Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.
ENDA ET2011 PID TEMPERATURE CONTROLLER
Thank you for choosing 2011 temperature controller.ENDA ET
* x mm .77 35 sized
* Selectable dual-set value.
* Se tlectable thermocouple ypes or Pt100 input.(Selection must be
specified in order).
* (SELF TUNE).Automatic calculation of PID parameters.
Enter PID parameters of the system if they are known at the beginning.
Otherwise, Self-Tune should be activated.
* Soft-Start feature.
* Input offset feature.
* C/A2 Relay output can be programmable as alarm or control output.
* .Selectable SSR control output
* Selectable heating/cooling control.
* In the case of sensor failure periodical running or relay state can be
selected.
TECHNICAL SPECIFICATIONS
°F
ENDA
C/A2
SSR
°C
SET
SET
english
F
ET2011
Input type
Pt 100 Resistance thermometer
Pt 100 Resistance thermometer
J (Fe-CuNi) Thermocouple
K (NiCr-Ni) Thermocouple
T (Cu-CuNi) Thermocouple
S (Pt 0Rh-Pt) T1 hermocouple
R (Pt13Rh-Pt) Thermocouple
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60751
EN 60751 -200...600 °C
- ... 00 °C99.9 3 .0
0...1700
Temperature range
°C
0... 600
°C
0...1300
°C
0... 400
°C
0...1700
°C
°C
+32... +3092
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature
Max. Relative humidity
Rated pollution degree
Height
Do not use the device in locations subject to corrosive and flammable gases.
0 ... +50 /°C -25... +70°C (with no icing)
80 up to 31 decreasing linearly 50 at 40.% %
According to EN 60529 Front panel : IP65
Rear panel : IP20
Max. 2000m
°C
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Line resistance
Data retention
EMC
Safety requirements
230V AC +%10 -%20, 50/60Hz 24V AC %10, 50/60Hzor
Max. 5VA
Power : , Si : 1 ²connector 2.5mm²' screw-terminal gnal connector ,5mm screw-terminal conenction.
Max. 100ohm
EEPROM ( )minimum 10 years
EN 61326-1: 2006
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
OUTPUTS
C/A2 output
SSR output
Life expectancy for relay
R : 250V AC, 8A (for resistive load), Selectable as NO+NC Control or Alarm2 output.elay
R : 250V AC, 16A (for resistive load), Selectable as NO Control or Alarm2 output.elay
Max 20mA 12Volt (as control output)
Withot load 30.000.000 mechanical operation; 250V AC, on the 8A resistive load 100.000
electrical switching
CONTROL
Control type
Control algorithm
A/D converter
Sampling time
Proportional band
Control period
Hysteresis
Output power
Single set-point and alarm control
1 bit2
00ms1
Adjustable between 0 and 100 . If Pb=0 , On-Off control is selected.% % %
and 250 secondsAdjustable between 1
1 and 50Adjustable between °C/F
The ratio of power at a set point can be adjusted between 0 and 100% %
HOUSING
Housing type
Dimensions
Weight
Enclosure material
While cleaning the device, solvents (thinner, benzine, acid etc.) or must not be used.corrosive materials
Suitable for flush-panel mounting according to DIN 43 700.
W77xH35xD71mm
Approx. 200g (after packing)
Self extinguishing plastics.
°F
- ...543 °F99.9 .0
-328...1112 °F
+32... +1112
+32... +2 237
+32... +752
+32... +3092
Accuracy
0,5% (of full scale)
0,5% (of full scale) 1 digit
°F
°F
°F
°F
°F
0, % ( )5 of full scale
0, % ( )5 of full scale
0, % ( )5 of full scale 1 digit
0, % ( )5 of full scale 1 digit
0, % ( )5 of full scale 1 digit
1 digit
1 digit
1 digit
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
ET2011-E-06052019
1. / 4

SET
SET
If key is pressed while holding key, the programming mode is enabled.
SET
Con.o.
C.s.Lo.
C.s.Hi.
C. pb
C.Hys
C. ti
C. td
C. Ct.
C.p.st
C.E.p.s.
s.s.t.s.
C.typ
C.s.lo.= Control set point lower limit.(for
selected output)
Adjustable between 0 and C.s.Hi.
C.s.Hi.= Control setpoint upper limit.(for
selected output)
Adjustable between and Upper scale
value.
C. Pb
=
output)
Adjustable between .0 and .0.
C. Pb
= %0 On-Off
C.Hys
= Hysteresis of the output.(for
selected output)
Adjustable between 1 and 50 °C.
C. Pb
= 0,this parameter is active.
