Endress+Hauser Cerabar PMP23 Operating Instructions Manual

Page 1
Products Solutions Services
Operating Instructions
Cerabar PMP23 IO-Link
Process pressure measurement Pressure transducer for safe measurement and monitoring of absolute and gauge pressure
Page 2
Cerabar PMP23 IO-Link
2 Endress+Hauser
Order code:
Ext. ord. cd.:
Ser. no.:
www.endress.com/deviceviewer
Endress+Hauser Operations App
XXXXXXXXXXXX
XXXXX-XXXXXX
XXX.XXXX.XX
Serial number
1.
3.
2.
A0023555
• Make sure the document is stored in a safe place such that it is always available when working on or with the device.
• To avoid danger to individuals or the facility, read the "Basic safety instructions" section carefully, as well as all other safety instructions in the document that are specific to working procedures.
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to these Operating Instructions.
Page 3
Cerabar PMP23 IO-Link Table of contents
Endress+Hauser 3
Table of contents
1 Document information .............. 4
1.1 Document function ..................... 4
1.2 Symbols used .......................... 4
1.3 Documentation ........................ 5
1.4 Terms and abbreviations ................. 6
1.5 Turn down calculation ................... 7
1.6 Registered trademarks ................... 7
2 Basic safety instructions ............ 8
2.1 Requirements concerning the staff .......... 8
2.2 Designated use ........................ 8
2.3 Workplace safety ....................... 9
2.4 Operational safety ...................... 9
2.5 Product safety ......................... 9
3 Product description ................ 10
3.1 Product design ........................ 10
3.2 Function ............................ 10
4 Incoming acceptance and product
identification ..................... 11
4.1 Incoming acceptance ................... 11
4.2 Product identification ................... 12
4.3 Storage and transport .................. 12
5 Installation ....................... 14
5.1 Mounting dimensions .................. 14
5.2 Installation conditions .................. 14
5.3 Influence of the installation position ........ 14
5.4 Mounting location ..................... 15
5.5 Mounting of the profile seal for universal
process mounting adapter ............... 16
5.6 Post-installation check .................. 16
6 Electrical connection .............. 17
6.1 Connecting the measuring unit ............ 17
6.2 Switching capacity ..................... 18
6.3 Connection data ....................... 18
6.4 Post-connection check .................. 18
7 Operation options ................. 19
7.1 Operation with an operating menu ......... 19
8 System integration ................ 20
8.1 Process data ......................... 20
8.2 Reading out and writing device data (ISDU –
Indexed Service Data Unit) ............... 20
8.3 Overview of diagnostic events ............. 22
9 Commissioning .................... 23
9.1 Function check ....................... 23
9.2 Commissioning with an operating menu ..... 23
9.3 Configuring pressure measurement ........ 24
9.4 Performing position adjustment ........... 26
9.5 Configuring process monitoring ........... 28
9.6 Current output ........................ 32
9.7 Application examples ................... 35
10 Diagnostics and troubleshooting ... 36
10.1 Troubleshooting ...................... 36
10.2 Diagnostic events ...................... 37
10.3 Behavior of the device in the event of a fault .. 39
10.4 Behavior of current output in the event of a
fault ............................... 39
10.5 Resetting to factory settings (reset) ........ 40
11 Maintenance ...................... 40
11.1 Exterior cleaning ...................... 40
12 Repairs ........................... 41
12.1 General notes ........................ 41
12.2 Return .............................. 41
12.3 Disposal ............................ 41
13 Overview of the operating menu ... 42
14 Description of device parameters ... 43
14.1 Identification ......................... 43
14.2 Diagnostics .......................... 43
14.3 Parameter ........................... 45
14.4 Observation ......................... 56
15 Accessories ....................... 57
15.1 Weld-in adapter ...................... 57
15.2 Process adapter M24 ................... 57
15.3 M12 plug connectors ................... 58
16 Technical data .................... 59
16.1 Input ............................... 59
16.2 Output ............................. 61
16.3 Performance characteristics of metal process
isolating diaphragm .................... 63
16.4 Environment ......................... 65
16.5 Process ............................. 66
Index .................................. 67
Page 4
Document information Cerabar PMP23 IO-Link
4 Endress+Hauser
1 Document information
1.1 Document function
These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
1.2 Symbols used
1.2.1 Safety symbols
Symbol Meaning
DANGER
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in seriousor fatal injury.
WARNING
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
CAUTION
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minoror medium injury.
NOTICE
NOTICE!
This symbol contains information on procedures and other facts which do not result in personalinjury.
1.2.2 Electrical symbols
Symbol Meaning Symbol Meaning
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
1.2.3 Tool symbols
Symbol Meaning
A0011222
Open-ended wrench
1.2.4 Symbols for certain types of information
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Page 5
Cerabar PMP23 IO-Link Document information
Endress+Hauser 5
Symbol Meaning
Reference to documentation
A
Reference to page
Reference to graphic
,…,
1.
2.
3.
Series of steps
Result of a step
Visual inspection
1.2.5 Symbols in graphics
Symbol Meaning
1, 2, 3 ... Item numbers
,…,
1.
2.
3.
Series of steps
A, B, C, ... Views
1.3 Documentation
The document types listed are available: In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download
1.3.1 Technical Information (TI): planning aid for your device
TI01203P
The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.
Page 6
Document information Cerabar PMP23 IO-Link
6 Endress+Hauser
1.4 Terms and abbreviations
URL OPLMWP
LRL
0
p
LRV
URV
1
2
3
4
A0029505
Item Term/
abbreviation
Explanation
1 OPL The OPL (over pressure limit = sensor overload limit) for the measuring device
depends on the lowest-rated element, with regard to pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes, see the "Pressure specifications" section →  66 . The OPL may only be applied for a limited period of time.
2 MWP The MWP (maximum working pressure) for the sensors depends on the lowest-
rated element, with regard to pressure, of the selected components, i.e. the process connection has to be taken into consideration in addition to the measuring cell. Also observe pressure-temperature dependency. For the relevant standards and additional notes, see the "Pressure specifications" section →  66 . The MWP may be applied at the device for an unlimited period. The MWP can also be found on the nameplate.
3 Maximum sensor
measuring range
Span between LRL and URL This sensor measuring range is equivalent to the maximum calibratable/adjustable span.
4 Calibrated/
adjusted span
Span between LRV and URV Factory setting: 0 to URL Other calibrated spans can be ordered as customized spans.
p - Pressure
- LRL Lower range limit
- URL Upper range limit
- LRV Lower range value
- URV Upper range value
- TD (turn down) Turn down The turn down is preset at the factory and cannot be changed. Example - see the following section.
Page 7
Cerabar PMP23 IO-Link Document information
Endress+Hauser 7
1.5 Turn down calculation
LRV
URLURV
LRL
1 = 2
3
A0029545
1 Calibrated/adjusted span 2 Zero point-based span 3 URL sensor
Example
• Sensor:10 bar (150 psi)
• Upper range value (URL) = 10 bar (150 psi)
Turn down (TD):
• Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)
• Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
TD =
URL
|URV - LRV|
TD =
10 bar (150 psi)
= 2
|5 bar (75 psi) - 0 bar (0 psi)|
In this example, the TD is 2:1. This span is based on the zero point.
1.6 Registered trademarks
is a registered trademark of the IO-Link company group.
Page 8
Basic safety instructions Cerabar PMP23 IO-Link
8 Endress+Hauser
2 Basic safety instructions
2.1 Requirements concerning the staff
The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements:
Trained, qualified specialists: must have a relevant qualification for this specific function and task
Are authorized by the plant owner/operator
Are familiar with federal/national regulations
Before beginning work, the specialist staff must have read and understood the instructions in the Operating Instructions and supplementary documentation as well as in the certificates (depending on the application)
Following instructions and basic conditions
The operating personnel must fulfill the following requirements:
Being instructed and authorized according to the requirements of the task by the facility's owner-operator
Following the instructions in these Operating Instructions
2.2 Designated use
2.2.1 Application and media
The Cerabar is used to measure absolute and gauge pressure in gases, vapors and liquids. The process-wetted materials of the measuring device must have an adequate level of resistance to the media.
The measuring device may be used for the following measurements (process variables)
• in compliance with the limit values specified under "Technical data"
• in compliance with the conditions that are listed in this manual.
Measured process variable
Gauge pressure or absolute pressure
Calculated process variable
Pressure
2.2.2 Incorrect use
The manufacturer is not liable for damage caused by improper or non-designated use.
Verification for borderline cases:
For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of process-wetted materials, but does not accept any warranty or liability.
2.2.3 Residual risks
When in operation, the housing may reach a temperature close to the process temperature.
Danger of burns from contact with surfaces!
For elevated process temperatures, ensure protection against contact to prevent burns.
Page 9
Cerabar PMP23 IO-Link Basic safety instructions
Endress+Hauser 9
2.3 Workplace safety
For work on and with the device:
Wear the required personal protective equipment according to federal/national regulations.
Switch off the supply voltage before connecting the device.
2.4 Operational safety
Risk of injury!
Operate the device in proper technical condition and fail-safe condition only.
The operator is responsible for interference-free operation of the device.
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable dangers.
If, despite this, modifications are required, consult with Endress+Hauser.
Hazardous area
To eliminate the risk of danger to persons or the facility when the device is used in the approval-related area (e.g. pressure equipment safety):
Check the nameplate to verify if the device ordered can be put to its intended use in the approval-related area.
2.5 Product safety
This measuring device is designed in accordance with good engineering practice to meet state-of-the-art safety requirements, has been tested, and left the factory in a condition in which it is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device.
Page 10
Product description Cerabar PMP23 IO-Link
10 Endress+Hauser
3 Product description
3.1 Product design
Overview Position Description
C - 1
A0021987
C - 2
A0027289
C- 1 M12 plug
Housing cap made of plastic
C- 2 M12 plug
IP69: metal housing cap
D
E
A0027227
D E
Housing Process connection (sample illustration)
3.2 Function
3.2.1 Calculating the pressure
Devices with metallic process isolating diaphragm
The process pressure deflects the metal process isolating diaphragm of the sensor and a fill fluid transfers the pressure to a Wheatstone bridge (semiconductor technology). The pressure-dependent change in the bridge output voltage is measured and evaluated.
Page 11
Cerabar PMP23 IO-Link Incoming acceptance and product identification
Endress+Hauser 11
4 Incoming acceptance and product
identification
4.1 Incoming acceptance
A0028673
DELIVERY NOTE
1 = 2
A0016870
Is the order code on the delivery note (1) identical to the order code on the product sticker (2)?
A0022100
A0028673
A0022103
Are the goods undamaged?
A0028673
DELIVERYNOTE
A0022105
Do the data on the nameplate correspond to the order specifications and the delivery note?
If one of these conditions does not apply, please contact your Endress+Hauser sales office.
Page 12
Incoming acceptance and product identification Cerabar PMP23 IO-Link
12 Endress+Hauser
4.2 Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer (www.endress.com/deviceviewer): All information about the measuring device is displayed.
For an overview of the technical documentation provided, enter the serial number from the nameplates in W@M Device Viewer (www.endress.com/deviceviewer)
4.2.1 Manufacturer address
Endress+Hauser GmbH+Co. KG Hauptstraße 1 79689 Maulburg, Germany
Address of the manufacturing plant: See nameplate.
4.2.2 Nameplate
Ser. no.:
Ord. cd.:
Ext. ord. cd.:
D-79689 Maulburg
Made in Germany,
Cerabar
5
1 2
3 4
Date:
TAG:
A0024456
1 Manufacturer's address 2 Device name 3 Order number 4 Serial number 5 Extended order number
4.3 Storage and transport
4.3.1 Storage conditions
Use original packaging.
Store the measuring device in clean and dry conditions and protect from damage caused by shocks (EN 837-2).
Storage temperature range
–40 to +85 °C (–40 to +185 °F)
Page 13
Cerabar PMP23 IO-Link Incoming acceptance and product identification
Endress+Hauser 13
4.3.2 Transporting the product to the measuring point
L
WARNING
Incorrect transport!
