Emerson Process Management 1153 D User Manual

Reference Manual
00809-0100-4388, Rev BA January 2008
Rosemount 1153 Series D
Alphaline® Nuclear Pressure Transmitter
www.rosemountnuclear.com
IMPOR TANT NOTICE -- ERRATA
Model 1153 Series D Product Manual 00809-0100-4388 Rev BA (January 2008)
Affected
No.
Pages
1 6-8
Process Flange –CF3M (Cast version of 316L SST)
Description of Change
Drain/Vent Valves –316L SST Process Connections – 3/8-inch Swagelok compression fitting, 316L SST (1/4-18
NPT optional)
2 3-8 Change the first paragraph on the page to read as follows:
”Damping electronics are available as an option. Transmitters with standard electronics can be retrofitted with the adjustable damping feature by changing out both the amplifier board and the calibration board. Please reference Table 6-2 (Rosemount 1153 Series D Spare Parts List) for the applicable part numbers.”
Effect.
Date
10/21/09
4/13/12
3 6-11 Table 6-2,”Rosemount 1153 Series D Spare Parts List”, in all locations the
following part numbers are updated: Amplifier Circuit Board, Output Code R:
”01154-0001-0005” is replaced by ”01154-0153-0001” Amplifier Circuit Board with Damping, Output Code R:
”01154-0021-0004” is replaced by ”01154-0156-0001” Amplifier Circuit Board, Output Code R, N0026:
”01154-0001-0006” is replace by ”01154-0153-0002”
(5)
Sensor Module, 316 SST 0-5/30 inH
O: ”01153-0320-0232” is replaced by ”01153-5320-0232”
2
:
”01153-0320-0132” is replaced by ”01153-5320-0132” 0-25/150 inH
O: ”01153-0320-0242” is replaced by ”01153-5320-0242”
2
”01153-0320-0342” is replaced by ”01153-5320-0342” ”01153-0320-0142” is replaced by ”01153-5320-0142”
0-125/750 inH
O: ”01153-0320-0252” is replaced by ”01153-5320-0252”
2
”01153-0320-0352” is replaced by ”01153-5320-0352” ”01153-0320-0152” is replaced by ”01153-5320-0152” ”01153-0320-0052” is replaced by ”01153-5320-0052”
0-17/100 psi: ”01153-0320-0262” is replaced by ”01153-5320-0262” ”01153-0320-0362” is replaced by ”01153-5320-0362” ”01153-0320-0162” is replaced by ”01153-5320-0162” ”01153-0320-0062” is replaced by ”01153-5320-0062”
0-50/300 psi: ”01153-0320-0272” is replaced by ”01153-5320-0272” ”01153-0320-0372” is replaced by ”01153-5320-0372” ”01153-0320-0172” is replaced by ”01153-5320-0172” ”01153-0320-0072” is replaced by ”01153-5320-0072”
0-170/1,000 psi: ”01153-0320-0282” is replaced by ”01153-5320-0282” ”01153-0320-0182” is replaced by ”01153-5320-0182” ”01153-0320-0082” is replaced by ”01153-5320-0082”
0-500/3,000 psi: ”01153-0320-0192” is replaced by ”01153-5320-0192” 0-1,000/4,000 psi: ”01153-0320-0102” is replaced by ”01153-5320-0102”
4 6-12 Table 6-2,”Rosemount 1153 Series D Spare Parts List”, the table footnotes are
updated to add note (5) which will read as follows:
4/13/12
4/13/12
(5) IMPORTANT NOTICE: To maintain a transmitter’s qualified configuration,
when purchasing or installing a new Sensor Module, Rosemount Qualification report D2011019 must be carefully reviewed to verify that the Sensor Module to be installed and the associated Amplifier Circuit Board in a given transmitter is a qualified configuration. As detailed in the referenced
report, not all Sensor Module part numbers are considered qualified in conjunction with certain Amplifier Circuit Boards.
Reference Manual
Alphaline, Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. -Cell is a trademark of Rosemount Inc. D.C. 55 is a registered trademarks of Dow Corning. Loctite is a registered trademark of Henkel KGaA Corporation. Grafoil is a trademark of Union Carbide Corp. Swagelok is a registered trademark of Swagelok Co. Lubri-Bond is a registered trademark of E/M Corporation.
