Emerson Y610A, Y611A, Y612A Instruction Manual

Instruction Manual Form 1477
May 2012
Y610A, Y611A, and Y612A Series
Y610A, Y611A, and Y612A Series Vacuum Service Equipment and Relief Valves
WARNING
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion,
re and/or chemical contamination
causing property damage and personal injury or death.
®
Fisher valves must be installed, operated and maintained in accordance with federal, state, and local codes, rules and regulations, and Emerson Process Management Regulator Technologies, Inc. instructions.
If a leak develops or if the outlet continually vents gas, service to the unit may be required. Failure to correct trouble could result in a hazardous
condition. Only a qualied person must
install or service the unit.
vacuum breakers or relief
W1094_1
Figure 1. Type Y610A Vacuum Breaker
Introduction
Scope of the Manual
This manual describes and provides instructions and parts lists for Y610A, Y611A, and Y612A Series vacuum service equipment and relief valves. Instructions and parts lists for other equipment used with these regulators are found in separate manuals.
Product Description
The Y610A, Y611A, and Y612A Series devices are used in a wide variety of vacuum and relief service applications. The Y610A Series devices (Figure 1) are used as vacuum breakers, the Y611A Series devices are used as either vacuum breakers or relief valves, and the Y612A Series devices are used as vacuum regulators, and are described as follows:
www.fisherregulators.com
Type Y610A—Direct-operated vacuum breaker with upward pointing 1 NPT vent connection, and internal registration requiring no downstream control line.
Type Y610AP—Same as Type Y610A except with blocked throat, diaphragm case assembly tapped 1/2 NPT for control line connection, and O-ring stem seal.
Type Y611A—Direct-operated relief valve with upward pointing 1 NPT vent connection, and internal registration requiring no downstream control line.
Type Y611AP—Direct-operated vacuum breaker with blocked throat, 1 NPT screened side vent, diaphragm case assembly tapped 1/2 NPT for control line connection, and O-ring stem seal.
D103116X012
Y610A, Y611A, and Y612A Series
Specications
The Specications section gives some general Y610A, Y611A, and Y612A Series ratings and other specications. Individual regulator data as it comes from the factory is stamped either on the closing cap or
on a nameplate (Figure 2).
Body Sizes (Inlet x Outlet) and End Connection Style
(2)
Type Y610A, Y610AP, Y611A, Y611AP, Y612A, or Y612AP: 1-1/2 or 2 NPT,
or NPS 2 / DN 50 CL125 FF or
CL250 RF anged
Pressure Information
(1)
Type Y610A or Y610AP Vacuum Breaker:
See Table 1 Type Y611A or Y611AP Relief Valve: See Table 2 Type Y612A or Y612AP Vacuum Regulator: See Table 3
1. The pressure/temperature limits in this Instruction Manual and any applicable standard limitation should not be exceeded.
2. DIN (or other) end connections threaded to various national or international thread standards can usually be supplied; consult your local Sales Ofce.
Temperature Capabilities
-20 to 150°F / -29 to 66°C
Pressure Registration
Type Y610A, Y611A, or Y612A: Internal Type Y610AP, Y611AP, or Y612AP: External
Approximate Weights
Type Y610A, Y610AP, Y611A, Y611AP, Y612A, or Y612AP
With 1-1/2 NPT Body: 25 pounds / 11 kg
With NPS 2 / DN 50 Body:
30 pounds / 14 kg
(1)
Type Y612A—Direct-operated vacuum regulator with
upward pointing 1 NPT vent connection, and internal registration requiring no downstream control line.
Type Y612AP—Same as Type Y612A except with blocked throat, diaphragm case assembly tapped 1/2 NPT for control line connection, and O-ring stem seal.
Installation
WARNING
Personal injury, property damage, equipment damage, or leakage due to escaping gas or bursting of pressure­containing parts may result if this equipment is overpressured or is installed where service conditions could exceed the limits given in Tables 1 through 3, or where conditions exceed any ratings of the adjacent piping or piping connections. To avoid such injury or damage, provide pressure­relieving or pressure-limiting devices (as required by the appropriate code, regulation, or standard) to prevent service conditions from exceeding those limits.
2
11A5497_J
Figure 2. Nameplate
Additionally, physical damage to this equipment could cause personal injury or property damage due to escaping gas. To avoid such injury or damage, install the equipment in a safe and well ventilated location.
Equipment operation within ratings does not preclude the possibility of damage from debris in the lines or from external sources. This equipment should be inspected for damage periodically and after any overpressure condition.