Housing and diaphragm may become damaged, and there is a risk of injury!
Transport the measuring device to the measuring point in its original packaging or by the process connection.
Page 14
Installation Cerabar PMP23 IO-Link
14 Endress+Hauser
5 Installation
5.1 Mounting dimensions
For dimensions, see the "Mechanical construction" section in the Technical Information.
5.2 Installation conditions
• Moisture must not penetrate the housing when mounting the device, establishing the electrical connection and during operation.
• For M12 plug made of metal: Do not remove the protection cap (only in IP69) of M12 plug connection until shortly before electrical connection.
• Do not clean or touch process isolating diaphragms with hard and/or pointed objects.
• Do not remove process isolating diaphragm protection until shortly before installation.
• Always tighten the cable entry firmly.
• Point the cable and connector downwards where possible to prevent moisture from entering (e.g. rain or condensation water).
• Protect housing against impact.
• For devices with gauge pressure sensor, the following applies:
NOTICE
If a heated device is cooled in the course of a cleaning process (by cold water, for example), a vacuum develops for a short time causing moisture to penetrate the sensor via the pressure compensation element (1).
Device could be destroyed!
In the event of this happening, mount the device in such a way that the pressure compensation element (1) is pointing downwards at an angle or to the side, if possible.
1
1
1
1
A0022252
5.3 Influence of the installation position
Any orientation is possible. However, the orientation may cause a zero point shift i.e. the measured value does not show zero when the vessel is empty or partially full.
C
A
B
A0024708
Type Process isolating diaphragm
axis is horizontal (A)
Process isolating diaphragm pointing upwards (B)
Process isolating diaphragm pointing downwards (C)
PMP23 Calibration position, no effect Up to +4 mbar (+0.058 psi) Up to –4 mbar (–0.058 psi)
Page 15
Cerabar PMP23 IO-Link Installation
Endress+Hauser 15
5.4 Mounting location
5.4.1 Pressure measurement
Pressure measurement in gases
Mount the device with shutoff device above the tapping point so that any condensate can flow into the process.
1
2
A0021904
1 Device 2 Shutoff device
Pressure measurement in vapors
For pressure measurement in vapors, use a siphon. The siphon reduces the temperature to almost ambient temperature. Mount the device with a shutoff device at the same height as the tapping point.
Advantage: only minor/negligible heat effects on the device.
Note the max. permitted ambient temperature of the transmitter!
1
2
3
A0024395
1 Device 2 Shutoff device 3 Siphon
Pressure measurement in liquids
Mount the device with a shutoff device at the same height as the tapping point.
Page 16
Installation Cerabar PMP23 IO-Link
16 Endress+Hauser
1
2
A0024399
1 Device 2 Shutoff device
5.4.2 Level measurement
• Always install the device below the lowest measuring point.
• Do not install the device at the following positions: – In the filling curtain – In the tank outlet – In the suction area of a pump – Or at a point in the tank which could be affected by pressure pulses from the agitator.
A0024405
5.5 Mounting of the profile seal for universal process
mounting adapter
For details on mounting, see KA00096F/00/A3.
5.6 Post-installation check
 Is the device undamaged (visual inspection)?
Does the device comply with the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature range
• Measuring range
 Are the measuring point identification and labeling correct (visual inspection)?
 Is the device adequately protected against precipitation and direct sunlight?
 Are the securing screws tightened securely?
 Is the pressure compensation element pointing downwards at an angle or to the side?
 To prevent moisture from penetrating, ensure that the connecting cables/plugs are pointing downwards.
Page 17
Cerabar PMP23 IO-Link Electrical connection
Endress+Hauser 17
6 Electrical connection
6.1 Connecting the measuring unit
6.1.1 Terminal assignment
L
WARNING
Risk of injury from the uncontrolled activation of processes!
Switch off the supply voltage before connecting the device.
Make sure that downstream processes are not started unintentionally.
L
WARNING
An incorrect connection compromises electrical safety!
A suitable circuit breaker must be provided for the device in accordance with IEC/ EN61010.
The device must be operated with a 500 mA fine-wire fuse (slow-blow).
Protective circuits against reverse polarity are integrated.
Connect the device in the following order:
1. Check that the supply voltage corresponds to the supply voltage indicated on the nameplate.
2. Connect the device in accordance with the following diagram.
Switch on the supply voltage.
Device M12 plug
PMP23
C/Q L–
L+
2
1
3
4
SIO
IO-Link
A0034006
1 Supply voltage + 2 4-20 mA 3 Supply voltage ­4 C/Q (IO-Link communication or SIO mode)
6.1.2 Supply voltage
Electronic version Device Supply voltage
IO-Link PMP23 10 to 30 V DC
The IO-Link communication is guaranteed only if the supply voltage is at least 18 V.
6.1.3 Current consumption and alarm signal
Number of wires Device Normal operation Alarm signal
1)
3 or 4 PMP23 Maximum current consumption: ≤ 300 mA
1) For MAX alarm (factory setting)
Page 18
Electrical connection Cerabar PMP23 IO-Link
18 Endress+Hauser
6.2 Switching capacity
• Switch status ON: Ia ≤ 250 mA
1)
; switch status OFF: Ia ≤1 mA
• Switch cycles: >10,000,000
• Voltage drop PNP: ≤2 V
• Overload protection: Automatic load testing of switching current; – Max. capacitance load: 14 μF at max. supply voltage (without resistive load) – Max. cycle duration: 0.5 s; min. ton: 4 ms – Periodic disconnection from protective circuit in the event of overcurrent (f = 2 Hz) and
"F804" displayed
6.3 Connection data
6.3.1 Load
In order to guarantee sufficient terminal voltage, a maximum load resistance RL (including line resistance) must not be exceeded depending on the supply voltage UB of the supply unit.
[ ]W
20 30
10
0
1022
587
152
U [V]
1
2
R
R
L
L
max
max
£
-U 6.5V
23mA
B
B
A0031107
1 Power supply 10 to 30 V DC 2 R
Lmax
Maximum load resistance
UBSupply voltage
• Error current is output and "S803" displayed (output: MIN alarm current)
• Periodic checking to establish if it is possible to quit fault state
6.4 Post-connection check
 Is the device or cable undamaged (visual check)?
 Do the cables comply with the requirements ?
 Do the cables have adequate strain relief?
 Are all the cable glands installed, firmly tightened and leak-tight?
 Does the supply voltage match the specifications on the nameplate?
 Is the terminal assignment correct ?
 If required: Has protective ground connection been established ?
1) The SIO mode supports 250 mA, thus deviating from the IO-Link standard.
Page 19
Cerabar PMP23 IO-Link Operation options
Endress+Hauser 19
7 Operation options
7.1 Operation with an operating menu
7.1.1 IO-Link
IO-Link information
IO-Link is a point-to-point connection for communication between the measuring device and an IO-Link master. The measuring device features an IO-Link communication interface type 2 with a second IO function on pin 4. This requires an IO-Link-compatible assembly (IO-Link master) for operation. The IO-Link communication interface enables direct access to the process and diagnostic data. It also provides the option of configuring the measuring device while in operation.
Physical layer, the measuring devices supports the following features:
• IO-Link specification: version 1.1
• IO-Link Smart Sensor Profile 2nd Edition
• SIO mode: yes
• Speed: COM2; 38.4 kBaud
• Minimum cycle time: 2.5 msec.
• Process data width: 24 bit
• IO-Link data storage: yes
• Block configuration: no
IO-Link download
http://www.endress.com/download
• Select "Software" as the media type.
• Select "Device Driver" as the software type. Select IO-Link (IODD).
• In the "Text Search" field enter the device name.
https://ioddfinder.io-link.com/
Search by – Manufacturer – Article number – Product type
7.1.2 Structure of the operating menu
The menu structure has been implemented according to VDMA 24574-1 and complemented by Endress+Hauser-specific menu items.
For an overview of the operating menu, see →  42
Page 20
System integration Cerabar PMP23 IO-Link
20 Endress+Hauser
8 System integration
8.1 Process data
The measuring device has a current output and a switch output. The status of the switch output is transmitted in the form of process data via IO-Link.
• In the SIO mode, switch output 1 is switched at pin 4 of the M12 plug. In the IO-Link communication mode, this pin is reserved exclusively for communication.
• The current output at pin 2 of the M12 plug is always active or can be optionally deactivated via IO-Link.
• The device's process data are transmitted cyclically in 24-bit chunks.
Bit 0 (LSB) 1 ... 20 21 (MSB) 22 23
Measuring device Pressure value OU1 res.
Bit 23 is reserved. Bit 22 provides the status of the switch output.
Here, 1 or DC 24 V corresponds to the logical "closed" state on the switch output. The remaining 22 bits contain the analog raw measured value of the device. This value has yet to be scaled by the target system to the nominal operating range of the existing measuring device.
Bit Process value Value range
22 OU1 0 = open
1 = closed
0 to 21 Raw value Int22
The decimal separator must be determined using a factor that depends on the unit in question. The following units are available:
• bar: 0.001
• kPa: 0.1
• MPa: 0.0001
• psi: 0.01
Examples:
Pressure value Transmitted Scaled with factor
-320 mbar -320 -0.32
22 bar 22000 22
133 Pa 1330 133
665 psi 66500 665
399.5 bar 399500 399.5
8.2 Reading out and writing device data (ISDU – Indexed
Service Data Unit)
Device data are always exchanged acyclically and at the request of the IO-Link master. Using the device data, the following parameter values or device statuses can be read out:
Page 21
Cerabar PMP23 IO-Link System integration
Endress+Hauser 21
8.2.1 Endress+Hauser-specific device data
Designation ISDU
(dec)
ISDU (hex)
Size (byte)
Data type
Access Default
value
Value range Offset /
Gradient
Data storage
Range limits
Extended Ordercode 259 0x0103 60 String ro
ENP_VERSION 257 0x0101 16 String ro 36587
Simulation switch output (OU1)
85 0x0055 1 unit r/w 0 ~ off
1 ~ low 2 ~ high
No
Simulation current output (OU2)
66 0x0042 1 unit r/w 0 ~ off
4 ~ 4 mA 5 ~ 8 mA 6 ~ 12 mA 7 ~16 mA 8 ~ 20 mA 9 ~ 21.95 mA otherwise 3.5 mA
No
Unit changeover (UNI) 67 0x0043 1 unit r/w 0 ~ bar
1 ~ kPa 2 ~ MPa 3 ~ psi
Yes
Zero point configuration (ZRO)
68 0x0044 4 int r/w 0 as 00.00%
Default 0.00%
Yes
Zero point adoption (GTZ) 69 0x0045 1 unit w No
Damping (TAU) 70 0x0046 2 unit r/w 20 in 000.0 sec
Default 2.0 sec
0.1 Yes
Value for 4 mA (STL) 71 0x0047 4 int r/w 0 as 00.00%
Default 0.00%
bar: 0 / 0.001 kPa: 0 / 0.1 MPa: 0 /
0.0001 psi: 0 / 0.01
Yes
Value for 20 mA (STU) 72 0x0048 4 int r/w 10000 as 00.00%
Default 100.00%
bar: 0 / 0.001 kPa: 0 / 0.1 MPa: 0 /
0.0001 psi: 0 / 0.01
Yes
Pressure applied for 4mA (GTL)
73 0x0049 1 unit w No
Pressure applied for 20mA (GTU)
74 0x004A 1 unit w No
Alarm current (FCU) 75 0x004B 1 unit r/w MAX 0 ~ MIN
1 ~ MAX
Yes
Current output (I) 76 0x004C 1 unit r/w ON 0 ~ ON
1 ~ OFF
Yes
Switch point value / Upper value for pressure window, output 1 (SP1 / FH1)
77 0x004D 4 int r/w 9000 as 00.00%
Default 90%
bar: 0 / 0.001 kPa: 0 / 0.1 MPa: 0 /
0.0001 psi: 0 / 0.01
Yes
Switchback point value / Lower value for pressure window, output 1 (rP1 / FL1)
78 0x004E 4 int r/w 1000 as 00.00%
Default 10%
bar: 0 / 0.001 kPa: 0 / 0.1 MPa: 0 /
0.0001 psi: 0 / 0.01
Yes
Switching delay time, Output 1 (dS1)
79 0x004F 2 unit r/w 0 in 00.00 sec 0 / 0.01 Yes
Switchback delay time, Output 1 (dR1)
80 0x0050 2 unit r/w 0 in 00.00 sec 0 / 0.01 Yes
Page 22
System integration Cerabar PMP23 IO-Link
22 Endress+Hauser
Designation ISDU
(dec)
ISDU (hex)
Size (byte)
Data type
Access Default
value
Value range Offset /
Gradient
Data storage
Range limits
Output 1 (Ou1) 81 0x0051 1 unit r/w HNO 0 ~ HNO
1)
1 ~ HNC
1)
2 ~ FNO
1)
3 ~ FNC
1)
Yes
Hi Max value (maximum indicator)
82 0x0052 4 int ro No
Lo Min value (minimum indicator)
83 0x0053 4 int ro No
Revisioncounter (RVC) 84 0x0054 2 unit ro No
1) For an explanation of the abbreviations, see the parameter description →  32
8.2.2 IO-Link-specific device data
Designation ISDU (dec) ISDU (hex) Size (byte) Data type Access Default value Data storage
Serial number 21 0x0015 max. 16 String ro
Firmware version 23 0x0017 max. 64 String ro
ProductID 19 0x0013 max. 64 String ro PMP23
ProductName 18 0x0012 max. 64 String ro Cerabar
ProductText 20 0x0014 max. 64 String ro Absolute and gauge pressure
VendorName 16 0x0010 max. 64 String ro Endress+Hauser
VendorText 17 0x0011 max. 64 String ro People for Process Automation
Hardware Revision 22 0x0016 max. 64 String ro
Application Specific Tag 24 0x0018 32 String r/w
Device Type 256 0x0100 2 Uinteger16 ro 0x92FF
Actual Diagnostics (STA) 260 0x0104 4 String ro No
Last Diagnostic (LST) 261 0x0105 4 String ro No
8.2.3 System commands
Designation ISDU (dec) ISDU (hex) Value range Access
Reset to factory settings (RES) 2 0x0002 130 w
Device Access Locks.Data Storage Lock 12 0x000C 0 ~ False
2 ~ True
rw
8.3 Overview of diagnostic events
→  38
Page 23
Cerabar PMP23 IO-Link Commissioning
Endress+Hauser 23
9 Commissioning
If an existing configuration is changed, measuring operation continues! The new or modified entries are only accepted once the setting has been made.