C. ti
==Integral time.(for selected output)
Adjustable between 0 and 100.0 minutes.
C. ti
C. Pb
parameter is different from “0”,this
parameter appears.
C. td
==Derivative time.(for selected output)
Asjustable between 0.00 and 25.00 minutes.
C. td
C. Pb
parameter is different from”0”,this
parameter appears.
C. Ct.
= Period time.(for selected output)
Adjustable between 1 and 250 second.
C. Pb
parameter is different is different
from“0”,this parameter appears.
C.p.st = The ratio of output power at the
setpoint.Adjustable between %0 and %100.
C.E.P.s. = The percentage of faulty sensor
selected output power.Adjustable between
%0 and %100.
Sst.S =Sofy starter timer set value
This parameter indicates the time to reach set point
value when the device is first enegised.
Adjustable between 0 and 250 minutes.
If 0 is selected, soft start feature will be enable and the
device reaches set point value quickly.
C.typ. = Control output type
C.typ. HEAt
=
C.typ. CooL
=
While the parameter names appear,if and
keys are pressed together, returns to the program
mode.
C.s.Lo.
Proportional band.(for selected
%0 %100
.0, control is selected.
0.0,integral impact is disable.
0.0, derivative time is disable.
Pb = 0, so start feature will be disable. Setting ft
means heatign control.
means cooling control.
Entering from the programming mode to the run mode:
If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the run mode is entered.
AL2.o.
A2.S.L
A2.S.H
A2.HY
A2.tP
A2.St.
A2.Er.
this parameter is seen and
adjustable only
if set co.SE SSR =
a2.s.l= Alarm2set value lower limit.
Adjustable between 0and A2.S.H
parameter value.
a2.s.H= Alarm2set value upper limit.
Adjustable between
parameter value and upper scale
value.
a2.Hy=.Hysteresis of the Alarm2
output
Adjustable between 1 and 50 °C.
A2.tp
= Function of Alarm type.
Four kinds of functions can be
selected.
indE.
= alarm
Independdnt
(Independent)
dE.
= Deviation
bAnd
= Band alarm (Band)
bAn.i
= Band with inhibition
A2.st.Hi= The state of Alarm2 output.
If A2 output is above the set
=
value. (on)
lo=If A2 output is above the set
value.(off)
A2.Er.on=
State of Alarm2 output in the
case of sensor failure.
2 output is probe failure (on).
= A
off= A2output is probe faiure (off).
A2.S.L
Alternatively, the same function occurs first pressing key and key is pressing programming mode is entered.Then and keys are pressing
together,data is recorded and running mode is entered.
Programming mode
SET
SET
ConF.
inp.t.
=
inp.t.
Unit
fltr.
2
C.o.sE
offs.
F.k.E.C.
m.SEt.
Input type selection.
FE.cn. nc.nA. c.cn.
= J type , = K type = T
p10.r. P13.r.
type =S type , = R type
thermocouple selection.
This parameter varies when changing
some parameters.
Unit = The temperature unit.
°C °F= °C, = °F
(This parameter varies when
changing some parameters.)
fLtr.= Coefficient of digital filter.
Filter for display value.
Adjustable between 1 and . If this parameter is 1,
digital filter runs most quick. If the parameter is ,
the filter run most slow. The value of parameter should
be increased in interference.
C.o.sE = Control output selection
C-A2
= C/A2 (Relay) output selection
SSR
= SSR output selection
oFfS. = Offset value.
Offset value is added to the measurement value.
Adjusted between -100 and +100°C.The normal value is 0.
F.kE.C. = Function key setting parameter
nonE
= Function key is off.
C2.S.A.
= The function key with 2.set value is used.
manu.
= Manual mode can be achieved with the function key.
dSP.o
= Device only the temperature display mode is entered
.
with function key.
m.SEt.
=
The percentage of manual output parameter.
Adjustable between %0 and %100.
This parameter allows manual adjustment of the output
power when the manual output selection.
C. Pb.
0=
200
, this parameter is not seen.
F
SET
S.tun.
St.Cu = Self tune control parameter.
s.t.Co.
200
SET
If both keys are pressed ,
message is displayed on the screen
and self tune process is started
automatically.
SET
If both keys are pressed,
message is displayed on the screen
and self tune process is stopped.
Selt tune begins when the measurement,
and measurement value
PIdt.
message
are shown alternately.Self tune process
completed automatically after the
parameter is done no and is entered to the
working mode. Self tune process begin when
the measured temperature is expected fall
below 90% of the set value the display shows
message alternately.Expected to fall
te.HI
below the temperature set point 60% evolved
and then self tune process starts automatically.
