Emerson Y690VB Instruction Manual

Instruction Manual Form 5465
December 2009
Y690VB Series Vacuum Breakers
Introduction
This manual describes and provides instructions and parts lists for Types Y690VB and Y690VBM vacuum breakers. Instructions and parts lists for other equipment used with these breakers are found in separate manuals.
Product Description
The Y690VB Series vacuum breakers are used for precise control of small capacity, low-pressure service applications where an increase in vacuum must be limited. These direct-operated vacuum breakers come in NPS 3/4 and 1 (DN 20 and 25) body sizes and
have an 1/4 or 1/2-inch (6,4 or 13 mm) orice. The
individual products are described as follows:
Type Y690VB
W7292
Figure 1. Type Y690VB Vacuum Breaker
Y690VB Series
The Type Y690VB is a vacuum breaker with internal pressure registration requiring no downstream control line.
Type Y690VBM
The Type Y690VBM is a vacuum breaker with a control line connection and a throat seal for external pressure registration.
Specications
Specications section gives some general ratings and specications for the Y690VB Series vacuum
breakers. Individual breakers come from the factory
with the specic data stamped on the nameplate.
Installation
Warning
!
Personal injury, property damage, equipment damage, or leakage due to escaping gas or bursting of
pressure-containing parts may result if this equipment is overpressured or is installed where service conditions could exceed the limits given in Specications section, or where conditions exceed any ratings of the adjacent piping or piping connections. To avoid such injury or damage, provide pressure-relieving or pressure-limiting devices (as required by the appropriate code, regulation, or standard) to prevent service conditions from exceeding those limits. Additionally, physical damage to this equipment could cause personal injury or property damage due to escaping gas. To avoid such injury or damage, install the equipment in a safe and well ventilated location.
Equipment operation within ratings does not preclude the possibility of damage from debris in the lines or from external sources. This equipment should be inspected for damage periodically and after any overpressure condition.
www.sherregulators.com
D102594X012
Y690VB Series
Specications
Body Sizes
NPS 3/4 or 1 (DN 20 or 25)
End Connection Styles
(1)
See Table 2
Maximum Allowable Inlet (Positive) Pressure
(2)
150 psig (10,3 bar)
Vacuum Control Pressure Ranges
(2)
See Table 1
Maximum Outlet (Casing) Pressure
(2)
Full Vacuum
Maximum Emergency Outlet Pressure to Avoid Internal Parts Damage
(2)
150 psig (10,3 bar)
Spring Case Connection
1/4 NPT
Orice Size
Change in Vacuum Control Pressure to Wide-Open
(2)
See Table 1
Pressure Registration
Type Y690VB: Internal Type Y690VBM: External
Temperature Capabilities
Nitrile (NBR):
-20° to 180°F (-29° to 82°C)
Fluorocarbon (FKM):
40° to 300°F (4° to 149°C)
Ethylenepropylene (EPDM):
-20° to 275°F (-29° to 135°C)
Peruoroelastomer (FFKM):
-20° to 300°F (-29° to 149°C)
Approximate Weight
19 pounds (9 kg)
1/4 or 1/2-inch (6,4 or 13 mm)
1. End connections for other than U.S. standards can usually be provided; consult the local Sales Ofce.
2. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
(2)
B2672
VACUUM
PUMP
INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE
Figure 2. Type Y690VB Operational Schematic
VACUUM
BEing
LIMITED
POSITIVE PRESSURE OR ATMOSPHERE OR A
LESSER VACUUM THAN THE ONE BEING LIMITED
2
Table 1. Vacuum Pressure Information
Y690VB Series
VACUUM CONTROL
PRESSURE RANGE
0 to 4-inches w.c. (0 to 10 mbar) 0.6-inches w.c. (1,5 mbar) 1.3-inches w.c. (3 mbar) 0N039427222 Unpainted 0.062-inches (1,6 mm)
0 to 1.0 psig (0 to 0,07 bar) 10-inches w.c. (25 mbar) 0.7 psig (0,05 bar) 0N086127022 Unpainted 0.125-inches (3,2 mm)
0 to 2.1 psig (0 to 0,14 bar) 1.2 psig (0,08 bar) 2.4 psig (0,17 bar) 0N004327022 Yellow 0.172-inches (4,4 mm)
0 to 5 psig (0 to 0,34 bar) 3.2 psig (0,22 bar) 6.3 psig (0,43 bar) 1D141827012 Dark blue 0.207-inches (5,3 mm)
1. Spring ranges based on atmospheric inlet pressure.
2. To convert to inches Hg, multiply psig value by 2.04.
(1)(2)
If this equipment is shipped mounted on another unit, install that unit according to the appropriate instruction manual.
1. Only personnel qualied through training and
experience should install, operate, and maintain this equipment. For Y690VB Series equipment
CHANGE IN VACUUM TO WIDE-OPEN
1/4-inch (6,4 mm) Orice
Note
1/2-inch (13 mm)
Orice
downstream vacuum, to enter the system and restore the controlled vacuum to its original pressure setting. A Type Y690VB (Figure 3) direct-operated vacuum breaker is self-contained and requires no control line. A Type Y690VBM (Figure 4) vacuum breaker requires a control line from the 1/2 NPT tapping in the diaphragm case assembly to the point where the vacuum needs to be controlled.
Spring
PART NUMBER
SPRING COLOR
Spring WirE
DIAMETER
that is shipped separately, make sure that there is no damage to or foreign material in it. Also ensure that all tubing and piping have been blown free.
2. This equipment may be installed in any position
as long as the ow through the body is in the
direction indicated by the arrow attached to the body. If continuous operation is required during inspection or maintenance, install a three-way bypass valve around the equipment.
Startup and Adjustment
All Y690VB Series equipment can be placed in operation by slowly introducing inlet vacuum or pressure. This equipment takes control when vacuum is established. This equipment is suitable for the pressure range stamped on the nameplate (key 46), and listed in Table 1. To adjust the pressure setting, remove the closing cap (key 22) and turn the adjusting
Warning
!
This equipment may vent some gas to the atmosphere. In hazardous or ammable gas service, vented gas may
nut (key 20) clockwise to increase the pressure setting or counterclockwise to decrease the setting. Replace the cap after making this adjustment. If desired, the closing cap may be wired to the hole provided in the spring case (key 3) to discourage tampering.
accumulate and cause personal injury, death, or property damage due to re or explosion. Vent equipment in hazardous gas service to a remote, safe location away from air intakes or any hazardous area. The vent line or stack opening must be protected against condensation or clogging.
Shutdown
First close the nearest upstream shutoff valve and then close the nearest downstream shutoff valve to vent the equipment properly. Next, open the vent valve between the equipment and the downstream shutoff valve nearest to it. All pressure between these shutoff valves is released through the open vent valve.
Principle of Operation
The Y690VB Series vacuum breakers (Figure 2) are used in applications where an increase in vacuum must be limited. An increase in vacuum (decrease in absolute pressure) is transmitted to the lower side of the diaphragm, opening the disk assembly. This permits positive pressure, atmosphere, or an upstream vacuum that has higher absolute pressure than the
Maintenance
Equipment parts are subject to normal wear and must be inspected and replaced as necessary. The frequency of inspection and replacement of parts depends on the severity of service conditions and upon applicable codes and government regulations.
3
Loading...
+ 5 hidden pages