• Make sure the document is stored in a safe place such that it is always available when
working on or with the device.
• To avoid danger to individuals or the facility, read the "Basic safety instructions" section
carefully, as well as all other safety instructions in the document that are specific to
working procedures.
• The manufacturer reserves the right to modify technical data without prior notice. Your
Endress+Hauser Sales Center will supply you with current information and updates to
these instructions.
16.12 Certificates and approvals .............. 184
16.13 Application packages .................. 185
16.14 Accessories ......................... 185
16.15 Supplementary documentation ........... 185
Index ................................. 187
Endress+Hauser5
Page 6
Document informationProline Prowirl C 200 HART
DANGER
WARNING
CAUTION
NOTICE
1 Document information
1.1 Document function
These Operating Instructions contain all the information that is required in various phases
of the life cycle of the device: from product identification, incoming acceptance and
storage, to mounting, connection, operation and commissioning through to
troubleshooting, maintenance and disposal.
1.2 Symbols used
1.2.1 Safety symbols
SymbolMeaning
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
1.2.2 Electrical symbols
SymbolMeaningSymbolMeaning
Direct currentAlternating current
Direct current and alternating currentGround connection
Protective ground connection
A terminal which must be connected
to ground prior to establishing any
other connections.
1.2.3 Tool symbols
SymbolMeaning
Flat blade screwdriver
Allen key
A grounded terminal which, as far as
the operator is concerned, is
grounded via a grounding system.
Equipotential connection
A connection that has to be connected
to the plant grounding system: This
may be a potential equalization line
or a star grounding system depending
on national or company codes of
practice.
Open-ended wrench
6Endress+Hauser
Page 7
Proline Prowirl C 200 HARTDocument information
,…,
,…,
-
.
1.2.4 Symbols for certain types of information
SymbolMeaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Series of steps
Result of a step
Help in the event of a problem
Visual inspection
1.2.5 Symbols in graphics
SymbolMeaningSymbolMeaning
1, 2, 3,...Item numbers
A, B, C, ...ViewsA-A, B-B, C-C, ... Sections
Hazardous area
Flow direction
Series of steps
Safe area (non-hazardous area)
1.3 Documentation
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate
or scan the 2-D matrix code (QR code) on the nameplate.
For a detailed list of the individual documents along with the documentation code
Endress+Hauser7
Page 8
Document informationProline Prowirl C 200 HART
1.3.1 Standard documentation
Document typePurpose and content of the document
Technical InformationPlanning aid for your device
The document contains all the technical data on the device and provides
an overview of the accessories and other products that can be ordered for
the device.
Brief Operating InstructionsGuide that takes you quickly to the 1st measured value
The Brief Operating Instructions contain all the essential information
from incoming acceptance to initial commissioning.
Additional documents are supplied depending on the device version ordered: Always
comply strictly with the instructions in the supplementary documentation. The
supplementary documentation is an integral part of the device documentation.
1.4 Registered trademarks
®
HART
Registered trademark of the HART Communication Foundation, Austin, USA
KALREZ ®, VITON
Registered trademarks of DuPont Performance Elastomers L.L.C., Wilmington, DE USA
GYLON
®
Registered trademark of Garlock Sealing Technologies, Palmyar, NY, USA
®
Applicator®, FieldCare®, DeviceCare ®, Field XpertTM, HistoROM®, Heartbeat
Technology
TM
Registered or registration-pending trademarks of the Endress+Hauser Group
8Endress+Hauser
Page 9
Proline Prowirl C 200 HARTBasic safety instructions
2 Basic safety instructions
2.1 Requirements for the personnel
The personnel for installation, commissioning, diagnostics and maintenance must fulfill
the following requirements:
Trained, qualified specialists must have a relevant qualification for this specific function
‣
and task
Are authorized by the plant owner/operator
‣
Are familiar with federal/national regulations
‣
Before beginning work, the specialist staff must have read and understood the
‣
instructions in the Operating Instructions and supplementary documentation as well as
in the certificates (depending on the application)
Following instructions and basic conditions
‣
The operating personnel must fulfill the following requirements:
Being instructed and authorized according to the requirements of the task by the
‣
facility's owner-operator
Following the instructions in these Operating Instructions
‣
2.2 Designated use
Application and media
Depending on the version ordered, the measuring device can also measure potentially
explosive, flammable, poisonous and oxidizing media.
Measuring devices for use in hazardous areas, in hygienic applications or in applications
where there is an increased risk due to process pressure, are labeled accordingly on the
nameplate.
To ensure that the measuring device remains in proper condition for the operation time:
Only use the measuring device in full compliance with the data on the nameplate and
‣
the general conditions listed in the Operating Instructions and supplementary
documentation.
Check the nameplate to verify if the device ordered can be put to its intended use in the
‣
approval-related area (e.g. explosion protection, pressure vessel safety).
Use the measuring device only for media against which the process-wetted materials
‣
are adequately resistant.
If the measuring device is not operated at atmospheric temperature, compliance with
‣
the relevant basic conditions specified in the associated device documentation is
absolutely essential: "Documentation" section → 7.
Protect the measuring device permanently against corrosion from environmental
‣
influences.
Incorrect use
Non-designated use can compromise safety. The manufacturer is not liable for damage
caused by improper or non-designated use.
WARNING
L
Danger of breakage of the sensor due to corrosive or abrasive fluids or from
environmental conditions!
Verify the compatibility of the process fluid with the sensor material.
‣
Ensure the resistance of all fluid-wetted materials in the process.
‣
Keep within the specified pressure and temperature range.
‣
Verification for borderline cases:
For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance
‣
in verifying the corrosion resistance of fluid-wetted materials, but does not accept any
Endress+Hauser9
Page 10
Basic safety instructionsProline Prowirl C 200 HART
warranty or liability as minute changes in the temperature, concentration or level of
contamination in the process can alter the corrosion resistance properties.
Residual risks
Possible burn hazard due to fluid temperatures!
For elevated fluid temperature, ensure protection against contact to prevent burns.
‣
2.3 Workplace safety
For work on and with the device:
Wear the required personal protective equipment according to federal/national
‣
regulations.
For welding work on the piping:
Do not ground the welding unit via the measuring device.
‣
If working on and with the device with wet hands:
It is recommended to wear gloves on account of the higher risk of electric shock.
‣
2.4 Operational safety
Risk of injury.
Operate the device in proper technical condition and fail-safe condition only.
‣
The operator is responsible for interference-free operation of the device.
‣
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers.
If, despite this, modifications are required, consult with Endress+Hauser.
‣
Repair
To ensure continued operational safety and reliability,
Carry out repairs on the device only if they are expressly permitted.
‣
Observe federal/national regulations pertaining to repair of an electrical device.
‣
Use original spare parts and accessories from Endress+Hauser only.
‣
2.5 Product safety
This measuring device is designed in accordance with good engineering practice to meet
state-of-the-art safety requirements, has been tested, and left the factory in a condition in
which it is safe to operate.
It meets general safety standards and legal requirements. It also complies with the EC
directives listed in the device-specific EC Declaration of Conformity.
2.6 IT security
We only provide a warranty if the device is installed and used as described in the
Operating Instructions. The device is equipped with security mechanisms to protect it
against any inadvertent changes to the device settings.
IT security measures in line with operators' security standards and designed to provide
additional protection for the device and device data transfer must be implemented by the
operators themselves.
10Endress+Hauser
Page 11
Proline Prowirl C 200 HARTProduct description
12
3
4
56
7
8
9
+
E
–
3 Product description
The device consists of a transmitter and a sensor.
Two device versions are available:
• Compact version – transmitter and sensor form a mechanical unit.
• Remote version - transmitter and sensor are mounted in separate locations.
Incoming acceptance and product identificationProline Prowirl C 200 HART
1
+
2
1
+
2
4 Incoming acceptance and product
identification
4.1 Incoming acceptance
Are the order codes on the
delivery note (1) and the
product sticker (2)
identical?
Are the goods undamaged?
Do the nameplate data
match the ordering
information on the delivery
note?
Is the CD-ROM with the
Technical Documentation
(depends on device
version) and documents
present?
• If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center.
• Depending on the device version, the CD-ROM might not be part of the delivery!
The Technical Documentation is available via the Internet or via the Endress+HauserOperations App, see the "Product identification" section → 13.
4.2 Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
(www.endress.com/deviceviewer): All information about the measuring device is
displayed.
• Enter the serial number from the nameplates into the Endress+Hauser Operations App
or scan the 2-D matrix code (QR code) on the nameplate with the Endress+HauserOperations App: all the information for the measuring device is displayed.
12Endress+Hauser
Page 13
Proline Prowirl C 200 HARTIncoming acceptance and product identification
Ordercode:
Ext.ord.cd.:
Ser.no.:
Date:
i
i
Patents
322540-0001
1
2
3 4 5
6
7
8
9
1011
12
14
15
16
17
13
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The chapters "Additional standard documentation on the device" → 8 and
"Supplementary device-dependent documentation" → 8
• The W@M Device Viewer: Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or
scan the 2-D matrix code (QR code) on the nameplate.
4.2.1 Transmitter nameplate
A0013906
2Example of a transmitter nameplate
1Manufacturing location
2Name of the transmitter
3Order code
4Serial number (Ser. no.)
5Extended order code (Ext. ord. cd.)
6Electrical connection data, e.g. available inputs and outputs, supply voltage
7Type of cable glands
8Permitted ambient temperature (Ta)
9Firmware version (FW) and device revision (Dev.Rev.) from the factory
10 CE mark, C-Tick
11 Additional information on version: certificates, approvals
12 Permitted temperature range for cable
13 Manufacturing date: year-month
14 Degree of protection
15 Approval information for explosion protection
16 Document number of safety-related supplementary documentation
17 2-D matrix code
Endress+Hauser13
Page 14
Incoming acceptance and product identificationProline Prowirl C 200 HART
Ser. no.:
Ptest:
Size:
Materials:
Tm:
Qmax(G):
Gasket:
Ta:
1
2
568
7
9
3
4
10
111213
4.2.2 Sensor nameplate
Order code for "Housing" option C "GT20 two-chamber, aluminum coated"
A0020758
3Example of a sensor nameplate
1Nominal diameter of the sensor
2Flange nominal diameter/nominal pressure
3Measuring tube material
4Measuring tube material
5Serial number (Ser. no.)
6Maximal permitted volume flow (gas/steam)
7Test pressure of the sensor
8Degree of protection
9Approval information for explosion protection and Pressure Equipment Directive
10 CE mark
11 Seal material
12 Medium temperature range
13 Ambient temperature range
14Endress+Hauser
Page 15
Proline Prowirl C 200 HARTIncoming acceptance and product identification
Order code:
Ext. ord. cd.:
Ser. no.:
Ptest:
Size:
Ta:
Materials:
Gasket:
Tm:
Qmax(G):
4
1
5
8
12
2
7
9
10
11
13141516
3
6
Order code for "Housing" option J "GT20 two-chamber, remote, aluminum coated"
A0020759
4Example of a sensor nameplate
1Name of the sensor
2Nominal diameter of the sensor
3Flange nominal diameter/nominal pressure
4Order code
5Serial number (Ser. no.)
6Extended order code (Ext. ord. cd.)
7Maximal permitted volume flow (gas/steam)
8Degree of protection
9Approval information for explosion protection and Pressure Equipment Directive
10 Ambient temperature range
11 Document number of safety-related supplementary documentation → 185
12 Test pressure of the sensor
13 Measuring tube material
14 Measuring tube material
15 Seal material
16 Medium temperature range
Endress+Hauser15
Order code
The measuring device is reordered using the order code.
Extended order code
• The device type (product root) and basic specifications (mandatory features) are
always listed.