If asked to abort the self tune process,
parameter is done and key is
pressed.
NOTE:
If the output does not switch the relay and the C / A2 LED
does not light up though correct wiring and parameter
settings of the device:
Parameter on change over with the "F" key
from temperature indicator to temperature controller, then
change parameters back to “ ".
or
Reset the device to factory settings.
no
FtEC dSP.o
DEFAULT PARAMETERS
C.s.lO.
C.s.Hi.
C. PB
C.HyS
C. ti
C. td
C. Ct.
C.P.St.
C.EP.S.
S.s.t.S.
C.typ.
Control output
parameters
Pt100 input
TC input
0
600
0
2
4.0
1.00
20
0
0
0
HEat
-200
Set parameters
C1.sE.
400
C2.SE.
400
A2.SE.
500
F
A2.s.l
A2.s.H
A2Hy.
A2.tp
a2.st.
a2.Er.
Alarm2 output
parameters
TC input
0
600
indE
Hi
on
Pt100 input
-200
2
inp.t.
Unit
Fltr.
C.o.SE.
offs.
f.k.E.C.
m.sEt.
Configuration
parameters
Pt100 input
TC input
FE.cn.
°C
25
C-A2
0
nonE
50
Pt.
a2.Er.
Self tune
parameters
TC input
Pt100 input
no
Co.sc.
A2.Sc.
Cn.Sc.
S.t.Sc.
dEf.P.
Security
When holding key, the value of parameter flashes and using
parameters
keys the requested value can be adjusted.
Pt100 input
TC input
P.yEs
P.yEs
P.yEs
P.yEs
no
If key is pressed and held 0.6 seconds, the value of the selected
parameter changes rapidly. If waited enough,the value increases 100 at each
step. After 1 second following the release of the key, initial condition is
returned.The same procedure is valid for the decrement key.
SET
SET
SEcu.
S.Cod =.Security menu access
S.Cod.
yes
no
a.2.sc.
stco
Cn.sc.
St.Co
S.t.sc.
.
nonE
Modification Of Parameter Diagram
SET
SET
code
It should be 2011.
Cosc. CoN.o.
Co.sc.
menu security access level code.
nonE
P.yEs
P. no
a.2.sc. al2.o.
menu security access level code.
nonE
P.yEs
P. no
Co.sc. Conf.
menu security access level code.
nonE
P.yEs
P. no
S.t.Sc. S.tun.
men
u security access level code.
nonE
P.yEs
Co.sc. Conf.
dEF.P.
m
enu security access level code.
no
=
Parameter settings are not
change.
yEs
=
restored.
SET SET
=
Parameters of
=
Invisible.
=
Modification can be done.
= Only visible.
=
Parameters of
=
Invisible.
=
Modification can be done.
= Only visible.
=
Parameters of
=
Invisible.
=
Modification can be done.
= Only visible.
=
Parameters of
=
Invisible.
=
Modification can be done.
=
Parameters of
Parameter setting will be
SET
2. / 4
ET -E-050620192011

TERMS
( )5
C/A2
°F
SSR
ENDA
( 1 ) PV and SV display
Character heights
( ),( ),( )2 3 4 Keypad
( )5 State indicator
7 4 LED display segment, digits red
mm12
Mikro switch
, Alarm1 SSRFor control and outputs 3 digits red LED
ALARM2 OUTPUT TYPES
Independent Alarm
A2.tp. indE=
SV
ON
OFF
Deviation Alarm
A2.tp dE.
SV
°C
SET
SET
ET2011
=
( 1 ) )
Measurement value and set value indicator Running mode
Paramet (Progra )
er name and value mming mode
( ) ( rogram )
2 Value increment key P ming mode
F
ON
A2.St. H i=
OFF
If only this key is pressed in normal operation,software version
number is seen. parameter processing
( )
2 Value decrement and parameter selection key.
( rogram )
P ming mode
( ) ( )
4 Control ve Alarm set selection key Running mode
Paramet (Program )
er set key ming mode
(F.k.E.C. )
Band
Alarm
=
A2.tp. bAnd
SV
ON
OFF
A2.St. l o=
ON
OFF
a2,Hy
(ASV min. =
ASV ma = )
SV = ASV =Set point of CONT output Set point of alarm output
ASV
beginning of scale
x. end of scale
SV+ASV
SV
SV-ASV
ON
OFF
Beginning
SV = ASV = (ASV min. = 0, ASV maks. = 300 )Set point of CONT output Set point of AL2 output
-300
(ASV min. =-300, ASV ma . = +300)x
Band alarm is possible
MODIFICATION OF CONTROL AND ALARM SET POINTS
250
3 seconds later
SET
C1.SE.
