The Types Y690VB and Y690VBM have common
spare parts with the other Y690A Series products.
• Tamper–Resistant Adjustment:
Closing cap and spring case on many types allow
installation of sealing wire to discourage or detect
unauthorized adjustment of pressure setting.
• Easy Conversion:
The Type Y690VB converts easily to the
Type Y690VBM.
• Precision Control of Low-Pressure Settings:
Large diaphragm areas provide more accurate
control at low-pressure settings.
• Corrosion Resistance:
Constructions are available in a variety of materials
for compatibility with corrosive process gases.
Introduction
The Y690VB Series direct-operated vacuum breakers
are used for precise control of small capacity and
low-pressure service applications where an increase
in vacuum must be limited. The Type Y690VB has
internal pressure registration. The Type Y690VBM has
a control line connection and an O-ring stem seal for
external pressure registration.
www.sherregulators.com
D102593X012
Bulletin 71.3:Y690VB
Specications
Available Congurations
Type Y690VB: Direct-operated vacuum breaker with internal registration.
Type Y690VBM: Direct-operated vacuum breaker equipped with a blocked throat and control line connection for external pressure registration.
Body Sizes
NPS 3/4 or 1 (DN 20 or DN 25)
End Connection Styles
See Table 1
Maximum Allowable Inlet Pressure
(1)
150 psig (10,3 bar)
Maximum Outlet (Casing) Pressure
(1)
Full Vacuum
Maximum Emergency Outlet Pressure to Avoid
Internal Parts Damage
(1)
150 psig (10,3 bar)
Vacuum Control Pressure Ranges
(1)
See Table 4
Construction Materials
See Table 3
Temperature Capabilities
(1)
Nitrile (NBR):
-20° to 180°F (-29° to 82°C)
Fluorocarbon (FKM):40° to 300°F (4° to 149°C)
Ethylenepropylene (EPDM):
-20° to 300°F (-29° to 149°C)
Peruoroelastomer (FFKM):
-20° to 300°F (-29° to 149°C)
Pressure Registration
Type Y690VB: InternalType Y690VBM: External
Orice Size
1/4-inch (6,3 mm)
1/2-inch (13 mm)
Pressure Setting Adjustment
Adjusting Nut
Spring Case Connection
1/4 NPT
Flow Coefcients
See Table 2
Flow Capacities
See Table 6
1. The pressure/temperature limits in this Bulletin and any applicable standard or code limitation should not be exceeded.
Table 1. End Connection Styles
BODY SIZE,
NPS (DN)
3/4 (20)
1 (25)
1. All ange dimensions are 14-inches (356 mm) face-to-face.
END CONNECTION STYLE
Ductile IronStainless Steel
NPT
NPT, SWE, or ASME
(1)
CL150 RF
Diaphragm Case Connection
1/2 NPT
Approximate Weight
19 pounds (9 kg)
Table 2. Flow Coefcients
ORIFICE SIZE
INCHES (mm)
1/4 (6,3)501.435
1/2 (13)2005.735
FLOW COEFFICIENT
C
g
C
v
C
1
2
VACUUM PUMP
Type Y692
July 2007
Type Y692
Bulletin 71.3:Y690VB
VACUUM BEING LIMITED
INLET PRESSURE
CONTROLPRESSURE (VACUUM)
INLET PRESSURE
CONTROL PRESSURE (OUTLET PRESSURE)
ATMOSPHERIC PRESSURE
ATMOSPHERIC PRESSURE
B2672
Figure 2. Y690VB Series Operational Schematic
POSITIVE PRESSURE OR ATMOSPHERE, OR A
LESSER VACUUM THAN THE ONE BEING LIMITED
3
Bulletin 71.3:Y690VB
Table 3. Construction Materials
BODYSPRING CASEDIAPHRAGM CASETRIMDIAPHRAGMDISK
Ductile iron or CF8M
Stainless steel
Table 4. Vacuum Control Pressure Ranges
Ductile iron or
CF8M Stainless steel
CF8M Stainless steel
Ductile iron or
S303 Stainless steel
Nitrile (NBR) or
Fluorocarbon (FKM)
Nitrile (NBR) or
Fluorocarbon (FKM)
VACUUM
CONTROL
PRESSURE
(1)(2)
RANGE
0 to 4-inches w.c.