Cover Photo: 1153-001AB
Rosemount Nuclear Instruments, Inc. satisfies all obligations coming from legislation to harmonize product requirements in the European Union.
00809-0100-4388, Rev BA January 2008
Rosemount 1153 Series D
Rosemount 1153 Series D Alphaline
®
Pressure
Transmitters
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
For equipment service needs outside the United States, contact the nearest Rosemount representative.
Within the United States, the North American Response Center is at your service 24 hours a day, and is a single-point contact for all Rosemount equipment service needs. If at any time you are not sure what to do, you have a question about using the product, or you have a service or support request, call the center toll free at 1-800-654-RSMT (7768). This contact is your fastest link to quick and complete answers about any Rosemount group, product, or service.
www.rosemountnuclear.com
Reference Manual
00809-0100-4388, Rev BA
Rosemount 1153 Series D
January 2008
Rosemount Nuclear Instruments, Inc. Warranty and Limitations of Remedy
The warranty and limitations of remedy applicable to this Rosemount equipment are as stated on the reverse of the current Rosemount quotation and customer acknowledgment forms.
RETURN OF MATERIAL
Authorization for return is required from Rosemount Nuclear Instruments, Inc. prior to shipment. Contact Rosemount Nuclear Instruments, Inc. (1-952-949-5210) for details on obtaining Return Material Authorization (RMA). Rosemount Nuclear Instruments will not accept any returned material without a Returned Material Authorization. Material returned without authorization is subject to return to customer.
Material returned for repair, whether in or out of warranty, should be shipped prepaid to:
Rosemount Nuclear Instruments, Inc. 8200 Market Blvd. Chanhassen, MN 55317 USA
IMPORTANT
The Rosemount 1153 Series D Pressure Transmitter is designed for Nuclear Class IE usage, has been tested per IEEE Std 323-1974 and 344-1975 as defined in the Qualifications Test Report D8300040, and is manufactured to the requirements of NQA-1; 10CFR50, Appendix B quality assurance programs; and 10CFR Part 21. During qualification testing, interfaces were defined between the transmitter and its environment that are essential to meeting IEEE Std 323-1974 requirements. To ensure compliance with 10CFR Part 21, the transmitter must comply with the requirements herein throughout its installation, operation, and maintenance. It is incumbent upon the user to ensure that the Rosemount Nuclear Instruments, Inc. component traceability program is continued throughout the qualified life of the transmitter.
In order to maintain the qualified life status of the transmitter, the essential environmental interfaces must not be compromised. Performance of any operations on the transmitter other than those specifically authorized in this manual has the potential for compromising an essential environmental interface.
Where the manual uses the terms requirements, mandatory, must, or required, the instructions so referenced must be carefully followed. Rosemount Nuclear Instruments, Inc. expressly disclaims all responsibility and liability for transmitters for which the foregoing has not been complied with by the user.
ii
Reference Manual
00809-0100-4388, Rev BA January 2008
Rosemount 1153 Series D
Revision Status
Changes From 1999 to January 2008
Page (Old) Page (New) Changes
Cover Cover Document revision date change from May 1999 to January 2008, rev from AA to BA
Inside cover, i, ii, 5-9 & back cover
3-7, 6-9 & 6-10 3-8, 6-11 & 6-12 Include errata sheet information on circuit board number changes:
Throughout Throughout References to Fisher-Rosemount were changed to Emerson Process Management
i, back cover Cover, i, ii & back
- Cover, i, back page Added reference to European Union product requirement (CE)
2-1,3-1,4-1,5-1,6-1 2-1,3-1,4-1,5-1,6-1 Added table of contents to each section
2-2 2-2 Updated reference to Swagelok catalog and added web address, removed street
2-2 2-2 Removed word “process” from sentence indicating user assumes responsibility for
2-4 2-4 Rearranged wording on shielded cable, removed reference to 353C
2-6 & 2-7 2-7 & 2-8 Added word ‘nominal’ to Notes in drawings. Changed significant digits to conform to
5-6 & 6-10 5-6 & 6-12 Inserted information on the spare parts kit for bolts and nuts for process flange
6-2 6-2 Changed ISO 9001 to ISO 9001:2000
6-10 6-12 Replaced pipe mount bracket kit (adapters) P/N 01154-0038-0001 with P/N
- Back cover Added trademark & registration information
ii & back cover Include errata sheet information on address and phone numbers
• Replaced amplifier circuit card, output code R P/N 01154-0001-0001 with 01154-0001-0005.
