3 USER INTERFACE ...................................................................................................................................................... 2
4 FAST ACCESS MENU ................................................................................................................................................. 5
5 SECTION MENU .......................................................................................................................................................... 6
5.1. T
O SET ENERGY SAVING TIMES................................................................................................................................... 6
5.2. T
O SET TIMED DEFROST PARAMETERS ........................................................................................................................ 6
6 ELECTRONIC EXPANSION VALVE MENU (FOR MODEL XM679 ONLY).................................................... 7
7.2.1. First Kind of Regulation: Standard Regulation.................................................................................................... 8
7.2.2. Second Kind of Regulation: Continuous Regulation (For Model XM679 Only).................................................. 8
ANS ............................................................................................................................................................................. 9
7.4.1. Control With Relay................................................................................................................................................ 9
7.4.2. Control With Analog Output (If Present).............................................................................................................. 9
9 DIGITAL INPUTS....................................................................................................................................................... 19
OOR SWITCH INPUT (DOR) ....................................................................................................................................... 19
9.5. S
TART DEFROST (DEF)............................................................................................................................................... 19
9.6. R
ELAY AUX ACTUATION (AUS) ................................................................................................................................ 19
OT USED) ..................................................................................................................................................... 19
12 RS485 SERIAL LINE ................................................................................................................................................ 21
13 HOW TO USE THE HOT KEY ............................................................................................................................... 21
15 TECHNICAL DATA ................................................................................................................................................. 25
16 UL RATINGS ............................................................................................................................................................. 26
22.3.1. Set Up Network Ports........................................................................................................................................ 35
22.3.2. Add and Connect the Device..................................................... ..................................... ................................... 35
Please read the following safety precautions and
warnings before using this manual:
CAUTION!
• This manual is part of the product and
should be kept near the device for easy and
quick reference.
• The device should not be used for purposes
different from those described in this manual. It
cannot be used as a safety device.
• Check the application limits before proceeding.
SAFETY PRECAUTIONS AND
WARNINGS!
• Check that the supply voltage is correct
before connecting the device.
• Do not expose to water or moisture: use the
controller only within the operating limits and avoid
sudden temperature changes with high atmospheric
humidity to prevent condensation from forming.
• Warning! Disconnect all electrical connections
before performing any kind of maintenance.
• Fit the probe where it is not accessible by the end
user. The device must not be opened.
• In case of failure or faulty operation, send the
device back to the distributor or to Emerson (see
address) with a detailed description of the fault.
• Verify the maximum current that can be applied
to each relay (see Section 15, Technical Data).
• Ensure that the wires for probes, loads, and the
power supply are separated and far enough from each
other without crossing or intertwining.
• In case of applications in industrial
environments, the use of main filters in parallel with
inductive loads could be useful.
2.1.How to Check the
Software Release of the
XM679K
1. Check the software release of the
XM679K printed on the label of the
controller.
Figure 2-1 - XM679K Software Release
2.2.General Description
Models XM670-XM679 are high level
microprocessor based controllers for multiplexed
cabinets, suitable for applications on medium or low
temperature. It can be inserted in a Local Area
Connection (LAN) of up to eight (8) different sections
that can operate depending on the programming, as
stand alone controllers or by following the commands
coming from the other sections.
XM670/XM679 controllers can have six (6) relay
outputs to control the solenoid valve, defrost that can
be either electrical or hot gas, evaporator fans, lights,
auxiliary output, alarm output and an output to drive
pulsed electronic expansion valves (applicable for
XM679 only).
The controllers can also have up to four (4) probe
inputs: the first one for temperature control, the
second for defrost end temperature control of the
evaporator, the third for the display, and the fourth
probe input can be used for applications with virtual
probe or for inlet/outlet air temperature measurement.
Model XM679 can exclusively have two (2) other
probes that can be used for superheat measurement
and regulation. Both XM670 and XM679 controllers
General WarningIntroduction • 1
Page 8
are also equipped with three digital inputs (free
contact) that are fully configurable through
parameters.
The Hot Key connector allows simple programming
of the controllers.
Direct serial output RS485
MODBUS-RTU compatible permits a simple XWEB
interfacing. Depending on the model, the Hot Key
connector can also be used to connect X-REP display.
2.3.Ordering Codes
Device
Name
XM670
XM670
XM679
XM679
Table 2-1 - Product Ordering Codes
Description
Solenoid Case Control
Solenoid Case Control
11
5V
23
0V
Pulse Case Control
11
5V
Pulse Case Control
23
0V
Emerson
Part
Number
318-6520
318-6521
318-6700
318-6701
2 • XM679K I&O Manual026-1218 Rev 4
Page 9
3User Interface
Measurement unit
Measurement unit
Measurement unit
Measurement unit
Key Combinations
Locks/Unlocks the keyboard
Switches mode to programming mode
Exits the programming mode
Figure 3-1 - XM670 - XM679 Front Panel
3.1.Keys and Functions
Table 3-1 lists the keys that are found on the front
panel of XM670-XM679 controllers and the function
of each:
.
KeyFunction
Press to display the target setpoint, to
select a parameter in programming mode,
or to confirm an operation. Pressing this
key for three (3) seconds while the
minimum or maximum temperature is
displayed will erase the temperature
currently displayed.
Press this key to browse the parameter
codes in programming mode or increases
the displayed value. Pressing this key for
three (3) seconds will give you access to
the Section menu.
Press this key to access the fast access
menu, browse the parameter codes in
programming mode, decrease the
displayed value, or activate or deactivate
an auxiliary output.
Starts a defrost when pressed for three (3)
seconds.
Switches the room light ON and OFF.
Press for three (3) seconds to switch the
device ON and OFF.
Table 3-1 - XM670/XM679 Front Panel Keys and Functions
(Continued)
3.2.Use of LEDS
Each LED function is described in Table 3-2:
LEDModeFunction
Compressor and valve regulation
ON
FlashingAnti-short cycle delay enabled
ONDefrost enabled
FlashingDrip time in progress
ONAn alarm is occurring
ONEnergy saving enabled
ONFans enabled (fans are running)
FlashingDoor opened or delay after defrost
ONAuxiliary relay ON
ONMeasurement unit
FlashingProgramming phase
ON
Flashing
Flashing
enabled.
percentage, enter the fast access
menu.
The controller is
ALL mode
The controller is
remote virtual display mode
During the CLOCK modification
(if clock is presen
To see the valve opening
working in
working in
t)
Table 3-1 - XM670
Keys and FunctionsUser Interface • 3
/XM679 Front Panel Keys and Functions
Table 3-2 - LEDs
Page 10
3.3.How to Enter the Fast
Access Menu
1. Press and release the UP button.
2. The First Label will be displayed. Press the UP or
DOWN button to navigate the menu.
1. Enter the programming mode by pressing the SET
and DOWN buttons for a few seconds (wait for the
measurement unit to start blinking).
2. The controller will show the first parameter present
in Pr1.
3.8.How to Enter the
Parameters List PR2
3.4.How to See the MAX
and MIN Temperature
Recorded
1. Press and release the UP button.
2. The First Label will be displayed. Press the UP or
DOWN button to navigate the menu. Search the L°t
label and press SET to see minimum temperature;
search the H°t label and press SET to see maximum
temperature.
3.5.How to See and Modify
the Setpoint
1. Press the SET button for three (3) seconds to show
the setpoint value.
2. The measurement unit starts blinking.
3. To change the setpoint value, press the UP or
DOWN button for 10 seconds.
4. To store the new setpoint value, press the SET key
again or wait 10 seconds.
To access the parameter list in Pr2:
1. Enter the Pr1 lev el . F ol lo w t he st ep s i n Section 3.7.,
How to Enter the Parameters List PR1.
2. Select Pr2 parameter and press the SET key.
3. The PAS flashing message will display, followed
shortly by “0 --” with a flashing zero.
4. Use the UP or DOWN button to input the security
code in the flashing digit. Confirm the security code
by pressing SET. The security code is 321.
5. If the security code is correct, the access to Pr2 is
enabled by pressing SET on the last digit.
3.6.How to Start a Manual
Defrost
Press the DEF key for more than three
(3) seconds to start a manual defrost.
3.7.How to Enter the
Figure 3-2 - Parameters List 2
Another way to enter the programming mode is by
pressing the SET and DOWN buttons for 30 seconds
immediately after switching the controller ON.
NOTE: Each parameter in Pr2 can be removed
or put into Pr1 (user level) by pressing SET +
DOWN buttons. When a parameter is present
in Pr1, the Alarm LED will be display.
Parameters List PR1
To enter the parameter list in Pr1 (user accessible
parameters):
4 • XM679K I&O Manual026-1218 Rev 4
Page 11
3.9.How to Assign a
MODBUS Address
1. To enter the programming mode, press and hold the
SET and DOWN buttons together until the
temperature measurements start blinking.
2. Scroll through the parameters using the UP or
DOWN button until Adr is displayed.
3. Press and hold SET to select Adr.
4. Use the arrow keys to choose the address number of
the device.
5. Press and hold SET again to select the desired
number and save.
6. To exit, press the SET and UP arrow keys together.
3.10.How to Change the
Parameter Value
1. Enter the programming mode.
2. Select the required parameter using the UP or
DOWN button.
3. Press the SET key to display the parameter value
(measurement unit starts blinking).
4. Use the UP or DOWN button to change the value.
5. Press SET to store the new value and move to the
next parameter.
6. To exit, press SET + UP keys or wait 15 seconds
without pressing a key.
NOTE: During the OFF status, the Light and
AUX buttons are active.
NOTE: The set value is stored even when the
time-out expires and ends the procedure.
3.11.ON/OFF Function
By pressing the ON/OFF key, the
controller shows OFF. During the OFF
status, all the relays are switched OFF
and the regulations are stopped; if a
monitoring system is connected, it does not record the
controller data and alarms.
