Endress+Hauser CCA151 Specifications

TI01357C/07/EN/01.17 71371626
Products Solutions Services
Technical Information
Flowfit CCA151
Flow assembly for disinfection sensors CCS5xD
Simple assembly for measuring disinfection in drinking and process water
Application
• Drinking water
• Utilities in all sectors
• Applications with low sample volumes
Your benefits
• Suitable for all disinfection processes without pH compensation - chlorine dioxide and others
• Requires only low sample flow: At least 5 l/h (1.32 gal/h)
• A new addition to the flow assembly range: Same form as and can be exchanged for CCA250

Function and system design

1
3
6
8
2
7
4
5
Flowfit CCA151

Mode of operation

Measuring system

You can carry out reliable chlorine dioxide measurements using suitable sensors with flow assembly CCA151 . You can remove, clean, sterilize or calibrate/adjust the sensors without interrupting the process.
The assembly can be installed in both vessels and pipes.
A complete measuring system comprises:
• Disinfection sensor CCS50D (membrane-covered, ⌀25 mm) with corresponding installation adapter
• Flowfit CCA151 flow assembly
• Measuring cable CYK10
• Transmitter, e.g. Liquiline CM44x or CM44xR
• Optional: Extension cable CYK11
 1 Example of a measuring system
1 Transmitter Liquiline CM44x 2 Power cable for transmitter 3 Disinfection sensor CCS5xD (membrane-covered, ⌀25 mm), e.g. CCS50D 4 Outlet from Flowfit CCA151 flow assembly 5 Inlet to Flowfit CCA151 flow assembly 6 Flowfit CCA151 flow assembly 7 Coupling nut for installing sensor CCS50D in Flowfit CCA151 flow assembly 8 Measuring cable CYK10
2 Endress+Hauser
A0034241
Flowfit CCA151

Installation

Orientation

Installation instructions

The assembly is designed for installation on panels, walls or level surfaces. G 1/8" connections and a hose connection with an external diameter of 6 mm and an internal diameter of 4 mm are provided for this purpose.
The assembly is designed in such a way that it must be installed vertically.
The sensor that is used can restrict the orientation.
WARNING
L
Risk of injury from high pressure, high temperature or chemical hazards if process medium escapes.
Wear protective gloves, protective goggles and protective clothing.
Mount the assembly only if vessels or pipes are empty and unpressurized.
Prior to installation, check the flange seal between the flanges.
1. Mount assembly on vertical surface.
2. Connect to the vessel or pipe via the process connection.
Bypass operation
To achieve flow through the assembly with a bypass, pressure p1 must be higher than pressure p2.
This requires the installation of an orifice plate or throttle valve in the main pipe.
p1 must not exceed the permitted operating pressure for the assembly of 4 bar (58 psi).
If the sensor is installed, the sensor's pressure specifications must also be observed.
1. Mount the assembly vertically.
2. Connect the medium using the usual commercial connection fittings. Depending on requirements, use the usual sealing materials, e.g. PMMA-compatible thread adhesive, Teflon tape or O-ring made of FKM.
3. Installing the assembly in the bypass is preferable to installing it directly in the process line. The bypass line can be blocked off without interrupting the process (a shut-off valve is required upstream and downstream). This allows, for example, the sensor to be cleaned without restricting the process.
4. Install a dirt trap (filter) with a mesh size of 500 μm upstream from the assembly. If a pressure-reducing valve is used, it usually includes a dirt trap.
5. Set flow value upstream from the assembly, e. g. by installation of a flow setting.
6. Install a DN5-8 tap downstream from the assembly outlet to allow samples to be taken for reference measurements in accordance with the DPD method.
Endress+Hauser 3
1 2 3
4
p1
p2
p1 > p2
 2 Connection example with bypass and orifice plate in the main pipe
1 Shut-off valve (provided by customer) 2 Pressure-reducing valve (at p1 > 4 bar (58 psi)) (provided by customer) 3 Shut-off valve (provided by customer) 4 Orifice plate in process line (provided by customer)
Flowfit CCA151
A0034259
Open outlet operation
p must not exceed the permitted operating pressure for the assembly of 4 bar (58 psi).
If the sensor is installed, the sensor's pressure specifications must also be observed.
If the medium pressure is above 4 bar (58 psi), a pressure-reducing valve is required.
1. Mount the assembly vertically.
2. Connect the medium using the usual commercial connection fittings. Depending on requirements, use the usual sealing materials, e.g. PMMA-compatible thread adhesive, Teflon tape or O-ring made of FKM.
3. Installing the assembly in the bypass is preferable to installing it directly in the process line. The bypass line can be blocked off without interrupting the process (a shut-off valve is required upstream and downstream). This allows, for example, the sensor to be cleaned without restricting the process.
4. Install a dirt trap (filter) with a mesh size of 500 μm upstream from the assembly. If a pressure-reducing valve is used, it usually includes a dirt trap.
5. Set flow value upstream from the assembly, e. g. by installation of a flow setting.
6. Install a DN5-8 tap downstream from the assembly outlet to allow samples to be taken for reference measurements in accordance with the DPD method.
4 Endress+Hauser
Loading...
+ 8 hidden pages