• Replaced amplifier circuit card with damping, output code R P/N 01154-0021-0002 with 01154-0021-0004.
• Replaced amplifier circuit card, output code R, N0026 P/N 01154-0001-0002 with 01154-0001-0006.
Web address changed from www.rosemount.com to www.rosemountnuclear.com
cover
address
qualifying the connection interface
standards
01154-0044-0001
NOTE
The above Revision Status list summarizes the changes made. Please refer to both manuals for complete comparison details.
www.rosemountnuclear.com
Rosemount 1153 Series D
Reference Manual
00809-0100-4388, Rev BA
January 2008
iv
Reference Manual
00809-0100-4388, Rev BA January 2008
Rosemount 1153 Series D
Table of Contents
SECTION 1 Introduction
SECTION 2 Installation
SECTION 3 Calibration
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
About The Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Process Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Span Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Zero Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Calibration Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Zero and Span Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Linearity Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Damping Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Correction For High Line Pressure
(Rosemount 1153DD and 1153HD Only) . . . . . . . . . . . . . . . . . . . . 3-9
Span . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Zero . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
SECTION 4 Operation
www.rosemountnuclear.com
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Transmitter Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
The d-Cell Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Demodulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Linearity Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Oscillator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Voltage Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Zero And Span Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Current Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Current Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Reverse Polarity Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Rosemount 1153 Series D
Reference Manual
00809-0100-4388, Rev BA
January 2008
SECTION 5 Maintenance and Troubleshooting
SECTION 6 Specifications and Reference Data
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Test Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Board Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Sensing Module Checkout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Disassembly Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Process Flange Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Electrical Housing Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Removing Sensor Module from Electrical Housing . . . . . . . . . . . . 5-4
Reassembly Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Preliminary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Connecting Electrical Housing to Sensor Module . . . . . . . . . . . . . 5-5
Electrical Housing Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Process Flange Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Post-assembly Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Nuclear Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Output Code P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Output Code R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Both Output Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Spare Parts Shelf Life. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
Important Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13
TOC-2
Reference Manual
00809-0100-4388, Rev BA January 2008
Rosemount 1153 Series D
Section 1 Introduction
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
About The Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
OVERVIEW This manual is designed to assist in installing, operating, and maintaining the
Rosemount 1153 Series D Pressure Transmitter. The manual is organized into the following six sections:
Section 1: Introduction
Section 2: Installation
Provides general, mechanical, and electrical installation considerations to guide you through a safe and effective transmitter installation.
Section 3: Calibration
ABOUT THE TRANSMITTER
Provides transmitter calibration procedures.
Section 4: Operation
Provides descriptions of how the transmitter operates.
Section 5: Maintenance and Troubleshooting
Provides basic hardware troubleshooting considerations including sensing module checkout, disassembly and reassembly procedures, and post-assembly tests.
Section 6: Specifications and Reference Data
Provides nuclear, performance, functional, and physical transmitter specifications; also includes ordering information, and a list of spare parts.
Rosemount 1153 Series D Alphaline Pressure Transmitters are designed for precision pressure measurements in nuclear applications requiring reliable performance and safety over a specified qualified life. These transmitters were generically tested to the IEEE Std 323-1974 and IEEE Std 344-1975 per the Qualification Test Report D8300040. The Rosemount 1153 Series D has been qualification tested to environments typical of Pressurized Water Reactors (PWR) under accident conditions. Stringent quality control during the manufacturing process includes traceability of pressure retaining parts, special nuclear cleaning, and hydrostatic testing.
