ENDA 2411 ON/OFF HEAT CONTROLLER ET
Thank you for choosing ON/OFF Heat Controller.ENDA ET2411
- 77 x 35mm sized.
- Single NTC sensor input.
- Zero point input shift.
- Selectable heating or cooling control for C1 relay output.
- Selectable heating or cooling control.
- In the case of sensor failure, relay state can be set to ON or OFF.
- Upper and lower setpoint limits can be adjusted.
- Temperature unit can be selected as °C or °F.
- CE marked according to European Norms.
1 - Supply Voltage
230... 230V AC
Order Code : ET2411 - -
1
.....
24........24V AC
0 /DC
2
012........12V AC/DC
SM.........7-24VAC/9-30VDC
ENDA ET2411 is intended for installation within control panels. Make sure that the device is used only for
intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the
cables that are connected to the device must be free of electrical power. The device must be protected against
inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded.
All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables.
These cables should not be close to the power cables or components. The installation and electrical connections must
be carried out by a qualified staff and must be according to the relevant locally applicable regulations.
ENDAINDUSTRIAL ELECTRONICS
ET2411-230-08
DIGITAL THERMOSTAT
Made in Turkey
250V AC 8A
RESISTIVE LOAD
C1
1 2 3 4 5 6
NOTE:
SUPPLY:
184-253V AC
50/60Hz 3VA
up to date: 25.03.2019, modification reserved and can be change any time previous notice !
5
6
7 8 9
Line
Neutral
SN: XXXXXXXXX
10
ENDAINDUSTRIAL ELECTRONICS
ET2411-230-16
DIGITAL THERMOSTAT
Made in Turkey
250V AC 16A
RESISTIVE LOAD
NTC
C1
12
Fuse
F 100 mA
250V AC
1 2 3 4 5 6
Switch
Cable size: 1,5mm²
230V AC
Supply
11
Equipment is protected throughout
by DOUBLE INSULATION
Fuse should
be connected
SN: XXXXXXXXX
7 8 9
11
10
Note:
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
SURAN Industrieelektronik
Dettinger Str. 9
D-72160 Horb a.N.
Tel.: +49 (0)7451 / 625 617 E-mail : info@suran-elektronik.de
Fax: +49 (0)7451 / 625 0650 Internet : www.suran-elektronik.de
C1
°F
ENDA
2 - Relay Current Selection
05.....5A Re
08.....8A
16...16A Relay Output
ENDAINDUSTRIAL ELECTRONICS
ET2411-SM-05
DIGITAL THERMOSTAT
Made in Turkey
250V AC 5A
RESISTIVE LOAD
NTC
12
C1
1 2 3 4 5 6
Holding screw
0.4-0.5Nm.
lay Output
Relay Output
7 8 9
°C
SET
SET
ET2411
R HS
Konform
SN: XXXXXXXXX
NTC
11
10
12
TECHNICAL SPECIFICATIONS
INPUT
Input Type
NTC Sensor Typ 103AT-2
at 25 °C - 10 kOhm
Ambient/Storage temperature
Relative Humidity
Protection Class
Height
Do not use the device in locations subject to corrosive and flammable gasses.
EN 60751
0 ... +50 /
Max. humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.
According to EN60529; Front panel: IP65 Rear panel : IP20
Max. 2000m
°C °C without icing( )
-25... +70
S alc e Range
- ... 0 °C -76.0...302.0°F60.0 15 .0
ENVIRONMENTAL CONDITIONS
ELECTRICAL CHARACTERISTICS
Supply
Power onsumptionC
Wiring
Line Resistance
Data Retention
EMC
Safety Requirements
Indicator
230V AC + % - %, 50/60Hz 24V AC %10 20 or 12/ /DC 10
Max. 3 VA
Power connector : 2.5mm² screw-terminal, Signal connector : 1,5mm² screw-terminal conenction.
Max. 100ohm
EEPROM ( 10 )Min. years
EN 61326-1 : 2013 (Performance criterion B is satisfied for EN 61000-4-3)
EN 61010-1 : 20 (Pollution degree 2, overvoltage category II) 10
4 digits, 12.5mm, 7 segment red LED
OUTPUT
C1 Output
Life Expectancy for Relay
For 5A Models : 250V AC, 5A (resistive load), NO control output.
For 8A Models : 250V AC, 8A ( ), NO and NC control output.resistive load
For 16A Models : 250V AC, 16A ( ), NO control output.resistive load
For 5A Models : 5. Switching for no-load operation; 100.000 switching for 5A resistive load at 250VAC. Mio.
For 8A Models : 30. Switching for no-load operation; 300.000 switching for 8A resistive load at 250VAC. Mio.
For 16A Models : 30. Switching for no-load operation; 100.000 switching for 16A resistive load at 250VAC. Mio.
