Emerson Process Management 00809-0100-4952 User Manual

Reference Manual
00809-0100-4952, Rev BA
Rosemount Pipe Clamp Sensor
February 2014
Reference Manual
NOTICE
00809-0100-4952, Rev BA
Title Page
The Rosemount 0085 Pipe Clamp Sensor
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one International number. Customer Central
1-800-999-9307 (7:00 A.M. to 7:00 P.M. CST) International
1-(952) 906-8888 National Response Center
1-800-654-7768 (24 hours a day) Equipment service needs
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Representative.
This device is intended for use in temperature monitoring applications and should not be used in control and safety applications.
i
Reference Manual
00809-0100-4952, Rev BA
Table of contents
1Section 1: Introduction
1.1 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 Receiving and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.3 Returning the product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.4.1 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2Section 2: Installation
2.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Installation flowchart and checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.3.1 Tools and supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table of Contents
3Section 3: Operation and maintenance
3.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
AAppendix A: Reference data
A.1 Rosemount Pipe Clamp Sensor ordering information . . . . . . . . . . . . . . . . . . . . . . . 9
A.1.1 Design example drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
BAppendix B: Product Certifications
B.1 Approved manufacturing locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
B.2 European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
B.2.1 Ordinary Location Certification from FM Approvals . . . . . . . . . . . . . . . . . .13
B.2.2 Hazardous Locations Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
B.3 Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Tab le of C onten ts
iii
Reference Manual
00809-0100-4952, Rev BA

Section 1 Introduction

Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1
Receiving and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Returning the product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2

1.1 Using this manual

This product manual provides installation, configuration, troubleshooting, and maintenance instructions for the 0085 Pipe Clamp Sensor.
Section 1: Introduction
Section 2: Installation
Installation flowchart and checklist
Mounting and installation
Wiring to transmitter/connection head
Section 3: Operation and maintenance
Tro u bl esh o oti ng
Replaceable insert maintenance
Appendix A: Reference data
Specifications
Dimensional drawings
Appendix B: Product Certifications
Product Certifications
Installation Drawings
Introduction
1
Section 1: Introduction
February 2014

1.2 Receiving and inspection

The 0085 Pipe Clamp Sensor comes in several different types of materials and clamp sizes so it's important to inspect and verify that the appropriate model was delivered before installation.
Upon receipt of the shipment, check the packing list against the material received and the purchase order. Report any damage to the carrier.

1.3 Returning the product

To expedite the return process, call the Rosemount National Response Center toll-free at 800-654-7768. This center, available 24 hours a day, will assist you with any needed information or materials.
The center will ask for the following information:
Product model
Serial numbers
The last process material to which the product was exposed
Reference Manual
00809-0100-4952, Rev BA
The center will provide:
A Return Material Authorization (RMA) number
Instructions and procedures that are necessary to return goods that were exposed to
hazardous substances
Note
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS), required by law to be available to people exposed to specific hazardous substances, must be included with the returned materials.

1.4 Considerations

Information in this manual applies to circular pipes only. Consult Rosemount Customer Central for instruction regarding other uses.

1.4.1 Limitations

Functional
The most accurate and repeatable surface temperature measurement occurs with the following insulation best practices:
Use weather proof insulation with aluminum cladding
Install insulation extending at least 0.5 meters in each direction from sensor (at least 1
meter total)
Insulate the sensor extension
Install insulation with minimal gaps to isolate sensor as much as possible from ambient
conditions.
2
Introduction
Reference Manual
00809-0100-4952, Rev BA

Section 2 Installation

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Installation flowchart and checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5

2.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Please refer to the following safety messages before performing any operation in this section.
Section 2: Installation
Explosions could result in death or serious injury:
Do not remove the housing cover in explosive atmospheres when the circuit is live. Before connecting a Field Communicator in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify that the operating atmosphere of the sensor is consistent with the appropriate
hazardous locations certifications.
Housing cover must be fully engaged to meet explosion-proof requirements.
Failure to follow these installation guidelines could result in death or serious injury:
Make sure only qualified personnel perform the installation.
Installation
3
Section 2: Installation
Start.
Unpack Instrument
Review Product Manual.
Verify proper installation location.
Steps 1, 2
Bench
Configure?
YES
See Appropriate Transmitter Manual for
Bench Configuration information.
NO
Veri fy model
indicated on tag.
Remote
Mounted
Tra ns mit te r?
NO
Finish
Install hardware
Install Transmitter
Install Pipe Clamp Sensor
Wire Sensor
Remote
Mounted
Tra ns mi tt er ?
YES
Commission the transmitter. See Appropriate
Transmitter Manual for Bench Configuration
information.
YES
NO
Steps 5-7
Steps 4
Steps 5-7
Steps 8-10
February 2014