Rosemount 1153 Transmitters are of a design unique to Class 1E nuclear service while retaining the working concept and design parameters of the Rosemount 1151 Series that have become a standard of reliable service. Units are available in Absolute (A), Gage (G), Differential (D), and High-Line Differential (H) configurations, with a variety of pressure range options (See Table 6-1 on page 6-10). Figure 2-5 on page 2-7 shows transmitter dimensional drawings.
www.rosemountnuclear.com
Rosemount 1153 Series D
Reference Manual
00809-0100-4388, Rev BA
January 2008
1-2
Reference Manual
Electronics
Qualified Life
Ambient Temperature (°F)
Time (Years)
Module Qualified Life
00809-0100-4388, Rev BA January 2008
Rosemount 1153 Series D
Section 2 Installation
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . page 2-2
Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-6
OVERVIEW This section contains information and instructions regarding the following
installation-related information:
General Considerations
Mechanical Considerations Process Connections Conduit
Electrical Considerations
Installation Procedures Mechanical Electrical
GENERAL CONSIDERATIONS
Figure 2-1. Qualified Life vs. Ambient Temperature.
The quality and accuracy of flow, level, or pressure measurement depends largely on the proper installation of the transmitter and its associated impulse piping and valves. For flow measurement, proper installation of the primary measuring element is also critical to the accuracy of the measurement. Transmitter installation should minimize the effects of temperature gradients and temperature fluctuations, and avoid vibration and shock during normal operation. Take care when designing the measurement to minimize the error caused by incorrect installation. The ambient temperature of the transmitter environment affects the qualified life of the transmitter (see Figure 2-1 on page 2-1).
www.rosemountnuclear.com
Rosemount 1153 Series D
Reference Manual
00809-0100-4388, Rev BA
January 2008
MECHANICAL CONSIDERATIONS
This section contains information you should consider when preparing to mount the transmitter. Read this section carefully before proceeding to the mechanical installation procedure.
Mount the Rosemount 1153 Series D transmitter to a rigid support (a support with a fundamental mechanical resonant frequency of 40 Hz or greater). A mounting bracket included with the transmitter facilitates panel mounting. Figure 2-4 on page 2-6 shows qualified transmitter mounting configurations. The transmitter was seismic tested and qualified with the bracket mounted using four
3
/8-in. diameter bolts. Orientation with respect to gravity is not critical to qualification. However, if the transmitter is mounted with the flanges in a horizontal position, rezero the transmitter to cancel the liquid head effect caused by the difference in height of the process connections.
If you mount the transmitter to a non-rigid panel, ensure that seismic input to the mounting bracket does not exceed qualification levels given in Rosemount Report D8300040.
Process Connections Process tubing installation must prevent any added mechanical stress on the
transmitter under seismic disturbances. This may be done by using stress-relief loops in the process tubing or by separately supporting the process tubing close to the transmitter.
The process connections to the transmitter flanges were qualified with tubing using compression fittings (Swagelok
®
). For options using 1/4–18 NPT
connections, the user assumes responsibility for qualifying the interface.
Transmitters with Flange Options A, D, H, J, L, or M are shipped with Swagelok fittings for process connections. Included are front ferrule, rear ferrule, and nut. Ensure that they are placed on the tubing with the orientation and relative position shown in Detail A, Figure 2-5 on page 2-7.
Process tubing used is
3
/8-in. outside diameter, and of suitable thickness for
the pressure involved.
3
/8-in.
2-2
The Swagelok tube fittings come completely assembled and are ready for immediate use. Do not disassemble them before use; because they may become dirty or a foreign material get into the fitting and cause leaks. Insert the tubing into the Swagelok tube fitting, making sure that the tubing rests firmly on the shoulder of the fitting and that the nut is finger tight. Tighten the nut one-and-one-quarter turns and it is ready for use. Do not overtighten.
The connections can be loosened and retightened 20–30 times without compromising the leak-proof seal. To reconnect, insert the tubing with pre-swaged ferrules into the fitting until the front ferrule sits in the fitting. Tighten the nut by hand, then rotate one-quarter turn more or to the original one-and-one-quarter tight position. Then snug it slightly with a wrench. For more information regarding the use of Swagelok tube fittings, refer to:
Fittings Catalog MS-01-140 “Gaugeable Tube Fittings and Adapter Fittings” www.swagelok.com
If the drain/vent valves must be opened to bleed process lines, torque them to
1
7
/2 ft-lb (10 N-m) when closing.