• Of the optional specifications (optional features), only the safety and approvalrelated specifications are listed (e.g. LA). If other optional specifications are also
ordered, these are indicated collectively using the # placeholder symbol (e.g. #LA#).
• If the ordered optional specifications do not include any safety and approval-related
specifications, they are indicated by the + placeholder symbol (e.g. XXXXXX-ABCDE
+).
Page 16
Incoming acceptance and product identificationProline Prowirl C 200 HART
Ser. no.:
K-factor:
MDMT:
1234
Additional sensor nameplate
A0021042
5Example of an additional sensor nameplate
1Name of the sensor
2Serial number (Ser. no.)
3K-factor
4Minimum permitted material temperature
4.2.3 Symbols on measuring device
SymbolMeaning
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious
or fatal injury.
Reference to documentation
Refers to the corresponding device documentation.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
16Endress+Hauser
Page 17
Proline Prowirl C 200 HARTStorage and transport
5 Storage and transport
5.1 Storage conditions
Observe the following notes for storage:
• Store in the original packaging to ensure protection from shock.
• Do not remove protective covers or protective caps installed on process connections.
They prevent mechanical damage to the sealing surfaces and contamination in the
measuring tube.
• Protect from direct sunlight to avoid unacceptably high surface temperatures.
• Store in a dry and dust-free place.
• Do not store outdoors.
Storage temperature:
– All components apart from the display modules: –50 to +80 °C (–58 to +176 °F)
– Display modules: –40 to +80 °C (–40 to +176 °F)
5.2 Transporting the product
Transport the measuring device to the measuring point in the original packaging.
A0015604
Do not remove protective covers or caps installed on process connections. They
prevent mechanical damage to the sealing surfaces and contamination in the
measuring tube.
5.2.1 Measuring devices without lifting lugs
WARNING
L
Center of gravity of the measuring device is higher than the suspension points of the
webbing slings.
Risk of injury if the measuring device slips.
Secure the measuring device against slipping or turning.
‣
Observe the weight specified on the packaging (stick-on label).
‣
A0015606
Endress+Hauser17
Page 18
Storage and transportProline Prowirl C 200 HART
5.2.2 Measuring devices with lifting lugs
CAUTION
L
Special transportation instructions for devices with lifting lugs
Only use the lifting lugs fitted on the device or flanges to transport the device.
‣
The device must always be secured at two lifting lugs at least.
‣
5.2.3 Transporting with a fork lift
If transporting in wood crates, the floor structure enables the crates to be lifted lengthwise
or at both sides using a forklift.
5.3 Packaging disposal
All packaging materials are environmentally friendly and 100% recyclable:
• Measuring device secondary packaging: polymer stretch film that conforms to EC
Directive 2002/95/EC (RoHS).
• Packaging:
– Wood crate, treated in accordance with ISPM 15 standard, which is confirmed by the
affixed IPPC logo.
or
– Carton in accordance with European Packaging Directive 94/62EC; recyclability is
confirmed by the affixed RESY symbol.
• Seaworthy packaging (optional): Wood crate, treated in accordance with ISPM 15
standard, which is confirmed by the affixed IPPC logo.
The direction of the arrow on the sensor nameplate helps you to install the sensor
according to the flow direction (direction of medium flow through the piping).
Vortex meters require a fully developed flow profile as a prerequisite for correct volume
flow measurement. Therefore, please note the following:
OrientationCompact versionRemote version
A Vertical orientation
A0015545
B Horizontal orientation, transmitter head up
A0015589
C Horizontal orientation, transmitter head down
A0015590
D Horizontal orientation, transmitter head at side
A0015592
1)
2) 3)
4) 5)
4)
A0015543
1)In the case of liquids, there should be upward flow in vertical pipes to avoid partial pipe filling (Fig. A).
Disruption in flow measurement! In the case of vertical orientation and downward flowing liquid, the pipe
always needs to be completely filled to ensure correct liquid flow measurement.
2)Danger of electronics overheating! If the fluid temperature is ≥ 200 °C (392 °F) orientation B is not
permitted for the wafer version (Prowirl D) with nominal diameters DN 100 (4") and DN 150 (6").
3)In the case of hot media (e.g. steam or fluid temperature (TM) ≥ 200 °C (392 °F): orientation C or D
4)In the case of very cold media (e.g. liquid nitrogen): orientation B or D
5)For "wet steam detection/measurement" option: orientation C
Endress+Hauser19
Page 20
InstallationProline Prowirl C 200 HART
A
L
Minimum spacing and cable length
A0019211
AMinimum spacing in all directions
LRequired cable length
The following dimensions must be observed to guarantee problem-free access to the device
for service purposes:
• A =100 mm (3.94 in)
• L = L + 150 mm (5.91 in)
Rotating the electronics housing and the display
The electronics housing can be rotated continuously by 360 °° on the housing support. The
display unit can be rotated in 45 ° stages. This means you can read the display comfortably
from all directions.
Inlet and outlet runs
To attain the specified level of accuracy of the measuring device, the inlet and outlet runs
mentioned below must be maintained at the very minimum.
20Endress+Hauser
Page 21
Proline Prowirl C 200 HARTInstallation
15 × DN
5 × DN
1
3
25 × DN
5 × DN
40 × DN
5 × DN
4
2
20 × DN
5 × DN
5
20 × DN
5 × DN
6
17 × DN + 8 × h
5 × DN
h
7
50 × DN
5 × DN
9
40 × DN
5 × DN
8
5 × DN
DN25 (1"):≤
DN40 (1½"):≥
PT
TT
3...5 x DN
4...8 x DN
6Minimum inlet and outlet runs with various flow obstructions
hDifference in expansion
1Reduction by one nominal diameter size
2Single elbow (90° elbow)
3Double elbow (2 × 90° elbows, opposite)
4Double elbow 3D (2 × 90° elbows, opposite, not on one plane)
5T-piece
6Expansion
7Control valve
8Two measuring devices in a row where DN ≤ 25 (1"): directly flange on flange
9Two measuring devices in a row where DN ≥ 40 (1½"): for spacing, see graphic
Outlet runs when installing external devices
If installing an external device, observe the specified distance.
A0019189
Endress+Hauser21
PT Pressure transmitter
TT Temperature transmitter
A0019205
Page 22
InstallationProline Prowirl C 200 HART
Installation dimensions
For the dimensions and installation lengths of the device, see the "Technical
Information" document, "Mechanical construction" section
6.1.2 Requirements from environment and process
Ambient temperature range
Compact version
Measuring deviceNon-Ex:–40 to +80 °C (–40 to +176 °F)
Ex i:–40 to +70 °C (–40 to +158 °F)
EEx d/XP version:–40 to +60 °C (–40 to +140 °F)
ATEX II1/2G Ex d, Ex ia:–40 to +60 °C (–40 to +140 °F)
Local display–20 to +70 °C (–4 to +158 °F)
1)Additionally available as order code for "Test, certificate", option JN "Transmitter ambient temperature –50
°C (–58 °F)".
1)
1)
1)
1)
1)
Remote version
TransmitterNon-Ex:–40 to +80 °C (–40 to +176 °F)
Ex i:–40 to +80 °C (–40 to +176 °F)
Ex d:–40 to +60 °C (–40 to +140 °F)
ATEX II1/2G Ex d, Ex ia:–40 to +60 °C (–40 to +140 °F)
SensorNon-Ex:–40 to +85 °C (–40 to +185 °F)
Ex i:–40 to +85 °C (–40 to +185 °F)
Ex d:–40 to +85 °C (–40 to +185 °F)
ATEX II1/2G Ex d, Ex ia:–40 to +85 °C (–40 to +185 °F)
Local display–20 to +70 °C (–4 to +158 °F)
1)Additionally available as order code for "Test, certificate", option JN "Transmitter ambient temperature –50
°C (–58 °F)".
If operating outdoors:
‣
1)
1)
1)
1)
1)
1)
1)
1)
1)
Avoid direct sunlight, particularly in warm climatic regions.
Thermal insulation
For optimum temperature measurement and mass calculation, heat transfer at the sensor
must be avoided for some fluids. This can be ensured by installing thermal insulation. A
wide range of materials can be used for the required insulation.
This applies for:
• Compact version
• Remote sensor version
The maximum insulation height permitted is illustrated in the diagram:
22Endress+Hauser
Page 23
Proline Prowirl C 200 HARTInstallation
1
A0019212
1Maximum insulation height
When insulating, ensure that a sufficiently large area of the housing support remains
‣
exposed.
The uncovered part serves as a radiator and protects the electronics from overheating and
excessive cooling.
NOTICE
Electronics overheating on account of thermal insulation!
Observe the maximum permitted insulation height of the transmitter neck so that the
‣
transmitter head and/or the connection housing of the remote version is completely
free.
Observe information on the permissible temperature ranges .
‣
Note that a certain orientation might be required, depending on the fluid temperature
‣
→ 19.
Vibrations
The correct operation of the measuring system is not affected by plant vibrations up to 1 g,
10 to 500 Hz. Therefore no special measures are needed to secure the sensors.
6.1.3 Special mounting instructions
Inspection kit
The inspection kit contains the necessary parts for the annual visual inspection of the
primary measurement element (bluff body) in accordance with ERCB Dir. 017.
Consists of:
• 2 inspection centering sleeves
• 8 screws
• 2 inspection seals
• 2 inspection covers
The centering sleeve supports the user by centering the calipers in the inspection ports.
This makes it easier to measure the distance from the sealing surface to the bluff body. In
addition, the kit also contains screws, seals and covers for the inspection ports.
An inspection kit can be ordered separately (see the "Accessories" section → 160).
Installation for delta heat measurements
Order code for "Sensor version", option 3 "Mass flow (integrated temperature measurement)"
Endress+Hauser23
Page 24
InstallationProline Prowirl C 200 HART
Q
1
2
3
The second temperature measurement is taken using a separate temperature sensor. The
measuring device reads in this value via a communication interface.
• In the case of saturated steam delta heat measurements, the Prowirl 200 must be
installed on the steam side.
• In the case of water delta heat measurements, the Prowirl 200 can be installed on the
cold or warm side.
In the case of saturated steam delta heat measurements, the value 0 bar abs. must be
set in the Fixed process pressure parameter (→ 71) in order for the measuring
device to calculate on the saturated steam curve. The current input can then be used
to read in the temperature.
A0019209
7Layout for delta heat measurement of saturated steam and water
Observe the following minimum head clearance: 222 mm (8.74 in)
For information on the weather protection cover, see → 159
6.2 Mounting the measuring device
6.2.1 Required tools
For transmitter
• For turning the transmitter housing: Open-ended wrench8 mm
• For opening the securing clamps: Allen key3 mm
For sensor
For flanges and other process connections: Corresponding mounting tools
6.2.2 Preparing the measuring device
1.Remove all remaining transport packaging.
24Endress+Hauser
Page 25
Proline Prowirl C 200 HARTInstallation
2.Remove any protective covers or protective caps present from the sensor.
3.Remove stick-on label on the electronics compartment cover.
6.2.3 Mounting the sensor
WARNING
L
Danger due to improper process sealing!
Ensure that the inside diameters of the gaskets are greater than or equal to that of the
‣
process connections and piping.
Ensure that the gaskets are clean and undamaged.
‣
Install the gaskets correctly.
‣
1.Ensure that the direction of the arrow on the sensor matches the flow direction of
the medium.
2.To ensure compliance with device specifications, install the measuring device
between the pipe flanges in a way that it is centered in the measurement section.
3.Install the measuring device or turn the transmitter housing so that the cable entries
do not point upwards.
6.2.4 Mounting the transmitter of the remote version
CAUTION
L
Ambient temperature too high!
