 See Table, Step 12. 4 See Table, Step 13.
4 m
–0.5 m
8 Endress+Hauser
Cerabar S/Deltabar S Level measurement (FF configuration program)
Description
12 Enter the tank height via the LEVEL_TANK_HEIGHT/
TANK HEIGHT parameter, here 4 m for example.
13 Enter the level offset via the LEVEL_OFFSET/ZERO
POSITION parameter, here 0.5 m for example.
14 Set the Pressure Transducer Block to the "Auto" block
mode.
15 If necessary, use the Analog Input Block to configure the
CHANNEL parameter ( Page 67), L_TYPE parameter ( Page 69), XD_SCALE parameter ( Page 73) and OUT_SCALE parameter ( Page 71).
16 Result:
The measuring device is ready for level measurement.
!
Note!
1. For this level type, the measured variables %, level, volume and mass are available. → See
Page 40 ff.
2. You can also specify customer-specific units. See parameter descriptions for CAL_UNIT
(Page 34), HEIGHT_UNIT (Page 41), VOLUME_UNIT (Page 42) and MASS_UNIT (Page 43).
3. The "Wet" calibration mode (LEVEL_ADJUST_MODE) is not available by means of the FF operating programs. A kind of wet calibration can be carried out as follows: – Select the "No linearization" option by means of the LINEARIZATION parameter. – Select the "Level", "Volume" or "Mass" option, depending on the measured variable required,
by means of the PRIMARY_VALUE_TYPE parameter. – Fill the tank up to the lower level point. – The PRESSURE_1_AFTER_SENSOR/SENSOR PRESSURE parameter displays the pressure
present at the device. Enter the value displayed for the SCALE_IN parameter, EU_0
element. – Enter the associated level value for the SCALE_OUT parameter, EU_0 element. – Using the SCALE_OUT parameter, "Units Index" element, select a unit to suit the measured
variable. – Fill the tank up to the upper level point. – The PRESSURE_1_AFTER_SENSOR/SENSOR PRESSURE parameter displays the pressure
present at the device. Enter the value displayed for the SCALE_IN parameter, EU_100
element. – Enter the associated level value for the SCALE_OUT parameter, EU_100 element.
Endress+Hauser 9
Level measurement (FF configuration program) Cerabar S/Deltabar S

4. 3 "Pressure linearized" level type

4.3.1 Semiautomatic entry of the linearisation table

!
Example:
In this example, the volume in a tank with a conical outlet should be measured in m
3
.
Prerequisite:
• The tank can be filled. The linearisation characteristic must rise continuously.
Note!
• See also Operating Instructions BA301P Deltabar S or Operating Instructions BA302P Cerabar S, Section 6.6 "Level measurement".
• For a description of the parameters mentioned, see – Page 33, Pressure Transducer Block. – Page 65, Analog Input Block.
Description
1 Deltabar S: before configuring the device for your
application, the pressure piping must be cleaned and the device filled with fluid. See Operating Instructions BA301P, Section 6.6.1.
2 Open the Pressure Transducer Block and set the block
mode to OOS.
3 You have the following ways of carrying out position
adjustment:
• By means of the "Pos. zero adjust" method, see Operating Instructions BA301P or BA302P, Section 6.4.
• By means of the parameters – PRESSURE_1_ACCEPT_ZERO_INSTALL_
OFFSET/POS. ZERO ADJUST (Page 38) or
– PRESSURE_1_ACCEPT_INSTALL_OFFSET/
POS. INPUT VALUE (Page 38) or
– PRESSURE_1_INSTALL_OFFSET/CALIB. OFFSET
(Page 38).
Carry out basic setup:
4 Select the measuring mode if necessary:
• Select the "Level linearized" option by means of the LINEARIZATION parameter.
• Select the "Volume" option by means of the PRIMARY_VALUE_TYPE parameter. See also the following note, point 3.
5 Select a pressure unit via the CAL_UNIT parameter, here
mbar for example.
6 Select the "Pressure linearized" option by means of the
LEVEL_TYPE/LEVEL MODE parameter.
7 Select the "Pressure and volume" option by means of the
MEASURAND_LINEAR/Lind. MEASURAND parameter.
8 Select a volume unit via the VOLUME_UNIT/UNIT
VOLUME parameter, here m
9Select SCALE_IN parameter, EU_0 element.
Enter the minimum hydrostatic pressure to be expected, here 0 mbar for example.
10 Select SCALE_IN parameter, EU_100
Enter the maximum hydrostatic pressure to be expected, here 350 mbar for example.
3
for example.
element.
V
3
[m ]
3.5
0
0 350
P01-PMP75xxx-19-xx-xx-xx-002
p
[mbar]
10 Endress+Hauser
Cerabar S/Deltabar S Level measurement (FF configuration program)
Description
Carry out linearisation:
11 Select SCALE_OUT parameter, EU_0 element.
Specify the minimum tank contents to be expected, here
3
0 m
for example.
12 Select SCALE_OUT parameter, EU_100 element.
Specify the maximum tank contents to be expected, here
3
3.5 m
for example. See also the following note, point 4.
13 Select the "Semiautomatic" option by means of the
LINEARIZATION_TABLE_MODE/LIN. EDIT MODE parameter.
14 Select the "Edit table" option by means of the
TAB_OBCODE/TABLE SELECTION parameter.
15 Enter linearisation table (min. 2 points, max. 32 points).
Fill the tank to the height of the 1st point.
TAB_ENTRY: enter the value of the corresponding point.
The PRESSURE_1_AFTER_DAMPING/PRESSURE parameter displays the measured hydrostatic pressure. This hydrostatic pressure displayed is saved by confirming the Y-value. See the following line.
TAB_XY_VALUE, 2nd element (Y-value): enter the volume value, here 0 m value.
16 You can enter further points for the linearisation table as
explained in Step 15. The previous point first has to be saved in the linearisation table before the next point can be entered. In other words, a complete linearisation table cannot be saved to the device. Once all the points have been entered, the table must be activated by means of the TAB_OBCODE/TABLE SELECTION parameter.
17 Set the Pressure Transducer Block to the "Auto" block
mode.
18 If necessary, use the Analog Input Block to configure the
CHANNEL parameter ( Page 67), L_TYPE parameter ( Page 69), XD_SCALE parameter ( Page 73) and OUT_SCALE parameter ( Page 71).
19 Result:
The linearisation table is entered and the measuring device is ready for level measurement.
3
for example, and confirm the
V
3
[m ]
3.5
0
0 350
Fig. 2: Semiautomatic entry of the linearisation
table
1 See Table, Step 9. 2 See Table, Step 10. 3 See Table, Step 11. 4 See Table, Step 12. 5 See Table, Steps 13 to 16.
p
[mbar]
P01-xxxxxxxx-05-xx-xx-xx-015
!
Note!
1. For this level type, the measured variables %, volume and mass are available. See Page 40 ff.
2. You can also specify customer-specific units. See parameter descriptions for CAL_UNIT
(Page 34), HEIGHT_UNIT (Page 41), VOLUME_UNIT (Page 42) and MASS_UNIT (Page 43).
Endress+Hauser 11
Level measurement (FF configuration program) Cerabar S/Deltabar S
3. Once you have selected the "Pressure linearized" level type (LEVEL_TYPE), the warning message "W710 Set span too small. Not allowed." can appear. At this stage the linearisation table already consists of two points as standard. It could be the case that the 2nd value, and thus the highest X-value of the linearisation table, is smaller than the minimum span permitted (CAL_MIN_SPAN, Page 34). The message goes out as soon as the highest X-value is larger than the minimum span and the table entered is active.
4. Once you have entered the maximum tank contents to be expected for SCALE_OUT, EU_100 element, the alarm "A719 Y-Val of lin. table out of edit limits" can appear. At this stage the linearisation table already consists of two points as standard. It could be the case that the 2nd value, and thus the highest Y-value of the linearisation table, is larger than the value entered for SCALE_OUT, EU_100 element. The message goes out as soon as no Y-value is larger than the value for SCALE_OUT, EU_100 element and the table entered is active.

