Emerson Process Management 3051, 3051CF User Manual

Quick Start Guide
00825-0100-4007, Rev CB
February 2015
Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flowmeters
with 4-20 mA HART® Revision 5 and 7 protocol
Note
Before installing the transmitter, confirm the correct Device Driver is loaded on the host systems. See page 3 for System Readiness.
Quick Start Guide
February 2015
NOTICE
This guide provides basic guidelines for Rosemount 3051 Transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 3051 HART 7 Reference Manual (document number 00809-0100-4007) for more instruction. This manual is also available electronically on www.rosemount.com.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the 3051 reference manual for any restrictions associated with a safe installation.
Before connecting a HART-based communicator in an explosive atmosphere, make sure the instruments
in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter covers when power is
applied to the unit.
Process leaks may cause harm or result in death.
To avoid process leaks, only use the O-ring designed to seal with the corresponding flange adapter.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals. High voltage that may be present on leads can cause
electrical shock.
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a
use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries.
1
/2-14 NPT thread form. Only
Contents
System readiness . . . . . . . . . . . . . . . . . . . . . . . 3
Transmitter installation
. . . . . . . . . . . . . . . . . 4
Mount the transmitter . . . . . . . . . . . . . . . . . . 4
Consider housing rotation Set the switches
. . . . . . . . . . . . . . . . . . . . . . . . 8
Connect the wiring and power up
. . . . . . . . . . . . . . 8
. . . . . . . 9
2
Verify configuration . . . . . . . . . . . . . . . . . . .11
Trim the transmitter
. . . . . . . . . . . . . . . . . . .14
Safety instrumented systems installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product Certifications
. . . . . . . . . . . . . . . . .17
16
February 2015
Quick Start Guide

System readiness

Confirm HART Revision capability

If using HART based control or asset management systems, please confirm the
HART capability of those systems prior to transmitter installation. Not all systems are capable of communicating with HART Revision 7 protocol. This transmitter can be configured for either HART Revision 5 or 7.
For instructions on how to change the HART revision of your transmitter, see
page 13.

Confirm correct device driver

Verify the latest Device Driver (DD/DTM
proper communications.
Download the latest Device Driver at www.emersonprocess.com or
www.hartcomm.org.
Rosemount 3051 device revisions and drivers
Ta bl e 1 provides the information necessary to ensure you have the correct Device
Driver and Documentation for your device.
Table 1. Rosemount 3051 Device Revisions and Files
) is loaded on your systems to ensure
Identify device Find device driver
Software
releas e
date
Dec-11 1.0.0 01
Jan-98 N/A 178 5 3 00809-0100-4001 N/A
1.
1. NAMUR Software Revision is located on the hardware tag of the device. In accordance with NE53, revisions of the least significant level X (of 1.0.X) do not change functionality or operation of the device and will not be reflected in this device revision history.
2. HART Software Revision can be read using a HART capable configuration tool.
3. Device Driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to communicate with new HART devices. To access new functionality, the new Device Driver must be downloaded. It is recommended to download new Device Driver files to ensure full functionality.
4. HART Revision 5 and 7 Select able, Power Diagnostics, Safety Certified, Local Operator Interface, Process Aler ts, Scaled Variable, Configurable Alarms, Expanded Engineering Units.
NAMUR
software
revision
(1)
HART
software
revision
(2)
HART
universal
revision
7 10
5 9
Device
revision
(3)
Review
instructions
Manual document
number
00809-0100-4007
Review
functionality
Changes to
(4)
software
See Footnote 4 for
list of changes.
3
Quick Start Guide
Flow
Flow

Transmitter installation

Step 1: Mount the transmitter

February 2015
Liquid applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented upward.
Gas applications
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
Steam applications
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Fill impulse lines with water.
Coplanar In-line
Flow
4
February 2015
Figure 1. Panel and Pipe Mounting
Panel mount
(1)
Quick Start Guide
Pipe mount
Coplanar flange
Traditional flange
1.
1.5/16 11/2 Panel Bolts are customer supplied.
Rosemount 3051T
5
Quick Start Guide