399
ON
OFF
=A1.St. L o
A2.Hy
SV+ASV
+300
300
SV = ASV =Set point of CONT output Set point of AL2 output
Band Alarm With Inhibition
=
A2.tp. bAn.i
SV+ASV
SV
SV-ASV
ON
OFF
Beginning
400
3 seconds later
A2.Hy
SV-ASV
Band alarm is possible
SV+ASV
(ASV min. = 0, ASV ma = +300)X.
ON
OFF
A2.Hy
ERROR MESSAGES
pfa
----
____
psC
=A2.St. H i
300
Sensor is broken
Temperature value is
higher than the value
Temperature value is
lower than the scale
Pt100 sensor is short circuit
C2.SE.
SET
a2.SE.
399
499
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
398
500
3 seconds later
3 seconds later
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
parameter, is set to the parameter,this
F.kE.C. C2.S.A.
parameter is displayed.
C.O.SE.parameter is set to the output of SSR,this
parameter is seen.
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
ET2011-E-06052019
3. / 4

DIMENSIONS
C/A2
°F
77mm
SSR
°C
SET
SET
Depth
73mm 5mm
For removing the device from
the panel:
F
- While pressing both side of
the device in direction , push it1
in direction 2.
ENDA
12
10
11
-
TC
789
-
MADE IN TURKEY
SN: XXXXXXXXX
Order Code 2011-X XXX- X: ET -
CONNECTION DIAGRAM
ENDA ET2011 is intended for installation in control panels. Make sure that the device is used only for intended
purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are
connected to the device must be free of energy. The device must be protected against inadmissible humidity,
vibrations, severe soiling.Make sure that the operation temperature is not exceeded. All input and output lines
that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should
not be close to the power cables or components. The installation and electrical connections must be carried on by
a qualified staff and must be according to the relevant locally applicable regulations.
ET2011
1 2 3 4 5 6
RESISTIVE LOAD
250V AC 8A
C/A2
PID DIGITAL THERMOSTAT
ET20 1-T-230
1
ENDAINDUSTRIAL ELECTRONICS
Input selection
RT....PT100 input
....
T TC input
Flush
mounting
Connection
cable
Panel cut-out
71mm
2
clamp
1
Note
1) Panel thickness should be maximum 7mm.
2) If there is no 60mm free space at back side of the device,
it would be difficult to remove it from the panel.
Supply voltage
230 ... 230V AC
VAC ...
110VAC......110V AC
24 ........24V AC
0 VAC
SM.......9-30VDC/7-24V AC
Contact current selection
None......8A contact output
....
P 16A contact output
Flush mounting
clamp
Panel
ENDAINDUSTRIAL ELECTRONICS
ET20 1-T-230
1
PID DIGITAL THERMOSTAT
C/A2
250V AC 8A
RESISTIVE LOAD
11223344556
ENDAINDUSTRIAL ELECTRONICS
ET20 1-T-230-P
1
PID DIGITAL THERMOSTAT
C/A2
250V AC 16A
RESISTIVE LOAD
NOTE :
SUPPLY:
Phase
184-253V AC
50/60Hz 5VA
5
Neutral
6
77889
6
Holding screw
0.4-0.5Nm
F 100 mA
250V AC
Fuse should
be connected.
Fuse
SN: XXXXXXXXX
-
10
SN: XXXXXXXXX
-
9
11
10
Switch
Cable size: 1,5mm²
ENDAINDUSTRIAL ELECTRONICS
ET20 1-RT-230
1
PID DIGITAL THERMOSTAT
TC
C/A2
250V AC 8A
RESISTIVE LOAD
-
11
12
TC
1 2 3 4 5 6
ENDAINDUSTRIAL ELECTRONICS
ET20 1-RT-230-P
1
PID DIGITAL THERMOSTAT
C/A2
250V AC 16A
RESISTIVE LOAD
7 8 9
-
12
1 2 3 4 5 6
Equipment is protected throughout
by DOUBLE INSULATION.
Note
1) Mains supply cords shall meet the requirements
of IEC 60227 or IEC 60245.
230V AC
Supply
2) In accordance with the safety regulations, the
power supply switch shall bring the identification of
the relevant instrument and it should be easily
accessible by the operator.
7 8 9
SN: XXXXXXXXX
-
10
SN: XXXXXXXXX
-
10
PT100
11
PT100
11
12
12
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
ET2011-E-06052019
4. / 4