4.3.2 Manual entry of the linearisation table

!
Example:
In this example, the volume in a tank with a conical outlet should be measured in m
3
.
Prerequisite:
• This is a theoretical calibration, i.e. the points for the linearisation table are known.
Note!
• See also Operating Instructions BA301P Deltabar S or Operating Instructions BA302P Cerabar S,
Section 6.6 "Level measurement".
• For a description of the parameters mentioned, see
– Page 33, Pressure Transducer Block. – Page 65, Analog Input Block.
Description
1 Perform calibration as per Section 4.3.1, Steps 1 to 10.
Carry out linearisation:
2 Select SCALE_OUT parameter, EU_0 element.
Specify the minimum tank contents to be expected, here
3
0 m
for example.
3Select SCALE_OUT parameter, EU_100 element.
Specify the maximum tank contents to be expected, here
3
3.5 m
for example. See also the following note, point 3.
4 Select the "Manual" option by means of the
LINEARIZATION_TABLE_MODE/LIN. EDIT MODE parameter.
5 Select the "Edit table" option by means of the
TAB_OBCODE/TABLE SELECTION parameter.
V
3
[m ]
3.5
0
0 350
P01-PMP75xxx-19-xx-xx-xx-002
p
[mbar]
12 Endress+Hauser
Cerabar S/Deltabar S Level measurement (FF configuration program)
Description
6 Enter linearisation table (min. 2 points, max. 32 points).
TAB_ENTRY: enter the value of the corresponding point.
TAB_XY_VALUE, 1st element (X-value): enter the pressure value.
TAB_XY_VALUE, 2nd element (Y-value): enter the volume value, here 0 m
7 You can enter further points for the linearisation table as
explained in Step 6. The previous point first has to be saved in the linearisation table before the next point can be entered. In other words, a complete linearisation table cannot be saved to the device. Once all the points have been entered, the table must be activated by means of the TAB_OBCODE/TABLE SELECTION parameter.
8 Set the Pressure Transducer Block to the "Auto" block
mode.
9 If necessary, use the Analog Input Block to configure the
CHANNEL parameter ( Page 67), L_TYPE parameter ( Page 69), XD_SCALE parameter ( Page 73) and OUT_SCALE parameter ( Page 71).
10 Result:
The linearisation table is entered and the measuring device is ready for level measurement.
3
for example, and confirm.
V
3
[m ]
3.5
0
0 350
Fig. 3: Manual entry of the linearisation table
1 See Section 4.3.1, Table, Step 9. 2 See Section 4.3.1, Table, Step 10. 3 See this Table, Step 2. 4 See this Table, Step 3. 5 See this Table, Steps 4 to 7.
p
[mbar]
P01-xxxxxxxx-05-xx-xx-xx-015
!
Note!
1. For this level type, the measured variables %, volume and mass are available. See Page 40 ff.
2. You can also specify customer-specific units. See parameter descriptions for CAL_UNIT
(Page 34), HEIGHT_UNIT (Page 41), VOLUME_UNIT (Page 42) and MASS_UNIT (Page 43).
3. Once you have entered the maximum tank contents to be expect ed f or S CAL E_OUT, EU_100 element, the alarm "A719 Y-Val of lin. table out of edit limits" can appear. At this stage the linearisation table already consists of two points as standard. It could be the case that the 2nd value, and thus the highest Y-value of the linearisation table, is larger than the value entered for SCALE_OUT, EU_100 element. The message goes out as soon as no Y-value is larger than the value for SCALE_OUT, EU_100 element and the table entered is active.
Endress+Hauser 13
Level measurement (FF configuration program) Cerabar S/Deltabar S