How to Assign a MODBUS AddressUser Interface • 5
Page 12
4Fast Access Menu
This menu contains the lists probes and some values that are automatically evacuated by the board, such as the
superheat and the percentage of valve opening. The values below stands for:
• nP or noP - probe not present or value not evacuate
• Err - value out of range, probe damaged, not connected or incorrectly configured
FAST ACESS MENU
HMFast Access Menu to Clock Settings(If present)
An
SHSuperheatShows the actual superheat value (Only XM679)
oPPValve opening percentageShows the actual opening percentage of the valve (Only XM679)
dP1Probe 1 value displayingShows the temperature measured by probe 1
dP2Probe 2 value displayingShows the temperature measured by probe 2
dP3Probe 3 value displayingShows the temperature measured by probe 3
dP4Probe 4 value displayingShows the temperature measured by probe 4
dP5Probe 5 value displayingShows the temperature measured by probe 5
dP6Probe 6 value displayingShows the temperature measured by probe 6
dPPPressure probe value
rPPRemote pressure probe value
L°tMinimum measured temperatureShows the minimum temperature read by the regulation probe
H°tMaximum measured temperatureShows the maximum temperature read by the regulation probe
dPrVirtual regulation probe valueShows the value measured by the virtual regulation probe
dPdVirtual defrost probe valueShows the value measured by the virtual defrost probe
dPFVirtual fans probe valueShows the value measured by virtual fan probe
rSEReal setpoint
Fast Access to Analog Output
Reading
(If present)
Shows the value of pressure measured by pressure transducer
(Only XM679)
Shows the value of pressure received by remote pressure probe
connected to other XM600 device (Only XM679)
Shows the setpoint used during the energy saving cycle or during
the continuous cycle
Table 4-1 - Fast Access Menu
6 • XM679K I&O Manual026-1218 Rev 4
Page 13
5Section Menu
This menu allows the user to access to a particular
feature of the XM series related to the LAN (Local
Area Network) of controllers. Depending on the
programming of this menu, a single keyboard can
control either the module of the local section of the
LAN or ALL. The possibilities are: LOC: the
keyboard controls and display the value, the status,
and the alarms of the local section of the LAN; and
ALL: the command given by the keyboard are
effective on all the sections of the LAN.
1. Press the UP key for more than three (3) seconds.
2. The label corresponding to the section controlled by
the keyboard will be displayed.
3. Using the UP or DOWN key, select the section you
want to control.
4. Press the SET key to confirm and exit.
5.1.To Set Energy Saving
Times
ILEEnergy Saving cycle
dLEEnergy Saving cycle
ISEEnergy Saving cycle
dSEEnergy Saving cycle
HESTemperature
Table 5-1 - Energy Saving Times Parameters
start during
workdays
l
ength during
workdays
start on ho
l
ength on holidays
increase during the
Ener
lidays
gy Saving cycle
(0 to 23 h 50 min)
During the Energy
Saving cycle, the
setpoint is increased by
the value in HES so
that the operation
setpoint is SET + HES.
(0 to 24 h 00 min) Sets
the duration of the
Energy Saving cycle on
workdays.
(0 to 23h 50 min)
(0 o 24h 00 min)
(-54 to 54°F/ -30 to
°C) Sets the
30
increasing value of the
setpoint during the
Energy Saving cycle.
5.2.To Set Timed Defrost
Parameters
Ld1
Workday
to
defrost start
Ld6
Sd1
Holiday
to
defrost start
Sd
6
Table 5-2 - Timed Defrost Parameters
NOTE: To disable a defrost cycle, set it to nu
(not used). For example, if Ld6=nu, the sixth
defrost cycle is disabled.
(0 to 23h 50 min) These
parameters set the beginning of
the eight programmable defrost
cycles during workdays. For
example, when Ld2=12.4, the
second defrost starts at 12.40
during workdays.
(0 to 23h 50 min) These
parameters set the beginning of
the eight programmable defrost
cycles during holidays. For
example, when Sd2=3.4, the
second defrost starts at 3.40 on
holidays.
To Set Energy Saving TimesSection Menu • 7
Page 14
6Electronic
Expansion Valve
Menu (For Model
XM679 Only)
1. Enter the programming mode by pressing the SET
and DOWN buttons for a few seconds
(measurement unit starts blinking).
2. Press the UP or DOWN key until the controller
displays the EEU label.
3. Press SET. You are now in EEV function menu.
7Controlling Loads
7.1.Solenoid Valve
The regulation is performed based on the temperature
measured by the thermostat probe that can be a
physical probe or a virtual probe obtained by a
weighted average between the two probes (see
Section 8, Parameters List) with a positive
differential from the setpoint. If the temperature
increases and reaches setpoint plus the differential,
the solenoid valve is opened and then it is closed
when the temperature reaches the setpoint value
again.
In case of fault in the thermostat probe, the opening
and closing time of the solenoid valve are configured
by Con and CoF parameters.
7.2.Standards Regulation
and Continuous
Regulation
The regulation can be performed in two ways:
• Standard regulation is reaching the best superheat
via a classic temperature regulation obtained using
hysteresis.
• Continuous regulation permits the use of the valve
to realize a high performance temperature regulation
with a good factor of superheat precision. This only
can be used only in centralized plants and it is
available only with electronic expansion valve by
selecting the CrE=Y parameter.
In any case, the regulation is performed via the PI
regulator that gives the opening percentage to the
valve via PWM modulation explained as follows:
Opening Percentage is obtained from the average of
the Opening Time with respect to the CyP time period
Figure 7-1).
(see
8 • XM679K I&O Manual026-1218 Rev 4
Page 15
Figure 7-1 - Regulation via PI Regulator
Opening percentage is the percentage of the cycle
period where the valve is open. For example, if
CyP=6s (standard value) and the valve is opened at
50%, this means that the valve is opened for three (3)
seconds during the cycle period.
7.2.1. First Kind of Regulation:
Standard Regulation
In this case, the Hy parameter is the differential for
the standard ON/OFF regulation. In this case, the int
parameter is neglected. The regulation follows the
diagram shown in
Figure 7-2 - First Kind of Regulation
Figure 7-2:
7.2.2. Second Kind of Regulation:
Continuous Regulation
(For Model XM679 Only)
In this case, the Hy parameter is the proportional band
of PI in charge of room temperature regulation. It is
advisable to use at least Hy=10°F/ 5.0°C.
The int parameter is the integral time of the same PI
regulator. Increasing the int parameter will cause the
PI regulator to react more slowly, and is true vice
versa. To disable the integral part of regulation, set
int=0.
Figure 7-3 - Second Kind of Regulation
7.3.Defrost
7.3.1. Defrost starting
In any case, the device checks the temperature that is
read by the configured defrost probe before starting
defrost procedure. After that:
• Starting defrost cycles can be operated locally
(manual activation by means of the keyboard or
digital input or end of interval time) or the command
can come from the Master defrost unit of the LAN.
In this case, the controller will operate the defrost
cycle following the parameters it has programmed,
but at the end of the drip time it will wait until all the
other LAN controllers finish their defrost cycle
before the normal regulation of the temperature is
restarted according to the dEM parameter.
• Every time any of the LAN controllers begin a
defrost cycle, it issues the command to the network
making all the other controllers start their own cycle.
This allows a perfect synchronization of the defrost
in the whole multiplexed cabinet according to LMd
parameter.
• By selecting the dPA and dPb probes and changing
the dtP and ddP parameters, defrost can be started
when the difference between the dPA and dPb
probes is lower than dtP for all ddP time. This is
useful to start defrost when a low thermal exchange
is detected. If ddP=0, this function is disabled.
7.3.2. Defrost Ending
•If dPA and dPb are present and d2P=y, the
controller stops the defrost procedure when dPA is
higher than the dtE temperature and dPb is higher
than the dtS temperature.
At the end of defrost, the drip time is controlled
through the Fdt parameter.
DefrostControlling Loads • 9
Page 16
7.4.Fans
7.5.Anti-Sweat Heaters
7.4.1. Control With Relay
The fan control mode is selected by means of the FnC
parameter:
• C-n = running with the solenoid valve, OFF during
defrost
• C-y = running with th1e solenoid valve, ON during
defrost
• O-n = continuous mode, OFF during defrost
• O-y = continuous mode, ON during defrost
An additional parameter FSt provides the setting of
temperature, detected by the evaporator probe, above
which the fans are always OFF. This ensures that air
is circulated only if the temperature is lower than set
in FSt.
7.4.2. Control With Analog Output
(If Present)
The modulating output (trA=rEG) works in a
proportional manner (excluding the first AMt
seconds where the fans speed is the maximum). The
regulation setpoint is relative to the regulation
setpoint and is indicated by the parameter ASr, the
proportional band is always located above the
SET+ASr value and its value is PbA. The fans are at
minimum speed (AMi) when the temperature read by
the fan probe is SET+ASr and the fans are at
maximum speed (AMA) when the temperature is
SET+ASr+PbA.
(If Present)
This control is performed when trA=AC. In this case,
there are two ways to control the anti-sweat heaters:
• Without real dewpoint information: in this case, the
default value for dewpoint is used (SdP parameter).
• Dewpoint received from the XWEB5000 system:
the SdP parameter is overwritten when the valid
value for dewpoint is received from XWEB.
The P4 probe is used to perform the regulation and it
should be placed on the showcase glass. In case of P4
error or if P4 is absent, the output is at AMA value for
the AMt time then the output is at 0 value for the time
255-AMt time performing a simple PWM
modulation.
Figure 7-5 - Anti-Sweat Heaters
7.6.Auxiliary Output
The auxiliary output is switched ON and OFF by
means of the corresponding digital input or by
pressing and releasing the DOWN key.
Figure 7-4 - Control with Analog Output
10 • XM679K I&O Manual026-1218 Rev 4
Page 17
8Parameters List
EEUAccess to EEV submenu (only XM679)
Differential: (1 to 45°F; 0.1 to 25.5°C) This is the intervention differential for setpoint, this value is always
Hy
positive. Solenoid valve Cut IN is Setpoint Plus Differential (Hy). Solenoid valve Cut OUT is when the
temperature reaches the setpoint.