2.2 Installation flowchart and checklist

Figure 2-1 is an installation flowchart that provides guidance through the installation process.
Following the figure, an installation checklist has been provided to verify that all critical steps have been taken in the installation process. The checklist numbers are indicated in the flowchart.
Figure 2-1. Installation Chart
Reference Manual
00809-0100-4952, Rev BA
4
Installation
Reference Manual
00809-0100-4952, Rev BA
Section 2: Installation
The following list is a summary of the steps required to complete a Pipe Clamp Sensor installation.
1. Determine where the Pipe Clamp Sensor is to be placed within the piping system.
2. Establish the proper orientation as determined by the intended application.
3. Confirm the configuration.
4. Mount the sensor and tighten the clamp bolts.
5. Check the fit-up of the instrument assembly to the pipe.
6. Check for full contact between RTD sensor tip and pipe.
7. Wire the instrument.
8. Supply power to the transmitter.
9. Commission the instrument.

2.3 Mounting

2.3.1 Tools and supplies

Tools required include the following:
Open end or combination wrenches.
Adjustable wrench: 40mm (1½-in.) jaw.
Supplies required include the following:
Pipe compound or PTFE tape (where local piping codes allow).

2.4 Installation

Step 1: determine the proper orientation
The Pipe Clamp Sensor should be mounted in a secure position to ensure there is no rotational movement after installation. The mounting best practice is to install the sensor vertically.
Step 2: install the pipe clamp sensor
Mount the Pipe Clamp Sensor and tighten the bolts.
Installation
Step 3: install the transmitter
See appropriate transmitter product manual for sensor-transmitter installation.
Step 4: commission the transmitter
See appropriate transmitter product manual for transmitter commissioning instructions.
5
Section 2: Installation
Red
Red
White
White
Red Red
Green
Black
Blue Blue
February 2014
Figure 2-2. Sensor Lead Wire Termination
Single Element 4-Wire Dual Element 3-wire
Reference Manual
00809-0100-4952, Rev BA
Pipe Clamp RTD Flying Leads and Spring Loaded
6
Installation
Reference Manual
00809-0100-4952, Rev BA
Section 3: Operation and maintenance
February 2014

Section 3 Operation and maintenance

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8

3.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Please refer to the following safety messages before performing any operation in this section.
Explosions could result in death or serious injury:
Do not remove the housing cover in explosive atmospheres when the circuit is live. Housing cover must be fully engaged to meet explosion-proof requirements. Before connecting a communicator in an explosive atmosphere, make sure the
instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and the terminals.
Operation and Maintenance
7
Section 3: Operation and maintenance
February 2014