4. 4 "Height linearized" level type

4.4.1 Dry calibration and manual entry of the linearisation table

Example:
In this example, the height and the volume should be measured at the same time.
Prerequisite:
• This is a theoretical calibration, i.e. the points for the linearisation table are known.
!
Note!
• See also Operating Instructions BA301P Deltabar S or Operating Instructions BA302P Cerabar S,
Section 6.6 "Level measurement".
• For a description of the parameters mentioned, see
– Page 33, Pressure Transducer Block. – Page 65, Analog Input Block.
Description
1 Deltabar S: before configuring the device for your
application, the pressure piping must be cleaned and the device filled with fluid. See Operating Instructions BA301P, Section 6.6.1
2 Open the Pressure Transducer Block and set the block
mode to OOS.
3 You have the following ways of carrying out position
adjustment:
• By means of the "Pos. zero adjust" method, see Operating Instructions BA301P or BA302P, Section 6.4.
• By means of the parameters – PRESSURE_1_ACCEPT_ZERO_INSTALL_
OFFSET/POS. ZERO ADJUST (Page 38) or
– PRESSURE_1_ACCEPT_INSTALL_OFFSET/
POS. INPUT VALUE (Page 38) or
– PRESSURE_1_INSTALL_OFFSET/CALIB. OFFSET
(Page 38).
Perform calibration for the 1st measured variable:
4 Select the measuring mode if necessary:
• Select the "Level combined" option by means of the LINEARIZATION parameter.
• Select the "Volume" option by means of the PRIMARY_VALUE_TYPE parameter.
5 Select a pressure unit via the CAL_UNIT parameter, here
mbar for example.
6 Select the "Height linearised" option by means of the
LEVEL_TYPE/LEVEL MODE parameter.
7 Select the "Height + volume" option by means of the
MEASURAND_COMBINED/COM. MEASURAND parameter.
8 Select the unit for the 1st measured value via the
HEIGHT UNIT parameter, here m for example.
9 Select the unit for the 2nd measured variable via the
VOLUME_UNIT/UNIT VOLUME parameter, here m for example.
3
Fig. 4: Calibrating the 1st measured variable
1 See Table, Step 10. 2 See Table, Step 11.
P01-PMP75xxx-19-xx-xx-xx-006
14 Endress+Hauser
Cerabar S/Deltabar S Level measurement (FF configuration program)
Description
10 Select the LINEAR_LEVEL_MIN/LEVEL MIN.
parameter.
Enter the minimum level to be expected, here 0 m for example.
11 Select the LINEAR_LEVEL_MAX/LEVEL MAX.
parameter.
Enter the maximum height to be expected, here 3 m for example. See also the following note, point 3.
12 Select the "Dry" option by means of the
LEVEL_ADJUST_MODE/ CALIBRATION MODE parameter (calibration mode for the 1st measured variable). See also the following note, point 4.
13 Enter the value for density via the
LEVEL_ADJUST_DENSITY/ADJUST DENSITY and DENSITY_UNIT parameters, here 1 kg/dm
3
for
example.
14 Result:
The calibration for the 1st measured variable is carried out.
Perform linearisation (calibration for the 2nd measured variable)
15 Select SCALE_OUT parameter, EU_0 element.
Specify the minimum tank contents to be expected, here
3
0 m
for example.
16 Select SCALE_OUT parameter, EU_100 element.
Specify the maximum tank contents to be expected, here
3
5 m
for example.
17 Select the "Manual" option by means of the
LINEARIZATION_TABLE_MODE/LIN. EDIT MODE parameter.
18 Select the "Edit table" option by means of the
TAB_OBCODE/TABLE SELECTION parameter.
19 Enter linearisation table (min. 2 points, max. 32 points).
TAB_ENTRY: enter the value of the corresponding point.
TAB_XY_VALUE, 1st element (X-value): enter the level, here 0 m for example.
TAB_XY_VALUE, 2nd element (Y-value): enter the volume value, here 0 m
3
.
20 You can enter further points for the linearisation table as
explained in Step 19. The previous point first has to be saved in the linearisation table before the next point can be entered. In other words, a complete linearisation table cannot be saved to the device. Once all the points have been entered, the table must be activated by means of the TAB_OBCODE/TABLE SELECTION parameter.
21 Set the Pressure Transducer Block to the "Auto" block
mode.
22 If necessary, use the Analog Input Block to configure the
CHANNEL parameter ( Page 67), L_TYPE parameter ( Page 69), XD_SCALE parameter ( Page 73) and OUT_SCALE parameter ( Page 71).
V
3
[m ]
5
0
03
Fig. 5: Calibrating the 2nd measured variable
3 See Table, Step 15 4 See Table, Step 16. 5 See Table, Steps 17 to 20.
V
3
[m ]
5
0
03
P01-PMP75xxx-19-xx-xx-xx-005
[m]
h
h
[m]
P01-xxxxxxxx-05-xx-xx-xx-022
Endress+Hauser 15
Level measurement (FF configuration program) Cerabar S/Deltabar S
Description
23 Result:
– The linearisation table has been entered. – The measured value display and the
PRIMARY_VALUE parameter display the 2nd measured value (here the volume).
– The MEASURED_LEVEL_AFTER_SIMULATION/
LEVEL BEFORE LIN parameter displays the 1st measured value (here the height). See also the following note, point 5.
!
Note!
1. For this level type, the measured variables "height + %", "height + volume", "height + mass", "%-height + %", "%-height + volume" and "%-height + mass" are available. See Page 41 ff.
2. You can also specify customer-specific units. See parameter descriptions for CAL_UNIT (Page 34), HEIGHT_UNIT (Page 41), VOLUME_UNIT (Page 42) and MASS_UNIT (Page 43).
3. Once you have entered the maximum height to be expected for LINEAR_LEVEL_MAX/ LEVEL MAX., the alarm "A707 X-Val of lin. table out of edit limits" can appear. At this stage the linearisation table already consists of two points as standard. It could be the case that the 2nd value, and thus the highest X-value of the linearisation table, is greater than the maximum level entered. The message goes out as soon as the highest X-value is larger than the maximum level and the table entered is active.
4. The "Wet" calibration mode is not available by means of the FF operating programs.
5. You can use the DISPLAY_MAINLINE_CONTENT/ MENU DESCRIPTOR parameter (→ Page 60) to specify which measured value should be displayed on the on-site display.
16 Endress+Hauser

