Emerson Process Management 2700 User Manual

Configuration and Use Manual
P/N 20000327, Rev. FB June 2011
Micro Motion
®
Model 2700 Transmitter with PROFIBUS-PA
Configuration and Use Manual
The Emerson logo is a trademark and service mark of Emerson Electric Co. Micro Motion, ELITE, ProLink, MVD and MVD Direct Connect are marks of one of the Emerson Process Management family of companies. All other trademarks are property of their respective owners.
Contents
Chapter 1 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Determining transmitter information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.4 PROFIBUS-PA functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5 Determining version information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.6 Communication tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.7 Planning the configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.8 Pre-configuration worksheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.9 Flowmeter documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.10 Micro Motion customer service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter 2 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Applying power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Setting the node address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Configuring the analog input function block channels. . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5 Setting the I/O mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.5.1 Overriding the status byte format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.6 Configuring the totalizer block mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7 Configuring pressure compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7.1 Pressure compensation values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.7.2 Enabling pressure compensation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.7.3 Configuring a pressure source. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.8 Configuring temperature compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.8.1 Enabling external temperature compensation . . . . . . . . . . . . . . . . . . . . . 16
2.8.2 Configuring a temperature source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Chapter 3 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2 Characterization, Smart Meter Verification, meter validation, and calibration . . . . . . 19
3.2.1 Characterization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.2 Smart Meter Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.3 Meter validation and meter factors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.4 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.5 Comparison and recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.3 Performing a characterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.3.1 Characterization parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.3.2 How to characterize . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4 Performing Smart Meter Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.4.1 Preparing for the Smart Meter Verification test . . . . . . . . . . . . . . . . . . . . 26
3.4.2 Running the Smart Meter Verification test . . . . . . . . . . . . . . . . . . . . . . . . 26
3.4.3 Reading and interpreting Smart Meter Verification test results . . . . . . . . 31
3.4.4 Setting up automatic or remote execution of the
Smart Meter Verification test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Configuration and Use Manual iii
Contents
3.5 Performing meter validation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.6 Performing zero calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.1 Preparing for the zeroing procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.2 Zeroing procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.7 Performing density calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.7.1 Preparing for density calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3.7.2 Density calibration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3.8 Performing temperature calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Chapter 4 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.2 Default target mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.3 Configuration map. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.4 Configuring standard volume flow measurement for gas . . . . . . . . . . . . . . . . . . . . . 48
4.5 Changing the measurement units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.6 Configuring the petroleum measurement application . . . . . . . . . . . . . . . . . . . . . . . . 55
4.6.1 About the petroleum measurement application . . . . . . . . . . . . . . . . . . . . 55
4.6.2 Configuration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
4.7 Configuring the concentration measurement application . . . . . . . . . . . . . . . . . . . . . 59
4.7.1 About the concentration measurement application . . . . . . . . . . . . . . . . . 59
4.7.2 Configuration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.8 Changing the output scale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
4.9 Changing process alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
4.9.1 Alarm values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
4.9.2 Alarm hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
4.10 Configuring status alarm severity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
4.11 Changing the damping values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4.11.1 Damping and volume measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4.12 Changing slug flow limits and duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4.13 Configuring cutoffs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
4.14 Changing the measurement mode parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
4.15 Configuring sensor parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
4.16 Configuring the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.16.1 Enabling and disabling display functions . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.16.2 Changing the scroll rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4.16.3 Changing the update period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4.16.4 Changing the off-line password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4.16.5 Changing the display language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4.16.6 Changing the display variables and precision . . . . . . . . . . . . . . . . . . . . . 78
4.17 Enabling LD Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Chapter 5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.2 Using the I&M functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.3 Recording process variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.4 Viewing process variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.4.1 With the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.4.2 With ProLink II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.4.3 With PROFIBUS EDD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.4.4 With bus parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.5 Using sensor simulation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.6 Accessing diagnostic information with a PROFIBUS host . . . . . . . . . . . . . . . . . . . . 86
iv Model 2700 Transmitter with PROFIBUS-PA
Contents
5.7 Viewing transmitter status and alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
5.7.1 With the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
5.7.2 With ProLink II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.7.3 With EDD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
5.7.4 With bus parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
5.8 Using the totalizers and inventories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
5.8.1 Viewing current values for totalizers and inventories . . . . . . . . . . . . . . . . 88
5.8.2 Controlling the totalizers and inventories . . . . . . . . . . . . . . . . . . . . . . . . . 90
Chapter 6 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.2 Guide to troubleshooting topics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.3 Transmitter does not operate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.4 Transmitter does not communicate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.5 Function blocks in Out-of-Service mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.6 Zero or calibration failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.7 Output problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
6.7.1 Damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.7.2 Low-flow cutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.7.3 Output scale. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.7.4 Characterization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.7.5 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.8 Status alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
6.9 Diagnosing wiring problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
6.9.1 Checking the power-supply wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
6.9.2 Checking the sensor-to-transmitter wiring . . . . . . . . . . . . . . . . . . . . . . . 102
6.9.3 Checking the grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
6.9.4 Checking the communication wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
6.10 Checking slug flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
6.11 Restoring a working configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
6.12 Checking the test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
6.12.1 Obtaining the test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
6.12.2 Evaluating the test points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
6.12.3 Excessive drive gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
6.12.4 Erratic drive gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
6.12.5 Low pickoff voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
6.13 Checking the core processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
6.13.1 Exposing the core processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
6.13.2 Checking the core processor LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
6.13.3 Core processor resistance test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
6.14 Checking sensor coils and RTD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
6.14.1 9-wire remote or remote core processor with
remote transmitter installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
6.14.2 4-wire remote or integral installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Appendix A Flowmeter Installation Types and Components . . . . . . . . . . . . . . . 115
A.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
A.2 Installation diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
A.3 Component diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
A.4 Wiring and terminal diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Configuration and Use Manual v
Contents
Appendix B Using the Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
B.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
B.2 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
B.3 Using the optical switches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
B.4 Using the display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
B.4.1 Display language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
B.4.2 Viewing process variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
B.4.3 Using display menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
B.4.4 Display password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
B.4.5 Entering floating-point values with the display. . . . . . . . . . . . . . . . . . . . 124
B.5 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
B.6 Display menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Appendix C Connecting with ProLink II. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
C.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
C.2 Connecting to a personal computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
C.2.1 Connecting to the service port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Appendix D PROFIBUS-PA Status Byte . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
D.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
D.2 Classic-mode status byte format. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
D.3 Condensed-mode status byte format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Appendix E Slave Diagnostic Response Bytes. . . . . . . . . . . . . . . . . . . . . . . . 141
E.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
E.2 PROFIBUS specification diagnostic bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Appendix F Model 2700 PROFIBUS Block Parameters . . . . . . . . . . . . . . . . . . 151
F.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
F.2 Slot identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
F.3 Physical block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
F.3.1 Physical block object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
F.3.2 Physical block views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
F.4 Transducer block 1 (measurement, calibration, and diagnosis) . . . . . . . . . . . . . . . 154
F.4.1 Transducer block 1 object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
F.4.2 Transducer block 1 (measurement, calibration,
and diagnosis) views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
F.4.3 Transducer block 2 (device information, API, CM) parameters . . . . . . . 172
F.4.4 Transducer block 2 object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
F.4.5 Transducer block 2 (device information, API, CM) views . . . . . . . . . . . . 177
F.4.6 I & M functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
F.4.7 AI function block parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
F.4.8 Analog input block objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
F.4.9 AI function block views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
F.4.10 AO function block parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
F.4.11 Analog output block objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
F.4.12 AO function block views. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
F.4.13 Totalizer block parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
F.4.14 Totalizer block objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
F.4.15 Totalizer function block views. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
vi Model 2700 Transmitter with PROFIBUS-PA
Contents
Appendix G NE53 History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
G.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
G.2 Software change history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Configuration and Use Manual vii
viii Model 2700 Transmitter with PROFIBUS-PA
Chapter 1
2700 * 1 * G * * * * * *
Mounting code:
• R = 4-wire remote mount
• I = Integral mount
• B = 4-wire remote mount to 9-wire remote core processor
• C = 9-wire remote mount
Display code
• 1 = Display with glass lens
• 2 = Backlit display with glass lens
• 3 = No display
• 5 = Backlit display with IIC approval, glass lens
• 7 = Backlit display with non-glass lens
Output option code
• G = PROFIBUS-PA
Software code 1: G = Concentration measurement application A = Petroleum measurement (API) application
Software code 2: C = Smart Meter Verification

