Emerson YARWAY 516 Series, YARWAY 515 Series Installation, Operation And Maintenance Instructions

YARWAY SERIES 515/516* INTEGRAL STRAINER STEAM TRAPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
Before installation these instructions must be fully read and understood
RATINGS
Operating pressure ranges
MAX. TEMPERATURE (C)
SATURATION CURVE
ALL LIQUID
PHASE
SERIES 515
ALL
SUPERHEAT
MAX. TEMPERATURE, PSI
SERIES 516
MAX. TEMPERATURE, BAR
MAX. TEMPERATURE (F)
SHELL PRESSURE/TEMPERATURE RATINGS
Back Pressure Limits
SERIES NUMBERS
Piston valve traps rated to 1500 psig (100 bar) (incl.) are factory set to operate from 150psig (10 bar) to maximum rated pressure. Maximum allowable back pressure at trap outlet equals
To determine the size, series number, and pressure/temperature rating, refer to the
Suffix Letter Identification
SW Socketweld ends
A, B Internal Part Size
R* Commercial (flanges per ANSI Standard)
E* Navy (flanges per MIL-T-960E)
End Conn. Figure No. Internal Parts Piston End Conn. Rating
1/2", 3/4", 1"
Note: Series 515 socketweld end traps are chrome moly steel construction. *Series 516 socketweld end traps are constructed from carbon steel.
515
516*
A or B
SW SW
1500 psig (100 bar) - 875F (468C) 1500 psig (100 bar) - 775F (413C)
Emerson.com/FinalControl
© 2018 Emerson. All Rights Reserved. VCIOM-09537-EN 18/09
YARWAY SERIES 515/516* INTEGRAL STRAINER STEAM TRAPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
FIGURE 1
Equipment drain
Yarway Welbond shut off valve
Steam trap
Dirt leg (optional)
Strainer blow-down (optional) ½ Yarway Welbond globe valve
Test valve (optional) Yarway Welbond globe valve
INSTALLATION
Piping to and from the trap should be equal to trap size or one size larger. Discharge line for short runs equal to trap size; larger for long runs. Avoid configurations that would cause excessive back pressure.
Blow the System Out before installing the trap. Frequent strainer blowdown or cleaning is recommended on a new system. Conditions will dictate frequency of blowdown in normal operation.
Elevated return
Check valve
Return main
Welding - Socket or seal welding of this
trap body to the piping should be completed
according to applicable codes, standards, and
procedures.
DO NOT make electrical welding connections
to the trap body or any other part of the trap
to prevent internal arcing. Electrical ground
should be made to the pipe and not the trap.
Note: It is not necessary to disassemble the
trap prior to welding, but avoid subjecting the
internals to temperatures higher than 500F.
Valves - Use globe type (Yarway Welbond
®
) for isolation strainer blow down, or for test (see Figure No. 1). Bypasses not recommended except for critical installations. If discharge is to a multistation or overhead return, put a swing check valve in discharge line to prevent backflooding on shutdown. Select a check valve suitable for the application.
Locate Trap below outlet from equipment (gravity flow). If trap must be above the drain provide a "U" or lift fitting at the bottom of the riser before the trap (water seal). The trap may be installed in a horizontal or vertical line or at any angle so long as the discharge is downward or horizontal.
WARNING
Hot discharge from this product may cause severe burns. Discharge must be piped away or directed so that persons in the vicinity are not endangered. This product must be isolated, vented and cool to the touch before repairing or inspecting.
2
YARWAY SERIES 515/516* INTEGRAL STRAINER STEAM TRAPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
MAINTENANCE
1. For the best trap operation and maximum
service life, strainer screen should be cleaned frequently. This can best be done by using a blowdown valve connected to blow­off connection.
2. Periodically remove the bonnet and clean
and inspect the screen. This should be done at least once a year and more frequently if the trap is not fitted with a strainer blowdown valve.
3. When cleaning the strainer it is
recommended that the trap be inspected and working parts cleaned if necessary. In the event of condensate drainage problems, check before opening the trap whether the trouble is due to a clogged line, valve broken or in wrong position, or dirty strainer requiring blowdown.
CHECKING
Check bonnet and cap nut torque after 48 hours of operation. More frequent checks for proper trap operation can be quickly made by one of the following methods: a. Observe the discharge from the trap
through the test connection—first closing the downstream stop valve.
b. Hold screwdriver or metal rod against base
of cap. Listen for characteristic clicking
sound of valve as it opens and closes. If trap is remaining open continuously or not opening at all: —strainer screen may be damaged or dirty. —parts may be worn from service. —dirt and scale may be lodged in internals. Disassemble and inspect the trap.