L
WARNING
Risk of injury from the uncontrolled activation of processes!
Make sure that downstream processes are not started unintentionally.
L
WARNING
If a pressure smaller than the minimum permitted pressure or greater than the maximum permitted pressure is present at the device, the following messages are output in succession:
S140
F270
9.1 Function check
Before commissioning your measuring point, ensure that the post-installation and post­connection check have been performed:
• "Post-installation check" checklist →  16
• "Post-connection check" checklist →  18
9.2 Commissioning with an operating menu
Commissioning comprises the following steps:
• Configure pressure measurement →  24
• If necessary, perform position adjustment→  26
• If necessary, configure process monitoring →  28
Page 24
Commissioning Cerabar PMP23 IO-Link
24 Endress+Hauser
9.3 Configuring pressure measurement
9.3.1 Calibration without reference pressure (dry calibration =
calibration without medium)
Example:
In this example, a device with a 400 mbar (6 psi) sensor is configured for the measuring range 0 to 300 mbar (0 to 4.4 psi).
The following values should be assigned:
• 0 mbar = 4 mA value
• 300 mbar (4.4 psi) = 20 mA value
Prerequisite:
This is a theoretical calibration, i.e. the pressure values for the lower and upper range are known. It is not necessary to apply pressure.
Due to the orientation of the device, there may be pressure shifts in the measured value, i.e. the measured value is not zero in a pressureless condition. For information on how to perform position adjustment, see the "Performing position adjustment" section →  26.
For a description of the parameters mentioned and possible error messages, see the "Description of device parameters" section →  43 and →  36.
Performing the configuration
1. Select a pressure unit, here "bar" for example, via the Unit changeover (UNI) parameter. Menu path: Application → Sensor → Unit changeover (UNI)
2. Select Value for 4 mA (STL) parameter. Menu path: Application → Current output (OU2) → Value for 4 mA (STL). Enter the value (0 bar (0 psi)) and confirm.
 This pressure value is assigned to the lower current value (4 mA).
3. Select Value for 20 mA (STU) parameter. Menu path: Application → Current output (OU2) → Value for 20 mA (STU). Enter the value (300 mbar (4.4 psi)) and confirm.
 This pressure value is assigned to the upper current value (20 mA).
The measuring range is configured for 0 to 300 mbar (0 to 4.4 psi).
Page 25
Cerabar PMP23 IO-Link Commissioning
Endress+Hauser 25
9.3.2 Calibration with reference pressure (wet calibration = calibration with medium)
Example:
In this example, a device with a 400 mbar (6 psi) sensor is configured for the measuring range 0 to 300 mbar (0 to 4.4 psi).
The following values should be assigned:
• 0 mbar = 4 mA value
• 300 mbar (4.4 psi) = 20 mA value
Prerequisite:
The pressure values 0 mbar and 300 mbar (4.4 psi) can be specified. The device is already mounted, for example.
Due to the orientation of the device, there may be pressure shifts in the measured value, i.e. the measured value is not zero in a pressureless condition. For information on how to perform position adjustment, see the "Performing position adjustment" section →  26.
For a description of the parameters mentioned and possible error messages, see the "Description of device parameters" section →  43 and →  36.
Performing the configuration
1. Select a pressure unit, here "bar" for example, via the Unit changeover (UNI) parameter. Menu path: Application → Sensor → Unit changeover (UNI)
2. The pressure for the LRV (4 mA value) is present at the device, here 0 bar (0 psi) for example. Select Pressure applied for 4mA (GTL) parameter. Menu path: Application → Current output (OU2) → Pressure applied for 4mA (GTL). The selection is confirmed by pressing "Get Lower Limit".
 The pressure value present is assigned to the lower current value (4 mA).
3. The pressure for the URV (20 mA value) is present at the device, here 300 mbar (4.4 psi)for example. Select Pressure applied for 20mA (GTU) parameter. Menu path: Application → Current output (OU2) → Pressure applied for 20mA (GTU). The selection is confirmed by pressing "Get Lower Limit".
 The pressure value present is assigned to the upper current value (20 mA).
The measuring range is configured for 0 to 300 mbar (0 to 4.4 psi).
Page 26
Commissioning Cerabar PMP23 IO-Link
26 Endress+Hauser
9.4 Performing position adjustment
Zero point configuration (ZRO)
Navigation Application → Sensor → Zero point configuration (ZRO)
Description (typically absolute pressure sensor)
A pressure shift resulting from the orientation of the device can be corrected by the position adjustment. The pressure difference between zero (set point) and the measured pressure must be known.
Prerequisite An offset is possible (parallel shifting of the sensor characteristic) to correct the
orientation and any zero point drift. The set value of the parameter is subtracted from the "raw measured value". The requirement to be able to perform a zero point shift without changing the span is met with the offset function. Maximum offset value = ± 20 % of the sensor nominal range. If an offset value is entered that shifts the span beyond the physical limits of the sensor, the value is admitted but a warning message is generated and displayed via IO-Link. The warning message only disappears when the span is within the sensor limits, taking the offset value currently configured into consideration.
The sensor can
• be operated in a physically unfavorable range, i.e. outside its specifications, or
• be operated by making appropriate corrections to the offset or span.
Raw measured value – (manual offset) = display value (measured value)
Example • Measured value0.002 mbar (0.029 psi)
• Set the measured value in the parameter to 0.002.
• Measured value (after pos. zero adjust) = 0.000 mbar (0 psi)
• The current value is also corrected.
Note Setting in increments of 0.001. As the value is entered numerically, the increment
depends on the measuring range
Options No selection. The user is free to edit the values.
Factory setting 0
Zero point adoption (GTZ)
Navigation Application → Sensor → Zero point adoption (GTZ)
Description (typically gauge pressure sensor)
A pressure shift resulting from the orientation of the device can be corrected by the position adjustment. The pressure difference between zero (set point) and the measured pressure need not be known.
Page 27
Cerabar PMP23 IO-Link Commissioning
Endress+Hauser 27
Prerequisite The pressure value present is automatically adopted as the zero point.
An offset is possible (parallel shifting of the sensor characteristic) to correct the orientation and any zero point drift. The accepted value of the parameter is subtracted from the "raw measured value". The requirement to be able to perform a zero point shift without changing the span is met with the offset function. Maximum offset value = ± 20 % of the sensor nominal range. If an offset value is entered that shifts the span beyond the physical limits of the sensor, the value is admitted but a warning message is generated and displayed via IO-Link. The warning message only disappears when the span is within the sensor limits, taking the offset value currently configured into consideration.
The sensor can
• be operated in a physically unfavorable range, i.e. outside its specifications, or
• be operated by making appropriate corrections to the offset or span.
Raw measured value – (manual offset) = display value (measured value)
Example 1 • Measured value0.002 mbar (0.029 psi)
• Use the Zero point adoption (GTZ) parameter to correct the measured value with the value, e.g. 0.002 mbar (0.029 psi). This means that you are assigning the value 0.000 (0 psi) to the pressure present.
• Measured value (after pos. zero adjust) = 0.000 mbar (0 psi)
• The current value is also corrected.
• If necessary, check and correct switch points and span settings.
Example 2 Sensor measuring range: –0.4 to +0.4 bar (–6 to +6 psi) (SP1 = 0.4 bar (6 psi); STU =
0.4 bar (6 psi))
• Measured value0.08 bar (1.2 psi)
• Use the Zero point adoption (GTZ) parameter to correct the measured value with the value, e.g. 0.08 bar (1.2 psi). This means that you are assigning the value 0 mbar (0 psi) to the pressure present.
• Measured value (after pos. zero adjust) = 0 mbar (0 psi)
• The current value is also corrected.
• Warnings C431 or C432 appear because the value 0 bar (0 psi) was assigned to the real value of 0.08 bar (1.2 psi) present and the sensor measuring range was thus exceeded by ± 20%. SP1 and STU values must be readjusted downwards by 0.08 bar (1.2 psi).
Page 28
Commissioning Cerabar PMP23 IO-Link
28 Endress+Hauser
9.5 Configuring process monitoring
To monitor the process, it is possible to specify a pressure range which is monitored by the limit switch. Both monitoring versions are described below. The monitoring function allows the user to define optimum ranges for the process (with high yields etc.) and deploy limit switches to monitor the ranges.
9.5.1 Digital process monitoring (switch output)
It is possible to select defined switch points and switchback points which act as NO or NC contacts depending on whether a window function or hysteresis function is configured .
Function Selection Output Abbreviation for
operation
Hysteresis Hysteresis normally open Closing HNO
Hysteresis Hysteresis normally closed NC contact HNC
Window Window normally open Closing FNO
Window Window normally closed NC contact FNC
If the device is restarted within the given hysteresis, the switch output is open (0 V present at the output).
9.5.2 Analog process monitoring (4 to 20 mA output)
• The 3.8 to 20.5 mA signal range is controlled according to NAMUR NE 43.
• The alarm current and current simulation are exceptions: – If the defined limit is exceeded, the device continues measuring linearly. The output
current increases linearly up to 20.5 mA and holds the value until the measured value drops below 20.5 mA again or the device detects an error →  36.
– If the defined limit is undershot, the device continues measuring linearly. The output
current decreases linearly to 3.8 mA and holds the value until the measured value rises above 3.8 mA again or the device detects an error →  36.