Reference Manual
00809-0100-4388, Rev BA January 2008
Rosemount 1153 Series D
Proper location of the transmitter with respect to the process tubing depends on various process parameters. When determining the best location, consider the following:
Keep hot or corrosive fluids from contacting the transmitter.
Prevent sediment from depositing in the impulse tubing.
Ambient temperature gradients and fluctuations can result in erroneous transmitter readings.
Keep impulse tubing as short as possible.
For differential transmitters, balance the liquid head on both legs of the impulse tubing.
For liquid flow or pressure measurements, make taps on the side of the line to avoid sediment deposits, and mount the transmitter beside or below the taps so gases vent into the process line (see Figure 2-6 on page 2-8).
For gas flow or pressure measurements, make taps on the top or side of the line and mount the transmitter beside or above the taps so liquid drains into the process line (see Figure 2-6 on page 2-8).
For steam flow or pressure measurements, make taps on the side of the line, and mount the transmitter below the taps so the impulse tubing stays filled with condensate (See Figure 2-6 on page 2-8).
For steam service, fill the lines with water to prevent steam from contacting the transmitter. Condensate chambers are not necessary since the volumetric displacement of the transmitter is negligible.
The piping between the process and the transmitter must transfer the pressure measured at the process taps to the transmitter. Possible sources of error in this pressure transfer are:
•Leaks.
Friction loss (particularly if purging is used).
Trapped gas in a liquid line or trapped liquid in a gas line (head error).
Temperature-induced density variation between legs (head error), for differential transmitters.
To minimize the possibility of errors, take the following precautions:
Make impulse tubing as short as possible.
Slope tubing at least one inch per foot up toward the process connections for liquid and steam.
Slope tubing at least one inch per foot down toward the process connections for gas.
Avoid high points in liquid lines and low points in gas lines.
Use impulse tubing of sufficient diameter to avoid friction effects.
Ensure that all gas is vented from liquid tubing legs.
Ensure that impulse tubing is of adequate strength to be compatible with anticipated pressures.
2-3
Rosemount 1153 Series D
For differential transmitters, also consider the following:
Keep both impulse legs at the same temperature.
When using sealing fluid, fill both piping legs to the same level.
When purging, make the purge connection close to the process taps and purge through equal lengths of the same size tubing. Avoid purging through the transmitter.
Reference Manual
00809-0100-4388, Rev BA
January 2008
Conduit The conduit connection to the transmitter is
conduit seal at the conduit entry to prevent moisture from accumulating in the terminal side of the housing during accident conditions. To prevent the conduit from adding mechanical stress to the transmitter during seismic disturbances, use flexible conduit or support the conduit near the transmitter. Install the conduit seal in accordance with the manufacturer’s instructions or use the procedure on page 2-8.
ELECTRICAL CONSIDERATIONS
This section contains information that you should consider when preparing to make electrical connections to the transmitter. Read this section carefully before proceeding to the electrical installation procedures.
The Rosemount 1153 Series D pressure transmitter provides a 4–20 mA signal when connected to a suitable dc power source. Figure 2-2 on page 2-5 illustrates a typical signal loop consisting of transmitter, power supply, and various receivers (i.e., controller, indicator, computer). The power supply must supply at least 12 volts to the transmitter terminals at 30 mA (overscale) signal, or the maximum output current required for proper system operation. Any power supply ripple appears in the output load. The supply voltage versus load limitation relationship is shown in Figure 2-3 on page 2-5. See qualification report D8300040 for details. The load is the sum of the resistance of the signal leads and the load resistance of the receivers.
Signal wiring need not be shielded, but twisted pairs yield the best results. In electrically noisy environments, shielded cable should be used for best results. Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Signal wiring may be ungrounded (floating) or grounded at any place in the signal loop. The transmitter case may be grounded or ungrounded.