REGULATION
Int
CrE
LSMinimum setpoint limit: (-67°F to SET; -55.0°C to SET) Sets the minimum acceptable value for the setpoint.
USMaximum setpoint limit: (SET to 302°F; SET to 150°C) Set the maximum acceptable value for setpoint.
OdS
ACAnti-short cycle delay: (0 to 60 min) The interval between the solenoid valve stop and the following restart.
CCt
CCS
Con
CoF
Integral time for room temperature regulation (Only XM679): (0 to 255 s) This is the integral time for room
temperature PI regulator. 0= no integral action.
Continuous regulation activation (Only XM679): (n to Y) n= standard regulation; Y= continuous regulation.
Use it only in centralized plants.
Outputs activation delay at start up: (0 to 255 min) This function is enabled at the initial start up of the device
and inhibits any output activation for the time set in the parameter. (AUX and Light can work)
Compressor ON time during continuous cycle: (0.0 to 24.0h; resolution 10min) Allows to set the length of
the continuous cycle: compressor stays on without interruption for the CCt time. Can be used, for instance,
when the room is filled with new products.
Setpoint for continuous cycle: (-67 to 302°F / -55 to 150°C) it sets the setpoint used during the continuous
cycle.
Solenoid valve ON time with faulty probe: (0 to 255 min) The time during which the solenoid valve is active
in case of faulty thermostat probe. With COn=0 solenoid valve is always OFF.
Solenoid valve OFF time with faulty probe: (0 to 255 min) time during which the solenoid valve is off in case
of faulty thermostat probe. With COF=0 solenoid valve is always active.
DISPLAY
CF
PrU
PMU
PMd
rESResolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display
Lod
Table 8-1 - XM670 to XM679 Parameters List
Auxiliary OutputParameters List • 11
Temperature measurement unit: °C = Celsius; °F = Fahrenheit. CAUTION! When the measurement unit is
changed the parameters with temperature values have to be checked.
Pressure mode: (rEL or AbS) defines the mode to use the pressure. CAUTION! the setting of PrU is used for
all the pressure parameters. If PrU = rEL all pressure parameters are in relative pressure unit, if PrU = AbS
all pressure parameters are in absolute pressure unit. (Only XM679)
Pressure measurement unit: (bAr - PSI - MPA) it selects the pressure measurement units. MPA= the value of
pressure measured by kPA*10. (Only XM679)
Way of displaying pressure: (tEM - PrE) it permits showing the value measured by pressure probe with
tEM= temperature or by PrE= pressure (Only XM679)
Device display: (nP; P1; P2, P3, P4, P5, P6, tEr, dEF) it selects which probe is displayed by the device. P1,
P2, P3, P4, P5, P6, tEr= virtual probe for thermostat, dEF= virtual probe for defrost.
Page 18
red
Remote display: (nP; P1; P2, P3, P4, P5, P6, tEr, dEF) it selects which probe is displayed by the X-REP. P1,
P2, P3, P4, P5, P6, tEr= virtual probe for thermostat, dEF= virtual probe for defrost.
dLy
rPA
rPb
rPE
Display delay: (0 to 24.0 m; resolution 10s) when the temperature increases, the display is updated of
1 °F/1°C after this time.
Regulation probe A: (nP; P1; P2, P3, P4, P5) first probe used to regulate room temperature. If rPA = nP the
regulation is performed with real value of rPb.
Regulation probe B: (nP; P1; P2, P3, P4, P5) second probe used to regulate room temperature. If rPb = nP
the regulation is performed with real value of rPA
Regulation virtual probe percentage: (0 to 100%) it defines the percentage of the rPA respect to rPb. The value
used to regulate room temperature is obtained by: value_for_room = (rPA*rPE + rPb*(100-rPE))/100
ELECTRONIC EXPANSION VALVE SUBMENU (Only XM679)
FtY
Kind of gas (R22, 134, 404, 407, 410, 507,CO2): Type of gas used by plant. Fundamental parameter for
correct functioning of all system.
SSHSuperheat setpoint: [1°F to 45°F] [0.1°C to 25.5°C] This is the value used to regulate superheat.
CyPCycle Period: (1 to 15s) Allows to set cycle time
PbProportional band: (1 to 108°F / 0.1 to 60.0) PI proportional band
rSBand Offset: (-21 to 21°F / -12.0 to 12.0°C) PI band offset
inCIntegration time: (0 to 255s) PI integration time
PEO
Probe Error opening percentage: (0 to 100%) if a temporary probe error occurs, valve opening percentage is
PEo until PEd time is elapsed.
Probe Error delay before stopping regulation: (0 to 239 sec. - On = unlimited) if probe error duration is bigger
PEd
than PEd then valve totally closes. Pf message displays. If PEd = On valve opening is PEo until probe error
finishes.
OPE
SFd
OPd
Pdd
MnF
dCL
Start opening Percentage: (0 to 100%) Valve opening percentage when start function is active. This phase
duration is SFd time.
Start Function duration: (0.0 to 42.0 min: resolution 10s) Sets start function duration and post-defrost
duration. During this phase the alarms are neglected.
Opening Percentage after defrost phase: (0 to 100%) Opening valve percentage when after defrost function
is active. This phase duration is Pdd time.
Post Defrost Function duration: (0.0 to 42.0 min: resolution 10s) Sets start function duration and post-defrost
duration. During this phase the alarms are neglected.
Maximum opening percentage at normal Functioning: (0 to 100%) during regulation it sets the maximum
valve opening percentage.
Delay before stopping valve regulation: (0 to 255s) When the cooling request goes off, the electronic valve
regulation can go on for the dCL time in order to prevent uncontrolled superheat variation.
Forced opening percentage: (0 to 100% - nu) it permits to force the valve opening to the specified value. This
Fot
value overwrites the value calculated by PID algorithm. CAUTION! To obtain the correct superheat
regulation you have to set Fot = nu.
Type of Pressure Transducer: (PP - LAn) it sets type of pressure transducer to use: PP= 4 to 20mA pressure
tPP
transducer or ratiometric transducer 0 to 5V depending on P5C parameter, LAn= the pressure signal arrives
from another XM600. Referred to Pb5
Table 8-1 - XM670 to XM679 Parameters List
12 • XM679K I&O Manual026-1218 Rev 4
Page 19
PA4
Probe value At 4mA or At 0V: (-1.0 to P20 bar / -14 to PSI / -10 to P20 kPA*10) pressure value measured by
probe at 4mA or at 0V (related to PrM parameter) Referred to Pb5
P20
Probe value 20mA or At 5V: (PA4 to 50.0 bar / 725 psi / 500 kPA*10) pressure value measured by probe at
20mA or at 5V (related to PrM parameter) Referred to Pb5
Lower Pressure Limit for superheat regulation: (PA4 to P20 bar / psi / kPA*10) when suction pressure comes
LPL
down to LPL the regulation is performed with a LPL fixed value for pressure, when pressure comes back to
LPL the normal pressure value is used. (related to PrM parameter)
MOP
LOP
Maximum Operating Pressure threshold: (PA4 to P20 bar / psi / kPA*10) if suction pressure exceeds
maximum operating pressure value, device signals situation with MOP alarm. (related to PrM parameter)
Lowest Operating Pressure threshold: (PA4 to P20 bar / psi / kPA*10) If the suction pressure comes down to
this value, a low pressure alarm is signaled with LOP alarm. (related to PrM parameter)
delta MOP-LOP: (0 to 100%) When a MOP alarm occurs, the valve will close of the dML percentage every
dML
cycle period until MOP alarm is active. When LOP occurs, the valve will open of the dML percentage every
cycle period until LOP alarm is active.
MSH
LSH
Maximum Superheat alarm: (LSH to 144°F / LSH to 80.0°C) When the superheat exceeds this value, a high
superheat alarm is signaled after interval SHd.
Lowest Superheat alarm: (0 to MSH °F / 0.0 to MSH °C) When the superheat goes down to this value, a low
superheat alarm is signaled after interval SHd.
SHySuperheat alarm Hysteresis: (1 to 45°F / 0.1 to 25.5°C) Hysteresis for superheat alarm deactivation.
SHd
FrC
Superheat alarm activation delay: (0.0 to 42.0 min: resolution 10s) When a superheat alarm occurs, the time
SHd have to pass before signaling the alarm.
Fast-recovery Constant: (0 to 100 s) permits to increase integral time when SH is below the setpoint. If FrC=0
fast recovery function is disabled.
DEFROST
dPA
dPb
dPE
defrost Probe A: (nP; P1; P2, P3, P4, P5) first probe used for defrost. If rPA = nP the regulation is performed
with real value of dPb.
defrost Probe B: (nP; P1; P2, P3, P4, P5) second probe used for defrost. If rPB = nP the regulation is
performed with real value of dPA.
defrost virtual probe percentage: (0 to 100%) it defines the percentage of the dPA respect to dPb. The value
used to regulate room temperature is obtained by: value_for_defrost= (dPA*dPE + dPb*(100-dPE))/100.
tdF Defrost type: (EL - in) EL = electrical heater; in = hot gas.
EdFDefrost mode: (in) In= interval defrost activation with idf.
Srt
Heater setpoint during defrost: (-67 to 302°F; -55.0 to 150.0°C) if tdF=EL during the defrost the defrost relay
perform an ON/OFF regulation with Srt as setpoint.
HyrDifferential for heater: (1°F to 45°F, 0.1°C to 25.5°C) the differential for heater
Time out for heater: 0 to 255 (min.) if the defrost probe temperature is bigger than Srt for all tod time the
tod
defrost ends although the defrost probe temperature is lower than dtE or dtS. It permits to reduce defrost
duration.
dtP
Minimum temperature difference to start defrost: [1°F to 90°F] [0.1°C to 50.0°C] if the difference between
the two defrost probes stays lower than dtP for all ddP time the defrost is activated.
ddPDelay before starting defrost (related to dtP): (0 to 60 min) delay related to dtP.