Bolting considerations

If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow the assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 2 on page 6 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
Figure 2. Common Transmitter Assemblies
A
4 x 1.75-in. (44mm)
B
C
4 x 1.75-in.
(44mm)
4 x 2.25-in. (57mm)
4 x 1.50-in.
(38mm)
4 x 1.75-in. (44mm)
February 2015
D
4 x 2.88-in. (73mm)
A. Transmitter with Coplanar Flange B. Transmitter with Coplanar Flange and Optional Flange Adapters C. Transmitter with Traditional Flange and Optional Flange Adapters D. Transmitter with Coplanar Flange and Optional Manifold and Flange Adapters
Bolts are typically carbon steel or stainless steel. Confirm the material by viewing the markings on the head of the bolt and referencing Table 2 on page 7. If bolt material is not shown in Ta bl e 2, contact a local Emerson Process Management representative for more information.
Use the following bolt installation procedure:
1. Carbon steel bolts do not require lubrication and the stainless steel bolts are
coated with a lubricant to ease installation. However, no additional lubricant should be applied when installing either type of bolt.
2. Finger-tighten the bolts.
3. Torque the bolts to the initial torque value using a crossing pattern. See
Ta bl e 2 for initial torque value.
4. Torque the bolts to the final torque value using the same crossing pattern. See
Ta bl e 2 for final torque value.
5. Verify that the flange bolts are protruding through the isolator plate before
applying pressure.
6
February 2015
Quick Start Guide
Table 2. Torque values for the flange and flange adapter bolts
Bolt material Head markings Initial torque Final torque
B8M
STM
316
B7M
316
SW
316
Carbon Steel (CS) 300 in.-lbs. 650 in.-lbs.
316
Stainless Steel (SST) 150 in.-lbs. 300 in.-lbs.
316
R

In-line gage transmitter orientation

The low side pressure port (atmospheric reference) on the in-line gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See
Figure 3.)
Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the process can drain away.
Figure 3. In-line Gage Low Side Pressure Port
A
A. Low side pressure port (atmospheric reference)
7
Quick Start Guide

Step 2: Consider housing rotation

To improve field access to wiring or to better view the optional LCD display:
1. Loosen the housing rotation set screw using a 5/64-in. hex wrench.
2. Turn the housing left or right maximum up to 180° from its original position
Please note that over rotating can damage the transmitter.
3. Re-tighten the housing rotation set screw to no more than 7 in-lbs when
desired location is reached.
Figure 4. Transmitter Housing Set Screw
A
A. Housing rotation set screw (5/64-in.)
February 2015
(1)
.

Step 3: Set the switches

Set Alarm and Security switch configuration before installation as shown in
Figure 5.
The Alarm switch sets the analog output alarm to high or low.
- Default alarm is high.
The Security switch allows (unlocked symbol) or prevents (locked symbol) any
configuration of the transmitter.
- Default security is off (unlocked symbol).
Use the following procedure to change the switch configuration:
1. If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the
instrument cover in explosive atmospheres when the circuit is live.
3. Slide the security and alarm switches into the preferred position using a small
screwdriver.
4. Reattach the transmitter cover. The cover must be fully engaged to comply
with explosion-proof requirements.
1. 3051C original position aligns with “H” side; 3051T original position is the opposite side of bracket holes.
8
February 2015
A
B
C
Figure 5. Transmitter Electronics Board
Without LCD display
A
B
A. Alarm B. Security
With LCD or LOI display