Page 29
Cerabar PMP23 IO-Link Commissioning
Endress+Hauser 29
9.5.3 Switch output (OU1)
Behavior of switch output
Switch point value / Upper value for pressure window, output 1 (SP1 / FH1) Switchback point value / Lower value for pressure window, output 1 (RP1 / FL1)
Navigation Application → Switch output (OU1) → Switch point value / Upper value for pressure
window, output 1 (SP1 / FH1) Application → Switch output (OU1) → Switchback point value / Lower value for pressure window, output 1 (RP1 / FL1)
Prerequisite The following functions are available only if a hysteresis function has been configured for
the switch output (output 1 (Ou1)).
Description of behavior of SP1 / RP1
The hysteresis is implemented using the SP1 and RP1 parameters. Since the parameter settings depend on one another, the parameters are described all together. The switch point "SP1" and switchback point "RP1" can be defined with these functions (e.g. for pump control). When the set switch point "SP1" is reached (with increasing pressure), an electrical signal change takes place at the switch output. When the set switchback point "RP1" is reached (with decreasing pressure), an electrical signal change takes place at the switch output. The difference between the value of switch point "SP1" and the value of switchback point "RP1" is known as the hysteresis. The configured value for the switch point "SP1" must be greater than the switchback point "RP1"! A diagnostic message is displayed if a switch point "SP1" is entered that is ≤ the switchback point "RP1". While it is possible to make this entry, it does not take effect in the device. The entry must be corrected!
1
2
0
SP1
RP1
0
HNO
p
t
1
HNC
A0034025
0 0-signal. Output open in quiescent state. 1 1-signal. Output closed in quiescent state. 2 Hysteresis SP1 Switch point RP1 Switchback point HNO Closing HNC NC contact
To prevent switch-on and switch-off if values are around the switch point "SP1" or switchback point "RP1", a delay can be set for the relevant points. In this regard, see the Switching delay time, output 1 (dS1) and Switchback delay time, output 1 (dR1) parameter descriptions.
Page 30
Commissioning Cerabar PMP23 IO-Link
30 Endress+Hauser
Prerequisite The following functions are available only if a window function has been configured for
the switch output (output 1 (Ou1)).
Description of behavior of FH1 / FL1
The window function is implemented using the FH1 and FL1 parameters. Since the parameter settings depend on one another, the parameters are described all together. The upper value of the pressure window "FH1" and the lower value of the pressure window "FL1" can be defined with these functions (e.g. for monitoring a certain pressure range). When the lower value of the pressure window "FL1" is reached (with increasing or decreasing pressure), an electrical signal change takes place at the switch output. When the upper value of the pressure window "FH1" is reached (with increasing or decreasing pressure), an electrical signal change takes place at the switch output. The difference between the upper value of the pressure window "FH1" and the lower value of the pressure window "FL1" is known as the pressure window. The upper value of the pressure window "FH1" must be greater than the lower value of the pressure window "FL1"! A diagnostic message is displayed if the upper value entered for the pressure window "FH1" is less than the lower value of the pressure window "FL1". While it is possible to make this entry, it does not take effect in the device. The entry must be corrected!
1
2
0
FH1
FL1
0
FNO
p
t
1
FNC
A0034026
0 0-signal. Output open in quiescent state. 1 1-signal. Output closed in quiescent state. 2 Pressure window (difference between the value of the high window "FH1" and the low window "FL1") FNO Closing FNC NC contact FH1 Upper value of the pressure window FL1 Lower value of the pressure window
Options No selection. The user is free to edit the values.
Factory setting Factory setting (if no customer-specific setting is ordered):
Switch point SP1 / FH1: 90%; switchback point RP1 / FL1: 10%
Page 31
Cerabar PMP23 IO-Link Commissioning
Endress+Hauser 31
Switching delay
Switching delay time, output 1 (dS1) Switchback delay time, output 1 (dR1)
Note The switching delay time/switchback delay time function is implemented using the dS1
and dR1 parameters. Since the parameter settings depend on one another, the parameters are described all together.
• dS1 = switching delay time, output 1
• dR1 = switchback delay time, output 1
Navigation Application → Switch output (OU1) → Switching delay time, output 1 (dS1)
Application → Switch output (OU1) → Switchback delay time, output 1 (dR1)
Description To prevent switch-on and switch-off if values are around the switch point "SP1" or the
switchback point "RP1", a delay in a range of 0 – 50 seconds, to two decimal places, can be set for the individual points. If the measured value leaves the switching range during the delay time, the delay time starts again from scratch.
Example • SP1 = 2 bar (29 psi)
• RP1 = 1 bar (14.5 psi)
• dS1 = 5 seconds
• dR1 = 2 seconds
dS1/: ≥2 bar (29 psi) must be present for at least 5 seconds for SP1 to become active. dR1/: ≥1 bar (14.5 psi) must be present for at least 2 seconds for RP1 to become active.
2
1
0
SP1
RP1
dS1
dS1 dR1
0
HNO
p
t
1
HNC
A0034027
0 0-signal. Output open in quiescent state. 1 1-signal. Output closed in quiescent state. 2 Hysteresis (difference between the value of the switch point "SP1" and the value of the switchback point "RP1") HNO Closing HNC NC contact SP1 Switch point 1 RP1 Switchback point 1 dS1 Set time for which the specific switch point must be reached continuously without interruption until an
electrical signal change takes place.
dR1 Set time for which the specific switchback point must be reached continuously without interruption until an
electrical signal change takes place.
Page 32
Commissioning Cerabar PMP23 IO-Link
32 Endress+Hauser
Switch on value 0
Input range 0.00 - 50.00 seconds
Factory setting 0
Output 1 (OU1)
Navigation Application → Switch output (OU1) → Output 1 (OU1)
Description • Hysteresis normally open (HNO):
The switch output is specified as a NO contact with hysteresis properties.
• Hysteresis normally closed (HNC): The switch output is specified as an NC contact with hysteresis properties.
• Window normally open (FNO): The switch output is specified as a NO contact with window properties.
• Window normally closed (FNC): The switch output is specified as an NC contact with window properties.
Options • Hysteresis normally open (HNO)
• Hysteresis normally closed (HNC)
• Window normally open (FNO)
• Window normally closed (FNC)
Factory setting Hysteresis normally open (HNO) or as per order specifications
9.6 Current output
Current output (I)
Navigation Application → Current output (OU2) → Current output (I)
Description Switches the current output on or off.
Options • ON
• OFF
Factory setting ON
Value for 4 mA (STL)
Navigation Application → Current output (OU2) → Value for 4 mA (STL)
Description Assignment of the pressure value which should correspond to the 4 mA value.
It is possible to invert the current output. To do so, assign the pressure upper range value to the lower measuring current.
Page 33
Cerabar PMP23 IO-Link Commissioning
Endress+Hauser 33
Note Enter the value for 4 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the measuring range).
Options No selection. The user is free to edit the values.
Factory setting 0.0 or as per order specifications
Value for 20 mA (STU)
Navigation Application → Current output (OU2) → Value for 20 mA (STU)
Description Assignment of the pressure value which should correspond to the 20 mA value.
It is possible to invert the current output. To do so, assign the pressure lower range value to the upper measuring current.
Note Enter the value for 20 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the measuring range).
Options No selection. The user is free to edit the values.
Factory setting Upper measuring limit or as per order specifications.
Pressure applied for 4mA (GTL)
Navigation Application → Current output (OU2) → Pressure applied for 4mA (GTL)
Description The pressure value present is automatically adopted for the 4 mA current signal.
Parameter for which the current range can be assigned to any section of the nominal range. This occurs by assigning the pressure lower range value to the lower measuring current and the pressure upper range value to the upper measuring current. The pressure lower range value and upper range value can be configured independently of one another so the pressure measuring span does not remain constant. The LRV and URV pressure measuring span can be edited over the entire sensor range. An invalid TD value is indicated by diagnostic message S510. An invalid position offset is indicated by diagnostic message C431. The editing operation cannot result in the device being operated outside the minimum and maximum sensor limits.
Incorrect entries are declined as indicated by the following messages, and the last valid value prior to the change is used again:
• Parameter value above limit (0x8031)
• Parameter value below limit (0x8032)
The measured value currently present is accepted as the value for 4mA anywhere within the measuring range. The sensor characteristic curve is shifted such that the pressure present becomes the zero value.
Pressure applied for 20mA (GTU)
Page 34
Commissioning Cerabar PMP23 IO-Link
34 Endress+Hauser
Navigation Application → Current output (OU2) → Pressure applied for 20mA (GTU)
Description The pressure value present is automatically adopted for the 20 mA current signal.
Parameter for which the current range can be assigned to any section of the nominal range. This occurs by assigning the pressure lower range value to the lower measuring current and the pressure upper range value to the upper measuring current. The pressure lower range value and upper range value can be configured independently of one another so the pressure measuring span does not remain constant. The LRV and URV pressure measuring span can be edited over the entire sensor range. An invalid TD value is indicated by diagnostic message S510. An invalid position offset is indicated by diagnostic message C431. The editing operation cannot result in the device being operated outside the minimum and maximum sensor limits. Incorrect entries are declined, and the last valid value prior to the change is used again. The measured value currently present is accepted as the value for 20 mA anywhere within the measuring range. There is a parallel shift of the sensor characteristic so that the pressure present becomes the max value.
Page 35
Cerabar PMP23 IO-Link Commissioning
Endress+Hauser 35
9.7 Application examples
9.7.1 Compressor control with hysteresis function
Example: The compressor is started when the pressure drops below a certain value. The compressor is switched off when a certain value is exceeded.
1. Set the switch point to 2 bar (29 psi)
2. Set the switchback point to 1 bar (14.5 psi)
3. Configure the switch output as an "NC contact" (HNC function)
The compressor is controlled by the defined settings.
9.7.2 Pump control with hysteresis function
Example: The pump should switch on when 2 bar (29 psi) is reached (increasing pressure) and switch off when 1 bar (14.5 psi) is reached (decreasing pressure).
1. Set the switch point to 2 bar (29 psi)
2. Set the switchback point to 1 bar (14.5 psi)
3. Configure the switch output as an "NO contact" (HNO function)
The pump is controlled by the defined settings.
Page 36
Diagnostics and troubleshooting Cerabar PMP23 IO-Link
36 Endress+Hauser
10 Diagnostics and troubleshooting
10.1 Troubleshooting
If an illegal configuration exists in the device, the device switches to the failsafe mode.
Example:
• The diagnostic message "C485" is displayed via IO-Link.
• The device is in the simulation mode.
• If the device configuration is corrected, e.g. by resetting the device, the device quits the fault state and switches to the measuring mode.
General errors
Problem Possible cause Solution
Device does not respond Supply voltage does not match the value
indicated on the nameplate.
Apply correct voltage.
The polarity of the supply voltage is wrong. Correct the polarity.
Connecting cables are not in contact with the terminals.
Check for electrical contact between cables and correct.
No communication • Communication cable not connected.
• Communication cable incorrectly attached to device.
• Communication cable incorrectly attached to the IO-Link master.
Check wiring and cables.
Output current ≤ 3.6 mA
Signal line is not wired correctly. Check wiring.
No transmission of process data
There is an error in the device. Correct errors that are
displayed as a diagnostic event→  38.
Page 37
Cerabar PMP23 IO-Link Diagnostics and troubleshooting
Endress+Hauser 37
10.2 Diagnostic events
10.2.1 Diagnostic message
Faults that are detected by the device's self-monitoring system are displayed as a diagnostic message via IO-Link.
Status signals
The table →  38 lists the messages that may occur. The Actual Diagnostic (STA) parameter displays the message with the highest priority. The device has four different status information codes according to NAMUR NE107:
A0013956
"Failure"
A device error has occurred. The measured value is no longer valid.
A0013957
"Maintenance required"
Maintenance is required. The measured value remains valid.