Table 8-1 - XM670 to XM679 Parameters List
Auxiliary OutputParameters List • 13
Page 20
d2P
dtE
dtS
Defrost with two probes: (n - Y) n= only the dPA probe is used to defrost management; Y= defrost is managed
with dPA probe and dPb probe. Defrost can performed only if both probe value are lower than dtE for dPA
probe and dtS for dPb probe.
Defrost termination temperature (Probe A): (-67 to 122°F; -55.0 to 50.0°C) (Enabled only when the
evaporator probe is present) sets the temperature measured by the evaporator probe dPA which causes the
end of defrost.
Defrost termination temperature (Probe B): (-67 to 122°F; -55.0 to 50.0°C) (Enabled only when the
evaporator probe is present) sets the temperature measured by the evaporator probe dPb which causes the end
of defrost.
IdF
MdF
dSd
dFd
dAd
Interval between defrosts: (0 to 120h) Determines the time interval between the beginning of two defrost
cycles.
Maximum duration of defrost: (0 to 255 min) When dPA and dPb aren't present, it sets the defrost duration,
otherwise it sets the maximum duration for defrost.
Start defrost delay: (0 to 255 min) This is useful when different defrost start times are necessary to avoid
overloading the plant.
Display during defrost: rt = real temperature; it = temperature reading at the defrost start; Set = setpoint;
dEF = “dEF” label.
Defrost display time out: (0 to 255 min) Sets the maximum time between the end of defrost and the restarting
of the real room temperature display.
Drain down time: (0 to 255 min.) time interval between reaching defrost termination temperature and the
Fdt
restoring of the control's normal operation. This time allows the evaporator to eliminate water drops that
might have formed due to defrost.
dPo First defrost after start-up: y = Immediately; n = after the IdF time
dAF
Defrost delay after continuous cycle: (0 to 23.5h) time interval between the end of the fast freezing cycle and
the following defrost related to it.
FAN
FPA
FPB
Fan probe A: (nP; P1; P2, P3, P4, P5) first probe used for fan. If FPA = nP the regulation is performed with
real value of FPB.
Fan probe B: (nP; P1; P2, P3, P4, P5) second probe used for defrost. If FPB = nP the regulation is performed
with real value of FPB.
FPE
Fan virtual probe percentage: (0 to 100%) Defines the percentage of the FPA with respect to FPb. The value
used to regulate room temperature is obtained by: value_for_defrost= (FPA*FPE + FPb*(100-FPE))/100.
Fan operating mode: C-n = running with the solenoid valve, OFF during the defrost; C-y = running with the
FnC
solenoid valve, ON during the defrost; O-n = continuous mode, OFF during the defrost; O-y = continuous
mode, ON during the defrost.
Fnd Fan delay after defrost: (0 to 255 min) The time interval between the defrost end and evaporator fans start.
Temperature differential avoiding short cycles of fans (0°F to 90°F; 0.0°C to 50.0°C) If the difference of
FCt
temperature between the evaporator and the room probes is more than the value of the Fct parameter, the fans
are switched on.
FSt
Table 8-1 - XM670 to XM679 Parameters List
14 • XM679K I&O Manual026-1218 Rev 4
Fan stop temperature: (-58 to 230°F; -50 to 110°C) setting of temperature, detected by evaporator probe,
above which the fan is always OFF.
Page 21
FHy
Differential to restart fan: (1°F to 45°F) (0.1°C to 25.5°C) when stopped, fan restarts when fan probe reaches
FSt-FHy temperature.
FodFan activation time after defrost: (0 to 255 min.) it forces fan activation for indicated time.
Fan ON time: (0 to 15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). Sets the
Fon
evaporator fan ON cycling time when the compressor is off. With Fon =0 and FoF =0 the fan are always off,
with Fon=0 and FoF =0 the fan are always off.
Fan OFF time: (0 to 15 min) with Fnc = C_n or C_y, (fan activated in parallel with compressor). Sets the
FoF
evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF =0 the fans are always off,
with Fon=0 and FoF =0 the fans are always off.
MODULATING OUTPUT (AnOUT) If Present
Kind of regulation with PWM output: (UAL - rEG - AC) it selects the functioning for the PWM output if
trA
CoM is not equal to OA7. UAL= the output is at FSA value; rEG= the output is regulated with fan algorithm
described in fan section; AC= anti-sweat heaters control (require the XWEB5000 system).
SOAFixed value for analog output: (0 to 100%) value for the output if trA = UAL.
SdP
ASr
Default value for Dew point: (-67 to 122°F; -55.0 to 50.0°C) default value of dew point used when there is
no supervising system (XWEB5000). Used only when trA=AC.
Dew-point offset (trA=AC) / Differential for modulating fan regulation (trA=rEG): (-45°F to 45°F)
(-25.5°C to 25.5°C).
PbADifferential for anti-sweat heaters: (1°F to 45°F) (0.1°C to 25.5°C)
AMiMinimum value for analog output: (0 to AMA)
AMAMaximum value for analog output: (Ami to 100)
AMt
Anti-sweat heaters cycle period (trA=AC)/ Time with fan at maximum speed (trA=rEG): (0 to 255 s) when
the fan starts, during this time the fan is at maximum speed.
ALARMS
rAL
ALC
ALU
ALL
AHy
Probe for temperature alarm: (nP - P1 - P2 - P3 - P4 - P5 - tEr) Selects the probe used to signal alarm
temperature.
Temperature alarm configuration: rE = High and Low alarms related to Setpoint; Ab = High and low alarms
related to the absolute temperature.
High temperature alarm setting: (ALC= rE, 0 to 90°F or 50°C / ALC= Ab, ALL to 302°F or 150°C) when
this temperature is reached and after the ALd delay time the HA alarm is enabled.
Low temperature alarm setting: (ALC = rE, 0 to 90°F or 50 °C / ALC = Ab, - 67°F or - 55°C to ALU) when
this temperature is reached and after the ALd delay time, the LA alarm is enabled.
Differential for temperature alarm: (1°F to 45°F / 0.1°C to 25.5°C) Intervention differential for recovery of
temperature alarm.
ALd
dLU
dLL
Table 8-1 - XM670 to XM679 Parameters List
Auxiliary OutputParameters List • 15
Temperature alarm delay: (0 to 255 min) The time interval between the detection of an alarm condition and
the corresponding alarm signaling.
High temperature alarm (defrost probe): (ALC= rE, 0 to 90°F or 50°C / ALC= Ab, ALL to 302°F or 150°C)
When this temperature is reached and after the ddA delay time, the HAd alarm is enabled.
Low temperature alarm (defrost probe): (ALC = rE, 0 to 90°F or 50 ° C / ALC = Ab, - 67°F or - 55°C to ALU)
when this temperature is reached and after the ALd delay time, the LAd alarm is enabled.
Page 22
dAH
Differential for temperature alarm (defrost probe): (1°F to 45°F / 0.1°C to 25.5°C) Intervention differential
for recovery of temperature alarm.
ddA
FLU
FLL
FAH
FAd
dAO
EdA
Temperature alarm delay (defrost probe): (0 to 255 min) time interval between the detection of an alarm
condition and the corresponding alarm signaling.
High temperature alarm (defrost probe): (ALC= rE, 0 to 90°F or 50°C / ALC= Ab, ALL to 302°F or 150°C)
when this temperature is reached and after the FAd delay time the HAF alarm is enabled.
Low temperature alarm (defrost probe): (ALC = rE, 0 to 90°F or 50°C / ALC = Ab, - 67°F or - 55°C to ALU)
when this temperature is reached and after the FAd delay time, the LAF alarm is enabled.
Differential for temperature alarm (defrost probe): (1°F to 45°F / 0.1°C to 25.5°C) Intervention differential
for recovery of temperature alarm.
Temperature alarm delay (defrost probe): (0 to 255 min) time interval between the detection of an alarm
condition and the corresponding alarm signaling.
Delay of temperature alarm at start-up: (0min to 23h 50min) The time interval between the detection of the
temperature alarm condition after the device power on and the alarm signaling.
Alarm delay at the end of defrost: (0 to 255 min) Time interval between the detection of the temperature alarm
condition at the end of defrost and the alarm signaling.
dotTemperature alarm exclusion after door open
Sti
Std
Stop regulation interval (Only XM679): (0.0 to 24.0 hours: tens of minutes) After regulating continuously for
Sti time, the valve closes for Std time to prevent ice from forming.
Stop duration (Only XM679): (0 to 60 min.) Defines the stop regulation time after Sti. During this stop
display shows StP message.
Sixth relay configuration (CPr-dEF-Fan-ALr-LiG-AUS-db-OnF): CPr= relay works as a compressor or
OA6
solenoid valve relay; dEF= relay works as defrost relay; Fan= relay works as a Fan relay; ALr= activation
with alarm conditions; LiG= light activation; AUS= auxiliary relay, it can be switched ON/OFF also by key;
db= deadband regulation (not compatible with CrE = y); OnF= ON/OFF functioning.
OPTIONAL OUTPUT (AnOUT) If Present
Modulating output configuration (if CoM=0A7): (CPr - dEF - FAn - ALr - LiG - AUS - db) it selects the
OA7
functioning of the modulating output in case of CoM=OA7: CPr= compressor; dEF= defrost; FAn= Fan;
Alr= Alarm; LiG= Light; AUS= auxiliary; db= neutral zone (not available with CrE=Y)
Type of functioning modulating output:
CoM
For models with PWM / O.C. output -> PM5= PWM 50Hz; PM6= PWM 60Hz; OA7= two state, it can be
used as an open collector output
For models with 4 to 20mA / 0 to 10V output -> Cur= 4 to 20mA current output; tEn= 0 to 10V voltage output
AOPAlarm relay polarity: cL= normally closed; oP= normally opened
iAU
Auxiliary output is unrelated to ON/OFF device status: n= if the device is switched off also the auxiliary
output is switched off; Y= the auxiliary output state is unrelated to the ON/OFF device status.