Cerabar S/Deltabar S Flow measurement (FF configuration program)

5Flow measurement
(FF configuration program)

5. 1 Calibration

!
Example:
In this example, a volume flow should be measured in m
3
/h.
Note!
• The "Flow measurement" measuring mode is only available for the Deltabar S differential pressure transmitter.
• See also Operating Instructions BA301P Deltabar S, Section 6.5 "Flow measurement".
• For a description of the parameters mentioned, see – Page 33, Pressure Transducer Block. – Page 65, Analog Input Block.
Description
1 Before configuring the device for your application, the
pressure piping must be cleaned and the device filled with fluid. See Operating Instructions BA301P, Section
6.5.1.
2 Open the Pressure Transducer Block and set the block
mode to OOS.
3 Carry out position adjustment if necessary.
You have the following ways of carrying out position adjustment:
• By means of the "Pos. zero adjust" method, see Operating Instructions BA301P, Section 6.4.
• By means of the parameters – PRESSURE_1_ACCEPT_ZERO_INSTALL_
OFFSET/POS. ZERO ADJUST (Page 38) or
– PRESSURE_1_ACCEPT_INSTALL_OFFSET/
POS. INPUT VALUE (Page 38) or
– PRESSURE_1_INSTALL_OFFSET/CALIB. OFFSET
(Page 38).
4 Select the measuring mode if necessary:
• Select the "Flow Square root" option by means of the LINEARIZATION parameter.
• Select the "Flow" option by means of the PRIMARY_VALUE_TYPE parameter.
5 Select a pressure unit via the CAL_UNIT parameter, here
mbar for example.
6 Select the "Volume p. cond." option by means of the
FLOW_TYPE/FLOW-MEAS. TYPE parameter.
7 Select a flow unit via the FLOW_UNIT/UNIT FLOW
parameter, here m
8 Select SCALE_OUT parameter, EU_100 element.
Enter the maximum flow value of the primary device, here 6000 m
9 Select SCALE_IN parameter, EU_100 element.
Enter the maximum pressure, here 400 mbar for example. See also layout sheet of primary device.
3
/h for example.
3
/h. See also layout sheet of primary device.
V
3
[m /h]
6000
0
0 400
Fig. 6: Flow measurement calibration
1 See Table, Step 8. 2 See Table, Step 9.
p
[mbar]
P01-xMD7xxx-05-xx-xx-xx-010
Endress+Hauser 17
Flow measurement (FF configuration program) Cerabar S/Deltabar S
Description
10 Set the Pressure Transducer Block to the "Auto" block
mode.
11 If necessary, use the Analog Input Block to configure the
CHANNEL parameter ( Page 67), L_TYPE parameter ( Page 69), XD_SCALE parameter ( Page 73) and OUT_SCALE parameter ( Page 71).
12 Result:
The measuring device is configured for flow measurement.
!
Note!
1. Using the FLOW_TYPE/FLOW_MEAS. TYPE parameter, you can choose between the following flow types: – Volume p. cond. (volume under operating conditions) – Gas norm. cond. (norm volume under norm conditions in Europe: 1013.25 mbar and
273.15 K (0 °C))
– Gas std. cond. (standard volume under standard conditions in USA: 1013.25 mbar (14.7 psi)
and 288. 15 K (15 °C/59 °F))
– Mass p. cond. (mass under operating conditions)
2. The unit selected by means of the FLOW_UNIT/UNIT FLOW (→ Page 47) parameter must suit the flow type selected (FLOW_TYPE/FLOW_MEAS. TYPE).
3. In the lower measuring range, small flow quantities (creepages) can lead to large measured value fluctuations. You can activate low flow cut-off via the CREEP_FLOW_SUPPRESSION_ ENABLE/LOW FLOW CUT-OFF parameter (Page 48).
18 Endress+Hauser
Cerabar S/Deltabar S Flow measurement (FF configuration program)

5. 2 Totalizers

!
Example:
In this example, the volume flow should be totalised and displayed in the unit m should be added to the flow rate.
Note!
• For a description of the parameters mentioned, see – Page 58, Totalizer Transducer Block – Page 65, Analog Input Block.
• Totalizer 1 can be reset. Totalizer 2 cannot be reset.
Description
1 Calibrate the device as per Section 5.1.
2 Open the Totalizer Transducer Block.
3 Select a flow unit via the TOTALIZER_1_UNIT/TOTAL.
1 ENG. UNIT parameter, here m
4 Use the TOTALIZER_1_MODE/ NEG. FLOW TOT. 1
parameter to specify the totalising mode for negative flows, here the "Positive" option for example.
5 Reset totalizer 1 to zero via the TOTALIZER_1_RESET/
RESET TOTALIZER 1 parameter.
6Result:
The TOTALIZER_1_VALUE parameter displays the totalised volume flow.
3 E3
for example.
3E3
. Negative flows
!
Note!
• You can also specify a customer-specific unit. See parameter description for TOTALIZER_1_ UNIT (Page 58).
• You can use the DISPLAY_MAINLINE_CONTENT/ MENU DESCRIPTOR parameter (Page 60) to specify which measured value should be displayed on the on-site display.
• The parameters for the 2nd totalizer such as TOTALIZER_2_UNIT/TOTAL. 2 ENG. UNIT, TOTALIZER_2_MODE/NEG. FLOW TOT. 2 and TOTALIZER_2_FLOAT/TOTALIZER 2 are in the Pressure Transducer Block.
Endress+Hauser 19
Flow measurement (FF configuration program) Cerabar S/Deltabar S