A0013959
"Function check"
The device is in the service mode (e. g. during a simulation).
A0013958
"Out of specification"
The device is operated:
• Outside its technical specifications (e. g. during warmup or cleaning process)
• Outside the parameter configuration undertaken by the user (e. g. level outside of configured span)
Diagnostic event and event text
The fault can be identified by means of the diagnostic event.
Diagnostic event
Status signal Event number
Example
A0013959
469
If two or more diagnostic events are pending simultaneously, only the diagnostic message with the highest priority is shown.
The last diagnostic message is displayed - see Last Diagnostic (LST) in the Diagnosis submenu →  43.
Page 38
Diagnostics and troubleshooting Cerabar PMP23 IO-Link
38 Endress+Hauser
10.2.2 Overview of diagnostic events
Status
signal/
Diagnostic
event
Diagnostic behavior
EventCode Event text Cause Corrective measure
S140 Warning 0x180F Sensor signal outside
of permitted ranges
Overpressure or low pressure present
Operate device in the specified measuring range
S140 Warning 0x180F Sensor signal outside
of permitted ranges
Sensor defective Replace device
F270
1) 2)
Problem 0x1800 Overpressure/low
pressure
Overpressure or low pressure present
• Check the process pressure
• Check sensor range
• Restart device
F270
1) 2)
Problem 0x1800 Defect in electronics/
sensor
Defect in electronics/sensor Replace device
C431
3)
Warning 0x1805 Invalid position
adjustment (Current output)
The adjustment performed would cause the sensor nominal range to be exceeded or undershot.
Position adjustment + parameter of the current output must be within the sensor nominal range
• Check position adjustment (see Zero point configuration (ZRO) parameter)
• Check measuring range (see Value for 20 mA (STU) and Value for 4 mA (STL) parameters)
C432 Warning 0x1806 Invalid position
adjustment (Switching output)
The adjustment performed causes the switch points to be outside the sensor nominal range.
Position adjustment + parameter of the hysteresis and window function must be within the sensor nominal range
• Check position adjustment (see Zero point configuration (ZRO) parameter)
• Check the switch point, switchback point for hysteresis and window function
F437 Problem 0x1810 Incompatible
configuration
Invalid device configuration • Restart device
• Reset device
• Replace device
C469 Problem 0x1803 Switch points output
violated
Switch point ≤ switchback point Check switch points at output
C485 Warning 0x8C01
4)
Simulation active During simulation of the switch
output or current output, the device issues a warning message.
Switch off simulation.
S510 Problem 0x1802 Turn down violated A change in the span results in a
violation of the turn down (max. TD 5:1) Values for calibration (lower range value and upper range value) are too close together
• Operate device in the specified measuring range
• Check the measuring range
S803 Problem 0x1804 Current loop Impedance of load resistance at
analog output is too high
• Check the cabling and load at the current output.
• If the current output is not required, switch the current output off via the configuration.
S803 Problem 0x1804 Current output not
connected
Current output not connected • Connect current output with load.
• If the current output is not required, switch the current output off via the configuration.
F804 Problem - Overload at switch
output
Load current > 250 mA Increase load resistance at switch output
Page 39
Cerabar PMP23 IO-Link Diagnostics and troubleshooting
Endress+Hauser 39
Status
signal/
Diagnostic
event
Diagnostic behavior
EventCode Event text Cause Corrective measure
F804 Problem - Overload at switch
output
Switch output defective • Check output circuit
• Replace device
S971 Warning 0x1811 Measured value is
outside sensor range
The current is outside the permitted range 3.8 to 20.5 mA. The present pressure value is outside the configured measuring range (but within the sensor range, if applicable).
Operate the device within the set span
1) The switch output is open and the current output adopts the configured alarm current. Therefore, errors affecting the switch output are not displayed since the switch output is in the safe state.
2) The device outputs an error current of 0 mA if an internal communication error occurs. In all other cases the device returns the configured error current.
3) If no remedial measures are taken, the warning messages are displayed following a device restart if configuration (span, switch points and offset) is performed with a gauge pressure device and readings are > URL + 10 % or < LRL + 5 % and with an absolute pressure device and readings are > URL + 10% or < LRL.
4) EventCode as per IO-Link standard 1.1
10.3 Behavior of the device in the event of a fault
The device displays warnings and faults via I/O-Link. All the device warnings and faults are for information purposes only and do not have a safety function. The errors diagnosed by the device are displayed via IO-Link in accordance with NE107. In accordance with the diagnostic message, the device behaves as per a warning or fault condition. It is necessary to distinguish between the following types of errors here:
• Warning: – The device continues measuring if this type of error occurs. The output signal is not
affected (exception: simulation is active).
– The switch output remains in the state defined by the switch points.
• Fault: – The device does not continue measuring if this type of error occurs. The output signal
adopts its fault state (value in the event of an error - see the following section). – The fault state is displayed via IO-Link. – The switch output changes to the "open" state. – For the analog output option, an error is signaled with the configured alarm current
behavior.
10.4 Behavior of current output in the event of a fault
The behavior of the current output in the event of a fault is regulated in accordance with NAMUR NE43.
The behavior of the current output in the event of faults is defined in the following parameters:
Alarm current FCU "MIN": Lower alarm current (≤3.6 mA) (optional, see the following table)
Alarm current FCU "MAX" (factory setting): Upper alarm current (≥21 mA)
• The selected alarm current is used for all errors.
• Errors and warning messages are displayed via IO-Link.
• It is not possible to acknowledge errors and warnings. The relevant message disappears if the event is no longer pending.
• The failsafe mode can be changed directly when a device is running (see the following table).
Page 40
Maintenance Cerabar PMP23 IO-Link
40 Endress+Hauser
Changing the failsafe mode After writing to the device
from MAX to MIN active immediately
from MIN to MAX active immediately
10.4.1 alarm current
Device Designation Option
PMP23 Adjusted min. alarm current IA
1)
1) Product Configurator order code for "Service"
10.5 Resetting to factory settings (reset)
See Reset to factory settings (RES) parameter description→  55.
11 Maintenance
No special maintenance work is required.
Keep the pressure compensation element (1) free from contamination.
1
A0022141
11.1 Exterior cleaning
Please note the following points when cleaning the device:
• The cleaning agents used should not corrode the surface and the seals.
• Mechanical damage to the process isolating diaphragm, e.g. due to sharp objects, must be avoided.
• Observe the degree of protection of the device. See the nameplate if necessary →  12.
Page 41
Cerabar PMP23 IO-Link Repairs
Endress+Hauser 41
12 Repairs
12.1 General notes
12.1.1 Repair concept
Repairs are not possible.
12.2 Return
The measuring device must be returned if the wrong device has been ordered or delivered.
As an ISO-certified company and also due to legal regulations, Endress+Hauser is obliged to follow certain procedures when handling any returned products that have been in contact with medium. To ensure swift, safe and professional device returns, please read the return procedures and conditions on the Endress+Hauser website at
www.services.endress.com/return-material
12.3 Disposal
When disposing, separate and recycle the device components based on the materials.
Page 42
Overview of the operating menu Cerabar PMP23 IO-Link
42 Endress+Hauser
13 Overview of the operating menu
Depending on the parameter configuration, not all submenus and parameters are available. Information on this can be found in the parameter description under "Prerequisite".
IO-Link Level 1 Level 2 Level 3 Details
Identification Extended Ordercode →  43
ENP_VERSION →  43
Application Specific Tag →  43
Diagnosis Actual Diagnostics (STA) →  43
Last Diagnostic (LST) →  43
Simulation Switch Output (OU1) →  44
Simulation Current Output (OU2) →  44
Parameter Application Sensor Unit changeover (UNI) →  45
Zero point configuration (ZRO) →  26
Zero point adoption (GTZ) →  26
Damping (TAU) →  47
Current output (OU2) Value for 4 mA (STL) →  32
Value for 20 mA (STU) →  33
Pressure applied for 4mA (GTL) →  33
Pressure applied for 20mA (GTU) →  33
Alarm current (FCU) →  49
Current output (I) →  32
Switch output (OU1) Switch point value / Upper value for pressure
window, output 1 (SP1 / FH1)
→  29
Switchback point value / Lower value for pressure window, output 1 (RP1 / FL1)
→  29
Switching delay time, output 1 (dS1) →  31
Switchback delay time, output 1 (dR1) →  31
Output 1 (OU1) →  32
System HI Max value
(maximum indicator)
→  55
LO Min value (minimum indicator)
→  55
Revisioncounter (RVC) →  55
Reset to factory settings (RES) →  55
Device Access Locks.Data Storage Lock →  56
Observation Pressure →  56
Switch State Output (OU1) →  56
Page 43
Cerabar PMP23 IO-Link Description of device parameters
Endress+Hauser 43
14 Description of device parameters
14.1 Identification
Extended ordercode
Navigation Identification → Extended ordercode
Description Used to replace the device.
Displays the extended order code (max. 60 alphanumeric characters).
Factory setting As per order specifications
ENP_VERSION
Navigation Identification → ENP_VERSION
Description Displays the ENP version (ENP: electronic name plate)
Application Specific Tag
Navigation Identification → Application Specific Tag
Description Used for unique identification of device in the field.
Enter device tag (max. 32 alphanumeric characters).
Factory setting As per order specifications
14.2 Diagnostics
Actual Diagnostics (STA)
Navigation Diagnosis → Actual Diagnostics (STA)
Description Displays the current device status.
Last Diagnostic (LST)
Navigation Diagnosis → Last Diagnostic (LST)
Description Displays the latest device status (error or warning) that was rectified during operation.
Page 44
Description of device parameters Cerabar PMP23 IO-Link
44 Endress+Hauser
Simulation Switch Output (OU1)
Navigation Diagnosis → Simulation Switch Output (OU1)
Description The simulation affects the process data only. It does not affect the physical switch output.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user that the device is in the simulation mode. A warning is communicated via IO-Link (C485 ­simulation active). The simulation must be ended actively via the menu. If the device is disconnected from the power supply during the simulation and power is then resupplied, the simulation mode is not resumed, and instead the device continues operation in the measuring mode.
Options • Off
• ou1 = high
• ou1= low
Simulation Current Output (OU2)
Navigation Diagnosis → Simulation Current Output (OU2)
Description Simulation affects the process data and the physical current output.
If a simulation is active, a warning to this effect is displayed so that it is obvious to the user that the device is in the simulation mode. A warning is communicated via IO-Link (C485 ­simulation active). The simulation must be ended actively via the menu. If the device is disconnected from the power supply during the simulation and then power is resupplied afterwards, the simulation mode is not resumed, and instead the device continues operation in the measuring mode.
Options • Off
• 4 mA
• 8 mA
• 12 mA
• 16 mA
• 20 mA
• 21.95 mA
• 3.5 mA
Page 45
Cerabar PMP23 IO-Link Description of device parameters
Endress+Hauser 45
14.3 Parameter
14.3.1 Application
Sensor
Unit changeover (UNI)
Navigation Application → Sensor → Unit changeover (UNI)
Description Select the pressure unit. If a new pressure engineering unit is selected, all pressure-specific
parameters are converted.
Switch on value Depends on order specifications.
Options • bar
• kPa
• Mpa
• psi
Factory setting Depends on order specifications.
Zero point configuration (ZRO)
Navigation Application → Sensor → Zero point configuration (ZRO)
Description (typically absolute pressure sensor)
A pressure shift resulting from the orientation of the device can be corrected by the position adjustment. The pressure difference between zero (set point) and the measured pressure must be known.
Prerequisite An offset is possible (parallel shifting of the sensor characteristic) to correct the
orientation and any zero point drift. The set value of the parameter is subtracted from the "raw measured value". The requirement to be able to perform a zero point shift without changing the span is met with the offset function. Maximum offset value = ± 20 % of the sensor nominal range. If an offset value is entered that shifts the span beyond the physical limits of the sensor, the value is admitted but a warning message is generated and displayed via IO-Link. The warning message only disappears when the span is within the sensor limits, taking the offset value currently configured into consideration.