DIGITAL INPUTS
i1P
Table 8-1 - XM670 to XM679 Parameters List
Digital input 1 polarity: (cL - oP) CL: the digital input is activated by closing the contact; OP: the digital input
is activated by opening the contact.
16 • XM679K I&O Manual026-1218 Rev 4
Page 23
i1F
d1d
Digital input 1 function: (EAL - bAL - PAL - dor - dEF - AUS - LiG - OnF - Htr - FHU - ES - Hdy) EAL=
external alarm; bAL= serious external alarm; PAL= pressure switch activation; dor= door open; dEF= defrost
activation; AUS= auxiliary activation; LiG= light activation; OnF= switch on/off the device; Htr= change
type of action; FHU= not used; ES= activate energy saving; Hdy= activate holiday function
Time interval/delay for digital input alarm: (0 to 255 min.) Time interval to calculate the number of the
pressure switch activation when i1F=PAL. If I1F=EAL or bAL (external alarms), “d1d” parameter defines
the time delay between the detection and the successive signaling of the alarm. If i1F=dor this is the delay to
activate door open alarm.
i2P
i2F
d2d
i3P
i3F
d3d
nPS
Digital input 2 polarity: (cL - oP) CL: the digital input is activated by closing the contact; OP: the digital input
is activated by opening the contact.
Digital input 2 function: (EAL - bAL - PAL - dor - dEF - AUS - LiG - OnF - Htr - FHU - ES - Hdy) EAL=
external alarm; bAL= serious external alarm; PAL= pressure switch activation; dor= door open; dEF= defrost
activation; AUS= auxiliary activation; LiG= light activation; OnF= switch on/off the device; Htr= change
type of action; FHU= not used; ES= activate energy saving; Hdy= activate holiday function
Time interval/delay for digital input alarm: (0 to 255 min.) Time interval to calculate the number of the
pressure switch activation when i2F=PAL. If I2F=EAL or bAL (external alarms), “d2d”parameter defines the
time delay between the detection and the successive signaling of the alarm. If i2F=dor this is the delay to
activate door open alarm.
Digital input 3 polarity: (cL - oP) CL: the digital input is activated by closing the contact; OP: the digital input
is activated by opening the contact.
Digital input 3 function: (EAL - bAL - PAL - dor - dEF - AUS - LiG - OnF - Htr - FHU - ES - Hdy) EAL=
external alarm; bAL= serious external alarm; PAL= pressure switch activation; dor= door open; dEF= defrost
activation; AUS= auxiliary activation; LiG= light activation; OnF= switch on/off the device; Htr= change
type of action; FHU= not used; ES= activate energy saving; Hdy= activate holiday function
Time interval/delay for digital input alarm: (0 to 255 min.) Time interval to calculate the number of the
pressure switch activation when i3F=PAL. If i3F=EAL or bAL (external alarms), “d3d” parameter defines
the time delay between the detection and the successive signaling of the alarm. If i3F=dor this is the delay to
activate door open alarm.
Pressure switch number: (0 to 15) Number of activation of the pressure switch, during the “d#d” interval,
before signaling the alarm event (I2F= PAL). If the nPS activation in the did time is reached, switch off and
on the device to restart normal regulation.
odc
Compressor and fan status when open door: no = normal; Fan = Fan OFF; CPr = Compressor OFF; F_C =
Compressor and fan OFF.
Temperature increase during the Energy Saving cycle: (-54 to 54°F / -30 to 30°C) sets the increasing value
of the setpoint during the Energy Saving cycle.
Energy saving activation when light is switched off: (n to Y) n= function disabled; Y= energy saving is
activated when the light is switched off and vice versa.
LAN MANAGEMENT
LMd
Table 8-1 - XM670 to XM679 Parameters List
Auxiliary OutputParameters List • 17
Defrost synchronization: y= the section send a command to start defrost to other controllers, n= the section
don't send a global defrost command
Page 24
dEMType of end defrost: n= the of the LAN defrost are independent; y= the end of the defrost are synchronized
LSP
LdS
LOF
LLi
LAU
LES
LSd
LPP
L.A.N. set-point synchronization: y= the section set-point, when modified, is updated to the same value on
all the other sections; n= the set-point value is modified only in the local section
L.A.N. display synchronization: y= the value displayed by the section is sent to all the other sections; n= the
set-point value is modified only in the local section
L.A.N. On/Off synchronization this parameter states if the On/Off command of the section will act on all the
other ones too: y= the On/Off command is sent to all the other sections; n= the On/Off command acts only in
the local section
L.A.N. light synchronization this parameter states if the light command of the section will act on all the other
ones too: y= the light command is sent to all the other sections; n= the light command acts only in the local
section
L.A.N. AUX output synchronization this parameter states if the AUX command of the section will act on all
the other ones too: y= the light command is sent to all the other sections; n= the light command acts only in
the local section
L.A.N. energy saving synchronization this parameter states if the energy saving command of the section will
act on all the other ones too: y= the Energy Saving command is sent to all the other sections; n= the Energy
Saving command acts only in the local section
Remote probe display: this parameter states if the section has to display the local probe value or the value
coming from another section: y= the displayed value is the one coming from another section (which has
parameter LdS = y); n= the displayed value is the local probe one.
Remote pressure probe: n= the value of pressure probe is read from local probe; Y= the value of pressure
probe is sent via LAN.
StM
Solenoid activation via LAN: n= not used; Y= a generic cooling requests from LAN activate the solenoid
valve connected to compressor relay.
Probe 6 calibration: (-21 to 21°F/ -12.0 to 12.0°C) allows to adjust possible offset of the probe 6.
(Only XM679)
Table 8-1 - XM670 to XM679 Parameters List
18 • XM679K I&O Manual026-1218 Rev 4
Page 25
SERVICE - READ ONLY
CLtCooling time percentage: it shows the effective cooling time calculated by XM600 during regulation
tMdTime to next defrost: it shows time before the next defrost if interval defrost is selected
LSnL.A.N. section number (1 to 5) Shows the number of sections available in the L.A.N.
Lan
Adr
L.A.N. serial address (1 to LSn) Identifies the device address inside local network of multiplexed cabinet
controller.
RS485 serial address (1 to 247): Identifies the device address when connected to a MODBUS compatible
monitoring system.
Rel Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the dIXEL parameter map.
Pr2 Access to the protected parameter list (read only)
Table 8-1 - XM670 to XM679 Parameters List
Auxiliary OutputParameters List • 19
Page 26
9Digital Inputs
The XM600 series of controllers can support up to
three (3) configurable digital inputs that are free of
voltage contact (depending on the models). They are
configurable via i#F parameter.
1. The terminals [30] to
[33] are free of voltage.
2. Use shielded cable for
distances higher than
one meter.
For each input, the following
has to be configured: the
polarity of activation, the
function of the input, and the
delay of signaling. The
parameters to perform this
configuration are i1P, i1F, i1d respectively for polarity,
functioning, and delay.
9.4.Door Switch Input (dor)
This input signals the door status and the
corresponding relay output status through the odc
parameter: no = normal (any change); Fan = Fan
OFF; CPr = Compressor OFF; F_C = Compressor
and fan OFF. Since the door is opened, after the delay
time set through parameter d#d, the door alarm is
enabled, the display shows the message dA, and the
regulation restarts after rrd time. The alarm stops as
soon as the external digital input is disabled again.
With the door open, the high and low temperature
alarms are disabled.
9.5.Start Defrost (dEF)
A defrost will start if the right conditions exist. After
the defrost is finished, normal regulation will restart
only if the digital input is disabled; otherwise, the
controller will wait until the MdF safety time is
expired.
9.1.Generic Alarm (EAL)
As soon as the digital input is activated, the controller
will wait for the did time delay before signaling the
EAL alarm message. The outputs status don’t change.
The alarm will stop as soon as the digital input is
deactivated.
9.2.Serious Alarm Mode
(bAL)
When the digital input is activated, the controller will
wait for the did time delay before signaling the bAL
alarm message. The relay outputs are switched OFF.
The alarm will stop as soon as the digital input is
deactivated.
9.3.Pressure Switch (PAL)
If the pressure switch has reached the number of
activation of the nPS parameter during the interval
time set by the d#d parameter, the CA pressure alarm
message will be displayed. The compressor and the
regulation are stopped. When the digital input is ON
the compressor is always OFF.
in the d#d time is reached, switch the controller OFF
and ON to restart normal regulation.
If the nPS activation
9.6.Relay Aux Actuation
(AUS)
This function enables the auxiliary relay to be turned
ON and OFF by using the digital input as external
switch.
9.7.Relay Light Actuation
(LiG)
This function enables the light relay to be turned ON
and OFF by using the digital input as external switch.
9.8.Remote ON/OFF (OnF)
This function switches the controller ON and OFF.
9.9.Kind of Action (Htr)
This function enables the change in the kind of
regulation: from cooling to heating and vice versa.
20 • XM679K I&O Manual026-1218 Rev 4
Page 27
9.10.FHU (Not Used)
This function enables the change in the kind of
regulation: from cooling to heating and vice versa.
9.11.Energy Saving Input
(ES)
The Energy Saving function allows you to change the
setpoint value as the result of the SET+ HES
(parameter) sum. This function is enabled until the
digital input is activated.
9.12.Configurable Input Holiday Function (HDY)
In Holiday function, the Energy Saving and defrost
cycles follow holiday times (Sd1…Sd6).
10Installation and
Mounting
The XM679 can operate without any user interface,
but normal application is with the CX660 keyboard.
The CX660 keyboard should be mounted on a vertical
panel, in a 29 mm x 71 mm hole, and secured using
the special bracket supplied.
9.13.Digital Inputs Polarity
The digital inputs polarity depends on the I#P
parameters: CL (the digital input is activated by
closing the contact) and OP (the digital input is
activated by opening the contact).
Figure 10-1 - Installation and Mounting of CX660 Keyboard
The temperature range allowed for correct operation
is 0 to 60°C. Avoid places subject to strong
vibrations, corrosive gases, excessive dirt, or
humidity. The same recommendations apply to
probes. Allow air to circulate through the cooling
holes.
