Empire GWT-50-3, GWT-50-3 SG, GWT-50-3 RB Installation Instructions And Owner's Manual

INSTALLATION INSTRUCTIONS
AND
OWNER'S MANUAL
GRAVITY VENTED
DUAL WALL FURNACE
MODEL
GWT-50-3 (SG, RB)
Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference.
WARNING: If the information in these instructions
are not followed exactly, a re or explosion may
result causing property damage, personal injury or loss of life.
— Donot storeor usegasoline orother ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the
redepartment.
— Installation and service must be performed by a
qualiedinstaller,serviceagencyorthegassup­plier.
Page 1
TABLE OF CONTENTS
SECTION PAGE
Important Safety Information ....................................................................................3
Safety Information for Users of LP Gas ...................................................................4
Introduction ..............................................................................................................5
Specications ...........................................................................................................5
Recommended Vent Conguration ..........................................................................6
Gas Supply ...............................................................................................................7
Clearances ..............................................................................................................8
Ventilation and Combustion Air ................................................................................8
Location - All Models ................................................................................................8
Rough-In Instructions ............................................................................................8-9
Finishing Instructions ..........................................................................................9-10
Optional Thermostat Location (SG Models) ........................................................... 11
Lighting Instructions ...............................................................................................12
Vent Safety Shutoff System ...................................................................................13
Proper Main Burner Flame .....................................................................................13
Proper Pilot Flame .................................................................................................13
Troubleshooting ......................................................................................................14
Parts List ................................................................................................................15
How To Order Repair Parts ....................................................................................15
Parts View .............................................................................................................16
Remote Bulb Control Installation Instructions ........................................................17
Optional Blower Installation Instructions .......................................................... 18-19
Service Notes .........................................................................................................20
Master Parts Distributor List ...................................................................................21
Warranty .................................................................................................................22
32039-1-0314Page 2
IMPORTANT SAFETY INFORMATION
THIS IS A HEATING APPLIANCE
DO NOT OPERATE THIS APPLIANCE WITHOUT OUTER CASING INSTALLED.
Due to high temperatures the appliance should be
locatedoutoftrafcandawayfromfurnitureand
draperies.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
• Clothingorotherammablematerialshouldnotbe
placed on or near the appliance.
Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance.
Keep burner and control compartment clean.
Installation and repair should be done by a QUALIFIED SERVICE PERSON. The appliance should be inspected before use and at least annually
by  a qualied service person.  More frequent
cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating
air passageways of the appliance be kept clean.
DO NOT put anything around the furnace that will
obstructtheowofcombustionandventilationair.
• DO keep the appliance area clear and free from
combustiblematerial,gasolineandotherammable
vapors and liquids.
• DO examine venting system periodically and replace damaged parts.
• DO make a periodic visual check of pilot and burners. Clean and replace damaged parts.
DO NOT use this heater if any part has been under
water.Immediatelycallaqualiedservicetechnician
to inspect the heater and to replace any part of the control system and any gas control which has been under water.
This furnace must not be connected to a chimney
ueservingaseparatesolid-fuelburningappliance.
32039-1-0314 Page 3
SAFETY INFORMATION FOR USERS OF LP-GAS
Propane(LP-Gas)isaammablegaswhichcancauseres
and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precau­tions which can protect both you and your family from an accident. Read them carefully now, then review them point by
point with the members of your household. Someday when there may not be a minute to lose, everyone's safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!
Do not operate electric switches, light matches, use your phone. Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until
reghters declare them to be safe.
Use your neighbor's phone and call a trained LP-Gas service
person and the re department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.
Finally, let the service man and reghters check for escaped
gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odorofthechemicalputintothegas.Youmustndoutifyou
can smell the odorant in propane. Smoking can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under some circumstances. For example, if there is an underground
leak, the movement of the gas through soil can lter the odorant.
Odorants in LP-Gas also are subject to oxidation. This fading can occur if there is rust inside the storage tank or in iron gas pipes. The odorant in escaped gas can adsorb or absorb onto or into
walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity. LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.