Before You Begin

1.1 Overview

This chapter provides an orientation to the use of this manual, and includes a configuration overview flowchart and a pre-configuration worksheet. This manual describes the procedures required to start, configure, use, maintain, and troubleshoot Micro Motion PROFIBUS-PA.
®
Model 2700 transmitters with

1.2 Safety

Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.

1.3 Determining transmitter information

Transmitter options are indicated by the model number located on the transmitter tag. The model number is a string of the following form:
Startup ConfigurationCalibrationBefore You Begin
Configuration and Use Manual 1
Before You Begin

1.4 PROFIBUS-PA functionality

The transmitter supports the following methods of configuration and operation:
Configuration methods:
- Device description (EDD) for use with a PROFIBUS configuration tool such as Siemens Simatic
®
Process Device Manager (PDM). In this manual, the term “EDD” is used to refer
to this type of configuration.
- Direct read and write of PROFIBUS-PA bus parameters.
Operation methods:
- GSD file with a PROFIBUS host. The transmitter supports two GSD options— Profile-specific, which is created by PNO, and Manufacturer-specific, which is created by by Micro Motion in order to implement a larger set of function blocks. See Section 2.5 for more information about the two GSD options.
In this manual, the term “host” or “PROFIBUS host” is used to refer to this type of operation.
- Device description (EDD) with PROFIBUS configuration tool (e.g., Simatic PDM). The EDD provides a superset of the operational functionality of the GSD, plus configuration capability.
Identification and maintenance (I&M) functions:
®
-I&M 0
-I&M 1
-I&M 2
-PA I&M 0
The transmitter supports both classic and condensed status byte formats.
Classic mode conforms to the PROFIBUS-PA Profile v3.01, Section 3.7.3.6.
Condensed mode conforms to the PROFIBUS-PA Specification June 2005 Amendment 2 to the PROFIBUS Profile v3.01, Condensed Status and Diagnostic Messages v1.0.

