Enda ET2412, ET2412-230-08, ET2412-110-08, ET2412-012-08, ET2412-024-08 User guide

...
8680407715299
8 680 40 7 71 53 12
8 680 40 7 71 53 05
8 680 40 7 71 52 99
english
Read this document carefully before using this device. The guarantee will be expired by device demages if you don't attend to the directions in the user manual. Also we don't accept any compensations for personal injury, material damage or capital disadvantages.
ENDA 2412 ON/OFF HEAT CONTROLLER ET
Thank you for choosing ON/OFF Heat Controller.ENDA ET2412
77 x 35mm sized.
Single NTC sensor input. Zero point input shift. Selectable heating or cooling control for C1 relay output. A1 Relay output for alarm control. Selectable independent, deviation and band alarm types. In the case of sensor failure, relay state can be set to ON or OFF. Upper and lower setpoint limits can be adjusted. Temperature unit can be selected as °C or °F. CE marked according to European Norms.
Order Code : ET2412 - -
1
1 - Supply Voltage
2
230... 230V AC
.....
110........110V AC
24........24V AC
0 /DC
012........12V AC/DC
SM.........7-24VAC/9-30VDC
CONNECTION DIAGRAM
ENDA ET2412 is intended for installation within control panels. Make sure that the device is used only for
intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of electrical power. The device must be protected against inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is notexceeded.
All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be close to the power cables or components. The installation and electrical connections must be carried out by a qualified staff and must be according to the relevant locally applicable regulations.
ENDAINDUSTRIAL ELECTRONICS
ET2412-012-08 DIGITAL THERMOSTAT
Made in Turkey
250V AC 8A
RESISTIVE LOAD
up to date: 25.03.2019, modification reserved and can be change any time previous notice !
A1
C1
1 2 3 4 5 6
NOTE:
SUPPLY:
184-253V AC 50/60Hz 3VA
5 6
SN: XXXXXXXXX
7 8 9
10
Equipment is protected throughout by DOUBLE INSULATION
Line
Neutral
Fuse should be connected
ENDAINDUSTRIAL ELECTRONICS
ET2412-024-08 DIGITAL THERMOSTAT
Made in Turkey
250V AC 8A
RESISTIVE LOAD
NTC
11
F 100 mA
250V AC
12
Fuse
C1
1 2 3 4 5 6
Switch
Cable size: 1,5mm²
A1
230V AC Supply
SN: XXXXXXXXX
7 8 9
11
10
Note:
1) Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it should be easily accessible by the operator.
C1
°F
A1
ENDA
2 - Relay Current Selection
08.....8A Relay Output
ENDAINDUSTRIAL ELECTRONICS
ET2412-230-08 DIGITAL THERMOSTAT
Made in Turkey
250V AC 8A
RESISTIVE LOAD
NTC
12
A1
C1
1 2 3 4 5 6
Holding screw
0.4-0.5Nm.
°C
SET
SET
7 8 9
ET2412
SN: XXXXXXXXX
NTC
11
10
TECHNICAL SPECIFICATIONS
INPUT
Input Type NTC Sensor Resistance
EN 60751
S alc e Range
- ... 0 °C -76.0...302.0°F60.0 15 .0
Accuracy
± 1% (for full scale) ±
1 Digit
ENVIRONMENTAL CONDITIONS
Ambient/Storage temperature
Relative Humidity
Protection Class
Height
Do not use the device in locations subject to corrosive and flammable gasses.