MAXIMUM
ALLOWABLE
TYPES
Y610A and
Y610AP
TYPES
Y611A and
Y611AP
1. Including buildup.
INLET (BODY)
PRESSURE
psig bar psig bar
13 0.90 15 1.0
Table 1. Types Y610A and Y610AP Vacuum Breaker Pressure Information
MAXIMUM
EMERGENCY
OUTLET
(CASING)
PRESSURE
(POSITIVE)
Table 2. Types Y611A and Y611AP Relief Valve Pressure Information
MAXIMUM
MAXIMUM
ALLOWABLE
INLET (CASING)
PRESSURE
psig bar psig bar
15 1.0
(1)
OPERATING
INLET (RELIEF)
PRESSURE TO
PREVENT PART
DAMAGE
5.1 0.35
5.2 0.36
5.3 0.37
5.5 0.38
6 0.41
6.5 0.45
7.5 0.52
SET PRESSURE
RANGE (VACUUM)
With Spring Case
Above Diaphragm
1 to 3 inches w.c. /
2 to 7 mbar
1.5 to 5 inches w.c. / 4 to 12 mbar
3 to 8 inches w.c. /
7 to 20 mbar
8 to 16 inches w.c. /
20 to 40 mbar
16 to 32 inches w.c. /
40 to 80 mbar
0.25 to 3 psig / 17 to 207 mbar
(1)
With Spring Case
Above Diaphragm
3 to 4 inches w.c. /
7 to 10 mbar
3.75 to 6 inches w.c. / 9 to 15 mbar
5 to 8 inches w.c. /
12 to 20 mbar
7 to 16 inches w.c. /
17 to 40 mbar
10 to 30 inches w.c. /
25 to 75 mbar
0.75 to 1.5 psig / 52 to 103 mbar
1 to 2.5 psig /
69 to 172 mbar
Y610A, Y611A, and Y612A Series
CHANGE IN OUTLET
(CONTROLLED)
PRESSURE
REQUIRED TO
FULLY OPEN
VACUUM BREAKER
0.043 3
0.078 5
0.143 1
0.181 12
0.378 26
1.944 134
BUILDUP OVER INLET
PRESSURE REQUIRED
TO FULLY OPEN
RELIEF VALVE
psig mbar
0.089 6
0.100 7
0.124 9
0.216 15
0.351 24
0.648 45
1.026 71
With Spring Case Below Diaphragm
0 to 2 inches w.c. /
0 to 5 mbar
0.50 to 4 inches w.c. / 1 to 10 mbar
2 to 7 inches w.c. /
5 to 17 mbar
7 to 15 inches w.c. /
17 to 37 mbar
15 to 31 inches w.c. /
37 to 77 mbar
0.25 to 3 psig / 17 to 207 mbar
INLET RELIEF
SET PRESSURE RANGE,
With Spring Case Below Diaphragm
2 to 3 inches w.c. /
5 to 7 mbar
2.75 to 5 inches w.c. /
6.9 to 12 mbar
4 to 7 inches w.c. /
10 to 17 mbar
6 to 15 inches w.c. /
15 to 37 mbar
9 to 29 inches w.c. /
22 to 72 mbar
0.75 to 1.5 psig / 52 to 103 mbar
1 to 2.5 psig /
69 to 172 mbar
MAXIMUM
ALLOWABLE
VACUUM
psig bar psig mbar
5.1 0.35
5.2 0.36
5.3 0.37
5.6 0.39
6.1 0.42
8.0 0.55
CONTROL
SPRING
COLOR CODE,
PART NUMBER
Brown Stripe,
1D892527022
Pink Stripe,
1D765427012
Purple Stripe,
0B019727052
Gray,
1B766627062
Unpainted,
1B883327022
Black,
1A630627022
CONTROL
SPRING
COLOR CODE,
PART NUMBER
Red,
1D892627022
Red,
1D892727012
Black,
1D892727012
White Stripe,
1D893227032
Green,
1D893327032
Blue,
1H975827032
Orange,
1H975927032
Note
If this equipment is shipped mounted on another unit, install that unit according to the appropriate instruction manual.
1. Only personnel qualied through training
and experience should install, operate, and maintain this equipment. For Y610A, Y611A, or Y612A Series equipment that is shipped separately, make sure that there is no damage to or foreign material in it. Also ensure that all tubing and piping have been blown free.
2. This equipment may be installed in any position
as long as the ow through the body is in the
direction indicated by the arrow cast on thebody. If continuous operation is required during inspection or maintenance, install a three-valve bypass around the equipment.
