YARWAY SERIES 515/516* INTEGRAL STRAINER STEAM TRAPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Before installation these instructions must be fully read and understood
RATINGS
Operating pressure ranges
MAX. TEMPERATURE (C)
SATURATION CURVE
ALL LIQUID
PHASE
SERIES 515
ALL
SUPERHEAT
MAX. TEMPERATURE, PSI
SERIES 516
MAX. TEMPERATURE, BAR
MAX. TEMPERATURE (F)
SHELL PRESSURE/TEMPERATURE RATINGS
Back Pressure Limits
SERIES NUMBERS
Piston valve traps rated to 1500 psig (100 bar) (incl.) are factory set to operate from 150psig (10 bar) to maximum rated pressure. Maximum allowable back pressure at trap outlet equals
To determine the size, series number, and pressure/temperature rating, refer to the
Suffix Letter Identification
SW Socketweld ends
A, B Internal Part Size
R* Commercial (flanges per ANSI Standard)
E* Navy (flanges per MIL-T-960E)
End Conn. Figure No. Internal Parts Piston End Conn. Rating
1/2", 3/4", 1"
Note: Series 515 socketweld end traps are chrome moly steel construction. *Series 516 socketweld end traps are constructed from carbon steel.
515
516*
A or B
SW SW
1500 psig (100 bar) - 875F (468C) 1500 psig (100 bar) - 775F (413C)
Emerson.com/FinalControl
© 2018 Emerson. All Rights Reserved. VCIOM-09537-EN 18/09
YARWAY SERIES 515/516* INTEGRAL STRAINER STEAM TRAPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
FIGURE 1
Equipment drain
Yarway Welbond shut off valve
Steam trap
Dirt leg (optional)
Strainer blow-down (optional) ½ Yarway Welbond globe valve
Test valve (optional) Yarway Welbond globe valve
INSTALLATION
Piping to and from the trap should be equal to trap size or one size larger. Discharge line for short runs equal to trap size; larger for long runs. Avoid configurations that would cause excessive back pressure.
Blow the System Out before installing the trap. Frequent strainer blowdown or cleaning is recommended on a new system. Conditions will dictate frequency of blowdown in normal operation.
Elevated return
Check valve
Return main
Welding - Socket or seal welding of this
trap body to the piping should be completed
according to applicable codes, standards, and
procedures.
DO NOT make electrical welding connections
to the trap body or any other part of the trap
to prevent internal arcing. Electrical ground
should be made to the pipe and not the trap.
Note: It is not necessary to disassemble the
trap prior to welding, but avoid subjecting the
internals to temperatures higher than 500F.
Valves - Use globe type (Yarway Welbond
®
) for isolation strainer blow down, or for test (see Figure No. 1). Bypasses not recommended except for critical installations. If discharge is to a multistation or overhead return, put a swing check valve in discharge line to prevent backflooding on shutdown. Select a check valve suitable for the application.
Locate Trap below outlet from equipment (gravity flow). If trap must be above the drain provide a "U" or lift fitting at the bottom of the riser before the trap (water seal). The trap may be installed in a horizontal or vertical line or at any angle so long as the discharge is downward or horizontal.
WARNING
Hot discharge from this product may cause severe burns. Discharge must be piped away or directed so that persons in the vicinity are not endangered. This product must be isolated, vented and cool to the touch before repairing or inspecting.