3.2 Troubleshooting

If a malfunction is suspected despite the absence of a diagnostic message on the communicator display, follow the procedures described below to verify that the Pipe Clamp Sensor, transmitter, and process connections are in good working order. Always approach the most likely and easi­est-to-check conditions first.
Symptom Possible source Corrective action
Loop Wiring
Tra nsmi tter Does N ot Communicate with Field Communicator
Sensor Input Failure or Connection
Loop Wiring
Power Supply
High Output
Electronics Module
Loop Wiring
Erratic Output
Electronics Module
Sensor Element
Loop Wiring
Low Output or No Output
Electronics Module
• Check the revision level of the transmitter device descriptors (DDs) stored in your communicator. The communicator should report Dev v4, DD v1 (improved), or reference “Field Communicator” for previous versions. Contact Emerson Process Management Customer Central for assistance.
• Check for a minimum of 250 ohms resistance between the power supply and Field Communicator connection.
• Check for adequate voltage to the transmitter. If a Field Communicator is connected and 250 ohms resistance is properly in the loop, then the transmitter requires a minimum of 12.0 V at the terminals to operate (over entire 3.5 to 23.0 mA operating range), and 12.5 V minimum to communicate digitally.
• Check for intermittent shorts, open circuits, and multiple grounds.
• Connect a Field Communicator and enter the transmitter test mode to isolate a sensor failure.
• Check for a sensor open circuit.
• Check if the process variable is out of range.
• Check for dirty or defective terminals, interconnecting pins, or receptacles.
• Check the output voltage of the power supply at the transmitter terminals. It should be 12.0 to 42.4 Vdc (over entire 3.5 to 23.0 mA operating range).
• Connect a Field Communicator and enter the transmitter test mode to isolate module failure.
• Connect a Field Communicator and check the sensor limits to ensure calibration adjustments are within the sensor range.
• Check for adequate voltage to the transmitter. It should be 12.0 to 42.4 Vdc at the transmitter terminals (over entire 3.5 to 23.0 mA operating range).
• Check for intermittent shorts, open circuits, and multiple grounds.
• Connect a Field Communicator and enter the loop test mode to generate signals of 4 mA, 20 mA, and user-selected values.
• Connect a Field Communicator and enter the transmitter test ode to isolate module failure.
• Connect a Field Communicator and enter the transmitter test mode to isolate module failure.
• Check if the process variable is out of range.
• Check for adequate voltage to the transmitter. It should be 12.0 to 42.4 Vdc at the transmitter terminals (over entire 3.5 to 23.0 mA operating range).
• Check for shorts and multiple grounds.
• Check for proper polarity at the signal terminal.
• Check the loop impedance.
• Connect a Field Communicator and enter the loop test mode.
• Check wire insulation to detect possible shorts to ground.
• Connect a Field Communicator and check the sensor limits to ensure calibration adjustments are within the sensor range.
• Connect a Field Communicator and enter the transmitter test mode to isolate an electronic module failure.
Reference Manual
00809-0100-4952, Rev BA
8
Operation and Maintenance
Reference Manual
00809-0100-4952, Rev AA
Appendix A: Reference Data