1.5 Determining version information

Table 1-1 lists the version information you may need to know and describes how to obtain the information. This manual assumes transmitter firmware v3.2 or a later version and ProLink v2.92 with the Build 9827 patch or a later version.
Note: The hardware for transmitters with v2.0 and lower firmware is incompatible with the hardware needed to support v3.0 and later firmware. To upgrade from an earlier firmware version to v3.0 or higher firmware requires hardware replacement.
Table 1-1 Obtaining version information
Component Tool Method
Transmitter software With ProLink II View > Installed Options > Software Revision
With EDD MMI Coriolis Flow > Transducer Block > Device
Information > Software Rev
With display OFF-LINE MAINT > VER
2 Model 2700 Transmitter with PROFIBUS-PA
Before You Begin
Table 1-1 Obtaining version information (continued)
Component Tool Method
Core processor software With ProLink II Not available
ProLink II With ProLink II Help > About ProLink II
GSD version
EDD version Text editor Open file MMIcorflow.DDL and check parameter
(1) There are two GSD options available: Manufacturer-specific and Profile-specific. See Section 2.5 for more information.
(1)

1.6 Communication tools

Most of the procedures described in this manual require the use of a communication tool. Table 1-2 lists the communication tools that can be used, with their functionality and requirements.
Note: You can use ProLink II, the EDD, or PROFIBUS bus parameters for transmitter setup and maintenance. It is not necessary to have more than one of these methods available.
With EDD Not available
With display OFF-LINE MAINT > VER
Text editor Open file V3x_057A.gsd or PA139742.GSD and
check parameter GSD_Revision
DD_REVISION
Startup ConfigurationCalibrationBefore You Begin
Table 1-2 Communication tools for Model 2700 transmitter with PROFIBUS-PA
Functionality
Tool
Transmitter display Partial Partial Transmitter with display
ProLink II Full Full ProLink II v2.92 or later
(1)
Host
EDD Full Full PDM file set
Bus parameters Full Full None
(1) There are two GSD options available: Manufacturer-specific and Profile-specific. See Section 2.5 for more information.
Partial None GSD file V3x_057A.gsd or
RequirementsView/operation Setup/maintenance
PA139742.GSD
The PDM and GSD files can be downloaded from the following address:
http://www.emersonprocess.com/micromotion/softwaredownloads
Also available at this address is a document titled Commissioning MVD Profibus PA Documentation
®
Supplement. This supplement will assist you with connecting to the transmitter with Siemens Simatic
®
Process Device Manager (PDM). If you are using Simatic PDM, download the PDM file set
and follow the EDD instructions in this manual.
Basic information on using the display is provided in Appendix B.
Basic information on ProLink II is provided in Appendix C. For more information, refer to the ProLink II manual, which is available on the Micro Motion web site (www.micromotion.com). Although some functions of the Model 2700 transmitter with PROFIBUS-PA may be available through earlier versions of ProLink II, version 2.92 with the Build 9827 patch or a later version is required for full configuration, maintenance, and operation.
Configuration and Use Manual 3
Before You Begin
Chapter 2
Flowmeter Startup
Chapter 1
Before You Begin
Fill out pre-configuration
worksheet
Apply power
Set node address
Chapter 3
Calibration OPTIONAL
Characterize the flowmeter
Zero the flowmeter
Verify meter performance
Validate against a standard
Calibrate for density
Calibrate for temperature
Chapter 4
Configuration
Configure AI function block
channels
Set I/O mode
Measurement units
Output scale
Process alarms
Damping
Slug flow
Alarm severity
Gas standard volume
Petroleum measurement
Concentration measurement
Cutoffs
Measurement mode
Device settings
Sensor parameters
Display functionality
Optional:
Configure pressure
compensation
Optional:
Configure temperature
compensation

1.7 Planning the configuration

Refer to the configuration overview flowchart in Figure 1-1 to plan transmitter configuration. In general, perform configuration steps in the order shown here.
Note: Depending on your installation and application, some configuration tasks may be optional.
Note: This manual provides information on topics that are not included in the configuration overview flowchart, e.g., using the transmitter, troubleshooting, and calibration procedures. Be sure to review these topics as required.
Figure 1-1 Configuration overview
4 Model 2700 Transmitter with PROFIBUS-PA
Before You Begin

1.8 Pre-configuration worksheet

The pre-configuration worksheet provides a place to record information about your flowmeter and your application. This information will affect your configuration options as you work through this manual. You may need to consult with transmitter installation or application process personnel to obtain the required information.
If you are configuring multiple transmitters, make copies of this worksheet and fill one out for each individual transmitter.
PRE-CONFIGURATION WORKSHEET FOR TRANSMITTER:
TRANSMITTER SENSOR
MODEL NUMBER MODEL NUMBER
SERIAL NUMBER SERIAL NUMBER
SOFTWARE VERSION
NODE ADDRESS
MEASUREMENT UNITS
MASS FLOW VOLUME FLOW
DENSITY PRESSURE
TEMPERATURE
INSTALLED APPLICATIONS
METER VERIFICATION SOFTWARE
PETROLEUM MEASUREMENT APPLICATION
CONCENTRATION MEASUREMENT APPLICATION
Startup ConfigurationCalibrationBefore You Begin
Configuration and Use Manual 5
Before You Begin