Learn to recognize the odor of LP-gas. Your local LP-Gas
Dealer can give you a "Scratch and Sniff" pamphlet. Use it to
nd out what the propane odor smells like. If you suspect that
your LP-Gas has a weak or abnormal odor, call your LP-Gas Dealer.
If you are not qualied, do not light pilot lights, perform service,
or make adjustments to appliances on the LP-Gas system. If
you are qualied, consciously think about the odor of LP-Gas
prior to and while lighting pilot lights or performing service or making adjustments.
Sometimes a basement or a closed-up house has a musty smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.
Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or
reinstalled old tanks, if they are lled and allowed to set too long before relling. Cylinders and tanks which have been
out of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist,
SOME POINTS TO REMEMBER
a periodic sniff test of the gas is advisable. If you have any question about the gas odor, call your LP-gas dealer. A periodic sniff test of the LP-gas is a good safety measure under any condition.
If, at any time, you do not smell the LP-Gas odorant and you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.
If you experience a complete "gas out," (the container is un­der no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in
some air through openings such as pilot light orices. If this
occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it
relled before it is completely empty.
32039-1-0314Page 4
INTRODUCTION
Introduction
Vented wall furnace is shipped ready to install in a 2" x 4" stud wall, with studs 16" (406mm) center to center. Always consult your local Building Department regarding regulations, codes or ordinances which apply to the installation of a vented wall furnace.
Instructions to Installer
1. Installer must leave instruction manual with owner after instal­lation.
2. Installer must have owner ll out and mail warranty card sup­plied with furnace.
3. Installer should show owner how to start and operate furnace and thermostat.
Warning: Any change to this furnace or its control can be dangerous. This is a heating appliance and any panel, door or guard removed for servicing an appliance must be replaced prior to operating the appliance.
To conserve Gas: Turn off pilot when heater is not in use.
General Information
This series is design certied in accordance with American National
Standard / CSA Standard Z21.86 and CSA 2.32 by the Canadian Standards Association, as a Vented Wall Furnace and must be installed according to these instructions.
Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change.
Important
All correspondence should refer to complete Model No., Serial No. and type of gas.
Notice: During initial ring of this furnace, its paint will bake out and smoke will occur. To prevent triggering of smoke alarms, ventilate the room in which the furnace is installed.
Installation in Residential Garages
Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less
than 18" (457mm) above the oor.
Such equipment shall be located, or protected, so it is not subject to physical damage by a moving vehicle.
QualiedInstallingAgency
Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be
performed only by a qualied agency. The term "qualied agency" means any individual, rm, corporation or company which either in
person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.
State of Massachusetts: The installation must be made
by a licensed plumber or gas tter in the Commonwealth of
Massachusetts.
The installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA
54* Natural Gas and Propane Installation Code, CSA B149.1. *Available from the American National Standards Institute, Inc., 11 West 42nd St., New York, N.Y. 10036.
High Altitudes
For altitudes/elevations above 2,000 feet (610m), input ratings should be reduced at the rate of 4 percent for each 1,000 (305m) feet above sea level. Canadian High Altitudes for locations having an elevation above mean sea level between 2,000 feet (610m) and 4,500 feet (1370m), the manifold pressure is to be decreased from
3.5" w.c. (.871kPa) to 3.0" w.c. (.747kPa) for Natural Gas and from
10.0" w.c. (2.49kPa) to 8.0" w.c. (1.992kPa) for Propane Gas.
Model GWT-50 Input BTU/HR (KW/H) 50,000 (14.7) Height 66 1/8" (1679mm) Width 16" (406mm) Depth (Out of wall) 6" (152mm) Gas Inlet Pipe 1/2" Vent Pipe Type B Oval 4" (102mm)
Accessory
Blower Package GWTB-2 Wall Thermostat Millivolt TMV Wireless Remote Wall Thermostat TRW Remote Bulb Thermostat GWRBT GWT-50 (SG, RB) Is a DUAL WALL Furnace. Warmed air is discharged into two rooms which share a common wall.