Appendix A Reference data

Rosemount Pipe Clamp Sensor ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
A.1 Rosemount Pipe Clamp Sensor ordering
information
Table A-1. Rosemount Pipe Clamp Sensor Ordering Table
The Standard offering represents the most common options. The starred options () should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Model Product description
Standard Standard
0085 Non Intrusive Pipe Clamp Sensor
Code Connection head IP Rating Conduit entry
Standard Standard
C Connection Head Rosemount, Aluminum 66/68 M20 x 1.5 D Connection Head Rosemount, Aluminum 66/68 G Connection Head Rosemount, Stainless Steel 66/68 M20 x 1.5 H Connection Head Rosemount, Stainless Steel 66/68 N No connection head 66/68 1 Connection Head Rosemount, Aluminum with LCD display cover 66/68 M20 x 1.5 2 Connection Head Rosemount, Aluminum with LCD display cover 66/68 3 Connection Head Rosemount, Stainless Steel with LCD display cover 66/68 M20 x 1.5 4 Connection Head Rosemount, Stainless Steel with LCD display cover 66/68
1
/2 in. NPT
1
/2 in. NPT
1
/2 in. NPT
1
/2 in. NPT
Code Sensor connection
Standard Standard
3 Spring Loaded Adapter 5 Spring Loaded Adapter with Terminal Block
Code Sensor type Temperature range
Standard Standard
P1 RTD, Single Element, 4-Wire, Silver tip -50 to 300 °C (-58 to 572 °F) P2 RTD, Dual Element, 3-Wire, Silver tip -50 to 300 °C (-58 to 572 °F) P3 RTD, Single Element, 4 Wire, Nickel tip -200 to 300 °C (-328 to 572 °F) P4 RTD, Dual Element, 3 Wire, Nickel tip -200 to 300 °C (-328 to 572 °F)
Instrument
Code Extension type Head connection
connection
Material
Standard Standard
J Nipple -Union None
1
/2 in. NPT Stainless steel
Code Extension length (N) in mm
Standard Standard
0080 80 mm 0150 150 mm
Expanded
XXXX Non Standard lengths 200 - 500 mm - Available in 50 mm increments
Reference Data
9
Appendix A: Reference Data
February 2014
Reference Manual
00809-0100-4952, Rev AA
Table A-1. Rosemount Pipe Clamp Sensor Ordering Table
The Standard offering represents the most common options. The starred options () should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Code Pipe clamp material
Standard Standard
P ASTM 304 SST (1.4301)
Expanded
B Duplex F51 (1.4462)
Code Inner diameter (D) Suitable pipe size inch
Suitable
pipe size DIN
Clamp/bolt dimensions
Standard Standard
0022 22 mm
1
/2 in. DN15 30 x 5 mm, M10 0034 34 mm 1 in. DN25 30 x 5 mm, M10 0061 61 mm 2 in. DN50 40 x 6 mm, M12 0089 89 mm 3 in. DN80 40 x 6 mm, M12 0115 115 mm 4 in. DN100 50 x 8 mm, M16 0140 140 mm 5 in. DN125 50 x 8 mm, M16 0169 169 mm 6 in. DN150 50 x 8 mm, M16 0220 220 mm 8 in. DN200 50 x 8 mm, M16 0273 273 mm 10 in. DN250 60 x 8 mm, M20
Expanded
0027 27 mm 0030 30 mm DN25 30 x 5 mm, M10 0043 43 mm 1 1/4 in. DN32 30 x 5 mm, M10 0049 49 mm 1 1/2 in. DN40 30 x 5 mm, M10 0077 77 mm 2 1/2 in. DN65 40 x 6 mm, M12 0159 159 mm DN150 50 x 8 mm, M16 0306 306 mm 60 x 8 mm, M20 0324 324 mm 12 in. DN300 60 x 8 mm, M20 0356 356 mm 14 in. DN350 60 x 8 mm, M20 0368 368 mm DN350 60 x 8 mm, M20 0407 407 mm 16 in. DN400 60 x 8 mm, M20 0458 458 mm 18 in. DN450 70 x 10 mm, M24 0508 508 mm 20 in. DN500 70 x 10 mm, M24 0521 521 mm DN500 70 x 10 mm, M24 0610 610 mm 24 in. DN600 70 x 10 mm, M24 0660 660 mm 26 in. 70 x 10 mm, M24 0720 720 mm 70 x 10 mm, M24 0762 762 mm 30 in. DN790 70 x 10 mm, M24 0813 813 mm 32 in. DN900 70 x 10 mm, M24 0915 915 mm 36 in. DN1000 70 x 10 mm, M24 1016 1016 mm 40 in. 70 x 10 mm, M24 1070 1070 mm 42 in. 70 x 10 mm, M24 1219 1219 mm 48 in. 70 x 10 mm, M24
3
/4 in. DN20 30 x 5 mm, M10
Code Corrosion protection inlay
Standard Standard
N None
Expanded
A Material NBR
10
Reference Data
Reference Manual
00809-0100-4952, Rev AA
Appendix A: Reference Data
Table A-1. Rosemount Pipe Clamp Sensor Ordering Table
The Standard offering represents the most common options. The starred options () should be selected for best delivery. __The Expanded offering is subject to additional delivery lead time.
Options (include with selected model number)
Code Sensor options
Standard Standard
A1 Single Element Class A Sensor from -50 to 300 °C (-58 to 572 °F) A2 Dual Element Class A Sensor from -50 to 300 °C (-58 to 572 °F)
Code Assemble to option
Standard Standard
XA Assemble Sensor to Specific Temperature Transmitter
Code Cable gland options
Standard Standard
G2 Cable Gland, Ex d, Brass, 7.5-11.9 mm G7 Cable Gland, M20x1.5, Ex e, Blue, Polyamide, Diam 5-9 mm
Code Product certifications
Standard Standard
E1 ATEX Fla mep roo f E7 IECEx Flameproof and Dust E5 FM Explosion-proof E6 CSA Explosion-proof
Code Cover chain option
Standard Standard
G3 Cover Chain - only available with Rosemount Connection Head Material Codes C, D, G, and H
Code Product certifications
Standard Standard
LT Special Material to meet extended Temperature rage of -51 Deg C
Reference Data
11
Appendix A: Reference Data
A
February 2014
A.1.1 Design example drawings
Figure A-1. Pipe Clamp Sensor Assembly
Reference Manual
00809-0100-4952, Rev AA
A. 1/2-in. NPT Spring loaded adapter
12
Reference Data
Reference Manual
00809-0100-4952, Rev BA
Appendix B: Product Certifications

Appendix B Product Certifications

Approved manufacturing locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 13
European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 13
Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15

B.1 Approved manufacturing locations

Emerson Process Management Rosemount Division. – Chanhassen, MN
Emerson Process Management Asia Pacific Limited – Singapore
Emerson Process Management GmbH & Co. - Karlstein, Germany
Emerson Process Management (India) Private Ltd. – Mumbai, India
Emerson Process Management Brazil - Sorocaba, Brazil
Emerson Process Management, Dubai - Emerson FZE
Beijing Rosemount Far East Instrument Co., Limited. - Beijing, China
February 2014

