Shipping Temperature Range ................. -40 to +150°F (-40 to +65°C)
Dimensions Thermostat...................... 4-9/16"H x 5-13/16"W x 1-3/16"D
Humidity Setpoint Range..................... 5 to 50%
Dehumidification Setpoint Range .............. 40 to 95%
Thermostat
Applications
Gas, Oil, Electric, Heat Only,
Cool Only or Heat/Cool
Systems, 2 or 3 wire Hydronic
Zone (Hot Water or Steam)
Systems, 24 Volt or Millivolt
Single Stage Compressor
Heat Pump Systems - up to 2
Stages Aux./Emergency Heat
Two Stage or Two Compressor
Heat Pump systems - up to 2
Stages Aux./Emergency Heat
Maximum
Stages
Heat/Cool
1+1
2+2
3+1
4+2
1F95-1291 Humidity Control Touchscreen Thermostat
SPECIFICATIONS
CAUTION
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
This product does not contain mercury. However, this product may replace a product that contains mercury.
Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled
mercury. Wearing non-absorbent gloves, clean up any
spilled mercury and place in a sealed container. For proper
disposal of a product containing mercury or a sealed
container of spilled mercury, place it in a suitable shipping
container. Refer to www.thermostat-recycle.org for location to send the product containing mercury.
Troubleshooting15
PART NO. 37-7313B
www.white-rodgers.com
www.emersonclimate.com
Replaces 37-7313A
1241
!
INSTALLATION
WARNING
Thermostat installation and all components of the
control system shall conform to Class II circuits per
the NEC code.
Remove Old Thermostat
Before removing wires from old thermostat, mark wires for
terminal identification so the proper connections will be made
to the new thermostat.
Installing New Thermostat
1. Pull the thermostat body off the thermostat base. Forcing
or prying on the thermostat will cause damage to the unit.
2. Place base over hole in wall and mark mounting hole
locations on wall using base as a template.
3. Move base out of the way. Drill mounting holes. If you
are using existing mounting holes and the holes drilled
are too large and do not allow you to tighten base snugly,
use plastic screw anchors to secure the base.
4. Fasten base snugly to wall using mounting holes shown
in Figure 1 and two mounting screws. Leveling is for
appearance only and will not affect thermostat operation.
5. Connect wires to terminal block on base using appropriate
wiring schematic.
6. Push excess wire into wall and plug hole with a fire resistant material (such as fiberglass insulation) to prevent
drafts from affecting thermostat operation.
7. Carefully line the thermostat up with the base and snap
into place.
Battery Location
2 "AA" alkaline batteries are included in the thermostat at the
factory with a battery tag to prevent power drainage. Remove
the battery tag to engage the batteries.
To replace batteries, set system to OFF, remove thermostat
from wall and install the batteries in the rear along the top
of the thermostat (see Figure 1). For best results, use a
premium brand "AA" alkaline battery such as Duracell
Energizer
extended period (over 3 months) and
®
. If the home is going to be unoccupied for an
is displayed, the
batteries should be replaced before leaving.
Power Stealing Switches
The Power Stealing Switches (Fig. 1) should be left in the
"On" position for most systems. The information in the
following table details the thermostat power method and
switch options.
®
or
Thermostat Power MethodSwitch Position/Description
Battery Powered, no 24
Volt system power available.
Hardwired with Battery
Back-up, for 24 Volt systems
with common connection from
transformer to "C" terminal
on thermostat.
*Battery Powered with
Power Stealing Assist,
for 24 Volt systems with no
common connection from
transformer to "C" terminal on
thermostat.
Switches "On", thermostat
runs on batteries.
Switches "On", thermostat
runs on power directly from
transformer with battery backup.
Switches "On", thermostat
runs on batteries and
supplemental power drawn
through the heat or cool circuit.
*Power Stealing Assist is very reliable to increase battery life,
but on a small number of heating or cooling systems with high
impedance electronic modules you may observe one of the
following conditions:
1. The furnace draft inducer motor may run with no call for
heat.
2. The furnace fan may turn on with no call for heat or may
not turn off.
3. The furnace may not turn off when the call for heat ends.
4. The air conditioner may not turn off when the call for cool
ends.
If the Power Stealing Assist method is not compatible with
your system, place the Power Stealing Switches to "Off". This
cancels Power Stealing Assist, operates the thermostat on
batteries and corrects the condition.