1.9 Flowmeter documentation

Table 1-3 lists documentation sources for additional information.
Table 1-3 Flowmeter documentation resources
Topic Document
Sensor installation Sensor documentation
Transmitter installation Micro Motion® Model 1700 and Model 2700
Connecting the transmitter to Simatic PDM Commissioning MVD Profibus PA Documentation
Hazardous area installation See the approval documentation shipped with the

1.10 Micro Motion customer service

For customer service, phone the support center nearest you:
In the U.S.A., phone
800-522-MASS (800-522-6277) (toll-free)
In Canada and Latin America, phone +1 303-527-5200 (U.S.A.)
Transmitters: Installation Manual
Supplement
transmitter, or download the appropriate documentation from the Micro Motion web site (www.micromotion.com)
•In Asia:
- In Japan, phone 3 5769-6803
- In other locations, phone +65 6777-8211 (Singapore)
•In Europe:
- In the U.K., phone 0870 240 1978 (toll-free)
- In other locations, phone +31 (0) 318 495 555 (The Netherlands)
Customers outside the U.S.A. can also email Micro Motion customer service at: flow.support@emerson.com.
6 Model 2700 Transmitter with PROFIBUS-PA
Chapter 2

Startup

2.1 Overview

This chapter describes the procedures you should perform the first time you start the flowmeter. You do not need to use these procedures every time you cycle power to the flowmeter.
The procedures in this section will enable you to:
Apply power to the flowmeter (Section 2.2)
Set the node address (Section 2.3)
Configure the AI block channels (Section 2.4)
Set the I/O mode of the transmitter (Section 2.5)
Configure the totalizer block mode (Section 2.6)
Optional: Configure pressure compensation (Section 2.7)
Optional: Configure temperature compensation (Section 2.8)
Note: All procedures provided in this chapter assume that you have established communication with the transmitter and that you are complying with all applicable safety requirements. See Appendix C or the documentation for your PROFIBUS host or configuration tool.

2.2 Applying power

Before you apply power to the flowmeter, close and tighten all housing covers.
Operating the flowmeter without covers in place creates electrical hazards that can cause death, injury, or property damage. Make sure all covers are in place before applying power to the transmitter.
Turn on the electrical power at the power supply. The flowmeter will automatically perform diagnostic routines. If the transmitter has a display, the status LED will turn green and begin to flash when the transmitter has finished its startup diagnostics.
Note: If this is the initial startup, or if power has been off long enough to allow components to reach ambient temperature, the flowmeter is ready to receive process fluid approximately one minute after power-up. However, it may take up to ten minutes for the electronics in the flowmeter to reach thermal equilibrium. During this warm-up period, you may observe minor measurement instability or inaccuracy.
Startup ConfigurationCalibrationBefore You Begin
Configuration and Use Manual 7
Startup

2.3 Setting the node address

The factory default setting for the node address is 126. To set the node address:
With the display, choose
OFF-LINE MAINT > CONFG > ADDRESS PBUS.
With ProLink II, choose
ProLink > Configuration > Device (Profibus) > Profibus Address.
With a PROFIBUS host, use the change address function of the host.