Step 4: Connect the wiring and power up

Figure 6. Transmitter Wiring Diagrams (4–20 mA)
Quick Start Guide
A. 24 Vdc supply
250
B. R
L
C. Current Meter (Optional)
Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5,000 feet (1500 meters) in length. If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.
Installation of the transient protection terminal block does not provide transient protection unless the
3051 case is properly grounded.
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment.Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the
terminal block.
Use the following steps to wire the transmitter:
1. Remove the housing cover on the FIELD TERMINALS side.
2. Connect the positive lead to the “+” terminal (PWR/COMM) and the negative
lead to the “–” terminal.
9
Quick Start Guide
DP
A
B
C
E
D
F
3. Ground housing to fulfill local grounding regulations.
4. Ensure proper grounding. It is important that the instrument cable shield:
a. Be trimmed close and insulated from touching the transmitter housing b. Be connected to the next shield if cable is routed through a junction box c. Be connected to a good earth ground at the power supply end
5. If transient protection is needed, refer to section “Grounding for Transient
Terminal Block” for grounding instructions.
6. Plug and seal unused conduit connections.
7. Replace the housing cover.
Figure 7. Wiring
February 2015
A. Minimize Distance B. Trim shield and insulate C. Protective Grounding Terminal
D. Insulate Shield E. Minimize Distance F. Connect Shield Back to the Power Supply
Ground
Grounding for transient terminal block
Ground termination is provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when the transient protection terminal blocks are installed. It is recommended that 18 AWG or larger wire is used to connect housing ground to earth ground (internal or external).
If the transmitter is currently not wired for power up and communication, follow procedures 1-7 of Connect the wiring and power up properly wired, refer to Figure 7 for internal and external transient grounding locations.
10
. When the transmitter is
February 2015
Quick Start Guide

Step 5: Verify configuration

Verify the configuration using any HART capable configuration tool or Local Operator Interface (LOI) - option code M4. Configuration instructions for a Field Communicator and LOI are included in this step. See Rosemount 3051 reference manual (00809-0100-4007) for configuration instructions using AMS Manager.
Verifying configuration with a Field Communicator
A Rosemount 3051 DD must be installed on the Field Communicator to verify configuration. Fast Key sequences for the latest DD are shown in Table 3 on page
11. For Fast Key sequences using legacy DD's, contact your local Emerson Process
Management representative.
Note
Emerson recommends installing the latest DD to access the complete functionality. Visit www.fieldcommunicator.com for information on updating the DD Library.
1. Verify device configuration using the fast key sequences in Tab l e 3. a. A check () indicates the basic configuration parameters. At minimum,
these parameters should be verified as part of configuration and startup.
b. A (7) indicates availability only in HART revision 7 mode.
Table 3. Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key Sequence
®
Device
Function
Alarm and Saturation Levels
Damping
Range Values
Tag
Transfer Function
Units
Burst Mode
Custom Display Configuration
Date
Descriptor
Digital to Analog Trim (4 - 20 mA Output)
Disable Configuration Buttons
Rerange with Keypad
Loop Test
Fast Key se quen ce
HART 7 HART 5
2, 2, 2, 5, 7 2, 2, 2, 5, 7
2, 2, 1, 1, 5 2, 2, 1, 1, 5
2, 2, 2 2, 2, 2
2, 2, 7, 1, 1 2, 2, 7, 1, 1
2, 2, 1, 1, 6 2, 2, 1, 1, 6
2, 2, 1, 1, 4 2, 2, 1, 1, 4
2, 2, 5, 3 2, 2, 5, 3
2, 2, 4 2, 2, 4
2, 2, 7, 1, 4 2, 2, 7, 1, 3
2, 2, 7, 1, 5 2, 2, 7, 1, 4
3, 4, 2 3, 4, 2
2, 2, 6, 3 2, 2, 6, 3
2, 2, 2, 1 2, 2, 2, 1
3, 5, 1 3, 5, 1
11
Quick Start Guide
A
February 2015
Table 3. Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key Sequence
Fast Key sequence
Function
Lower Sensor Trim
Message
Scaled D/A Trim (4 - 20 mA Output)
Sensor Temperature/Trend (3051S)
Upper Sensor Trim
Digital Zero Trim
Password
Scaled Variable
HART revision 5 to HART revision 7 switch
7
Long Tag
7
Find Device
7
Simulate Digital Signal
HART 7 HART 5
3, 4, 1, 2 3, 4, 1, 2
2, 2, 7, 1, 6 2, 2, 7, 1, 5
3, 4, 2 3, 4, 2
3, 3, 3 3, 3, 3
3, 4, 1, 1 3, 4, 1, 1
3, 4, 1, 3 3, 4, 1, 3
2, 2, 6, 5 2, 2, 6, 4
3, 2, 2 3, 2, 2
2, 2, 5, 2, 3 2, 2, 5, 2, 3
2, 2, 7, 1, 2 N/A
3, 4, 5 N/A
3, 4, 5 N/A
Verifying configuration with Local Operator Interface (LOI)
The optional LOI can be used for commissioning the device. The LOI is a two button design with internal and external buttons. The internal buttons are located on the display of the transmitter, while the external buttons are located underneath the top metal tag. To activate the LOI push any button. LOI button functionality is shown on the bottom corners of the display. See Ta bl e 4 and
Figure 9 for button operation and menu information.
Figure 8. Internal and External LOI Buttons
B
A. Internal buttons B. External buttons
12
February 2015
Assign PV
HART Revision
Note
See Figure 10 on page 15 to confirm External Button Functionality.
Table 4. LOI Button Operation
Button
Left
Right
No SCROLL
Yes ENTER
Figure 9. LOI Menu
Quick Start Guide
Switch HART revision mode
If the HART configuration tool is not capable of communicating with HART Revision 7, the 3051 will load a generic menu with limited capability. The following procedures will switch the HART revision mode from the generic menu:
1. Manual Setup > Device Information > Identification > Message
a. To change to HART Revision 5, Enter: “HART5” in the Message field. b. To change to HART Revision 7, Enter: “HART7” in the Message field.
Note
See Table 3 on page 11 to change HART revision when the correct Device Driver is loaded.
13
Quick Start Guide
February 2015