Figure 1 – Thermostat Base Multi-Stage 1F95-1291
Mounting
Hole
Place Level
across Mounting Tabs
(for appearance only)
O/B
L
Y2
Y
+
S
-
HM
W2
W/E
6
DHM
Mounting
Hole
Place Level
across Mounting Tabs
(for appearance only)
Rear view of thermostat
2 "AA" Batteries
Stack
Power
Stealing
Switch
Power
Stealing
Switches
2
WIRING DIAGRAMS
TRANSFORMER
Figure 2 – Single Stage or Multi-Stage System
(No Heat Pump) with Single Transformer
System
Single Stage 1
(SS1)
Multi Stage 2
(MS2)
RCRHCY Y2W/EW2GO/B6L
24 volt
power for
cooling
24 volt
power for
heating
24 volt
common
(optional
for system
operation,
required
for remote
sensor)
Call for cool
Cool mode-1st
stage
No Output
Cool mode-2nd
stage
Call for heat
Heat mode-1st
stage
Single Stage and Multi-Stage Connections
Refer to equipment manufacturers’ instructions for specific system
wiring information.
This thermostat is designed to operate a single-transformer or twotransformer system.
You can configure the thermostat for use with the following fossil fuel
systems:
Figure 3 – Heat Pump Systems
System
RCRHCY Y2*W/E*W2GO/B6L
Heat mode-2nd
stage, Emergency
stage,
stage,
Mode-1st stage
*Note: Dual Fuel
energizes Heat
mode stage 1
(compressor)
when auxiliary
heat is energized
Heat mode-3rd
stage, Emergency
Mode-1st stage
*Note: Dual Fuel
energizes Heat
mode stages 1
compressors)
when auxiliary
heat is energized
Heat
Pump 1
(HP1)
Heat
Pump 2
(HP2)
24 volt
power for
cooling
24 volt
power for
heating
24 volt
common
(optional
for system
operation,
required
for remote
sensor)
Heat mode-1st
stage,
Cool mode-1st
stage,
(Compressor)
No Output
Heat mode-2nd
Cool mode-2nd
(Compressor)
No output
Heat mode-2nd
stage
Blower/Circulator fan
energized on a call
for cool or Fan On
(also energized in
heating if configured
for Electric Heat)
Installer
Configuration
Menu selects
“O” or “B” for
changeover
function. Set
to “O” terminal
energized in Cool
& Off mode. Set
to “B” terminal
energized in
Heat & mergency
mode
Power closed
connection for
SPDT 3-wire
zone valve
Fault or System
Malfunction
Indicator for
Heat Pumps
with “L” terminal
connection.
Original production
1F95-1291’s
do not have this
connection
NEUTRAL
24VAC
HOT
SINGLE STAGE (SS 1) gas, oil or electric.
MULTI-STAGE (MS 2) gas, oil or electric.
After wiring, see INSTALLER CONFIGURATION section for proper
thermostat configuration.
Heat mode-3rd
stage, Emergency
Mode-2nd stage
option de-
option de-
and 2 (both
*Note: Dual Fuel
option de-
energizes Heat
mode stage 1
(compressor)
when auxiliary
heat is energized
Heat mode-4th
stage, Emergency
Mode-2nd stage
*Note: Dual Fuel
option deenergizes Heat
mode stages 1
and 2 (both
compressors)
when auxiliary
heat is energized
Blower/Circulator fan
energized on a call
for cool or Fan On
(also energized in
heating if configured
for Electric Heat)
Installer
Configuration
Menu selects
“O” or “B” for
changeover
function. Set
to “O” terminal
energized in Cool
& Off mode. Set
to “B” terminal
energized in
Heat & mergency
mode
Power closed
connection for
SPDT 3-wire
zone valve
Fault or System
Malfunction
Indicator for
Heat Pumps
with “L” ter minal
connection.
Original production
1F95-1291’s
do not have this
connection
120VAC
CLASS II
120VAC
HEATING
120VAC
CLASS II
TRANSFORMER
24VAC
HOT
*Dual fuel option, if selected turns off compressor(s) when Auxiliary stages energize.
Heat Pump Connections
If you do not have a heat pump system, refer to figures 3 & 4.
Refer to equipment manufacturers’ instructions for specific system
wiring information.
You can configure the thermostat for use with the following heat pump
systems.
NEUTRAL
NEUTRAL
24VAC
HOT
TRANSFORMER
120VAC
COOLING
CLASS II
HEAT PUMP TYPE 1 (HP 1). Single stage compressor system;
gas or electric backup.
HEAT PUMP TYPE 2 (HP 2).Multi-stage compressor or two
compressor system with gas or electric backup.
After wiring, see INSTALLER CONFIGURATION section for proper
thermostat configuration.
3
WIRING DIAGRAMS
TRANSFORMER
Figure 4 – Humidity and Sensors
HM
Humidification Terminal,
Energizes on call for
heat if Humidity setpoint
is above room humidity.
Can also be used to
provide humidification
independent of a call for
heat and/or in cooling
mode if Automatic
Humidification is
selected in Configura-
tion Menu item #34
DHM
De-energizes on call for
Dehumidification to
lower the fan speed.
The DHM terminal is
only used on systems
with a compatible
dehumidification feature
that have the required
terminal connection on
the contol module or
have a relay installed to
lower the fan speed
+
Supply voltage
to remote
temperature
sensor
S
Remote
temperature
sensor signal
-
Supply voltage
to remote
temperature
sensor
Dehumidification wiring without an electronically controlled variable speed blower system for
single stage compressor system only.