WARNING
This equipment may vent some gas to the atmosphere. In hazardous or
ammable gas service, vented gas
may accumulate and cause personal
3
Y610A, Y611A, and Y612A Series
Table 3. Types Y612A and Y612AP Vacuum Regulator Pressure Information
MAXIMUM
ALLOWABLE
INLET
(CASING)
PRESSURE
psig bar psig bar
15 1.03
MAXIMUM
OPERATING
INLET
PRESSURE
TO PREVENT
PART
DAMAGE
5.1 0.35
5.2 0.36
5.3 0.37
5.6 0.39
6.1 0.42
8.0 0.55
SET PRESSURE
RANGE (VACUUM)
With Spring Case
Above Diaphragm
1 to 3 inches w.c. /
2.5 to 7 mbar
1.5 to 5 inches w.c. / 4 to 12 mbar
3 to 8 inches w.c. /
7 to 20 mbar
8 to 16 inches w.c. /
20 to 40 mbar
16 to 32 inches w.c. /
40 to 80 mbar
0.25 to 3 psig / 17 to 207 mbar
With Spring Case Below Diaphragm
0 to 2 inches w.c. /
0 to 5 mbar
0.50 to 4 inches w.c. /
1.2 to 10 mbar
2 to 7 inches w.c. /
5 to 17 mbar
7 to 15 inches w.c. /
17 to 37 mbar
15 to 31 inches w.c. /
37 to 77 mbar
0.25 to 3 psig /
17 to 207 mbar
MAXIMUM
ALLOWABLE
VACUUM
psig bar psig mbar psig mbar psig mbar
5.1 0.35
5.2 0.36
5.3 0.37
5.6 0.39
6.1 0.42
8.0 0.55
CONTROL
SPRING
COLOR
CODE,
PART
NUMBER
Brown Stripe,
1D892527022
Pink Stripe,
1D765427012
Purple Stripe,
0B019727052
Gray,
1B766627062
Unpainted,
1B883327022
Black,
1A630627022
CHANGE IN OUTLET (CONTROLLED)
PRESSURE REQUIRED TO FULLY OPEN
VACUUM REGULATOR
5/8-inch /
16 mm
Port Diameter
0.089 6.1 0.053 3.6 0.076 5.2
0.124 8.6 0.074 5.1 0.106 7.3
0.189 13 0.112 7.7 0.161 11
0.227 16 0.134 9.3 0.193 13
0.405 28 0.240 17 0.345 24
1.944 134 1.152 79 1.656 11 4
1-inch /
25 mm
Port Diameter
1-3/16-inch /
30 mm
Port Diameter
injury, death, or property damage due
to re or explosion. Vent equipment in
hazardous gas service to a remote, safe location away from air intakes or any hazardous area. The vent line or stack opening must be protected against condensation or clogging.
3. A Type Y610A or Y610AP vacuum breaker (Figure 3) is used in applications where an increase in vacuum must be limited. An increase in vacuum (decrease in absolute pressure) is transmitted to the lower side of the diaphragm, opening the disk assembly. This permits atmosphere, or an upstream vacuum that has higher absolute pressure than the downstream vacuum, to enter the system and restore the controlled vacuum to its original pressure setting. A Type Y610A direct-operated vacuum breaker is self-contained and requires no control line. A Type Y610AP vacuum breaker requires a control line from the 1/2 NPT tapping in the diaphragm case assembly (key 20, Figure 4) to a point downstream of the body (key 28, Figure 4).
4. A Type Y611AP vacuum breaker (Figure 3) also is used in applications where an increase in vacuum must be limited. An increase in vacuum (decrease in absolute pressure) is transmitted to the upper side of the diaphragm, opening the disk assembly. This permits atmosphere, or
an upstream vacuum that has higher absolute pressure than the downstream vacuum, to enter the system and restore the controlled vacuum to its original pressure setting. A Type Y611AP vacuum breaker requires a control line from the 1/2 NPT tapping in the spring case assembly (key 23, Figure 5) to a point downstream of the body (key 28, Figure 5).
5. A Type Y611A relief valve (Figure 3) is used to maintain a constant inlet pressure with the outlet
owing to atmosphere or to any system whose
pressure is lower than the pressure at the relief valve inlet. An increase in inlet pressure opens the disk assembly, relieving the excess pressure and restoring the inlet pressure to its original setting. A Type Y611A direct-operated relief valve is self-contained and requires no control line.
6. A Type Y612A or Y612AP vacuum regulator is used to maintain a constant vacuum at the regulator inlet. A decrease in this vacuum (increase in absolute pressure) beyond this value registers underneath the diaphragm and opens the disk. This permits a downstream vacuum of lower absolute pressure than the upstream vacuum to restore the upstream vacuum to its original pressure setting. A Type Y612A (Figure 6) direct-operated vacuum regulator is self-contained and requires no control line. A Type Y612AP vacuum regulator requires a control line from the 1/2 NPT tapping in the diaphragm case assembly to a point upstream of the body.