0 ... +50 / Max. humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C. According to EN60529; Front panel: IP65 Rear panel : IP20 Max. 2000m
°C °C without icing( )
-25... +70
ELECTRICAL CHARACTERISTICS
Supply Power onsumptionC
Wiring Line Resistance Data Retention EMC Safety Requirements Indicator
230V AC +%10 -%20, 50/60Hz 24V AC %10or 12/ /DC
Max. 3 VA Power connector : 2.5mm² screw-terminal, Signal connector : 1,5mm² screw-terminal conenction. Max. 100ohm EEPROM ( 10 )Min. years
EN 61326-1: 2013 (Performance criterion B is satisfied for EN 61000-4-3) EN 61010-1: 20 (Pollution degree 2, overvoltage category II)10
4 digits, 12.5mm, 7 segment red LED
OUTPUT
C1 Output A1 Output
Life Expectancy for Relay
250V AC, 8A ( ), NO and NC control output.resistive load 250V AC, 8A ( ), NO control output.resistive load
30. Switching for no-load operation; 300.000 switching for 8A resistive load at 250VAC. Mio.
CONTROL
ontrolC Type Control Algorithm
A/D Converter
Hysteresis
Single and alarm .-setpoint control
12 bit , sampling time.resolution 100ms Adjustable between 0.1 and 20.0°C/F.
HOUSING
Housing Type Dimensions Weight Enclosure Materials
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
according to DIN 43 700.Suitable for flush-panel mounting 5 1W77xH3 xD6 mm Approx. 215g (A )fter packing
Self extinguishing plastics
Dimensions
77mm
C1
°F
A1
°C
SET
SET
12
ENDA
ET2412
For removing mounting clamps:
- Push the flush-mounting clamp
in direction as shown in the figure below.Then,pull out the clamp in direction .12
Connection
Cable
Flush mounting
2
12
10
11
NTC
SN: XXXXXXXXX
A1
1 2 3 4 5 6
C1
RESISTIVE LOAD
250V AC 8A
Made in Turkey
DIGITAL THERMOSTAT ET2412-230
ENDAINDUSTRIAL ELECTRONICS
Flush mounting
clamp
1
Panel cut-out
71,5mm
Depth
61mm
clamp
Note:
Panel
1) Panel thickness should be maximum 7mm.
2) If there is no 60mm free space at the back side of the device,it would be difficult to remove it from the panel.
5mm
Rubber
Packing
t
SURAN Industrieelektronik
SURAN Industrieelektronik
Dettinger Str. 9
Dettinger Str. 9 D-72160 Horb a.N.
D-72160 Horb a.N.
Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de
Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de
Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de
Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de
1. / 2
ET2412-E-25032019
Measured temperature
SET
105 C1.SE.
SET
A1.SE.
Default value
100
110
C1 Set value
100
A1 Set value
110
101
111
Programming Diagram
Running Mode
102
112
If no key is pressed within 3 seconds, Running Mode is entered.
101
111
If no key is pressed within 3 seconds, Running Mode is entered.
When this button is pressed
message is appeared
C.SEt
and temperature setpoint
SET
adjustment mode is entered. If key is pressed while holding down key,
then Programming Menu is entered.
SET SET SET
C1.Cn. A1.Cn. ConF.
Default
Value
-60
150
2
ERROR MESSAGES
pfa
----
____
Modification Of Parameter Diagram
SET
Wh holding key, parameter and ,
ile down value blinks by
using keys the requested value can be adjusted.
If key is pressed and held 0.6 seconds, the value of the selected parameter increases rapidly. If waited enough,the value increases a hundred at each step. After 1 second, following the release of the key, initial increasing condition is returned. The same procedure is valid for the decrementing.
C1..L.L.= Control set point lower limit for C1 output.
C1..L.L.
It can be adjusted between -60.0 and
parameter value.C1.H.L.
C1H.L.= Control set point upper limit
C1..H.L.
for C1 output. It can be adjusted between 150.0 and
parameter value.C1.L.L.
C1.Hy. = Output hysteresis value.
C1.Hy.
It can be adjusted between and
.
20.0 °C
Sensor is broken
Temperature value is higher than the scale
Temperature value is lower than the scale
SET SET
SET
0.1
Temperature setpoint value is adjusted with buttons then, when one of these buttons are pressed for the first time, blinking
SET
setpoint value appears.