(0 to 10 mbar)
0 to 1.0 psig
(0 to 0,07 bar)
0 to 2.1 psig
(0 to 0,15 bar)
0 to 5 psig
(0 to 0,35 bar)
1. Spring ranges based on atmospheric inlet pressure.
2. To convert to inches Hg, multiply psig value by 2.04.
CHANGE IN VACUUM TO WIDE-OPEN
1/4-inch
(6,3 mm) Orice
0.6-inches w.c.
(1,5 mbar)
10-inches w.c.
(25 mbar)
1.2 psig
(0,08 bar)
3.2 psig
(0,22 bar)
1/2-inch
(13 mm) Orice
1.3-inches w.c.
(3 mbar)
0.7 psig
(0,05 bar)
2.4 psig
(0,17 bar)
6.3 psig
(0,43 bar)
Table 5. Maximum Setpoints for Achieving Wide-Open Flow
SPRING RANGE,
PART NUMBER,
AND COLOR
0 to 4-inches w.c.
(0 to 10 mbar)
0N039427222
Unpainted
0 to 1.0 psig
(0 to 0,07 bar)
0N086127022
Unpainted
0 to 2.1 psig
(0 to 0,14 bar)
0N004327022
Yellow
0 to 5 psig
(0 to 0,34 bar)
1D141827012
Dark blue
1. Spring ranges based on atmospheric inlet pressure.
2. To convert to inches Hg, multiply psig value by 2.04.
(1)(2)
ORIFICE SIZE
INCHES (mm)
1/4 (6,3)
1/2 (13)
1/4 (6,3)
1/2 (13)
1/4 (6,3)
1/2 (13)
1/4 (6,3)
1/2 (13)
MAXIMUM
ALLOWED
VACUUM
5.1 psig
(0,35 bar)
6.0 psig
(0,41 bar)
7.1 psig
(0,49 bar)
12.0 psig
(0,83 bar)
MAXIMUM SETPOINTS FOR ACHIEVING WIDE-OPEN FLOW AT SPECIFIC INLET PRESSURES
1. Spring ranges based on atmospheric inlet pressure.
2. To convert to inches Hg, multiply psig value by 2.04.
(1)
VACUUM
CONTROL SETTING
2-inches w.c. (5 mbar)
0.5 psig (0,03 bar)
2 psig (0,14 bar)
4 psig (0,28 bar)
(2)
ORIFICE SIZE
INCHES (mm)
Principle of Operation
An increase in vacuum (decrease in absolute
pressure) beyond a setpoint registers on the
diaphragm, opening the disk. This permits
atmosphere, positive, or an upstream vacuum that
has higher absolute pressure than the downstream
vacuum, to enter the system and restore the controlled
vacuum to the setpoint. On the Type Y690VB,
the pressure registers internally underneath the
diaphragm. The Type Y690VBM has a control line
connecting the diaphragm casing to the vacuum line
and a throat seal allowing for registration only through
the control line connection.
Installation
CHANGE IN VACUUM
TO WIDE-OPEN
1/4 (6,3)0.6-inches w.c. (1,5 mbar)110 (2,95)
1/2 (13)1.3-inches w.c. (3 mbar)486 (13,0)
1/4 (6,3)10-inches w.c. (25 mbar)293 (7,85)
1/2 (13)0.7 psig (0,05 bar)1382 (37,0)
1/4 (6,3)1.2 psig (0,08 bar)524 (14,0)
1/2 (13)2.4 psig (0,17 bar)2353 (63,1)
1/4 (6,3)3.2 psig (0,22 bar)682 (18,3)
1/2 (13)6.3 psig (0,43 bar)2910 (78,0)
CAPACITIES IN SCFH
(Nm³/h) OF 1.0 SPECIFIC
GRAVITY AIR
Capacity Information
To determine ow capacities for the Y690VB Series
vacuum breakers, use the following formula:
3415
Q = P
SIN
1abs Cg
C
where,
Q = ow capacity in SCFH (60°F and 14.7 psia) of air
P
direction of the arrow on the body. Normal installation
is with the spring case vertical above or below the
diaphragm case. When exposed to the weather, the
vent should be protected by the optional umbrella
vent or pointed down to allow condensate to drain. If
used in hazardous gas service on indoor installations,
this connection should be piped outdoors. External
dimensions and connections are shown in Figure 3.