2.4 Configuring the analog input function block channels

You can set each of the transmitter’s AI function blocks to measure one transducer block channel. The AI blocks are set at the factory to a default setting that is adequate for most applications, but you can change the assignment of the AI blocks to meet special needs.
The default channel configuration for each block is shown in Table 2-1.
Table 2-1 Default channel configuration
Block Default channel Default units
AI 1 Mass flow kg/s
AI 2 Temperature K
AI 3 Density kg/l
AI 4 Volume flow m
The available transducer block channels are shown in Table 2-2.
3
/h
Table 2-2 Process variables by transducer block channel
Channel value
Process variableSlot Index Value
11 (0x0B) 17 (0x11) 0x0B11 Volume flow
11 (0x0B) 21 (0x15) 0x0B15 Mass flow
11 (0x0B) 25 (0x19) 0x0B19 Density
11 (0x0B) 29 (0x1D) 0x0B1D Temperature
11 (0x0B) 64 (0x40) 0x0B40 Gas standard volume flow
11 (0x0B) 114 (0x72) 0x0B72 Pressure
11 (0x0B) 160 (0xA0) 0x0BA0 Drive gain
12 (0x0C) 29 (0x1D) 0x0C1D Petroluem measurement – corrected density
12 (0x0C) 30 (0x1E) 0x0C1E Petroluem measurement – corrected volume flow
12 (0x0C) 31 (0x1F) 0x0C1F Petroluem measurement – average corrected density
12 (0x0C) 32 (0x20) 0x0C20 Petroluem measurement – average corrected temp
12 (0x0C) 33 (0x21) 0x0C21 Petroluem measurement – CTL
12 (0x0C) 47 (0x2F) 0x0C2F Concentration measurement – reference density
12 (0x0C) 48 (0x30) 0x0C30 Concentration measurement – specific gravity
12 (0x0C) 49 (0x31) 0x0C31 Concentration measurement – standard volume flow
12 (0x0C) 50 (0x32) 0x0C32 Concentration measurement – net mass flow
8 Model 2700 Transmitter with PROFIBUS-PA
Startup
ProLink II
Function blocks tab
Apply
ProLink > Configuration
Select a channel for each
AI function block
Select units for each AI
and AO function block
EDD
Bus parameters
Block: Analog Input Block (Slots 1, 2, 3, and 5) Index: 30 (transducer block channel)
Channel
Block: Analog Input Block (Slots 1, 2, 3, and 5) Index 28, Parameter 3 (units index)
AI Block units
Block: Analog Output Block (Slots 9 and 10) Index 27, Parameter 3 (units index)
AO Block
units
Table 2-2 Process variables by transducer block channel (continued)
12 (0x0C) 51 (0x33) 0x0C33 Concentration measurement – net volume flow
12 (0x0C) 52 (0x34) 0x0C34 Concentration measurement – concentration
12 (0x0C) 53 (0x35) 0x0C35 Concentration measurement – Baume
To configure the AI function block channels:
With the EDD, bus parameters, or ProLink II, see the menu flowcharts in Figure 2-1.
With the display, see the menu flowchart in Figure B-14.
Figure 2-1 Configuring channels and units – EDD, bus parameters, and ProLink II
Startup ConfigurationCalibrationBefore You Begin
Configuration and Use Manual 9
Startup
EDD Bus parameters

2.5 Setting the I/O mode

The transmitter can function in two different I/O modes: Profile-specific and Manufacturer-specific. The factory default is Manufacturer-specific. The two modes control which function blocks are available for use, and whether the format of the status byte is “classic” or “condensed.” (See Appendix D for more information on the format of the status byte.)
In Profile-specific mode, the transmitter has the use of three AI blocks and one totalizer block. The status byte output format defaults to classic mode.
In Manufacturer-specific mode, the transmitter has the use of four AI blocks, four totalizer blocks, and two AO blocks. The status byte output format defaults to condensed mode.
Refer to Table 2-3 for the slot identifications and blocks permitted by each mode. You must select modules exactly as described in Table 2-3, or select an empty module for slots that you do not intend to use. If any modules are left unconfigured, the transmitter will not send data.
Table 2-3 I/O mode slot configurations
Slot Profile-specific mode Manufacturer-specific mode
1 AI 1 AI 1
2 AI 2 AI 2
3 AI 3 AI 3
4 Totalizer 1 Totalizer 1
5AI 4
6 Totalizer 2
7 Totalizer 3
8 Totalizer 4
9AO 1
10 AO 2
To set the I/O mode of the transmitter:
With the EDD or bus parameters, see the menu flowcharts in Figure 2-2.
With the display, choose
Figure 2-2 Setting the I/O mode
There are two GSD files that correspond to the two I/O modes. If you are using a PROFIBUS host with GSD files to operate the transmitter, you must use the GSD that corresponds to the I/O mode you have chosen. Table 2-4 lists the GSD file names. Load the correct GSD file into your PROFIBUS host or configuration tool.
OFFLINE_MAINT > CONFG > IDENT SEL.
10 Model 2700 Transmitter with PROFIBUS-PA
Startup
Block: Physical Block 1 (Slot 0) Index 43 (Condensed status diagnostics)
Status byte format
EDD Bus parameters
Note: Set the I/O mode in the Physical Block before loading the GSD file.
Table 2-4 PROFIBUS GSD file names
Identification number GSD file name
Profile specific PA139742.GSD
Manufacturer specific V3x_057A.gsd

2.5.1 Overriding the status byte format

Each I/O mode has a default status byte format – classic or condensed. To override this default:
With the GSD, set the Condensed Status parameterization bit to either 1 (for condensed status) or 0 (for classic status).
With the EDD or bus parameters, use the menu flowcharts in Figure 2-3.
Figure 2-3 Status byte format