Programming Menu
Entering Running Mode in Programming Mode :
In Programmin Mode, if no keys are pressed for 20 seconds information is saved automatically and Running Mode is entered. Alternatively, if and keys are pressed together, Programming Menu is entered. In the Programming Menu, if key is pressed while holding
SET
down key, then Running Mode is entered.
SET
SET
SECu.
Default
Value
-60
150
2
in.A.L.
off
A1..L.L.= Control set point lower limit for
A.1.L.L.
A1 output. It can be adjusted between -60.0 and
A1H.L.= Control set point upper limit for
A1.H.L.
A1 output. It can be adjusted between 150.0 and
A1.Hy. = .
A1.Hy.
0.1 ile 20.0 °C arasinda ayarlanabilir
A1.ty = .
A1.ty.
Please see A1 Output Format Table for settings.
A1.E.S.
A1.E.S.
sensor failure.
on
= Output is ON in case of sensor
failure.
off
failure.
A1 OUTPUT FORMATS
Independent Alarm
A1.ty. in.A.l.=
ON ON
A1.ty. in.A.H.=
OFF
a1,Hy.
ASV
(ASV . =
Min Beginning of Scale
ASV . = )
Max End of Scale
SV = C1 output setpoint ASV = A1 output setpoint
parameter value.A1.H.L.
parameter value.A1.L.L.
A1çikisi histerisiz degeri
Alarm type selection
= A1 Output state in case of
= Output is OFF in case of sensor
.
Deviation Alarm
=A1.ty. dE.a.l.
OFF
=A1.ty. dE.a.H.
ON
-300 (ASV in. =-300, ASV . = +300)M Max
OFF
Default
Value
HEAt
°C
no
0
off
C.typ. = Control type selection.
C.tyP.
C.typ. HEAt
=
C.typ. CooL Unit = Temperature unit selection.
Unit.
Unit. °C °F = Can be selected as or
d.P. = Decimal point display selection.
d.P.
If , decimal value is not dotted.
d.P.. no
If = , decimal value is dotted.
d.P. YES
oFFS. = Offset .
oFFs.
Zero point shift value is added to the measured value. This feature is used for eliminating the measuring probe distance errors. It can be adjusted between - and
°C.
20.0
C1.E.S.
C1.E.S.
failure.
on
= Output is ON in case of sensor
failure.
off
= Output is OFF in case of sensor
failure.
Heating control is selected.
=
Cooling control is selected.
=
value
= C1 Output state in case of sensor
20.0
Band larmA
=A1.ty. bi.A.l.
OFF
OFF
ON
=A1.ty. bi.A.H.
ON
A1.Hy.
SV+ASV
SV
+300
300
SV =C1 output setpoint ASV = A1 output setpoint
ON
A1.Hy.
SV-ASV
(ASV in. = 0, ASV . = +300)M Max
SV+ASV
SV
OFF
A1.Hy.
300
Default
Value
0
P.YES
P.YES
P.YES
P.YES
P.YES
S.Cod.
C1.sc.
A1..sc.
Co..sc.
C.S.sc.
A.S.sc.
S.Cod = Access code for security menu.
This parameter should be .412
When , if key is
s.co. = 0
pressed for 4 seconds while holding down key, then
d.PAr.
device is returned to factory settings.
C1..sc. C1,Cn.
=
level.
nonE
=
Invisible.
P.yEs
= Can be m ed
P. no
Visible but can’t be modified
= .
a1..sc. A1.Cn.
= Security menu access
level
nonE
= Invisible.
P.yEs
= Can be modified.
P. no
Visible but can’t be modified. =
..Co.sc. ConF.
= Configuration menu
access level.
nonE
= Invisible.
P.yEs
= Can be modified.
P. no
Visible but can’t be modified. =
C.S.sc.
= security access
C1 set value
level.
P.yEs
=
Can be modified.
P. no
= Visible but can’t be modified
C.S.sc.
= security access
Alarm set value
level.
P.yEs
=
Can be modified.
P. no
= Visible but can’t be modified
SET
is seen on display and the
Security menu access
odifi .
.
.
2. / 2
ET2412-E-25032019