Danger of electronics overheating and housing deformation.
Do not exceed the permitted maximum ambient temperature .
‣
If operating outdoors: Avoid direct sunlight and exposure to weathering, particularly in
‣
warm climatic regions.
CAUTION
L
Excessive force can damage the housing!
Avoid excessive mechanical stress.
‣
The transmitter of the remote version can be mounted in the following ways:
• Wall mounting
• Pipe mounting
A0013964
Endress+Hauser25
Page 26
InstallationProline Prowirl C 200 HART
80 (3.15)
80 (3.15)
19 (0.6)
! 8.6 (0.39)
M 8
! 20…70
(! 0.79 to 2.75)
1
4 x
SW 13
Wall mounting
A0019864
8Engineering unit mm (in)
1.Drill the holes.
2.Insert wall plugs into the drilled holes.
3.Screw in the securing screws slightly at first.
4.Fit the transmitter housing over the securing screws and mount in place.
5.Tighten the securing screws.
Post mounting
A0019862
9Engineering unit mm (in)
1Post retainer kit for post mounting
6.2.5 Turning the transmitter housing
To provide easier access to the connection compartment or display module, the transmitter
housing can be turned.
26Endress+Hauser
Page 27
Proline Prowirl C 200 HARTInstallation
max.350°
8mm
8mm
+
E
–
1
3mm
A0013713
1.Release the fixing screw.
2.Turn the housing to the desired position.
3.Firmly tighten the securing screw.
6.2.6 Turning the display module
The display module can be turned to optimize display readability and operability.
1.Loosen the securing clamp of the electronics compartment cover using an Allen key.
2.Unscrew cover of the electronics compartment from the transmitter housing.
3.Optional: pull out the display module with a gentle rotational movement.
4.Rotate the display module into the desired position: Max. 8 × 45° in each direction.
5.Without display module pulled out:
Allow display module to engage at desired position.
6.With display module pulled out:
Feed the cable into the gap between the housing and main electronics module and
plug the display module into the electronics compartment until it engages.
7.Reverse the removal procedure to reassemble the transmitter.
A0013905
6.3 Post-installation check
Is the device undamaged (visual inspection)?
Endress+Hauser27
Page 28
InstallationProline Prowirl C 200 HART
Does the measuring device conform to the measuring point specifications?
For example:
• Process temperature
• Process pressure (refer to the section on "Pressure-temperature ratings" in the "Technical
Information" document )
• Ambient temperature
• Measuring range → 167
Has the correct orientation for the sensor been selected → 19?
• According to sensor type
• According to medium temperature
• According to medium properties (outgassing, with entrained solids)
Does the arrow on the sensor nameplate match the direction of flow of the fluid through the
piping → 19?
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected from precipitation and direct sunlight?
Are the securing screw and securing clamp tightened securely?
28Endress+Hauser
Page 29
Proline Prowirl C 200 HARTElectrical connection
7 Electrical connection
The measuring device does not have an internal circuit breaker. For this reason,
assign the measuring device a switch or power-circuit breaker so that the power
supply line can be easily disconnected from the mains.
7.1 Connection conditions
7.1.1 Required tools
• For cable entries: Use corresponding tools
• For securing clamp: Allen key 3 mm
• Wire stripper
• When using stranded cables: crimping tool for ferrule
• For removing cables from terminal: flat blade screwdriver ≤3 mm (0.12 in)
7.1.2 Connecting cable requirements
The connecting cables provided by the customer must fulfill the following requirements.
Electrical safety
In accordance with applicable federal/national regulations.
Permitted temperature range
• –40 °C (–40 °F) to +80 °C (+176 °F)
• Minimum requirement: cable temperature range ≥ ambient temperature +20 K
Signal cable
Current output
• For 4-20 mA: standard installation cable is sufficient.
• For 4-20 mA HART: Shielded cable recommended. Observe grounding concept of the
plant.
Pulse/frequency/switch output
Standard installation cable is sufficient.
Current input
Standard installation cable is sufficient.
Connecting cable for remote version
Connecting cable (standard)
Standard cable
Flame resistanceAccording to DIN EN 60332-1-2
Oil-resistanceAccording to DIN EN 60811-2-1
ShieldingGalvanized copper-braid, opt. density approx. 85%
Cable length5 m (16 ft), 10 m (32 ft), 20 m (65 ft), 30 m (98 ft)
Operating temperatureWhen mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
2 × 2 × 0.34 mm2 (22 AWG) PVC cable with common shield (2 pairs, pairstranded)
can move freely: –25 to +105 °C (–13 to +221 °F)
Endress+Hauser29
Page 30
Electrical connectionProline Prowirl C 200 HART
Connecting cable (reinforced)
Cable, reinforced
Flame resistanceAccording to DIN EN 60332-1-2
Oil-resistanceAccording to DIN EN 60811-2-1
ShieldingGalvanized copper-braid, opt. density approx. 85%
Strain relief and
reinforcement
Cable length5 m (16 ft), 10 m (32 ft), 20 m (65 ft), 30 m (98 ft)
Operating temperatureWhen mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable
2 × 2 × 0.34 mm2 (22 AWG) PVC cable with common shield (2 pairs, pairstranded) and additional steel-wire braided sheath
Steel-wire braid, galvanized
can move freely: –25 to +105 °C (–13 to +221 °F)
Cable diameter
• Cable glands supplied:
M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• Plug-in spring terminals for device version without integrated overvoltage protection:
wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG)
• Screw terminals for device version with integrated overvoltage protection: wire crosssections 0.2 to 2.5 mm2 (24 to 14 AWG)
30Endress+Hauser
Page 31
Proline Prowirl C 200 HARTElectrical connection
–
4
+
1
–
2
+
3
1
2
4
–
6
+
5
3
+
1
–
2
–
4
+
3
–
6
+
5
3
1
2
4
7.1.3 Terminal assignment
Transmitter
4-20 mA HART connection version with additional inputs and outputs
A0020738
Maximum number of terminals
Terminals 1 to 6:
Without integrated overvoltage protection
1
Output 1 (passive): supply voltage and signal transmission
2
Output 2 (passive): supply voltage and signal transmission
3
Input (passive): supply voltage and signal transmission
4
Ground terminal for cable shield
Order code for "Output"Terminal numbers
Output 1Output 2Input
1 (+)2 (-)3 (+)4 (-)5 (+)6 (-)
Option A4-20 mA HART (passive)--
Option B
Option C
Option D
1)
1)
1) 2)
4-20 mA HART (passive)
4-20 mA HART (passive) 4-20 mA analog (passive)-
4-20 mA HART (passive)
Maximum number of terminals for order code for
"Accessory mounted", option NA "Overvoltage
protection"
• Terminals 1 to 4:
With integrated overvoltage protection
• Terminals 5 to 6:
Without integrated overvoltage protection
Pulse/frequency/switch
output (passive)
Pulse/frequency/switch
output (passive)
A0020739
-
4-20 mA current input
(passive)
1)Output 1 must always be used; output 2 is optional.
2)The integrated overvoltage protection is not used with option D: Terminals 5 and 6 (current input) are not
protected against overvoltage.
Remote version
In the case of the remote version, the sensor and transmitter are mounted separately from
one another and connected by a connecting cable. The sensor is connected via the
Endress+Hauser31
Page 32
Electrical connectionProline Prowirl C 200 HART
4
1
2
3
1
2
+
–
connection housing while the transmitter is connected via the connection compartment of
the wall holder unit.
The way the transmitter wall holder is connected depends on the measuring device
approval and the version of the connecting cable used.
Connection is only possible via terminals:
• For approvals Ex n, Ex tb and cCSAus Div. 1
• If a reinforced connecting cable is used
The connection is via an M12 connector:
• For all other approvals
• If the standard connecting cable is used
Connection to the connection housing of the sensor is always via the terminals
(tightening torque for terminals: 1.2 to 1.7 Nm).
A0019335
10Terminals for connection compartment in the transmitter wall holder and the sensor connection housing
1Terminals for connecting cable
2Grounding via the cable strain relief
Terminal numberAssignmentCable color
Connecting cable
1Supply voltageBrown
2GroundingWhite
3RS485 (+)Yellow
4RS485 (–)Green
7.1.4 Requirements for the supply unit
Supply voltage
Transmitter
An external power supply is required for each output.
The following supply voltage values apply for the outputs available:
Supply voltage for a compact version without a local display
1)
Order code for "Output"Minimum
terminal voltage
Option A: 4-20 mA HART≥ DC 12 VDC 35 V
32Endress+Hauser
Option B: 4-20 mA HART, pulse/
frequency/switch output
≥ DC 12 VDC 35 V
2)
Maximum
terminal voltage
Page 33
Proline Prowirl C 200 HARTElectrical connection
0
100
200
300
400
500
121416
1820
22242628
U [V]
s
R [ ]bW
1.11.21
30323436
35
Order code for "Output"Minimum
terminal voltage
Option C: 4-20 mA HART + 4-20 mA
analog
Option D: 4-20 mA HART, pulse/
frequency/switch output, 4-20 mA current
3)
input
1)In event of external supply voltage of the power supply unit with load
2)The minimum terminal voltage increases if local operation is used: see the following table
3)Voltage drop 2.2 to 3 V for 3.59 to 22 mA
≥ DC 12 VDC 30 V
≥ DC 12 VDC 35 V
2)
Maximum
terminal voltage
Increase in minimum terminal voltage
Local operation
Order code for "Display; Operation", option C:
Local operation SD02
Order code for "Display; Operation", option E:
Local operation SD03 with lighting
(backlighting not used)
Order code for "Display; Operation", option E:
Local operation SD03 with lighting
(backlighting used)
Increase in minimum
terminal voltage
+ DC 1 V
+ DC 1 V
+ DC 3 V
Load
Load for current output: 0 to 500 Ω, depending on the external supply voltage of the power
supply unit
Calculation of the maximum load
Depending on the supply voltage of the power supply unit (US), the maximum load (RB)
including line resistance must be observed to ensure adequate terminal voltage at the
device. In doing so, observe the minimum terminal voltage
• RB ≤ (US - U
term. min
): 0.022 A
• RB ≤ 500 Ω
11Load for a compact version without local operation
1Operating range
1.1 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with Ex i and option C "4-20 mA HART + 4-20 mA analog"
1.2 For order code for "Output", option A "4-20 mA HART"/option B "4-20 mA HART, pulse/frequency/switch
output" with non-Ex and Ex d
A0020417
Endress+Hauser33
Page 34
Electrical connectionProline Prowirl C 200 HART
Sample calculation
Supply voltage of the supply unit:
– US = 19 V
– U
Maximum load: RB ≤ (19 V - 13 V): 0.022 A = 273 Ω
= 12 V (measuring device) + 1 V (local operation without lighting) = 13 V
term. min
The minimum terminal voltage (U
(Verweisziel existiert nicht, aber @y.link.required='true').
) increases if local operation is used
term. min
7.1.5 Preparing the measuring device
1.Remove dummy plug if present.
2.NOTICE
Insufficient sealing of the housing!
Operational reliability of the measuring device could be compromised.
Use suitable cable glands corresponding to the degree of protection.
‣
If measuring device is delivered without cable glands:
Provide suitable cable gland for corresponding connecting cable .
3.If measuring device is delivered with cable glands:
Observe cable specification .
7.2 Connecting the measuring device
NOTICE
Limitation of electrical safety due to incorrect connection!
Have electrical connection work carried out by correspondingly trained specialists only.
‣
Observe applicable federal/national installation codes and regulations.
‣
Comply with local workplace safety regulations.
‣
For use in potentially explosive atmospheres, observe the information in the device-
‣
specific Ex documentation.