Figure 10-2 - CX660 Keyboard Dimensions
FHU (Not Used)Installation and Mounting • 21
Page 28
11Electrical
13How to Use the
Connections
The XM670/XM679 controllers come with a screw
terminal block to connect cables with a cross section
up to 1.6 mm
RS485, the LAN, the probes, the digital inputs, and
the keyboard. Other inputs, power supply, and relay
connections are provided with a Faston connection
(5.0 mm). Heat-resistant cables have to be used.
Before connecting cables, verify that the power
supply complies with the controller’s requirements.
Separate the probe cables from the power supply
cables, from the outputs and the power connections.
Do not exceed the maximum current allowed on each
relay; in case of heavier loads, use a suitable external
relay.
2
for all the low voltage connections: the
NOTE: Maximum current allowed for all the
load is 16A.
11.1.Probe Connections
The probes should be mounted with the bulb upwards
to prevent damages due to casual liquid infiltration. It
is recommended that the thermostat probe be placed
away from air streams to measure the average room
temperature correctly. Place the defrost termination
probe among the evaporator fans in the coldest place,
(where most ice is formed) and far from heaters or
from the warmest place during defrost to prevent
premature defrost termination.
12RS485 Serial Line
Each XM670/XM679 controller has a direct RS485
connection that enables the controller to be linked to
a network line that is MODBUS-RTU compatible
with all monitoring systems.
Hot Key
XM controllers can download or upload the
parameter list from its own non-volatile internal
memory to the Hot Key and vice-versa through a
5-pin connector. The Hot Key will not change the
Adr.
13.1.Download (From the
Hotkey to the Device)
1. Turn OFF the controller by pressing the on/off
buttonfor five (5) seconds. OFF will display.
Insert the Hot Key into the 5-pin connector
labeled HOT-KEY, and then turn the controller
back ON by pressing the on/off button again for
five (5) seconds. The normal temperature value
will display to indicate the controller is ON.
2. The parameter list of the Hot Key is downloaded
into the controller memory automatically and
doL will display. After 10 seconds, the controller
will start working with the new parameters.
3. End will display at the end of the data transfer
phase if the controller is programmed correctly.
Err will display if there is an error or failure in
programming.
• End = correct programming. This means the
controller will start regularly with the new
programming.
• Err = failed programming. In this case, turn the
controller OFF and then ON if you want to restart
the download again or remove the Hot Key to abort
the operation.
4. Remove the Hot Key.
Note: The procedure may fail if the firmware version
and the controller models are different.
22 • XM679K I&O Manual026-1218 Rev 4
Page 29
13.2.Upload (From the
Device to the Hotkey)
1. When the XM controller is ON, insert the Hot
Key into the 5-pin connector labeled HOT-KEY.
2. Press and release the up arrow button.
3. The upload will begin, and UPL will blink on the
display. End will display at the end of the data
transfer phase if a successful upload has
occurred. Err will display if there is an error or
failure in programming.
• End = correct programming.
• Err = failed programming. In this case, press the
SET key if you want to restart the programming
again or remove the unprogrammed Hot Key.
4. Remove the Hot Key.
Note: The upload procedure will overwrite everything
previously uploaded from the last Hot Key upload.
Upload (From the Device to the Hotkey)How to Use the Hot Key • 23
Page 30
14Alarm Signals
MessageCauseOutputs
KEYBOARD
No display: the keyboard is trying to
nod
PONKeyboard enabledOutputs unchanged
POFKeyboard lockedOutputs unchanged
rstAlarm resetAlarm relay reset
nOP, nP, nAProbe not presentCompressor output according to parameter Con and COF
noL
P1First probe failureCompressor output according to parameters Con and COF
P2Second probe failureDefrost end is timed
P3Third probe failureOutputs unchanged
P4Fourth probe failureOutputs unchanged
P5Fifth probe failureOutputs unchanged
P6Sixth probe failureOutputs unchanged
PPF
CPF
HAMaximum temperature alarmOutputs unchanged
LAMinimum temperature alarmOutputs unchanged
HAdDefrost high temperatureOutputs unchanged
LAdDefrost low temperatureOutputs unchanged
FAdDefrost low temperatureOutputs unchanged
HAFFan high temperatureOutputs unchanged
LAFFan high temperatureOutputs unchanged
StP
PALLock due to pressure switchAll outputs OFF
dADoor openCompressor and fans restarts according to rrd and odc
EAExternal alarmOutputs unchanged
CASerious external alarm (i1F=bAL)All outputs OFF
LOPMinimum operating pressure reachedAccording to dML
MOPMaximum operating pressure reachedAccording to dML
work with another board that is not
working or not present.
They keyboard is not able to
communicate with the XM679K.
ALARM FROM PROBE INPUT
PPF is displayed by slaves of pressure
that don’t receive the value of pressure.
CPF is displayed when the remote
probe 4 is not working,
TEMPERATURE ALARM
Stop due to regulation pauses
(Sti and Std parameters)
DIGITAL INPUT ALARM
ELECTRONIC VALVE ALARM
Press the UP arrow for three (3) seconds. Enter the SEC
menu, and select LOC entry.
Verify the connection. Call the service.
The percentage of the valve opening is fixed at PEO value.
The percentage of the valve opening is fixed at PEO value.
Compressor and valve OFF
Table 14-1 - Alarm Signals
24 • XM679K I&O Manual026-1218 Rev 4
Page 31
LSHMinimum superheat alarmValve closed
MSHMaximum superheat alarmOutputs unchanged
HSHMinimum superheat alarmOutputs changed.
CLOCK ALARM
rtCClock settings lost.
Defrost will be performed with ldF until the settings of
RTC has been restored.
rtFClock damaged.Defrost will be performed with ldF.
Upload (From the Device to the Hotkey)Alarm Signals • 25
Page 32
14.1.EE Alarm
The controllers are provided with an internal check
for data integrity. Alarm EE flashes when a failure in
the memory data occurs. In such cases, the alarm
output is enabled.
14.2.Alarm Recovery
Probe alarms, P1 (probe1 faulty), P2, P3, P4, P5, and
P6 automatically stop 10 seconds after the probe
restarts normal operation. Check connections before
replacing the probe. Temperature alarms, HA, LA,
HAd, LAd, HAF, and LAF automatically stop as
soon as the thermostat temperature returns to normal
values or when the defrost starts. External alarms
EAL and bAL stop as soon as the external digital
input is disabled.
26 • XM679K I&O Manual026-1218 Rev 4
Page 33
15Technical Data
CX660 KEYBOARD
HousingSelf-extinguishing ABS
Case:
Dimensions
Protection
Power SupplyFrom XM600 power module
Display3 digits, red LED, 14.2 mm H
Optional OutputBuzzer
Case8 DIN
Connections
Power Supply
Power Absorption9VA max
InputsUp to 6 NTC/PTC/Pt1000 probes
Digital InputsThree (3) voltage-free
Relay Outputs
(Total current on loads MAX 16A)
See Section 16, UL Ratings.
Va lv e O u tp uta.c. output up to 30W (Only XM679)
Optional Output (AnOUT)
Depending on the model
Serial OutputRS485 with MODBUS-RTU and LAN
Data StoringOn the volatile memory (EEPROM)
Kind of Action1B
Pollution GradeNormal
Software ClassA
Operating Temperature32 to 140°F (0 to 60°C)
Storage Temperature-13 to 140°F (-25°C to 60°C)
Relative Humidity20 to 85% (no condensing)
Front: 35 mm x 77 mm
Depth: 18 mm
Panel Mount: 29 mm x 71 mm panel cut-out
IP20
Frontal: IP65
POWER MODULES
Screw terminal block ≤ 1.6 mm2 heat-resistant wiring and 5.0 mm
Faston
Depending on the model:
12VAC – 24VAC - 110VAC ± 10% - 230VAC ± 10% or 90 to 230VAC
with switching power supply
PWM/ Open Collector outputs: PWM or 12VDC max 40mA
Pollution Degree - 2 (Normally only non-conductive pollution. However, a temporary conductivity caused by condensation
may be expected.)
28 • XM679K I&O Manual026-1218 Rev 4
g temperature 60°C
Page 35
17Connections
17.1.E2 to XM Device Communication Recommendations
Baud Rate: 19.2K Baud (9600 baud is not recommended for E2 to XM device communications).
Cable Length: Belden 8761 or equivalent (1200ft or less).
I/O Net Biasing: Up to 25 XM6xx devices can be connected to each E2 COM2A, COM2B, COM4A, COM4B
and COM6 port. Contact Technical Service if you have more than 25 devices per COM segment.
17.1.1.Wiring Guidelines
DEVICE TYPEEMERSON
ANALOG TEMP SENSOR
DIGITAL INPUT
RS-485 NETWORKBELDEN #8761 #22-2 SHIELDED
PRESSURE TRANSDUCER**BELDEN #8771 #22-3 SHIELDED
POWER, LOADS, AND VALVE
Table 17-1 - Wiring Guidelines
BELDEN #8761 #22-2 SHIELDED
Emerson P/N 035-0002
Emerson P/N 035-0002
BELDEN #8641 #24-2 SHIELDED
Emerson P/N 135-8641
Emerson P/N 135-8771
**#8771 for alternate 600v rated wire use BELDEN
#8618 16 AWG
Allows a maximum wire size of 14 AWG (2 mm
17.2.XM670 - Wiring Diagram
2
).
Figure 17-1 - XM670 - ALL Power Supply
E2 to XM Device Communication RecommendationsConnections • 29
Page 36
17.3.XM679 - 230VAC Valves/Wiring Diagram
Figure 17-2 - XM679 - 230VAC Valves
Models at 115V
Supply: Terminals 7-8
Valve at 115V: Terminals 4-5
17.4.XM679 - 24VAC Valves/Wiring Diagram
Figure 17-3 - XM679 - 24VAC Valves
NOTE: The jumper labeled as JMP is located inside the case of the controller. The JMP jumper should be
closed only when driving the 24VAC valve.