CONTROL
ontrolC Type
Control Algorithm
A/D Converter
Hysteresis
Single and alarm .-setpoint control
12 bit , sampling time.resolution 100ms
Adjustable between 0.1 and 20.0°C/F.
HOUSING
Housing Type
Dimensions
Weight
Enclosure Materials
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
according to DIN 43 700.Suitable for flush-panel mounting
5 1W77xH3 xD6 mm
Approx. 215g (A )fter packing
Self extinguishing plastics
Dimensions
77mm
°F
ENDA
12
C1
°C
SET
SET
ET2411
10
11
7 8 9
NTC
SN: XXXXXXXXX
1 2 3 4 5 6
C1
RESISTIVE LOAD
250V AC 8A
Made in Turkey
DIGITAL THERMOSTAT
ET2411-230-08
ENDAINDUSTRIAL ELECTRONICS
For removing mounting clamps:
- Push the flush-mounting clamp
in direction as shown in the
figure below.Then,pull
out the clamp in direction .12
Connection
Cable
Flush mounting
clamp
Panel cut-out
1
2
71,5mm
Accuracy
± 1% (for full scale) ±
Depth
61mm
Flush mounting
clamp
1) Panel thickness should
Note:
be maximum 7mm.
2) If there is no 60mm free
space at the back side of
the device,it would be
difficult to remove it from
the panel.
ET2411-E-25032019
1. / 2
Panel
1 Digit
5mm
Rubber
Packing
t
Measured temperature
SET
105 C1.SE.
When this button is pressed
message is appeared
C.SEt
and
temperature setpoint
adjustment mode is entered.
If key is pressed while holding down key,
then Programming Menu is entered.
Default value
100
SET
C1.Cn.
C1..L.L.= Control set point lower limit for C1
C1..L.L.
C1..H.L.
C1.Hy.
Modification Of Parameter Diagram
SET
Wh holding key, parameter and
,
ile down value blinks by
using keys the requested value can be adjusted.
If key is pressed and held 0.6 seconds, the value of the
selected parameter increases rapidly. If waited enough,the
value increases a hundred at each step. After 1 second,
following the release of the key, initial increasing condition is
returned. The same procedure is valid for the decrementing.
output.
It can be adjusted between -60.0 and
parameter value.
C1H.L.= Control set point upper limit for C1
output.
It can be adjusted between 150.0 and
parameter value.
C1.Hy. = Output hysteresis value.
It can be adjusted between and .0.1 20.0 °C
SET SET
SET
Programming Diagram
Running Mode
C1 Set value
100
Temperature setpoint value is adjusted with buttons then,
when one of these buttons are pressed for the first time, blinking setpoint value appears.
SET
101
102
101
Programming Menu
SET
ConF.
Default
Value
C1.H.L.
C1.L.L.
HEAt
°C
no
0
ERROR MESSAGES
pfa
----
____
Sensor is broken
Temperature value is
higher than the scale
Temperature value is
lower than the scale
C.tyP.
Unit.
d.P.
oFFs.
C1.E.S.
C.typ. = Control type selection.
C.typ. HEAt
=
C.typ. CooL
=
Unit = Temperature unit selection.
Unit. °C °F = Can be selected as or
d.P. = Decimal point display selection.
If , decimal value is not dotted.
d.P.. no
=
If = , decimal value is dotted.
d.P. YES
oFFS. = Offset .
Zero point shift value is added to the measured
value. This feature is used for eliminating the
measuring probe distance errors. It can be
adjusted between - and °C.
C1.E.S.
= C1 Output state in case of sensor failure.
on
= Output is ON in case of sensor failure.
off
= Output is OFF in case of sensor failure.
Heating control is selected.
Cooling control is selected.
value
20.0 20.0
If no key is pressed within 3 seconds, Running Mode is entered.
Entering Running Mode in Programming Mode :
In Programmin Mode, if no keys are pressed for 20 seconds information is
saved automatically and Running Mode is entered.
Alternatively, if and keys are pressed together, Programming Menu
is entered. In the Programming Menu, if key is pressed while holding
SET
down key, then Running Mode is entered.
SET
SECu.
Default
Value
0
P.YES
P.YES
P.YES
S.Cod.
C1.sc.
Co.sc.
C.S..sc.
S.Cod = Access code for security menu.
This parameter should be .411
When , if key is
s.co. = 0
pressed for 4 seconds while holding
SET
down key, then is seen
on display and the device is returned
to factory settings.
C1..sc. C1,Cn.
=
nonE
=
P.yEs
= Can be m ed
P. no
= .
..Co.sc. ConF.
=
nonE
= Invisible.
P.yEs
= Can be modified.
P. no
=
C.S.sc.
= security access level.
P.yEs
=
P. no
= Visible but can’t be modified
Security menu access level.
Invisible.
odifi .
Visible but can’t be modified
Configuration menu access level.
Visible but can’t be modified.
C1 set value
Can be modified.
SET
d.PAr.
.
2. / 2
ET2411-E-25032019