7.2.1 Connecting the remote version
WARNING
L
Risk of damaging the electronic components!
Ground the remote version and in doing so connect the sensor and transmitter to the
‣
same potential equalization.
Only connect the sensor to a transmitter with the same serial number.
‣
The following procedure (in the action sequence given) is recommended for the remote
version:
1.Mount the transmitter and sensor.
2.Connect the connecting cable.
34Endress+Hauser
Page 35
Proline Prowirl C 200 HARTElectrical connection
3 mm
3.Connect the transmitter.
The way the transmitter wall holder is connected depends on the measuring device
approval and the version of the connecting cable used.
Connection is only possible via terminals:
• For approvals Ex n, Ex tb and cCSAus Div. 1
• If a reinforced connecting cable is used
The connection is via an M12 connector:
• For all other approvals
• If the standard connecting cable is used
Connection to the connection housing of the sensor is always via the terminals
(tightening torque for terminals: 1.2 to 1.7 Nm).
Connecting the sensor connection housing
A0020410
A0020411
1.Loosen the securing clamp.
2.Unscrew the housing cover.
3.Guide the connecting cable through the cable entry and into the connection housing
(if using a connecting cable without an M12 device plug, use the shorter stripped end
of the connecting cable).
Endress+Hauser35
Page 36
Electrical connectionProline Prowirl C 200 HART
+
E
–
3 mm
4.NOTICE
Terminals tightened with an incorrect tightening torque.
Incorrect connection or damaged terminal.
Tighten the terminals with a tightening torque in the 1.2 to 1.7 Nm range.
‣
Wire the connecting cable:
Terminal 1 = brown cable
Terminal 2 = white cable
Terminal 3 = yellow cable
Terminal 4 = green cable
5.Connect the cable shield via the cable strain relief.
6.Reverse the removal procedure to reassemble the transmitter.
Connection to the wall holder of the transmitter
Connecting the transmitter via plug
Connect the plug.
‣
Connecting the transmitter via terminals
A0020412
A0020404
36Endress+Hauser
Page 37
Proline Prowirl C 200 HARTElectrical connection
8 mm
TX 10
~15°
A0020405
A0020406
A0020407
Endress+Hauser37
Page 38
Electrical connectionProline Prowirl C 200 HART
A0020409
1.Loosen the securing clamp of the transmitter housing.
2.Loosen the securing clamp of the electronics compartment cover.
3.Unscrew the electronics compartment cover.
4.Pull out the display module with a gentle rotational movement. To make it easier to
access the lock switch, attach the display module to the edge of the electronics
compartment.
5.Loosen the locking screw of the transmitter housing.
6.Turn the transmitter housing to the right until the mark and lift it up. The connection
board of the wall housing is connected to the electronics board of the transmitter via
a signal cable. Pay attention to the signal cable when lifting the transmitter housing!
7.Disconnect the signal cable from the connection board of the wall housing by
pressing in the locking clip on the connector.
8.Remove the transmitter housing.
9.Guide the connecting cable through the cable entry and into the connection housing
(if using a connecting cable without an M12 device plug, use the shorter stripped end
of the connecting cable).
10. Wire the connecting cable:
Terminal 1 = brown cable
Terminal 2 = white cable
Terminal 3 = yellow cable
Terminal 4 = green cable
11. Connect the cable shield via the cable strain relief.
12. Reverse the removal procedure to reassemble the transmitter.
7.2.2 Connecting the transmitter
38Endress+Hauser
Page 39
Proline Prowirl C 200 HARTElectrical connection
10(0.4)
mm(in)
20 mm3mm
mm (in)
213 4
3 (0.12)
Connection via terminals
A0013836
1.Loosen the securing clamp of the connection compartment cover.
2.Unscrew the connection compartment cover.
3.Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4.Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
5.Connect the cable in accordance with the terminal assignment . For HART
communication: when connecting the cable shielding to the ground terminal, observe
the grounding concept of the facility.
6.Firmly tighten the cable glands.
7.
WARNING
L
Housing degree of protection may be voided due to insufficient sealing of the
housing.
Screw in the screw without using any lubricant. The threads on the cover are
‣
coated with a dry lubricant.
Reverse the removal procedure to reassemble the transmitter.
Removing a cable
A0013835
Endress+Hauser39
Page 40
Electrical connectionProline Prowirl C 200 HART
2
3
4...20 mA
41
+
-
5
+
-
To remove a cable from the terminal, use a flat-blade screwdriver to push the slot
‣
between the two terminal holes while simultaneously pulling the cable end out of the
terminal.
7.2.3 Ensuring potential equalization
Requirements
Please consider the following to ensure correct measurement:
• Same electrical potential for the fluid and sensor
• Remote version: same electrical potential for the sensor and transmitter
• Company-internal grounding concepts
• Pipe material and grounding
For devices intended for use in hazardous locations, please observe the guidelines in
the Ex documentation (XA).
7.3 Special connection instructions
7.3.1 Connection examples
Current output 4-20 mA HART
A0015511
12Connection example for 4-20 mA HART current output (passive)
1Automation system with current input (e.g. PLC)
2Active barrier for power supply with integrated resistor for HART communication (≥ 250 Ω)(e.g. RN221N)
Connection for HART operating devices → 182
Observe the maximum load → 33
3Cable shield, observe cable specifications
4Analog display unit: observe maximum load → 33
5Transmitter
40Endress+Hauser
Page 41
Proline Prowirl C 200 HARTElectrical connection
1
+
_
12345
2
+
–
+
–
3
1
+
_
+
_
2
+
_
3
2
+
-
4
+
-
31
Pulse/frequency output
A0016801
13Connection example for pulse/frequency output (passive)
1Automation system with pulse/frequency input (e.g. PLC)
2Power supply
3Transmitter: observe input values → 170
Switch output
14Connection example for switch output (passive)
1Automation system with switch input (e.g. PLC)
2Power supply
3Transmitter: observe input values
Current input
15Connection example for 4-20 mA current input
1Control system (e.g. PLC)
2Power supply
3External measuring device (for reading in pressure or temperature, for instance)
4Transmitter: Observe input values → 168
A0016802
A0020741
Endress+Hauser41
Page 42
Electrical connectionProline Prowirl C 200 HART
3
4...20 mA
5
1
+
-
3
6
+
–
+
+
–
+
–
+
–
+
–
–
2
4
4
7
+
-
HART input
A0016029
16Connection example for HART input with a common negative
1Automation system with HART output (e.g. PLC)
2Resistor for HART communication (≥ 250 Ω): observe maximum load → 33
3Active barrier for power supply (e.g. RN221N)
4Cable shield, observe cable specifications
5Analog display unit: observe maximum load → 33
6Pressure transmitter (e.g. Cerabar M, Cerabar S): see requirements
7Transmitter
7.4 Ensuring the degree of protection
The measuring device fulfills all the requirements for the IP66/67 degree of protection,
Type 4X enclosure.
To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following
steps after the electrical connection:
1.Check that the housing seals are clean and fitted correctly. Dry, clean or replace the
seals if necessary.
2.Tighten all housing screws and screw covers.
3.Firmly tighten the cable glands.
4.To ensure that moisture does not enter the cable entry, route the cable so that it
loops down before the cable entry ("water trap").
5.Insert dummy plugs into unused cable entries.
A0013960
42Endress+Hauser
Page 43
Proline Prowirl C 200 HARTElectrical connection
7.5 Post-connection check
Are cables or the device undamaged (visual inspection)?
Do the cables comply with the requirements ?
Do the cables have adequate strain relief?
Are all the cable glands installed, firmly tightened and leak-tight? Cable run with "water trap"
→ 42 ?
Depending on the device version: are all the device plugs firmly tightened ?
Does the supply voltage match the specifications on the transmitter nameplate ?
Is the terminal assignment correct ?
If supply voltage is present, do values appear on the display module?
Are all housing covers installed and firmly tightened?
Is the securing clamp tightened correctly?
Endress+Hauser43
Page 44
Operation optionsProline Prowirl C 200 HART
1
23
45
S
C
8 Operation options
8.1 Overview of operating options
A0015607
1Local operation via display module
2Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
3Field Xpert SFX350 or SFX370
4Field Communicator 475
5Automation system (e.g. PLC)
44Endress+Hauser
Page 45
Proline Prowirl C 200 HARTOperation options
!
Expert
System
Sensor
Communication
Application
Diagnostics
Access status display
Output
Operating menu for experts
Language
OperatationLanguage
Parameter 1
Setup
Submenu 1
Submenu n
Device tag
Advanced setup
Enter access code
Parameter 1
Parameter n
Submenu 1
Submenu n
Diagnostics
Parameter 1
Parameter n
Submenu 1
Submenu n
Operating menu for operators and maintenances
Parameter n
Operator
Maintenance
Task-oriented
Function-oriented
Expert
Wizard 1 / Parameter 1
Wizard n / Parameter n
Parameter n
Intput
8.2 Structure and function of the operating menu
8.2.1 Structure of the operating menu
For an overview of the operating menu with menus and parameters
Endress+Hauser45
17Schematic structure of the operating menu
A0018237-EN
Page 46
Operation optionsProline Prowirl C 200 HART
8.2.2 Operating philosophy
The individual parts of the operating menu are assigned to certain user roles (operator,
maintenance etc.). Each user role contains typical tasks within the device lifecycle.
Contains all parameters for error detection and analyzing
process and device errors:
• Diagnostic list
Contains up to 5 currently pending diagnostic messages.
• Event logbook
Contains up to 20 or 100 (order option " Extended
HistoROM") event messages that have occurred.
• Device information
Contains information for identifying the device.
• Measured values
Contains all current measured values.
• Data logging
(Order option "Extended HistoROM")
Storage and visualization of up to 1000 measured values
• Heartbeat
The functionality of the device is checked on demand and the
verification results are documented.
• Simulation
Is used to simulate measured values or output values.
Expertfunction-oriented Tasks that require detailed knowledge
of the function of the device:
• Commissioning measurements under
difficult conditions
• Optimal adaptation of the
measurement to difficult conditions
• Detailed configuration of the
communication interface
• Error diagnostics in difficult cases
Contains all the parameters of the device and makes it possible
to access these parameters directly using an access code. The
structure of this menu is based on the function blocks of the
device:
• System
Contains all higher-order device parameters which do not
concern the measurement or the communication interface.
• Sensor
Configuration of the measurement.
• Input
Configuration of the input.
• Output
Configuration of the outputs.
• Communication
Configuration of the digital communication interface.
• Application
Configuration of the functions that go beyond the actual
measurement (e.g. totalizer).
• Diagnostics
Error detection and analysis of process and device errors and
for device simulation and Heartbeat Technology.
46Endress+Hauser
Page 47
Proline Prowirl C 200 HARTOperation options
X X X X X X XXX
4
2
1
3
5
l/h
1120.50
F
8.3 Access to the operating menu via the local display
8.3.1 Operational display
A0016502
1
Operational display
2
Device tag
3
Status area
4
Display area for measured values (4-line)
5
Operating elements → 52
Status area
The following symbols appear in the status area of the operational display at the top right:
• Status signals→ 138
– F: Failure
– C: Function check
– S: Out of specification
– M: Maintenance required
• Diagnostic behavior→ 139
–: Alarm
–: Warning
•: Locking (the device is locked via the hardware )
•: Communication (communication via remote operation is active)
Display area
In the display area, each measured value is prefaced by certain symbol types for further
description:
Measured variableMeasurement channel
number
↓↓↓
Example
Diagnostic behavior
Appears only if a diagnostics
event is present for this
measured variable.