Step 6: Trim the transmitter

Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on gage and differential pressure transmitters to eliminate error due to mounting position or static pressure effects. A zero trim can be performed using either a Field Communicator or configuration buttons.
For instructions using AMS, please see the Rosemount 3051 HART 7 Product Manual (00809-0100-4007).
Note
When performing a zero trim, ensure that the equalization valve is open and all wet legs are filled to the correct level.
It is not recommended to zero an absolute transmitter, models 3051C A or 3051TA.
1. Choose your trim procedure.
a. Analog Zero Trim – Sets the analog output to 4 mA.
Also referred to as a “rerange,” it sets the Lower Range Value (LRV) equal
to the measured pressure.
The display and digital HART output remains unchanged.
b. Digital Zero Trim – Recalibrates the sensor zero.
The LRV is unaffected. The pressure value will be zero (on display and
HART output). 4 mA point may not be at zero.
This requires that the factory calibrated zero pressure is within a range of
3% of the URL [0 + 3% URL].
Example
URV = 250 inH2O Applied Zero Pressure = + 0.03 250 inH
O = + 7.5 inH2O (compared to
2
factory settings) values outside this range will be rejected by the transmitter.
Trimming with a Field Communicator
1. Connect the Field Communicator, see “Connect the wiring and power up” on
page 9 for instructions.
2. Follow the HART menu to perform the desired zero trim.
Table 5. Zero Trim Fast Keys
Analog zero (set 4 mA) Digital zero
Fast Key Se quenc e 3, 4, 2 3, 4, 1, 3
14
February 2015
Quick Start Guide
Trimming with configuration buttons
A zero trim is to be performed using one of the three possible sets of external configuration buttons located under the top tag.
To access the configuration buttons, loosen the screw and slide the tag on the top of the transmitter. Confirm the functionality using Figure 10.
Figure 10. External Configuration Buttons
D
A
A. LOI B. Analog Zero and Span
BC
C. Digital Zero D. Configuration Buttons
Use the following procedures to perform a Zero Trim:
Perform trim with LOI (option M4)
1. Set the transmitter pressure.
2. See Figure 9 on page 13 for the operating menu. a. Perform an analog zero trim by selecting Rerange.
b. Perform a digital zero trim by selecting Zero Trim.
Perform trim with analog zero and span (option D4)
1. Set the transmitter pressure.
2. Press and hold the zero button for two seconds to perform an analog zero
trim.
Perform trim with digital zero (option DZ)
1. Set the transmitter pressure.
2. Press and hold the zero button for two seconds to perform a digital zero trim.
15
Quick Start Guide
February 2015