30 • XM679K I&O Manual026-1218 Rev 4
Page 37
18E2 MODBUS Network Wiring
LON
EARTH GROUND
AC1
Shield
24VAC
Keyboard
RS-232
AC2
ON
OFF
LON
RS485-1B
+ 0v -
E2 STANDARD (3.XX and Below Version)
POWER INTERFACE BOARD (PIB)
237-4810,Version1.00
E2PowerInterfaceBoard(P.I.B.)
R
Echelon Terminate Up
+ 0V RS485-2B
TX1 RX2RX1
JP4
JP5
JP6
JP1
JP2
JP3
REVERSE POLARITY OF +/-
ON RS485 CABLE FROM E2
BELDEN 8641
(TYPICAL)
earth ground
connection
100 ohm
Watt
1/2
18 17 16 15 14 13
12 10 9 7811321
19 20 22 23 24 25 26
39
38
37
36
35343332313029282721
+
RS485
-
+
modbus
Black
White
XM67X Series
Shield
MODBUS TERMINATION
BLOCK 537-2711
150 ohm
18 17 16 15 14 13
12 10 9 7811321
19 20 22 23 24 25 263938
3736
35343332313029282721
+
18
17 16 15 14 13
12 10 9 7811321
19 20 22 23 24 25 263938
3736
35343332313029282721
+
RS485
-
+
modbus
Black
White
RS485
-
+
modbus
Black
White
BELDEN 8641
(TYPICAL)
Shield
Shield
XM67X SeriesXM67XK Series
Position the three
jumpers to provide
RS485 termination
at the E2
TERMINATE NETWORK
+ 0v -
637-4890
White +
Black -
RS485-2A
+ 0V -
9600 Baud Only
*Note that for E2 Enhanced PIB
boards, the RS-485 connection
can be wired on COM 2, COM 4,
or COM 6 port.
MODBUS 485
MODBUS 485
• Connect the MODBUS Network to the RS485 Connector on the E2 PIB board (Belden 8641 recommended).
• Note to wire the RS485 +/- polarity at the E2 in the reverse
• Position the three termination jumpers to the UP (terminated) position to provide RS485 termination at the E2.
• Do not connect the shield of the MODBUS network to the E2 PIB center terminal. Instead, use a 100 ohm 1/2 watt
resistor to connect the MODBUS cable shield to earth ground.
• At each XM670 - XM679 device, wire the MODBUS cable to the RS485 +/- terminals and connect the MODBUS
shield to the pin 38 terminal.
• Terminate the end of the MODBUS network at the last XM670 - XM679 device on the daisy chain with the
MODBUS termination block (P/N 535-2711), or by connecting a 150 ohm resistor between the MODBUS +/-
CAUTION! For the XR, XM, and XEV series of controllers, the shield wire must not come into contact with
any other wire or ground source. If contact with other wires or devices does occur, the 485 MODBUS
network will malfunction or connected devices will be damaged. This applies to all installations where the
shield is tied to ground through a 100 ohm ½ Watt resistor.
Refer to Appendix A - Alternate MODBUS COM
Wiring Method for E2, XR, XM, and XEV Devices.
Figure 19-1 - Wiring Guidelines for Sharing a Pressure Transducer Across Multiple Units on the Same Circuit - XM679 Only
32 • XM679K I&O Manual026-1218 Rev 4
Page 39
20Pressure
Pb6
Superheat
Probe
Pb6
Superheat
Probe
Pb6
Transducer
4 to 20mA
Pb6
Superheat
Probe
38 39
19 20 21 22
38 39
38 39
Brown
In
+12v
gnd
In
+5v
Transducer Setup
(XM679 Only)
4 to 20 mA for PP07,
PP11, or similar models
Generic metric ratio
0 to 5V
Virtual Pressure: In this example of programming,
the master device is the regulator with the pressure
probe connected.
A working LAN connection is required (green LED
on all XM679K boards of the same LAN). Connect
lit
and configure a pressure transducer only on one
XM679K of the network. Afterwards, the value of the
pressure read by the unique transducer connected will
be available to each device connected to the same
LAN.
SlaveMasterSlave
tPP = LAn
LPP = n
P5C = n
P
tPP = PP
LPP = Y
P5C = 4
(transd.)
20
Tpp = LAn
LPP = n
P5C = n
P
Slave device
pressure:
rPP: Shows the
value of pressure
received by
remote pressure
probe connected
to other XM600
device.
Master device
re:
pressu
dPP = Sho
ws
the value of
pressure
measured by
pressure
transducer.dP5 =
Sho ws t he
temperature
value measured
Slave device
pressu
re:
rPP:
Shows the
value of
pressure
received by
remote pressure
probe
connected to
other XM600
device.
by probe 5.
Check for error messages. Error message examples:
• dPP = Err: in the Master device, the value of
pressure read from the transducer is outside the
acceptable range regarding parameters PA4- PA20;
is connected incorrectly or it is not configured to
parameter P5C.
• PPF = reading on the slave device - LAN
communication is not functional.
• tPP = LAn: in the master controller, LAN address
sequences are not correct. LPP = Y means the
address sequences are not correct.
Final Control From Superheat (SH) Reading Control
Values:
• dPP = Shows the value of pressure measured by
pressure transducer.
• dP6 = Shows the temperature measured by probe 6.
Corresponds to the outlet temperature of gas of the
evaporator.
• SH = S hows the actual super he at value. It must have
a consistent value for difference between the values
dP6 and dP5. If displaying nA, err or nd, the value
is not calculable at the moment of the reading.
Press the arrow keys to access menu readings for
pressure.
If the LAN is well connected, the green LED will be
ON. If the green LED blinks, then the connection is
wrongly configured. The maximum distance allowed
is 30m.
1. Terminals -34 and +35
2. Use twisted shielded cable AWG 18 or less in case
of long distance.
3. Keep at a maximum distance of 30m.
The XM679 board can also operate without a
keyboard.
20.2.Synchronized Defrost
The synchronized defrost (also called master-slave
functioning) allows the user to manage multiple
defrost from different boards connec
LAN connection. In this way, the boards can perform
simultaneous defrosts with the possibility to end them
in a synchronized way.
Follow the next steps to create a LAN connection,
h is a necessary condition to perform
whic
synchronized defrost.
1. Connect a shielded cable between terminals -38 and
+39 for a maximum of 8 sections.
2. The Adr parameter identifies each electronic board.
Address duplication is not permitted. In this case,
the synchronized defrost and the communication
with the monitoring system is not guaranteed. (The
Adr is also the MODBUS address). For example, a
correct configuration would be:
ted through the
20.3.Sensors for Superheat
Control
Temperature probe: Pb6
terminals [19]-[20]
without any polarity.
Select the kind of sensor
with P6C parameter.
Pressure transducer: Pb5
minals:
ter
[21] = input of the signal
[22] = Power Supply for 4
t
o 20 mA transducer
[20] = GND
[23] = +5Vdc power
su
pply for ratiometric
pressure transducer
Select the configuration of the transducer with
parameter P5C.
20.4.Analog Output
• Selectable between 4
to 2mA and 0 to
10Vdc.
• Use CABCJ15 to
perform the
connections.
The analog output is located near the terminal [39] on
a 2-pin connector. The output can be used to control
anti-sweat heaters through a chopped phase controller
XRPW500 (500 watt) or family XVD or XVK.
Figure 20-1 - Synchronized Defrost
34 • XM679K I&O Manual026-1218 Rev 4
Page 41
20.5.RS485 Net Monitoring
Shielded Serial Cable
LANLAN
Shielded Serial Cable
Temperatures
1. Terminals -36 and +37
2. Use Belden cable #8761
or #8641.
3. Keep at a maximum
distance of
approximately 1Km.
4. Don’t connect the shield
to the earth or to GND
terminals of the device.
Avoid accidental contact
by using insulating tape.
20.5.1.RS485 Connection
Sharing a single pressure transducer across multiple
controllers on a LAN:
Figure 20-2 - Sharing a Pressure Transducer Between Devices
on LAN
CAUTION! Do not connect the RS485 cable to
all the instruments that are already connected
on the LAN - only connect the RS485 to the
master device of the LAN.
Set the value of Adr parameter, then press
SET to confirm the parameter.
Press the two keys together to exit from
the menu or wait for about 10 seconds.
20.6.How to Enable a
Pressure Probe to
Share Across the LAN
1. Enter the Pr 1 l ev el . F ollo w t he st ep s i n Section 3.7.,
How to Enter the Parameters List PR1.
2. Select Pr2 parameter and press the SET key.
3. The PAS flashing message will display, followed
shortly by “0 --” with a flashing zero.
4. Use the UP or DOWN button to input the security
code in the flashing digit. Confirm the security code
by pressing SET. The security code is 321.
5. If the security code is correct, the access to Pr2 is
enabled by pressing SET on the last digit.
6. Navigate to the LPP of the Master device (the
device where the pressure probe is connected) and
select (Y). Set the LPP to (N) for all other slave
devices.
7. Navigate to tPP of the Master device and set it to
PP (Pressure Probe). The slave devices tPP
parameter will be set to LAn.
8. Navigate to P5C parameter (Pressure Probe will
always be assigned to P5C) of the Master device
and set it to Pressure Probe type. The slave devices
P5C parameter will be set to nP (No Probe).
The parameter (Adr) al
configurations on the RS485 network (besides the
LAn); its value must be only from 1 to the total
number of devices present on the RS485 and the LAN
networks.
CAUTION! The same value of the Adr
parameter in different controllers creates
malfunctioning in the monitoring system or
problems on the synchronized defrosts.
Press for three (3) seconds, the rtC or
other will be shown. The measurement
unit blinks.
Press more than once the DOWN arrow to
find the Adr parameter, then press SET.