5.2.1 Resetting totalizer 1 automatically

Use the Analog Alarm and Discrete Output Block to automatically reset Totalizer 1 in the Totalizer Transducer Block.
HI_HI_LIM HI_HI_ALM
Totalizer Transducer Block
Analog Input Block 3
TOTALIZER_1_
VALUE/
TOTALIZER 1
CHANNEL = 6 L_TYPE = Direct
Analog Alarm
OUT
IN
Block
CAS_IN_D
OUT_ALM
Discrete Output Block
CHANNEL = 2
P01-xxxxxxxx-02-xx-xx-xx-002
OUT_D
The Totalizer Transducer Block is linked to an Analog Input Block by means of the CHANNEL parameter (CHANNEL = 6). In the Analog Alarm Block, the HI_HI_LIM parameter is used to set a limit value at which the totalizer should be reset to zero. As soon as this limit value is overshot, the Analog Alarm Block sends an alarm value to the downstream Discrete Output Block. This changes its output from 0 to 1, thereby resetting the totalizer in the Totalizer Transducer Block to 0. The output of the Analog Alarm Block changes back to the value 0.
20 Endress+Hauser

Cerabar S/Deltabar S Description of parameters (FF configuration program)

6 Description of parameters
(FF configuration program)
!
Note!
• In FOUNDATION Fieldbus, all the device parameters are categorised depending on their functional properties and tasks and assigned to the Resource Block, the Transducer Blocks and the function blocks. This Section describes the parameters of the Resource Block, the Transducer Blocks and the Analog Input Block. For a parameter description of other function blocks, such as the PID or Discrete Output Block, see Operating Instructions BA013S "FOUNDATION Fieldbus Overview" or the FOUNDATION Fieldbus Specification.
• Some parameters are only displayed if other parameters are appropriately configured. For example, the PRESSURE_1_UNIT_TEXT/CUSTOMER UNIT P parameter is not displayed unless the "User Unit" option was selected for the CAL_UNIT parameter. There is a comment in the parameter description here stating: Note: prerequisite: CAL_UNIT = User Unit.
• Parameter names are written in upper case in the text.

6.1 Deltabar S and Cerabar S block model

Deltabar S/Cerabar S has the following blocks:
• Resource Block (device block)
• Transducer Blocks – Pressure Transducer Block
This Block supplies the output variables PRIMARY_VALUE and SECONDARY_VALUE. It contains all the parameters to configure the measuring device for the measuring task such as measuring mode selection, linearisation function and unit selection.
– Service Transducer Block
This Block supplies the output variables PRESSURE, MAX. MEAS. PRESS. and COUNTER: P > Pmax. It also includes all the counters for measuring range overshoot/ undershoot for pressure and temperature, minimum and maximum measured values for pressure and temperature and the HistoROM function.
– Totalizer Transducer Block (Deltabar S only)
This Block supplies the output variable TOTALIZER_1_VALUE/TOTALIZER 1. It contains all the parameters that are needed to configure this totalizer.
– Display Transducer Block
This Block does not return any output variable. It contains all the parameters for configuring the on-site display such as DISPLAY_LANGUAGE/LANGUAGE and DISPLAY_CONTRAST.
– Diagnostic Transducer Block
This Block does not return any output variable. It contains the simulation function for the Pressure Transducer Block, parameters to configure the alarm response and the user limits for pressure and temperature.
• Function blocks – Deltabar S: 3 Analog Input Blocks (AI), Cerabar S: 2 Analog Input Blocks (AI) – Discrete Output Block (DO) – PID Block (PID) – Arithmetic Block (ARB) – Signal Characterizer Block (SCB) – Input Selector Block (ISB) – Analog Alarm Block (AALB)
Endress+Hauser 21
Description of parameters (FF configuration program) Cerabar S/Deltabar S
Block configuration when delivered
The block model shown below illustrates the block configuration when the device is delivered.
Measured variable
Sensor
Signal evaluation
Pressure Transducer Block
Service Transducer Block
Totalizer Transducer Block
Display Transducer Block
Diagnostic Transducer Block
Fig. 7: Block configuration when delivered
Display
with scaling
Primary value
Secondary value
Deltabar only
TOTALIZER 1
Analog Input Block 1
CHANNEL = 1 L_TYPE = Direct
Analog Input Block 2
CHANNEL = 2 L_TYPE = Direct
Analog Input Block 3
CHANNEL = 6 L_TYPE = Direct
Arithmetic Block
Discrete Output Block
Resource Block
PID Block
Signal Characterizer Block
Input Selector Block
Analog Alarm Block
P01-xMx7xxxx-02-xx-xx-xx-000
!
Cerabar S
The Pressure Transducer Block returns the Primary Value (pressure measured value) and the Secondary Value (sensor temperature). Primary Value and Secondary Value are each transferred to one Analog Input Block by means of the CHANNEL parameter (see also Page 67, parameter description CHANNEL). The Discrete Output, PID, Arithmetic, Signal Characterizer, Input Selector and Analog Alarm Block are not connected in the as-delivered state.
Deltabar S
The Pressure Transducer Block returns the Primary Value (pressure measured value) and the Secondary Value (sensor temperature). In the Totalizer Transducer Block, the flow is totalized in the "Flow" measuring mode and output by means of the TOTALIZER_1_VALUE/TOTALIZER 1 parameter. Primary Value, Secondary Value and TOTALIZER_1_VALUE are each transferred to one Analog Input Block by means of the CHANNEL parameter (see also Page 67, parameter description CHANNEL). The Discrete Output, PID, Arithmetic, Signal Characterizer, Input Selector and Analog Alarm Block are not connected in the as-delivered state.
Note! Please note that the links between the blocks are deleted and the FF parameters are reset to the default values following a reset by means of the RESTART parameter in the Resource Block, "Default" option.
22 Endress+Hauser
Cerabar S/Deltabar S Description of parameters (FF configuration program)