Safety instrumented systems installation

For Safety Certified installations, refer to product manual (00809-0100-4007) for installation procedure and system requirements.
16
February 2015
Quick Start Guide

Product Certifications

European Directive Information

A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com.

Ordinary Location Certification from FM Approvals

As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by FM Approvals, a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 0T2H0.AE Standards: FM Class 3600 - 2011, FM Class 3615 - 2006, FM Class 3810 - 2005,
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III;
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 1Q4A4.AX Standards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004,
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when
Special Conditions for Safe Use (X):
1. The Model 3051 transmitter housing contains aluminum and is considered a
2. The Model 3051 transmitter with the transient terminal block (Option code T1) will
C6 CSA Explosionproof, Dust-Ignitionproof, Intrinsic Safety and Division 2
Certificate: 1053834 Standards: ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No. 30 -M1986,
Markings: Explosionproof for Class I, Division 1, Groups B, C and D; Suitable for Class I,
ANSI/NEMA 250 - 2003
T5(-50 °C ≤ T
FM Class 3810 - 2005
connected per Rosemount drawing 03031-1019; NI CL 1, DIV 2, GP A, B, C, D; T4(-50 °C ≤ T
potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact and friction.
not pass the 500 Vrms dielectric strength test and this must be taken into account during installation.
CSA Std. C22.2 No.142-M1987, CSA Std. C22.2. No.157-92, CSA Std. C22.2 No. 213 - M1987
Zone 1, Group IIB+H2, T5; Dust-Ignitionproof Class II, Division 1, Groups E, F, G; Class III Division 1; Intrinsically Safe Class I, Division 1 Groups A, B, C, D when connected in accordance with Rosemount drawing 03031-1024, Temperature Code T3C; Suitable for Class I, Zone 0; Class I Division 2 Groups A, B, C and D, T5; Suitable for Class I Zone 2, Group IIC; Type 4X; Factory Sealed; Single Seal (See drawing 03031-1053)
+85 °C); Factory Sealed; Type 4X
a
+70 °C), T5(-50 °C Ta +40 °C) [HART]; Type 4x
a
17
Quick Start Guide
Europe
E8 ATEX Flameproof and Dust
Certificate: KEMA00ATEX2013X; Baseefa11ATEX0275X Standards: EN60079-0:2012, EN60079-1:2007, EN60079-26:2007, EN60079-31:2009
Markings: II 1/2 G Ex d IIC T6/T5 Ga/Gb, T6(-50 °C ≤ T
T5(-50 °C ≤ T
II 1 D Ex ta IIIC T95 °C T
Table 6. Process Temperature
Temperature class Process temperature
T6 -50 °C to +65 °C
T5 -50 °C to +80 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
3. The capacitance of the wrap around label, being 1.6 nF, exceed the limit in Table 9 of EN60079-0. The user shall determine suitability for the specific application.
4. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking.
I1 ATEX Intrinsic Safety and Dust
Certificate: BAS97ATEX1089X; Baseefa11ATEX0275X Standards: EN60079-0:2012, EN60079-11:2012, EN60079-31:2009
Markings: II 1 G Ex ia IIC T5/T4 Ga, T5(-60 °C ≤ T
II 1 D Ex ta IIIC T95 °C T
Table 7. Input Parameters
+80 °C);
a
+65 °C),
a
105 °C Da (-20 °C ≤ Ta +85 °C)
500
+40 °C), T4(-60 °C Ta +70 °C)
a
105 °C Da (-20 °C ≤ Ta +85 °C)
500
February 2015
18
HART
Volta ge U
Current I
i
Power P
i
Capacitance C
Inductance L
i
i
i
30 V
200 mA
0.9 W
0.012 μF
0 mH