The sensor can
• be operated in a physically unfavorable range, i.e. outside its specifications, or
• be operated by making appropriate corrections to the offset or span.
Raw measured value – (manual offset) = display value (measured value)
Example • Measured value0.002 mbar (0.029 psi)
• Set the measured value in the parameter to 0.002.
• Measured value (after pos. zero adjust) = 0.000 mbar (0 psi)
• The current value is also corrected.
Page 46
Description of device parameters Cerabar PMP23 IO-Link
46 Endress+Hauser
Note Setting in increments of 0.001. As the value is entered numerically, the increment
depends on the measuring range
Options No selection. The user is free to edit the values.
Factory setting 0
Zero point adoption (GTZ)
Navigation Application → Sensor → Zero point adoption (GTZ)
Description (typically gauge pressure sensor)
A pressure shift resulting from the orientation of the device can be corrected by the position adjustment. The pressure difference between zero (set point) and the measured pressure need not be known.
Prerequisite The pressure value present is automatically adopted as the zero point.
An offset is possible (parallel shifting of the sensor characteristic) to correct the orientation and any zero point drift. The accepted value of the parameter is subtracted from the "raw measured value". The requirement to be able to perform a zero point shift without changing the span is met with the offset function. Maximum offset value = ± 20 % of the sensor nominal range. If an offset value is entered that shifts the span beyond the physical limits of the sensor, the value is admitted but a warning message is generated and displayed via IO-Link. The warning message only disappears when the span is within the sensor limits, taking the offset value currently configured into consideration.
The sensor can
• be operated in a physically unfavorable range, i.e. outside its specifications, or
• be operated by making appropriate corrections to the offset or span.
Raw measured value – (manual offset) = display value (measured value)
Example 1 • Measured value0.002 mbar (0.029 psi)
• Use the Zero point adoption (GTZ) parameter to correct the measured value with the value, e.g. 0.002 mbar (0.029 psi). This means that you are assigning the value 0.000 (0 psi) to the pressure present.
• Measured value (after pos. zero adjust) = 0.000 mbar (0 psi)
• The current value is also corrected.
• If necessary, check and correct switch points and span settings.
Example 2 Sensor measuring range: –0.4 to +0.4 bar (–6 to +6 psi) (SP1 = 0.4 bar (6 psi); STU =
0.4 bar (6 psi))
• Measured value0.08 bar (1.2 psi)
• Use the Zero point adoption (GTZ) parameter to correct the measured value with the value, e.g. 0.08 bar (1.2 psi). This means that you are assigning the value 0 mbar (0 psi) to the pressure present.
• Measured value (after pos. zero adjust) = 0 mbar (0 psi)
• The current value is also corrected.
• Warnings C431 or C432 appear because the value 0 bar (0 psi) was assigned to the real value of 0.08 bar (1.2 psi) present and the sensor measuring range was thus exceeded by ± 20%. SP1 and STU values must be readjusted downwards by 0.08 bar (1.2 psi).
Page 47
Cerabar PMP23 IO-Link Description of device parameters
Endress+Hauser 47
Damping (TAU)
Navigation Application → Sensor → Damping (TAU)
Description The damping affects the speed at which the measured value reacts to changes in pressure.
Input range 0.0 to 999.9 seconds in increments of 0.1 seconds
Factory setting 2 seconds
Page 48
Description of device parameters Cerabar PMP23 IO-Link
48 Endress+Hauser
Current output (OU2)
Value for 4 mA (STL)
Navigation Application → Current output (OU2) → Value for 4 mA (STL)
Description Assignment of the pressure value which should correspond to the 4 mA value.
It is possible to invert the current output. To do so, assign the pressure upper range value to the lower measuring current.
Note Enter the value for 4 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the measuring range).
Options No selection. The user is free to edit the values.
Factory setting 0.0 or as per order specifications
Value for 20 mA (STU)
Navigation Application → Current output (OU2) → Value for 20 mA (STU)
Description Assignment of the pressure value which should correspond to the 20 mA value.
It is possible to invert the current output. To do so, assign the pressure lower range value to the upper measuring current.
Note Enter the value for 20 mA in the selected pressure unit anywhere within the measuring
range. The value can be entered in increments of 0.1 (increment depends on the measuring range).
Options No selection. The user is free to edit the values.
Factory setting Upper measuring limit or as per order specifications.
Pressure applied for 4mA (GTL)
Navigation Application → Current output (OU2) → Pressure applied for 4mA (GTL)
Page 49
Cerabar PMP23 IO-Link Description of device parameters
Endress+Hauser 49
Description The pressure value present is automatically adopted for the 4 mA current signal.
Parameter for which the current range can be assigned to any section of the nominal range. This occurs by assigning the pressure lower range value to the lower measuring current and the pressure upper range value to the upper measuring current. The pressure lower range value and upper range value can be configured independently of one another so the pressure measuring span does not remain constant. The LRV and URV pressure measuring span can be edited over the entire sensor range. An invalid TD value is indicated by diagnostic message S510. An invalid position offset is indicated by diagnostic message C431. The editing operation cannot result in the device being operated outside the minimum and maximum sensor limits.
Incorrect entries are declined as indicated by the following messages, and the last valid value prior to the change is used again:
• Parameter value above limit (0x8031)
• Parameter value below limit (0x8032)
The measured value currently present is accepted as the value for 4mA anywhere within the measuring range. The sensor characteristic curve is shifted such that the pressure present becomes the zero value.
Pressure applied for 20mA (GTU)
Navigation Application → Current output (OU2) → Pressure applied for 20mA (GTU)
Description The pressure value present is automatically adopted for the 20 mA current signal.
Parameter for which the current range can be assigned to any section of the nominal range. This occurs by assigning the pressure lower range value to the lower measuring current and the pressure upper range value to the upper measuring current. The pressure lower range value and upper range value can be configured independently of one another so the pressure measuring span does not remain constant. The LRV and URV pressure measuring span can be edited over the entire sensor range. An invalid TD value is indicated by diagnostic message S510. An invalid position offset is indicated by diagnostic message C431. The editing operation cannot result in the device being operated outside the minimum and maximum sensor limits. Incorrect entries are declined, and the last valid value prior to the change is used again. The measured value currently present is accepted as the value for 20 mA anywhere within the measuring range. There is a parallel shift of the sensor characteristic so that the pressure present becomes the max value.
Alarm current (FCU)
Navigation Application → Current output (OU2) → Alarm current (FCU)
Page 50
Description of device parameters Cerabar PMP23 IO-Link
50 Endress+Hauser
Description The device displays warnings and faults. This is done via IO-Link using the diagnostic
message stored in the device. The purpose of all device diagnostics is solely to provide information to the user; they do not have a safety function. The errors diagnosed by the device are displayed via IO-Link in accordance with NE107. In accordance with the diagnostic message, the device behaves as per a warning or fault condition:
Warning (S971, S140, C485, C431, C432):
With this type of error, the device continues to measure. The output signal does not adopt its fault state (value in the event of an error). The main measured value and the state in the form of the letter plus a defined number are displayed alternately (0.5 Hz) via IO-Link. The switch outputs remain in the state defined by the switch points.
Fault (F437, S803, F270, S510, C469, F804):
With this type of error, the device does not continue to measure. The output signal adopts its fault state (value in the event of an error). The fault state is displayed via IO-Link in the form of the letter plus a defined number. The switch output changes to the defined state (open). For the analog output option, an error is also signaled and transmitted via the 4 to 20mA signal. In NE43, NAMUR defines a current ≤3.6 mA and ≥21 mA as a device failure. A corresponding diagnostic message is displayed. Current levels available for selection: The selected alarm current is used for all errors. Diagnostic messages are displayed with numbers and letter via IO-Link. It is not possible to acknowledge all the diagnostic messages. The relevant message disappears if the event is no longer pending.
The messages are displayed in order of priority:
• Highest priority = first message displayed
• Lowest priority = last message displayed
Options • Min: Lower alarm current (≤3.6 mA)
• Max: Upper alarm current (≥21 mA)
Factory setting Max or as per order specifications
Current output (I)
Navigation Application → Current output (OU2) → Current output (I)
Description Switches the current output on or off.
Options • ON
• OFF
Factory setting ON
Page 51
Cerabar PMP23 IO-Link Description of device parameters
Endress+Hauser 51
Switch output (OU1)
Behavior of switch output
Switch point value / Upper value for pressure window, output 1 (SP1 / FH1) Switchback point value / Lower value for pressure window, output 1 (RP1 / FL1)
Navigation Application → Switch output (OU1) → Switch point value / Upper value for pressure
window, output 1 (SP1 / FH1) Application → Switch output (OU1) → Switchback point value / Lower value for pressure window, output 1 (RP1 / FL1)
Prerequisite The following functions are available only if a hysteresis function has been configured for
the switch output (output 1 (Ou1)).
Description of behavior of SP1 / RP1
The hysteresis is implemented using the SP1 and RP1 parameters. Since the parameter settings depend on one another, the parameters are described all together. The switch point "SP1" and switchback point "RP1" can be defined with these functions (e.g. for pump control). When the set switch point "SP1" is reached (with increasing pressure), an electrical signal change takes place at the switch output. When the set switchback point "RP1" is reached (with decreasing pressure), an electrical signal change takes place at the switch output. The difference between the value of switch point "SP1" and the value of switchback point "RP1" is known as the hysteresis. The configured value for the switch point "SP1" must be greater than the switchback point "RP1"! A diagnostic message is displayed if a switch point "SP1" is entered that is ≤ the switchback point "RP1". While it is possible to make this entry, it does not take effect in the device. The entry must be corrected!
1
2
0
SP1
RP1
0
HNO
p
t
1
HNC
A0034025
0 0-signal. Output open in quiescent state. 1 1-signal. Output closed in quiescent state. 2 Hysteresis SP1 Switch point RP1 Switchback point HNO Closing HNC NC contact
To prevent switch-on and switch-off if values are around the switch point "SP1" or switchback point "RP1", a delay can be set for the relevant points. In this regard, see the Switching delay time, output 1 (dS1) and Switchback delay time, output 1 (dR1) parameter descriptions.
Page 52
Description of device parameters Cerabar PMP23 IO-Link
52 Endress+Hauser
Prerequisite The following functions are available only if a window function has been configured for
the switch output (output 1 (Ou1)).
Description of behavior of FH1 / FL1
The window function is implemented using the FH1 and FL1 parameters. Since the parameter settings depend on one another, the parameters are described all together. The upper value of the pressure window "FH1" and the lower value of the pressure window "FL1" can be defined with these functions (e.g. for monitoring a certain pressure range). When the lower value of the pressure window "FL1" is reached (with increasing or decreasing pressure), an electrical signal change takes place at the switch output. When the upper value of the pressure window "FH1" is reached (with increasing or decreasing pressure), an electrical signal change takes place at the switch output. The difference between the upper value of the pressure window "FH1" and the lower value of the pressure window "FL1" is known as the pressure window. The upper value of the pressure window "FH1" must be greater than the lower value of the pressure window "FL1"! A diagnostic message is displayed if the upper value entered for the pressure window "FH1" is less than the lower value of the pressure window "FL1". While it is possible to make this entry, it does not take effect in the device. The entry must be corrected!
1
2
0
FH1
FL1
0
FNO
p
t
1
FNC
A0034026
0 0-signal. Output open in quiescent state. 1 1-signal. Output closed in quiescent state. 2 Pressure window (difference between the value of the high window "FH1" and the low window "FL1") FNO Closing FNC NC contact FH1 Upper value of the pressure window FL1 Lower value of the pressure window
Options No selection. The user is free to edit the values.
Factory setting Factory setting (if no customer-specific setting is ordered):
Switch point SP1 / FH1: 90%; switchback point RP1 / FL1: 10%
Page 53
Cerabar PMP23 IO-Link Description of device parameters
Endress+Hauser 53
Switching delay
Switching delay time, output 1 (dS1) Switchback delay time, output 1 (dR1)
Note The switching delay time/switchback delay time function is implemented using the dS1
and dR1 parameters. Since the parameter settings depend on one another, the parameters are described all together.