32039-1-0314 Page 5
SPECIFICATIONS
RECOMMENDED VENT CONFIGURATION
Note: No vent equipment supplied with furnace. 4" Oval (all parts purchase locally)
1. Type B-1 oval pipe
2. Single story type B-1 gas vents require a baseplate and one pair of ceiling plate spacers.
3. Multi-story type B-1 gas vents require a baseplate, one pair of ceiling
plate spacers at the rst oor ceiling and one pair of re stop spacers
at each successive ceiling level.
Type B-W gas vent pipe is available for single story or multi-story installations. Type B-W gas vent pipe is to be used with the
Listed base plate, ceiling plate spacers and re stop spacers.
Insulated Vent Enclosure
Gravity vented wall furnaces installed in buildings with at roofs can have
poor venting. The cold vent pipe will have a delay in proper venting and cause the wall furnace to shut "off" by the vent safety switch. To prevent
delayed venting as well as condensation of ue products an insulated vent
enclosure is recommended. Use Type B vent pipe and maintain at least a one inch (25mm) clearance
to combustibles. Use metal thimble to protect vent pipe as it passes through combustibles. Baseplate Gasket is factory installed on header. Baseplate attaches to header
with screws. B-vent snaps into and is attached to baseplate. Minimum height of vent pipe must be six feet (1.8m) above header.
Stud space around gas vents must be free of obstructions and building paper. Uninsulated Single-Wall Metal Pipe shall not be used outdoors in cold
climates for venting gas utilization equipment. Attention: The main burner uses room air for combustion. As the gas/air
mixture is injected into the main burner, there is also the ow of dust and
lint particles into the main burner. Dust and lint accumulation inside the main burner will result in a yellow main
burner ame and possible sooting inside the combustion chamber and vent
pipe. To clean main burner refer to Page 13, "Proper Main Burner Flame."
32039-1-0314Page 6
GAS SUPPLY
Check all local codes for requirements, especially for the size and type of gas supply line required.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe
Inside Diameter
Nat. L.P. Nat. L.P.
0-10 feet
0-3 meters
10-40 feet
4-12 meters
40-100 feet
13-30 meters
100-150 feet
31-46 meters
Note: Never use plastic pipe. Check to conrm whether your local
codes allow copper tubing or galvanized. Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
Check all local codes for requirements, especially for the size and type of gas supply line required. On Natural gas lines less than 15' (4.57m) long, use 1/2" pipe; on longer runs, use 3/4" iron pipe or equal. On LP gas lines please consult LP gas supplier.
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock. A manual main gas cock should be located in the vicinity of the unit.
Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liqueed petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.
Neveruseanexposedametocheckforleaks.Appliancemust
be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.
1/2”
12.7mm 1/2”
12.7mm 1/2”
12.7mm 3/4”
19mm
3/8”
9.5mm 1/2”
12.7mm 1/2”
12.7mm 1/2”
12.7mm
Tubing, Type L
Outside Diameter
1/2”
12.7mm 5/8”
15.9mm 3/4”
19mm
7/8”
22.2mm
3/8”
9.5mm 1/2”
12.7mm 1/2”
12.7mm 3/4”
19mm
Figure 1
The use of the following gas connectors is recommended: — ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a
exible appliance connector cannot exceed three feet in length.
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8" (3.175mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.
2. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
3. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.
Checking Manifold Pressure
Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of
10.5" w.c. (2.614kPa) Propane gas models will have a manifold
pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 11.0" w.c. (2.739kPa) for the purpose of input adjustment to a maximum of
13.0" w.c. (3.237kPa).
A 1/8" (3.175mm) N.P.T. plugged tapping, accessible for test gauge connection, is located on the outlet side of the gas control.
32039-1-0314 Page 7
CLEARANCES
1. In selecting a location for installation, it is necessary to provide adequate accessibility clearances for servicing and proper installation.
2. Clearances to combustible surfaces are 4" (102mm) from sides,
12" (305mm) to top, 1 1/2" (38mm) from oor.
NOTE: Minimum distance of 1 1/2" (38mm) must also be maintained
VENTILATION AND COMBUSTION AIR
Wall furnaces shall be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas and proper venting under normal conditions. In buildings of conventional frame, brick, or stone construction without tight storm windows and doors,
inltration is normally adequate to provide air for combustion and
draft hood dilution.
from top surface of carpeting, tile, etc.