RS485 Net Monitoring TemperaturesPressure Transducer Setup (XM679 Only) • 35
so defines the number of
NOTE: If pressure is not being shared across
the LAN, each XM679 will need its own
Pressure Transducer. Please reference Figure
18-1 and Figure 19-1 wiring diagrams.
Page 42
21Wiring Connection to Site Supervisor
Figure 21-1 - Site Supervisor Wiring
36 • XM679K I&O Manual026-1218 Rev 4
Page 43
22ECT MODBUS
E2 PIB COM PORT ASSOCIATIONS
COM1
COM4
COM6
COM2
Serial Device
RS485 COM Port
(2 Connectors)
RS485 COM Card
(2 Connectors)
Serial Device
RS232 Port
POWER INTERFACE BOARD
(PIB)
E2 Modem/Expansion
COM Card Mounted
Above PIB
Plug-In
Modem
Card
COM3
E2 Enclosure (Right Side)
RS485
RS232
E2
XM670/
XM679
#1
TERMINATED,
BIASED
(ALL 3 JUMPERS
IN UP POSITION)
XM670/
XM679
#2
XM670/
XM679
#3
E2 PIB COM PORT ASSOCIATIONS
COM1
Serial Device
RS232 Port
POWER INTERFACE BOARD
(PIB)
E2 Enclosure (Right Side)
COM2COM6
COM4
Serial Device
RS485 COM Ports
Plug-In
Modem
Card
COM3
Networking to
E2s
Connecting a XM670 - XM679 controller to an E2
requires the E2 to be version 2.84 or above. Contact
Emerson for upgrade information if the controller is a
version before 2.84.
22.1.COM Port Associations
- E2 Versions 3.xx and
Below
your E2 is equipped with an RS485 COM Card (P/N
637-4890) and configured in E2 General Services
(
, Serial tab)to enable COM4 or an
E2 Expansion COM Card (P/N 637-4871) to enable
COM6.
Connect the MODBUS network cable to the threeterminal connector on the COM port you wish to
assign as MODBUS. Reverse polarity of +/- on
RS485 cable from E2 to the device.
Figure 22-2 - MODBUS Networking
22.2.COM Port Associations
Figure 22-1 - Location of E2 Com Ports - E2 PIB Board (E2
versions 3.xx and Below)
An E2 has up to three COM ports that can be assigned
for MODBUS communication: COM2, an RS485
port on the E2 power interface board, and COM4 and
COM6, which are optional ports requiring expansion
cards.
connection of XM670 - XM679 units.
COM ports can only be used for one function; in other
words, if COM2 is set up as the I/O network, you
cannot connect MODBUS devices to COM2. Ensure
COM Port Associations - E2 Versions 3.xx and BelowECT MODBUS Networking to E2s • 37
COM4 is recommended for MODBUS
- E2 Versions 4.0 and
Above
Figure 22-3 - Location of E2 Com Ports - E2 PIB Board (E2
versions 4.0 and Above)
Page 44
An E2 has three COM ports that can be assigned for
E2
XM670/
XM679
#1
TERMINATED,
BIASED
(ALL 3 JUMPERS
IN UP POSITION)
XM670/
XM679
#2
XM670/
XM679
#3
MODBUS communication (COM2). COM ports can
only be used for one function; in other words, if
COM2 is set up as the I/O network, you cannot
connect MODBUS devices to COM2. Ensure your E2
is configured in E2 General Services (
,
Serial tab) to enable COM4 or COM6.
Connect the MODBUS network cable to the threeterminal connector on the COM port you wish to
assign as MODBUS. Reverse polarity of +/- on
RS485 cable from E2 to the device.
Figure 22-4 - MODBUS Networking
22.3.E2 Setup of Devices
22.3.1.Set Up Network Ports
Before setting up a device, the port on the E2 that has
the MODBUS cable connected must be set up as a
MODBUS port.
1. Log in to the E2 with Level 4 access.
2. Press
followed by - General
Controller Info.
Figure 22-5 - Serial Communications Manager Screen
4. This screen will have a “Connection” field for all
COM ports on the E2. Highlight the COM port
connection field that will be used for the device, and
press - LOOK UP. From the list of network
types, select MODBUS.
5. Four fields will become visible underneath the
COM port connection field, which pertain to the
way the device communicates:
• Baud - Default setting is 19.2k. The baud rate
setting should be set to match the baud rate of the
XM670 - XM679 device (9600). (All devices
connected to the same COM port should be set to the
same baud rate.)
• Data Size - Leave this field at the default value (8).
• Parity - Leave this field at the default value (None).
• Stop Bits - Leave this field at the default value (1).
3. Press
+ to open the Serial tab of the General
Controller Info setup screens:
6. Press
22.3.2.Add and Connect the Device
to save changes and exit.
To enable communications between E2 and the
XM670 - XM679 units, the devices must be added
and addressed in E2.
1. Log in to the E2 with Level 4 access.
2. Press
38 • XM679K I&O Manual026-1218 Rev 4
- Connected I/O Boards
and Controllers.
Page 45
Figure 22-6 - Num Network Ctrls: NetSetup Screen
3. In the Num Network Ctrls: NetSetup screen, under
the ECT tab, enter the number of devices in the
Quantity field. (Max shows the maximum number
of devices allowed on the network.)
address set up through the front display, and press
to select it. A window will open where you
can specify the address of the controller. If a
network ID has already been selected, its name will
be shown next to the network ID in this list. If the
network ID you are trying to assign has already
been used, you must set the address on this device
to a different number that is not being used.
4. Press
5. Locate the units you added to the network list (press
to return to the Network Setup menu,
then select
- Network Summary.
and to scroll through the list). If desired,
enter a new name for each device in the Name field.
Figure 22-7 - Network Summary Screen
6. By default, each device in the network list has a
board number of 0. To set the address and begin
communication, choose the device and press .
In the list of MODBUS devices, choose the address
number corresponding to the XM670 - XM679
Figure 22-8 - List of MODBUS Devices
7. Repeat Steps 5 and 6 until each device has a name
and address.
8. When finished, press
Setup menu, then press
(Figure 22-7). Locate the devices you set up, and
look at each device’s status in the Status field. You
will see one of the following messages:
• Online - The device is communicating normally.
• Offline - The device is not communicating, has not
been commissioned, is not functional, or is not
powered up. Verify the device is powered up, wired
correctly, and has the proper network address, baud
rate, and parity.
• Unknown - The device is not communicating or has
not been commissioned. Verify the device is
powered up, wired correctly, and has the proper
network address, baud rate, and parity.
• No Port - No port is set up in the E2 Serial
Configuration Manager to be a MODBUS port.
• Wrong FW Rev - This message is likely caused by
the device having a firmware version older than the
minimum revision required by E2 for
communication. Replace the device with a new one
or a device that has the latest version of firmware on
to return to the Network
- Network Summary
E2 Setup of DevicesECT MODBUS Networking to E2s • 39
Page 46
it.
FROM LAST
DEVICE
AT END OF
DAISY-CHAIN
SHIELD WIRE
(CONNECT TO
OF DEVICE)
PIN 38
TO TERMINAL DEVICE
Figure 22-9 - Network Summary Screen
22.4.Wiring Types
Emerson specifies Belden #8761 shielded twisted pair
cables for use as MODBUS wiring (or Belden #82761
and Belden #88761 for plenum installations).
For MODBUS network wiring of XM670 - XM679
ntrollers to E2, Belden #8641 (Emerson
co
P/N 135-8641) is the recommended wire type to use.
If the recommended cable is not available in your
area
, be sure the wiring meets or exceeds the
following specs:
22.5.MODBUS Termination
Blocks
Because the XM670/XM679 device has no on-board
means of termination, use the MODBUS termination
block (P/N 535-2711) for termination that can be
wired to the end of the cable segment using the threepin connector. Wire the two signal wires to the
outside terminals, and connect the shield to pin 38 of
the device, keeping the exposed shield wire length as
short as possible (3 inches ideal maximum length).
To simplify MODBUS communication wiring with E2, (both Standard and Enhanced versions) XR, XM, and
XEV series devices, the alternate method outlined below may be used.
Wire Type
Use Belden 8761 or equivalent cable.
Shield
DO NOT connect the shield to the device. Keep the shield continuous throughout a network segment. The shield
must be twisted together and insulated with electrical tape or heatshrink at each device within a network
segment. Securely connect the shield to an earth grounded chassis at each end of a network segment.
Termination
Each network segment must be biased and terminated at the E2 controller’s end (all three jumpers in the MOD
position for E2 Enhanced, or all three jumpers in the UP position for E2 Standard) and terminated with a 150
ohm resistor at the other end of the network segment (150 ohms between the two communication wires).
Recommended
For reliable communication on some installations, it may be necessary to connect a 100 ohm resistor between
the XR, XM, or XEV device’s previously identified ground terminal and earth ground.
Some E2 MODBUS COM Ports Can Support Two Network Segments
For E2 Enhanced 4.x Controller Hardware
CO M2 supports two network segments: one on connector RS485-COM2A, and the second on connector RS485COM2B.
CO M4 supports two network segments: one on connector RS485-COM4A, and the second on connector RS485COM4B.
COM6 only supports one network segment on connector RS485-COM6.
For E2 Standard 3.x Controller Hardware
COM2 supports two network segments: one on connector RS485-1A, and the second on connector
RS485-1B.
For information on the maximum recommended number of XR, XM, and XEV devices for each network segment
(load and bandwidth calculations), contact Emerson Technical Support at 770-425-2724.
48 • XM679K I&O Manual026-1218 Rev 4
Page 55
Figure 1 - MODBUS COM Wiring Diagram
MODBUS Termination BlocksAppendix A - Alternate MODBUS COM Wiring Method for E2, XR, XM, and XEV Devices • 49
Page 56
Page 57
For Technical Support call 770-425-2724 or email ColdChain.TechnicalServices@Emerson.com
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or
services described herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or
specifications of such products at any time without notice. Emerson does not assume responsibility for the selecti on, use or maintenance of any product. Responsibility for proper selection, use
and maintenance of any product remains solely with the purchaser and end-user.