1
/2–14 NPT. Use a qualified
2-4
The capacitance-sensing element uses alternating current to generate a capacitance signal. This alternating current is developed in an oscillator circuit with a frequency of 32,000 ±10,000 Hz. This 32,000 Hz signal is capacitor coupled to transmitter case ground through the sensing element. Because of this coupling, a voltage may be imposed across the load, depending on choice of grounding.
This impressed voltage, which is seen as high-frequency noise, has no effect on most instruments. Computers with short sampling times in a circuit where the negative transmitter terminal is grounded will detect a significant noise signal. Filter this noise with a large capacitor (1 µf) or by using a 32,000 Hz LC filter across the load. Signal loops grounded at any other point are negligibly affected by this noise and do not need filtering.
Reference Manual
Power
Supply
Terminal Side (Cover Removed)
4—20 mA DC
Design Region
Qualified
Region
2000
1650
1325
1500
1000
500
0
0
12
13.5
30
40
45
Power Supply (V DC)
Load Resistance (Ω)
4—20 mA DC
Design Region
Qualified
Region
1825
1575
1500
1000
500
0
0
12
13.5
35
40
45
50
Power Supply (V DC)
Load Resistance (Ω)
00809-0100-4388, Rev BA January 2008
Figure 2-2. Transmitter Wiring Connections.
Rosemount 1153 Series D
Figure 2-3. Transmitter Load Limits.
Output Code P
Output Code R
2-5
Rosemount 1153 Series D
PANEL MOUNTING
HOLE PATTERN
(BACK SIDE)
Center of Gravity (Bracket Included)
2.81
(71.4)
5
(127)
1.2
(30)
2.3
(58)
2.75
(69.9)
10 (254) Minimum
Clearance
3
/8-in.
Bolts (4)
(Customer
Supplied)
ACCEPTABLE ALTERNATE MOUNTING
2.3
(58)
NOTE All dimensions are nominal in inches (millimeters).
Center of Gravity (Bracket Included)
1.8
(45.7)
MOUNTING BRACKET
FOR PANEL MOUNT SHOWN IN TYPICAL
MOUNTING CONFIGURATION
NOTES
1. Orientation with respect to gravity is not critical.
2. Units can alternately be mounted with process connection adjacent to bracket.
4.93
(125)
2.81
(71.4)
Reference Manual
00809-0100-4388, Rev BA
January 2008
INSTALLATION PROCEDURES
Mechanical
Transmitter
Installation consists of mounting the transmitter and conduit and making electrical connections. Following are procedures for each operation.
Be careful not to break the neck seal between the sensor module and the electronics housing.
The threaded interface between the sensor module and the electronics housing is hermetically sealed before shipment. The integrity of this seal is necessary for the safe operation of the transmitter during accident conditions. If the seal is broken, reseal it according to “Connecting Electrical Housing to Sensor Module” on page 5-5.
1. Mount the bracket to a panel or other flat surface (see Figure 2-4 on page 2-6). Use four
3
/8-in. diameter bolts (not supplied with unit). SAE grade 2 bolts were used during qualification testing. Torque each bolt to 19 ft-lb (26 N-m).
2. Attach the transmitter to the mounting bracket (see Figure 2-4 on page 2-6). Use four
7
/16–20 3/4 bolts with washers (supplied with
unit). Torque each bolt to 21 ft-lb (29 N-m).
Figure 2-4. Typical Transmitter Mounting Bracket Configuration.
2-6
Reference Manual
Low Side Vent (GD only)
7
/16–20 UNF (Typical)
9 Max. (228.6)
4.7 Max. (119.4)
4.72 Max. (119.9)
3.4
(86.4)
7
/16–14 UNC
(4 Places)
Nameplate
(Remove for
Zero and Span
Adjust)
Transmitter
Circuitry
(this Side)
Terminal
Connections
(this Side)
Dim
A
0.8 (20) to End of Mating Tubing
Compression Fittings (1) Swagelok for
3
/8-in. Tubing
(Optional
1
/4–18 NPT Available)
Welded Drain/Vent Valve (1) (Optional
1
/4–18 NPT
Available)
Low Side
Vent
(GD only)
DETAIL A
3
/8-in. Mating Tubing
0.8
(20)
Welded Drain/Vent Valve (2) (Optional
1
/4–18 NPT
Dim.