If you have a single stage compressor system see the diagram below. A relay (customer provided) should be installed
as shown in Fig 7 to switch the fan speed to the next lower
speed on a call for dehumidification from the thermostat. The
reduction in air flow allows the coil to remove more humidity
from the air. The relay should be rated for blower motor load.
Since this configuration reduces the air flow in cooling, the
Figure 5 – Typical Wiring for Dehumidifier System
Normal High
DHM
No
Relay
90-293Q
or equivalent
N
“Cool Fan Output”
1
Normal Cool speed position (DHM energized)
2
Dehum speed mode (DHM de-energized)
NC
1
2
Dehum
Speed Fan
anti-freeze-up control (White-Rodgers CAFC) or equivalent is
recommended. The CAFC prevents the air conditioning coil
from freezing due to low air flow, dirty filters, low refrigerant
pressure, etc. The CAFC snaps onto the suction line close to
the evaporator coil as possible and breaks the compressor
circuit when the suction line drops below 38 °F and re-make
the circuit at 46°F.
Med
Low
“Heat Fan Output”
N
HM
Humidifier
System
4
Figure 6 – Typical Wiring for 120V Humidifier System
HM
Relay
90-290Q
or equivalent
Humidifier
System
HOT
NEUTRAL
120 VAC
Figure 7 – Typical Wiring for 24V Humidifier System
R
24 VAC
NEUTRAL
HOT
24 VAC
120 VAC
R
NEUTRAL
TRANSFORMER
HOT
120 VAC
3
4
7
15
6
5
123456789
101112131
415161718
1
92021222324252627282930313233343536373839
3
20
21
2
1
1112
10
1617
9
8
18
14
13
4
19
19
20
THERMOSTAT QUICK REFERENCE
Time of Day
Day of Week
Room
Temperature
System
Switch
Fan
Switch
Indicates when
thermostat is calling
for Heat or Cool
Battery Level Indicator
Indicating the current power level
of the 2 “AA” batteries.
Full power remaining.
Half power remaining.
Change The batteries should be replaced at this time.
Menu key for entering
different modes such as
Cleaning, Configuration, Set
Time and Set Schedule
Press to view
Humidity setpoint
Temperature
UP/Down used for
modifying setpoint
as well as to
navigating the menus
Set Temperature/Humidity
Note: If is displayed, the
thermostat is battery powered.
When battery power remaining
is approximately half, will
be displayed. If the home is
going to be unoccupied for an
extended period (over 3 months)
and is displayed, the batteries
should be replaced before leaving.
Home Screen Description
Figure 8 – Home Screen Display
Programming and Configuration Items
Displays
1
lockout mode.
Displays
Lockout" when limited range is activated and locked.
Displays only "Temperature Limit" when limited range
is activated.
2
Indicates period of day being programmed.
RUN SCHEDULE (run program) key.
SET TIME key or HOLD temperature key.
Displays "Change Filter"/"Change Pad"/"Change UV
5
Lamp" when the system has run for the programmed
filter/humidity pad/UV lamp time period as a reminder
to change or clean your filter/humidity pad or to replace
UV lamp.
6
COPY key or INSTALLER CONFIG key.
CLEAN DISPLAY key allows 30 seconds to wipe off
7
the display or ADVANCE DAY key for programming.
Used in programming to set time and in configuration
8
menu to change selections.
"Hold Until" indicates the time when a temporary hold
9
10
11
12
13
14
period will end.
"Hours" and "Days" displays during steps in installer
configuration.
The words "Hold At" are displayed when the
thermostat is in the HOLD mode. "Temporary Hold
At" is displayed when the thermostat is in a temporary
HOLD mode.
"Humidity" indicates that the "Set At" display is Hu-
midity setpoint.
"System On" indicates when heating or cooling stage
is energized. "+2" indicates when a second stage is
energized.
"Copy" indicates the copy program feature is being
used during programming.
and "Keypad Lockout" when in keypad
and "Temperature Limit" and "Keypad
Figure 9 – Programming & Configuration Items
A steady "Cool Savings" display indicates the feature
15
is enabled in the installer menu. A flashing "Cool
Savings" display indicates the feature is active.
"Remote" indicates that the indoor remote temperature
16
sensor, is being accessed. "Outdoor Remote" indicates the outdoor remote temperature sensor is being
accessed.
17
Display time, remote temperature or humidity.
"Heat Pump" displays when the system configuration
18
is set in HP1/HP2.
"Call for Service" indicates a fault in the heating/cooling
systems. It does not indicate a fault in the thermostat.
Auto Schedule key for Auto Schedule function or
Humidity key to display current Humidity and Humidity
setpoint.
21
In Configuration Menu, shows screen number. If blank,
thermostat is earlier model and requires instruction sheet
37-6914E.
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.