PARTS LIST
Item Description
1 Body 2 Bonnet 3 Cap 4* Valve 5* Control cylinder 6* Seat 7* Lock nut 8* Lock pin 9* Seal gasket 10* Cap gasket 11* Bonnet gasket 12* Screen 13 Bonnet stud 14 Bonnet nut 15 Cap stud 16 Cap nut
* Renewal kit
DISASSEMBLY
1. Remove bonnet and unscrew seat.
2. Inspect and clean all parts. If satisfactory, reassemble trap. It is recommended that new gaskets be used.
*Consult factory for non-standard product, flanges and Series 516.
If Internals Require Replacing
1. Remove cap nuts, cap and using wrench and screw driver simultaneously, loosen control cylinder.
2. Pull lock pin, remove lock nut and unscrew control cylinder.
3. Install new internals, screen and gaskets. Reassemble trap.
FIGURE 2 Piston valve type
3
YARWAY SERIES 515/516* INTEGRAL STRAINER STEAM TRAPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
SERVICING
After disassembly, clean internal parts with a cloth and non-corrosive solvent. Heavy deposits may be cleaned from orifice in top of piston valve with a piece of fine wire or toothpick.
BE CAREFUL not to damage valve orifice, disc edge, or control cylinder bore. Under no circumstances should crocus cloth or tools be used to clean any surfaces of trap parts.
Inspect control cylinder bore, valve and seat for wear. Worn parts cause inefficient or improper operation. They should be replaced with a factory-set renewal kit.
CAUTION: The valve, seat and control cylinder or the renewal kit are matched parts. They are not individually interchangeable with similar parts from other repair kits. Do not re-use any of the old parts when installing a new renewalkit.
SPARE PARTS
To cover a one year service period, it is recommended that one (1) renewal kit for every four (4) integral strainer traps installed of same internals be stocked. (Minimum number of kits1) and sufficient gaskets for trap inspection.
Internal part size Renewal kit part no.
A 963557-01 B 963557-02
REASSEMBLY
Installing Repair Kit
1. Clean sealing surfaces and all internal parts.
2. Clean studs, and lubricate studs and nut faces with high temperature lubricant, such as “Molykote”.
3. Remove lock pin and nut from control cylinder stem.
4. Lubricate threads. Screw control cylinder into bonnet.
5. Insert valve in seat, holding valve in position, lubricate threads screw seat into bonnet— be sure valve enters control cylinder and that seat contacts the bottom of the counterbore in the bonnet.
6. Replace lock nut (bevel up), and fully insert lock pin.
7. Screw cylinder down; tighten lock nut per Table 1.
8. Push screen into body recess and with new bonnet and seat gaskets in place lower bonnet over studs.
9. Run bonnet nuts on studs and tighten alternately to the torque indicated in Table1.
10. Replace cap gasket, cap and nuts. Torque per Table 1. Table 1—Torque Values ft-lbs (Nm)
TABLE 1 - TORQUE VALUES ft-lbs (Nm)
Item ft-lbs (Nm)
Bonnet nuts 110-130 (149-176) Cap nuts 14-18 (19-24) Lock nut 7.9-8.3 (10.7-11.3)
FIGURE 3 Trap disassembled exposing strainer and 'cage' arrangement of all trap working parts mounted in the bonnet.
FIGURE 4 Seat removed to show valve and control cylinder.
4
YARWAY SERIES 515/516* INTEGRAL STRAINER STEAM TRAPS
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
NOTE
Any malfunction of this product must be reported to the service department. Repare made to the product by unauthorized personnel will void the warranty.
Right to know laws and OSHA standard 29CFR (1910.1200)
Material Safety Data Sheets on the following Yarway products: Valves, Steam Traps and Strainers
The OSHA Hazard Communication Standard 29CFR 1910.1200, states that the standard does not apply to “articles.” The standard defines an article as: “A manufactured item formed to a specific shape or design for a particular use which does not release or otherwise expose an employee to a hazardous chemical under normal conditions of use.” The above named products fall within the definition of an “article”, no Material Safety Data Sheets are available or are required. Our product is manufactured as an “end product.” If the product is a weld end the following applies.
WARNING
Materials used in manufacture of Yarway products are considered in a stable condition when shipped. However, under certain conditions purchasers could create potential hazardous conditions by their future operations.
CAUTION
Welding, cutting, burning, machining or grinding of this product can generate toxic dust and fumes of potentially hazardous ingredients. The dust or fumes can cause irritation of the respiratory tract, nose, throat, skin and eyes. It may cause temporary or permanent respiratory disease in a small percentage of exposed individuals. Use moderate ventilation when grinding or welding. Avoid breathing dust, fumes or mist. Avoid prolongued skin contact with dust or mist. Maintain dust levels below OSHA and ACGIH levels. Use protective devices. Wash hands thoroughly after contact with dust before eating or smoking.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Yarway is a mark owned by one of the companies in the Emerson Automated Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson andthe Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson.com/FinalControl
5
Loading...