Measured variables
SymbolMeaning
Volume flow
Endress+Hauser47
Page 48
Operation optionsProline Prowirl C 200 HART
4
2
1
3
5
/../Operation
0091-1
Access stat.disp
Operator
Locking status
Display
S
4
2
1
5
3
/../Curr. output 1
Assign curr.
Volume flow
Totalizer
The measurement channel number indicates which of the three totalizers is
displayed.
Output
The measurement channel number indicates which of the two current outputs is
displayed.
Measurement channel numbers
SymbolMeaning
Measurement channel 1 to 4
The measurement channel number is displayed only if more than one channel is present for the same measured
variable type (e.g. totalizer 1-3).
Diagnostic behavior
The diagnostic behavior pertains to a diagnostic event that is relevant to the displayed measured variable.
For information on the symbols → 139
The number and display format of the measured values can be configured via the
"Format display" parameter → 89. "Operation" menu → Display → Format
display
8.3.2 Navigation view
In the submenuIn the wizard
A0013993-EN
1
Navigation view
2
Navigation path to current position
3
Status area
4
Display area for navigation
5
Operating elements → 52
Navigation path
The navigation path - displayed at the top left in the navigation view - consists of the
following elements:
A0016327-EN
• In the submenu:
Display symbol for menu
• In the wizard:
Display symbol for wizard
↓↓↓
Examples/ ../Display
Omission symbol for
operating menu levels in
between
/ ../Display
Name of current
• Submenu
• Wizard
• Parameter
48Endress+Hauser
Page 49
Proline Prowirl C 200 HARTOperation options
For more information about the menu icons, refer to the "Display area" section
→ 49
Status area
The following appears in the status area of the navigation view in the top right corner:
• Of the submenu
– The direct access code for the parameter you are navigating to (e.g. 0022-1)
– If a diagnostic event is present, the diagnostic behavior and status signal
• In the wizard
If a diagnostic event is present, the diagnostic behavior and status signal
• For information on the diagnostic behavior and status signal → 138
• For information on the function and entry of the direct access code → 54
Display area
Menus
SymbolMeaning
Operation
Appears:
• In the menu next to the "Operation" selection
• At the left in the navigation path in the "Operation" menu
Setup
Appears:
• In the menu next to the "Setup" selection
• At the left in the navigation path in the "Setup" menu
Diagnostics
Appears:
• In the menu next to the "Diagnostics" selection
• At the left in the navigation path in the "Diagnostics" menu
Expert
Appears:
• In the menu next to the "Expert" selection
• At the left in the navigation path in the "Expert" menu
Submenus, wizards, parameters
SymbolMeaning
Submenu
Wizard
Parameters within a wizard
No display symbol exists for parameters in submenus.
Locking
SymbolMeaning
Parameter locked
When displayed in front of a parameter name, indicates that the parameter is locked.
• By a user-specific access code
• By the hardware write protection switch
Endress+Hauser49
Page 50
Operation optionsProline Prowirl C 200 HART
3
2
1
4
3
4
0
12
9
5
6
8
7
20
…
0
9
.
–
Wizard operation
SymbolMeaning
Switches to the previous parameter.
Confirms the parameter value and switches to the next parameter.
Opens the editing view of the parameter.
8.3.3 Editing view
Numeric editorText editor
A0013941 A0013999
1
Editing view
2
Display area of the entered values
3
Input mask
4
Operating elements → 52
Input mask
The following input symbols are available in the input mask of the numeric and text editor:
Numeric editor
SymbolMeaning
Selection of numbers from 0 to 9.
Inserts decimal separator at the input position.
Inserts minus sign at the input position.
Confirms selection.
Moves the input position one position to the left.
Exits the input without applying the changes.
Clears all entered characters.
50Endress+Hauser
Page 51
Proline Prowirl C 200 HARTOperation options
Aa1
XYZ
ABC
_
…
xyz
abc
_
…
~&
"'^
_
…
_
Text editor
SymbolMeaning
Toggle
• Between upper-case and lower-case letters
• For entering numbers
• For entering special characters
Selection of letters from A to Z.
Selection of letters from a to z.
Selection of special characters.
Confirms selection.
Switches to the selection of the correction tools.
Exits the input without applying the changes.
Clears all entered characters.
Correction symbols under
SymbolMeaning
Clears all entered characters.
Moves the input position one position to the right.
Moves the input position one position to the left.
Deletes one character immediately to the left of the input position.
Endress+Hauser51
Page 52
Operation optionsProline Prowirl C 200 HART
+
+
+
++
8.3.4 Operating elements
KeyMeaning
Minus key
In a menu, submenu
Moves the selection bar upwards in a choose list.
With a Wizard
Confirms the parameter value and goes to the previous parameter.
With a text and numeric editor
In the input mask, moves the selection bar to the left (backwards).
Plus key
In a menu, submenu
Moves the selection bar downwards in a choose list.
With a Wizard
Confirms the parameter value and goes to the next parameter.
With a text and numeric editor
Moves the selection bar to the right (forwards) in an input screen.
Enter key
For operational display
• Pressing the key briefly opens the operating menu.
• Pressing the key for 2 s opens the context menu.
In a menu, submenu
• Pressing the key briefly:
– Opens the selected menu, submenu or parameter.
– Starts the wizard.
– If help text is open, closes the help text of the parameter.
• Pressing the key for 2 s for parameter:
If present, opens the help text for the function of the parameter.
With a Wizard
Opens the editing view of the parameter.
With a text and numeric editor
• Pressing the key briefly:
– Opens the selected group.
– Carries out the selected action.
• Pressing the key for 2 s confirms the edited parameter value.
• Pressing the key briefly:
– Exits the current menu level and takes you to the next higher level.
– If help text is open, closes the help text of the parameter.
• Pressing the key for 2 s returns you to the operational display ("home position").
With a Wizard
Exits the wizard and takes you to the next higher level.
With a text and numeric editor
Closes the text or numeric editor without applying changes.
Minus/Enter key combination (press the keys simultaneously)
Reduces the contrast (brighter setting).
Plus/Enter key combination (press and hold down the keys simultaneously)
Increases the contrast (darker setting).
Minus/Plus/Enter key combination (press the keys simultaneously)
For operational display
Enables or disables the keypad lock (only SD02 display module).
8.3.5 Opening the context menu
Using the context menu, the user can call up the following menus quickly and directly from
the operational display:
52Endress+Hauser
Page 53
Proline Prowirl C 200 HARTOperation options
• Setup
• Conf. backup disp.
• Simulation
Calling up and closing the context menu
The user is in the operational display.
1.Press for 2 s.
The context menu opens.
A0016326-EN
2.Press + simultaneously.
The context menu is closed and the operational display appears.
Calling up the menu via the context menu
1.Open the context menu.
2.Press to navigate to the desired menu.
3.Press to confirm the selection.
The selected menu opens.
Endress+Hauser53
Page 54
Operation optionsProline Prowirl C 200 HART
X X X X X XXXX
20.50
0104-1
2 s
0091-1
0098-1
0098-1
0098-1
X X X X X XXXX
10.50
19.00
XX
XX
XXXX
Operation
Operation
Setup
Main menu
English
Main menu
Format display
/ ../Display
Contrast display
Display intervall
1 value, max.
Setup
Access stat.disp
/ ../Operation
Display
Locking status
1 value, max.
/ ../Format display
2 values
Val. large+2val.
Bargr. + 1 value
Locking status
/ ../Operation
Display
1 value, max.
/ ../Format display
2 values
Val. large+2val.
Bargr. + 1 value
Operator
Language
Language
8.3.6 Navigating and selecting from list
Different operating elements are used to navigate through the operating menu. The
navigation path is displayed on the left in the header. Icons are displayed in front of the
individual menus. These icons are also shown in the header during navigation.
For an explanation of the navigation view with symbols and operating elements
→ 48
Example: Setting the number of displayed measured values to "2 values"
54Endress+Hauser
8.3.7 Calling the parameter directly
A parameter number is assigned to every parameter to be able to access a parameter
directly via the onsite display. Entering this access code in the Direct access parameter
calls up the desired parameter directly.
The direct access code consists of a 4-digit number and the channel number, which
identifies the channel of a process variable: e.g. 0914-1. In the navigation view, this
appears on the right-hand side in the header of the selected parameter.
A0017223
1Direct access code
Note the following when entering the direct access code:
• The leading zeros in the direct access code do not have to be entered.
Example: Input of "914" instead of "0914"
• If no channel number is entered, channel 1 is jumped to automatically.
Example: Input of "0914" → Parameter Totalizer 1
• If a different channel is jumped to: Enter the direct access code with the corresponding
channel number.
Example: Input of "0914-2" → Parameter Totalizer 2
For the direct access codes of the individual parameters
8.3.8 Calling up help text
For some parameters, help texts exist, which the user can call up from the navigation view.
These briefly describe the function of the parameter and thus support fast and reliable
commissioning.
Calling up and closing the help text
The user is in the navigation view and the selection bar is on a parameter.
1.Press for 2 s.
The help text for the selected parameter opens.
A0014002-EN
18Example: Help text for parameter "Enter access code"
2.Press + simultaneously.
The help text is closed.
Endress+Hauser55
Page 56
Operation optionsProline Prowirl C 200 HART
3x
001-FT-101
DEFGHIJK
LMNO
PQRSTUVW
XYZ
Aa1@
ABC
001-FT-101
DEFGHIJK
LMNO
PQRSTUVW
XYZ
Aa1@
ABC
001-FT-101
DEFGHIJK
ABC
001-FT-10
DEFGHIJK
ABC
001-FT-10
DEFGHIJK
ABC
1x
001-FT-10
DEFGHIJK
LMNO
PQRSTUVW
XYZ
Aa1@
ABC
001-FT-10
DEFGHIJK
LMNO
PQRSTUVW
XYZ
Aa1@
ABC
001-FT-10
DEFGHIJK
ABC
A a 1
@
001-FT-10
DEFGHIJK
ABC
A a 1
@
001-FT-10
3456789
= + - *
/
[ ]
( )
< >
{ }
Aa1@
012
001-FT-10
3456789
012
0 1 2
001-FT-10
3456789
012
0 1 2
001-FT-102
3456789
012
012
001-FT-102
3456789
= + - *
/
[ ]
( )
< >
{ }
Aa1@
012
001-FT-102
3456789
012
012
001-FT-102
3456789
= + - *
/
[ ]
( )
< >
{ }
Aa1@
012
001-FT-102
3456789
012
012
001-FT-102
3456789
= + - *
/
[ ]
( )
< >
{ }
Aa1@
012
001-FT-102
1496-1
1x
2x
4x
2x
1x
001-FT-101
1496-1
Max.
Tag description
Ent. access code
Def. access code
/../Advanced setup
Tag description
/../Advanced setup
Ent. access code
Def. access code
8.3.9 Changing the parameters
For a description of the editing display - consisting of text editor and numeric editor with symbols → 50, for a description of the operating elements → 52
Example: Changing the tag name in the "Tag description" parameter from 001-FT-101 to
001-FT-102
56Endress+Hauser
A0014020-EN
Page 57
Proline Prowirl C 200 HARTOperation options
8.3.10 User roles and related access authorization
The two user roles "Operator" and "Maintenance" have different write access to the
parameters if the customer defines a user-specific access code. This protects the device
configuration via the local display from unauthorized access .
Access authorization to parameters
User roleRead accessWrite access
Without access code
(from the factory)
Operator--
Maintenance
1)Despite the defined access code, certain parameters can always be modified and thus are excepted from
the write protection, as they do not affect the measurement. Refer to the "Write protection via access code"
section
If an incorrect access code is entered, the user obtains the access rights of the "Operator"
role.