6.2 Resource Block

Resource Block
Parameter Description
ACK_OPTION Selection
Index: 38 Data type: Bit String Access: Auto, OOS
ALARM_SUM Display, Selection
Index: 45 Data type: DS-74 Access: Auto, OOS
ALERT_KEY Entry
Index: 4 Data type: Unsigned8 Access: Auto, OOS
BLOCK_ALM Display, Selection
Index: 36 Data type: DS-72 Access: Auto, OOS
BLOCK_ERR Display
Index: 6 Data type: Bit String Access: Read only
Use this parameter to specify which process alarm is automatically acknowledged by the fieldbus host system when it is detected. If the option is activated for a process alarm, this process alarm is automatically acknowledged by the fieldbus host system.
Options:
• DiscAlm: write protection alarm
• BlockAlm: block alarm
Note!
!
For process alarms for which automatic confirmation is not active, the message must be acknowledged by means of the BLOCK_ALM parameter, UNACKNOWLEDGE element.
Factory setting:
The option is not active for any process alarm, i.e. every process alarm message must be acknowledged manually.
The ALARM_SUM parameter is a structured parameter consisting of four elements.
CURRENT
• Displays the current status of the process alarms in the Resource Block. The following alarms are possible: DiscAlm and BlockAlm.
UNACKNOWLEDGED
• Displays the process alarms not confirmed.
UNREPORTED
• Displays the process alarms not reported.
DISABLED
• Possibility to deactivate process alarms.
Enter the identification number for the measuring device or for every individual block. The host system uses this identification number to sort alarm and event messages and initiate further processing.
Input range:
1...255
Factory setting:
0
The BLOCK_ALM parameter is a structured parameter consisting of five elements.
UNACKNOWLEDGED
• If the "Deactivated" option was selected for the alarm occurring via the ACK_OPTION parameter, this alarm can only be acknowledged via this element.
ALARM_STATE
• Displays the current block status with information on the pending configuration, hardware or system errors. The following block alarm messages are possible for the Resource Block: –Simulate Active –Out of Service
TIME_STAMP
• Displays the time the alarm occurred.
SUB_CODE
• Displays the reason why the alarm was reported.
VALUE
• Displays the value of the parameter at the time the alarm was reported.
Displays the active block errors.
Possibilities:
• Out Of Service: the Resource Block is in the OOS block mode.
• Simulation active: DIP switch 2 "Simulation" on the electronic insert is set to "On", i.e. simulation is possible.
Endress+Hauser 23
Description of parameters (FF configuration program) Cerabar S/Deltabar S
Resource Block
Parameter Description
CLR_FSTATE/ CLEAR FAULT STATE Selection
Index: 30 Data type: Unsigned8 Access: Auto, OOS
CONFIRM_TIME Entry
Index: 33 Data type: Unsigned32 Access: Auto, OOS
CYCLE_SEL Display
Index: 20 Data type: Bit String Access: Auto, OOS
CYCLE_TYPE Display
Manually deactivate the fault state of the Discrete Output function block. See also this table, SET_FSTATE parameter description.
Possibilities:
• Uninititalized
•Off
• Clear (the fault state is deactivated.)
Enter the confirmation time for the event report. If the device does not receive any confirmation within this period, the event report is sent again to the fieldbus host system.
Factory setting:
1
640000
/32 ms
Displays the block execution method used by the fieldbus host system. The fieldbus host system selects the block execution method.
Possibilities:
• Scheduled: cyclical block execution method
• Block execution: sequential block execution method
Displays the block execution methods supported by the device. See also this table, CYCLE_SEL parameter description.
Index: 19 Data type: Bit String Access: Read only
DD_REV Display
Index: 13 Data type: Unsigned8 Access: Read only
DEV_REV Display
Index: 12 Data type: Unsigned8 Access: Read only
DEV_TYPE Display
Index: 11 Data type: Unsigned16 Access: Read only
FAULT_STATE Display
Index: 28 Data type: Unsigned8 Access: Read only
FEATURES Display
Displays the revision number of the device description (DD).
Displays the revision number of the device.
Displays the device identification number. Deltabar S: hexadecimal: 1009, decimal: 4105. Cerabar S: hexadecimal: 1007, decimal: 4103.
Current status display of the fault state of the Discrete Output function block.
Possibilities:
• Uninititalized
• Clear (fault state not active)
• Active (fault state active)
Displays the additional functions supported by the device. See also this table, FEATURE_SEL parameter description.
Index: 17 Data type: Bit String Access: Read only
FEATURE_SEL/ FEATURE SELECTION Selection
Index: 18 Data type: Bit String Access: Auto, OOS
Select additional device functions. The additional functions the device supports is displayed in the FEATURES parameter ( Page 24).
24 Endress+Hauser
Cerabar S/Deltabar S Description of parameters (FF configuration program)
Resource Block
Parameter Description
FREE_SPACE Display
Index: 24 Data type: Float Access: Read only
FREE_TIME Display
Index: 25 Data type: Float Access: Read only
GRANT_DENY Selection
Index: 14 Data type: DS-70 Access: Auto, OOS
HARD_TYPES Display
Displays in percent the system space available to execute further function blocks.
Input range:
0...100 %
Displays in percent the free system time available to execute further function blocks.
Input range:
0...100 %
Grant or restrict access rights for a fieldbus host system to the device. This parameter is not evaluated by Deltabar S and Cerabar S.
Displays the input signal type for the Analog Input function blocks.
Index: 15 Data type: Bit String Access: Read only
ITK_VER Display
Index: 41 Data type: Unsigned16 Access: Read only