A
1.63
(41.3)
7
/16–20 UNF (Typical)
9 Max. (228.6)
3.7 (94)
4.7 Max. (119.4)
4.72 Max. (119.9)
3.4
(86.4)
7
/16–14 UNC
(4 Places)
Nameplate
(Remove for
Zero and Span
Adjust)
Transmitter
Circuitry
(this Side)
Terminal
Connections
(this Side)
0.8 (20) to End of Mating Tubing
Compression Fittings (2) Swagelok
®
for 3/8-in. Tubing
(Optional
1
/4–18 NPT Available)
Pressure
Range Code
Dimension
A
3, 4, 5 2.13 (54)
6, 7 2.19 (55.6)
8 2.25 (57.2) 9 2.28 (57.9) 0 2.33 (59.1)
ROSEMOUNT 1153DD AND 1153HD
ROSEMOUNT 1153AD AND 1153GD
3.7
(94)
1
/2–14 NPT Conduit Connection (1 place)
1
/2–14 NPT Conduit Connection (1 place)
0.75 (19) Clearance for Cover Removal (Typical)
0.75 (19) Clearance for Cover Remov al (Typical)
1.63
(41.3)
NOTE All dimensions are nominal in inches (millimeters).
00809-0100-4388, Rev BA January 2008
Figure 2-5. Transmitter Dimensional Drawings.
Rosemount 1153 Series D
2-7
Reference Manual
Blocking Valves
Flow
3-Valve Manifold
Plugged Tees for Steam
Service or Sealing Fluid
Drain/Vent Valves
Sufficient
Length
for Cooling
Rosemount 1153DD, HD
Plugged Tees for Steam Service or
Sealing Fluid
Blocking Valve
Drain/Vent Valve
Sufficient
Length
for Cooling
Rosemount 1153AD, GD
Rosemount 1153AD, GD
LIQUID SERVICE
Drain/Vent Valve s
Drain/Vent Valve
3-Valve Manifold
Flow
Rosemount 1153DD, HD
GAS SERVICE
H
H
L
L
00809-0100-4388, Rev BA
Rosemount 1153 Series D
January 2008
Conduit 1. Seal the conduit threads with thread sealant (the transmitter conduit
seal interface was qualified using Grafoil™ tape). Conduit threads mate with a standard
2. Starting at zero thread engagement, install the conduit into the transmitter between 4 and 7 turns, or a minimum of 12.5 ft-lb (16.9 N-m). Hold the electronics housing securely to avoid damaging the threaded neck seal between the sensor module and the electronics housing during conduit installation.
3. Provide separate support for the conduit if necessary.
Figure 2-6. Transmitter Installation Configurations
1
/2–14 NPT male fitting.
2-8
Reference Manual
Signal
Terminals
Test Terminals
00809-0100-4388, Rev BA January 2008
Rosemount 1153 Series D
Electrical 1. Remove the cover from the terminal side of the transmitter (see
Figure 2-5 on page 2-7).
2. Connect the power leads to the “SIGNAL” terminals on the transmitter terminal block (see Figure 2-7 on page 2-9). Torque the terminal screws to 5 in-lb (0.6 N-m), or hand-tight.
Do not connect signal leads to the “TEST” terminals.
3. Recheck the connections for proper polarity.
4. Check the cover O-ring grooves for cleanliness. If chips or dirt are present, clean the seat and mating portion of the cover with alcohol. Lubricate replacement O-ring with O-ring grease (RMT P/N 01153-0248-0001 or P/N 01153-0053-0001). The transmitter was qualified using Dow Corning
5. Spray the inside threads of the electronics covers with cover lubricant (Rosemount P/N 01153-0333-0001 or equivalent) if necessary; if covers are already sufficiently lubricated, do not spray.
6. Carefully replace the cover and tighten to 16.5 ft-lb (22.4 N-m).
®
55 Silicone O-ring Grease.
Figure 2-7. Transmitter Terminal Block.
2-9
Rosemount 1153 Series D
Reference Manual
00809-0100-4388, Rev BA
January 2008
2-10
Loading...
+ 44 hidden pages