The user role with which the user is currently logged on is indicated by the Access
status display parameter. Navigation path: Operation → Access status display
With access codeWithout access code
(from the factory)
With access code
1)
8.3.11 Disabling write protection via access code
If the -symbol appears on the local display in front of a parameter, the parameter is
write-protected by a user-specific access code and its value cannot be changed at the
moment using the local display .
The locking of the write access via local operation can be disabled by entering the
customer-defined access code via the respective access option.
1.After you press , the input prompt for the access code appears.
2.Enter the access code.
The -symbol in front of the parameters disappears; all previously write-
protected parameters are now re-enabled.
8.3.12 Enabling and disabling the keypad lock
The keypad lock makes it possible to block access to the entire operating menu via local
operation. As a result, it is no longer possible to navigate through the operating menu or
change the values of individual parameters. Users can only read the measured values on
the operational display.
Local operation with mechanical push buttons (display module SD02)
Display module SD02: order characteristic "Display; Operation", option C
The keypad lock is switched on and off in the same way:
Switching on the keypad lock
The device is in the measured value display.
‣
Press the + + keys simultaneously.
The message Keylock on appears on the display: The keypad lock is switched on.
If the user attempts to access the operating menu while the keypad lock is active, the
message Keylock on appears.
Endress+Hauser57
Page 58
Operation optionsProline Prowirl C 200 HART
Switching off the keypad lock
The keypad lock is switched on.
‣
Press the + + keys simultaneously.
The message Keylock off appears on the display: The keypad lock is switched off.
Local operation with touch control (display module SD03)
Display module SD03: Order characteristic "Display; Operation", option E
The keypad lock is switched on and off via the context menu.
Switching on the keypad lock
The keypad lock is switched on automatically:
• Each time the device is restarted.
• If the device has not been operated for longer than one minute in the measured value
display.
1.The device is in the measured value display.
Press the key for longer than 2 seconds.
A context menu appears.
2.In the context menu, select the Keylock on option.
The keypad lock is switched on.
If the user attempts to access the operating menu while the keypad lock is active, the
message Keylock on appears.
Switching off the keypad lock
1.The keypad lock is switched on.
Press the key for longer than 2 seconds.
A context menu appears.
2.In the context menu, select the Keylock off option.
The keypad lock is switched off.
8.4 Access to the operating menu via the operating tool
The structure of the operating menu in the operating tools is the same as for operation via
the local display.
58Endress+Hauser
Page 59
Proline Prowirl C 200 HARTOperation options
12
3
+
E
–
8.4.1 Connecting the operating tool
Via service interface (CDI)
A0020545
1Service interface (CDI = Endress+Hauser Common Data Interface) of the measuring device
2Commubox FXA291
3Computer with "FieldCare" operating tool with COM DTM "CDI Communication FXA291"
8.4.2 Field Xpert SFX350, SFX370
Function scope
Field Xpert SFX350 and Field Xpert SFX370 are mobile computers for commissioning and
maintenance. They enable efficient device configuration and diagnostics for HART and
FOUNDATION fieldbus devices in the non-Ex area (SFX350, SFX370) and the Ex area
(SFX370).
For details, see Operating Instructions BA01202S
Source for device description files
See data → 62
8.4.3 FieldCare
Function scope
FDT-based plant asset management tool from Endress+Hauser. It can configure all smart
field devices in a system and helps you manage them. By using the status information, it is
also a simple but effective way of checking their status and condition.
Access is via:
• HART protocol
• Service interface CDI → 59
Endress+Hauser59
Page 60
Operation optionsProline Prowirl C 200 HART
6
5
32
1
Xxxxxx/…/…/
7
P
P
+
–
P
–
P
+
+
+
+
+
+
4
89
10
11
Xxxxxxx
GoodStatus:
Device tag:
Xxxxxxx
Device name:
Mass flow:
12.34
kg/h
Volume flow:
12.34
m /h³
Mass flow unit:
Volume flow unit:
kg/h
m /h³
Access status tooling
Operation
Setup
Xxxxxx
Mass flow unit
Volume flow unit
Select medium
Device tag
…
…
Advanced setup
Diagnostics
Expert
Maintenance
kg/h
m /h³
Xxxxxx
System units
Typical functions:
• Configuring parameters of transmitters
• Loading and saving device data (upload/download)
• Documentation of the measuring point
• Visualization of the measured value memory (line recorder) and event logbook
For additional information about FieldCare, see Operating Instructions BA00027S
and BA00059S
Source for device description files
See information → 62
Establishing a connection
For additional information, see Operating Instructions BA00027S and BA00059S
User interface
1Header
2Picture of device
3Device name
4Tag name
5Status area with status signal
6Display area for current measured values
7Edit toolbar with additional functions such as save/restore, event list and create documentation
8Navigation area with operating menu structure
9Working area
10 Range of action
11 Status area
60Endress+Hauser
A0021051-EN
Page 61
Proline Prowirl C 200 HARTOperation options
8.4.4 AMS Device Manager
Function scope
Program from Emerson Process Management for operating and configuring measuring
devices via HART protocol.
Source for device description files
See data → 62
8.4.5 SIMATIC PDM
Function scope
SIMATIC PDM is a standardized, manufacturer-independent program from Siemens for
the operation, configuration, maintenance and diagnosis of intelligent field devices via
HART protocol.
Source for device description files
See data → 62
8.4.6 Field Communicator 475
Function scope
Industrial handheld terminal from Emerson Process Management for remote
configuration and measured value display via HART protocol.
Source for device description files
See data → 62
Endress+Hauser61
Page 62
System integrationProline Prowirl C 200 HART
9 System integration
9.1 Overview of device description files
9.1.1 Current version data for the device
Firmware version01.02.00• On the title page of the Operating instructions
• On transmitter nameplate
• Firmware version parameter
"Diagnostics" menu → Device information
→ Firmware version
Release date of firmware version10.2014---
Manufacturer ID0x11Manufacturer ID parameter
"Diagnostics" menu → Device information
→ Manufacturer ID
Device type ID0x38Device type parameter
"Diagnostics" menu → Device information → Device
type
HART protocol revision7---
Device revision3• On transmitter nameplate
• Device revision parameter
"Diagnostics" menu → Device information → Device
revision
For an overview of the different firmware versions for the device → 153
9.1.2 Operating tools
The suitable device description file for the individual operating tools is listed in the table
below, along with information on where the file can be acquired.
Operating tool via
HART protocol
• Field Xpert SFX350
• Field Xpert SFX370
FieldCare• www.endress.com → Download Area
AMS Device Manager
(Emerson Process Management)
SIMATIC PDM
(Siemens)
Field Communicator 475
(Emerson Process Management)
Sources for obtaining device descriptions
Use update function of handheld terminal
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
www.endress.com → Download Area
www.endress.com → Download Area
Use update function of handheld terminal
9.2 Measured variables via HART protocol
The following measured variables (HART device variables) are assigned to the dynamic
variables at the factory:
Dynamic variablesMeasured variables
(HART device variables)
Primary dynamic variable (PV)Volume flow
Secondary dynamic variable (SV)Temperature
62Endress+Hauser
Page 63
Proline Prowirl C 200 HARTSystem integration
Dynamic variablesMeasured variables
(HART device variables)
Tertiary dynamic variable (TV)Totalizer 1
Quaternary dynamic variable (QV)Totalizer 2
The assignment of the measured variables to the dynamic variables can be modified and
assigned as desired via local operation and the operating tool using the following
parameters:
The following measured variables can be assigned to the dynamic variables:
Measured variables for PV (primary dynamic variable)
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Measured variables for SV, TV, QV (secondary, tertiary and quaternary dynamic
variable)
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
• Condensate mass flow
• Reynolds number
• Totalizer 1 to 3
• HART input
• Density
• Pressure
• Specific volume
• Degree of overheating
The range of options increases if the measuring device has one or more application
packages.
Device variables
The device variables are permanently assigned. A maximum of 8 device variables can be
transmitted:
• 0 = volume flow
• 1 = corrected volume flow
• 2 = Mass flow
• 3 = flow velocity
• 4 = temperature
Endress+Hauser63
Page 64
System integrationProline Prowirl C 200 HART
• 5 = calculated saturated steam pressure
• 6 = steam quality
• 7 = total mass flow
• 8 = energy flow
• 9 = heat flow difference
• 10 = condensate mass flow
• 11 = Reynolds number
• 12 = totalizer 1
• 13 = totalizer 2
• 14 = totalizer 3
9.3 Other settings
9.3.1 Burst mode functionality in accordance with HART 7
Specification
Navigation
"Expert" menu → Communication → HART output → Burst configuration → Burst
configuration 1 to 3
Burst configuration
‣
Burst configuration 1 to 3
‣
Burst mode 1 to 3
Burst command 1 to 3
Burst variable 0
Burst variable 1
Burst variable 2
Burst variable 3
Burst variable 4
Burst variable 5
Burst variable 6
Burst variable 7
Burst trigger mode
Burst trigger level
64Endress+Hauser
Page 65
Proline Prowirl C 200 HARTSystem integration
Min. update period
Max. update period
Parameter overview with brief description
ParameterDescriptionSelection / User entryFactory setting
Burst mode 1 to 3Activate the HART burst mode for burst
message X.
Burst command 1 to 3Select the HART command that is sent to the
HART master.
Burst variable 0• Volume flow
Burst variable 1See the Burst variable 0
Burst variable 2See the Burst variable 0
Burst variable 3See the Burst variable 0
Burst variable 4See the Burst variable 0
Burst variable 5See the Burst variable 0
Burst variable 6See the Burst variable 0
Burst variable 7See the Burst variable 0
• Off
• On
• Command 1
• Command 2
• Command 3
• Command 9
• Command 33
• Command 48
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
• Condensate mass flow
• Reynolds number
pressure
*
*
*
*
*
*
*
• Totalizer 1
• Totalizer 2
• Totalizer 3
• HART input
• Density
• Pressure
• Specific volume
• Degrees of superheat
*
*
*
*
• Percent Of Range
• Measured current
• Primary variable (PV)
• Secondary variable (SV)
• Tertiary variable (TV)
• Quaternary variable (QV)
• Not used
parameter.
parameter.
parameter.
parameter.
parameter.
parameter.
parameter.
Off
Command 2
Volume flow
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Endress+Hauser65
Page 66
System integrationProline Prowirl C 200 HART
ParameterDescriptionSelection / User entryFactory setting
Burst trigger modeSelect the event that triggers burst messageX.• Continuous
• Window
• Rising
• Falling
• On change
Burst trigger levelEnter the burst trigger value.
Together with the option selected in the
Burst trigger mode parameter the burst
trigger value determines the time of burst
message X.
Min. update periodPositive integer1000 ms
Max. update periodPositive integer2000 ms
*Visibility depends on order options or device settings
Positive floating-point number –
Continuous
66Endress+Hauser
Page 67
Proline Prowirl C 200 HARTCommissioning
X X X X X XXXX
20.50
Operation
Setup
Main menu
0104-1
Language
English
Español
Français
Language
English
Deutsch
Ã
0104-1
Ã
Español
Français
Language
English
Deutsch
0104-1
Betrieb
Setup
Hauptmenü
Sprache
Deutsch
0104-1
XXXX
10 Commissioning
10.1 Function check
Before commissioning the measuring device:
Make sure that the post-installation and post-connection checks have been performed.
‣
• "Post-installation check" checklist → 27
• "Post-connection check" checklist → 43
10.2 Switching on the measuring device
After a successful function check, switch on the measuring device.
‣
After a successful startup, the local display switches automatically from the startup
display to the operational display.
If nothing appears on the local display or a diagnostic message is displayed, refer to
the section on "Diagnostics and troubleshooting" → 136.