2.6 Configuring the totalizer block mode

The behavior of the four totalizer function blocks can be configured in two ways:
Standard, which provides standard PROFIBUS totalizer function block behavior.
In this mode, the totalizer block will integrate whatever data it receives. The Out value of a totalizer in this mode has no relationship to the totalizer data reported by the transducer block, ProLink II, or the display.
Any of the values in Table 2-5, which cause the totalizer function block to pass through the specified totalizer value from the transducer block.
Micro Motion recommends using one of these modes, because the totalizer block output will be more accurate and will match readings taken with ProLink II and the display.
To configure the totalizer block mode:
Startup ConfigurationCalibrationBefore You Begin
Configuration and Use Manual 11
With the EDD or bus parameters, refer to the menu flowcharts in Figure 2-4.
With the display, refer to the menu flowcharts in Figure B-16.
Startup
EDD
Block: Totalizer 1 (Slot 4) Index 52 (set to Mode value from table)
Mode
Block: Totalizer 1 (Slot 4) Index 52 (set to Mode value from table)
Block: Totalizer 1 (Slot 4) Index 52 (set to Mode value from table)
Block: Totalizer 1 (Slot 4) Index 52 (set to Mode value from table)
Bus parameters
MMI Coriolis Flow > Function Block
Totalizer 1 > Parameter
Integrator Function
Block
Totalizer 2 > Parameter
Totalizer 3 > Parameter
Totalizer 4 > Parameter
Selection
Figure 2-4 Configuring totalizer function block mode
Table 2-5 Process variables by transducer block channel
Channel value
Process variableSlot Index Value
11(0x0B) 17(0x11) 0x0B11 Volume flow
11(0x0B) 21(0x15) 0x0B15 Mass flow
11(0x0B) 64(0x40) 0x0B40 Gas standard volume flow
12(0x0C) 30(0x1E) 0x0C1E Petroleum measurement – corrected volume flow
12(0x0C) 49(0x31) 0x0C31 Concentration measurement – standard volume flow
12(0x0C) 50(0x32) 0x0C32 Concentration measurement – net mass flow
12(0x0C) 51(0x33) 0x0C33 Concentration measurement – net volume flow
12 Model 2700 Transmitter with PROFIBUS-PA
Startup

2.7 Configuring pressure compensation

Due to process pressure change away from calibration pressure, there can be a change in sensor flow and density sensitivity. This change is called pressure effect. Pressure compensation corrects for these changes.
Not all sensors and applications require pressure compensation. Contact Micro Motion Customer Service before you configure pressure compensation.
Configuring pressure compensation requires three steps:
1. Determining pressure compensation values (Section 2.7.1)
2. Enabling pressure compensation (Section 2.7.2)
3. Selecting a pressure source (Section 2.7.3)

2.7.1 Pressure compensation values

There are three values involved in pressure compensation:
Flow factor – The flow factor is the percent change in flow rate per psi. Consult the product data sheet for your sensor for this value. You will need to reverse the sign of the flow factor. For example, if the flow factor in the product data sheet is –0.001% per psi, the pressure compensation flow factor would be +0.001% per psi.
Density factor – The density factor is the change in fluid density, in g/cm product data sheet for your sensor for this value. You will need to reverse the sign of the density factor. For example, if the density factor in the product data sheet is –0.00004 g/cm per psi, the pressure compensation flow factor would be +0.00004 g/cm
Flow calibration pressure – The pressure at which the flowmeter was calibrated. Refer to the calibration document shipped with your sensor. If the data is unavailable, use 20 psi (1,4 bar).
3
per psi. Consult the
3
per psi.
Startup ConfigurationCalibrationBefore You Begin
3
Configuration and Use Manual 13
Startup
Block: Transducer Block 1 (Slot 11) Index 112 (enable pressure compensation)
Enable pressure
comp.
Block: Transducer Block 1 (Slot 11) Index 116 (flow factor) Index 117 (density factor) Index 118 (flow calibration pressure)
Pressure correction
values
Block: Transducer Block 1 (Slot 11) Index 115 (pressure units)
Pressure units
Block: Transducer Block 1 (Slot 11) Index 113 (pressure value)
Optional: Fixed
pressure value
View > Preferences
Select Enable External
Pressure Compensation
Apply
ProLink > Configuration
Enter values:
Flow factor in Flow factor box Density factor in Dens factor box Flow calibration pressure in Cal pressure box
Apply
Pressure tab
Set pressure units to
match source
Optional: Enter a fixed
pressure value in the
External Pressure box
EDD Bus parameters
ProLink II

2.7.2 Enabling pressure compensation

To enable pressure compensation, see the menu flowcharts in Figure 2-5. You will need the three pressure compensation values from Section 2.7.1.
Figure 2-5 Enabling pressure compensation
14 Model 2700 Transmitter with PROFIBUS-PA
Startup
Function Block
Analog Output 1
Set IN Channel to
Pressure
Parameters > General
Analog Output 2
MMI Coriolis Flow
Transducer Block
Compensation
AO Compensation
Note: When setting the IN channel to Pressure via the EDD, the OUT channel will be automatically set to Pressure as well. Setting the IN channel via bus parameters does not automatically change the OUT channel. You must manually set the OUT channel to Pressure or the block will go into Out of Service mode.

2.7.3 Configuring a pressure source

You will need to choose one of two sources for pressure data:
Analog Output function block – This option allows you to poll for pressure data from an external pressure source.
Fixed pressure data – This option uses a known, constant pressure value.
Note: If you configure a fixed pressure value, ensure that it is accurate. If you configure polling for pressure, ensure that the external pressure measurement device is accurate and reliable.
If you configure pressure compensation to use an AO block for pressure compensation, the other AO block remains available for temperature compensation. However, only one of the AO blocks can be set up for external pressure.
To configure fixed pressure data, refer to the menu flowcharts in Figure 2-5.
To configure an AO function block for pressure compensation:
With the EDD, refer to the flowchart in Figure 2-6.
With bus parameters, refer to the flowchart in Figure 2-7.
With the display, refer to the menu flowcharts in Figure B-15.
Startup ConfigurationCalibrationBefore You Begin
Figure 2-6 Configuring an AO function block for pressure compensation – EDD
Configuration and Use Manual 15
Startup
Block: Analog Output Block (Slots 9 and 10) Index 37 (IN channel), value = 0x0b72 Index 38 (OUT channel), value = 0x0b72
Configure channel
Block: Transducer Block 1 (Slots 11) Index 121 (AO Compensation), value = 1
Configure channel
MMI Coriolis Flow > Transducer Block > Compensation > Temperature
Enable Disable Ext
Temp
EDD
Block: Transducer Block 1 (Slot 11) Index 110 (enable temperature compensation)
Enable temperature
comp.
Bus parameters
View > Preferences
Select Use External
Temperature
Apply
ProLink II
Figure 2-7 Configuring an AO function block for pressure compensation – Bus parameters