• dS1 = switching delay time, output 1
• dR1 = switchback delay time, output 1
Navigation Application → Switch output (OU1) → Switching delay time, output 1 (dS1)
Application → Switch output (OU1) → Switchback delay time, output 1 (dR1)
Description To prevent switch-on and switch-off if values are around the switch point "SP1" or the
switchback point "RP1", a delay in a range of 0 – 50 seconds, to two decimal places, can be set for the individual points. If the measured value leaves the switching range during the delay time, the delay time starts again from scratch.
Example • SP1 = 2 bar (29 psi)
• RP1 = 1 bar (14.5 psi)
• dS1 = 5 seconds
• dR1 = 2 seconds
dS1/: ≥2 bar (29 psi) must be present for at least 5 seconds for SP1 to become active. dR1/: ≥1 bar (14.5 psi) must be present for at least 2 seconds for RP1 to become active.
2
1
0
SP1
RP1
dS1
dS1 dR1
0
HNO
p
t
1
HNC
A0034027
0 0-signal. Output open in quiescent state. 1 1-signal. Output closed in quiescent state. 2 Hysteresis (difference between the value of the switch point "SP1" and the value of the switchback point "RP1") HNO Closing HNC NC contact SP1 Switch point 1 RP1 Switchback point 1 dS1 Set time for which the specific switch point must be reached continuously without interruption until an
electrical signal change takes place.
dR1 Set time for which the specific switchback point must be reached continuously without interruption until an
electrical signal change takes place.
Page 54
Description of device parameters Cerabar PMP23 IO-Link
54 Endress+Hauser
Switch on value 0
Input range 0.00 - 50.00 seconds
Factory setting 0
Output 1 (OU1)
Navigation Application → Switch output (OU1) → Output 1 (OU1)
Description • Hysteresis normally open (HNO):
The switch output is specified as a NO contact with hysteresis properties.
• Hysteresis normally closed (HNC): The switch output is specified as an NC contact with hysteresis properties.
• Window normally open (FNO): The switch output is specified as a NO contact with window properties.
• Window normally closed (FNC): The switch output is specified as an NC contact with window properties.
Options • Hysteresis normally open (HNO)
• Hysteresis normally closed (HNC)
• Window normally open (FNO)
• Window normally closed (FNC)
Factory setting Hysteresis normally open (HNO) or as per order specifications
Page 55
Cerabar PMP23 IO-Link Description of device parameters
Endress+Hauser 55
14.3.2 System
HI Max value (maximum indicator)
Navigation System → HI Max value (maximum indicator)
Description This parameter is used as the maximum indicator and makes it possible to call up
retroactively the highest value ever measured for pressure. A pressure that is present for at least 2.5 ms is logged to the maximum indicator. The maximum indicators cannot be reset.
LO Min value (minimum indicator)
Navigation System → LO Min value (minimum indicator)
Description This parameter is used as the maximum indicator and makes it possible to call up
retroactively the lowest value ever measured for pressure. A pressure that is present for at least 2.5 ms is logged to the maximum indicator. The maximum indicators cannot be reset.
Revisioncounter (RVC)
Navigation System → Revisioncounter (RVC)
Description Counter that indicates the number of parameter changes.
Reset to factory settings (RES)
Navigation System → Reset to factory settings (RES)
Description
L
WARNING
Confirming the "Standard Command" with "Reset to factory settings" causes an immediate reset to the factory settings of the order configuration.
If the factory settings have been changed, downstream processes might be affected following a reset (the behavior of the switch output or current output might be changed).
Make sure that downstream processes are not started unintentionally.
The reset is not subject to additional locking, such as in the form of device locking. The reset also depends on the device status. Any customer-specific configuration carried out at the factory is not affected by a reset (customer-specific configuration remains).
The following parameters are not reset when a reset is performed:
• LO Min value (minimum indicator)
• HI Max value (maximum indicator)
• Last Diagnostic (LST)
• Revisioncounter (RVC)
Page 56
Description of device parameters Cerabar PMP23 IO-Link
56 Endress+Hauser
Note The last error is not reset in a reset.
Device Access Locks.Data Storage Lock
Navigation System → Device Access Locks.Data Storage Lock
Description The device supports DataStorage. If a device is being replaced, this allows the configuration
of the old device to be written to the new device. If, when a device is being replaced, the original configuration of the new device is to be retained, the Device Access Locks.Data Storage Lock parameter can be used to prevent the parameters from being overwritten. If this parameter is set to "true", the new device does not adopt the data stored in the master's DataStorage.
Options • false
• true
14.4 Observation
The process data →  20 are transmitted acyclically.
Page 57
Cerabar PMP23 IO-Link Accessories
Endress+Hauser 57
15 Accessories
15.1 Weld-in adapter
Various weld-in adapters are available for installation in vessels or pipes.
Device Description Option
1)
Order number
PMP23 Weld-in adapter M24, d=65, 316L PM 71041381
PMP23 Weld-in adapter M24, d=65, 316L 3.1 EN10204-3.1
material, inspection certificate
PN 71041383
PMP23 Weld-in adapter G1, 316L, conical metal joint QE 52005087
PMP23 Weld-in adapter G1, 316L, 3.1, conical metal joint,
EN10204-3.1 material, inspection certificate
QF 52010171
PMP23 Weld-in tool adapter G1, brass QG 52005272
PMP23 Weld-in adapter G1, 316L, silicone O-ring seal QJ 52001051
PMP23 Weld-in adapter G1, 316L, 3.1, silicone O-ring seal,
EN10204-3.1 material, inspection certificate
QK 52011896
PMP23 Weld-in adapter Uni D65, 316L QL 214880-0002
PMP23 Weld-in adapter Uni D65, 316L 3.1 EN10204-3.1
material, inspection certificate
QM 52010174
PMP23 Weld-in tool adapter Uni D65/D85, brass QN 71114210
PMP23 Weld-in adapter Uni D85, 316L QP 52006262
PMP23 Weld-in adapter Uni D85, 316L 3.1 EN10204-3.1
material, inspection certificate
QR 52010173
1) Product Configurator, order code for "Enclosed accessories"
If installed horizontally and weld-in adapters with a leakage hole are used, ensure that the leakage hole is pointing down. This allows leaks to be detected as quickly as possible.
15.2 Process adapter M24
The following process adapters can be ordered for the process connections with order option X2J and X3J:
Device Description Order number Order number with inspection certificate 3.1 EN10204
PMP23 Varivent F DN32 PN40 52023996 52024003
PMP23 Varivent N DN50 PN40 52023997 52024004
PMP23 DIN11851 DN40 52023999 52024006
PMP23 DIN11851 DN50 52023998 52024005
PMP23 SMS 1½" 52026997 52026999
PMP23 Clamp 1½" 52023994 52024001
PMP23 Clamp 2" 52023995 52024002
Page 58
Accessories Cerabar PMP23 IO-Link
58 Endress+Hauser
15.3 M12 plug connectors
Connector Degree of protection Material Option
1)
Order number
M12 (self-terminated connection at M12 plug)
53 (2.09)
ø
20
(0.8)
A0024475
IP67 • Union nut: Cu Sn/Ni
• Body: PBT
• Seal: NBR
R1 52006263
M12 90 degrees with 5m (16 ft) cable
28
(1.1)
40 (1.57)³
A0024476
IP67 • Union nut: GD Zn/Ni
• Body: PUR
• Cable: PVC
RZ 52010285
M12 90 degrees (self-terminated connection at M12 plug)
35
(1.38)
28
(1.1)
20 (0.79)
A0024478
IP67 • Union nut: GD Zn/Ni
• Body: PBT
• Seal: NBR
RM 71114212
M12 90 degrees with 5m (16 ft) cable (terminated at one end)
28
(1.1)
40 (1.57)³
A0024477
IP69
2)
• Union nut: 316L (1.4435)
• Body and cable: PVC and PUR
RW 52024216
1) Product Configurator, order code for "Enclosed accessories"
2) Designation of the IP protection class according to DIN EN 60529. Previous designation "IP69K" according to DIN 40050 Part 9 is no longer valid (standard withdrawn on November 1, 2012). The tests required by both standards are identical.
Page 59
Cerabar PMP23 IO-Link Technical data
Endress+Hauser 59
16 Technical data
16.1 Input
16.1.1 Measured variable
Measured process variable
Gauge pressure or absolute pressure
Calculated process variable
Pressure
16.1.2 Measuring range
Metal process isolating diaphragm
Sensor Device Maximum
Sensor measuring range
Lowest calibratable span
1)
MWP OPL Factory settings
2)
Option
3)
lower (LRL) upper (URL)
[bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)]
Devices for gauge pressure measurement
400 mbar (6 psi)
4)
PMP23 –0.4 (–6) +0.4 (+6) 0.4 (6) 1 (15) 1.6 (24) 0 to 400 mbar (0 to 6 psi) 1F
1 bar (15 psi)
4)
PMP23 –1 (–15) +1 (+15) 0.4 (6) 2.7 (40.5) 4 (60) 0 to 1 bar (0 to 15 psi) 1H
2 bar (30 psi)
4)
PMP23 –1 (–15) +2 (+30) 0.4 (6) 6.7 (100.5) 10 (150) 0 to 2 bar (0 to 30 psi) 1K
4 bar (60 psi)
4)
PMP23 –1 (–15) +4 (+60) 0.8 (12) 10.7 (160.5) 16 (240) 0 to 4 bar (0 to 60 psi) 1M
6 bar (90 psi)
4)
PMP23 –1 (–15) +6 (+90) 2.4 (36) 16 (240) 24 (360) 0 to 6 bar (0 to 90 psi) 1N
10 bar (150 psi)
4)
PMP23 –1 (–15) +10 (+150) 2 (30) 25 (375) 40 (600) 0 to 10 bar (0 to 150 psi) 1P
16 bar (240 psi)
4)
PMP23 –1 (–15) +16 (+240) 5 (75) 25 (375) 64 (960) 0 to 16 bar (0 to 240 psi) 1Q
25 bar (375 psi)
4)
PMP23 –1 (–15) +25 (+375) 5 (75) 25 (375) 100 (1500) 0 to 25 bar (0 to 375 psi) 1R
40 bar (600 psi)
4)
PMP23 –1 (–15) +40 (+600) 8 (120) 100 (1500) 160 (2400) 0 to 40 bar (0 to 600 psi) 1S
Devices for absolute pressure measurement
400 mbar (6 psi)
4)
PMP23 0 (0) 0.4 (+6) 0.4 (6) 1 (15) 1.6 (24) 0 to 400 mbar (0 to 6 psi) 2F
1 bar (15 psi)
4)
PMP23 0 (0) 1 (+15) 0.4 (6) 2.7 (40.5) 4 (60) 0 to 1 bar (0 to 15 psi) 2H
2 bar (30 psi)
4)
PMP23 0 (0) 2 (+30) 0.4 (6) 6.7 (100.5) 10 (150) 0 to 2 bar (0 to 30 psi) 2K
4 bar (60 psi)
4)
PMP23 0 (0) 4 (+60) 0.8 (12) 10.7 (160.5) 16 (240) 0 to 4 bar (0 to 60 psi) 2M
10 bar (150 psi)
4)
PMP23 0 (0) 10 (+150) 2 (30) 25 (375) 40 (600) 0 to 10 bar (0 to 150 psi) 2P
40 bar (600 psi)
4)
PMP23 0 (0) +40 (+600) 8 (120) 100 (1500) 160 (2400) 0 to 40 bar (0 to 600 psi) 2S
1) Highest turn down that can be set at the factory: 5:1. The turn down is preset and cannot be changed.