Where appliances are installed in conned and unconned spaces
within a building, the building being of unusually tight construction, air for combustion and ventilation must be obtained directly from outdoors or from such spaces that freely communicate with the
outdoors. Under these conditions, the conned and unconned
spaces shall be provided with two permanent openings, one near the top of the enclosure and one near the bottom; each opening shall have a free area of not less than one square inch (6.45cm2) per 2,000 BTU (.6KW/H) per hour of total input.
LOCATION - ALL MODELS
Select a location near the center of the space to be heated. Overow heat will circulate through doorways into adjacent rooms.
For large homes or spread-out oor plans, two or more furnaces are
recommended. Do not locate furnace where a door could swing over the outer casing, or where circulation could be retarded by furniture or cabinets.
Do not install in a closet, alcove or small hallway where the furnace could be isolated by closing doors to the heated space.
When location is selected, check the walls, attic and roof to make
ROUGH-IN INSTRUCTIONS
Provide an opening in the wall 14 1/2" (368mm) wide and 66 1/8"
(168cm) high measured from top of oor plate (See Figure 2 and
Figure 3). Wall depth is to be 2" x 4" framing with 1/4" (6.5mm) to 5/8" (16mm) sheeting. Attach baseplate (not supplied with furnace) to header plate with sheet metal screws at each end. Attach 4" (102mm) oval, double wall vent pipe to baseplate. Attach enough vent pipe so that when installed in wall opening the vent pipe will extend above the ceiling plate by at least 6" (152mm). Install ceiling spacers according to manufacturer's instructions. Two header extensions are attached to the header plate. One header extension is welded to the header plate and one header extension is screwed to the header plate. To install header plate into wall opening remove the header extension that is screwed to the header plate (2 screws).
sure there are no obstructions such as pipes, electric wiring, etc., which would interfere with the installation of the furnace or vent pipe.
NOTE: If Optional Blower is to be used, hard wiring must be
completed for the optional blower prior to installation of header plate.
Insert header plate with attached 4" oval, double wall vent pipe into wall opening. Position header plate at height shown in Figure
2. Locate rear edge of nailing ange at the back of the 2" x 4" stud
which will center the vent collar in the wall. Locate the angled edge
of header plate ush with the top of the wall opening. Nail header
plate to the wall studs. Replace and attach header extension onto header plate with 2 screws.
32039-1-0314Page 8
62 1/4”
(1581 mm)
14 ½”
(368 mm)
Figure 2
66 1/8”
(1679 mm)
WALL
OPENING
FINISHING INSTRUCTIONS
Figure 3
Plastering (Figure 4)
In new construction use only plain (not perforated) gypsum lath around furnace and vent pipe so that plaster "Keys" will not project into wall space.
Use wood strips nailed to inside of studs and top of bottom plate. These must be removed before installation of furnace. Lath and plaster against top projection of Header Plate.
Do not allow wall nish materials to project into furnace recess..
14 ½”
(368 mm)
66 1/8”
(1679 mm)
WALL
OPENING
Installing Furnace (Figure 5)
Clear the recess of all debris, and remove any wood plaster-grounds.
Stand the furnace on oor in front of wall opening. Insert furnace ue into rectangular opening in header plate and
raise furnace carefully (see Figure 5). Swing bottom of furnace into
wall opening with back of legs ush with rear of oor plate. Secure furnace support legs to the oor plate.
Figure 4
32039-1-0314 Page 9
Figure 5
FINISHING INSTRUCTIONS (continued)
IMPORTANT — Avoid securing too tightly and disturbing the inner
casing. Do not try to force furnace into a wall opening which is
smaller than specied dimension.
OUTER CASING (Figure 6)
1. Align 1 3/4" slot on casing bracket with bottom screw hole on inner casing. Attach casing bracket to inner casing with one (1) 10 x 1/2" screws for each casing bracket. Do not completely tighten screws at this time.