Note
Downstream piping will vary with the
installation, but to obtain the calculated
characteristics, the pipe should be the
same size as the outlet and should be
straight for the rst 18 inches (457 mm).
Note
If the actual change in (control) pressure
(from the service conditions) is less than
the minimum change in (control) pressure
required to fully open the vacuum breaker
(Table 6), the Cg in the formula must
be reduced accordingly. To obtain the
correct reduced Cg, multiply the Cg from
Table 2 by the ratio of the actual change in
(control) pressure to the minimum change
in (control) pressure required to fully
open the vacuum breaker.
5
Bulletin 71.3:Y690VB
Conversion Factors
To determine equivalent capacities for natural gas,
propane, butane, or nitrogen, multiply the calculated
capacity by the following appropriate conversion
factor: 1.29 for natural gas, 0.810 for propane, 0.707
for butane, or 1.018 for nitrogen. For gases of other
specic gravities, divide by the square root of the
appropriate specic gravity. Then, if capacity is
desired in normal cubic meters per hour at 0°C and
1.01325 bar, multiply SCFH by 0.0268.
Example Problem Using Formula
This example involves a Type Y690VB vacuum breaker
with its outlet connected to a vessel in which the vacuum
must be limited. This breaker has a 1/4-inch (6,4 mm)
orice and a control spring set to start opening and
admit atmospheric pressure whenever the vacuum
pump downstream from the vessel increases the vessel
vacuum to more than 4-inches w.c. (10 mbar). It is
desirable to nd the air ow by the time the pump has
increased the vessel vacuum to 9-inches w.c. (22 mbar)
and the breaker has opened more. To nd the air ow
through the breaker under these conditions:
1. Check whether the change in outlet (controlled)
pressure of 5-inches w.c. (12 mbar) is less than the
minimum change in outlet (controlled) pressure
required to fully open the vacuum breaker. Since
the minimum change in outlet (controlled) pressure
required to fully open the vacuum breaker with
a 1/4-inch (6,4 mm) orice and control spring is
0.6-inches w.c. (1,5 mbar) from Table 4, no
reduction in the regulating Cg of 50 (Table 2) need
be made.
2. Solve the problem by using the appropriate
values in the formula as follows, remembering
that the
9-inches w.c. (0.325 psig) (22 mbar):
=184 SCFH (4,93 Nm³/h) of Air
P across the vacuum breaker is
Q = 14.7(50) SIN DEG
3415350.325
14.7
Ordering Information
When ordering, specify:
Application
1. Composition and specic gravity of gas (including
chemical analysis if possible)
2. Range of temperatures, owing inlet pressures
(maximum, minimum, nominal), and
pressure drops
3. Desired pressure setting or range
4. Range of ow rates (minimum controlled,
maximum, normal)
5. Piping size(s)
Construction
Refer to the Specications section and to each
referenced table; specify the desired selection
whenever there is a choice to be made. Always
be sure to specify the type number and the spring
case orientation.
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75069-1872 USA
Tel: 1-800-558-5853
Outside U.S. 1-972-548-3574
Asia-Pacic
Shanghai, China 201206
Tel: +86 21 2892 9000
Europe
Bologna, Italy 40013
Tel: +39 051 4190611
Middle East and Africa
Dubai, United Arab Emirates
Tel: +971 4811 8100
For further information visit www.sherregulators.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a
business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such
products at any time without notice.
Emerson Process Management does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson
Process Management product remains solely with the purchaser.
Natural Gas Technologies
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75069-1872 USA
Tel: 1-800-558-5853
Outside U.S. 1-972-548-3574
Asia-Pacic
Singapore, Singapore 128461
Tel: +65 6777 8211
Europe
Bologna, Italy 40013
Tel: +39 051 4190611
Gallardon, France 28320
Tel: +33 (0)2 37 33 47 00
TESCOM
Emerson Process Management
Tescom Corporation
USA - Headquarters
Elk River, Minnesota 55330-2445 USA
Tel: 1-763-241-3238
Europe
Selmsdorf, Germany 23923
Tel: +49 (0) 38823 31 0