2) Other measuring ranges (e.g. –1 to +5 bar (–15 to 75 psi)) can be ordered with customer-specific settings (see the Product Configurator, order code for "Calibration; Unit" option "J"). It is possible to invert the output signal (LRV = 20 mA; URV = 4 mA). Prerequisite: URV < LRV
3) Product Configurator, order code for "Sensor range"
4) Vacuum resistance: 0.01 bar (0.145 psi) abs
Page 60
Technical data Cerabar PMP23 IO-Link
60 Endress+Hauser
Maximum turn down which can be ordered for absolute pressure and gauge pressure sensors
Device Range 400 mbar (6 psi) 1 bar (15 psi)
6 bar (90 psi) 16 bar (240 psi)
2 bar (30 psi) 4 bar (60 psi) 10 bar (150 psi) 25 to 40 bar (375 to 600 psi)
PMP23 0.3% TD 1:1 TD 1:1 to TD 2.5:1 TD 1:1 to TD 5:1
Page 61
Cerabar PMP23 IO-Link Technical data
Endress+Hauser 61
16.2 Output
16.2.1 Output signal
Designation Option
1)
IO-Link 4 to 20 mA (3- or 4-wire) 7
1) Product Configurator, order code for "Output"
16.2.2 Switching capacity
• Switch status ON: Ia ≤ 250 mA
2)
; switch status OFF: Ia ≤1 mA
• Switch cycles: >10,000,000
• Voltage drop PNP: ≤2 V
• Overload protection: Automatic load testing of switching current; – Max. capacitance load: 14 μF at max. supply voltage (without resistive load) – Max. cycle duration: 0.5 s; min. ton: 4 ms – Periodic disconnection from protective circuit in the event of overcurrent (f = 2 Hz) and
"F804" displayed
16.2.3 Signal range 4 to 20 mA
3.8 mA to 20.5 mA
16.2.4 Load
In order to guarantee sufficient terminal voltage, a maximum load resistance RL (including line resistance) must not be exceeded depending on the supply voltage UB of the supply unit.
[ ]W
20 30
10
0
1022
587
152
U [V]
1
2
R
R
L
L
max
max
£
-U 6.5V
23mA
B
B
A0031107
1 Power supply 10 to 30 V DC 2 R
Lmax
Maximum load resistance
UBSupply voltage
• Error current is output and "S803" displayed (output: MIN alarm current)
• Periodic checking to establish if it is possible to quit fault state
2) The SIO mode supports 250 mA, thus deviating from the IO-Link standard.
Page 62
Technical data Cerabar PMP23 IO-Link
62 Endress+Hauser
16.2.5 Signal on alarm 4 to 20 mA
The response of the output to error is regulated in accordance with NAMUR NE43.
Factory setting MAX alarm: >21 mA
alarm current
Device Description Option
PMP23 Adjusted min. alarm current IA
1)
1) Product Configurator order code for "Service"
16.2.6 Dead time, time constant
Presentation of the dead time and the time constant:
I
63 %
100 %
t
t1t
2
90 %
t
3
A0019786
16.2.7 Dynamic behavior
Dead time (t1) [ms] Time constant (T63), t2 [ms] Time constant (T90), t3 [ms]
7 ms 11 ms 16 ms
16.2.8 Dynamic behavior of switch output
Response time ≤20 ms
Page 63
Cerabar PMP23 IO-Link Technical data
Endress+Hauser 63
16.3 Performance characteristics of metal process
isolating diaphragm
16.3.1 Reference operating conditions
• As per IEC 60770
• Ambient temperature TA = constant, in the range of:+21 to +33 °C (+70 to +91 °F)
• Humidity φ = constant, in the range of 5 to 80 % rH
• Ambient pressure pA = constant, in the range of:860 to 1 060 mbar (12.47 to 15.37 psi)
• Position of measuring cell = constant, in range: horizontal ±1° (see also "Influence of the installation position" section →  14)
• Zero based span
• Process isolating diaphragm material: AISI 316L (1.4435)
• Filling oil: NSF-H1 synthetic oil in accordance with FDA 21 CFR 178.3570
• Supply voltage: 24 V DC ±3 V DC
• Load: 320 Ω (at 4 to 20 mA output)
16.3.2 Measuring uncertainty for small absolute pressure measuring
ranges
The smallest extended uncertainty of measurement that can delivered by our standards is:
• in the range 1 to 30 mbar (0.0145 to 0.435 psi): 0.4 % of reading
• in the range < 1 mbar (0.0145 psi): 1 % of reading.
16.3.3 Influence of the installation position
→  14
16.3.4 Resolution
Current output: min. 1.6 μA
16.3.5 Reference accuracy
The reference accuracy contains the non-linearity [DIN EN 61298-2 3.11] including the pressure hysteresis [DIN EN 61298-23.13] and non-repeatability [DIN EN 61298-2 3.11] in accordance with the limit point method as per [DIN EN 60770].
Device % of the calibrated span to the maximum turn down
Reference accuracy Non-linearity Non-repeatability
PMP23 ±0.3 ±0.1 ±0.1
Overview of the turn down ranges →  60
16.3.6 Thermal change of the zero output and the output span
PMP23
Measuring cell –10 to +85 °C (+14 to +185 °F) +85 to +100 °C (+185 to +212 °F)
% of the calibrated span for TD 1:1
<1 bar (15 psi) <1 <1.2
≥ 1 bar (15 psi) <0.8 <1
Page 64
Technical data Cerabar PMP23 IO-Link
64 Endress+Hauser
16.3.7 Long-term stability
Device 1 year 5 years 8 years
% of URL
IO-Link ±0.2 In preparation In preparation
16.3.8 Switch-on time
≤2 s
For small measuring ranges, pay attention to the thermal compensation effects.
Page 65
Cerabar PMP23 IO-Link Technical data
Endress+Hauser 65
16.4 Environment
16.4.1 Ambient temperature range
Device Ambient temperature range
1)
PMP23 –40 to +70 °C (–40 to +158 °F)
PMP23 Devices for hazardous areas: –40 to +70 °C (–40 to +158 °F)
1) Exception: the following cable is designed for an operating temperature range of
–25 to +70 °C (–13 to +158 °F): Product Configurator order code for "Accessory enclosed", option "RZ".
16.4.2 Storage temperature range
–40 to +85 °C (–40 to +185 °F)
16.4.3 Climate class
Device Climate class Note
PMP23 Class 4K4H Air temperature: –20 to +55 °C (–4 to +131 °F),
relative humidity: 4 to 100 % satisfied according to DIN EN 60721-3-4 (condensation is possible)
16.4.4 Degree of protection
Device Connection Climate class Option
1)
PMP23 M12 plug IP65/67 NEMA type 4X enclosure M
PMP23 M12 plug made of metal IP66/69
2)
NEMA type 4X enclosure N
1) Product Configurator, order code for "Electrical connection"
2) Designation of the IP protection class according to DIN EN 60529. Previous designation "IP69K" according
to DIN 40050 Part 9 is no longer valid (standard withdrawn on November 1, 2012). The tests required by both standards are identical.
16.4.5 Vibration resistance
Test standard Vibration resistance
IEC 60068-2-64:2008 Guaranteed for 5 to 2000Hz: 0.05g2/Hz
16.4.6 Electromagnetic compatibility
• Interference emission as per EN 61326-1 equipment B
• Interference immunity as per EN 61326-1 (industrial environment) For intended use in case of transient faults, the switch output can switch for 0.2 s into communication mode (only for devices with IO-Link).
• Maximum deviation: 1.5% for TD 1:1
For more details, refer to the Declaration of Conformity.
Page 66
Technical data Cerabar PMP23 IO-Link
66 Endress+Hauser
16.5 Process
16.5.1 Process temperature range for devices with metallic process isolating diaphragm
Device Process temperature range
PMP23 –10 to +100 °C (+14 to +212 °F)
PMP23
Sterilization in place (SIP)
At +135°C (+275 °F) for a maximum of one hour (device in operation but not within measuring specification)
Applications with changes in temperature
Frequent extreme changes in temperatures can temporarily cause measuring errors. Internal temperature compensation is faster the smaller the change in temperature and the longer the time interval.
For further information please contact your local Endress+Hauser Sales Center.
16.5.2 Pressure specifications
L
WARNING
The maximum pressure for the measuring device depends on the lowest-rated element with regard to pressure.
For pressure specifications, see the "Measuring range" section and "Mechanical construction" section in the Technical Information.
The Pressure Equipment Directive (2014/68/EU) uses the abbreviation "PS". The abbreviation "PS" corresponds to the MWP (maximum working pressure) of the measuring device.
MWP (maximum working pressure): The MWP (maximum working pressure) is specified on the nameplate. This value is based on a reference temperature of +20 °C (+68 °F) and may be applied to the device for an unlimited period of time. Observe the temperature dependency of the MWP.
OPL (over pressure limit): The test pressure corresponds to the over pressure limit of the sensor and may only be applied temporarily to ensure that the measurement is within the specifications and no permanent damage develops. In the case of sensor range and process connections where the over pressure limit (OPL) of the process connection is smaller than the nominal value of the sensor, the device is set at the factory, at the very maximum, to the OPL value of the process connection. If you want to use the entire sensor range, select a process connection with a higher OPL value.
Page 67
Cerabar PMP23 IO-Link Index
Endress+Hauser 67
Index
A
Actual Diagnostics (STA) ...................... 43
Alarm current (FCU) ......................... 49
Application ................................. 8
Application Specific Tag ...................... 43
C
CE mark (declaration of conformity) ...............9
Cleaning .................................. 40
Configuration of a pressure measurement ......... 24
Configuring pressure measurement .............. 24
Current output (I) ........................ 32, 50
D
Damping (TAU) .............................47
Declaration of Conformity ...................... 9
Designated use .............................. 8
Device Access Locks.Data Storage Lock ............56
Diagnostic event ............................ 37
Diagnostic events ........................... 37
Diagnostic message .......................... 37
Diagnostics
Symbols ................................ 37
Disposal .................................. 41
E
ENP_VERSION ............................. 43
Event text ................................. 37
Extended ordercode ......................... 43
Exterior cleaning ............................40
F
Field of application
Residual risks ............................. 8
H
HI Max value (maximum indicator) .............. 55
Hysteresis .............................. 29, 51
I
In alarm condition ........................... 37
L
Last Diagnostic (LST) .........................43
LO Min value (minimum indicator) .............. 55
M
Maintenance ...............................40
Media ..................................... 8
Menu
Description of device parameters ..............43
Overview ............................... 42
N
Nameplate ................................ 12
O
Operating menu
Description of device parameters ..............43
Overview ............................... 42
Operational safety ............................9
Output 1 (OU1) .......................... 32, 54
P
Pressure applied for 4mA (GTL) .............. 33, 48
Pressure applied for 20mA (GTU) .............33, 49
Product safety ............................... 9
R
Repair concept ............................. 41
Reset to factory settings (RES) .................. 55
Revisioncounter (RVC) ....................... 55
S
Safety instructions
Basic ................................... 8
Simulation Current Output (OU2) ................44
Simulation Switch Output (OU1) ................ 44
Staff
Requirements .............................8
Status signals .............................. 37
Switch point value / Upper value for pressure window,
output 1 (SP1 / FH1) ...................... 29, 51
Switchback delay time, output 1 (dR1) ......... 31, 53
Switchback point value / Lower value for pressure
window, output 1 (RP1 / FL1) ............... 29, 51
Switching delay time, output 1 (dS1) .......... 31, 53
T
Troubleshooting ............................ 36
U
Unit changeover (UNI) - µC-Temperature ..........45
Using measuring device
Borderline cases ........................... 8
Incorrect use ............................. 8
see Designated use
V
Value for 4 mA (STL) ......................32, 48
Value for 20 mA (STU) .................... 33, 48
W
Window function .........................29, 51
Workplace safety ............................ 9
Z
Zero point adoption (GTZ) .................. 26, 46
Zero point configuration (ZRO) ...............26, 45
Page 68
www.addresses.endress.com
*71378480*
71378480
Loading...