Special Conditions for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-11. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0.
3. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking.
February 2015
N1 ATE X Type n a nd D ust
Certificate: BAS00ATEX3105X; Baseefa11ATEX0275X Standards: EN60079-0:2012, EN60079-15:2010, EN60079-31:2009
Markings: II 3 G Ex nA IIC T5 Gc (–40 °C ≤ T
Special Conditions for Safe Use (X):
1. This apparatus is not capable of withstanding the 500 V insulation test that is required by EN60079-15. This must be taken into account when installing the apparatus.
2. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking.
International
E7 IECEx Flameproof and Dust
Certificate: IECEx KEM 09.0034X; IECEx BAS 10.0034X
Standards: IEC60079-0:2011, IEC60079-1:2007-04, IEC60079-26:2006,
IEC60079-31:2008
Markings: Ex d IIC T6/T5 Ga/Gb, T6(-50 °C ≤ T
Ex ta IIIC T95 °C T
Table 8. Process Temperature
Tem per atu re c las s Process temperature
+70 °C);
a
II 1 D Ex ta IIIC T95 °C T
500
T6 -50 °C to +65 °C
T5 -50 °C to +80 °C
105 °C Da (-20 °C ≤ Ta +85 °C)
500
+65 °C), T5(-50 °C Ta +80 °C);
a
105 °C Da (-20 °C ≤ Ta +85 °C)
Quick Start Guide
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
3. The capacitance of the wrap around label, being 1.6 nF, exceed the limit in Table 9 of EN60079-0. The user shall determine suitability for the specific application.
4. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking.
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 09.0076X Standards: IEC60079-0:2011, IEC60079-11:2011 Markings: Ex ia IIC T5/T4 Ga, T5(-60 °C ≤ T
+40 °C), T4(-60 °C Ta +70 °C)
a
Table 9 . Input Pa ramete rs
HART
Volt age U
Current I
i
Power P
i
Capacitance C
Inductance L
i
i
i
30 V
200 mA
0.9 W
0.012 μF
0 mH
19
Quick Start Guide
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by IEC60079-11. This must be taken into account when installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in Zone 0.
IECEx Mining (Special A0259) Certificate: IECEx TSA 14.0001X Standards: IEC60079-0:2011, IEC60079-11:2011 Markings: Ex ia I Ma (-60 °C ≤ T
Table 10. Input Parameters
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by IEC60079-11. This must be taken into account when installing the apparatus.
2. It is a condition of safe use that the above input parameters shall be taken into account during installation.
3. It is a condition of manufacture that only the apparatus fitted with housing, covers and sensor module housing made out of stainless steel are used in Group I applications.
N7 IECEx Type n
Certificate: IECEx BAS 09.0077X Standards: IEC60079-0:2011, IEC60079-15:2010 Markings: Ex nA IIC T5 Gc (-40 °C ≤ T
Special Condition for Safe Use (X):
1. The apparatus is not capable of withstanding the 500 V insulation test required by IEC60079-15. This must be taken into account when installing the apparatus.
+70 °C)
a
HART
Volt age U
Capacitance C
Inductance L
Current I
Power P
i
i
i
i
i
+70 °C)
a
February 2015
30 V
200 mA
0.9 W
0.012 μF
0 mH
Brazil
E2 INMETRO Flameproof
Certificate: UL-BR 13.0643X Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011,
Markings: Ex d IIC T6/T5 Ga/Gb, T6(-50 °C ≤ T
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
20
ABNT NBR IEC60079-1:2009 + Errata 1:2011, ABNT NBR IEC60079-26:2008 + Errata 1:2008
+65 °C), T5(-50 °C Ta +80 °C)
a
February 2015