LIM_NOTIFY Entry
Index: 32 Data type: Unsigned8 Access: Auto, OOS
MANUFAC_ID Display
Index: 10 Data type: Unsigned16 Access: Read only
MAX_NOTIFY Display
Index: 31 Data type: Unsigned8 Access: Read only
MEMORY_SIZE Display
Displays the revision status of the ITKs (Interoperability Test Kit).
Enter the maximum possible number of event reports that can be simultaneously present as unacknowledged. The parameter is not evaluated by Deltabar S and Cerabar S.
Displays the manufacturer identification number. Endress+Hauser: 0 x 452B48 (decimal: 4533064)
Displays the number of event reports supported by the device that can be simultaneously present as unacknowledged. See also this table, LIM_NOTIFY parameter description.
Displays the configuration memory available in kilobyte. This parameter is not supported by Deltabar S and Cerabar S.
Index: 22 Data type: DS-69 Access: Read only
MIN_CYCLE_T Display
Index: 21 Data type: Unsigned32 Access: Read only
Displays the shortest execution time supported by the device.
Factory setting:
1
1600
/32 ms ( 50 ms)
Endress+Hauser 25
Description of parameters (FF configuration program) Cerabar S/Deltabar S
Resource Block
Parameter Description
MODE_BLK Selection, Display
Index: 5 Data type: DS-69 Access: Auto, OOS
NV_CYCLE_T/ NONVOLATILE CYCLE TIME Display
Index: 23 Data type: Unsigned32 Access: Read only
RESTART Selection
Index: 16 Data type: Unsigned8 Access: Auto, OOS
RS_STATE Display
Index: 7 Data type: Unsigned8 Access: Read only
SET_FSTATE/ SET FAULT STATE Selection
Index: 29 Data type: Unsigned8 Access: Auto, OOS
SHED_RCAS/ SHED REMOTE CASCADE Entry
Index: 26 Data type: Unsigned32 Access: Auto, OOS
SHED_ROUT/ SHED REMOTE OUT Entry
Index: 27 Data type: Unsigned32 Access: Auto, OOS
The MODE_BLK parameter is a structured parameter consisting of four elements. The Resource Block supports the "Auto" (automatic mode) and OOS (out of service) modes.
TARGET
• Change the block mode.
ACTUAL
• Displays the current block mode.
PERMITTED
• Displays the modes supported by the block.
NORMAL
• Displays the block mode during standard operation.
Displays the time interval in which the dynamic device parameters are stored in the non­volatile memory. As Cerabar S and Deltabar S do not store dynamic device parameters in the non-volatile memory, the parameter constantly displays the value 0
1
/32 ms.
Select reset mode.
Options:
• Run: standard operating mode
• Resource: this mode is not supported by Endress+Hauser.
• Defaults: device data and the function block link are reset to the factory setting. The manufacturer-specific parameters of the Transducer Block are not reset to the factory setting. See also Operating Instructions BA301P (Deltabar S) or BA302P (Cerabar S), Section 5.7 "Factory setting" (reset).
• Processor: warm start, of device, new processor start.
• Factory: the function block links, all FF and resettable manufacturer-specific parameters are reset to the factory setting.
Displays the current status of the Resource Block.
Possibilities:
• Standby: the Resource Block is in the OOS mode (out of service). It is not possible to execute the remaining blocks.
• Online linking: the configured links between the function blocks have not yet been established.
• Online: standard block mode, the Resource Block works in the Auto mode. All the configured links between the function blocks have been established. If a link is missing, this parameter displays the "online linking" status.
Manually activate the fault state of the Discrete Output function block. See also this table, CLR_FSTATE parameter description.
Possibilities:
• Uninititalized
•Off
• Set (the fault state is activated.)
Enter the monitoring time for checking the link between the fieldbus host system and the PID function block in the RCAS block mode. Once this monitoring time elapses, the PID function block changes from the RCAS block mode to the block mode selected by means of the SHED_OPT parameter.
Factory setting:
1
640000
/32 ms
Enter the monitoring time for checking the link between the fieldbus host system and the PID function block in the ROUT block mode. Once this monitoring time elapses, the PID function block changes from the ROUT block mode to the block mode selected by means of the SHED_OPT parameter.
Factory setting:
1
640000
/32 ms
26 Endress+Hauser
Cerabar S/Deltabar S Description of parameters (FF configuration program)
Resource Block
Parameter Description
ST_REV Display
Index: 1 Data type: Unsigned16 Access: Read only
STRATEGY Entry
Index: 3 Data type: Unsigned16 Access: Auto, OOS
TAG_DESC Entry
Index: 2 Data type: Octet String Access: Auto, OOS
TEST_RW/ TEST READ WRITE Display
Index: 8 Data type: DS-85 Access: Auto, OOS
UPDATE_EVT Display
Index: 35 Data type: DS-73 Access: Read only
WRITE_ALM Display
Index: 40 Data type: DS-72 Access: Read only
Displays the counter for static parameters of the Resource Block This counter is incremented by one with each change of a static parameter of the Resource Block. The counter counts up to 65535 and then starts again at zero.
Enter a user-specific value for grouping and thus faster evaluation of the blocks. Grouping takes place by entering the same numerical value for the STRATEGY parameter of the block in question. This value is neither checked nor processed by the Resource Block.
Input range:
0...65535
Factory setting:
0
Enter a description for the associated block or the measuring point e.g. TAG number (max. 32 alphanumeric characters).
This parameter is only needed for the FF conformance test and does not have any relevance during measuring operation.
The UPDATE_EVT parameter is a structured parameter consisting of five elements.
UNACKNOWLEDGED