B.2 European Directive Information

A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com.
B.2.1 Ordinary Location Certification from FM Approvals
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by FM Approvals, a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
B.2.2 Hazardous Locations Certifications
North America
E5 FM Explosionproof and Dust-Ignitionproof
Certificate: 0R7A2.AE Standards Used: FM Class 3600- 2011, FM Class 3615 - 2006, FM Class 3810 - 2005 ANSI/NEMA 250 - 1991 Markings: XP CL I, DIV 1, GP B, C, D, T6; DIP CL II / III, DIV 1, GP E, F, G, T6; Type 4X; Installed per 00068-0013;
E6 CSA Explosionproof, Dust-Ignitionproof and Division 2
Certificate:1063635 Standards Used: CAN/CSA C22.2 No. 0-M91, CSA Std. C22.2 No. 25-1966, CSA Std. C22.2 No. 30-M1986, CSA Std. C22.2 No.94-M91, CSA Std. C22.2 No. 142-M1987, CSA Std. C22.2 No. 213-M1987 Markings: XP Class I Groups B, C, and D; DIP Class II Groups E, F, G; Class III; Class I Div. 2 Groups A, B, C, D; Class I Zone 1 Group IIB+H2; Class I Zone 2 Group IIC; Installed per 00068-0033;
Product Certifications
13
Appendix B: Product Certifications
February 2014
Europe
E1 ATEX Fla m eproof
Certificate: FM12ATEX0065X Standards Used: EN60079-0:2012, EN60079-1:2007 Markings: II 2 G Ex d IIC T6…T1 Gb
Special Conditions for Safe Use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become a source of ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4 joules.
4. Consult the manufacturer if dimensional information on the flameproof joints is necessary.
International
E7 IECEX Flameproof
Certificate: IECEx FMG 12.0022X Standards Used: IEC60079-0:2011, IEC60079-1:2007 Markings: Ex d IIC T6…T1 Gb
Special Conditions for Safe Use (X):
Reference Manual
00809-0100-4952, Rev BA
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become a source of ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than 4 joules.
4. Consult the manufacturer if dimensional information on the flameproof joints is necessary.
14
Product Certifications
Reference Manual
00809-0100-4952, Rev BA
Appendix B: Product Certifications

B.3 Installation drawings

Figure B-1. FM Explosionproof Temperature Measurement Assembly (E5) Installation Drawing 00068-0013,
Rev AG.
Product Certifications
15
Appendix B: Product Certifications
February 2014
Reference Manual
00809-0100-4952, Rev BA
Figure B-2. CSA Explosionproof Temperature Measurement Assembly (E6) Installation Drawing 00068-0033,
Rev AG.
16
Product Certifications
Reference Manual
00809-0100-4952, Rev BA
Standard Terms and Conditions of Sale can be found at www.rosemount.com/terms_of_sale The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount. the Rosemount logotype, and SMART FAMILY are registered trademarks of Rosemount Inc. Coplanar is a trademark of Rosemount Inc. Halocarbon is a trademark of the Halocarbon Products Corporation.o. Fluorinert is a registered trademark of Minnesota Mining and Manufacturing Company Corporation Syltherm 800 and D.C. 200 are registered trademarks of Dow Corning Corporation. Neobee M-20 is a registered trademark of PVO International, Inc. HART is a registered trademark of the HART Communication Foundation. Foundation fieldbus is a registered trademark of the Fieldbus Foundation. All other marks are the property of their respective owners.
© February 2014 Rosemount, Inc. All rights reserved.
Emerson Process Management Rosemount Measurement
8200 Market Boulevard Chanhassen MN 55317 USA Tel (USA) 1 800 999 9307 Tel (International) +1 952 906 8888 Fax +1 952 906 8889
Emerson Process Management Latin America
1300 Concord Terrace, Suite 400 Sunrise Florida 33323 USA Tel + 1 954 846 5030
Emerson Process Management GmbH & Co.
Argelsrieder Feld 3 82234 Wessling Germany Tel 49 (8153) 9390 Fax 49 (8153) 939172
Emerson Process Management Asia Pacific Private Limited
1 Pandan Crescent Singapore 128461 T (65) 6777 8211 F (65) 6777 0947 Enquiries@AP.EmersonProcess.com
Beijing Rosemount Far East Instrument Co., Limited
No. 6 North Street, Hepingli, Dong Cheng District Beijing 100013, China T (86) (10) 6428 2233 F (86) (10) 6422 8586
Loading...