2.8 Configuring temperature compensation

External temperature compensation can be used with the petroleum measurement application or the enhanced density application:
If external temperature compensation is enabled, an external temperature value (or a fixed temperature value), rather than the temperature value from the Coriolis sensor, is used in petroleum measurement or enhanced density calculations only. The temperature value from the Coriolis sensor is used for all other calculations.
If external temperature compensation is disabled, the temperature value from the Coriolis sensor is used in all calculations.
Configuring temperature compensation requires two steps:
1. Enabling external temperature compensation (Section 2.8.1)
2. Configuring a temperature source (Section 2.8.2)

2.8.1 Enabling external temperature compensation

To enable temperature compensation, refer to the flowcharts in Figure 2-8.
Figure 2-8 Enabling external temperature compensation
16 Model 2700 Transmitter with PROFIBUS-PA
Startup
Function Block
Analog Output 1
Set IN Channel to
Temperature
Parameters > General
Analog Output 2
MMI Coriolis Flow
Transducer Block
Compensation
AO Compensation
Note: When setting the IN channel to Temperature via the EDD, the OUT channel will be automatically set to Temperature as well. Setting the IN channel via bus parameters does not automatically change the OUT channel. You must manually set the OUT channel to Temperature or the block will go into Out of Service mode.
Block: Analog Output Block (Slots 9 and 10) Index 37 (IN channel), value = 0x0b1D Index 38 (OUT channel), value = 0x0b6F
Configure channel
Block: Transducer Block 1 (Slots 11) Index 121 (AO Compensation), value = 1
Configure channel

2.8.2 Configuring a temperature source

External temperature data is reported through an analog output (AO) function block. The transmitter has two AO blocks, each of which can be assigned to a compensation variable channel.
To configure an AO function block for temperature compensation:
With the EDD, refer to the flowchart in Figure 2-9.
With bus parameters, refer to the flowchart in Figure 2-10.
With the display, refer to the flowcharts in Figure B-15.
Figure 2-9 Configuring an AO function block for temperature compensation – EDD
Startup ConfigurationCalibrationBefore You Begin
Configuration and Use Manual 17
Figure 2-10 Configuring an AO function block for temperature compensation – Bus parameters
18 Model 2700 Transmitter with PROFIBUS-PA
Chapter 3

Calibration

3.1 Overview

This chapter describes the following procedures:
Characterization (Section 3.3)
Smart Meter Verification (Section 3.4)
Meter validation and adjusting meter factors (Section 3.5)
Zero calibration (Section 3.6)
Density calibration (Section 3.7)
Temperature calibration (Section 3.8)
Note: All procedures provided in this chapter assume that you have established communication with the transmitter and that you are complying with all applicable safety requirements. See Appendix C or the documentation for your PROFIBUS host or configuration tool.
Startup ConfigurationCalibrationBefore You Begin

3.2 Characterization, Smart Meter Verification, meter validation, and calibration

There are four procedures:
Characterization – adjusts the transmitter to compensate for the unique traits of the sensor with which it is paired
Smart Meter Verification – establishing confidence in the sensor’s performance by analyzing secondary variables that are highly correlated with flow and density calibration factors
Meter validation – confirming performance by comparing the sensor’s measurements to a primary standard
Calibration – establishing the relationship between a process variable (flow, density, or temperature) and the signal produced by the sensor, or establishing the transmitter’s response to a zero-flow condition.
Meter validation, characterization, and calibration are available on all Model 2700 transmitters. Smart Meter Verification is available only if the Smart Meter Verification option was ordered with the transmitter.
These four procedures are discussed and compared in Sections 3.2.1 through 3.2.4. Before performing any of these procedures, review these sections to ensure that you will be performing the appropriate procedure for your purposes.
Configuration and Use Manual 19
Calibration

3.2.1 Characterization

Characterizing the flowmeter adjusts the transmitter to compensate for the unique traits of the sensor it is paired with. Characterization parameters (sometimes called “calibration factors”) describe the sensor’s sensitivity to flow, density, and temperature.
If the transmitter and the sensor were ordered together as a Coriolis flowmeter, then the flowmeter has already been characterized. Under some circumstances (typically when pairing a sensor and transmitter together for the first time), you may need to re-enter characterization data. If you are unsure about whether you should characterize your flowmeter, contact Micro Motion Customer Service.