Endress+Hauser67
10.3 Setting the operating language
Factory setting: English or ordered local language
19Taking the example of the local display
A0013996
Page 68
CommissioningProline Prowirl C 200 HART
X X X X X XXXX
20.50
0104-1
XXXXXXXXX
XXXXXXXXX
XXXX
Operation
Setup
Diagnostic
Operation
Setup
Main menu
English
Main menu
Medium selection
/ ../Setup
Language
10.4 Configuring the measuring device
• The Setup menuwith its guided wizards contains all the parameters needed for standard
operation.
• Navigation to the Setup menu
A0014007-EN
20Taking the example of the local display
Overview of the wizards in the "Setup" menu
Setup
→ 69
→ 70
→ 72
→ 75
→ 78
→ 89
→ 91
Device tag
Medium selection
‣
Current input
‣
Current output 1 to 2
‣
Pulse/frequency/switch output
‣
Display
‣
Output conditioning
‣
Low flow cut off
68Endress+Hauser
10.4.1 Defining the tag name
To enable fast identification of the measuring point within the system, you can enter a
unique designation using the Device tag parameter and thus change the factory setting.
‣
Advanced setup
‣
→ 92
→ 94
Page 69
Proline Prowirl C 200 HARTCommissioning
1
XXXXXXXXX
A0013375
21Header of the operational display with tag name
1Device tag
• The number of characters displayed depends on the characters used.
• Enter the tag name in the "FieldCare" operating tool → 60
Navigation
"Setup" menu → Device tag
Parameter overview with brief description
ParameterDescriptionUser entryFactory setting
Device tagEnter the name for the measuring point.Max. 32 characters such as
letters, numbers or special
characters (e.g. @, %, /).
Prowirl
Endress+Hauser69
Page 70
CommissioningProline Prowirl C 200 HART
End of wizard
Select
medium
Liquid
Gas
Steam
Select
gas type
Select
liquid type
Air
Natural
gas
Enthalpy calc.
Density calc.
User-spec.
gas
Gas
mixture
Single
gas
Water
LPG
User-spec.
liquid
Fixed process pressure
Enthalpy type
10.4.2 Selecting and setting the medium
The Medium selection wizard guides you systematically through all the parameters that
have to be configured for selecting and setting the medium.
Navigation
"Setup" menu → Medium selection
Structure of the wizard
A0020776-EN
22"Medium selection" wizard in the "Setup" menu
Parameter overview with brief description
ParameterPrerequisiteDescriptionSelection / User
Select medium–Select medium type.• Gas
Select gas typeThe following conditions are
met:
• Order code
– "Sensor version", option
"Mass flow"
– "Application package",
option "Air + Industrial
gases" or option "Natural
gas"
• The Gas option is selected in
the Select medium
parameter.
70Endress+Hauser
entry
• Liquid
• Steam
Select measured gas type.• Single gas
• Gas mixture
• Air
• Natural gas
• User-specific gas
Factory setting
Steam
User-specific gas
Page 71
Proline Prowirl C 200 HARTCommissioning
ParameterPrerequisiteDescriptionSelection / User
Select liquid typeThe following conditions are
met:
• Order code for "Sensor
version", option "Mass flow"
• The Liquid option is
selected in the Selectmedium parameter.
Select steam typeThe following conditions are
met:
• Order code for "Sensor
version", option "Mass flow
(integrated temperature
measurement)"
• In the Select medium
parameter, the Steam
option is selected.
Fixed process pressureThe following conditions are
met:
• Order code for "Sensor
version", option "Mass flow
(integrated temperature
measurement)"
• In the External value
parameter (→ 73), the
Pressure option is not
selected.
Enthalpy calculationThe following conditions are
met:
• Order code
– "Sensor version", option
"Mass flow (integrated
temperature
measurement)"
– "Application package",
option "Natural gas"
• In the Select medium
parameter, the Gas option is
selected and in the Select
gas type parameter, the
Natural gas option is
selected.
entry
Select measured liquid type.• Water
• LPG ((liquefied
petroleum gas))
• User-specific liquid
Select measured steam type.• Wet steam
• Superheated steam
• Saturated steam
Enter fixed value for process
pressure.
Dependency
The unit is taken from the
Pressure unit parameter
For detailed information
on the calculation of the
measured variables with
steam: → 165
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and Wet Steam
Measurement
→ 186 application
package.
Select the norm the enthalpy
calculation is based on.
0 to 250 bar abs.0 bar abs.
• AGA5
• ISO 6976
Factory setting
Water
Saturated steam
AGA5
Endress+Hauser71
Page 72
CommissioningProline Prowirl C 200 HART
ParameterPrerequisiteDescriptionSelection / User
Density calculationThe following conditions are
met:
• In the Select medium
parameter, the Gas option is
selected.
• In the Select gas type
parameter, the Natural gas
option is selected.
Enthalpy typeThe following conditions are
met:
• In the Select gas type
parameter, the User-specific gas option is
selected.
Or
• In the Select liquid type
parameter, the User-specific liquid option is
selected.
10.4.3 Configuring the current input
The "Current input" submenu guides you systematically through all the parameters that
have to be set for configuring the current input.
The Fixed process pressure parameter is set to the value 0 bar abs. (ex works). In
this case, the measuring device ignores the pressure read in via the current input. For
the measuring device to use the external (read-in) pressure, a value > 0 bar abs. must
be entered in the Fixed process pressure parameter.
For a detailed description of how to calculate the mass flow and energy flow:
→ 164
Select the norm the density
calculation is based on.
Define which kind of enthalpy
is used.
entry
• AGA Nx19
• ISO 12213- 2
• ISO 12213- 3
• Heat
• Calorific value
Factory setting
AGA Nx19
Heat
Navigation
"Setup" menu → Current input
Structure of the submenu
Current input
‣
External value
Pressure unit
Atmospheric pressure
Temperature unit
Density unit
Current span
4 mA value
20 mA value
72Endress+Hauser
Page 73
Proline Prowirl C 200 HARTCommissioning
Failure mode
Failure value
Parameter overview with brief description
ParameterPrerequisiteDescriptionSelection / User
External valueFor the following order code:
"Sensor version", option "Mass
flow"
Pressure unitFor the following order code:
"Sensor version", option "Mass
flow"
Atmospheric pressure–Enter atmospheric pressure
Temperature unit–Select temperature unit.
Density unit–Select density unit.
Assign variable from external
device to process variable.
For detailed information
on the calculation of the
measured variables with
steam: → 165
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and Wet Steam
Measurement
→ 186 application
package.
Select process pressure unit.
Effect
The unit is taken from the:
• Calculated saturated steam
pressure
• Atmospheric pressure
• Maximum value
• Fixed process pressure
• Pressure
• Reference pressure
value to be used for pressure
correction.
Effect
The selected unit applies for:
• Temperature
• Maximum value
• Minimum value
• Average value
• Maximum value
• Minimum value
• Maximum value
• Minimum value
• 2nd temperature delta heat
• Fixed temperature
• Reference combustion
temperature
• Reference temperature
• Saturation temperature
Effect
The selected unit applies for:
• Output
• Simulation process variable
Factory setting
entry
• Off
• Pressure
• Relative pressure
• Density
• Temperature
• 2nd temperature
delta heat
Unit choose listCountry-specific:
0 to 250 bar1.01325 bar
Unit choose listCountry-specific:
Unit choose listCountry-specific:
Off
• bar
• psi
• °C
• °F
• kg/m³
• lb/ft³
Endress+Hauser73
Page 74
CommissioningProline Prowirl C 200 HART
ParameterPrerequisiteDescriptionSelection / User
entry
Current span–Select current range for
process value output and
upper/lower level for alarm
signal.
4 mA value–Enter 4 mA value.Signed floating-point
20 mA value–Enter 20 mA value.Signed floating-point
Failure mode–Define input behavior in alarm
condition.
Failure valueIn the Failure mode
parameter, the Defined value
option is selected.
Enter value to be used by the
device if input value from
external device is missing.
• 4...20 mA
• 4...20 mA NAMUR
• 4...20 mA US
number
number
• Alarm
• Last valid value
• Defined value
Signed floating-point
number
Factory setting
Country-specific:
• 4...20 mA NAMUR
• 4...20 mA US
0
Depends on country
and nominal
diameter
Alarm
0
74Endress+Hauser
Page 75
Proline Prowirl C 200 HARTCommissioning
Assign current
output
4...20 mA
NAMUR
4...20 mA
US
4...20 mAFixed current
4 mA value
20 mA value
Failure mode
Min.Defined value
Failure current
Current span
Mass flow
Steam qualityTemperature
Volume flow
Flow velocity
Total mass flow
Calculated saturat.
steam pressure
Corrected volume
flow
Energy flow
Heat flow
difference
…
End of wizard
Off
10.4.4 Configuring the current output
The "Current output 1 to 2" wizard guides you systematically through all the parameters
that have to be set for configuring the specific current output.
Navigation
"Setup" menu → Current output 1 to 2
Structure of the wizard
23"Current output 1 to 2" wizard in the "Setup" menu
The selected unit applies for:
Corrected volume flow
Temperature unit–Select temperature unit.
Effect
The selected unit applies for:
• Temperature
• Maximum value
• Minimum value
• Average value
• Maximum value
• Minimum value
• Maximum value
• Minimum value
• 2nd temperature delta heat
• Fixed temperature
• Reference combustion
temperature
• Reference temperature
• Saturation temperature
Energy flow unitFor the following order code:
"Sensor version", option "Mass
flow"
Select energy flow unit.
Result
The selected unit applies for:
• Outputs
• Low flow cut off
Factory setting
entry
• Off
Volume flow
• Volume flow
• Corrected volume
flow
• Mass flow
• Flow velocity
• Temperature
• Calculated
saturated steam
*
pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow
difference
*
*
*
*
Unit choose listCountry-specific:
• kg/h
• lb/min
Unit choose listCountry-specific:
• m³/h
• ft³/min
Unit choose listCountry-specific:
• Nm³/h
• Sft³/h
Unit choose listCountry-specific:
• °C
• °F
Unit choose listCountry-specific:
• kW
• Btu/h
76Endress+Hauser
Page 77
Proline Prowirl C 200 HARTCommissioning
ParameterPrerequisiteDescriptionSelection / User
Pressure unitFor the following order code:
"Sensor version", option "Mass
flow"
Select process pressure unit.
Effect
The unit is taken from the:
• Calculated saturated steam
pressure
• Atmospheric pressure
• Maximum value
• Fixed process pressure
• Pressure
• Reference pressure
Velocity unit–Select velocity unit.
Result
The selected unit applies for:
• Flow velocity
• Maximum value
Current span–Select current range for
process value output and
upper/lower level for alarm
signal.
4 mA valueIn the Current span parameter
Enter 4 mA value.Signed floating-point
(→ 77), one of the
following options is selected:
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
20 mA valueIn the Current span parameter
Enter 20 mA value.Signed floating-point
(→ 77), one of the
following options is selected:
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
Failure modeIn the Assign current output
parameter (→ 76), one of
Define output behavior in
alarm condition.
the following options is
selected:
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
pressure
*
*
*
*
*
In the Current span parameter
(→ 77), one of the
following options is selected:
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
Failure currentThe Defined value option is
selected in the Failure mode
Enter current output value in
alarm condition.
parameter.
Factory setting
entry
Unit choose listCountry-specific:
• bar
• psi
Unit choose listCountry-specific:
• m/s
• ft/s
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
Country-specific:
• 4...20 mA NAMUR
• 4...20 mA US
• Fixed current
Country-specific:
number
• 0 m³/h
• 0 ft³/min
Depends on country
number
and nominal
diameter
• Min.
Max.
• Max.