2. Place outer casing onto header.
Attention: Use center clearance hole on outer casing top for
attachment to header with one (1) 8 x 3/8" Phillips screw when
optional blower is not installed.
Attention: Use outside clearance holes on outer casing top
for attachment to header with two (2) 8 x 3/8" Phillips screws
when optional blower is installed.
3. Align clearance holes on outer casing bottom with screw holes on casing brackets by adjusting slots on casing brackets.
4. Complete tightening casing bracket screws from Step 1 to inner casing at this time.
5. Attach outer casing to casing brackets with two (2) 10 x 1-1/2" screws.
INSTALLING CONTROL DOOR
Attach two washers supplied in hardware package to pivot pins located at bottom of control door. Install control door to outer cas­ing assembly.
Figure 6
32039-1-0314Page 10
THERMOSTAT LOCATION (SG MODELS)
CAUTION — Do not run wire behind anges of Header Plate or in
any location where it might be damaged. Millivolt wall thermostats are specially designed for use on self-
generating systems. They should never be used on line or low voltage A.C. circuits.
Interior Wall — The thermostat should be installed on an inside wall away from the furnace but in the same room.
It is important to use wire of a gauge proper for the length of the wire:
RECOMMENDED WIRE GAUGES
Maximum Length Wire Gauge
1' to 10' 18 10' to 25' 16 25' to 35' 14
Proper operation depends on a good pilot ame. The ame must cover the top of the thermopile. Cleaning of the pilot orice and
burner may be required due to spiders.
System Check (Figure 7)
A millivolt meter is required to check the system. Millivolt readings should be:
• Across the thermopile terminals, 400-450 millivolts with thermostat OFF.
• Across the thermopile terminals, 150-250 millivolts with thermostat ON.
Across the thermostat wires at the valve, less than 30 millivolts with thermostat ON.
Across the thermostat wires at the thermostat, less than 5 millivolts with thermostat ON. (Dirty pilot or low pressure will reduce readings.)
Figure 7
To conserve Gas: Turn off pilot when heater is not in use.
Connect thermostat wires to gas valve as shown in Figure 7.
32039-1-0314 Page 11
GAS CONTROL KNOB SHOWN IN "OFF" POSITION
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:Ifyoudonotfollowtheseinstructionsexactly,areorexplosion
may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand.
When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area
forgas.Besuretosmellnexttotheoorbecausesome gasisheavierthanairandwillsettleontheoor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• Ifyoucannotreachyourgassupplier,calltheredepart­ment.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting (if applicable).
3. Turn off all electric power to the appliance (if applicable).
4. Remove control access panel (control door).
5. Push in gas control knob slightly and turn clockwise
to "OFF."
NOTE: Knob cannot be turned from "PILOT" to "OFF" unless knob is pushed in slightly. Do not force.
6. Wait ten (10) minutes to clear out any gas. Then smell
forgas,includingneartheoor.Ifyousmellgas,STOP!
Follow "B" in the safety information above. If you don't smell gas, go to the next step.
7. Find pilot - follow metal tube from gas control. The pilot is mounted on front of main burner.
8. Turn gas control knob counterclockwise to "PI­LOT."
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turnbyhand,don'ttrytorepairit;callaqualiedservice technician.Forceorattemptedrepairmayresultinare
or explosion.
D. Do not use this appliance if any part has been under water.
Immediatelycallaqualiedservicetechniciantoinspect
the appliance and to replace any part of the control system and any gas control which has been under water.
9. Push in control knob all the way and hold in. Immediately light the pilot with a match. Continue to hold the control knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 9.
• If knob does not pop up when released, stop and imme-
diatelycallaqualiedservicetechnicianorgassupplier.
• If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.
10. Turn gas control knob counterclockwise to "ON."
11. Replace control access panel (control door).
12. Turn on all electric power to the appliance (if applicable).
13. Set thermostat to desired setting (if applicable).
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power (if applicable) to appliance if service is to be performed.
3. Remove control access panel (control door).
4. Push in gas control knob slightly and turn clockwise to "OFF." Do not force.
5. Replace control access panel (control door).
32039-1-0314Page 12
VENT SAFETY SHUTOFF SYSTEM
This appliance must be properly connected to a venting system. This appliance is equipped with a vent safety shutoff system.