2. In case of repair, contact the manufacturer for information on the dimensions of the flameproof joints.
3. The capacitance of the wrap around label, being 1.6 nF, exceeds the limit in Table 9 of ABNT NBR IEC 60079-0. The user shall determine suitability for the specific application.
I2 INMETRO Intrinsic Safety
Certificate: UL-BR 13.0584X Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009 Markings: Ex ia IIC T5/T4 Ga, T5(-60 °C ≤ T
Table 11. Input Parameters
Capacitance C
Inductance L
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90V transient suppressor, it is not capable of withstanding the 500 V insulation test required by ABNT NBR IRC 60079-11:2008. This must be taken into account when installing the equipment.
2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in Zone 0.
HART
Volt age U
Current I
Power P
i
i
i
i
i
Quick Start Guide
+40 °C), T4(-60 °C Ta +70 °C)
a
30 V
200 mA
0.9 W
0.012 μF
0 mH
China
E3 China Flameproof
Certificate: GYJ14.1041X; GYJ10.1313X [Flowmeters] Standards: GB3836.1-2000, GB3836.2-2000, GB4208-1993, GB12476-2000 Markings: Ex d IIC T6/T5, T6(-50 °C ≤ T
Special Condition for Safe Use (X):
Refer to Appendix B of the Rosemount 3051 reference manual (00809-0100-4007).
I3 China Intrinsic Safety
Certificate: GYJ13.1362X; GYJ101312X [Flowmeters] Standards: GB3836.1-2010, GB3836.4-2010, GB3836.20-2010, GB12476.1-2000 Markings: Ex ia IIC T5/T4 Ga, T5(-60 °C ≤ T
Special Condition for Safe Use (X):
Refer to Appendix B of the Rosemount 3051 reference manual (00809-0100-4007).
N3 China Type n
Certificate: GYJ101111X Standards: GB3836.1-2000, GB3836.8-2003 Markings: Ex nA IIC T5(-40 °C ≤ T
Special Condition for Safe Use (X):
Refer to Appendix B of the Rosemount 3051 reference manual (00809-0100-4007).
DIP A20 T
80 °C
A
+65 °C), T5(-50 °C Ta +80 °C)
a
+40 °C), T4(-60 °C Ta +70 °C);
a
+70 °C)
a
21
Quick Start Guide
Japan
E4 Japan Flameproof
Certificate: TC20577, TC20578, TC20583, TC20584
Markings: Ex d IIC T5
Technical Regulations Customs Union (EAC)
EM EAC Flameproof
Certificate: RU C-US.Gb05.B.00400
Markings: Ga/Gb Ex d IIC T5/T6 X, T5(-60 °C ≤ T
Special Condition for Safe Use (X):
See certificate for special conditions.
IM EAC Intrinsically Safe
Certificate: RU C-US.Gb05.B.00400
Markings: HART: 0Ex ia IIC T4/T5 Ga X, T4(-60 °C ≤ T
Fieldbus/PROFIBUS
Special Condition for Safe Use (X):
See certificate for special conditions.
®
: 0Ex ia IIC T4 Ga X (-60 °C ≤ Ta +60 °C)
+80 °C), T6(-60 °C Ta +65 °C)
a
a
Combinations
K2 Combination of E2 and I2 K5 Combination of E5 and I5 K6 Combination of C6, E8, and I1 K7 Combination of E7, I7, and N7 K8 Combination of E8, I1, and N1 KB Combination of E5, I5, and C6 KD Combination of E8, I1, E5, I5, and C6 KM Combination of EM and IM
February 2015
+70 °C), T5(-60 °C Ta +40 °C)
Conduit Plugs and Adapters
IECEx Flameproof and Increased Safety Certificate: IECEx FMG 13.0032X Standards: IEC60079-0:2011, IEC60079-1:2007, IEC60079-7:2006-2007 Markings: Ex de IIC Gb
ATEX Flameproof and Increased Safety Certificate: FM13ATEX0076X Standards: EN60079-0:2012, EN60079-1:2007, IEC60079-7:2007
Markings: II 2 G Ex de IIC Gb
Table 12. Conduit Plug Thread Sizes
Thread Identification mark
M20 1.5 M20
22
1
/2 - 14 NPT
G1/2A G1/2
1
/2 NPT
February 2015
Table 13. Thread Adapter Thread Sizes
Male thread Identification mark
M20 1.5 M20
1
/2 - 14 NPT
G1/2A G1/2
Femal e thread Identification mark