• Last valid value
• Actual value
• Defined value
3.59 to 22.5 mA22.5 mA
*Visibility depends on order options or device settings
Endress+Hauser77
Page 78
CommissioningProline Prowirl C 200 HART
Operating mode
Pulse
Assign pulse
output
Value per pulse
Mass flow
Volume flow
Total mass flow
Corrected
volume flow
Energy flow
Heat flow
difference
Volume unit
Corrected
volume unit
Energy unit
Mass unit
Off
Energy unit
Pulse width
Failure mode
Invert output signal
End of wizard
Operating mode
10.4.5 Configuring the pulse/frequency/switch output
The Pulse/frequency/switch output wizard guides you systematically through all the
parameters that can be set for configuring the selected output type.
Configuring the pulse output
Navigation
"Setup" menu → Pulse/frequency/switch output
Structure of the wizard for the pulse output
24"Pulse/frequency/switch output" wizard in the "Setup" menu: "Operating mode" parameter"Pulse" option
A0020792-EN
78Endress+Hauser
Page 79
Proline Prowirl C 200 HARTCommissioning
Parameter overview with brief description
ParameterPrerequisiteDescriptionSelection / User
Factory setting
entry
Operating mode–Define the output as a pulse,
frequency or switch output.
• Pulse
• Frequency
Pulse
• Switch
Assign pulse outputThe Pulse option is selected in
the Operating mode
parameter.
Select process variable for
pulse output.
• Off
• Volume flow
• Corrected volume
Volume flow
flow
• Mass flow
• Total mass flow
• Energy flow
• Heat flow
difference
*
*
*
Mass unit–Select mass unit.Unit choose listCountry-specific:
The selected unit applies for:
Corrected volume flow
Energy flow unitFor the following order code:
"Sensor version", option "Mass
flow"
Select energy flow unit.
Result
The selected unit applies for:
• Outputs
• Low flow cut off
Pressure unitFor the following order code:
"Sensor version", option "Mass
flow"
Select process pressure unit.
Effect
The unit is taken from the:
• Calculated saturated steam
pressure
• Atmospheric pressure
• Maximum value
• Fixed process pressure
• Pressure
• Reference pressure
Velocity unit–Select velocity unit.
Result
The selected unit applies for:
• Flow velocity
• Maximum value
Factory setting
entry
• Pulse
Pulse
• Frequency
• Switch
• Off
Off
• Volume flow
• Corrected volume
flow
• Mass flow
• Flow velocity
• Temperature
• Calculated
saturated steam
*
pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow
difference
*
*
*
*
Unit choose listCountry-specific:
• kg/h
• lb/min
Unit choose listCountry-specific:
• m³/h
• ft³/min
Unit choose listCountry-specific:
• Nm³/h
• Sft³/h
Unit choose listCountry-specific:
• kW
• Btu/h
Unit choose listCountry-specific:
• bar
• psi
Unit choose listCountry-specific:
• m/s
• ft/s
82Endress+Hauser
Page 83
Proline Prowirl C 200 HARTCommissioning
ParameterPrerequisiteDescriptionSelection / User
Temperature unit–Select temperature unit.
Effect
The selected unit applies for:
• Temperature
• Maximum value
• Minimum value
• Average value
• Maximum value
• Minimum value
• Maximum value
• Minimum value
• 2nd temperature delta heat
• Fixed temperature
• Reference combustion
temperature
• Reference temperature
• Saturation temperature
Minimum frequency valueThe Frequency option is
Enter minimum frequency.0 to 1000 Hz0 Hz
selected in the Operatingmode parameter, and one of
the following options is
selected in the Assignfrequency output parameter
(→ 82):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Maximum frequency valueThe Frequency option is
pressure
*
*
*
*
*
Enter maximum frequency.0 to 1000 Hz1000 Hz
selected in the Operatingmode parameter, and one of
the following options is
selected in the Assignfrequency output parameter
(→ 82):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
pressure
*
*
*
*
*
Factory setting
entry
Unit choose listCountry-specific:
• °C
• °F
Endress+Hauser83
Page 84
CommissioningProline Prowirl C 200 HART
ParameterPrerequisiteDescriptionSelection / User
Measuring value at minimum
frequency
The Frequency option is
selected in the Operatingmode parameter, and one of
the following options is
selected in the Assignfrequency output parameter
(→ 82):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
• Steam quality
• Total mass flow
• Energy flow
pressure
*
*
*
*
• Heat flow difference
Measuring value at maximum
frequency
The Frequency option is
selected in the Operatingmode parameter, and one of
the following options is
selected in the Assignfrequency output parameter
(→ 82):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
• Steam quality
• Total mass flow
• Energy flow
pressure
*
*
*
*
• Heat flow difference
Failure modeThe Frequency option is
selected in the Operatingmode parameter (→ 79),
and one of the following
options is selected in the
Assign frequency output
parameter (→ 82):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
• Steam quality
• Total mass flow
• Energy flow
pressure
*
*
*
*
• Heat flow difference
Factory setting
entry
Enter measured value for
minmum frequency.
Signed floating-point
number
Depends on country
and nominal
diameter
*
Enter measured value for
maximum frequency.
Signed floating-point
number
Depends on country
and nominal
diameter
*
Define output behavior in
alarm condition.
• Actual value
• Defined value
0 Hz
• 0 Hz
*
84Endress+Hauser
Page 85
Proline Prowirl C 200 HARTCommissioning
End of wizard
Operating
mode
Switch
Switch
out funct
Diag.
behavior
OffOn
Assign
diag. beh
Alarm
Alarm or
warning
Warning
Invert outp.sig.
ParameterPrerequisiteDescriptionSelection / User
Failure frequencyThe Frequency option is
selected in the Operating
Enter frequency output value
in alarm condition.
0.0 to 1250.0 Hz0.0 Hz
mode parameter (→ 79),
and one of the following
options is selected in the
Assign frequency output
parameter (→ 82):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
pressure
*
*
*
*
*
Invert output signal–Invert the output signal.• No
• Yes
*Visibility depends on order options or device settings
Configuring the switch output
Factory setting
entry
No
Navigation
"Setup" menu → Pulse/frequency/switch output
Structure of the wizard for the switch output
26"Pulse/frequency/switch output" wizard in the "Setup" menu: "Operating mode" parameter"Switch" option
(part 1)
Endress+Hauser85
A0017439-EN
Page 86
CommissioningProline Prowirl C 200 HART
Operating mode
Operating mode
Limit
Status
Assign limit
Assign status
Switch
Switch output
function
Switch-on value
Switch-off value
Switch-on delay
Switch-off delay
Failure mode
Inverted output signal
Ende of wizard
Steam
quality
Low flow cut
off
Volume
flow unit
Mass flow
unit
Corrected
vol. flow
Flow
velocity
Temp.
Calc. sat.
steam press.
Corr. vol.
flow unit
Velocity
unit
Energy
flow unit
Energy
flow
Total mass
flow
Mass flow
unit
Reynolds
number
Unit
totalizer
Mass flow
Volume
flow
Heat flow
difference
Totalizer
1/2/3
Temp.
unit
Pressure
unit
Energy
flow unit
Energy
flow unit
27"Pulse/frequency/switch output" wizard in the "Setup" menu: "Operating mode" parameter"Switch" option
(part 2)
Parameter overview with brief description
ParameterPrerequisiteDescriptionSelection / User
Operating mode–Define the output as a pulse,
Switch output functionThe Switch option is selected
in the Operating mode
parameter.
frequency or switch output.
Select function for switch
output.
entry
• Pulse
• Frequency
• Switch
• Off
• On
• Diagnostic
behavior
• Limit
• Status
A0020794-EN
Factory setting
Pulse
Off
86Endress+Hauser
Page 87
Proline Prowirl C 200 HARTCommissioning
ParameterPrerequisiteDescriptionSelection / User
Assign diagnostic behavior• The Switch option is
selected in the Operating
Select diagnostic behavior for
switch output.
mode parameter.
• The Diagnostic behavior
option is selected in the
Switch output function
parameter.
Assign limit• The Switch option is
selected in the Operating
Select process variable for limit
function.
mode parameter.
• The Limit option is selected
in the Switch outputfunction parameter.
Assign flow direction check• The Switch option is
selected in the Operating
Select process variable for flow
direction monitoring.
mode parameter.
• The Flow direction check
option is selected in the
Switch output function
parameter.
Assign status• The Switch option is
selected in the Operating
Select device status for switch
output.
mode parameter.
• The Status option is
selected in the Switchoutput function parameter.
output signal of the current
output to fluctuations in the
measured value.
Damping output 2The measuring device has a
second current output.
Damping output 2The measuring device has a
pulse/frequency/switch
output.
Set the reaction time of the
output signal of the second
current output to fluctuations
in the measured value.
Set the reaction time of the
output signal of the frequency
output to fluctuations in the
measured value.
10.4.8 Configuring the low flow cut off
The Low flow cut off wizard guides you systematically through all the parameters that
have to be set for configuring the low flow cut off.
0.0 to 999.9 s5.0 s
0 to 999.9 s1 s
0 to 999.9 s1 s
0 to 999.9 s1 s
92Endress+Hauser
Page 93
Proline Prowirl C 200 HARTCommissioning
Volume flow
Assign variable
Correct.vol.flow
Reynolds number
Off value
End of wizard
Off
On value
Mass flow
Navigation
"Setup" menu → Low flow cut off
Structure of the wizard
A0020775-EN
30"Low flow cut off" wizard in the "Setup" menu
Parameter overview with brief description
ParameterPrerequisiteDescriptionSelection / User
Assign process variable–Select process variable for low
flow cut off.
On value low flow cutoffOne of the following options is
selected in the Assign processvariable parameter (→ 93):
• Volume flow
• Corrected volume flow
• Mass flow
• Reynolds number
Off value low flow cutoffOne of the following options is
selected in the Assign processvariable parameter (→ 93):
• Volume flow
• Corrected volume flow
• Mass flow
• Reynolds number
*Visibility depends on order options or device settings
*
*
Enter on value for low flow cut
off.
Enter off value for low flow cut
off.
entry
• Off
• Volume flow
• Corrected volume
flow
• Mass flow
• Reynolds number
Positive floatingpoint number
0 to 100.0 %50 %
Off
*
0
Factory setting
Endress+Hauser93
Page 94
CommissioningProline Prowirl C 200 HART
X X X X X XXXX
20.50
0104-1
0092-1
****
XXXXXXXXX
XXXXXXXXX
XXXXXXXXX
XXXXXXXXX
XX
XX
Operatation
Setup
Diagnostic
Operatation
Setup
Main menu
English
Main menu
/ ../Setup
/ ../Setup
Advanced setup
Ent. access code
/ ../Advanced setup
Def. access code
Device tag
Language
Medium selection
10.5 Advanced settings
The Advanced setup submenu together with its submenus contains parameters for
specific settings.
Navigation to the "Advanced setup" submenu
31Taking the example of the local display
The number of submenus can vary depending on the device version. Some submenus
are not dealt with in the Operating Instructions. These submenus and the parameters
they contain are explained in the Special Documentation for the device.
Navigation
"Setup" menu → Advanced setup
Advanced setup
‣
Enter access code
System units
‣
Medium properties
‣
External compensation
‣
→ 95
→ 98
→ 112
A0014009-EN
94Endress+Hauser
Page 95
Proline Prowirl C 200 HARTCommissioning
Sensor adjustment
‣
Totalizer 1 to 3
‣
SIL confirmation
‣
Deactivate SIL
‣
Display
‣
Heartbeat setup
‣
Configuration backup display
‣
Administration
‣
10.5.1 Setting the system units
In the System units submenu the units of all the measured values can be set.