Warning: Operation of this wall furnace when not connected to a properly installed and maintained venting system or tampering with the vent safety shutoff system can result in carbon monoxide (CO) poisoning and possible death.
This furnace is equipped with a manual reset vent safety switch. The
manual reset vent safety switch will cause gas ow to the main burner to "shut off" due to improper venting or a blocked ue.
To reset the manual reset vent safety switch:
1. Remove outer casing.
2. Depress manual reset button. The manual reset vent safety switch is located on the draft diverter.
3. Replace outer casing.
If the manual reset vent safety switch continues to "shut off" the gas
ow to the main burner a qualied service person must be contacted to
inspect for improper venting, blockage in the vent pipe or the manual reset vent safety switch for being defective.
PROPER MAIN BURNER FLAME
The correct ame will be a short blue inner ame with a much larger light blue outer ame. The burner does not have a primary air adjustment. The ame will be proper if the factory-set pressure and orice are used.
After the furnace has begun operating, cleaning of the burner may be
needed for proper ame, examine at least 2 times per season.
To clean burner ports, disconnect the gas supply to the valve. Remove the burner assembly from the combustion chamber. Remove pilot burner from main burner and then remove the main burner. Force water into the ports and blow dry with vacuum cleaner air, or low pressure compressed air.
PROPER PILOT FLAME
The correct ame will be blue, extending past the thermopile. The ame
will surround the thermopile just below its tip. Natural gas pilots require adjusting when the inlet gas pressure is above
5" w.c. (1.245kPa). Remove the pilot cover screw on the control valve
and turn the adjustment screw clockwise to reduce ame. Replace
pilot cover screw to eliminate gas leaking at that control valve opening. LP gas (propane) will not require adjustment.
After use, cleaning may be required for the proper ame. Examine the pilot ame before and during each heating season.
Figure 8
Figure 9
32039-1-0314 Page 13
Figure 10
TROUBLESHOOTING
GENERAL All furnaces have been re-tested to check for proper
operation. This includes main burner ame, pilot ame, and gas
control operation. If the furnace fails to function on initial installation, it is advisable to re-check the following:
1. Inlet gas pressure.
2. Type of gas being used and that shown on the rating plate.
The Service Department at Empire Comfort Systems, Inc. may be contacted to assist in servicing furnace.
ServicingthePilotandMainBurner,PilotOrice,Thermopile andMainBurnerOrice
Disconnect the gas supply at the inlet to the control valve. Remove the burner assembly to which the above components are attached.
Pilot Does Not Light
With air in the gas line, such as when the furnace is rst installed or was "OFF" all summer, the pilot ame may be too lean to ignite on the rst few trials. Turn the gas control knob to PILOT position
and depress the gas control knob. Hold the gas control knob down to bleed the line;
1. Use lighter rod to light pilot with a match.
If Pilot Does Not Light By Any Means
1. Check gas control knob for being in the "Pilot" position.
2. Check pilot adjustment for being full open (counterclockwise to open).
3. If gas is available in the supply tubing, the pilot orice and/
or pilot burner is probably restricted by a spider web. Clean pilot assembly and relight.
If Pilot Does Not Remain "On" After Releasing Gas Control Knob
1. Follow instructions and hold gas control knob down longer and harder.
2. Determine if pilot ame extends past thermopile; if not, adjust pilot ame or clean pilot burner.
3. Replace thermopile if millivolt reading is less than 300 millivolts when wall thermostat or remote bulb is turned OFF. Replace gas control if magnet dropout millivolt reading is over 100 millivolts.
Pilot Outage During Normal Operation
1. Check input by manifold pressure gauge or gas meter.
2. Check millivolt output when furnace is in operation. If millivolt output decreases during furnace operation gas control may be defective.
Main Gas Valve Does Not Open When Thermostat Is Turned "On"
1. Check millivolt output of thermopile.
2. Thermostat wires may be broken.
3. Thermostat may be defective.
32039-1-0314Page 14
Loading...
+ 30 hidden pages