• This element is set to "Unacknowledged" as soon as a static parameter changes.
UPDATE_STATE
• Displays whether the change was reported.
TIME_STAMP
• Displays the date and time a static parameter was changed.
STATIC_REVISION
• The revision counter is increased when a static parameter changes.
RELATIVE_INDEX
• Displays the altered parameter in the form of the relative index. See also this table, "Parameter, Index" column.
The WRITE_ALM parameter is a structured parameter consisting of five elements.
UNACKNOWLEDGED
• If the "Deactivated" option was selected for the alarm occurring via the ACK_OPTION parameter, this alarm can only be acknowledged via this element.
ALARM_STATE
• Status display of the write protection alarm.
TIME_STATE
• Displays the time the alarm occurred.
SUB_CODE
• Displays the reason why the alarm was reported.
VALUE
• Displays the value of the parameter at the time the alarm was reported.
Endress+Hauser 27
Description of parameters (FF configuration program) Cerabar S/Deltabar S
Resource Block
Parameter Description
WRITE_LOCK Display
Index: 34 Data type: Unsigned8 Access: Read only
WRITE_PRI Entry
Index: 39 Data type: Unsigned8 Access: Read only
SW_LOCK/ INSERT PIN No. Entry
Index: 43 Data type: Unsigned16 Access: Auto, OOS
Endress+Hauser Resource Block parameters
DEVICE_DIALOG Display
Index: 42 Data type: Unsigned8 Access: Read only
DEVICE_ORDER_CODE /DEVICE DESIGN. Display
Displays the status of DIP switch 1 on the electronic insert. You can lock and unlock parameters relevant to the measured value with DIP switch 1. If operation is locked by means of the SW_LOCK/INSERT PIN No. parameter (see Page 28), you can only unlock operation again by means of this parameter. See also Operating Instructions BA301P (Deltabar S) or BA302P (Cerabar S), Section 5.6 "Locking/unlocking operation".
Possibilities:
• Locked: locking switched on, i.e. the parameters cannot be written to.
• Not Locked: locking switched off. Depending on the block mode in question, the
parameters can be written to (see tables, "Parameter", Access column).
Factory setting:
Locked (locking switched off)
Disabling write protection generates an alarm. Use this parameter to specify which priority should be assigned to this alarm.
Input range:
• 0...15
• 0: The alarm is suppressed.
• 15: Critical alarm with the highest priority.
For entering a code to lock or unlock operation.
Note!
!
• The symbol on the on-site display indicates that operation is locked. Parameters which refer to how the display appears, e.g. LANGUAGE and DISPLAY CONTRAST can still be altered.
• If operation is locked by means of the DIP-switch, you can only unlock operation again by means of the DIP-switch. If operation is locked by means of remote operation, you can only unlock operation again by means of remote operation.
See also Operating Instructions BA301P (Deltabar S) or BA302P (Cerabar S), Section 5.6 "Locking/unlocking operation".
Options:
• Lock: enter a number between 0...9999 which is ≠100.
• Unlock: enter number 100.
Factory setting:
100
If the configuration is not suitable, this parameter displays a message saying that a configuration error is present. The message can indicate which parameter was incorrectly configured.
Displays the device designation and the order code.
Index: 44 Data type: Visible String Access: Read only
HARDWARE_REVISION Display
Index: 45 Data type: Visible String Access: Read only
SOFTWARE_VERSION Display
Index: 46 Data type: Float Access: Read only
Displays the revision number of the main electronics e.g. V01.00.
Displays the software version e.g. V02.00.
28 Endress+Hauser
Cerabar S/Deltabar S Description of parameters (FF configuration program)
Resource Block
Parameter Description
ELECTRONIC _SERIAL _NUMBER/ ELECTR. SERIAL No. Display
Index: 47 Data type: Float Access: Read only
DEVICE_SERIAL_ NUMBER/ DEVICE SERIAL No. Display
Index: 48 Data type: Float Access: Read only
PROCESS_CONNEC­TION_MODEL/ PROC. CONN. TYPE Selection
Index: 49 Data type: Unsigned16 Access: Auto, OOS
PROCESS_CONNEC­TION_MATERIAL_ POSITIVE/ MAT. PROC. CONN. + Selection
Index: 50 Data type: Float Access: Auto, OOS
PROCESS_CONNEC­TION_MATERIAL_ NEGATIVE/ MAT.PROC. CONN.– Selection
Displays the serial number of the main electronics (11 alphanumeric characters).
Displays the serial number of the device (11 alphanumeric characters).
For selecting and displaying the process connection type.
Options:
•Not used
•Unknown
•Special
•Oval flange
• Thread female
•Thread male
•Flange
•Remote seal
For selecting and displaying the material of the process connection (P+). See also parameter description MAT. PROC. CONN. –
Options:
•Not used
•Unknown
•Special
• Steel
• 304 st. steel
• 316 st. steel
• Alloy C
•Monel
•Tantalum
• Titanium
•PTFE (Teflon)
• 316L st. steel
•PVC
•Inconel
•PVDF
•ECTFE
Factory setting:
As per order specifications
For selecting and displaying the material of the process connection (P–). See also parameter description MAT. PROC. CONN. +
Index: 51 Data type: Float Access: Auto, OOS
Endress+Hauser 29
Description of parameters (FF configuration program) Cerabar S/Deltabar S
Resource Block
Parameter Description
PROCESS_FLANGE_ GASKET_MATERIAL/ SEAL TYPE Selection
Index: 52 Data type: Visible String Access: Auto, OOS
SCI_OCTET_STR Display
For displaying and selecting the material of the process seal.
Options:
•Not used
•Unknown
•Special
• FKM Viton
•NBR
•EPDM
•Urethane
•IIR
•Kalrez
• FKM Viton oxyg
•CR
•MVQ
•PTFE glass
•PTFE graphite
• PTFE oxygen
• Copper
• Copper f. oxygen
Factory setting:
As per order specifications
Internal service parameter.
Index: 53 Data type: Visible String Access: Read only
30 Endress+Hauser
Loading...
+ 142 hidden pages