3.2.2 Smart Meter Verification

Smart Meter Verification evaluates the structural integrity of the sensor tubes by comparing current tube stiffness to the stiffness measured at the factory. Stiffness is defined as the load per unit deflection, or force divided by displacement. Because a change in structural integrity changes the sensor’s response to mass and density, this value can be used as an indicator of measurement performance. Changes in tube stiffness are typically caused by erosion, corrosion, or tube damage.
Smart Meter Verification does not affect measurement in any way. Micro Motion recommends performing Smart Meter Verification at regular intervals.

3.2.3 Meter validation and meter factors

Meter validation compares a measurement value reported by the transmitter with an external measurement standard. Meter validation requires one data point.
Note: For meter validation to be useful, the external measurement standard must be more accurate than the sensor. See the sensor’s product data sheet for its accuracy specification.
If the transmitter’s mass flow, volume flow, or density measurement is significantly different from the external measurement standard, you may want to adjust the corresponding meter factor. A meter factor is the value by which the transmitter multiplies the process variable value. The default meter factors are
1.0, resulting in no difference between the data retrieved from the sensor and the data
reported externally.
Meter factors are typically used for proving the flowmeter against a Weights & Measures standard. You may need to calculate and adjust meter factors periodically to comply with regulations.

3.2.4 Calibration

The flowmeter measures process variables based on fixed points of reference. Calibration adjusts those points of reference. Three types of calibration can be performed:
•Zero
Density calibration
Temperature calibration
Density and temperature calibration require two data points (low and high) and an external measurement for each. The density and temperature calibration procedure changes the offset and/or the slope of the line that represents the relationship between process density and the reported density value, or the relationship between process temperature and the reported temperature value.
Note: For density or temperature calibration to be useful, the external measurements must be accurate.
20 Model 2700 Transmitter with PROFIBUS-PA
Calibration
Zero calibration requires only that flow through the sensor is stopped.
Flowmeters are calibrated at the factory, and normally do not need to be calibrated in the field. Calibrate the flowmeter only if you must do so to meet regulatory requirements. Contact Micro Motion before calibrating your flowmeter.
Note: Micro Motion recommends using meter validation and meter factors, rather than calibration, to prove the meter against a regulatory standard or to correct measurement error.

3.2.5 Comparison and recommendations

When choosing among Smart Meter Verification, meter validation, and calibration, consider the following factors:
Process and measurement interruption
- Smart Meter Verification provides an option that allows process measurement to continue
during the test.
- Meter validation for density does not interrupt the process. However, meter validation for
mass flow or volume flow requires process down-time for the length of the test.
- Calibration requires process down-time. In addition, density and temperature calibration
require replacing the process fluid with low-density and high density fluids, or low-temperature and high-temperature fluids. Zero calibration requires stopping flow through the sensor.
Startup ConfigurationCalibrationBefore You Begin
External measurement requirements
- Smart Meter Verification does not require external measurements.
- Zero calibration does not require external measurements.
- Density calibration, temperature calibration, and meter validation require external
measurements. For good results, the external measurement must be highly accurate.
Measurement adjustment
- Smart Meter Verification is an indicator of sensor condition, but does not change
flowmeter internal measurement in any way.
- Meter validation does not change flowmeter internal measurement in any way. If you
decide to adjust a meter factor as a result of a meter validation procedure, only the reported measurement is changed—the base measurement is not changed. You can always reverse the change by returning the meter factor to its previous value.
- Calibration changes the transmitter’s interpretation of process data, and accordingly
changes the base measurement. If you perform a zero calibration, you can return to the factory zero (or, if using ProLink II, the previous zero). However, if you perform a density calibration or a temperature calibration, you cannot return to the previous calibration factors unless you have manually recorded them.
Micro Motion recommends obtaining the Smart Meter Verification transmitter option and performing Smart Meter Verification on a regular basis.
Configuration and Use Manual 21
Calibration

3.3 Performing a characterization

Characterizing a flowmeter involves entering parameters that are printed on the sensor tag.

3.3.1 Characterization parameters

The characterization parameters that must be entered depend on the sensor type: “T-Series” or “Other,” as listed in Table 3-1. The “Other” category includes all Micro Motion sensors except T-Ser ies .
The characterization parameters are provided on the sensor tag. The format of the sensor tag varies depending on your sensor’s date of purchase. See Figures 3-1 and 3-2 for illustrations of newer and older sensor tags.
Table 3-1 Sensor characterization parameters
Bus parameter
Characterization data EDD label
(1)
K1
(1)
K2
(1)
FD
(1)
D1
(1)
D2
DT or TC
Flow cal
FCF
FT
(1)
(2)
(2)
(2)
FTG FTG 103
FFQ FFQ 104
DTG DTG 105
DFQ1 DFQ1 106
DFQ2 DFQ2 107
(1) See the section entitled “Density calibration factors.” (2) See the section entitled “Flow calibration values.”
K1 92 ✓✓
K2 93 ✓✓
FD 94 ✓✓
D1 97 ✓✓
D2 98 ✓✓
Density Temp Coeff (DT) 102 ✓✓
FD Value 99
FD Value 99
FD Value 99
index
Sensor type
T- Ser i e s O t her
22 Model 2700 Transmitter with PROFIBUS-PA
Loading...
+ 174 hidden pages