M20 1.5 - 6H M20
1
/2 - 14 NPT
PG 13.5 PG 13.5
1
Special Conditions for Safe Use (X):
1. When the thread adapter is used with an enclosure in type of protection increased safety “e” the entry thread shall be suitably sealed in order to maintain the ingress protection rating (IP) of the enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms.
1
G
/2 and PG 13.5 thread forms are only acceptable for existing (legacy) equipment
installations.
Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate: 09-HS446883A-PDA Intended Use: Measure gauge or absolute pressure of liquid, gas or vapor applications
ABS Rules: 2009 Steel Vessels Rules 1-1-4/7.7, 4-6-2/5.15, 4-8-3/13.1
SBV Bureau Veritas (BV) Type Approval
Certificate: 23155/A3 BV Requirements: Bureau Veritas Rules for the Classification of Steel Ships Application: Class notations: AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS; Pressure
SDN Det Norske Veritas (DNV) Type Approval
Certificate: A-14086 Intended Use: Det Norske Veritas' Rules for Classification of Ships, High Speed & Light
Application:
SLL Lloyds Register (LR) Type Approval
Certificate: 11/60002 Application: Environmental categories ENV1, ENV2, ENV3 and ENV5
C5 Custody Transfer - Measurement Canada Accuracy Approval
Certificate: AG-0226; AG-0454; AG-0477
on ABS classed vessels, marine, and offshore installations.
transmitter type 3051 cannot be installed on diesel engines
Craft and Det Norske Veritas' Offshore Standards
Location classes
Typ e 3051
Tem pe ra tu r e D
Humidity B
Vibration A
EMC B
Enclosure D
1
/2 NPT
/2 - 14 NPT
Quick Start Guide
23
Quick Start Guide
Figure 11. Rosemount 3051 EC Declaration of Conformity
February 2015
24
February 2015
Quick Start Guide
25
Quick Start Guide
February 2015
26
February 2015
Quick Start Guide
27
Rosemount World Headquarters
Emerson Process Management
6021 Innovation Blvd Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com
North America Regional Office
Emerson Process Management
8200 Market Blvd. Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Process Management
1300 Concord Terrace, Suite 400 Sunrise, Florida, 33323, USA
+1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@EmersonProcess.com
Europe Regional Office
Emerson Process Management Europe GmbH
Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland
+41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@EmersonProcess.com
Asia Pacific Regional Office
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent Singapore 128461
+65 6777 8211 +65 6777 0947
Enquiries@AP.EmersonProcess.com
Middle East and Africa Regional Office
Emerson Process Management
Emerson FZE P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
+971 4 8118100 +971 4 8865465
RFQ.RMTMEA@Emerson.com
00825-0100-4007
Quick Start Guide
00825-0100-4007, Rev CB
Standard Terms and Conditions of Sale can be found at: www.rosemount.com\terms_of_sale. AMS and the Emerson logo are registered trademarks and service marks of Emerson Electric Co. Rosemount and Rosemount logotype are registered trademarks of Rosemount Inc. HART is a registered trademark of the HART Communication Foundation. DTM is a trademark of the FDT Group. PROFIBUS is a registered trademark of PROFINET International (PI). All other marks are the proper ty of their respective owners. © 2015 Rosemount Inc. All rights reserved.
February 2015
Loading...